Minimum Equipment Water Efficiency

Newly installed appliances, equipment, and processes within the project boundary must meet the requirements listed in Tables 3 and 4. Existing appliances and equipment can be excluded.

Table 3. Standards for appliances

ApplianceCol2RequirementCol4
Residential clothes washersResidential clothes washersENERGY STAR® or performance equivalentENERGY STAR® or performance equivalent
Commercial clothes washersCommercial clothes washersENERGY STAR® for commercial clothes washers with ≤ 8.0
cubic feet (227 liters) capacity or performance equivalent
ENERGY STAR® for commercial clothes washers with ≤ 8.0
cubic feet (227 liters) capacity or performance equivalent
Residential dishwashers (standard
and compact)
Residential dishwashers (standard
and compact)
ENERGY STAR® or performance equivalentENERGY STAR® or performance equivalent
Prerinse spray valvesPrerinse spray valves≤ 1.3 gpm (4.9 lpm)≤ 1.3 gpm (4.9 lpm)
Ice machineIce machineENERGY STAR® or performance equivalent and use either
air-cooled or closed-loop cooling, such as chilled or condenser
water system
ENERGY STAR® or performance equivalent and use either
air-cooled or closed-loop cooling, such as chilled or condenser
water system
Commercial kitchen equipmentCommercial kitchen equipmentRequirement (IP)Requirement (SI)
DishwasherUndercounter≤ 1.6 gal/rack≤ 6.0 liters/rack
DishwasherStationary, single
tank, door
≤ 1.4 gal/rack≤ 5.3 liters/rack
DishwasherSingle tank,
conveyor
≤ 1.0 gal/rack≤ 3.8 liters/rack
DishwasherMultiple tank,
conveyor
≤ 0.9 gal/rack≤ 3.4 liters/rack
DishwasherFlight machine≤ 180 gal/hour≤ 680 liters/hour
Food steamerBoilerless/
connectionless
≤ 2 gal/hr/pan≤ 7.5 liters/hr/pan
Food steamerSteam generator≤ 5 gal/hr/pan≤ 19 liters/hr/pan
Combination
oven
Countertop or
stand
≤ 1.5 gal/pan≤ 5.7 liters/pan
Combination
oven
Roll-in≤ 1.5 gal/pan≤ 5.7 liters/pan

Table 4. Standards for processes

ProcessRequirement
Heat rejection and coolingNo once-through cooling with potable water for any equipment or
appliances that reject heat.
Cooling towers and
evaporative condensers
Equip with all the following:

Makeup water meters

Conductivity controllers and overflow alarms

Efficient drift eliminators that reduce drift to max of 0.001% of
recirculated water volume for counterflow towers and 0.002%
of recirculated water flow for cross-flow towers
Discharge water
temperature tempering
Where local requirements limit the discharge temperature of fluids into
drainage system, use a tempering device that runs water only when
the equipment discharges hot water.