855773644-LEED-v5-BD-C-Reference-Guide-Launch-Edition - Page 180

Extracted Content

Water Efficiency Credit

WATER METERING AND LEAK DETECTION

WEc1

1 POINT

New Construction (1 point) Core and Shell(1 point)

INTENT

To conserve potable water resources, support water management, limit potential material waste due to water leak damages, and identify opportunities for additional water savings by tracking water consumption.

REQUIREMENTS
Achievement pathwaysPoints
New Construction and Core and Shell1
Option 1. Submeters1
OR
Option 2. Leak Detection Sensors1

Option 1. Submeters (1 point)

Install permanent water meters for each applicable subsystem defined below:

  • Indoor plumbing fixtures and fittings. Meter systems serving at least 80% of indoor fixtures and fittings as described in WEp2: Minimum Water Efficiency. Fixtures and fittings not addressed in the prerequisite, including janitor sinks, water coolers, and bottle fillers, may be included or excluded from the indoor plumbing fixtures’ subsystem at the project team’s discretion.

  • Irrigation system.

  • Each makeup water system (e.g., cold water inlet for domestic hot water, swimming pools, chilled water systems, process water systems).

  • Commercial kitchen (if the kitchen serves at least 100 meals per day of operation).

  • Laundry (if the project includes commercial laundry equipment that processes at least 120,000 lbs. [57,606 kg] of laundry per year or if the project includes a public laundry room).

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 170