  • Purchased chilled water (CHW) . Multiply the utility rate or source energy conversion factor for electricity by a factor of 0.325 to estimate the chilled water utility rate or source energy conversion factor.

    • Purchased heat from district hot water (HHW) . Multiply the utility rate or source energy conversion factor by a factor of 1.5 for the predominant fossil fuel source used to generate the district hot water or natural gas if unknown.

    • Purchased heat from district steam . Multiply the utility rate or source energy conversion factor by a factor of 1.7 for the predominant fossil fuel source used to generate the district hot water or natural gas if unknown.

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 224