| Refrigerant | Classification | GWP | Common system applications |
|---|---|---|---|
| R290 (Propane) | Natural | 3 | Commercial Refrigeration Heat Pumps Chillers |
| R1234ze | HFO | <1 | Heat Pumps Chillers |
| R744 (CO2) | Natural | 1 | Heat Pumps |
| R717 (NH4, ammonia) | Natural | 0 | Heat Pumps |
EQUIPMENT INVENTORY
Project teams must identify all refrigerant-containing equipment included in the scope of work, including any existing equipment within the project boundary owned or controlled by the project owner and/or facilities manager. Equipment that contains less than 0.5 pounds (225 grams) of refrigerant, such as standard residential refrigerators in dwelling units, can be excluded from the calculations.
Manage the inventory during the Construction Phase. If equipment substitutions occurred during the submittal and procurement phases, update the inventory to reflect the actual installed equipment.
Table 2 is a sample and non-comprehensive list of the types of refrigerant-using equipment that a project’s scope of work may include.
Additional considerations: Equipment inventory Completing the inventory in the Construction Documents Phase provides owners and design professionals with a complete understanding of the future climate impacts.
Table 2. Refrigerant-containing equipment
| Application | Equipment/System Type |
|---|---|
| HVAC, Space Cooling Equipment | Stationary air conditioners and heat pump Chillers Computer room air conditioning (CRAC) units |
| Service Water Heaters | Heat pump service water heaters |
| Retail | Food Refrigeration Cold Storage |
| Commercial | Vending Machines Ice Machines |
| Industrial Process Refrigeration | Process chillers Ice rink chillers Other process refrigeration |
U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 263