855773644-LEED-v5-BD-C-Reference-Guide-Launch-Edition - Page 279

Extracted Content

Equipment efficiency : Determine weighted average COP using either of the following:

  • Equipment efficiencies at rated conditions : For equipment with multiple rated conditions, use the rating closest to 17°F (–9°C) OA db, 32°F (0°C) entering liquid temperature, or 44°F (6°C) heating source leaving liquid temperature.

  • Annual average COP calculated with an energy simulation.

District energy : Projects with district energy must comply with the requirements of this credit at the district facility or see additional guidance for interpretation of credit requirements.

Fuel cells : Fuel cells using fossil fuel are ineligible for credit.

Low temperatures : “Low temperatures” refer to outside air dry-bulb temperatures (OA db) below 20°F (–6.5°C).

REQUIREMENTS: CORE AND SHELL
Achievement pathwaysPoints
Core and Shell1–4
Option 1. Electrification2–4
Path 1. No On-Site Combustion3–4
OR
Path 2. No On-Site Combustion Except at Low Temperatures1–3
Case 1. Space Heating1–2
OR
Case 2. Service Water Heating1
OR
Path 3. No On-Site Combustion—Limited Scope1–2
Option 2. Electrification Readiness1

Option 1. Electrification (2–4 points)

For Paths 1 and 2:

- Include all heating and service hot water systems necessary to meet total building

heating and service water heating load in the calculations of weighted average COP.

- Future heating or service water heating systems must be included in the calculations

with a COP of 1.0.

- Future equipment may be excluded from the calculations and deemed as compliant

when the applicable building code, or construction drawings for projects with tenancy, confirms a weighted average COP of at least 1.8 for future installed equipment.

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 269