  • Ground source heat pumps . 32°F (0°C) entering liquid temperature

    • Liquid source heat pump and heat recovery water-chilling packages . 44 ° F (6 ° C) heating source leaving liquid temperature.

Reference ASHRAE 90.1, Section 6.8 Tables to identify applicable rated conditions. For equipment with efficiency ratings using HSPF, AFUE, or any rating other than COP or COPH, convert these ratings to COP using Table 2 before calculating the weighted average COP.

Additional considerations For heat pump water-chilling packages or heat recovery water-chilling packages rated per ASHRAE 90.1, Table 6.8.1-16, adjust COP using the equations from Table 2 to align equipment ratings for entering/leaving heating liquid temperature at medium, high, or boost conditions with the default low ratings.

Table 2. Determination of equipment COP for calculation of weighted average COP

Heating equipment typeHeating equipment
efficiency rating
Equation to convert
to COP
Test
procedure
Electrically operated air-
cooled unitary heat pumps
HSPF2= -0.0296 x HSPF22
+ 0.7134 x HSPF2
AHRI 210/240-
2023
Electrically operated air-
cooled unitary heat pumps
SCOP2H= -0.3446 ×
SCOPH22
+ 2.434 × SCOPH2
AHRI 210/240-
2023
Electrically operated air-
cooled unitary heat pumps
COPH
at 17°F db/15°F wb
(–8.3°C db/–9.4°C wb)
= COPHAHRI 340/360
PTHPCOPH= COPHAHRI 310/380
SPVHPCOPH= COPHAHRI 390
VRF air cooledHSPF= -0.0296 x HSPF2 +
0.7134 x HSPF
AHRI 1230
VRF air cooledCOPH
at 17°F db/15°F wb
(–8.3°C db/–9.4°C wb)
= COPHAHRI 1230
VRF air cooledSCOPH= -0.3446 × SCOPH2
+ 2.434 × SCOPH
AHRI 210/240-
2023
VRF water sourceCOPH
68°F (20°C) entering
water
= COPHAHRI 1230
VRF groundwater sourceCOPH
50°F (10°C) entering
water
= COPHAHRI 1230
VRF ground sourceCOPH
32°F (0°C) entering
water
= COPHAHRI 1230