855773644-LEED-v5-BD-C-Reference-Guide-Launch-Edition - Page 321

Extracted Content

Points are awarded according to Table 3, using either Path 1 or Path 2.

Table 3. Points for percentage improvement in PI Below PIT

Path 1.
Percentage reduction excluding on-
site renewable contribution
(100% – PInre / PIt)
Col2ORPath 2.
Percentage reduction including
on-site renewable contribution
(100% – PI / PIt)
Col5Points
Case 1.
ASHRAE 90.1-
**2019 **
Case 2.
ASHRAE 90.1-
**2022 **
Case 2.
ASHRAE 90.1-
**2022 **
Case 1.
ASHRAE 90.1-
**2019 **
Case 2.
ASHRAE 90.1-
**2022 **
Case 2.
ASHRAE 90.1-
**2022 **
2%N/A10%N/A1
5%N/A20%0%2
8%0%30%13%3
11%3%40%26%4
14%6%50%39%5
17%9%60%52%6
20%12%70%65%7

Table 4. ASHRAE 90.1-2019 — Equivalent building performance factors for a future source energy metric

Building typeClimate zoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.740.690.730.700.730.700.710.700.630.700.710.690.680.700.700.680.680.680.74
Healthcare/hospital0.720.720.730.730.740.710.720.740.710.720.730.710.740.730.800.730.770.780.79
Hotel/motel0.720.710.720.710.710.700.710.730.720.710.730.730.710.730.740.700.720.700.70
Office0.620.630.610.620.580.600.570.620.550.550.610.570.580.610.590.580.600.540.58
Restaurant0.650.620.630.610.620.580.630.630.630.670.660.660.700.700.680.730.720.740.77
Retail0.570.540.530.530.480.470.470.470.470.520.500.560.570.530.590.580.560.530.60
School0.570.570.580.570.550.540.570.510.490.480.510.520.510.530.510.530.500.510.58
Warehouse0.280.300.240.270.230.240.270.230.200.330.260.280.400.320.290.440.380.400.44
All others0.650.620.640.620.570.540.570.560.580.590.570.600.600.590.650.620.620.610.64

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 311