Option 2. Monitoring-based Commissioning

Meet the same requirements as BD+C: New Construction Option 2, plus:

For Core and Shell projects, the base building EIS must have expansion capability, to ensure all data identified in EAp4: Energy Metering and Reporting is accessible through the EIS. This includes metering requirements for future tenants.

Tenant requirements If the project anticipates future tenants will lease space that is greater than 10,000 sq. ft. (929 sq. m.), install submeters for compliance with EAp2: Minimum Energy Efficiency . The base building EIS must include a tenant portal, where tenants can access reports, including visual representations of the energy consumption. At minimum, tenants must have access to the base building data for shared systems that serve the tenant space, and the electricity energy use associated with their space.

DOCUMENTATION
Project
types
OptionsPathsDocumentation
New
Construction
and
Core and
Shell
AllAllFinal (or Draft) Commissioning Report. If the report is a
draft, include a plan for the completion of commissioning
and training, including climatic and other conditions
required for performance of any deferred tests.
New
Construction
and
Core and
Shell
Option 1Path 1
and/or
Path 2
Confirmation of compliance with_ANSI/ASHRAE/IES_
Standard 202-2024 and/or_ASTM E2947-21a Standard_
Guide for Building Enclosure Commissioning, except
Section 7.2.4 and 7.4.3 (As applicable)
New
Construction
and
Core and
Shell
Option 1Path 1
and/or
Path 2
Confirmation of design phase/milestone meetings
New
Construction
and
Core and
Shell
Option 1Path 1
and/or
Path 2
Provide Commissioning Plan and sample FPT Test
scripts (1 sample per discipline)
New
Construction
and
Core and
Shell
Option 1Path 1
and/or
Path 2
Owner’s Project Requirements and BOD
New
Construction
and
Core and
Shell
Option 1Path 1
and/or
Path 2
Identification of Commissioning Provider including key
personnel (CxP) and Verification and Testing (V&T)
providers (as applicable)
New
Construction
and
Core and
Shell
Option 1Path 1
and/or
Path 2
Qualifications of CxP and V&T providers
New
Construction
and
Core and
Shell
Option 1Path 1
and/or
Path 2
Confirmation that submittals were reviewed and at least
25% of the contractors’ documents were QA/QC’d
New
Construction
and
Core and
Shell
Option 1Path 1.
Enhanced
Cx for MEP
Systems
Provide evidence, such as contract or other
documentation, confirming the involvement of CxP
during predesign or very early in the design phase
New
Construction
and
Core and
Shell
Option 1Path 2.
Enhanced
Cx for
building
Enclosure
Field report or completed test that proves building air
leakage testing, water penetration testing, infrared
imaging was completed

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 367