Energy and Atmosphere Credit

ENHANCED REFRIGERANT MANAGEMENT

EAc7 New Construction (1–2 points) Core and Shell (1–2 points)

INTENT

To reduce greenhouse gas emissions by accelerating the use of refrigerants with low global warming potential (GWP) and promoting better refrigerant management practices.

REQUIREMENTS
Achievement pathwaysPoints
New Construction and Core and Shell1–2
Option 1. No Refrigerants or Low GWP1–2
Path 1. No Refrigerants1
OR
Path 2. Low GWP Refrigerants1–2
AND/OR
Option 2. Limit Refrigerant Leakage1
AND/OR
Option 3. GreenChill Certification for Food Retailers1–2

Option 1. No Refrigerants or Low GWP (1–2 points)

PATH 1. NO REFRIGERANTS (1 POINT)

Do not use refrigerant-containing equipment in the project.

Core and Shell only Projects with future equipment necessary to meet the project’s heating or cooling load are not eligible for this option.

OR

PATH 2. LOW GWP REFRIGERANTS (1–2 POINTS)

The maximum total weighted average refrigerant GWP in all new refrigerant-containing equipment is less than or equal to 80% (1 point) or 50% (2 points) of the total weighted average GWP of refrigerants meeting the benchmarks in Table 1.

Projects that limit effective refrigerant GWP by reducing refrigerant charge per unit of capacity relative to comparable equipment may use adjusted benchmarks.

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 379