855773644-LEED-v5-BD-C-Reference-Guide-Launch-Edition - Page 487
Extracted Content
Indoor Environmental Quality Credit
ENHANCED AIR QUALITY
EQc1 New Construction (1 point)
INTENT
Impact Area Alignment
- Decarbonization
Quality of Life
Ecological Conservation
and Restoration
To design for increased indoor air quality (IAQ) to better protect the health of building occupants.
REQUIREMENTS
| Achievement pathways | Points |
|---|---|
| New Construction and Core and Shell | 1 |
| Option 1. Increased Ventilation | 1 |
| OR | |
| Option 2. Enhanced Indoor Air Quality Design | 1 |
Design the building to exceed the requirements of ASHRAE 62.1-2022, Section 6. If using the ventilation rate procedure to comply with EQp2: Fundamental Air Quality, use Option 1 or Option 2; if using the IAQ procedure, use Option 2.
Option 1. Increased Ventilation (1 point)
Increase breathing zone outdoor air ventilation rates by at least 15% above the minimum rates (for 1 point, or 30% for exemplary performance) as determined in EQp2: Fundamental Air Quality .
Increased outdoor air rates should be provided to 95% of all regularly occupied spaces.
OR
Option 2. Enhanced Indoor Air Quality Design (1 point)
In addition to the design compounds and design limits outlined in ASHRAE 62.1-2022, Tables 65 and 6-6, design and verify enhanced IAQ using the lower design limits listed below in Table 1.
Table 1. Additional design limits for enhanced indoor air quality design
| Design compound or PM2.5 | Enhanced IAQP design limit |
|---|---|
| PM2.5 | 10 ug/m3 |
| Formaldehyde | 20 µg/m³ |
| Ozone | 10 ppb |
U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 477