PATH 2. QUALITY ELECTRIC LIGHTING (1 POINT)

Comply with the following requirements for regularly occupied spaces:

Electric light glare control Each luminaire shall meet one of the following requirements:

Color rendering Use luminaires that have a color rendering index of at least 90, or that meet the color rendering requirements in Table 1, in accordance with Illuminating Engineering Society (IES) TM-30-20.

Table 1. Color rendering requirements using TM-30-20

MeasureCol2Requirement
Fidelity indexRf78 or higher
Gamut indexRg95 or higher
Red Local Chroma ShiftRcs,h1-1% to 15%

AND/OR

PATH 3. PROXIMITY TO WINDOWS FOR DAYLIGHT ACCESS (1 POINT)

Design the interior layout to provide at least 30% of the regularly occupied area to be within a 20-foot (6 meters) horizontal distance of envelope glazing. The glazing must have a visible light transmittance above 40%. Regularly occupied areas with visual obstructions (incapable of providing a view to envelope glazing) should be excluded from the compliant area.

OR

160 “NEMA White Paper on Unified Glare Rating”, NEMA, (2021), accessed March 21, 2025, https://www.nema.org/standards/view/white-paper-on-unified-glare-rating-(ugr)