855773644-LEED-v5-BD-C-Reference-Guide-Launch-Edition - Page 532

Extracted Content

the table. Measure for a four-hour period, calculating peak concentration for carbon monoxide and average concentration for ozone, PM2.5, and PM10.

Table 2. Limits for particulate matter and inorganic gases

Contaminant
(CAS#)
Concentration limit
(µg/m3)
Allowed test methods
(laboratory-based)
Direct reading
instrument minimum
specifications
Carbon monoxide
(CO)
9 ppm; no more than
2 ppm above outdoor
levels
ISO 4224
EPA Compendium Method
IP-3
GB/T 18883-2002 for
projects in China
Direct calibrated
electrochemical
instrument with accuracy
of +/– 3% of reading and
resolution of 0.1 ppm
NDIR CO sensors with
accuracy of 1% of 10
ppm full scale and display
resolution of less than 0.1
ppm
Particulates (for
projects in
attainment areas)
ISO class 8 or lower
per_ISO 14644-_
1:2015

OR meet

PM 10: 50 μg/m3

PM 2.5: 12 μg/m3
n/aAccuracy (+/–): Greater
of 5 μg/m3 or 20% of
reading
Resolution (+/–): 5 μg/m3
Particulates (for
projects in
attainment areas)
ISO class 8 or lower
per_ISO 14644-_
1:2015

OR meet

PM 10: 50 μg/m3

PM 2.5: 12 μg/m3
IP-10AIP-10A
Particulates (for
projects in
nonattainment
areas)
ISO class 8 or lower
per_ISO 14644-_
1:2015

OR meet

PM 10: 50 μg/m3

PM 2.5: 35 μg/m3
n/aAccuracy (+/–): Greater
of 5 μg/m3 or 20% of
reading
Resolution (+/–): 5 μg/m3
Particulates (for
projects in
nonattainment
areas)
ISO class 8 or lower
per_ISO 14644-_
1:2015

OR meet

PM 10: 50 μg/m3

PM 2.5: 35 μg/m3
IP-10AIP-10A
Ozone0.07 ppm

OR 0.01 ppm for
projects pursuing
EQc1: Enhanced Air
Quality, Option 1,
Path 2
ISO 13964
ASTM D5149-02
EPA-designated methods
for ozone
Monitoring device with
accuracy greater of 5 ppb
or 20% of reading and
resolution (5 min.
average data) +/– 5 ppb

AND/OR

PATH 2. VOLATILE ORGANIC COMPOUNDS (1 POINT)

Perform a screening test for total volatile organic compounds (TVOC). Use ISO 16000-6, EPA TO-17, or EPA TO-15 to collect and analyze the air sample. Calculate the TVOC value per EN 16516:2017 ; CDPH Standard Method v1.2 2017, Section 3.9.4; or alternative calculation method if full method description is included in test report.

U.S. Green Building Council LEED v5 Reference Guide for Building Design and Construction, April 2025 Launch Edition 522