855773667-LEED-v5-O-M-Reference-Guide-Launch-Edition-1 - Page 099
Extracted Content
or utility bills, teams must install additional meter(s) to meet the prerequisite. Water consumption data must be based on actual readings and not estimates.
Commitment to sharing data with USGBC Projects must commit to ongoing reporting of whole-project water usage data on an annual basis following certification.
DOCUMENTATION
| Project types | Options | Paths | Documentation |
|---|---|---|---|
All | All | All | Confirmation the project has permanent water meters for all potable and alternative water sources for the building and associated grounds |
All | All | All | Confirmation that alternative water sources are metered separately from municipally supplied potable water |
All | All | All | Confirmation that the facility manager and/or tenant(s) can access the meter data |
All | All | All | Commit to ongoing reporting of whole-project water usage data on an annual basis following certification |
All | All | All | Narrative describing the location of the water meters and the water source for each meter serving the building and associated grounds |
All | All | All | Documentation confirming water consumption values and dates highlighted verifying all consumption data provided for the 12-month reporting period. Acceptable documentation includes utility bills, data directly imported from the utility to the ENERGY STAR® Portfolio Manager, direct exports from utility providers, in-house meter logs, and BAS data. If providing data directly imported from the utility to ENERGY STAR® Portfolio Manager, direct exports from utility providers, in- house meter logs, and BAS data, and indicate the source and type of the documentation. |
| Campus | All | All | Documentation demonstrating campus-level irrigation water sources with prorated irrigation data and supporting calculations, methodology for proration, and documentation with campus water consumption values and dates highlighted verifying campus consumption data provided for the 12-month reporting period. Acceptable documentation includes utility bills, data directly imported from the utility to the ENERGY STAR® Portfolio Manager, direct exports from utility providers, in-house meter logs, and BAS data. If providing data directly imported from the utility to ENERGY STAR® Portfolio Manager, direct exports from utility providers, in-house meter logs, and BAS data, and indicate the source and type of the documentation. |
U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 89