855773667-LEED-v5-O-M-Reference-Guide-Launch-Edition-1 - Page 134
Extracted Content

Energy and Atmosphere Prerequisite
FUNDAMENTAL REFRIGERANT MANAGEMENT
EAp4
REQUIRED
INTENT
To reduce greenhouse gas emissions from refrigerants by accelerating the phaseout of refrigerants with high global warming potential (GWP) and by reducing refrigerant leakage.
REQUIREMENTS
| Achievement pathways | Points |
|---|---|
Existing Buildings | N/A |
Refrigerant Policy | |
AND | AND |
Refrigerant Performance | Refrigerant Performance |
Comply with all of the following requirements:
Refrigerant Policy
Provide and implement a refrigerant policy addressing the following:
-
Removal of refrigerant-containing equipment. Track the removal of refrigerant-containing equipment and ensure that such equipment and the refrigerants are disposed of properly, as per national and local requirements.
-
Refrigerant leakage management. Comply with the current refrigerant leakage management requirements from the U.S. Environmental Protection Agency Section 608, the European Union F-Gas regulation, or relevant national or local requirements.
AND
Refrigerant Performance
Comply with the following requirements for all of the refrigerant-using equipment under the control of the property owner or management during the 12-month reporting period:
- Refrigerant inventory : Complete an inventory of all refrigerant-containing equipment, including the type, GWP, amounts of refrigerants contained in each, and the total GWP of all refrigerants.
U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 124