o Reclamation . Clean the refrigerant for resale. The refrigerant must meet specific
purity requirements. Reclamation efforts commonly occur in a dedicated processing facility.
o Destruction . Incineration or other technologies break down the refrigerants into less
harmful components that will not contribute to ozone depletion or high GWP.
REFRIGERANT LEAKAGE MANAGEMENT
The policy must stipulate compliance with the current refrigerant leakage management requirements from the U.S. Environmental Protection Agency Section 608, the European Union F-Gas regulation, [70] or relevant national or local requirements. These requirements prohibit venting of refrigerants and include:
-
Procedures to limit refrigerant loss when servicing or repairing refrigerant-using equipment
-
Leak testing for new refrigerant system installations
-
Leakage monitoring for larger HVAC and refrigeration equipment, and reporting and repairing large leaks
-
Safe disposal of refrigerants
NO REFRIGERANTS
If the project does not have refrigerant-using equipment, the refrigerant policy must address potential future equipment installations.
Refrigerant Performance
For all refrigerant-using equipment under the control of the property owner or management, teams are required to develop a refrigerant inventory, perform a leakage inspection, recharge equipment that is undercharged due to leakage, and track refrigerant leakage. Projects with no refrigerant-using equipment under the control of the property owner or management have no obligations under this section.
Additional considerations If pursuing EAc3: Enhanced Refrigerant Management Performance, inventory the equipment under tenant control as well as the equipment under owner and/or facilities manager control.