REPORTING PERIOD AND TRACKING REQUIREMENTS

The reporting period for this prerequisite is 12 months. For initial LEED v5 O+M: Existing Buildings certification, refrigerant leakage tracking and reporting is only mandatory for the final three months of the reporting period.

Additional considerations If pursuing EAc3: Enhanced Refrigerant Management Performance, provide leakage tracking and reporting for the full 12-month reporting period.

REFRIGERANT INVENTORY

The refrigerant inventory tracks the total global warming potential (GWP) of equipment in the project. GWP measures the relative contribution of a substance toward heating the atmosphere compared to the same mass of carbon dioxide (CO2). For example, R-410A with a GWP of 2,088 traps 2,088 times more heat in the atmosphere than CO2.

During the 12-month reporting period, complete or update an inventory of all refrigerantcontaining equipment in the project boundary owned or controlled by the project owner and/or facilities manager.

Equipment that contains less than 0.5 pounds (225 grams) of refrigerant, such as standard residential refrigerators, can be excluded from the calculations. Table 1 is a sample, noncomprehensive list of equipment that may be present in a project.

Table 1. Refrigerant-containing equipment

ApplicationEquipment/System type

HVAC, space cooling equipment

Stationary air conditioners and heat pump
Chillers
Computer room air conditioning (CRAC) units
Service water heaters

Heat pump service water heaters

Retail

Food refrigeration
Cold storage
Commercial

Vending machines
Ice machines
Industrial process refrigeration

Process chillers
Ice rink chillers
Other process refrigeration

Data collection For each piece of equipment, document the refrigerant properties, including type of refrigerant, GWP of refrigerant (GWPREFRIGERANT), and refrigerant charge (Rc). When the project includes field-assembled refrigerant piping with long pipe lengths or large pressure drops (e.g., variable refrigerant flow, systems or industrial process equipment), teams must account for additional Rc

U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 127