comfort cooling and other appliances, while larger trigger rates are identified for commercial refrigeration and industrial process refrigeration. [71] Additional Considerations: Fixing smaller leaks below the trigger rates will further reduce GHG emissions from the equipment and support achievement of EAc3: Enhanced Refrigerant Management Performance .

Refrigerant leakage tracking Track refrigerant leakage for a minimum of three months for initial LEED v5 O+M: Existing Building certifications and at least the 12-month reporting period for recertifications or projects pursuing EAc3: Enhanced Refrigerant Management Performance . Tracking must commence no later than the visual leakage inspection for initial certifications. Include the weight of refrigerant added during recharge, the type of refrigerant, and the date and time of recharge.

Calculate the total GWP of all refrigerants used for recharging equipment during the performance period per Equation 4.

Equation 4. Total GWP leaked calculation

𝑛𝑛

where :

𝑛𝑛

𝑖𝑖 𝑇 𝑇 𝑇𝑇 𝐺 𝐺𝐺 𝑙 𝑙 𝑙 = �[(𝐺 𝐺𝐺) 𝑥𝑥 (𝑊 𝑊 ℎ𝑡𝑡 𝑜 𝑟 𝑟 𝑟 𝑟 𝑟 𝑟𝑟 𝑙 𝑙 𝑙 )]

𝑖𝑖=1

𝑖𝑖=1

i = Each refrigerant-using system recharged during the tracking period

GWP = The global warming potential for the refrigerant used in each system

Rc = Refrigerant charge: the amount (lbs or kg) of refrigerant in the system at full charge

Alternatively, for prerequisite compliance only, purchasing records can be used to determine the weight of refrigerant by type procured during the performance period, and approximate total GWP leaked.

DOCUMENTATION
Project typesOptionsPathsDocumentation
All
All
All
Confirm that the project has developed and
implemented a conforming refrigerant policy
Projects with no
refrigerant-
containing
equipment



Confirm no refrigerant-using equipment under the
control of the property owner or management (if
applicable)

Projects with
refrigerant-
containing
equipment

Refrigerant inventory with complete list of all
refrigerant-containing equipment under the control of
the property owner or management. Include the
equipment type, refrigerant type, GWP, and
refrigerant charge for each piece of equipment

Projects with
refrigerant-
containing
equipment


Total GWP of all refrigerants

71 U.S. EPA, Stationary Refrigeration Leak Repair Requirements , December 15, 2023, www.epa.gov/section608/stationary- refrigeration-leak-repair-requirements.

U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 129