855773667-LEED-v5-O-M-Reference-Guide-Launch-Edition-1 - Page 166

Extracted Content

Table 3. Points for percentage energy improvement over historical baseline

Percentage reductionPercentage reduction
high process load buildings*
Points
15%

8%
2

18%

10%

3

21%

12%

4

24%

14%

5

27%

16%

6

30%

18%

7

33%

20%

8

36%

22%

9

40%

24%

10

44%

27%

11

48%

30%

12

*High process load buildings applying the lower percentage reduction thresholds must meet all criteria for high process load buildings referenced in EAp3: Minimum Energy Performance .

REQUIREMENTS EXPLAINED

This credit rewards projects for exceeding the minimum performance thresholds required by EAp3: Minimum Energy Performance . Projects must use the same Option for this credit selected in EAp3: Minimum Energy Performance .

Option 1. ENERGY STAR® Score

Projects that use Option 1 must demonstrate that the building scores at least 69 or higher to claim points for the credit.

Option 2. Energy Use Intensity Target

For Option 2, percentage improvement thresholds are dependent on whether the building category is Category 1 or 2, per the LEED v5 O+M, Appendix II Table 1 . Points are awarded based on the percent improvement over the site energy or source energy use intensity (EUI), whichever results in a greater percentage improvement.

Option 3. Performance Relative to Historical Baseline

For Option 3, projects that meet at least a 15% reduction in either site or source energy use beyond the historical baseline will achieve points for the credit. For projects that met the high process load building eligibility criteria in the prerequisite, teams must show at least an 8% reduction to achieve two points.

U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 156