855773667-LEED-v5-O-M-Reference-Guide-Launch-Edition-1 - Page 168
Extracted Content

Energy and Atmosphere Credit
ENHANCED REFRIGERANT MANAGEMENT PERFORMANCE
EAc3
1–2 points
INTENT
To encourage reduced leakage of older refrigerants with high global warming potential (GWP) and ozone-depleting potential (ODP), and to encourage the installation of equipment using refrigerants with low GWP.
REQUIREMENTS
| Achievement pathways | Points |
|---|---|
Existing Buildings | 1–2 |
Enhanced Refrigerant Management Performance | 1–2 |
Refrigerant leakage emissions ratio To calculate the refrigerant leakage emissions ratio, divide the total GWP of the refrigerants leaked during the 12-month reporting period by the total weight of all refrigerants present in the project.
Points are awarded according to Table 1.
Table 1. Refrigerant leakage emissions ratio
| Refrigerant leakage emissions ratio | Points |
|---|---|
| ≤ 50 | 1 |
| ≤ 25 | 2 |
Projects that neither have refrigerant-using equipment in the project nor receive district thermal energy generated from refrigerant-using equipment automatically achieve the two-point threshold.
Equation 1. Refrigerant leakage emissions ratio
𝑅 𝑅 𝑅𝑅𝑔𝑔𝑒 𝑒 𝑒𝑒 𝑙 𝑙 𝑙 𝑙𝑙 𝑒 𝑒 𝑒 𝑒 𝑒𝑒 𝑟 𝑟 𝑟𝑟=
𝑛 𝑖=1 𝑖 ∑ [(𝐺 𝐺) 𝑥 (𝑊 𝑊 ℎ𝑡 𝑜 𝑟 𝑟 𝑟 𝑟 𝑟 𝑟 𝑙 𝑙 𝑙 )]
𝑛
𝑛
𝑖=1 𝑖
∑ [𝑅 ]
where :
U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 158