  • For projects in Climate Zone 6–8, metering for cooling loads is optional. Metering for heating loads is required.

Thermal demand may be directly logged and recorded with energy meters (often referred to as BTU meters) or may leverage data from the project’s building automation system (BAS) to calculate the hourly demand based on measured flow rates and water temperature for chilled and hot water.

Multiple heating meters or multiple cooling meters For projects with multiple meters for either heating or cooling, analyze the metered hourly data for the heating or cooling to determine the hour with peak coincident energy use.

DOCUMENTATION
Project
types
OptionsPathsDocumentation

Existing
Buildings
All

All

Narrative describing the meters or submeters, and the
method for determining peak coincident load

Existing
Buildings
All

All


If different than historical performance period in_EAp3:
Minimum Energy Performance or_EAc1: Greenhouse

Gas Emissions Reduction Performance, narrative
description confirming similar occupancy for the
historical baseline and describing any normalization

Existing
Buildings
All

All


If normalization is applied, documentation or calculations
supporting determination of normalized results

Existing
Buildings
Option 1
All

Provide electric demand for the 12-month reporting
period

Existing
Buildings
Option 1
All

Percentage electric demand reduction by comparing the
sum of monthly peak demand for the two months with
the highest peak demand for the 12-month reporting
period with a baseline 12-month reporting period
(Equation 1)

Existing
Buildings
Option 1
Projects with
excluded
tenant area

If applicable, meters and associated gross floor area
excluded from hourly demand metering. Total combined
area excluded for this credit and_EAp2: Energy_
Monitoring and Reporting cannot exceed 20% of total
project gross floor area

Existing
Buildings
Option 2All
Monthly peak hourly heating demand for the 12-month
reporting period, and the historical baseline 12-month
reporting period (Climate Zones 3–8)

Existing
Buildings
Option 2All
Monthly peak hourly cooling demand for the 12-month
reporting period, and the historical baseline 12-month
reporting period (Climate Zones 0–5)

Existing
Buildings
Option 2All
Percentage reduction in the sum of the monthly peak
hourly heating demand and the monthly hourly peak
cooling demand for the 12-month reporting period with a
baseline 12-month reporting period (Equation 3)

U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 168