855773667-LEED-v5-O-M-Reference-Guide-Launch-Edition-1 - Page 191

Extracted Content

Energy and Atmosphere Credit

COMMISSIONING

EAc7

1–2 points

INTENT

To use the existing building commissioning process to improve building operations and energy and resource efficiency.

REQUIREMENTS
Achievement pathwaysPoints

Existing Building

1–2

Option 1. Retro-Commissioning

2

OR



Option 2. Monitoring-Based Commissioning
1–2

Path 1. Basic MBCx

1

OR



Path 2. Enhanced MBCx
1

Option 1. Retro-commissioning (2 points)

Complete a retro-commissioning (RCx) process no more than three years before the end of the 12-month reporting period.

Engagement phase

  • Engage a third-party retro-commissioning provider (RCxP) with experience on at least two projects of similar type and scale.

Planning phase

  • Assemble a project team to include, at a minimum, the RCxP, an owner’s representative, and the building operator.

  • Develop the owner’s objectives for the RCx process.

Assessment phase

  • Develop the RCx plan to include owner and tenant requirements, documentation requirements, regulatory requirements, etc.

  • Perform a site visit and site assessment, including functional tests.

U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 181