855773667-LEED-v5-O-M-Reference-Guide-Launch-Edition-1 - Page 242
Extracted Content

Indoor Environmental Quality Credit
VENTILATION PERFORMANCE
EQc2
3–5 points
INTENT
To provide increased indoor air quality to better protect the health of building occupants.
REQUIREMENTS
| Achievement pathways | Points |
|---|---|
Existing Buildings | 3–5 |
Ventilation Performance | 3–5 |
Ventilation per ANSI/ASHRAE Standard 62.1
Demonstrate that outdoor air ventilation rates of all occupied spaces meet or exceed ASHRAE 62.1-2022 or later based on the measurements reported in EQp1: Verification of Ventilation and Filtration . Alternatively, the rates may meet or exceed the ventilation rate procedure outlined in Section 6.2 of ASHRAE 62.1, [106] editions 2016, 2013, 2010, or 2007. If demonstrating exceedance from the referenced standard, increased outdoor air rates shall be provided to 95% of all regularly occupied spaces.
Naturally ventilated spaces meet ASHRAE 62.1-2022, “Natural Ventilation Procedure,” or exceed opening sizes or natural ventilation airflow rates of ASHRAE 62.1-2022, “Natural Ventilation Procedure.”
Points are awarded according to Table 1.
Table 1. Points for ventilation
| Ventilation performance | Points |
|---|---|
Meet referenced standard | 3 |
Exceed referenced standard by 15% | 4 |
Exceed referenced standard by 30% | 5 |
106 ASHRAE, “The Standards for Ventilation and Indoor Air Quality,” n.d., https://www.ashrae.org/technical- resources/bookstore/standards-62-1-62-2.
U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, April 2025 Launch Edition 232