ASHRAE+62.1-2022+(1) - Page 020

Extracted Content

Table 6-1 Minimum Ventilation Rates in Breathing Zone (Continued)

People Outdoor

Air Rate Rp

Area Outdoor

Air Rate Ra

Default Values

Occupant Density

#/1000 ft [2]

or #/100 m [2]

L/s· person cfm/ft [2] L/s·m [2]

Air Class

OS (6.2.6.1.4)

Occupancy Category

cfm/ person

Cafeteria/fast-food dining 7.5 3.8 0.18 0.9 100 2

Kitchen (cooking) 7.5 3.8 0.12 0.6 20 2

Restaurant dining rooms 7.5 3.8 0.18 0.9 70 2

General

Break rooms 5 2.5 0.06 0.3 25 1 

Coffee stations 5 2.5 0.06 0.3 20 1 

Conference/meeting 5 2.5 0.06 0.3 50 1 

Corridors - - 0.06 0.3 - 1 

Occupiable storage rooms for liquids or gels 5 2.5 0.12 0.6 2 2

Hotels, Motels, Resorts, Dormitories

Barracks sleeping areas 5 2.5 0.06 0.3 20 1 

Bedroom/living room 5 2.5 0.06 0.3 10 1 

Laundry rooms, central 5 2.5 0.12 0.6 10 2

Laundry rooms within dwelling units 5 2.5 0.12 0.6 10 1

Lobbies/prefunction 7.5 3.8 0.06 0.3 30 1 

Multipurpose assembly 5 2.5 0.06 0.3 120 1 

Miscellaneous Spaces

Banks or bank lobbies 7.5 3.8 0.06 0.3 15 1 

Bank vaults/safe deposit 5 2.5 0.06 0.3 5 2 

Computer (not printing) 5 2.5 0.06 0.3 4 1 

Freezer and refrigerated spaces (<50°F [10°C]) 10 5 0 0 0 2

Manufacturing where hazardous materials  are not used

Manufacturing where hazardous materials are used (excludes heavy industrial and chemical processes)

10 5.0 0.18 0.9 7 2

10 5.0 0.18 0.9 7 3

Pharmacy (prep. area) 5 2.5 0.18 0.9 10 2

Photo studios 5 2.5 0.12 0.6 10 1

Shipping/receiving 10 5 0.12 0.6 2 2

Sorting, packing, light assembly 7.5 3.8 0.12 0.6 7 2

Telephone closets - - 0.00 0.0 - 1

Transportation waiting 7.5 3.8 0.06 0.3 100 1 

Warehouses 10 5 0.06 0.3 - 2

Office Buildings

Breakrooms 5 2.5 0.12 0.6 50 1

Main entry lobbies 5 2.5 0.06 0.3 10 1 

18 ANSI/ASHRAE Standard 62.1-2022