ASHRAE+62.1-2022+(1) - Page 021
Extracted Content
Table 6-1 Minimum Ventilation Rates in Breathing Zone (Continued)
People Outdoor
Air Rate Rp
Area Outdoor
Air Rate Ra
Default Values
Occupant Density
#/1000 ft [2]
or #/100 m [2]
L/s· person cfm/ft [2] L/s·m [2]
Air Class
OS (6.2.6.1.4)
Occupancy Category
cfm/ person
Occupiable storage rooms for dry materials 5 2.5 0.06 0.3 2 1
Office space 5 2.5 0.06 0.3 5 1
Reception areas 5 2.5 0.06 0.3 30 1
Telephone/data entry 5 2.5 0.06 0.3 60 1
Public Assembly Spaces
Auditorium seating area 5 2.5 0.06 0.3 150 1
Courtrooms 5 2.5 0.06 0.3 70 1
Legislative chambers 5 2.5 0.06 0.3 50 1
Libraries 5 2.5 0.12 0.6 10 1
Lobbies 5 2.5 0.06 0.3 150 1
Museums (children’s) 7.5 3.8 0.12 0.6 40 1
Museums/galleries 7.5 3.8 0.06 0.3 40 1
Places of religious worship 5 2.5 0.06 0.3 120 1
Residential
Common corridors - - 0.06 0.3 1
Retail
Sales (except as below) 7.5 3.8 0.12 0.6 15 2
Barbershop 7.5 3.8 0.06 0.3 25 2
Beauty and nail salons 20 10 0.12 0.6 25 2
Coin-operated laundries 7.5 3.8 0.12 0.6 20 2
Mall common areas 7.5 3.8 0.06 0.3 40 1
Pet shops (animal areas) 7.5 3.8 0.18 0.9 10 2
Supermarket 7.5 3.8 0.06 0.3 8 1
Sports and Entertainment
Bowling alley (seating) 10 5 0.12 0.6 40 1
Disco/dance floors 20 10 0.06 0.3 100 2
Gambling casinos 7.5 3.8 0.18 0.9 120 1
Game arcades 7.5 3.8 0.18 0.9 20 1
Gym, sports arena (play area) 20 10 0.18 0.9 7 2
Health club/aerobics room 20 10 0.06 0.3 40 2
Health club/weight rooms 20 10 0.06 0.3 10 2
Spectator areas 7.5 3.8 0.06 0.3 150 1
Stages, studios 10 5 0.06 0.3 70 1
Swimming (pool and deck) - - 0.48 2.4 - 2
ANSI/ASHRAE Standard 62.1-2022 19