Table G-1 Minimum Outdoor and Primary Airflow Rates
Outdoor Airflow Rate Rs
Zone Minimum Airflow
Minimum Primary
Airflow Rate, Rpz
Occupancy Category
Educational Facilities
cfm/ft [2] L/s·m [2] cfm/ft [2] L/s·m [2]
Classrooms (ages 5 to 8) 0.65 3.25 1.12 5.60
Classrooms (ages 9 plus) 0.82 4.10 1.41 7.05
Computer lab 0.65 3.25 1.12 5.60
Media center 0.65 3.25 1.12 5.60
Music/theater/dance 0.72 3.60 1.24 6.20
Multiuse assembly 1.42 7.10 2.45 12.25
General
Conference/meeting 0.44 2.20 0.76 3.80
Corridors 0.11 0.55 0.19 0.95
Office Buildings
Breakrooms 0.65 3.25 1.12 5.60
Main entry lobbies 0.19 0.95 0.33 1.65
Occupiable storage rooms for dry materials
0.12 0.60 0.21 1.05
Office space 0.15 0.75 0.26 1.30
Reception areas 0.37 1.85 0.64 3.20
Telephone/data entry 0.63 3.15 1.09 5.45
Public Assembly Spaces
Libraries 0.30 1.50 0.52 2.60
ANSI/ASHRAE Standard 62.1-2022 51