ASHRAE+62.1-2022+(1) - Page 073

Extracted Content

(This appendix is not part of this standard. It is merely informative and does not contain require- ments necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX M VENTILATION RATE CHECK TABLE

Table M-1 is not for design purposes. It is intended to provide check values. Default rate per unit area is based on a multiple-zone system with default occupancy and default Ev that equals 0.75. This is the default Ev in the simplified rate when D - 0.60.

Table M-1 Check Table for the Ventilation Rate Procedure (VRP)

Combined Outdoor Air Rate ( Rc )

Occupancy Category

Animal Facilities

cfm/ft [2] L/s· m [2]

Animal exam room (veterinary office) 0.43 2.13

Animal imaging (MRI/CT/PET) 0.51 2.53

Animal operating rooms 0.51 2.53

Animal postoperative recovery room 0.51 2.53

Animal preparation rooms 0.51 2.53

Animal procedure room 0.51 2.53

Animal surgery scrub 0.51 2.53

Large-animal holding room 0.51 2.53

Necropsy 0.51 2.53

Small-animal-cage room (static cages) 0.51 2.53

Small-animal-cage room (ventilated cages) 0.51 2.53

Correctional Facilities

Booking/waiting 0.58 2.93

Cell 0.33 1.63

Dayroom 0.28 1.40

Guard stations 0.18 0.90

Educational Facilities

Art classroom 0.51 2.53

Classrooms (ages 5 through 8) 0.49 2.47

Classrooms (ages 9 plus) 0.63 3.13

Computer lab 0.49 2.47

Daycare sickroom 0.57 2.87

Daycare (through age 4) 0.57 2.87

Lecture classroom 0.73 3.69

Lecture hall (fixed seats) 1.58 8.00

Libraries 0.23 1.13

Media center 0.49 2.47

ANSI/ASHRAE Standard 62.1-2022 71