ASHRAE+62.1-2022+(1) - Page 074
Extracted Content
Table M-1 Check Table for the Ventilation Rate Procedure (VRP) (Continued)
Combined Outdoor Air Rate ( Rc )
Occupancy Category
cfm/ft [2] L/s· m [2]
Multiuse assembly 1.08 5.47
Music/theater/dance 0.55 2.73
Science laboratories 0.57 2.87
University/college laboratories 0.57 2.87
Wood/metal shop 0.51 2.53
Food and Beverage Service
Bars, cocktail lounges 1.24 6.27
Cafeteria/fast-food dining 1.24 6.27
Kitchen (cooking) 0.36 1.81
Restaurant dining rooms 0.94 4.75
Food and Beverage Service, General
Break rooms 0.25 1.23
Coffee stations 0.21 1.07
Conference/meeting 0.41 2.07
Corridors 0.08 0.40
Occupiable storage rooms for liquids or gels 0.17 0.87
Hotels, Motels, Resorts, Dormitories
Barracks sleeping areas 0.21 1.07
Bedroom/living room 0.15 0.73
Laundry rooms (central) 0.23 1.13
Laundry rooms within dwelling units 0.23 1.13
Lobbies/prefunction 0.38 1.92
Multipurpose assembly 0.88 4.40
Miscellaneous Spaces
Banks or bank lobbies 0.23 1.16
Bank vaults/safe deposit 0.11 0.57
Computer (not printing) 0.11 0.53
Freezer and refrigerated spaces (<50°F [10°C]) 0.03 0.13
General manufacturing (excludes heavy industrial and processes using chemicals)
0.33 1.67
Pharmacy (prep area) 0.31 1.53
Photo studios 0.23 1.13
Shipping/receiving 0.19 0.93
Sorting, packing, light assembly 0.23 1.15
Telephone closets 0.00 0.00
Transportation waiting 1.08 5.47
Warehouses 0.09 0.47
72 ANSI/ASHRAE Standard 62.1-2022