LEED-BDC-v4-v5-Summary-of-Changes - Page 014

Extracted Content

CreditEnhanced Indoor Air Quality Strategies (continued)
  • Increased ventilation incorporated into new credit: EQc Enhanced Air Quality.
  • Requirement changed to 15% increase in outdoor air ventilation for 1 point, and 30% increase for exemplary performance.
  • Monitoring incorporated into EQc Air Quality Testing and Monitoring.
  • Removed the following strategies: interior cross contamination prevention, natural ventilation design calculations, mixed-mode design calculations, exterior contamination prevention, additional source control and monitoring, and natural ventilation room-by-room calculations.
CreditLow-Emitting Materials
  • Moved to the Materials and Resources category.
  • Reduced total point thresholds and modified the approach for awarding points.
  • Modified percentage compliance for paints/coatings, flooring, ceilings, adhesives and sealants, walls, insulation, composite wood and furniture.
  • Removed budget calculation method option.
  • Elaborated products and materials that can be excluded.
  • Added option to document paints and coatings by cost or surface area.
  • Added option to document adhesives and sealants by cost.
  • Reference standard for VOC emissions evaluation criteria updated to CDPH v1.2-2017.
  • Updated reference standard for furniture emissions evaluation criteria to ANSI/BIFMA Standard Method M7.1-2011(R2021) and ANSI/BIFMA e3-2014 or e3-2024 and elaborated on requirements for seating products, classroom furniture and appropriate evaluation scenarios.
  • Added requirements for formaldehyde emissions evaluation.
  • Removed additional VOC content requirements for wet-applied products.
CreditConstruction Indoor Air Quality Management Plan
  • Incorporated into new prerequisite: EQp Construction Management.
  • Added the following construction management practices: extreme heat protection, source control, pathway interruption, housekeeping & scheduling.
  • Modified requirement for filtration during construction.
CreditIndoor Air Quality Assessment
  • Incorporated into new credit: EQc Air Quality Testing and Monitoring
  • Modified requirements for air testing option and added a point for particulate matter (PM) and inorganic gases testing and added a separate point for volatile organic compounds (VOC) testing.
  • Updated reference standards and test methods and target compounds for VOC testing.
  • Added a new option for one point for continuous indoor air monitoring of CO2, PM2.5, TVOC, temperature, and relative humidity.
  • Removed flush out option.

Repair provenance

Reconstructed from the PDF’s embedded text and word/block coordinates, then visually verified against original PDF page 14 on 2026-07-26. The continued credit, four rows, percentages, ampersand, rating notation, and all bullet associations were confirmed from the original page image; no Marker or OCR text was used.

Visual Reference