Install automatic window shades or shielding that limit light transmittance to 10% or less during nighttime.
- The lighting in at least 50% of the nonresidential spaces adjacent to the building’s perimeter is controlled to turn off after hours and/or when there are no occupants.
AND
EXTERIOR LIGHTING
Meet at least one of the following measures:
-
All nonessential exterior fixtures are turned off between midnight and 6 a.m.
-
Meet the exterior lighting control requirements of ASHRAE 90.1-2019, Section 9.4.1.4.
OR
Option 2. Bird Collision Reduction (1 point)
Glass used below specified heights on the exterior of the building and site structures must have a maximum threat factor of 30, as defined in the American Bird Conservancy Threat Factor database.
This applies to all glass, including spandrel glass, when located:
-
From grade up to 50 feet (15 meters) measured at all points
-
Up to 20 feet (6 meters) measured from the finished grade of a green roof
-
At any distance from grade or roof for glass in guardrails and windshields