Energy and Atmosphere Credit
ENHANCED REFRIGERANT MANAGEMENT PERFORMANCE
EAc3
1–2 points
INTENT
To encourage reduced leakage of older refrigerants with high global warming potential (GWP) and ozone-depleting potential (ODP), and to encourage the installation of equipment using refrigerants with low GWP.
REQUIREMENTS
| Achievement Pathways | Points |
|---|---|
Existing Buildings | 1–2 |
Enhanced Refrigerant Management Performance | 1–2 |
Refrigerant Leakage Emissions Ratio To calculate the refrigerant leakage emissions ratio, divide the total GWP of the refrigerants leaked during the 12-month reporting period by the total weight of all refrigerants present in the project.
Points are awarded according to Table 1.
Table 1. Refrigerant Leakage Emissions Ratio
| Refrigerant Leakage Emissions Ratio | Points |
|---|---|
| ≤ 50 | 1 |
| ≤ 25 | 2 |
Projects that have neither refrigerant-using equipment in the project nor receive district thermal energy generated from refrigerant-using equipment automatically achieve the 2-point threshold.
Equation 1. Refrigerant leakage emissions ratio
𝑅 𝑅 𝑅 𝑅 𝑅 𝑅𝑅 𝑙 𝑙 𝑙 𝑙𝑙 𝑒 𝑒 𝑒 𝑒 𝑒𝑒 𝑟 𝑟 𝑟𝑟=
𝑛 𝑖=1 𝑖 ∑ [(𝐺 𝐺) 𝑥 (𝑊 𝑊 ℎ𝑡 𝑜 𝑟 𝑟 𝑟 𝑟 𝑟 𝑟 𝑙 𝑙 𝑙 )]
𝑛
where :
- i = Each refrigerant-using system in the project
𝑛
𝑖=1 𝑖
∑ [𝑅 ]
U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, November 2025 Edition 45