  • Heating demand (for climate zones 3–8): measure total hourly thermal energy consumed for space heating, service water heating, and process heating.

    • Cooling demand (for climate zones 0–5): measure total hourly thermal energy consumed for space cooling and process cooling.

Report the monthly peak hourly heating demand and the monthly peak hourly cooling demand for the current 12-month reporting period and for a baseline 12-month reporting period occurring within eight years before the end of the 12-month reporting period. Compare the current reporting period to the baseline reporting period to demonstrate a 10% reduction in the sum of the maximum monthly heating demand and the maximum monthly cooling demand.

U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, November 2025 Edition 48