Normalization of energy consumption
-
Automated reporting of energy use anomalies
-
Greenhouse gas emissions reporting
-
Hourly metering and visualization of electricity for the following, if applicable:
o On-site electricity generation
o HVAC or refrigeration equipment with thermal energy capacity exceeding 900,000
Btu/hr (264 kW, 75 tons), or with rated fan power exceeding 75 hp (56 kW)
o Electricity use for process equipment with thermal energy capacity exceeding
900,000 Btu/hr (264 kW, 75 tons)
o Commercial kitchen equipment in spaces with more than 25 kW of rated capacity
o Process equipment in spaces with more than 25 kW of rated capacity
FDD for projects with large HVAC and refrigeration capacity For total project installed capacity of either cooling systems, heating systems, or refrigeration systems exceeding 7,200 kBtu/hr (600 tons or 2,110 kW), provide a remotely accessible FDD system that addresses at least 60% weighted by capacity of:
-
Air handling equipment, AND
-
Large hydronic or commercial refrigeration equipment (chillers, boilers, etc.).
The FDD system must include the following functionality:
-
Perform smart analytics and visually present FDD data
-
Direct link from reported fault to view relevant trend data
-
Fault sorting and filtering
-
Exporting of fault reports (summary reports and detailed individual faults)
-
Data historian capable of storing critical trend data for at least three years