  • Carbon dioxide (CO2): 95th percentile value

    • PM2.5: Daily average

    • TVOC: Daily average in units of parts per million or micrograms per cubic meter

AND/OR

Option 2. Targeted One-Time Air testing (1–3 points)

Test for parameters listed in Table 2 at least once during the 12-month reporting period. Include a concurrent measurement of outdoor ambient air quality within the project boundary for reference comparison.

One point is available for testing and meeting the minimum IAQ limit for every two parameters listed in Table 2, for a total of up to 3 points. Use one of the allowed test methods listed in Table 2. One-time Air testing. Project teams may use laboratory-based or direct-read test methods.

Table 2. One-Time Air Testing

ParameterConcentration Limit
(µg/m3)
Allowed Test MethodsCol4
**Parameter **
Concentration Limit
**(µg/m3) **
Laboratory-Based
Direct-Reading
Instrument Minimum
Specifications
Carbon
monoxide
(CO)
9 ppm and no more than
2 ppm above outdoor
levels
ISO 4224
EPA Compendium Method
IP-3
_GB/T 18883-2002_for
projects in China
Direct calibrated
electrochemical
instrument with accuracy
of ±3% of reading and
resolution of 0.1 ppm
NDIR CO sensors with
accuracy of 1% of 10 ppm
full scale and display
resolution of less than 0.1
ppm
Particulates:
PM 10
ISO class 8 or lower per
ISO 14644-1:2015
OR
meet 50 μg/m3
IP-10A

Accuracy (±): Greater of 5
μg/m3 or 20% of reading
Resolution (±): 5 μg/m3
Particulates:
PM2.5*

ISO class 8 or lower per
ISO 14644-1:2015
OR
meet 12 μg/m3
IP-10A
Accuracy (±): Greater of 5
μg/m3 or 20% of reading
Resolution (±): 5 μg/m3
Particulates:
PM2.5*

OR, for projects located
in an area where the
national standard or
guideline for PM2.5 is
exceeded, meet35
μg/m3

OR, for projects located
in an area where the
national standard or
guideline for PM2.5 is
exceeded, meet35
μg/m3

OR, for projects located
in an area where the
national standard or
guideline for PM2.5 is
exceeded, meet35
μg/m3
Ozone
0.07 ppm
ISO 13964
ASTM D5149-02
Monitoring device with
accuracy greater of 5 ppb
or 20% of reading and