ParameterConcentration Limit
(µg/m3)
Allowed Test MethodsCol4
**Parameter **Concentration Limit
**(µg/m3) **
Laboratory-Based
Direct-Reading
Instrument Minimum
Specifications
EPA designated methods
for ozone
resolution (5 min average
data) ± 5 ppb
Nitrogen
dioxide (NO2)
40 µg/m3 (21 ppb)



Monitoring device with
measurement range of 0–
500 ppb and lower
detectable limit of 5 ppb
TVOC*N/A
Monitoring device that
meets or exceeds building
grade sensor
requirements

NOTE: May not earn points for both targeted one-time air testing and continuous indoor air monitoring for the same parameter.

AND/OR

Option 3. Targeted One-Time Individual Volatile Organic Compounds Testing (2 points)

Test for all volatile organic compounds (VOCs) listed in Table 3 at least once during the 12month reporting period. Laboratories that conduct the tests must be accredited under ISO/IEC 17025 for the test methods they use.

Calculate the total volatile organic compounds (TVOC) value per EN 16516:2017 ; CDPH Standard Method v1.2 2017, Section 3.9.4; [6] or an alternative calculation method if a full method description is included in the test report. If the TVOC levels exceed 500 µg/m [3], investigate for potential issues by comparing the individual VOC levels to associated cognizant authority health-based limits. Correct any identified issues and retest.

Two points are available for demonstrating that all contaminants do not exceed the concentration limits listed in Table 3.

Table 3. One-Time Air Testing of Individual Volatile Organic Compounds

Contaminant (CAS#)Concentration LimitAllowed Test Methods
(Laboratory-Based)
TVOCInvestigate and take corrective
action if levels exceed 500 µg/m3.
ISO 16000-6;
EPA TO-17;
EPA TO-15
Formaldehyde 50-00-020 µg/m3 (16 ppb)ISO 16000-3, 4;

6 CDPH, “Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions From Indoor Sources Using Environmental Chambers, Version 1.2,” January 2017, https://www.cdph.ca.gov/programs/ccdphp/deodc/ehlb/iaq/cdph%20document%20library/cdph- iaq_standardmethod_v1_2_2017_ada.pdf.

U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, November 2025 Edition 69