LEED v5 O+M Rating System_February 2026 - Page 077
Extracted Content

Indoor Environmental Quality Credit
VENTILATION PERFORMANCE
EQc2
3–5 points
INTENT
To provide increased indoor air quality to better protect the health of building occupants.
REQUIREMENTS
| Achievement Pathways | Points |
|---|---|
Existing Buildings | 3–5 |
Ventilation Performance | 3–5 |
Ventilation per ANSI/ASHRAE Standard 62.1
Demonstrate that outdoor air ventilation rates of all occupied spaces meet or exceed ASHRAE 62.1-2022 or later based on the measurements reported in EQp1: Verification of Ventilation and Filtration . Alternatively, the rates may meet or exceed the ventilation rate procedure outlined in Section 6.2 of ASHRAE 62.1, [7] editions 2016, 2013, 2010, or 2007.
Naturally ventilated spaces meet ASHRAE 62.1-2022, “Natural Ventilation Procedure,” or exceed opening sizes or natural ventilation airflow rates of ASHRAE 62.1-2022, “Natural Ventilation Procedure.”
If demonstrating exceedance from the referenced standard, increased outdoor air rates (or opening sizes) shall be provided to 95% of all regularly occupied spaces.
Points are awarded according to Table 1.
Table 1. Points for ventilation
| Ventilation Performance | Points |
|---|---|
Meet referenced standard | 3 |
Exceed referenced standard by 15% | 4 |
Exceed referenced standard by 30% | 5 |
7 ASHRAE, “Ventilation and Acceptable Indoor Air Quality,” ASHRAE 62.1-2022, 2022, accessed March 31, 2025, https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2, https://www.ashrae.org/technical- resources/bookstore/standards-62-1-62-2.
U.S. Green Building Council LEED v5 Reference Guide for Operations and Maintenance, November 2025 Edition 71