Table 3. Standards for appliances
| Appliance | Col2 | Requirement | Col4 |
|---|---|---|---|
| Residential clothes washer | Residential clothes washer | ENERGY STAR® or performance equivalent | ENERGY STAR® or performance equivalent |
| Commercial clothes washer | Commercial clothes washer | ENERGY STAR® for commercial clothes washers with ≤ 8.0 cubic feet (227 liters) of capacity or performance equivalent | ENERGY STAR® for commercial clothes washers with ≤ 8.0 cubic feet (227 liters) of capacity or performance equivalent |
| Residential dishwashers (standard and compact) | Residential dishwashers (standard and compact) | ENERGY STAR® or performance equivalent | ENERGY STAR® or performance equivalent |
| Prerinse spray valves | Prerinse spray valves | ≤ 1.3 gpm (4.9 lpm) | ≤ 1.3 gpm (4.9 lpm) |
| Ice machine | Ice machine | ENERGY STAR® or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system | ENERGY STAR® or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system |
| Commercial Kitchen Equipment | Commercial Kitchen Equipment | Requirement (IP) | Requirement (SI) |
| Dishwasher | Undercounter | ≤ 1.6 gal/rack | ≤ 6.0 liters/rack |
| Dishwasher | Stationary, single tank, door | ≤ 1.4 gal/rack | ≤ 5.3 liters/rack |
| Dishwasher | Single tank, conveyor | ≤ 1.0 gal/rack | ≤ 3.8 liters/rack |
| Dishwasher | Multiple tank, conveyor | ≤ 0.9 gal/rack | ≤ 3.4 liters/rack |
| Dishwasher | Flight machine | ≤ 180 gal/hr | ≤ 680 liters/hr |
| Food steamer | Boilerless/ connectionless | ≤ 2 gal/hr/pan | ≤ 7.5 liters/hr/pan |
| Food steamer | Steam generator | ≤ 5 gal/hr/pan | ≤ 19 liters/hr/pan |
| Combination oven | Countertop or stand | ≤ 1.5 gal/pan | ≤ 5.7 liters/pan |
| Combination oven | Roll-in | ≤ 1.5 gal/pan | ≤ 5.7 liters/pan |
Table 4. Standards for processes
| Process | Requirement |
|---|---|
| Heat rejection and cooling | No once-through cooling with potable water for any equipment or appliances that reject heat |
| Discharge water temperature tempering | Where local requirements limit the discharge temperature of fluids into a drainage system, use a tempering device that runs water only when the equipment discharges hot water. OR Provide a thermal recovery heat exchanger that cools drained discharge water below code-required maximum discharge temperatures while simultaneously preheating inlet makeup water. OR If fluid is steam condensate, return it to boiler. |
| Venturi-type flow-through vacuum generators or aspirators | Use no device that generates a vacuum by means of water flow through the device into the drain. |