district energy sources serving the project, derive these purchased energy rates and/or conversion factors as follows:

o Purchased chilled water (CHW) . Multiply the utility rate or source energy

conversion factor for electricity by a factor of 0.325 to estimate the CHW utility rate or source energy conversion factor.

o Purchased heat from district hot water (HHW) . Multiply the utility rate or

source energy conversion factor by a factor of 1.5 for the predominant fossil fuel source used to generate the district hot water or natural gas if unknown.

o Purchased heat from district steam . Multiply the utility rate or source energy

conversion factor by a factor of 1.7 for the predominant fossil fuel source used to generate the district hot water or natural gas if unknown.

Summary of EA credit linkages to EAp2: Minimum Energy Efficiency

Col1Option 1
ASHRAE 90.1-2019
Option 2.
ASHRAE 90.1-2022
Applicability

Limited to projects registered prior to
January 1, 2028.

Available to all projects.
Required for projects registered on or
after January 1, 2028.
Linked Credits:





EAc2: Enhanced Energy Efficiency





EAc2: Enhanced Energy Efficiency





EAc2: Enhanced Energy Efficiency



Prescriptive
Method

(Option 1, Paths
1 and 2 of the
credit)

Required as precondition to document
points for additional efficiency.

(See Path 2, Case 1)
3 points automatically awarded for
prerequisite compliance using
Prescriptive Method. (Path 1)

Further points for additional efficiency
using either Case 1. Systems
Optimization or Case 2. Additional
efficiency requirements beyond_ASHRAE_
90.1-2022.
Appendix G PRM

(Option 2 of the
credit)

NOTE**:** Treatment
of on-site
renewable energy
varies from
prerequisite.
Incremental performance improvement
documented using the future source
energy metric earns points.

Points awarded for improvement beyond
a 90.1-2019 equivalent-baseline using
the future source energy metric.

Performance target for prerequisite and
credit determined separately using
simple calculation adjusting referenced
BPF.

U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 114