855773520-LEED-v5-ID-C-Reference-Guide-Launch-Edition-1 - Page 139

Extracted Content

DOCUMENTATION
Project
types
OptionsPathsDocumentation
AllAllAllFinal (or draft) commissioning report. If the report is a draft,
include a plan for the completion of commissioning and
training, including climatic and other conditions required for
performance of any deferred tests.
AllAllAll
Identification of CxP including key personnel and V&T
providers (as applicable).
AllAllAll
Qualifications of CxP and V&T providers.
AllAllAllConfirmation that BOD/OPR were reviewed by CxP.
AllAllAllConfirmation of design phase/milestone meetings.
AllAllAllConfirmation that submittals were reviewed and at least
10% were QA/QC’d.
AllAllAll
Confirmation of compliance with_ANSI/ASHRAE/IES_
_Standard 90.1_commissioning requirements for building
systems, controls, and the building envelope (Section
4.2.5.2 exceptions shall not apply) as applicable to the
scope of work.
REFERENCED STANDARDS
  • ANSI/ASHRAE/IES Standard 90.1 commissioning requirements for building systems, controls, and the building envelope, with the following additional provisions

    • The referenced version with errata shall be:

o 2019 for projects registered prior to January 1, 2028,

(store.accuristech.com/ashrae/standards/ashrae-90-1-2019-i- p?product_id=2088527)

o 2022 for projects registered on or after January 1, 2028,

(store.accuristech.com/ashrae/standards/ashrae-90-1-2022-i- p?product_id=2522082)

U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 128