855773520-LEED-v5-ID-C-Reference-Guide-Launch-Edition-1 - Page 140

Extracted Content

Energy and Atmosphere Prerequisite

ENERGY METERING AND REPORTING

EAp4

REQUIRED

INTENT

To support energy management practices and facilitate identification of ongoing opportunities for energy and GHG emissions savings by tracking and reporting building energy use and demand.

REQUIREMENTS
Achievement pathwaysPoints

Commercial Interiors

N/A

Energy Monitoring and Recording

AND

AND

Report Energy Data

Report Energy Data

This prerequisite applies only to project scope including at least 1 of the following:

  • An initial fit-out of project with gross area of at least 10,000 square feet (929 square meters).

  • An alteration replacing electric power distribution for project with gross area of at least 10,000 square feet (929 square meters).

  • New service for electricity, fuel, or thermal energy supplied directly to the tenant by a utility, energy provider, or plant that is not in the building.

  • New on-site renewable energy.

Energy monitoring and recording For initial fit-out of interior spaces with gross area of at least 10,000 square feet (929 square meter), install (or use existing) measurement devices to monitor and record tenant energy use per ANSI/ASHRAE/IES Standard 90.1 .

The referenced version of Standard 90.1 with errata shall be:

o 2019 or later for projects registered before January 1, 2028.

o 2022 or later for projects registered on or after January 1, 2028.

For initial fit-out of interior spaces fewer than 10,000 square feet (929 square meters), or for all alterations replacing electrical power distribution or providing new energy service directly to the

U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 129