855773520-LEED-v5-ID-C-Reference-Guide-Launch-Edition-1 - Page 142

Extracted Content

Table 1. Summary of LEED v5 EAp4: Energy Metering and Reporting Requirements

Col1Alterations of
spaces in
existing buildings
Initial buildout or addition >=
10,000 sq. ft.
Col4

Alterations of
spaces in
existing buildings

Applicability or
recording
frequency
Referenced
90.1 Sections
or
LEED-specific
MONITORING
(excludes shared base building energy)





New energy service supplied directly to
the project space. Total energy by
energy source for:
•
Natural gas
•
Fuel oil
•
Propane
•
District CHW
•
District steam
•
District hot water
Monthly
Monthly
90.1-2019
10.4.6.1
90.1-2022
10.4.7.1


Total electricity for project space
Monthly
(For new service,
or alteration
replacing electric
power distribution)
15-minute
90.1-2019
8.4.3.1
90.1-2022
8.4.3.1
Submetered electricity for project
space (except residential dwelling
units):
•
HVAC
•
Interior lighting
•
Exterior lighting
•
Receptacle circuits
•
Refrigeration systems (90.1-
2022)

N/A
15-minute
90.1-2019
8.4.3.1
90.1-2022
8.4.3.1

On-site renewable electricity in project
scope.
Monthly
15-minute
LEED-Specific

REPORTING



For metered data, commit to annually
sharing monthly data with USGBC for:
•
Energy consumption by energy
source
•
On-site renewable energy
generation
•
Peak electrical demand.
X
X
LEED-Specific


Capable of creating user reports for
consumption and demand at least
hourly, daily, monthly, and annually,
with system capable of maintaining all
data collected for 36 months.
X90.1-2019
10.4.6.2 90.1-
2022 10.7.4.2

U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 131