| ASHRAE 90.1-2022, Section 11 credits | Points |
|---|---|
Minimum required by 90.1-2022 plus 38 credits | 3 |
| Minimum required by 90.1-2022 plus 50 credits | 4 |
AND/OR
PATH 3. PLUG AND PROCESS LOADS (1–5 POINTS)
Case 1. Plug Load Management (1 point)
Implement the following:
-
Provide a plug load dashboard that is accessible through an application to all regular occupants of the space.
-
For tenant types with IT departments, implement policies for PCs, monitors, and visual displays to be controlled off when not in use, except scheduled maintenance periods.
AND/OR
Case 2. Efficient Plug and Process Load Equipment (1–5 points)
Implement one or more of the following:
-
Install or reuse eligible plug and process equipment meeting the criteria in Table 3 for 90% of applicable equipment by quantity or rated load. Either include or exclude all eligible equipment reused in the project from the calculations. For one Table 3 equipment category (1 point)
-
For two Table 3 equipment categories (2 points)
-
For three or more Table 3 equipment categories (3 points)
OR
For process-intensive spaces, install or reuse eligible plug and process equipment meeting the criteria in Table 3 for at least 90% of total applicable equipment rated load. Rated load of compliant equipment must total at least:
-
0.3 W/sq. ft. (3.2 W/sq. m.) (3 points)
-
0.5 W/sq. ft. (5.4 W/sq. m.) (4 points)
-
1.0 W/sq. ft. (10.8 W/sq. m.) (5 points)
Table 3. Plug, process, refrigeration, and conveyance equipment criteria
| Equipment category | Applicable equipment | Criteria |
|---|---|---|
ENERGY STAR® products: plug | Office equipment Appliances Electronics | ENERGY STAR® rated or approved equivalent with at |