855773520-LEED-v5-ID-C-Reference-Guide-Launch-Edition-1 - Page 175

Extracted Content

Equipment
category
Applicable equipmentCriteria

loads and small
appliances
Other
(e.g., vending machines, pool
pumps, water coolers)
least 0.1 W/sq. ft. (1.1 W/sq.
m.) of total rated load
ENERGY STAR®
products: process
loads

Commercial food service equipment
Data center/server equipment
Commercial laundry equipment
Electric vehicle chargers (EVSE)
Other (e.g., laboratory-grade
refrigerators and freezers)
ENERGY STAR® rated or
approved equivalent with at
least 0.1 W/sq. ft. (1.1 W/sq.
m.) of total rated load
People conveyance

Elevators
Escalators
Moving walkways
ISO 25745
At least Class A-rated
Data center
electrical system

Electrical system design
ASHRAE 90.4-2022
Design electrical loss
component (ELC) is at least
20% lower than the maximum
design electrical loss
Refrigeration
systems
Referenced in_ASHRAE_ 90.1,
Section 6.8, tables AND not
ENERGY STAR®® eligible

10% improvement beyond
ASHRAE 90.1, Section 6.8,
tables
Refrigeration
systems

Refrigerated warehouse

California Title 24-2022,
Section 120.6, refrigerated
warehouse requirements
Airport equipmentBaggage handling equipment

Individual carrier systems
(ICS) with variable frequency
drive
Airport equipmentAircraft and jetway air-conditioning
Preconditioned air (PCA)
systems with efficiencies
meeting_ASHRAE 90.1_
prescriptive efficiencies for
HVAC equipment

OR

Case 3. Plug and Process Load Exceptional Calculation (1–5 points)

Using the ASHRAE 90.1, Section G2.5, exceptional calculation method, demonstrate a minimum percentage improvement in total project plug and process, refrigeration, and conveyance loads. Points are awarded according to Table 4 below.

Table 4. Points for percent improvement in plug and process loads

Percent improvementPoints
8%
1

16%

2

24%

3

32%

4

40%

5

U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 164