855773520-LEED-v5-ID-C-Reference-Guide-Launch-Edition-1 - Page 176
Extracted Content
PATH 4. BASE BUILDING ENERGY EFFICIENCY (2 POINTS)
Locate in a base building that complies with one of the following:
-
ASHRAE 90.1-2022
-
Current ENERGY STAR® score of at least 75
-
LEED base building documentation of energy efficiency per Table 5
Table 5. LEED base building documentation of energy efficiency
| Interior fit-out classification | LEED Base Building Documentation of Energy Efficiency | Col3 | Col4 |
|---|---|---|---|
| Interior fit-out classification | Rating system(s) | EA credit name and credit option | Base building minimum threshold |
| Initial build-out | LEED v5 BD+C | EAc3: Enhanced Energy Efficiency | 5 points |
| Alterations of previously occupied space | LEED v5 O+M | EAc2: Optimized Energy Performance | 5 points |
Initial build-out | LEED v4 or LEED v4.1 BD+C | EAc2: Optimized Energy Performance | 8 points |
OR
Option 2. Energy Simulation (1–12 points)
Demonstrate an improvement in future source energy calculated per ASHRAE Standard 90.1, Normative Appendix G, “Performance Rating Method,” with the following additional provisions:
-
Use the ASHRAE 90.1 version applied for EAp2: Minimum Energy Efficiency .
-
Replace ASHRAE 90.1-2019 or 90.1-2022, Table 4.2.1.1, BPFs , with Table 7 below. For alterations except initial build-out construction, the following ASHRAE 90.1-2022 adjustments may be applied:
o Substantial alteration . Multiply the BPF by 1.05 if the alteration is defined as a
substantial alteration in ASHRAE 90.1-2022, Section G3.1.4(a).
o Other alterations . Apply ASHRAE 90.1-2022, Section G3.3 (“Performance
Calculations for Other Alterations”). For projects documented using ASHRAE 90.1-2019, Appendix G, replace all references to 90.1-2022, Section 5–10, prescriptive criteria with the corresponding 90.1-2019, Section 5–10 criteria.
-
Replace all references to “cost” with “future source energy.” Use an electric site-tosource energy conversion factor of 2.0 based on future projections for the U.S. A lower national average value may be used as applicable for projects outside of the U.S.
-
Model energy efficiency measures for plug and process loads using Section G2.5, “Exceptional Calculation Method,” or approved calculations in the LEED reference
U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 165