No further adjustments are required to a BBP model with purchased heat and purchased CHW documented per ASHRAE 90.1-2022, Addendum A in EAp2: Minimum Energy Efficiency .

Combined heat and power (CHP) To limit undue credit for site-recovered energy from CHP with on-site combustion emissions, projects must model CHP systems using one of the following methods instead of ASHRAE 90.1 G2.4.2.1:

  • CHP in baseline and proposed . Model CHP systems including all fuel inputs and associated site-recovered energy identically in the baseline design and the proposed design.

  • Purchased electricity in baseline and proposed . Model purchased electricity instead of the on-site electricity generation. Either credit site-recovered energy from the CHP toward the thermal loads for the baseline and proposed design identically; or ignore the site-recovered energy contribution in the baseline and proposed design).

  • CHP in proposed and purchased electricity in baseline . Model CHP systems including all fuel inputs and associated site-recovered energy in the proposed design. Model the baseline design per ASHRAE 90.1 with purchased electricity and with no credit for site-recovered energy.

DOCUMENTATION
Project types AllOptions AllPaths AllDocumentation Demonstrate compliance with EAp2: Minimum

All
All
All
Demonstrate compliance with_EAp2: Minimum_
Energy Efficiency.

All
Option 1Path 1

Demonstrate compliance with_EAp2: Minimum_
Energy Efficiency ASHRAE 90.1-2022, Sections 5–
11.

All
Option 1Path 2: Case
1

Upload calculator to demonstrate compliance.

All
Option 1
Path 2: Case
2
Upload calculator to demonstrate compliance.

All
Option 1
Path 3: Case
1
Demonstrate compliance that plug load dashboard
has been supplied and meets requirements.
Examples include screenshots of dashboard, photos,
specifications etc.

All
Option 1
Path 3: Case
1

Provide documentation and/or IT policy.

All
Option 1Path 3: Case
2
Provide documentation installed equipment meets
criteria in Table 3

All
Option 1
Path 3: Case
3

Upload plug and process load exceptional calculation
and associated documentation.

All
Option 1
Path 4

ENERGY STAR® certificate; Comcheck or other
approved method showing compliance with_ASHRAE_
90.1 2022 or LEED credits.