Indoor Environmental Quality Credit
ENHANCED AIR QUALITY
EQc1
1–2 points
INTENT
To design for increased indoor air quality (IAQ) to better protect the health of building occupants.
REQUIREMENTS
| Achievement pathways | Points |
|---|---|
Commercial Interiors | 1–2 |
Option 1. Increased Ventilation | 2 |
OR | |
Option 2. Enhanced Indoor Air Quality Design | 1 |
OR | |
Option 3. Verification of Ventilation and Filtration | 1 |
Design the project to exceed the requirements of ASHRAE 62.1-2022, Section 6. If using the ventilation rate procedure to comply with EQp2: Fundamental Air Quality, use Option 1 or Option 2; if using the indoor air quality procedure (IAQP), use Option 2.
Option 1. Increased Ventilation (2 points)
Increase breathing zone outdoor air ventilation rates by at least 15% above the minimum rates (for 1 point, or 30% for 2 points) as determined in EQp2: Fundamental Air Quality .
Increased outdoor air rates should be provided to 95% of all regularly occupied spaces.
OR
Option 2. Enhanced Indoor Air Quality Design (1 point)
In addition to the design compounds and design limits outlined in ASHRAE 62.1-2022, Tables 65 and 6-6, design and verify enhanced IAQ using the lower design limits listed below in Table 1.
Table 1. Additional design limits for enhanced IA Q design
| Design compound or PM2.5 | Enhanced IAQP design limit* |
|---|---|
PM2.5 | 10 ug/m3 |
Formaldehyde | 20 µg/m³ |
Ozone | 10 ppb |
U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 308