855773520-LEED-v5-ID-C-Reference-Guide-Launch-Edition-1 - Page 357

Extracted Content

Indoor Environmental Quality Credit

AIR QUALITY TESTING AND MONITORING

EQc5

1–4 points

INTENT

To support better management of IAQ and identify opportunities for health-based approaches to building operations.

REQUIREMENTS
Achievement pathwaysPoints

Commercial Interiors

1–4

Option 1. Preoccupancy Air Testing

1–2

Path 1. Particulate Matter and Inorganic Gases

1

AND/OR


Path 2. Volatile Organic Compounds
1

AND/OR



Option 2. Continuous Indoor Air Monitoring

1

Option 1. Preoccupancy Air Testing (1–2 points)

After construction ends and before occupancy, but under ventilation conditions typical for occupancy, conduct baseline IAQ testing. Retail projects may conduct the testing within 14 days of occupancy. The number of measurements should be specified according to Table 1 and taken in respective locations of the building.

Table 1. Number of measurements required for preoccupancy air testing

Total occupied floor area, sq. ft (sq. m.)Number of measurements
≤ 5,000 (500)1
> 5,000 (500) and ≤ 15,000 (1,500)2
> 15,000 (1,500) and ≤ 25,000 (2,500)3
> 25,000 (2,500) and ≤ 200,000 (20,000)4 plus one additional measurement per
each 25,000 sq. ft. (2,500 sq. m.) above
25,000 sq. ft.

U.S. Green Building Council LEED v5 Reference Guide for Interior Design and Construction, April 2025 Launch Edition 346