Table 3. Volatile organic compound limits

Contaminant (CAS#)Concentration limit
(µg/m3)
Allowed test methods
Formaldehyde 50-00-020 µg/m3 (16 ppb)ISO 16000-3, 4;
EPA TO-11a;
EPA comp. IP-6A;
ASTM D5197-16
Acetaldehyde 75-07-0140 µg/m3140 µg/m3
Benzene 71-43-23 µg/m3ISO 16000-6;
EPA IP-1;
EPA TO-17;
EPA TO-15;
ISO 16017-1, 2;
ASTM D6196-15
Hexane (n-) 110-54-37,000 µg/m37,000 µg/m3
Naphthalene 91-20-39 µg/m39 µg/m3
Phenol 108-95-2200 µg/m3200 µg/m3
Styrene 100-42-5900 µg/m3900 µg/m3
Tetrachloroethylene 127-18-435 µg/m335 µg/m3
Toluene 108-88-3300 µg/m3300 µg/m3
Vinyl acetate 108-05-4200 µg/m3200 µg/m3
Dichlorobenzene (1,4-) 106-46-7800 µg/m3800 µg/m3
Xylenes—total 108-38-3, 95-47-
6, and 106-42-3
700 µg/m3700 µg/m3

AND/OR

Option 2. Continuous Indoor Air Monitoring (1 point)

Provide indoor air monitors for all of the following parameters:

  • Carbon dioxide (CO2)

  • Particulate matter (PM2.5)

  • Total volatile organic compounds (TVOC)

  • Temperature

  • Relative humidity

Monitors must be building grade or better and located between 3 and 6 feet (1–2 meters) above the floor.

REQUIREMENTS EXPLAINED

This credit helps the project gain a better understanding of their indoor air.