Monitor specifications Select indoor air monitoring devices that measure carbon dioxide (CO2), fine particulate matter (PM2.5), TVOC , temperature, and relative humidity. Monitors must meet the building grade requirements of RESET Grade B [152] or UL 2095 Grade B.

Hourly reporting Monitors must report hourly (or higher frequency including 15-minute data for CO2) data to a remote location that logs pollutant levels over time.

A digital display, or integration with the BMS, is not required to achieve the credit.

Table 1. RESET Grade B monitor specifications

RESET Grade B
monitor
specifications
CO2PM2.5TVOCTemperatureRelative
humidity

Data loss
10%
10%
10%
10%
10%

Operating range
for Temperature

0-40

0-40

0-40

0-40

0-40

Operating range
for Relative
Humidity

10-80 % RH non-condensing

10-80 % RH non-condensing

10-80 % RH non-condensing

10-80 % RH non-condensing

10-80 % RH non-condensing

Data Output
Interval
5 min





5 min





5 min





5 min





5 min






Sampling type

Active airflow




Sensor Output
Resolution

5 ppm

1 μg/m3

4.4 ppb

0.1

1 % RH

Measuring Range
400-5000
ppm
0-500 μg/m3
65-870 ppb
0-40
10-80 %
RH
Accuracy*

400–2000
ppm : ±50
&& 3%
2000 - 5000 :
±50 && 5%
0 - 150 : ±5
&& 15%
150 - 500 :
±5 && 20%
65–260 ppb :
±8.7 && 15%
260 - 870 :
±8.7 && 20%
±1~~℃~~

±8% RH
Performance
Check and Re-
calibration

Required
RequiredRequiredRequiredRequired

*Example for interpreting the accuracy requirement: If a reference monitor is reading 900 ppm, a Grade B monitor’s reading must read within 50 + (0.03 x 900) = ±77. The Grade B monitor’s reading must be between 823 and 977 ppm

152 RESET Indoor Air Quality Monitors, https://www.reset.build/directory/monitors/type/indoor.