Table 5.5-1 Building Envelope Requirements for Climate Zone 1 (A,B)*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.048 R-20 c.i. U-0.039 R-25 c.i. U-0.218 R-3.8 c.i.

Metal building [ a] U-0.041 R-10 + R-19 FC U-0.041 R-10 + R-19 FC U-0.115 R-10

Attic and other U-0.027 R-38 U-0.027 R-38 U-0.081 R-13

Walls, above Grade

Mass U-0.580 NR U-0.151 [b] R-5.7 c.i. [b] U-0.580 NR

Metal building U-0.094 R-0 + R-9.8 c.i. U-0.094 R-0 + R-9.8 c.i. U-0.352 NR

Steel-framed U-0.124 R-13 U-0.124 R-13 U-0.352 NR

Wood-framed and other U-0.089 R-13 U-0.089 R-13 U-0.292 NR

Wall, below Grade

Below-grade wall C-1.140 NR C-1.140 NR C-1.140 NR

Floors

Mass U-0.322 NR U-0.322 NR U-0.322 NR

Steel joist U-0.350 NR U-0.350 NR U-0.350 NR

Wood-framed and other U-0.282 NR U-0.282 NR U-0.282 NR

Slab-on-Grade Floors

Unheated F-0.730 NR F-0.730 NR F-0.730 NR

Heated F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.700

Nonswinging U-0.310 U-0.310 U-1.450

Assembly

Max. U

Assembly

Max. U

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.50 0.23 1.10 (for all

0.50 0.23 1.10 (for all

types)

1.20 NR (for all types)

NR (for all

Operable 0.62 0.21 types) 0.62 0.21 types) 1.20 types)

types)

Entrance door 0.83 0.21 0.83 0.21 1.10

Skylight, 0% to 3% of Roof

All types 0.70 0.30 NR 0.70 0.30 NR 1.80 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2). b. Exception to Section 5.5.3.2 applies for mass walls above grade .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 49