ASHRAE-90.1-2022- - Full Extract

PDF Page 1

Open page note

ANSI/ASHRAE/IES Standard 90.1-2022

(Supersedes ANSI/ASHRAE/IES Standard 90.1-2019) Includes ANSI/ASHRAE/IES addenda listed in Appendix M

Energy Standard for Sites and Buildings

Except Low-Rise Residential Buildings

(I-P Edition)

See Informative Appendix M for dates of approval by ASHRAE, the Illuminating Engineering Society, and the American National Standards Institute.

This Standard is under continuous maintenance by a Standing Standard Project Committee (SSPC) for which the Standards Committee has established a documented program for regular publication of addenda or revisions, including procedures for timely, documented, consensus action on requests for change to any part of the Standard. Instructions for how to submit a change can be found on the ASHRAE [®] website (www.ashrae.org/continuous-maintenance).

The latest edition of an ASHRAE Standard may be purchased from the ASHRAE website (www.ashrae.org) or from ASHRAE Customer Service, 180 Technology Parkway, Peachtree Corners, GA 30092. E-mail: orders@ashrae.org. Fax: 678-539-2129. Telephone: 404-636-8400 (worldwide), or toll free 1-800-527-4723 (for orders in US and Canada). For reprint permission, go to www.ashrae.org/permissions.

© 2022 ASHRAE ISSN 1041-2336

PDF Page 2

Open page note

ASHRAE Standard Project Committee 90.1 (2019–2022)

Cognizant TC: 7.6 Systems Energy Utilization SPLS Liaison: Jennifer Isenbeck · ASHRAE Staff Liaison: Emily Toto · IES Liaison: Mark Lien

Donald Brundage, Chair Phillip Gentry Andrew Klein Loren Ross Thomas Culp, Co-Vice Chair Jason Glazer Vladimir Kochkin Robert Ross Richard Lord, Co-Vice Chair Melissa Goren Michael Lane Marty Salzberg Rahul Athalye Krishnan Gowri Toby Lau Christopher Schaffner William Babbington Patricia Graef Chonghui Liu Greg Schluterman John Bade Mark Graham Emily Lorenz Amy Schmidt Sean Beilman Aaron Gunzner Joel Martell Leonard Sciarra Kyle Bergeron Pekka Hakkarainen Samuel Mason Kelly Seeger Jeffrey Boldt David Handwork Christopher Mathis Sean Smith Joseph Brooks Armin Hauer Merle McBride Wayne Stoppelmoor Scott Campbell Rick Heiden James McClendon Matthew Swenka Elizabeth Cassin Gary Heikkinen Benjamin Meyer Christian Taber Paula Cino Mark Heizer Darren Meyers William Talbert Glen Clapper David Herron Harry Misuriello Steven Taylor Ernest Conrad Scott Hintz James (Mike) Moore Michael Tillou Shannon Corcoran Emily Hoffman Frank Morrison Douglas Tucker Charles Cottrell Mike Houston Michael Myer Jason Vandever Jay Crandell Jonathan Humble Frank Myers Martha VanGeem Brandon Damas Michael Ivanovich Michael Patterson Michael Waite Julie Donovan Harold Jepsen Timothy Peglow McHenry Wallace Craig Drumheller Chad Johnson Tien Peng Helen Walter-Terrinoni John Dunlap Greg Johnson Christopher Perry Richard Watson James Earley Duane Jonlin Laura Petrillo-Groh Jerry White Drake Erbe Michael Jouaneh Catherine Rivest Jeremiah Williams D. Andrew Fouss Hyman Kaplan Michael Rosenberg Amber Wood Sam Francis Maria Karpman Steven Rosenstock

ASHRAE STANDARDS COMMITTEE 2022–2023

Susanna S. Hanson, Chair Phillip A. Johnson Lawrence C. Markel Christopher J. Seeton Jonathan Humble, Vice-Chair Srinivas Katipamula Patrick C. Marks Christian R. Taber William P. Bahnfleth Gerald J. Kettler Margaret M. Mathison Paolo M. Tronville Thomas E. Cappellin Jay A. Kohler Kathleen Owen William F. Walter Douglas D. Fick Cesar L. Lim Gwelen Paliaga Steven C. Sill, BOD ExO Patricia Graef Paul A. Lindahl, Jr. Karl L. Peterman Sarah E. Maston, CO Jaap Hogeling James D. Lutz Justin M. Prosser Jennifer A. Isenbeck Julie Majurin David Robin

Connor Barbaree, Senior Manager of Standards

SPECIAL NOTE This American National Standard (ANS) is a national voluntary consensus Standard developed under the auspices of ASHRAE. Consensus is defined by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved this Standard as an ANS, as “substantial agreement reached by directly and materially affected interest categories. This signifies the concurrence of more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.” Compliance with this Standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation.

ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review. ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project Committees.

The Senior Manager of Standards of ASHRAE should be contacted for

a. interpretation of the contents of this Standard, b. participation in the next review of the Standard, c. offering constructive criticism for improving the Standard, or d. permission to reprint portions of the Standard.

DISCLAIMER ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components, or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its Standards or Guidelines will be nonhazardous or free from risk.

ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method of testing for rating purposes, by suggesting safe practices in designing and installing equipment, by providing proper definitions of this equipment, and by providing other information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by the need for them, and conformance to them is completely voluntary. In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or implied, that the product has been approved by ASHRAE.

PDF Page 3

Open page note

CONTENTS

ANSI/ASHRAE/IES Standard 90.1-2022 Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings (I-P Edition)

SECTION PAGE

Foreword …2

1 Purpose…3

2 Scope…3

3 Definitions, Abbreviations, and Acronyms…4

4 Administration and Enforcement…36

5 Building Envelope …42

6 Heating, Ventilating, and Air Conditioning…71

7 Service Water Heating …137

8 Power…144

9 Lighting…148

10 Other Equipment …172

11 Additional Efficiency Requirements…181

12 Energy Cost Budget Method …208

13 Normative References…223

Normative Appendix A: Rated R-Value of Insulation and Assembly U-Factor, C-Factor, and

F-Factor Determinations …229

Informative Appendix B: (Retained for Future Use) …282

Normative Appendix C: Methodology for Building Envelope Trade-Off Option in Section 5.6…283

Informative Appendix D: (Retained for Future Use) …290

Informative Appendix E: Informative References…291

Informative Appendix F: U.S. Department of Energy Minimum Energy Efficiency Requirements,

Test Procedures, and Definitions…295

Normative Appendix G: Performance Rating Method …301

Informative Appendix H: Additional Guidance for Verification, Testing, and Commissioning …345

Informative Appendix I: Using Other Metrics in Conjunction with 

Appendix G Performance Rating Method when Approved by the Rating Authority…354

Normative Appendix J: Sets of Performance Curves…360

Informative Appendix K: Informative Figures—Thermal Bridges …367

Normative Appendix L: Mechanical System Performance Rating Method…372

Informative Appendix M: Addenda Description …393

Annex 1: Reference Standard Reproduction—ASHRAE Standard 169…399

NOTE

Approved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAE website at www.ashrae.org/technology.

© 2022 ASHRAE 180 Technology Parkway NW · Peachtree Corners, GA 30092 · www.ashrae.org · All rights reserved. ASHRAE is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

ANSI is a registered trademark of the American National Standards Institute.

PDF Page 4

Open page note

(This foreword is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI require- ments for a standard and may contain material that has not been subject to public review or a consen- sus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

FOREWORD

The 2022 edition of Standard 90.1 incorporates more than 80 addenda to the 2019 edition and includes numerous energy-saving measures. Notable changes include the following:

General

includes exceptions for small buildings, buildings with limited roof space, and other situations where PV installations would be problematic.

It should be noted that, due to the addition of a new section and several appendices, the number or letter designations of several well-known sections and appendices have changed from those used in the 2019 and previous editions of the standard.

Administration and Enforcement

There were no major changes to administration and enforcement.

Requirements were added that address the impacts of thermal bridges in building envelopes, with a new Informative Appendix K providing supplemental information on application.

A solar reflectance requirement for walls was added for Climate Zone 0. This is similar to the require- ments for high albedo roofs.

Specific provisions were added to distinguish roof replacements from other types of alterations.

A ne w reference was added for steel-framed walls to allow use of ANSI /AISI S250 for U-factor determi- nation.

Added a definition for insulated metal panels (IMPs).

Normative Appendix A was reformatted to clarify the requirements for thermal performance calculations.

Lighting and Power

Reorganized Section 9, “Lighting,” to be more consistent with the structure of other main sections of the standard.

Updated installed interior lighting power allowances and minimum control requirements; added a power exception for the germicidal function in luminaires and sources; and removed exceptions for casinos and parking garage daylight transition zone lighting.

Modified a number of lighting requirements to reflect greater use of higher efficiency LED products and revised lighting practices.

Added requirements for indoor horticultural lighting in greenhouses and indoor grow buildings based on a new metric, photosynthetic photon efficacy (PPE), developed in ANSI/ASABE S640.

Provided an additional interior lighting power allowance for video conferencing. Power allowances and controls have been moved to a table for ease of reference.

2 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 5

Open page note

Mechanical

Introduced an optional Mechanical System Performance Path that allows HVAC system efficiency trade- offs based on a new metric, total system performance ratio (TSPR).

Required condensing boilers for new construction in order to achieve 90% or greater efficiency for large boilers (1 to 10 million Btuh. The thermal efficiency requirements for high-capacity gas-fired service water-heating equipment were also increased.

Established a minimum enthalpy recovery ratio for energy recovery systems and specified operational requirements to ensure proper economized performance.

Revised demand control ventilation requirements to be based on climate zone and Standard 62.1 airflow requirements.

Modified the minimum efficiency requirements for air-source heat pumps and introduced a new metric, COPHR, for units that perform heat recovery during chiller operation.

Added the minimum energy efficiency requirements (and new CFEI metric) for large-diameter ceiling fans from 10 CFR 430.

Performance Rating Method (Appendix G)

New requirements were added to limit trade-offs between the building envelope and other building systems.

A new Informative Appendix I was added that provides information on how alternative performance met- rics other than cost could be used with the Performance Rating Method. These alternative metrics include site energy, source energy, and carbon emissions, and would be useful to assess building performance against carbon emission goals or for similar types of comparison.

A relaxation in stringency was added when using Normative Appendix G for retrofit projects consisting of substantial alterations.

Both Performance-Based Compliance Paths(Section 12 [Energy Cost Budget Method] and Appendix G)

Numerous changes were included to improve clarity and coordinate with revisions to other sections of the standard.

New Normative Appendix J

Contains performance curves that represent minimally compliant chiller performance for the budget and baseline building design and for proposed building designs when specific equipment performance is not known.

  1. PURPOSE + 2. SCOPE: NOT ADOPTED BY OREGON PER 2024 OEESC E102.3.2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 3

THEREFORE 3 STORY MULTIFAMILY IS UNDER THIS CODE?

1

PDF Page 6

Open page note

2.2 The provisions of this standard do not apply to

a. single-family houses and related incidental structures, multifamily structures of three stories or fewer

above grade, manufactured houses (mobile homes), and manufactured houses (modular) or b. buildings that use neither electricity nor fossil fuel .

2.3 Where specifically noted in this standard, certain other buildings or elements of buildings or sites shall be exempt.

2.4 This standard shall not be used to circumvent any safety, health, or environmental requirements.

3. DEFINITIONS, ABBREVIATIONS, AND ACRONYMS

3.1 General. Certain terms, abbreviations, and acronyms are defined in this section for the purposes of this standard. When the tense or plurality of the term is different than the defined term, the definition still applies. These definitions are applicable to all sections of this standard, wherever italicized . Terms that are not italicized shall have their ordinarily accepted meanings within the context in which they are used. Ordinarily accepted meanings shall be based on American standard English language usage as documented in an unabridged dictionary accepted by the adopting authority .

3.2 Definitions

above-grade wall: see wall .

access hatch: see door .

addition: an extension or increase in floor area or height of a building outside of the existing building enve- lope or the equipment or systems to a site .

adopting authority: the agency or agent that adopts this standard.

air economizer: see economizer, air .

air leakage: the uncontrolled airflow through the building envelope caused by pressure differences across the building envelope due to factors such as wind, inside and outside temperature differences, stack effect, and imbalance between supply and exhaust air systems . Air leakage can move inward (infiltration) or outward (exfiltration) through the building envelope .

air system balancing: see balancing, air system .

alteration: replacing or adding to systems, equipment, structures, or building assemblies; routine maintenance, repair, and service, or a change in the building or structure use classification or space conditioning category shall not constitute an alteration .

annual fuel utilization efficiency (AFUE): an efficiency descriptor of the ratio of annual output energy to annual input energy as developed in accordance with the requirements of U.S. Department of Energy (DOE) 10 CFR Part 430.

attic and other roofs: see roof .

authority having jurisdiction: the agency or agent responsible for enforcing this standard.

automatic or automatically: self-acting, operating by its own mechanism when actuated by some nonmanual influence, such as a change in current strength, pressure, temperature, or mechanical configuration.

automatic control device: a device capable of automatically turning loads off and on without manual intervention.

balancing, air system: adjusting airflow rates through air distribution system devices, such as fans and diffusers, by manually adjusting the position of dampers, splitter vanes, extractors, etc., or by using automatic control devices such as constant-air-volume or variable-air-volume (VAV) boxes.

balancing, hydronic system: adjusting water flow rates through hydronic distribution system devices, such as pumps and coils, by manually adjusting the position valves or by using automatic control devices such as automatic flow control valves.

ballast: a device used in conjunction with an electric-discharge lamp to cause the lamp to start and operate under the proper circuit conditions of voltage, current, wave form, electrode heat, etc.

baseline building design: a computer representation of a hypothetical design based on the proposed design . This representation is used as the basis for calculating the baseline building performance for rating abovestandard design or when using the Performance Rating Method as an alternative path for minimum standard compliance in accordance with Section 4.2.1.1.

4 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 7

Open page note

baseline building performance: the annual energy cost for a building design intended for use as a baseline for rating above-standard design or when using the Performance Rating Method as an alternative path for minimum standard compliance in accordance with Section 4.2.1.1.

below-grade wall: see wall .

best efficiency point (BEP): the pump hydraulic power operating point (consisting of both flow and head conditions) that results in the maximum efficiency .

boiler: a self-contained, low-pressure appliance for supplying steam or hot water.

modulating boiler: a boiler that is capable of more than a single firing rate in response to a varying temperature or heating load. packaged boiler: a boiler that is shipped complete with heating equipment, mechanical draft equipment, and automatic controls, and that is usually shipped in one or more sections. A packaged boiler includes factory-built boilers manufactured as a unit or system, disassembled for shipment, and reassembled at the site .

boiler system: one or more boilers and their piping and controls that work together to supply steam or hot water to heat output devices remote from the boiler .

branch circuit: the circuit conductors between the final overcurrent device protecting the circuit and the outlets; the final wiring run to the load.

bubble point: the refrigerant liquid saturation temperature at a specified pressure.

budget building design: a computer representation of a hypothetical design based on the actual proposed design . This representation is used as the basis for calculating the energy cost budget .

building: any structure used or intended for supporting or sheltering any use or occupancy.

building entrance: any doorway, set of doors, revolving door, vestibule, or other form of portal that is ordinarily used to gain access to the building or to exit from the building by its users and occupants. This does not include doors solely used to directly enter mechanical, electrical, and other building utility service equipment rooms.

building envelope: the exterior plus the semiexterior portions of a building . For the purposes of determining building envelope requirements, the classifications are defined as follows:

exterior building envelope: the elements of a building that separate conditioned spaces from the exterior. semiexterior building envelope: the elements of a building that separate conditioned space from uncon- ditioned space or that enclose semiheated spaces through which thermal energy may be transferred to or from the exterior, to or from unconditioned spaces, or to or from conditioned spaces .

building envelope trade-off schedules and loads: the schedules and internal loads [1], by building area type, to be used in the building envelope trade-off option simulations described in Normative Appendix C.

building material: any element of the building envelope, other than air films and insulation, through which heat flows and that is included in the component U-factor calculations.

building official: the officer or other designated authority having jurisdiction charged with the administration and enforcement of this standard, or a duly authorized representative.

building service: the equipment for delivering energy from the supply or distribution system to the premises served.

building service equipment: the necessary equipment, usually consisting of a circuit breaker or switch and fuses and accessories, located near the point of entrance of supply conductors to a building or other structure (or an otherwise defined area) and intended to constitute the main control and means of cutoff of the supply. Service equipment may consist of circuit breakers or fused switches provided to disconnect all undergrounded conductors in a building or other structure from the service-entrance conductors.

C-factor: see thermal conductance .

ceiling fan: a nonportable ( permanently installed ) device suspended from a ceiling or overhead structure for circulating air via the rotation of fan blades.

ceiling fan energy index (CFEI): the ratio of the electric input power of a reference ceiling fan to the electric input power of the actual ceiling fan as calculated per AMCA 208 with the following modifications to

  1. Schedules and internal loads by building area type are at https://web.ashrae.org/90_1files.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 5

PDF Page 8

Open page note

the calculations for the reference fan: using an airflow constant ( Q 0) of 26,500 cfm, a pressure constant ( P 0) of 0.002700 in. of water, and a fan efficiency constant (η0) of 42%.

ceiling fan, large diameter: a ceiling fan that is greater than or equal to 84.5 in. in diameter.

chi-factor (χ or Chi): thermal transmittance of a point thermal bridge in units of Btu/(h·°F).

circuit breaker: a device designed to open and close a circuit by nonautomatic means and to open the circuit automatically at a predetermined overcurrent without damage to itself when properly applied within its rating.

class of construction: for the building envelope, a subcategory of roof, above-grade wall, below-grade wall, floor, slab-on-grade floor, opaque door, vertical fenestration, or skylight . (See roof, wall, floor, slab-on- grade floor, door, and fenestration .)

clear-field thermal bridge: see thermal bridge.

code official: see building official.

coefficient of performance (COPH), heat pump—heating: the ratio of the rate of heat delivered to the rate of energy input, in consistent units, for a complete heat-pump system, including the compressor and, if applicable, auxiliary heat, under designated operating conditions.

combined energy efficiency ratio (CEER): a ratio of the total cooling one year divided by the total energy from active, standby, and OFF modes as specified in 10 CFR 430.23.

commissioning: a quality-focused process for enhancing the delivery of a project for verifying and documenting that the building and its systems, controls, and building envelope are planned, designed, installed, tested, and include plans for operation and maintenance to meet specified requirements.

commissioning provider: an entity who manages the commissioning team to implement building commis- sioning .

computer room: a room whose primary function is to house equipment for the processing and storage of electronic data and that has a design electronic data equipment power density exceeding 20 W/ft [2] of conditioned floor area.

computer room energy: annual energy use of the data center, including all IT equipment energy, plus energy that supports the IT equipment and computer room space, calculated in accordance with industry-accepted standards defined as Total Annual Energy (see Informative Appendix E).

condensing unit: a factory-made assembly of refrigeration components designed to compress and liquefy a specific refrigerant. It consists of one or more refrigerant compressors, refrigerant condensers (air-cooled, evaporatively cooled, and/or water-cooled), condenser fans and motors (where used), and factory-supplied accessories.

conditioned floor area, gross: see floor area, gross .

conditioned space: see space.

construction: the fabrication and erection of a new building or any addition to or alteration of an existing building .

construction documents: drawings and specifications used to construct, add to, or alter building s, systems, or equipment, or portions thereof.

continuous air barrier: the combination of interconnected materials, assemblies, and sealed joints and components of the building envelope that minimize air leakage into or out of the building envelope .

continuous daylight dimming: method of automatic lighting control using daylight photosensors, where the lights are dimmed continuously, or using at least four preset levels with at least a five-second fade between levels, where the control turns the lights off when sufficient daylight is available.

continuous dimming: a lighting control strategy that varies the light output of a lighting system over a continuous range from full light output to a minimum light output in imperceptible steps without flickering.

control: to regulate the operation of equipment . ( Informative Note: This definition is not applicable to the use of this word as a noun to describe a combination of control devices and software, used to achieve control of HVAC, lighting, or other equipment or systems .)

control device: a specialized device used to regulate the operation of equipment .

6 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 9

Open page note

cooldown: reduction of space temperature down to occupied set point after a period of shutdown or setup.

cooled space: see space, conditioned space .

cooling degree-day, base (CDD): see degree-day.

cooling design temperature: the outdoor dry-bulb temperature equal to the temperature that is exceeded by 1% of the number of hours during a typical weather year.

critical circuit: the hydronic circuit that determines the minimum differential pressure that the pump must produce to satisfy the zone loads (e.g., the circuit with the most-open valve). The critical circuit is the one with the highest pressure drop required to satisfy its load. At part-load conditions, the critical circuit can change based on zone loads.

daylight area: the floor area substantially illuminated by daylight.

daylight area under roof monitors: the daylight area under roof monitors is the combined daylight area under each roof monitor within each space . The daylight area under each roof monitor is the product of

a. the width of the vertical fenestration above the ceiling level plus, on each side, the smallest of

  1. 2 ft,
  2. the distance to any 5 ft or higher vertical obstruction, or
  3. the distance to the edge of any primary sidelighted area and b. the smaller of the following horizontal distances inward from the bottom edge of the vertical fenes-

tration (see Figure 3.2-1):

  1. The monitor sill height (MSH) (the vertical distance from the floor to the bottom edge of the monitor glazing)
  2. The distance to the nearest face of any opaque vertical obstruction, where any part of the obstruction is farther away than the difference between the height of the obstruction and the monitor sill height (MSH – OH) daylight area under skylights: the daylight area under skylights is the combined daylight area under each skylight within a space . The daylight area under each skylight is bounded by the opening beneath the skylight and horizontally in each direction (see Figure 3.2-2), the smaller of

a. 70% of the ceiling height (0.7 × CH) or b. the distance to the nearest face of any opaque vertical obstruction, where any part of the obstruction

is farther away than 70% of the distance between the top of the obstruction and the ceiling (0.7 ×

[CH – OH], where CH = the height of the ceiling at the lowest edge of the skylight, and OH = the height to the top of the obstruction). daylight area under skylights in multistory spaces: the daylight area under skylights in multistory spaces shall include floor areas directly beneath the skylight and portions of the uppermost floor adjacent to the multistory space that meet the criteria for a daylight area under skylights, where CH is the ceiling height of the uppermost floor (see Figure 3.2-3). primary sidelighted area: the total primary sidelighted area is the combined primary sidelighted area within each space . Each primary sidelighted area is directly adjacent to vertical fenestration in an exterior wall below the ceiling (see Figure 3.2-4).

a. The primary sidelighted area width is the width of the vertical fenestration plus, on each side, the

smaller of

  1. one half of the vertical fenestration head height (where head height is the distance from the floor to the top of the glazing) or
  2. the distance to any 5 ft or higher opaque vertical obstruction. b. The primary sidelighted area depth is the horizontal distance perpendicular to the vertical fenes-

tration, which is the smaller of

  1. one vertical fenestration head height or
  2. the distance to any 5 ft or higher opaque vertical obstruction. secondary sidelighted area: the total secondary sidelighted area is the combined secondary sidelighted area within a space . Each secondary sidelighted area is directly adjacent to a primary sidelighted area (see Figure 3.2-5):

a. The secondary sidelighted area width is the width of the vertical fenestration plus, on each side,

the smaller of

  1. one half of the vertical fenestration head height or
  2. the distance to any 5 ft or higher opaque vertical obstruction.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 7

PDF Page 10

Open page note

b. The secondary sidelighted area depth is the horizontal distance perpendicular to the vertical fenes-

tration, which begins at the edge of the primary sidelighted area depth and ends at the smaller of

  1. one vertical fenestration head height or
  2. the distance to any 5 ft or higher opaque vertical obstruction.

If the adjacent primary sidelighted area ends at a 5 ft or higher opaque vertical obstruction, there is no secondary sidelighted area beyond such obstruction.

dead band: the range of values within which a sensed variable can vary without initiating a change in the controlled process.

decorative lighting: see lighting, decorative .

dedicated replacement air: see makeup air .

degree-day: the difference in temperature between the outdoor mean temperature over a twenty-four-hour period and a given base temperature. The classifications are defined as follows:

cooling degree-day base 50°F (CDD50): for any one day, when the mean temperature is more than 50°F, there are as many degree-days as degrees Fahrenheit temperature difference between the mean temperature for the day and 50°F. Annual cooling degree-days ( CDDs ) are the sum of the degree-days over a calendar year. heating degree-day base 65°F (HDD65): for any one day, when the mean temperature is less than 65°F, there are as many degree-days as degrees Fahrenheit temperature difference between the mean temperature for the day and 65°F. Annual heating degree-days (HDDs) are the sum of the degree-days over a calendar year.

demand: the highest amount of power (average Btu/h over an interval) recorded for a building or facility in a selected time frame.

demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy.

design capacity: output capacity of a system or piece of equipment at design conditions .

design conditions: specified environmental conditions, such as temperature and light intensity, required to be produced and maintained by a system and under which the system must operate.

design energy cost: the annual energy cost calculated for a proposed design .

design professional: an architect or engineer licensed to practice in accordance with applicable state licensing laws.

dimmer: a lighting control device that is capable of varying the light output and energy usage of light sources.

direct digital control (DDC): a type of control where controlled and monitored analog or binary data (e.g., temperature, contact closures) are converted to digital format for manipulation and calculations by a digital computer or microprocessor and then converted back to analog or binary form to control physical devices.

distribution system: conveying means, such as ducts, pipes, and wires, to bring substances or energy from a source to the point of use. The distribution system includes such auxiliary equipment as fans, pumps, and transformers .

door: an operable opening area in the building envelope that is not fenestration . A door where more than one-half of the door area is glazed is considered fenestration, and a door where one-half or less of the door area is glazed is considered an opaque door . An access hatch is considered a door . For the purposes of determining building envelope requirements, the classifications are defined as follows:

metal coiling door: an upward-acting, nonswinging door assembly consisting of interlocking horizontal slats or sheets that, upon opening the door, roll up around a horizontal barrel above the door opening. nonswinging door: roll-up, metal coiling, sliding, and any other door that is not a swinging door . sectional garage door: an upward-acting, nonswinging door assembly made of two or more horizontal panels hinged together vertically. swinging door: a door having an operable opaque panel with hinges or pivots on one side.

door area: total area of the door measured using the rough opening and including the door slab and the frame. (See fenestration area .)

driver: a device designed to operate a solid-state (e.g., LED) light source.

8 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 11

Open page note

Figure 3.2-1 Computing the daylight area under roof monitors.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 9

PDF Page 12

Open page note

Figure 3.2-2 Computing the daylight area under skylights.

10 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 13

Open page note

Figure 3.2-3 Computing the daylight area under skylights in multistory spaces.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 11

PDF Page 14

Open page note

Figure 3.2-4 Computing the primary sidelighted area.

12 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 15

Open page note

Figure 3.2-5 Computing the secondary sidelighted area.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 13

PDF Page 16

Open page note

Figure 3.2-6 Computing the primary and secondary sidelighted areas with external projections.

14 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 17

Open page note

ductwork: a system of ducts for distribution and extraction of air.

dwelling unit: a single unit providing complete independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking, and sanitation.

direct-expansion dedicated outdoor air system units (DX-DOAS units): a type of air-cooled, water-cooled, or water-source factory-assembled product that dehumidifies 100% outdoor air to a low dew point and includes reheat that is capable of controlling the supply dry-bulb temperature of the dehumidified air to the designed supply air temperature. This conditioned outdoor air is then delivered directly or indirectly to the conditioned spaces . It may precondition outdoor air by containing an enthalpy wheel, sensible wheel, desiccant wheel, plate heat exchanger, heat pipes, or other heat or mass transfer apparatus.

dynamic glazing: any glazing system /glazing infill that has the fully reversible ability to change its performance properties, including U-factor, solar heat gain coefficient, or visible transmittance . This includes (but is not limited to) shading systems between the glazing layers and chromogenic glazing.

east-oriented: facing within 45 degrees of true east to the south and within less than 22.5 degrees of true east to the north in the northern hemisphere; facing within 45 degrees of true east to the north and within less than 22.5 degrees of true east to the south in the southern hemisphere.

economizer, air: a duct and damper arrangement and automatic control system that together allow a cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mild or cold weather.

economizer, fluid: a system by which the supply air of a cooling system is cooled indirectly with a fluid that is itself cooled by heat or mass transfer to the environment without the use of mechanical cooling . Examples of commonly used fluids are water, glycol mixtures, and refrigerants.

effective panel surface: see thermally effective panel surface .

efficacy (of a lamp): the ratio of the total luminous output of a lamp to the total power input to the lamp, typically expressed in lm/W.

efficiency: performance at specified rating conditions.

electric resistance: see resistance, electric.

emittance: the ratio of the radiant heat flux emitted by a specimen to that emitted by a blackbody at the same temperature and under the same conditions.

enclosed space: a volume substantially surrounded by solid surfaces, such as walls, floors, roofs, and openable devices, such as doors and operable windows.

energy: the capacity for doing work. It takes a number of forms that may be transformed from one into another such as thermal (heat), mechanical (work), electrical, and chemical (Btu).

energy cost budget: the annual energy cost for the budget building design intended for use in determining minimum compliance with this standard.

energy efficiency ratio (EER): the ratio of net cooling capacity (Btu/h) to total rate of electric input in watts under designated operating conditions. ( Informative Note: EER2 reflects the new higher static effective 1/1/2023.)

energy factor (EF): a measure of water heater overall efficiency .

envelope performance factor: the trade-off value for the building envelope performance compliance option, expressed in annual energy cost, calculated using the procedures specified in Section 5.6. For the purposes of determining building envelope requirements, the classifications are defined as follows:

base envelope performance factor: the building envelope performance factor for the base design.

proposed envelope performance factor: the building envelope performance factor for the proposed design .

energy recovery ratio, series (SERR): the difference between the dry-bulb air temperatures leaving the series energy recovery unit and leaving the dehumidifying coil divided by the difference between 75°F and the dry-bulb temperature of the air leaving the dehumidifying cooling coil.

energy recovery, series: a three-step process in which the first step is to remove energy from a single airstream without the use of mechanical cooling . In the second step, the airstream is mechanically cooled for the purpose of dehumidification. In the third step, the energy removed in step one is reintroduced to the airstream.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 15

PDF Page 18

Open page note

enthalpy recovery ratio: change in the enthalpy of the outdoor air supply divided by the difference between the outdoor air and entering exhaust air enthalpy, expressed as a percentage.

entrance door: see vertical fenestration.

equipment: devices for space heating, space cooling, ventilation, humidification, dehumidification, electric power, lighting, transportation, refrigeration, cooking, or service water heating, including (but not limited to) furnaces, boilers, air conditioners, heat pumps, chillers, water heaters, lamps, luminaires, ballasts, elevators, escalators, or other devices or installations.

essential facility: those portions of a building serving one of the following functions:

a. Hospitals and other health care facilities having surgery or emergency treatment facilities b. Fire, rescue, and police stations and emergency vehicle garages c. Designated earthquake, hurricane, or other emergency shelters d. Designated emergency preparedness, communication, and operation centers and other facilities

required for emergency response e. Power-generating stations and other public utility facilities required as emergency backup facilities for

other essential facilities f. Structures containing highly toxic materials where the quantity of the material exceeds the maximum allowable quantities g. Aviation control towers, air traffic control centers, and emergency aircraft hangars h. Buildings and other structures having critical national defense functions

evaporation design wet-bulb temperature: the outdoor wet-bulb temperature used in conjunction with the mean coincident dry-bulb temperature, often used for the sizing of evaporative systems such as cooling towers.

existing building: a building or portion thereof that was previously occupied or approved for occupancy by the authority having jurisdiction .

existing equipment: equipment previously installed in an existing building or on an existing site.

existing site: a site or portion thereof that was previously approved by the authority having jurisdiction .

existing system: a system or systems previously installed in an existing building or on an existing site .

exterior building envelope: see building envelope .

exterior lighting power allowance: see lighting power allowance, exterior .

exterior wall: see building envelope and wall .

eye adaptation: the process by which the retina becomes accustomed to more or less light than it was exposed to during an immediately preceding period. It results in a change in the sensitivity to light.

F-factor: the perimeter heat loss factor for slab-on-grade floors (Btu/h·ft·°F).

facade area: area of the facade, including overhanging soffits, cornices, and protruding columns, measured in elevation in a vertical plane parallel to the plane of the face of the building . Nonhorizontal roof surfaces shall be included in the calculation of vertical facade area by measuring the area in a plane parallel to the surface.

fan array: multiple fans in parallel between two plenum sections in an air distribution system .

fan brake horsepower (bhp): the horsepower delivered to the fan’s shaft. Brake horsepower does not include the mechanical drive losses (belts, gears, etc.).

fan, embedded: a fan that is part of a manufactured assembly where the assembly includes functions other than air movement.

fan energy index (FEI): the ratio of the electric input power of a reference fan to the electric input power of the actual fan as calculated per AMCA 208.

fan nameplate electrical input power: the nominal electrical input power rating stamped on a fan assembly nameplate.

fan system brake horsepower (bhp): the sum of the fan brake horsepower of all fans that are required to operate at fan system design conditions to supply air from the heating or cooling source to the conditioned spaces and return it to the source or exhaust it to the outdoors.

fan system design conditions: operating conditions that can be expected to occur during normal system operation that result in the highest supply airflow rate to conditioned spaces served by the system, other than during air economizer operation.

16 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 19

Open page note

fan system motor nameplate horsepower (hp): the sum of the motor nameplate horsepower of all fans that are required to operate at design conditions to supply air from the heating or cooling source to the condi- tioned spaces and return it to the source or exhaust it to the outdoors.

feeder conductors: the wires that connect the service equipment to the branch circuit breaker panels.

fenestration: an assembly, including the frame, in the building envelope that allows light to pass. Fenestra- tion assemblies include (but are not limited to) windows, plastic panels, clerestories, roof monitors, sky- lights, glass block, and doors where more than one-half of the door area is glazed. For the purposes of determining building envelope requirements, the classifications are defined as follows:

field-fabricated fenestration: fenestration whose frame is made at the construction site of materials that were not previously cut, or otherwise formed with the specific intention of being used to fabricate a fen- estration product or exterior glazed door . Field-fabricated fenestration does not include site -built fenes- tration designed to be glazed or assembled in the field using specific factory-cut or otherwise factoryformed framing and glazing units, such as storefront systems, curtain walls, and atrium roof systems. skylight: a fenestration surface having a slope of less than 60 degrees from the horizontal plane. Other fenestration, even if mounted on the roof of a building, is considered vertical fenestration . vertical fenestration: all fenestration other than skylights . Trombe wall assemblies, where glazing is installed within 12 in. of a mass wall, are considered walls, not fenestration.

fenestration area: total area of the fenestration measured using the rough opening and including the glazing, sash, and frame. For doors where the glazed vision area is less than 50% of the door area, the fenestration area is the glazed vision area. For all other doors, the fenestration area is the door area . (See door area .)

fixture: the component of a luminaire that houses the lamp or lamps or positions the lamp, shields it from view, and distributes the light. The fixture also provides for connection to the power supply, which may require the use of a ballast / driver .

floor: that lower portion of the building envelope, including opaque area and fenestration, that has conditioned or semiheated space above and is horizontal or tilted at an angle of less than 60 degrees from horizontal but excluding slab-on-grade floors . For the purposes of determining building envelope requirements, the classifications are defined as follows:

mass floor: a floor with a heat capacity that exceeds (a) 7 Btu/ft [2] ·°F or (b) 5 Btu/ft [2] ·°F, provided that the floor has a material unit mass not greater than 120 lb/ft [3] . steel-joist floor: a floor that (a) is not a mass floor and (b) has steel joist members supported by structural members. wood-framed and other floors: all other floor types, including wood-joist floors .

(See building envelope, fenestration, opaque, and slab-on-grade floor ) .

floor area, gross: the sum of the floor areas of the spaces within the building, including basements, mezzanine and intermediate-floored tiers, and penthouses with a headroom height of 7.5 ft or greater. It is measured from the exterior faces of walls or from the centerline of walls separating buildings, but excluding covered walkways, open roofed-over areas, porches and similar spaces, pipe trenches, exterior terraces or steps, chimneys, roof overhangs, and similar features.

gross conditioned floor area: the gross floor area of conditioned spaces . gross lighted floor area: the gross floor area of lighted spaces .

(See building envelope, floor, slab-on-grade floor, and space .)

flue damper: a device in the flue outlet or in the inlet of or upstream of the draft control device of an individual, automatically operated, fossil - fuel -fired appliance that is designed to automatically open the flue outlet during appliance operation and to automatically close the flue outlet when the appliance is in a standby condition.

fluid economizer: see economizer, fluid.

fuel: a material that may be used to produce heat or generate power by combustion.

fossil fuel: fuel derived from a hydrocarbon deposit, such as petroleum, coal, or natural gas derived from living matter of a previous geologic time.

functional performance testing (FPT): a systematic process to verify that controls and other elements of the building project are capable of and configured to operate or perform as required.

general lighting: see lighting, general .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 17

PDF Page 20

Open page note

generally accepted engineering standard: a specification, rule, guide, or procedure in the field of engineering, or related thereto, recognized and accepted as authoritative.

grade: the finished ground level adjoining a building at all walls .

greenhouse: a space with a skylight roof ratio of 50% or more above the growing area used exclusively for horticultural production, cultivation, or maintenance by utilizing a sunlit environment. Greenhouses are spaces erected for a period of 180 days or more.

gross conditioned floor area: see floor area, gross .

gross floor area: see floor area, gross .

gross lighted floor area: see floor area, gross .

gross roof area: see roof area, gross .

gross wall area: see wall area, gross .

growth media: an engineered formulation of inorganic and organic materials including but not limited to heat-expanded clays, slates, shales, aggregate, sand, perlite, vermiculite, and organic material including (but not limited to) compost worm castings, coir, peat, and other organic material.

heat capacity (HC): the amount of heat necessary to raise the temperature of a given mass 1°F. Numerically, the HC per unit area of surface (Btu/ft [2] ·°F) is the sum of the products of the mass per unit area of each individual material in the roof, wall, or floor surface multiplied by its individual specific heat.

heat recovery coefficient of performance (COPHR): a ratio of the net heat recovery capacity plus the net refrigerating capacity to the total input power at any given set of rating conditions. COPHR applies to units that are operating in a manner that uses either all or only a portion of heat generated during chiller operation to heat a load, while the remaining heat, if any, is rejected to the outdoor ambient. COPHR takes into account the beneficial cooling capacity as well as the heat recovery capacity.

heat trace: a heating system where the externally applied heat source follows (traces) the object to be heated (e.g., water piping ).

heated space: see space .

heating degree-day, base: see degree-day .

heating design temperature: the outdoor dry-bulb temperature equal to the temperature that is exceeded at least 99.6% of the number of hours during a typical weather year.

heating seasonal performance factor (HSPF): the total heating output of a heat pump during its normal annual usage period for heating (Btu) divided by the total electric energy input during the same period. ( Informative Note: HSPF2 reflects the new higher static and load line effective 1/1/2023.)

high-end trim: process of setting the maximum light output of individual luminaires or groups of luminaires to support visual needs of a space, task, or area. High-end trim is also known as “institutional tuning” or “task tuning.”

historic: a building or space that has been specifically designated historically significant by the adopting authority or is listed in The National Register of Historic Places or has been determined to be eligible for such listing by the U.S. Secretary of the Interior.

hot-water supply boiler: a boiler used to heat water for purposes other than space heating.

humidistatic controls: automatic controls used to maintain humidity at a fixed or adjustable set point .

HVAC system: the equipment, distribution systems, and terminals that provide, either collectively or individually, the processes of heating, ventilating, or air conditioning to a building or portion of a building .

HVAC zone: a space or group of spaces within a building with heating and cooling requirements that are sufficiently similar so that desired conditions (e.g., temperature) can be maintained throughout using a single sensor (e.g., thermostat or temperature sensor).

hydronic system balancing: see balancing, hydronic system .

IEC Design H motor: an electric motor that

a. is an induction motor designed for use with three-phase power; b. contains a cage rotor; c. is capable of direct-on-line starting; d. has 4, 6, or 8 poles;

18 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 21

Open page note

e. is rated from 0.4 to 1600 kW at a frequency of 60 Hz; and f. conforms to Sections 8.1, 8.2, and 8.3 of IEC 60034-12 (edition 2.1) requirements for starting torque, locked rotor apparent power, and starting.

IEC Design N motor: an electric motor that

a. is an induction motor designed for use with three-phase power; b. contains a cage rotor; c. is capable of direct-on-line starting; d. has 2, 4, 6, or 8 poles; e. is rated from 0.4 to 1600 kW at a frequency of 60 Hz; and f. conforms to Sections 6.1, 6.2, and 6.3 of IEC 60034-12 (edition 2.1) requirements for torque characteristics, locked rotor apparent power, and starting.

indirectly conditioned space: see space .

indoor grow: a space, other than a greenhouse, used exclusively for horticultural production, cultivation, or maintenance.

indoor pool dehumidifier: a type of air-cooled or water-cooled electrically operated vapor compression refrigeration system, factory assembled as a single package or split system, that includes an indoor cooling/ dehumidifying coil, an air reheat coil, one or more compressors, and an air-moving device. It may also include a refrigerant heat recovery unit, an auxiliary refrigerant condenser, an economizer, and an air-to-air heat recovery device. It shall provide the function of dehumidification, air circulation, and air reheating and may include the function of air-cooling, air-cleaning, pool water heating, and air-to-air heat recovery.

ineffective panel surface: see thermally ineffective panel surface .

installed exterior lighting power: the power in watts of all site, landscape, and building lighting systems for exterior luminaires .

installed interior lighting power: the power in watts of all general, task, and furniture lighting systems for interior luminaires .

insulated metal panel: a factory-manufactured panel consisting of metal facings, an insulative core, and a panel joint intended for use in an assembly forming an exterior wall, an exterior wall covering, or a roof cov- ering of a building envelope .

integrated energy efficiency ratio (IEER): a single-number figure of merit expressing cooling part-load EER efficiency for commercial unitary air-conditioning and heat-pump equipment on the basis of weighted operation at various load capacities for the equipment .

integrated part-load value (IPLV .IP ): a single-number figure of merit based on part-load EER expressing part-load efficiency for air-conditioning and heat-pump equipment on the basis of weighted operation at various load capacities for the equipment .

integrated seasonal coefficient of performance (ISCOP): a seasonal efficiency number that is a combined value based on the formula listed in AHRI Standard 920 of the two COP values for the heating season of a DX-DOAS unit water or air source heat pump, expressed in W/W.

integrated seasonal moisture removal efficiency (ISMRE): a seasonal efficiency number that is a combined value based on the formula listed in AHRI Standard 920 of the four dehumidification moisture removal effi- ciency ( MRE ) ratings required for DX-DOAS units, expressed in lb of moisture/kWh.

interior lighting power allowance: see lighting power allowance .

isolation devices: devices that isolate HVAC zones so that they can be operated independently of one another. Isolation devices include, but are not limited to, separate systems, isolation dampers, and controls providing shutoff at terminal boxes.

IT equipment energy: annual energy used for computer storage and network equipment along with supplemental equipment represented by the uninterruptible power supply (UPS) output calculated in accordance with industry-accepted standards (see Informative Appendix E).

joist, steel: any structural steel member of a building or structure made of hot-rolled or cold-rolled solid or open-web sections.

kilovolt-ampere (kVA): where the term kilovolt-ampere is used in this standard, it is the product of the line current (amperes) times the nominal system voltage (kilovolts) times 1.732 for three-phase currents. For

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 19

PDF Page 22

Open page note

single-phase applications, kVA is the product of the line current (amperes) times the nominal system voltage (kilovolts).

kilowatt (kW): the basic unit of electric power, equal to 1000 W.

labeled: equipment or materials to which a symbol or other identifying mark has been attached by the manu- facturer indicating compliance with specified standards or performance in a specified manner.

lamp: a generic term for a man-made light source, often called a “bulb” or “tube.”

high-intensity discharge (HID) lamp: an electric discharge lamp in which light is produced when an electric arc is discharged through a vaporized metal such as mercury or sodium. Some HID lamps may also have a phosphor coating that contributes to the light produced or enhances the light color.

light-to-solar-gain ratio (LSG): the ratio of the center-of-glass visible transmittance to the center-of-glass solar heat gain coefficient .

lighting, decorative: lighting that is ornamental or installed for aesthetic effect. Decorative lighting shall not include general lighting .

lighting, general: lighting that provides a substantially uniform level of illumination throughout an area. General lighting shall not include decorative lighting or lighting that provides a dissimilar level of illumination to serve a specialized application or feature within such area.

lighting, horticultural: electric lighting used for horticultural production, cultivation, or maintenance with either plug-in or hard-wired connections for electric power.

lighting power allowance (LPA), exterior: the maximum lighting power in watts allowed for the exterior of a property .

lighting power allowance (LPA), interior: the maximum lighting power in watts allowed for the interior of a building .

lighting power density (LPD): the lighting power per unit area of a building, space, or outdoor area expressed in W/ft [2] .

lighting system: a group of luminaires circuited or controlled to perform a specific function.

liner system (Ls): a continuous vapor barrier liner installed below the purlins and uninterrupted by framing members.

linear thermal bridge: see thermal bridge.

low-rise residential buildings: single-family houses, multifamily structures of three stories or fewer above grade, manufactured houses (mobile homes), and manufactured houses (modular).

lumen maintenance: a lighting control strategy that increases light source power over time to maintain light levels as sources age, dirt accumulates in luminaires, or both. Also known as “lumen depreciation compensation” or “constant lumen output.”

luminaire: a complete lighting unit consisting of a lamp or lamps together with the housing designed to distribute the light, position and protect the lamps, and connect the lamps to the power supply.

makeup air (dedicated replacement air): outdoor air deliberately brought into the building from the outside and supplied to the vicinity of an exhaust hood to replace air, vapor, and contaminants being exhausted. Makeup air is generally filtered and fan-forced, and it may be heated or cooled depending on the requirements of the application. Makeup air may be delivered through outlets integral to the exhaust hood or through outlets in the same room.

manual (nonautomatic): requiring personal intervention for control. Nonautomatic does not necessarily imply a manual controller, only that personal intervention is necessary. (See automatic .)

manufacturer: the company engaged in the original production and assembly of products or equipment or a company that purchases such products and equipment manufactured in accordance with company specifications.

mass floor: see floor .

mass wall: see wall.

mean temperature: one-half the sum of the minimum daily temperature and maximum daily temperature.

20 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 23

Open page note

mechanical cooling: reducing the temperature of a gas or liquid by using vapor compression, absorption, desiccant dehumidification combined with evaporative cooling, or another energy -driven thermodynamic cycle. Indirect or direct evaporative cooling alone is not considered mechanical cooling .

mechanical heating: raising the temperature of a gas or liquid by use of fossil fuel burners, electric resis- tance heaters, heat pumps, or other systems that require energy to operate.

metal building: a complete integrated set of mutually dependent components and assemblies that form a building, which consists of a steel-framed superstructure and metal skin.

metal building roof: see roof .

metal building wall: see wall .

metal building envelope: see building envelope.

metal framing: see vertical fenestration .

metering: instruments that measure electric voltage, current, power, etc.

moisture removal efficiency (MRE): a ratio of the moisture removal capacity in lb of moisture/h to the power input values in kW at any given set of standard rating conditions expressed in lb of moisture/kWh.

motor power, rated: the rated output power from the motor.

nameplate horsepower (hp): the nominal motor output power rating stamped on the motor nameplate.

nameplate rating: the design load operating conditions of a device as shown by the manufacturer on the nameplate or otherwise marked on the device.

NEMA Design A motor: a squirrel-cage motor that

a. is designed to withstand full-voltage starting and developing locked-rotor torque as shown in NEMA

MG 1, paragraph 12.38.1; b. has pull-up torque not less than the values shown in NEMA MG 1, paragraph 12.40.1; c. has breakdown torque not less than the values shown in NEMA MG 1, paragraph 12.39.1; d. has a locked-rotor current higher than the values shown in NEMA MG 1, paragraph 12.35.1, for 60 Hz,

and NEMA MG 1, paragraph 12.35.2, for 50 Hz; and e. has a slip at rated load of less than 5% for motors with fewer than 10 poles.

NEMA Design B motor: a squirrel-cage motor that is

a. designed to withstand full-voltage starting; b. develops locked-rotor, breakdown, and pull-up torques adequate for general application as specified in

NEMA MG1, paragraphs 12.38, 12.39, and 12.40; c. draws locked-rotor current not to exceed the values shown in NEMA MG1, paragraph 12.35.1, for 60

Hz, and paragraph 12.35.2 for 50 Hz; and d. has a slip at rated load of less than 5% for motors with fewer than 10 poles.

NEMA Design C motor: a squirrel-cage motor that

a. is designed to withstand full-voltage starting and developing locked-rotor torque for high-torque appli cations up to the values shown in NEMA MG1, paragraph 12.38.2 (incorporated by reference; see §431.15); b. has pull-up torque not less than the values shown in NEMA MG1, paragraph 12.40.2; c. has breakdown torque not less than the values shown in NEMA MG1, paragraph 12.39.2; d. has a locked-rotor current not to exceed the values shown in NEMA MG1, paragraph 12.35.1, for 60

Hz, and paragraph 12.35.2 for 50 Hz; and e. has a slip at rated load of less than 5%.

networked guest room control system: a control system, accessible from the hotel/motel front desk or other central location, that is capable of identifying rented and unrented rooms according to a timed schedule, and is capable of controlling HVAC in each hotel/motel guest room separately.

nonautomatic: see manual .

nonmetal framing: see vertical fenestration .

nonrecirculating system: a domestic or service hot-water distribution system that is not a recirculating system .

nonresidential: all occupancies other than residential . (See residential .)

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 21

PDF Page 24

Open page note

nonstandard part-load value (NPLV. IP ): a single-number part-load efficiency figure of merit calculated and referenced to conditions other than IPLV .IP conditions, for units that are not designed to operate at AHRI standard rating conditions.

nonswinging door: see door .

nontransient: occupancy of a dwelling unit or sleeping unit for more than 30 days.

nonweatherized space constrained single-package vertical unit: a single-package vertical air conditioner ( SPVAC ) or single-package vertical heat pump ( SPVHP ) that meets all of the following requirements:

a. Is for indoor use only b. Has rated cooling capacities no greater than 36,000 Btu/h c. Is a single-package unit requiring opening in an exterior wall or semiexterior wall with overall exterior

dimensions that requires or uses an existing sleeve that meets one of the following criteria:

  1. Has a width of less than 32 in. and height of less than 45 in.
  2. Fits inside an existing 1310 in. [2] opening d. Is commonly installed in site -built commercial buildings e. Is of a similar cooling capacity and, if a heat pump, similar heating capacity f. Draws outdoor air for heat exchange directly through an existing opening, used for both inlet and outlet, in the exterior wall or semiexterior wall g. Is restricted to applications where an existing air conditioner, heat pump, or gas/electric unit, installed

in an existing exterior wall or semiexterior wall opening, is to be replaced h. Bears a permanent “Replacement” marking, conspicuously placed and clearly indicating that its appli cation is limited to installations where an existing air conditioner or heat pump is to be replaced

north-oriented: facing within 67.5 degrees of true north in the northern hemisphere; facing within 67.5 degrees of true south in the southern hemisphere.

occupancy sensor: a device that detects the presence or absence of people within an area and causes lighting, equipment, or appliances to be regulated accordingly.

occupied-standby mode: when a zone is scheduled to be occupied, and an occupant sensor indicates no occupants are within the zone.

off-mode power consumption (PW,OFF): the power consumption when the unit is connected to its main power source but is neither providing cooling nor heating to the building it serves.

on-site electricity generation systems: systems located at the building site that generate electricity, including, but not limited to, generators, combined heat and power systems, fuel cells, and on-site renewable energy systems .

on-site renewable energy: energy from renewable resources harvested at the building site .

opaque: all areas in the building envelope, except fenestration and building service openings such as vents and grilles. (See building envelope and fenestration .)

optimum start controls: controls that are designed to automatically adjust the start time of an HVAC system each day with the intention of bringing the space to desired occupied temperature levels immediately before scheduled occupancy.

orientation: the direction an envelope element faces, i.e., the direction of a vector perpendicular to and pointing away from the surface outside of the element.

outdoor (outside) air: air that is outside the building envelope or is taken from outside the building that has not been previously circulated through the building .

overcurrent: any current in excess of the rated current of equipment or the ampacity of a conductor. It may result from overload, short circuit, or ground fault.

packaged terminal air conditioner (PTAC): a factory-selected wall sleeve and separate unencased combination of heating and cooling components, assemblies, or sections. It may include heating capability by hot water, steam, or electricity and is intended for mounting through the wall to serve a single room or zone.

packaged terminal heat pump (PTHP): a PTAC capable of using the refrigerating system in a reverse cycle or heat-pump mode to provide heat.

parking garage daylight transition zone: covered vehicle entrances and exits from buildings and parking structures not exceeding a depth of 66 ft inside the structure, or a depth as determined by ANSI/IES RP-8,

22 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 25

Open page note

and not exceeding a width of 30 ft to either side of the drive aisle centerline and not extending beyond adjacent walls.

parking garage section: a part of a parking garage where airflow is restricted from other parts of the garage by solid walls.

party wall: a fire wall on an interior lot line used or adapted for joint service between two buildings .

PEICL: the pump energy index for a constant load, hp.

PEIVL: the pump energy index for a variable load.

PERCL: the pump energy rating for a constant load, hp, determined in accordance with either testing for bare pumps, pumps sold with single-phase induction motors, and pumps sold with drivers other than electric motors, or testing for pumps sold with motors and rated using the testing-based approach, or testing for pumps sold with motors and rated using the calculation-based approach.

PERSTD: the PERCL for a pump that is minimally compliant with U.S. DOE energy conservation standards with the same flow and specific speed characteristics as the tested pump (hp).

PERVL: the pump energy rating for a variable load, hp, determined in accordance with testing for pumps sold with motors and continuous or noncontinuous controls rated using the testing-based approach, or testing for pumps sold with motors and continuous controls rated using the calculation-based approach.

Performance Rating Method: a calculation procedure that generates an index of merit for the performance of building designs that substantially exceeds the energy efficiency levels required by this standard or when using the Performance Rating Method as an alternative path for minimum standard compliance in accordance with Section 4.2.1.1.

permanently installed: equipment that is fixed in place and is not portable or movable.

photosensor: a device that detects the presence of visible light, infrared (IR) transmission, and/or ultraviolet (UV) energy .

photosynthetic photon efficacy (PPE): photosynthetic photon flux emitted by a light source between 400 and 700 nm divided by its electrical input power, expressed in units of micromoles per joule as defined by ANSI/ ASABE S640-2017.

piping: the pipes or tubes interconnecting the various parts of a fluid distribution system, including all elements that are in series with the fluid flow, such as pumps, valves, strainers, and air separators, but not including elements that are not in series with the fluid flow, such as expansion tanks, fill lines, chemical feeders, and drains.

plenum: a compartment or chamber to which one or more ducts are connected, that forms a part of the air distribution system, and that is not used for occupancy or storage. A plenum often is formed in part or in total by portions of the building .

point thermal bridge: see thermal bridge.

pool: any structure, basin, or tank containing an artificial body of water for swimming, diving, or recreational bathing. The term includes (but is not limited to) swimming pools, whirlpools, spas, and hot tubs.

power roof/wall ventilators (PRV): a fan consisting of a centrifugal or axial impeller with an integral driver in a weather-resistant housing and with a base designed to fit, usually by means of a curb, over a wall or roof opening.

primary sidelighted area: see daylight area .

process application: a manufacturing, industrial, or commercial procedure or activity where the primary purpose is other than conditioning spaces and maintaining comfort and amenities for the occupants of a building .

process energy: energy consumed in support of a process application .

process load: the load on a building resulting from the consumption or release of process energy .

projection factor (PF): the ratio of the horizontal depth of the external shading projection divided by the sum of the height of the fenestration and the distance from the top of the fenestration to the bottom of the farthest point of the external shading projection, in consistent units.

property: building or site.

proposed building performance: the annual energy cost calculated for a proposed design .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 23

PDF Page 26

Open page note

proposed design: a computer representation of the actual proposed building design, or portion thereof, used as the basis for calculating the design energy cost .

psi-factor (ψ or Psi): thermal transmittance per unit length of a linear thermal bridge in units of Btu/ (h·ft·°F).

public facility restroom: a restroom used by the transient public.

pump: equipment designed to move liquids that may include entrained gases, free solids, and totally dissolved solids by physical or mechanical action and that includes a bare pump and, if included by the manu- facturer at the time of sale, mechanical equipment, driver, and controls. ( Informative Note: The U.S. Code of Federal Regulations (CFR) contains official definitions related to pumps in 10 CFR 431.462. In the United States, the official definitions take precedence over the definitions shown below.)

clean-water pump: a device that is designed for use in pumping water with a maximum nonabsorbent free solid content of 0.016 lb/ft [3] and with a maximum dissolved solid content of 3.1 lb/ft [3], provided that the total gas content of the water does not exceed the saturation volume, and disregarding any additives necessary to prevent the water from freezing at a minimum of 14°F.

end-suction close-coupled (ESCC) pump: a close-coupled, dry-rotor, end-suction device that has a shaft input power greater than or equal to 1.0 hp and less than or equal to 200 hp at its best efficiency point ( BEP ) and full impeller diameter and that is not a dedicated-purpose pool pump . It is also a singlestage, rotodynamic pump in which the liquid enters the bare pump in a direction parallel to the impeller shaft and on the side opposite the bare pump ’s driver end and is then discharged through a volute in a plane perpendicular to the shaft.

end-suction frame-mounted/own-bearings (ESFM) pump: a mechanically coupled, dry-rotor, endsuction device that has a shaft input power greater than or equal to 1.0 hp and less than or equal to 200 hp at its best efficiency point ( BEP ) and full impeller diameter and that is not a dedicated-purpose pool pump . It is also a single-stage, rotodynamic pump in which the liquid enters the bare pump in a direction parallel to the impeller shaft and on the side opposite the bare pump ’s driver end and is then discharged through a volute in a plane perpendicular to the shaft.

inline (IL) pump: a device that is either a twin-head pump or a single-stage, single-axis flow, dry-rotor, rotodynamic pump that has a shaft input power greater than or equal to 1.0 hp and less than or equal to 200 hp at its best efficiency point ( BEP ) and full impeller diameter, in which liquid is discharged through a volute in a plane perpendicular to the shaft. Such pumps do not include pumps that are mechanically coupled or close-coupled, have a pump power output that is less than or equal to 5.0 hp at its BEP at full impeller diameter, and are distributed in commerce with a horizontal motor.

radially split, multistage, vertical, inline diffuser casing (RSV) pump: a device that is a vertically suspended, multistage, single-axis-flow, dry-rotor, rotodynamic pump and

a. has a shaft input power greater than or equal to 1.0 hp and less than or equal to 200 hp at its best

efficiency point ( BEP ) and full impeller diameter and at the number of stages required for testing; b. in which liquid is discharged in a place perpendicular to the impeller shaft; c. for which each stage (or bowl) consists of an impeller and diffuser; and d. for which no external part of such a pump is designed to be submerged in the pumped liquid.

submersible turbine (ST) pump: a device that is a single-stage or multistage, dry-rotor, rotodynamic pump that is designed to be operated with the motor and stage(s) fully submerged in the pumped liquid; that has a shaft input power greater than or equal to 1.0 hp and less than or equal to 200 hp at its best efficiency point ( BEP ) and full impeller diameter and at the number of stages required for testing; and in which each stage of this pump consists of an impeller and diffuser, and liquid enters and exits each stage of the bare pump in a direction parallel to the impeller shaft.

pump system power: the sum of the nominal power demand ( nameplate horsepower ) of motors of all pumps that are required to operate at design conditions to supply fluid from the heating or cooling source to all heat transfer devices (e.g., coils, heat exchanger) and return it to the source.

purchased energy: energy or power purchased for consumption and delivered to the building site .

purchased energy rates: costs for units of energy or power purchased at the building site . These costs may include energy costs as well as costs for power demand as determined by the adopting authority .

R-value: see thermal resistance .

24 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 27

Open page note

radiant heating system: a heating system that transfers heat to objects and surfaces within the heated space primarily (greater than 50%) by infrared radiation.

rated motor power: see motor power, rated .

rated R-value of insulation: the thermal resistance of the insulation alone as specified by the manufacturer in units of h·ft [2] ·°F/Btu at a mean temperature of 75°F. Rated R-value refers to the thermal resistance of the added insulation in framing cavities or insulated sheathing only and does not include the thermal resistance of other building materials or air films. (See thermal resistance .)

rating authority: the organization or agency that adopts or sanctions use of Normative Appendix G when quantifying performance that exceeds requirements of this standard.

readily accessible: installed in a manner and location that allows it to be reached quickly for operation, renewal, or inspection without requiring those to whom ready access is requisite to climb over or remove obstacles or to resort to portable ladders, chairs, etc. In public facilities, accessibility may be limited to certified personnel through locking covers or by placing equipment in locked rooms.

recirculating system: a domestic or service hot-water distribution system that includes a closed circulation circuit designed to maintain usage temperatures in hot-water pipes near terminal devices (e.g., lavatory faucets, shower heads) in order to reduce the time required to obtain hot water when the terminal device valve is opened. The motive force for circulation is either natural (due to water density variations with temperature) or mechanical (recirculation pump ).

recool: to lower the temperature of air that has been previously heated by a mechanical heating system .

record documents: drawings and other documents that record the conditions of the project as constructed. These include any refinements of the construction documents or bid documents.

refrigeration system, low-temperature: system for maintaining food products in their frozen state in refrigeration applications.

refrigeration system, medium-temperature: system for maintaining food products above their frozen state in refrigeration applications.

refrigerant dew point: the refrigerant vapor saturation temperature at a specified pressure.

regulated energy use: energy used by building systems and components with requirements prescribed in Sections 5 through 10. This includes energy used for HVAC, lighting, service water heating, motors, trans- formers, vertical transportation, refrigeration equipment, computer-room cooling equipment, and other building systems, components, and processes with requirements prescribed in Sections 5 through 10.

reheat: to raise the temperature of air that has been previously cooled either by mechanical refrigeration or an economizer system .

renewable energy resources: energy from solar, wind, biomass or hydro, or extracted from hot fluid or steam heated within the earth.

repair: the reconstruction or renewal of any part of an existing building for the purpose of its maintenance.

replacement air: outdoor air that is used to replace air removed from a building through an exhaust system . Replacement air may be derived from one or more of the following: makeup air, supply air, and transfer air .

reset: automatic adjustment of the controller set point to a higher or lower value.

residential: spaces in building s used primarily for living and sleeping. Residential spaces include, but are not limited to, dwelling units, hotel/motel guest rooms, dormitories, nursing homes, patient rooms in hospitals, lodging houses, fraternity/sorority houses, hostels, prisons, and fire stations.

residential associated HVAC zone: any HVAC zone that primarily includes nonresidential spaces designed to serve occupants of residential spaces, including but not limited to corridors, stairwells, elevator lobbies, and common restrooms, on a floor where over 75% of the gross conditioned floor area are residential spaces . This definition does not apply to HVAC zones within hospitals.

resistance, electric: the property of an electric circuit or of any object used as part of an electric circuit that determines for a given circuit the rate at which electric energy is converted into heat or radiant energy and that has a value such that the product of the resistance and the square of the current gives the rate of conversion of energy .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 25

PDF Page 28

Open page note

roof: the upper portion of the building envelope, including opaque areas and fenestration, that is horizontal or tilted at an angle of less than 60 degrees from horizontal. For the purposes of determining building enve- lope requirements, the classifications are defined as follows:

attic and other roofs: all other roofs, including roofs with insulation entirely below (inside of) the roof structure (i.e., attics, cathedral ceilings, and single-rafter ceilings), roofs with insulation both above and below the roof structure, and roofs without insulation but excluding metal building roofs . metal building roof: a roof that

a. is constructed with a metal, structural, weathering surface; b. has no ventilated cavity; and c. has the insulation entirely below deck (i.e., does not include composite concrete and metal deck

construction nor a roof framing system that is separated from the superstructure by a wood substrate) and whose structure consists of one or more of the following configurations:

  1. Metal roofing in direct contact with the steel framing members
  2. Metal roofing separated from the steel framing members by insulation
  3. Insulated metal roofing panels installed as described in subitems (a) or (b) roof with insulation entirely above deck: a roof with all insulation

a. installed above (outside of) the roof structure and b. continuous (i.e., uninterrupted by framing members). single-rafter roof: a subcategory of attic roofs where the roof above and the ceiling below are both attached to the same wood rafter and where insulation is located in the space between these wood rafters.

roof area, gross: the area of the roof measured from the exterior faces of walls or from the centerline of party walls . (See roof and wall .)

roof covering: the topmost component of the roof assembly intended for weather resistance, fire classification, or appearance.

roof monitor: that part of a building that projects above the plane of the roof and whose walls contain verti- cal fenestration for lighting the interior.

roof recovering: the process of installing an additional roof covering over an existing roof covering without removing the existing roof covering .

roof replacement: an alteration that includes the removal of all existing layers of the roof assembly materials down to the roof deck and installing a new roof assembly above the roof deck.

room air conditioner: an encased assembly designed as a unit to be mounted in a window or through a wall or as a console. It is designed primarily to provide direct delivery of conditioned air to an enclosed space, room, or zone. It includes a prime source of refrigeration for cooling and dehumidification and a means for circulating and cleaning air. It may also include a means for ventilating and heating.

room cavity ratio (RCR): a factor that characterizes room configuration as a ratio between the walls and ceiling and is based on room dimensions.

saturated condensing temperature: the saturation temperature corresponding to the measured refrigerant pressure at the condenser inlet for single component and azeotropic refrigerants, and the arithmetic average of the refrigerant dew-point temperature and the bubble-point temperature corresponding to the refrigerant pressure at the condenser entrance for zeotropic refrigerants.

seal class A: a ductwork sealing category that requires sealing all transverse joints, longitudinal seams, and duct wall penetrations. Duct wall penetrations are openings made by pipes, holes, conduit, tie rods, or wires. Longitudinal seams are joints oriented in the direction of airflow. Transverse joints are connections of two duct sections oriented perpendicular to airflow.

seasonal energy efficiency ratio (SEER): the total cooling output of an air conditioner during its normal annual usage period for cooling (Btu) divided by the total electric energy input during the same period (W). ( Informative Note: SEER2 reflects the new higher static effective 1/1/2023.)

secondary sidelighted area: see daylight area.

sectional garage door: see door .

semiexterior building envelope: see building envelope .

semiexterior wall: see building envelope and wall .

26 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 29

Open page note

semiheated floor area: see floor area, gross .

semiheated space: see space .

sensible energy recovery ratio: change in the dry-bulb temperature of the outdoor air supply divided by the difference between the outdoor air and entering exhaust air dry-bulb temperatures, expressed as a percentage.

sensible heating panel: a panel designed for sensible heating of an indoor space through heat transfer from the thermally effective panel surfaces to the occupants and/or indoor space by thermal radiation and natural convection.

service agency: an agency capable of providing calibration, testing, or manufacture of equipment, instrumentation, metering, or control apparatus, such as a contractor, laboratory, or manufacturer .

service water heating: heating water for domestic or commercial purposes other than space heating and pro- cess application requirements.

setback: reduction of heating (by reducing the set point ) or cooling (by increasing the set point ) during hours when a building is unoccupied or during periods when lesser demand is acceptable.

set point: point at which the desired temperature, °F, of the heated or cooled space is set.

SHGC: see solar heat gain coefficient .

shading coefficient (SC): the ratio of solar heat gain at normal incidence through glazing to that occurring through 1/8 in. thick clear, double-strength glass. SC does not include interior, exterior, or integral shading devices.

sidelighting effective aperture: relationship of daylight transmitted through vertical fenestration to the pri- mary sidelighted areas . The sidelighting effective aperture is calculated according to the following formula:

Sidelighting Effective Aperture

 Vertical Fenestration Area  Vertical Fenestration VT

= ----------------------------------------------------------------------------------------------------------------------------------------- - Area of Primary Sidelighted Area

where “ Vertical Fenestration VT ” is the visible transmittance of vertical fenestration as determined in accordance with Section 5.8.2.6.

simulation program: a computer program, including the simulation engine and the corresponding user interface, that is capable of simulating the energy performance of building systems .

simultaneous cooling and heating coefficient of performance (COPSHC): a ratio of the net heating capacity plus the net refrigerating capacity to the total input power at any given set of rating conditions. COPSHC applies to units that are operating in a manner that uses both the net heating and refrigerating capacities generated during operation. COPSHC takes into account the beneficial capacity as well as the heating capacity.

single-line diagram: a simplified schematic drawing that shows the connection between two or more items. Common multiple connections are shown as one line.

single-package vertical air conditioner (SPVAC): a type of air-cooled small or large commercial package airconditioning and heating equipment ; factory assembled as a single package having its major components arranged vertically, which is an encased combination of cooling and optional heating components; is intended for exterior mounting on, adjacent interior to, or through an outside wall ; and is powered by single or threephase current. It may contain separate indoor grilles, outdoor louvers, various ventilation options, or indoor free air discharge, ductwork, wall plenum, or sleeve. Heating components may include electrical resistance, steam, hot water, gas, or no heat, but may not include reverse-cycle refrigeration as a heating means.

single-package vertical heat pump (SPVHP): an SPVAC that uses reverse-cycle refrigeration as its primary heat source, with secondary supplemental heating by means of electrical resistance, steam, hot water, or gas.

single-rafter roof: see roof .

single-zone system: an HVAC system serving a single HVAC zone .

site: an area of land that is under the control of a single owner or entity, which contains systems or equipment .

site-recovered energy: waste energy recovered at the building site that is used to offset consumption of purchased fuel or electrical energy supplies.

skylight: a fenestration surface having a slope of less than 60 degrees from the horizontal plane. Other fenes- tration, even if mounted on the roof of a building, is considered vertical fenestration .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 27

PDF Page 30

Open page note

skylight effective aperture: the overall amount of visible transmittance of the roof via skylights . Skylight effective aperture is calculated according to the following formula:

Sidelighting Effective Aperture

0.85  Skylight Area  Skylight VT  WF

= -------------------------------------------------------------------------------------------------- - Daylight Area Under Skylights

where Skylight Area = total fenestration area of skylights Skylight VT = area-weighted average visible transmittance of skylights as determined in accordance with Section 5.8.2.6. WF = area-weighted average skylight well factor, where skylight well factor is 0.9 if skylight well depth is less than 2 ft, or 0.7 if skylight well depth is 2 ft or greater. Skylight well depth is measured vertically from the underside of the lowest point on the skylight glazing to the ceiling plane under the skylight .

skylight well: the shaft from the skylight to the ceiling.

slab-on-grade floor: that portion of a slab floor of the building envelope that is in contact with the ground and that is either above grade or is less than or equal to 24 in. below the final elevation of the nearest exterior grade .

heated slab-on-grade floor: a slab-on-grade floor with a heating source either within or below it. unheated slab-on-grade floor: a slab-on-grade floor that is not a heated slab-on-grade floor .

small electric motor: a NEMA general purpose, alternating current, single-speed induction motor, built in a two-digit frame number series in accordance with NEMA Standards Publication MG1-1987, including IEC metric equivalent motors; constructed in the NEMA 42, 48, and 56 frame sizes or IEC metric equivalent.

solar energy source: source of thermal, chemical, or electrical energy derived from direct conversion of incident solar radiation at the building site .

solar heat gain coefficient (SHGC): the ratio of the solar heat gain entering the space through the fenestra- tion area to the incident solar radiation. Solar heat gain includes directly transmitted solar heat and absorbed solar radiation, which is then reradiated, conducted, or convected into the space . (See fenestration area .)

south-oriented: facing within 45 degrees of true south in the northern hemisphere; facing within 45 degrees of true north in the southern hemisphere.

space: an enclosed space within a building . The classifications of spaces are as follows for the purpose of determining building envelope requirements:

conditioned space: a cooled space, heated space, or indirectly conditioned space defined as follows:

a. cooled space: an enclosed space within a building that is cooled by a cooling system whose sensible

output capacity is  3.4 Btu/h·ft [2] of floor area. b. heated space: an enclosed space within a building that is heated by a heating system whose output

capacity relative to the floor area is greater than or equal to the criteria in Table 3.2. c. indirectly conditioned space: an enclosed space within a building that is not a heated space or a

cooled space, which is heated or cooled indirectly by being connected to adjacent spaces, provided

  1. the product of the U-factors and surface areas of the space adjacent to connected spaces exceeds the combined sum of the product of the U-factor s and surface areas of the space adjoining the outdoors, unconditioned spaces, and to or from semiheated spaces (e.g., corridors) or
  2. that air from heated or cooled spaces is intentionally transferred (naturally or mechanically) into the space at a rate exceeding 3 ach (e.g., atria). semiheated space: an enclosed space within a building that is heated by a heating system whose output capacity is greater than or equal to 3.4 Btu/h·ft [2] of floor area but is not a conditioned space . unconditioned space: an enclosed space within a building that is not a conditioned space or a semi- heated space . Crawlspaces, attics, and parking garages with natural or mechanical ventilation are not considered enclosed spaces .

space conditioning category:

a. nonresidential conditioned space (See nonresidential .) b. residential conditioned space (See residential .) c. nonresidential and residential semiheated space (See space .)

28 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 31

Open page note

Table 3.2 Heated Space CriteriaCol2
Climate ZoneHeating Output, Btu/h·ft2
0>5
1>5
2>5
3A, 3B>9
3C>7
4A, 4B>10
4C>8
5>12
6>14
7>16
8>19

standby power mode consumption (PW,SB): the power used by a product or appliance when enabled but in the standby operating mode (refer to 10 CFR 430).

steel-framed wall: see wall .

steel-joist floor: see floor .

story: portion of a building that is between one finished floor level and the next higher finished floor level or the roof, provided, however, that a basement or cellar shall not be considered a story.

structure: that which is built or constructed.

substantial contact: a condition where adjacent building materials are placed so that proximal surfaces are contiguous, being installed and supported so they eliminate voids between materials without compressing or degrading the thermal performance of either product.

swinging door: see door .

system: a combination of equipment and auxiliary devices (e.g., controls, accessories, interconnecting means, and terminal elements) by which energy is transformed so it performs a specific function, such as HVAC, service water heating, or lighting. ( Informative Note: This definition is not applicable to the use of this word in building envelope contexts such as, but not limited to, “curtain wall system,” “drainage system,” “fenestration system,” “framing system,” “roof system,” and “shading system.”)

task lighting: lighting directed to a specific surface or area that provides illumination for visual tasks.

temperature control throttling range: the number of degrees that room temperature must change in order to go from full heating to no heating or from full cooling to no cooling.

terminal: a device by which energy from a system is finally delivered, e.g., registers, diffusers, lighting fix- tures, faucets, etc.

thermal block: a collection of one or more HVAC zones grouped together for simulation purposes. Spaces need not be contiguous to be combined within a single thermal block .

thermal bridge: an element that has higher thermal conductivity than the surrounding materials, which creates a path of least resistance for heat transfer. For the purposes of determining building envelope requirements, the classifications for thermal bridges are defined as follows:

clear-field thermal bridge: elements of a building envelope assembly that are distributed over the area of the assembly and addressed in determining the thermal performance of the assembly in accordance with Normative Appendix A. Examples of clear-field thermal bridges include studs, webs and face shells of masonry units, ties, tracks, plates, girts and purlins for metal building envelopes, and fasteners. Fasteners used to construct assemblies in accordance with Normative Appendix A are not considered nor separately defined as point thermal bridges . linear thermal bridge: a length-based element associated with horizontal, vertical, or diagonal elements that penetrates the insulation in the building envelope and with length measured along the exterior sur

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 29

PDF Page 32

Open page note

face of the building envelope . Examples of linear thermal bridges include edges of floors, balconies, columns and beams in the plane of an assembly, parapets, roof-wall-floor intersections, fenestration interfaces, shelf angles, and similar conditions not otherwise defined as a clear field thermal bridge or point thermal bridge . point thermal bridge: a discrete element that penetrates the insulation in the building envelope . Examples of point thermal bridges include a beam penetrating a wall, a column penetrating a roof or floor, and an anchor or connection used to attach an element to the building and not otherwise defined as a clear field thermal bridge or linear thermal bridge . The cross-sectional area of the point thermal bridge is measured at the outer surface of the outermost layer of insulation that is penetrated by the element.

thermal conductance (C-factor): time rate of steady-state heat flow through unit area of a material or con- struction, induced by a unit temperature difference between the body surfaces (Btu/h·ft [2] ·°F). Note that the C-factor does not include soil or air films.

thermal resistance (R-value): the reciprocal of the time rate of heat flow through a unit area induced by a unit temperature difference between two defined surfaces of material or construction under steady-state conditions (h·ft [2] ·°F/Btu).

thermal transmittance (U-factor): heat transmission in unit time through unit area of a material or construc- tion and the boundary air films, induced by unit temperature difference between the environments on each side (Btu/h·ft [2] ·°F).

thermally effective panel surface: any exterior surface of a panel that is intended to transfer heat between the panel and the occupants and/or the indoor space .

thermally ineffective panel surface: any exterior surface of a panel that is not intended to transfer heat between the panel and the occupants and/or the indoor space .

thermostat: an automatic control device used to maintain temperature at a fixed or adjustable set point .

thermostatic control: an automatic control device or system used to maintain temperature at a fixed or adjustable set point .

tinted: (as applied to fenestration ) bronze, green, blue, or gray coloring that is integral with the glazing material. Tinting does not include surface-applied films such as reflective coatings, applied either in the field or during the manufacturing process.

toplighting: lighting building interiors with daylight admitted through fenestration, such as skylights and roof monitors, located on the roof .

total system performance ratio (TSPR): ratio of the sum of a building’s annual heating and cooling load in kBtu to the sum of annual energy input of the building mechanical systems, where the input units are in accordance with Section L5.

transfer air: air transferred from one room to another through openings in the room envelope, whether it is transferred intentionally or not. The driving force for transfer air is generally a small pressure differential between the rooms, although one or more fans may be used.

transformer: a piece of electrical equipment used to convert electric power from one voltage to another voltage.

dry-type transformer: a transformer in which the core and coils are in a gaseous or dry compound.

trim compressor: a compressor that is designated for part-load operation, handling the short-term variable trim load of end uses in addition to the fully loaded base compressors.

TSPR reference building design: a computer representation of a hypothetical building design based on modifications to the proposed design in accordance with Section L4.3. This representation is used as the basis for calculating the mechanical total system performance ratio for determining alternative mechanical system performance in accordance with Section 6.6.2.

U-factor: see thermal transmittance .

unconditioned space: see space .

unenclosed space: a space that is not an enclosed space .

unitary air conditioners: one or more factory-made assemblies that normally include an evaporator or cooling coil and a compressor and condenser combination. Units that perform a heating function are also included.

30 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 33

Open page note

unitary heat pump: one or more factory-made assemblies that normally include an indoor conditioning coil, compressors, and an outdoor refrigerant-to-air coil or refrigerant-to-water heat exchanger. These units provide both heating and cooling functions.

unmet load hour: an hour in which one or more zones is outside of the thermostat set point plus or minus one half of the temperature control throttling range . Any hour with one or more zones with an unmet cooling load or unmet heating load is defined as an unmet load hour .

unregulated energy use: energy used by building systems and components that is not regulated energy use . (See regulated energy use .)

variable-air-volume (VAV) system: HVAC system that controls the dry-bulb temperature within a space by varying the volumetric flow of heated or cooled supply air to the space .

variable-refrigerant-flow (VRF) system: an engineered direct expansion (DX) multisplit system incorporating at least one variable capacity compressor distributing refrigerant through a piping network to multiple indoor fan-coil units, each capable of individual zone temperature control, through integral zone temperature control devices and common communications network. Variable refrigerant flow uses three or more steps of control on common, interconnecting piping .

vegetative roof system: vegetation, growth media, drainage system, and waterproofing over a roof deck.

vent damper: a device intended for installation in the venting system of an individual, automatically operated, fossil- fuel -fired appliance in the outlet or downstream of the appliance draft control device, which is designed to automatically open the venting system when the appliance is in operation and to automatically close off the venting system when the appliance is in a standby or shutdown condition.

ventilation: the process of supplying or removing air by natural or mechanical means to or from any space . Such air is not required to have been conditioned.

ventilation system motor nameplate horsepower (hp): the sum of the motor nameplate horsepower of all fans that are required to operate as part of the system .

verification and testing provider (V&T provider): an entity who completes the activities needed to implement the building functional performance testing ( FPT ) activities or verify that elements of the building project meet stated requirements.

vertical fenestration: all fenestration other than skylights . Trombe wall assemblies, where glazing is installed within 12 in. of a mass wall, are considered walls, not fenestration . For the purposes of determining building envelope requirements, the vertical fenestration classifications are defined as follows:

entrance door: any doorway, set of doors, turnstile, vestibule, or other form of portal that is ordinarily used to gain access by its users and occupants to the building or to individual tenant spaces accessed from the exterior. (See building entrance and door .)

fixed: all types of vertical fenestration, other than entrance door and operable, including, but not limited to, curtain walls, window walls, fixed windows, picture windows, glass block walls, nonopenable clerestory windows, roof monitors with nonopenable windows, and nonopenable sidelights and transoms.

operable: all vertical fenestration that opens, except entrance doors, including, but not limited to, casement windows, projecting windows, pivoting windows, horizontal sliding windows, vertical sliding windows, openable clerestory windows, openable sidelights and transoms, sliding glass doors, roof monitors with openable windows, and doors that are not entrance doors .

visible transmittance (VT): the ratio of visible radiation entering the space through the fenestration product to the incident visible radiation, determined as the spectral transmittance of the total fenestration system, weighted by the photopic response of the eye and integrated into a single dimensionless value.

voltage drop: a decrease in voltage caused by losses in the lines connecting the power source to the load.

VT: see visible transmittance .

walk-in cooler: an enclosed storage space of <3000 ft [2] that can be walked into and that is designed to maintain a space temperature of >32°F and  55°F.

walk-in freezer: an enclosed storage space of <3000 ft [2] that can be walked into that is designed to maintain a space temperature of  32°F.

wall: that portion of the building envelope, including opaque area and fenestration, that is vertical or tilted at an angle of 60 degrees from horizontal or greater. This includes above- and below-grade walls, between

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 31

PDF Page 34

Open page note

floor spandrels, peripheral edges of floors, and foundation walls . For the purposes of determining building envelope requirements, the classifications are defined as follows:

above-grade wall: a wall that is not a below-grade wall . below-grade wall: that portion of a wall in the building envelope that is entirely below the finish grade and in contact with the ground. mass wall: a wall with a heat capacity exceeding (a) 7 Btu/ft [2] ·°F or (b) 5 Btu/ft [2] ·°F, provided that the wall has a material unit weight not greater than 120 lb/ft [3] . metal building wall: a wall whose structure consists of metal spanning members supported by steel structural members (i.e., does not include spandrel glass or metal panels in curtain wall systems). steel-framed wall: a wall with a cavity (insulated or otherwise) whose exterior surfaces are separated by steel framing members (i.e., typical steel stud walls and curtain wall systems). wood-framed and other walls: all other wall types, including wood stud walls .

wall area, gross: the area of the wall measured on the exterior face from the top of the floor to the bottom of the roof .

warm-up: increase in space temperature to occupied set point after a period of shutdown or setback .

water heater: vessel in which water is heated and is withdrawn for use external to the system .

west-oriented: facing within 45 degrees of true west to the south and within less than 22.5 degrees of true west to the north in the northern hemisphere; facing within 45 degrees of true west to the north and within less than 22.5 degrees of true west to the south in the southern hemisphere.

wood-framed and other floors: see floor .

wood-framed and other walls: see wall .

3.3 Abbreviations and Acronyms

χ chi-factor, thermal transmittance of a point thermal bridge

Ψ psi-factor, thermal transmittance per unit length of a linear thermal bridge

ac alternating current

ach air changes per hour

AFUE annual fuel utilization efficiency

AHAM Association of Home Appliance Manufacturers

ANSI American National Standards Institute

AHRI Air-Conditioning, Heating and Refrigeration Institute

AMCA Air Movement Control Association

ASTM ASTM International

BEP best efficiency point

( fan ) bhp ( fan) brake horsepower

BSR Board of Standards Review

Btu British thermal unit

Btu/h British thermal unit per hour

Btu/ft [2] ·°F British thermal unit per square foot per degree Fahrenheit

Btu/h·ft [2] British thermal unit per hour per square foot

Btu/h·ft·°F British thermal unit per hour per linear foot per degree Fahrenheit

Btu/h·ft [2] ·°F British thermal unit per hour per square foot per degree Fahrenheit

CDD cooling degree-day

CDD 50 cooling degree-days base 50°F

CEER combined energy efficiency ratio

CFEI ceiling fan energy index

32 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 35

Open page note

cfm cubic feet per minute

CHW chilled water

CHWST chilled-water supply temperature

c.i. continuous insulation

COP coefficient of performance

COPH coefficient of performance, heat pump—heating

COPHR heat recovery coefficient of performance

COPSHC simultaneous cooling and heating coefficient of performance

CTI Cooling Technology Institute

CV constant volume

db dry-bulb

DCV demand control ventilation

DDC direct digital control

DOAS dedicated outdoor air system

DOE U.S. Department of Energy

DX direct expansion

Ec combustion efficiency

EER / EER2 energy efficiency ratio

EF energy factor

ER energy recovery

Et thermal efficiency

ESCC end-suction close-coupled

ESFM end-suction frame-mounted/own-bearings

°F Fahrenheit

FC filled cavity

FEI fan energy index

FL full-load

FPT functional performance testing

FPTU fan-powered terminal unit

ft foot

gr grains of moisture per pound of dry air

h hour

HC heat capacity

HDD heating degree-day

HDD 65 heating degree-days base 65°F

h·ft [2] ·°F/Btu hour per square foot per degree Fahrenheit per British thermal unit

HW heating water

HWST heating-water supply temperature

HID high-intensity discharge

hp horsepower

HSPF/HSPF2 heating seasonal performance factor

HVAC heating, ventilating, and air conditioning

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 33

PDF Page 36

Open page note

HVACR heating, ventilating, air conditioning, and refrigeration

IEC International Electrotechnical Commission

IEER integrated energy efficiency ratio

IES Illuminating Engineering Society

IL inline

in. inches

I-P inch-pound

IPLV .IP integrated part-load value

ISCOP integrated seasonal coefficient of performance

ISMRE integrated seasonal moisture removal efficiency

IT information technology

J joule

K kelvin

kJ kilojoule

kVA kilovolt-ampere

kW kilowatt

L length of a linear thermal bridge

LED light-emitting diode

lb pound

lin linear

lin ft linear foot

LPA maximum lighting power allowance in watts (W)

LPD lighting power density

Ls liner system

LSG light-to-solar-gain ratio

MICA Midwest Insulation Contractors Association

min. minimum

MPF mechanical performance factor

MRE moisture removal efficiency

MSH monitor seal height

n number of occurrences a point thermal bridge

NAECA U.S. National Appliance Energy Conservation Act

NEMA National Electric Manufacturers Association

NFPA National Fire Protection Association

NFRC National Fenestration Rating Council

NPLV .IP nonstandard part-load value

OAT outdoor air temperature (dry-bulb unless wet-bulb is specified)

OA outdoor air

PEI pump energy index

PER pump energy rating

PF projection factor

PFP parallel fan-powered

34 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 37

Open page note

PPE photosynthetic photon efficacy

PRV power roof/wall ventilator

PSZ-AC packaged single-zone air conditioner

PSZ-HP packaged single-zone heat pump

PTAC packaged terminal air conditioner

PTHP packaged terminal heat pump

R R-value ( thermal resistance )

RAT return air temperature (dry-bulb unless wet-bulb is specified)

Rc thermal resistance of a material or construction from surface to surface

RCR room cavity ratio

Ru total thermal resistance of a material or construction including air film resistances

rpm revolutions per minute

RSV radially split, multistage, vertical, inline diffuser casing

SAT supply air temperature (dry-bulb unless wet-bulb is specified)

SC shading coefficient

SEER / SEER2 seasonal energy efficiency ratio

SERR series energy recovery ratio

SHGC solar heat gain coefficient

SHW service hot water

SL standby loss

SMACNA Sheet Metal and Air Conditioning Contractors’ National Association

SPVAC single-package vertical air conditioner

SPVHP single-package vertical heat pump

ST submersible turbine

SZ single zone

Tdb dry-bulb temperature

TDA total display area

TSPR total system performance ratio

TSPRp TSPR of a proposed design

TSPRr TSPR of a TSPR reference building design

Twb wet-bulb temperature

UPS uninterruptible power supply

VAV variable air volume

VRF variable refrigerant flow

VSD variable-speed drive

VT visible transmittance (also known as visible light transmittance [VLT])

V&T verification and testing

W watt

wb wet-bulb

W/ft [2] watts per square foot

WF well factor

Wh watt-hour

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 35

PDF Page 38

Open page note

4. ADMINISTRATION AND ENFORCEMENT

4.1 General

4.1.1 Scope

4.1.1.1 New Buildings. New buildings shall comply with the standard as described in Section 4.2.

4.1.1.2 Additions to Existing Buildings. Additions to existing buildings shall comply with the standard as described in Section 4.2.

4.1.1.3 Alterations of Existing Buildings. Alterations of existing buildings shall comply with the standard as described in Section 4.2.

4.1.1.4 Replacement of Portions of Existing Buildings. Portions of a building envelope, heating, ventilating, air-conditioning, service water heating, power, lighting, and other systems and equipment that are being replaced shall be considered as alterations of existing buildings and shall comply with the standard as described in Section 4.2.

4.1.1.5 Changes in Space Conditioning. Whenever unconditioned space or semiheated space in a building is converted to a conditioned space, such conditioned space shall be brought into compliance with all the applicable requirements of this standard that would apply to the building envelope, heating, ventilating, air-conditioning, service water heating, power, lighting, and other systems and equipment of the space as if the building was new.

4.1.1.6 Sites and New Site Systems and Equipment. Sites, with or without a contiguous building or buildings, and s ite systems and equipment using or producing energy, such as site lighting, motors for pumps (for example, fountain pumps and water movement equipment ), and transportation equipment (for example, elevators and escalators) shall comply with the standard as described in Section 4.2 for systems and equip- ment specifically identified in the standard.

4.1.2 Administrative Requirements. Administrative requirements relating to permit requirements, enforcement by the authority having jurisdiction, locally adopted energy standards, interpretations, claims of exemption, and rights of appeal are specified by the authority having jurisdiction .

4.1.3 Alternative Materials, Methods of Construction, or Design. The provisions of this standard are not intended to prevent the use of any material, method of construction, design, equipment, or building sys- tem not specifically prescribed herein.

4.1.4 Validity. If any term, part, provision, section, paragraph, subdivision, table, chart, or referenced standard of this standard shall be held unconstitutional, invalid, or ineffective, in whole or in part, such determination shall not be deemed to invalidate any remaining term, part, provision, section, paragraph, subdivision, table, chart, or referenced standard of this standard.

4.1.5 Other Laws. The provisions of this standard shall not be deemed to nullify any provisions of local, state, or federal law. Where there is a conflict between a requirement of this standard and such other law affecting construction of the building, precedence shall be determined by the authority having jurisdiction .

4.1.6 Referenced Standards. The standards referenced in this standard and listed in Section 13 shall be considered part of the requirements of this standard to the prescribed extent of such reference. Where differences occur between the provision of this standard and referenced standards, the provisions of this standard shall apply. Informative references are cited to acknowledge sources and are not part of this standard. They are identified in Informative Appendix E.

4.1.7 Normative Appendices. The normative appendices to this standard are considered to be integral parts of the mandatory requirements of this standard, which, for reasons of convenience, are placed apart from all other normative elements.

4.1.8 Informative Appendices. The informative appendices to this standard, and informative notes located within this standard, contain additional information and are not mandatory or part of this standard.

4.1.9 Reference Standard Reproduction Annex. The reference standard reproduction annex contains material that is cited in this standard but contained in another standard. The reference standard reproduction annex is not part of this standard but is included in the publication of this standard to facilitate use of this standard.

4.2 Compliance

4

4.2.1 Compliance Paths

visions of

36 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 39

Open page note

existing buildings, and/or alterations to existing buildings shall be less than or equal to the Performance Cost Index Target (PCI t ) when calculated in accordance with the following:

PCI t =  BBUEC + BPF   BBREC  - PRE   BBP

where PCI = Performance Cost Index calculated in accordance with Section G1.2.2 BBUEC = baseline building unregulated energy cost, the portion of the annual energy cost of a baseline building design that is due to unregulated energy use BPF = building performance factor from Table 4.2.1.1. For building area types not listed in Table

Table 4.2.1.1. BBREC = baseline building regulated energy cost, the portion of the annual energy cost of a baseline building design that is due to regulated energy use PRE = PBP nre - PBP pre PBP = proposed building performance, including the reduced, annual purchased energy cost associated with all on-site renewable energy generation systems PBP nre = proposed building performance without any credit for reduced annual energy costs from on- site renewable energy generation systems PBP pre = proposed building performance, excluding any renewable energy system in the proposed design and including an on-site renewable energy system that meets but does not exceed the requirements of Section 10.5.1.1 modeled following the requirements for a budget building

design in Table 12.5.1, row 15 BBP = baseline building performance Regulated energy cost shall be calculated by multiplying the total energy cost by the ratio of regulated energy use to total energy use for each fuel type. Unregulated energy cost shall be calculated by subtracting regulated energy cost from total energy cost. MOST OF OREGON,Col2Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Table 4.2.1.1 Building Performance Factor (BPF)
MOST OF OREGON,
SEE 90.1-22 ERRATA LIST OF COUNTIES
Building
Area Type
Climate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate Zone
Building
Area Type
0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.690.680.710.700.720.720.710.760.630.690.760.710.660.720.710.650.670.650.67
Healthcare/hospital0.690.690.700.680.670.650.650.660.640.640.660.630.670.650.650.660.670.680.70
Hotel/motel0.660.660.690.650.650.640.640.650.650.630.650.630.620.630.620.610.620.590.58
Office0.540.540.530.520.520.520.500.540.480.480.530.480.490.520.480.480.490.460.48
Restaurant0.620.590.570.570.570.530.570.530.510.550.540.540.570.560.550.590.580.610.64
Retail0.510.490.480.480.440.430.430.430.440.420.430.460.430.420.470.430.430.410.44
School0.520.570.570.560.520.530.520.490.500.460.470.470.470.460.460.460.440.450.45
Warehouse0.260.260.220.250.210.220.250.210.190.250.220.220.280.240.220.310.280.290.32
All others0.620.600.620.590.550.510.530.520.550.530.520.550.530.530.560.540.540.540.54

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 37

PDF Page 40

Open page note

When (PBP pre - PBP)/BBP > 0.05, new buildings, additions to existing buildings, and/or alterations to existing buildings shall comply with the following:

PCI + [(PBP pre - PBP)/BBP] – 0.05 < PCI t Informative Notes:

  1. PBP nre = proposed building performance, no renewable energy .
  2. PBP pre = proposed building performance, prescriptive renewable energy .
  3. PRE = prescriptive renewable energy .
  4. See Informative Appendix I for using other metrics, including site energy, source energy, and carbon emissions, in conjunction with the Normative Appendix G Performance Rating Method when approved by the rating authority .

4.2.1.2 Additions to Existing Buildings. Additions to existing buildings shall comply with the provisions of Section 4.2.2 through 4.2.5 and one of the following:

a. Sections 5, “Building Envelope”; 6, “Heating, Ventilating, and Air Conditioning”; 7, “Service Water

Heating”; 8, “Power”; 9, “Lighting”; 10, “Other Equipment”; and 11, “Additional Efficiency Requirements,” or b. Section 12, “Energy Cost Budget Method,” or c. Normative Appendix G, “Performance Rating Method,” in accordance with Section 4.2.1.1.

4.2.1.2.1 When an addition to an existing building cannot comply by itself, trade-offs will be allowed by modification to one or more of the existing components of the existing building . Modeling of the modified components of the existing building and addition shall employ the procedures of Section 12 or Normative Appendix G; the addition shall not increase the energy consumption of the existing building plus the addition beyond the energy that would be consumed by the existing building plus the addition if the addition alone did comply.

4.2.1.3 Alterations of Existing Building Assemblies, Systems, and Equipment. Alterations of exist- ing building assemblies, systems, and equipment shall comply with the provisions of Section 4.2.2 through 4.2.5 and one of the following:

a. Sections 5, “Building Envelope”; 6, “Heating, Ventilating, and Air Conditioning”; 7, “Service Water

Heating”; 8, “Power”; 9, “Lighting”; 10, “Other Equipment”; and 11, “Additional Efficiency Requirements,” or b. Section 12, “Energy Cost Budget Method,” or c. Normative Appendix G, “Performance Rating Method,” in accordance with Section 4.2.1.1 with the fol lowing modifications:

  1. Alterations that meet the criteria in Section G3.1.4(a) shall use the BPF from Table 4.2.1.1 multiplied by 1.05.

  2. All other alterations modeled following Section G3.3 shall use BPF = 1.

Exceptions to 4.2.1.3: A building that has been specifically designated as historically significant by the

adopting authority or is listed in The National Register of Historic Places or has been determined to be eligible for listing by the U.S. Secretary of the Interior need not comply with these requirements.

4.2.1.4 New Sites and New Site Systems and Equipment. New sites and new site systems and equip- ment shall comply with either the provisions of

a. Sections 6, “Heating, Ventilating, and Air Conditioning”; 7, “Service Water Heating”; 8, “Power”; 9,

“Lighting”; and 10, “Other Equipment,” or b. Section 12, “Energy Cost Budget Method.”

4.2.1.5 Additions and Alterations to Existing Sites and Site Systems and Equipment. Additions and alterations to existing sites and existing site systems and equipment shall comply with the provisions of Sections 5, 6, 7, 8, 9, and 10, or Section 11. This section shall not apply to buildings on the site where the alterations or additions are to be performed except as required by Sections 4.2.1.2 and 4.2.1.3.

4.2.2.1 Construction Details. Compliance documents shall show all the pertinent data and features of the building, equipment, and systems in sufficient detail to permit a determination of compliance by the building official and to indicate compliance with the requirements of this standard.

38 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 41

Open page note

4.2.2.2 Supplemental Information. Supplemental information necessary to verify compliance with this standard, such as calculations, worksheets, compliance forms, vendor literature, or other data, shall be made available when required by the building official .

4.2.2.3 Manuals. Operating and maintenance information shall be provided to the building owner. This information shall include but not be limited to the information specified in Sections 5.7.3.2, 6.7.3.2, 7.7.3.2, 8.7.3.2, 9.7.3.2, and 10.7.3.2. 4.2.3 Labeling of Material and Equipment. Materials and equipment shall be labeled in a manner that will allow for a determination of their compliance with the applicable provisions of this standard.

4.2.4 I nspections. All building construction, additions, or alterations work subject to the provisions of this standard shall remain accessible and exposed for inspection purposes until approved in accordance with the procedures specified by the building official . The building official, upon notification, shall make the inspections set forth in Section 4.2.4.1 through 4.2.4.6.

4.2.4.1 Fenestration Inspections. Fenestration shall be inspected in accordance with the compliance path selected in Section 4.2.1 and approved documentation provided in Section 4.2.2.

4.2.4.2 Opaque Assembly Thermal Insulation Inspections. Opaque assemblies shall be inspected in accordance with the compliance path selected in Section 4.2.1 and approved documentation provided in Section 4.2.2.

4.2.4.3 Continuous-Air-Barrier Inspections. Where a continuous air barrier is installed as a component of an opaque roof, above-grade walls and below-grade walls, or floors, it shall be inspected for compliance in accordance with Section 5.8.3.1. Integration with adjoining fenestration and other continuous air barrier elements shall be in accordance with Section 5.4.3.1.

4.2.4.4 Operable Fenestration and Door Inspections. Fenestration and door closers, inclusive of operating mechanisms, shall be installed in accordance with the manufacturer ’s installation instructions. Associated seals and gaskets shall be installed in accordance with the manufacturer ’s installation instructions and consistent with the provisions of Section 5.4.3.

4.2.4.5 Loading-Dock Weatherseals Inspections. Loading-dock weatherseals shall be inspected for installation and to verify that the seals are in good condition.

4.2.4.6 Other Inspections. Other inspections related to mechanical, plumbing, lighting, and other equipment shall be inspected in accordance with the compliance path selected in Section 4.2.1 and approved documentation provided in Section 4.2.2, or as otherwise required by the building official .

Informative Notes:

.1: CDs: ID V&T Provider, FPT Scope of Documentation + Verification. .2: BECx: Now required per ASHRAE IES Standard 202 or other standard. .3: Owner Letter to AHJ prior to Occupancy OR reports if AHJ asks. :)

  1. There are additional requirements within specific sections of this standard regarding documentation, procedures, independence of providers, and reporting. Requirements in individual sections are in addition to the general requirements provided in Section 4.2.5.
  2. See Informative Appendix H for additional commissioning guidance. 4.2.5.1 Building Systems Verification and Testing Requirements. Verification or functional perfor- mance testing ( FPT ) to confirm compliance with required provisions of this standard shall be performed on building systems, controls, and the building envelope, as required by Sections 5.9.1, 6.9.1, 7.9.1, 8.9.1, 9.9.1, 10.9.1, 12.2(e), and G1.2.1(e). Where testing is required but specific FPT procedures are not specified in this main verif design + install AB standard, testing shall use generally accepted engineering standards acceptable to the building official .

For alterations and additions, verification and testing (V&T) shall be performed for new systems, and their interface and integration with existing building systems shall be verified or tested.

4.2.5.1.1 Information on Building Permit Application. The following information shall be included on th e construction documents as part of the building permit application:

a. For systems that are required to comply with Section 4.2.5.1, the construction documents shall identify

V&T providers. b. V&T providers shall review the construction documents to verify that the relevant sensor locations,

devices, and control sequences are properly specified; performance and testing criteria are included; and equipment to be tested is accessible for testing and maintenance.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 39

PDF Page 42

Open page note

the deferred tests. A copy of verification and FPT documentation shall be submitted to the building official if requested.

4.2.5.2 Building Commissioning Requirements. Commissioning shall be performed in accordance with this section and Sections 5.9.2, 6.9.2, 7.9.2, 8.9.2, 9.9.2, 10.9.2, 12.2(e), and G1.2.1(f). Commissioning shall use ASHRAE/IES Standard 202 or other generally accepted engineering standards acceptable to the building official . FPT and verification requirements for commissioning are as stated in Section 4.2.5.1. Com-

ing envelope with required provisions of this standard. Commissioning requirements shall be incorporated into the construction documents .

The commissioning provider shall have the necessary training, experience, and FPT equipment . The

Exceptions to 4.2.5.2:

EXCEPTIONS ARE FOR MECH, BUT 4.2.5.2 LINE 2 STATES 5.9.2 FOR AIR BARRIERS.

  1. Buildings, additions, or alterations with less than 10,000 ft [2] of conditioned space and combined heating, cooling, and service water heating equipment totaling less than 960,000 Btu/h in capacity.
  2. Buildings or portions of buildings that use the simplified approach building compliance path for HVAC systems in Section 6.3.
  3. Dwelling units . DOES THIS EXCEPTION MEAN COMMISSIONING IS NOT REQUIRED IN PORTIONS OF BUILDINGS WITH DWELLING UNITS?
  4. Nonrefrigerated warehouses.

4.2.5.2.1 Commissioning Activities Prior to Building Permit Issuance. The following activities shall be completed prior to issuance of a building permit:

a. A copy of the commissioning plan shall be submitted to the owner. A copy of the commissioning plan

shall be submitted with the building permit application if requested by the building official . b. A commissioning provider shall be designated by the owner to manage commissioning activities prior to

completion of construction documents . The construction documents shall identify the commissioning provider . c. The commissioning provider shall submit the design review report to the owner. d. Construction phase commissioning requirements shall be incorporated into construction documents .

4.2.5.2.2 Project Commissioning Documents. Project commissioning documents shall comply with ASHRAE/IES Standard 202 or other generally accepted engineering standards acceptable to the building official. The commissioning provider shall certify completion of the required commissioning process and provide the following documents to the owner and design teams:

a. Commissioning Plan. Identify FPT or verification procedures for all systems to be verified, commis sioned, or tested. b. Design Review Report. Detail compliance of the design with the Owner’s Project Requirements and

provisions of this standard. This commissioning design review shall not be considered a design peer review or a code or regulatory review. c. Preliminary Commissioning Report. The preliminary commissioning report shall include the following:

  1. Required performance of commissioned equipment, systems, and assemblies, and results of FPT and verification

  2. Summary of compliance of the building and its components, assemblies, controls, and systems with required provisions of this standard

  3. Issues and resolution logs, including itemization of deficiencies found during verification, testing, and commissioning that have not been corrected at the time of report preparation

  4. Deferred tests that cannot be performed at the time of report preparation

40 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 43

Open page note

  1. Documentation of the training of operating personnel and building occupants on commissioned sys- tems, and a plan for the completion of any deferred trainings not completed at the time of report preparation
  2. A plan for the completion of commissioning and training, including climatic and other conditions required for performance of the deferred tests d. Final Commissioning Report. T he construction documents shall require the commissioning provider to

provide a final commissioning report to the owner before completion of the contractor’s general warranty period. 4.2.5.3 Activities Prior to Building Occupancy. B efore issuance of a certificate of occupancy, the V&T providers or commissioning provider shall complete the following activities:

a. Verification and FPT of the systems specified in Section 4.2.5.1 shall be completed and documented.

Exception to 4.2.5.3(a): Systems for which operation is seasonally dependent, and which cannot be fully

verified or tested at the time of occupancy, shall be functionally tested or commissioned when allowed for by post-occupancy operating conditions as determined by the commissioning or V&T providers. b. The owner shall be provided with the verification and FPT documentation as provided for in Section

4.2.5.1.2, or a preliminary commissioning report as provided for in Section 4.2.5.2.2. c. The owner shall provide the building official with one of the following:

  1. A copy of the reports listed in Section 4.2.5.3(b), if requested by the building official

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 41

PDF Page 44

Open page note

5. BUILDING ENVELOPE

5.1 General

5.1.1 Scope. Section 5 specifies requirements for the building envelope .

5.1.2 New Buildings. Building envelope components installed in new buildings shall comply with the requirements of Section 5.2. 2nd choice: prescriptive or trade-off w/ required for all paths.

5.1.3 Additions to Existing Buildings. Building envelope components installed in additions shall comply with the requirements of Section 5.2.

5.1.4 Alterations to Building Envelopes. Alterations to the building envelope shall comply with the requirements of Section 5.2 for insulation, air leakage, and fenestration applicable to those specific portions of the building that are being altered.

Exceptions to 5.1.4: The following alterations need not comply with these requirements, provided such

alterations will not increase the energy use of the building :

  1. Installation of storm windows or glazing panels over existing glazing, provided the storm window or glazing panel contains a low-emissivity coating. However, a low-emissivity coating is not required where the existing glazing already has a low-emissivity coating. Installation is permitted to be either on the inside or outside of the existing glazing.
  2. Replacement of glazing in existing sash and frame, provided the U-factor and SHGC will be equal to or lower than before the glass replacement.
  3. Alterations to roof, wall, or floor cavities that are insulated to full depth with insulation having a minimum nominal value of R-3.0/in.
  4. Alterations to walls and floors, where the existing structure is without framing cavities and no new framing cavities are created.

element requirements for roofs in Tables 5.5-0 through 5.5-8 and Section 5.5.3.1.4. 8. Replacement of existing doors that separate a conditioned space from the exterior shall not require the installation of a vestibule or revolving door, provided that an existing vestibule that separates a conditioned space from the exterior shall not be removed.

42 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 45

Open page note

  1. Replacement of existing fenestration, provided that the area of the replacement fenestration does not exceed 25% of the total fenestration area of an existing building and that the U-factor and

lation requirements in Section 5.5.3.1.1 cannot be met due to existing roof conditions, the roof replacement shall be constructed in accordance with approved construction documents, which shall include

a. a roof inspection report documenting existing roof conditions and b. a roof design minimizing deviation from the requirements of Section 5.5.3.1.1.

Informative Note: The proposed roof design should be prepared by an approved entity capable of determining whether the design complies with the requirements of Section 5.1.4.1 to the extent practical.

5.1.5 Climate. Determine the climate zone for the location. For U.S. locations, follow the procedure in Section 5.1.5.1. For international locations, follow the procedure in Section 5.1.5.2.

Exception to 5.1.5.1: If there are recorded historical climatic data available for a construction site, they

may be used to determine compliance if approved by the building official .

Informative Note: Annex 1 (included at the end of this document) contains an extraction from ASHRAE Standard 169, Table B-1, “U.S. Climate Zones by State and County.”

5.1.5.2 International Locations. For locations in Canada that are listed in ASHRAE Standard 169, Table A-5, “Canada Stations and Climate Zones,” use this table to determine the required assigned climate zone number and, where required, the assigned climate zone letter. For locations in other international countries that are listed in ASHRAE Standard 169, Table A-6, “International Stations and Climate Zones,” use this table to determine the required climate zone number and, where required, the assigned climate zone letter. For all international locations that are not listed either in ASHRAE Standard 169, Table A-5, “Canada Stations and Climate Zones,” or ASHRAE Standard 169, Table A-6, “International Stations and Climate Zones,” use ASHRAE Standard 169, Section A3, “Climate Zone Definitions,” and Table A-3, “Thermal Climate Zone Definitions,” to determine both the climate zone number and letter.

Informative Note: Annex 1 (included at the end of this document) contains extractions from ASHRAE Standard 169, Table A-5, “Canada Stations and Climate Zones”; ASHRAE Standard 169, Table A-6, “International Stations and Climate Zones”; ASHRAE Standard 169, Section A3, “Climate Zone Definitions”; and Table A-3, “Thermal Climate Zone Definitions.”

5.1.6 Space Conditioning Categories 5.1.6.1 Separate building envelope requirements are specified for (a) nonresidential conditioned space, (b) residential conditioned space, and (c) semiheated space .

5.1.6.2 The minimum skylight area requirements in Section 5.5.4.2.3 are also specified for uncondi- tioned spaces .

5.1.6.3 Spaces shall be assumed to be conditioned spaces and shall comply with the requirements for conditioned spaces at the time of construction, regardless of whether mechanical or electrical equipment is included in the building permit application or installed at that time.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 43

PDF Page 46

Open page note

5.3 Simplified Building Compliance Path (Not Used)

PRESCRIPTIVE TRADE-OFF

INSTALL AND LABEL PRODUCTS CORRECTLY

SEMIEXTERIOR AIR BARRIER EXCEPTION.

3

5.4 Mandatory Provisions requirements found in Section 5.8.1. 5.4.1 Insulation. Where insulation is required in Section 5.5 or Section 5.6, it shall comply with the INSTALL AND LABEL PRODUCTS CORRECTLY PRESCRIPTIVE TRADE-OFF

5.4.2 Fenestration and Doors. Procedures for determining fenestration and door performance are described in Section 5.8.2. Product samples used for determining fenestration performance shall be production line units or representative of units purchased by the consumer or contractor.

5.4.3 Air Leakage

a. Air leakage control for the building envelope shall comply with this section. Materials and assemblies

that are part of the continuous air barrier and fenestration and doors shall comply with Section 5.8.3.

air barrier of an adjacent conditioned space . 2. Single wythe concrete masonry buildings in Climate Zone 2B.

leakage of the building envelope shall not excee d 0.35 cfm/ft [2] under a pressure differential of 75 Pa (0.30 in. of water), with this air leakage rate normalized by the sum of the above- grade and below- grade building envelope areas of the conditioned space and semiheated space and in accordance with this section.

a. Whole- building pressurization testing shall be conducted in accordance with ASTM E3158. For buildings

less than 10,000 ft [2] of gross conditioned floor area, and that contain no more than one single-zone system, air leakage testing may be conducted in accordance with ASTM E779, ASTM E1827, or ASTM E3158. Testing shall be conducted excluding HVAC related elements and be performed by an independent thirdparty verification and testing provider in accordance with Section 4.2.5.1. b. Where a building contains both conditioned space and semiheated space, compliance shall be shown

using one of the following as applicable:

  1. Separately for the conditioned space and for the semiheated space, with the air leakage rate for the conditioned space normalized by the exterior building envelope area of the conditioned space and the air leakage rate for the semiheated space normalized by the semiexterior building envelope area of the semiheated space
  2. For the conditioned space and for the semiheated space together, with the air leakage rate for the overall space normalized by the sum of the exterior building envelope area and the semiexterior building envelope area minus the semiexterior building envelope area that separates the conditioned space from the semiheated space c. Where the measured air leakage rate exceeds 0.35 cfm/ft [2] but does not exceed 0.45 cfm/ft [2], a diagnostic

evaluation, such as a smoke tracer or infrared imaging, shall be conducted while the building is pressurized, and any leaks noted shall be sealed if such sealing can be made without destruction of existing building components. In addition, a visual inspection of the air barrier shall be conducted, and any leaks noted shall be sealed if such sealing can be made without destruction of existing building components.

44 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 47

Open page note

An additional report identifying the corrective actions taken to seal leaks shall be submitted to the code official and the building owner and shall be deemed to satisfy the requirements of this section. d. Where the measured air leakage rate exceeds 0.45 cfm/ft [2], corrective actions must be made to the enve-

lope and an additional test completed where results are 0.45 cfm/ft [2] or less in order to demonstrate compliance. e. Reporting shall be in compliance with Section 4.2.5.1.2.

5.4.3.2 Continuous Air Barrier Design and Installation. The continuous air barrier shall be designed and installed in the following manner:

c. The continuous air barrier shall extend over all surfaces of the building envelope and be identified in the

construction documents to be continuous across the components of the below- grade areas, walls, fenes- tration, doors, and roofs . d. The continuous air barrier shall be designed to resist positive and negative pressures from wind, stack

effect, and mechanical ventilation and allow for anticipated movements. e. The following areas of the continuous air barrier in the building envelope shall be wrapped, sealed,

caulked, gasketed, or taped in an approved manner to minimize air leakage :

  1. Joints around fenestration and door frames
  2. Junctions between walls and floors ; between walls at building corners; between walls and roofs, including parapets and copings; and walls at foundations
  3. Penetrations through the continuous air barrier in building envelope roofs, walls, and floors
  4. Building assemblies used as ducts or plenums
  5. Joints, seams, connections between planes, and other changes in continuous air barrier materials
  6. Building and service components projecting through or attached through the continuous air barrier
  7. Junctions of the continuous air barrier that separate conditioned spaces from unconditioned spaces, semiheated spaces, and areas that are not enclosed spaces 5.4.3.3 Loading Dock Weatherseals. In Climate Zones 0 and 4 through 8, cargo doors and loading dock doors shall be equipped with weatherseals to restrict air leakage when vehicles are parked in the doorway.

5.4.3.4 Vestibules and Revolving Doors. Vestibules and revolving doors shall be installed in accordance with this section.

5.4.3.4.1 Location. Building entrances that separate conditioned space from the exterior shall have one of the following:

a. An enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing

devices b. A revolving door or doors opening into a vestibule or directly into the conditioned space c. A combination of (a) and (b)

5.4.3.4.2 Vestibule Size. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. Interior and exterior doors shall have a minimum distance between them of not less than 7 ft when in the closed position. The floor area of each vestibule shall not exceed the greater of 50 ft [2] or 2% of the gross conditioned floor area for that level of the building .

5.4.3.4.3 Vestibule Envelope. The exterior surfaces of both conditioned vestibules and unconditioned vestibules shall comply with the continuous air barrier requirements.

VESTIBULE EXCEPTIONS

  1. Doors opening directly from a dwelling unit.
  2. Building entrances in buildings located in Climate Zone 1 or 2.
  3. Doors opening into semiheated spaces .
  4. Enclosed elevator lobbies for building entrances directly from parking garages.
  5. Building entrances in buildings that are located in Climate Zone 3, where the building is less than four stories above grade and less than 10,000 ft [2] in gross conditioned floor area.
  6. Building entrances in buildings that are located in Climate Zone 0, 4, 5, 6, 7, or 8, where the building is less than 1000 ft [2] in gross conditioned floor area.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 45

PDF Page 48

Open page note

CHARGING LANGUAGE FOR PRESCRIPTIVE

Figure 5.5.2 Exterior and semiexterior building envelope.

  1. Doors that open directly from a space that is less than 3000 ft [2 ] in area and is separate from the building entrance.
  2. Self-closing doors in buildings in Climate Zones 0, 3, and 4 that have an air curtain unit complying with Sections 6.4.3.9 and 10.4.5.
  3. Self-closing doors in buildings 15 stories or less in Climate Zones 5 through 8 that have an air curtain unit complying with Sections 6.4.3.9 and 10.4.5.

climate.

The exterior surfaces of conditioned vestibules shall comply with the building envelope requirements for a conditioned space .

5.5.2 Semiexterior Building Envelope. If a building contains any semiheated space or unconditioned space then the semiexterior building envelope shall comply with the requirements for semiheated space in Tables 5.5-0 through 5.5-8 for the appropriate climate. (See Figure 5.5.2.)

The interior surfaces and exterior surfaces of unconditioned vestibules shall comply with the building envelope requirements for a semiheated space .

5.5.3 Opaque Elements. For all opaque elements, compliance with Tables 5.5-0 through 5.5-8 for each class of construction as described in Normative Appendix A, Sections A2 through A8 shall be demonstrated by one of the following two methods:

a. Providing a minimum rated R-value of insulation added to the assembly equal to or greater than the insu lation minimum R-value required of each insulation component. b. Providing insulation such that the maximum U-factor, C-factor, or F-factor for the entire assembly is not

exceeded as determined by one of the following:

  1. Precalculated values in accordance with Normative Appendix A, Section A1.1.

  2. Applicant-determined values in accordance with Normative Appendix A, Section A1.2 where such values are approved by the code official . Exceptions to 5.5.3:

  3. For opaque assemblies not complying with the classes of construction as described in Normative Appendix A, Sections A2 through A8, compliance with the maximum U-factors for the “attic and other” or “wood frame and other” opaque element conditions in Tables 5.5-0 through 5.5-8 shall be

46 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 49

Open page note

Table 5.5.3.1.4 Increased Roof Insulation Levels

Roofs Nonresidential Residential

Opaque Elements

Assembly Maximum

Insulation Min. R-Value

Climate Zone 0

Assembly Maximum

Insulation Min. R-Value

Insulation entirely above deck U-0.027 R-36 c.i. U-0.027 R-36 c.i.

Metal buildings U-0.028 R-35

Climate Zones 1 to 3

Insulation entirely above deck U-0.030 R-33 c.i. U-0.029 R-34 c.i.

Metal buildings U-0.028 R-35

demonstrated by testing or calculations representative of the designed assembly in accordance with Normative Appendix A, Section A9.1 where approved by the code official . 2. For multiple assemblies within a single class of construction for a single space conditioning cate- gory, compliance shall be shown for either (a) the most restrictive requirement or (b) an areaweighted average U-factor, C-factor, or F-factor .

5.5.3.1 Roofs 5.5.3.1.1 All roofs shall comply with the insulation values specified in Tables 5.5-0 through 5.5-8. 5.5.3.1.2 Roof Curbs. Skylight and other roof curbs shall be insulated to not less than R-5.0. 5.5.3.1.3 Joints in Roof Insulation. Joints in the insulation shall be installed in accordance with Section 5.8.1.10.

5.5.3.1.4 Roof Solar Reflectance and Thermal Emittance. Roofs in Climat e Zones 0 through 3 s hall have one of the following:

a. A minimum three-year-aged solar reflectance of 0.55 and a minimum three-year-aged thermal emittance

of 0.75 when tested in accordance with CRRC S100. b. A minimum Solar Reflectance Index of 64 when determined in accordance with the Solar Reflectance

Index method in ASTM E1980 using a convection coefficient of 2.1 Btu/h·ft [2] ·°F, based on three-yearaged solar reflectance and three-year-aged thermal emittance tested in accordance with CRRC S100. c. Increased roof insulation levels found in Table 5.5.3.1.4.

The values for three-year-aged solar reflectance and three-year-aged thermal emittance shall be determined by a laboratory accredited by a nationally recognized accreditation organization and shall be labeled and certified by the manufacturer .

Exceptions to 5.5.3.1.4:

  1. Ballasted roofs with a minimum stone ballast of 17 lb/ft [2 ] or 23 lb/ft [2] pavers.
  2. Vegetative roof systems that contain a minimum thickness of 2.5 in. of growing medium and covering a minimum of 75% of the roof area with durable plantings.
  3. Roofs where a minimum of 75% of the roof area a. is shaded during the peak sun angle on June 21 by permanent components or features of the

building ; b. is covered by offset photovoltaic arrays, building -integrated photovoltaic arrays, or solar air

or water collectors; or c. is permitted to be interpolated using a combination of 1 and 2 above. 4. Steep-sloped roofs . 5. Low-sloped metal building roofs in Climate Zones 2 and 3. 6. Roofs over ventilated attics, roofs over semiheated spaces, or roofs over conditioned spaces that are not cooled spaces . 7. Asphaltic membranes in Climate Zones 2 and 3.

5.5.3.1.5 Insulated Metal Panels. The U-factor of roof assemblies that include insulated metal panels shall not be greater than the U-factors of Tables 5.5-0 through 5.5-8 for the applicable class of construction . U-factors of insulated metal panels shall be determined in accordance with Section A9.4.7.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 47

PDF Page 50

Open page note

Table 5.5-0 Building Envelope Requirements for Climate Zone 0 (A,B)*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.039 R-25 c.i. U-0.032 R-30 c.i. U-0.218 R-3.8 c.i.

Metal building [ a] U-0.041 R-10 + R-19 FC U-0.041 R-10 + R-19 FC U-0.115 R-10

Attic and other U-0.027 R-38 U-0.027 R-38 U-0.081 R-13

Walls, above-Grade

Mass U-0.580 NR U-0.151 [b] R-5.7 c.i. [b] U-0.580 NR

Metal building U-0.094 R-0 + R-9.8 c.i. U-0.094 R-0 + R-9.8 c.i. U-0.352 NR

Steel-framed U-0.124 R-13 U-0.124 R-13 U-0.352 NR

Wood-framed and other U-0.089 R-13 U-0.089 R-13 U-0.292 NR

Wall, below-Grade

Below-grade wall C-1.140 NR C-1.140 NR C-1.140 NR

Floors

Mass U-0.322 NR U-0.322 NR U-0.322 NR

Steel joist U-0.350 NR U-0.350 NR U-0.350 NR

Wood-framed and other U-0.282 NR U-0.282 NR U-0.282 NR

Slab-on-Grade Floors

Unheated F-0.730 NR F-0.730 NR F-0.730 NR

Heated F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.700

Nonswinging U-0.310 U-0.310 U-1.450

Assembly

Max. U

Assembly

Max. U

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.50 0.22 1.10 (for all

0.50 0.22 1.10 (for all

types)

1.20 NR (for all

types)

NR (for all

Operable 0.62 0.20 types) 0.62 0.20 types) 1.20 types) types)

types)

Entrance door 0.83 0.20 0.83 0.20 1.10

Skylight, 0% to 3% of Roof

All types 0.70 0.30 NR 0.70 0.30 NR 1.80 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2). b. Exception to Section 5.5.3.2 applies for mass walls above grade .

48 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 51

Open page note

Table 5.5-1 Building Envelope Requirements for Climate Zone 1 (A,B)*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.048 R-20 c.i. U-0.039 R-25 c.i. U-0.218 R-3.8 c.i.

Metal building [ a] U-0.041 R-10 + R-19 FC U-0.041 R-10 + R-19 FC U-0.115 R-10

Attic and other U-0.027 R-38 U-0.027 R-38 U-0.081 R-13

Walls, above Grade

Mass U-0.580 NR U-0.151 [b] R-5.7 c.i. [b] U-0.580 NR

Metal building U-0.094 R-0 + R-9.8 c.i. U-0.094 R-0 + R-9.8 c.i. U-0.352 NR

Steel-framed U-0.124 R-13 U-0.124 R-13 U-0.352 NR

Wood-framed and other U-0.089 R-13 U-0.089 R-13 U-0.292 NR

Wall, below Grade

Below-grade wall C-1.140 NR C-1.140 NR C-1.140 NR

Floors

Mass U-0.322 NR U-0.322 NR U-0.322 NR

Steel joist U-0.350 NR U-0.350 NR U-0.350 NR

Wood-framed and other U-0.282 NR U-0.282 NR U-0.282 NR

Slab-on-Grade Floors

Unheated F-0.730 NR F-0.730 NR F-0.730 NR

Heated F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.700

Nonswinging U-0.310 U-0.310 U-1.450

Assembly

Max. U

Assembly

Max. U

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.50 0.23 1.10 (for all

0.50 0.23 1.10 (for all

types)

1.20 NR (for all types)

NR (for all

Operable 0.62 0.21 types) 0.62 0.21 types) 1.20 types)

types)

Entrance door 0.83 0.21 0.83 0.21 1.10

Skylight, 0% to 3% of Roof

All types 0.70 0.30 NR 0.70 0.30 NR 1.80 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2). b. Exception to Section 5.5.3.2 applies for mass walls above grade .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 49

PDF Page 52

Open page note

Table 5.5-2 Building Envelope Requirements for Climate Zone 2 (A,B)*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.039 R-25 c.i. U-0.039 R-25 c.i. U-0.173 R-5 c.i.

Metal building [ a] U-0.041 R-10 + R-19 FC U-0.041 R-10 + R-19 FC U-0.096 R-16

Attic and other U-0.027 R-38 U-0.027 R-38 U-0.053 R-19

Walls, above Grade

Mass U-0.151 [b] R-5.7 c.i. [b] U-0.123 R-7.6 c.i. U-0.580 NR

Metal building U-0.094 R-0 + R-9.8 c.i. U-0.094 R-0 + R-9.8. c.i. U-0.162 R-13

Steel-framed U-0.084 R-13 + R-3.8 c.i. U-0.064 R-13 + R-7.5 c.i. U-0.124 R-13

Wood-framed and other U-0.089 R-13 U-0.089 R-13 U-0.089 R-13

Wall, below Grade

Below-grade wall C-1.140 NR C-1.140 NR C-1.140 NR

Floors

Mass U-0.107 R-6.3 c.i. U-0.087 R-8.3 c.i. U-0.322 NR

Steel joist U-0.038 R-30 U-0.038 R-30 U-0.069 R-13

Wood-framed and other U-0.033 R-30 U-0.033 R-30 U-0.066 R-13

Slab-on-Grade Floors

Unheated F-0.730 NR F-0.730 NR F-0.730 NR

Heated F-0.900 R-10 for 24 in. F-0.860 R-15 for 24 in. F-1.020 R-7.5 for 12 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.700

Nonswinging U-0.310 U-0.310 U-1.450

Assembly

Max. U

Assembly

Max. U

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly

Max. SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.45 0.25 1.10 (for all

0.45 0.25 1.10 (for all

types)

0.50 NR (for all

types)

NR (for all

Operable 0.60 0.23 types) 0.60 0.23 types) 0.65 types) types)

types)

Entrance door 0.77 0.23 0.77 0.23 0.77

Skylight, 0% to 3% of Roof

All types 0.65 0.30 NR 0.65 0.30 NR 0.90 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2). b. Exception to Section 5.5.3.2 applies for mass walls above grade .

50 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 53

Open page note

Table 5.5-3 Building Envelope Requirements for Climate Zone 3 (A,B,C)*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.039 R-25 c.i. U-0.039 R-25 c.i. U-0.119 R-7.6 c.i.

Metal building [ a] U-0.041 R-10 + R-19 FC U-0.041 R-10 + R-19 FC U-0.096 R-16

Attic and other U-0.027 R-38 U-0.027 R-38 U-0.053 R-19

Walls, above Grade

Mass U-0.123 R-7.6 c.i. U-0.104 R-9.5 c.i. U-0.580 NR

Metal building U-0.094 R-0 + R-9.8 c.i. U-0.072 R-0 + R-13 c.i. U-0.162 R-13

Steel-framed U-0.077 R-13 + R-5 c.i. U-0.064 R-13 + R-7.5 c.i. U-0.124 R-13

Wood-framed and other U-0.089 R-13 U-0.064 R-13 + R-3.8 c.i. or R-20 U-0.089 R-13

Wall, below Grade

Below-grade wall C-1.140 NR C-1.140 NR C-1.140 NR

Floors

Mass U-0.074 R-10 c.i. U-0.074 R-10 c.i. U-0.137 R-4.2 c.i.

Steel joist U-0.038 R-30 U-0.038 R-30 U-0.052 R-19

Wood-framed and other U-0.033 R-30 U-0.033 R-30 U-0.051 R-19

Slab-on-Grade Floors

Unheated F-0.730 NR F-0.540 R-10 for 24 in. F-0.730 NR

Heated F-0.860 R-15 for 24 in. F-0.860 R-15 for 24 in. F-1.020 R-7.5 for 12 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.370

Nonswinging U-0.310 U-0.310 U-0.360

Assembly

Max. U

Assembly

Max. U

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly

Max. SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.42 0.25 1.10 (for all

0.42 0.25 1.10 (for all

types)

0.50 NR (for all

types)

NR (for all

Operable 0.54 0.23 types) 0.54 0.23 types) 0.65 types) types)

types)

Entrance door 0.68 0.23 0.68 0.23 0.77

Skylight, 0% to 3% of Roof

All types 0.55 0.30 NR 0.55 0.30 NR 0.90 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2).

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 51

PDF Page 54

Open page note

NonresidentialResidentialSemiheated
** Opaque Elements**

Assembly
Maximum
Insulation
Min. R-Value
** Opaque Elements**

Assembly
Maximum
Insulation
Min. R-Value
Assembly
Maximum
Insulation
Min. R-Value
Assembly
Maximum
Insulation
Min. R-Value
Insulation entirely
above deck
U-0.032
R-30_c.i._
Metal building a
U-0.037
R-19 + R-11_Ls_ or
R-25 + R-8_Ls_
Attic and other
U-0.021
R-49
Roofs
U-0.032
R-30_c.i._
U-0.037
R-19 + R-11_Ls_ or
R-25 + R-8_Ls_
U-0.021
R-49
U-0.093
R-10_c.i._
U-0.082
R-19
U-0.034
R-30
Wa
Mass
U-0.104
R-9.5_c.i._
Metal building
U-0.060
R-0 + R-15.8_c.i._
Steel-framed
U-0.064
R-13 + R-7.5_c.i._
Wood-framed and other
U-0.064
R-13 + R-3.8_c.i._ or R-20
lls, above Grade
U-0.090
R-11.4_c.i._
U-0.050
R-0 + R-19_c.i._
U-0.064
R-13 + R-7.5 c.i
U-0.064
R-13 + R-3.8_c.i._ or R-20
U-0.580
NR
U-0.162
R-13
U-0.124
R-13
U-0.089
R-13
Wa
Below-grade wall
C-0.119
R-7.5_c.i._
ll, below Grade
C-0.092
R-10_c.i._
C-1.140
NR
Mass
U-0.057
R-14.6_c.i._
Steel joist
U-0.038
R-30
Wood-framed and other
U-0.033
R-30
Floors
U-0.051
R-16.7_c.i._
U-0.038
R-30
U-0.033
R-30
U-0.107
R-6.3_c.i._
U-0.052
R-19
U-0.051
R-19
Slab
Unheated
F-0.520
R-15 for 24 in.
Heated
F-0.843
R-20 for 24 in.
-on-Grade Floors
F-0.520
R-15 for 24 in.
F-0.688
R-20 for 48 in.
F-0.730
NR
F-0.900
R-10 for 24 in.

Swinging
U-0.370

Nonswinging
U-0.310
Opaque Doors
U-0.370

U-0.310
U-0.370

U-0.360
Fenestration
Assembly
Max. U
Assembly
Max. SHGC
Assembly
Min.
VT/SHGC
Nonresidential
Assembly
Max. U
Assembly
Max. SHGC
Assembly
Min.
VT/SHGC
Residential
Assembly
Max. U
Assembly
Max.
SHGC
Assembly
Min.
VT/SHGC
Semiheated
Vertical Fene
Fixed
0.36
0.36
1.10
(for all
types)
Operable
0.45
0.33
Entrance door
0.63
0.33
_ stration_, 0% to 40% of_Wall_
0.36
0.36
1.10
(for all
types)
0.45
0.33
0.63
0.33
0.50
NR
(for all
types)
NR
(for all
types)
0.65
0.77
Skyligh
All types
0.50
0.40
NR
t, 0% to 3% of_Roof_
0.50
0.40
NR
0.75
NR
NR
  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), Ls = liner system (see Section A2.3.2.4); NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2).

52 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 55

Open page note

Table 5.5-5 Building Envelope Requirements for Climate Zone 5 (A,B,C)*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.032 R-30 c.i. U-0.032 R-30 c.i. U-0.063 R-15 c.i.

Metal building [ a] U-0.037 R-19 + R-11 Ls or

R-25 + R-8 Ls

U-0.037 R-19 + R-11 Ls or

R-25 + R-8 Ls

U-0.082 R-19

Attic and other U-0.021 R-49 U-0.021 R-49 U-0.034 R-30

Walls, above grade

Mass U-0.090 R-11.4 c.i. U-0.080 R-13.3 c.i. U-0.151 [b] R-5.7 c.i. [b]

Metal building U-0.050 R-0 + R-19 c.i. U-0.050 R-0 + R-19 c.i. U-0.094 R-0 + R-9.8 c.i.

Steel-framed U-0.055 R-13 + R-10 c.i. U-0.055 R-13 + R-10 c.i. U-0.084 R-13+R-3.8 c.i.

Wood-framed and other U-0.051 R-13 + R-7.5 c.i. or

R-19 + R-5 c.i.

U-0.051 R-13 + R-7.5 c.i. or

R-19 + R-5 c.i.

U-0.089 R-13

Wall, below Grade

Below-grade wall C-0.119 R-7.5 c.i. C-0.092 R-10 c.i. C-1.140 NR

Floors

Mass U-0.057 R-14.6 c.i. U-0.051 R-16.7 c.i. U-0.107 R-6.3 c.i.

Steel joist U-0.038 R-30 U-0.038 R-30 U-0.052 R-19

Wood-framed and other U-0.033 R-30 U-0.033 R-30 U-0.051 R-19

Slab-on-Grade Floors

Unheated F-0.520 R-15 for 24 in F-0.510 R-20 for 24 in. F-0.730 NR

Heated F-0.688 R-20 for 48 in. F-0.688 R-20 for 48 in. F-0.900 R-10 for 24 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.370

Nonswinging U-0.310 U-0.310 U-0.360

Assembly

Max. U

Assembly

Max. U

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly

Max. SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.36 0.38 1.10 (for all

0.36 0.38 1.10 (for all

types)

0.50 NR (for all

types)

NR (for all

Operable 0.45 0.33 types) 0.45 0.33 types) 0.65 types) types)

types)

Entrance door 0.63 0.33 0.63 0.33 0.77

Skylight, 0% to 3% of Roof

All types 0.50 0.40 NR 0.50 0.40 NR 0.75 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), Ls = liner system (see Section A2.3.2.4); NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2). b. Exception to Section 5.5.3.2 applies for mass walls above grade .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 53

PDF Page 56

Open page note

Table 5.5-6 Building Envelope Requirements for Climate Zone 6 (A,B)*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.032 R-30 c.i. U-0.032 R-30 c.i. U-0.063 R-15 c.i.

Metal building [ a] U-0.031 R-25 + R-11 Ls U-0.029 R-30 + R-11 Ls U-0.060 R-19 + R-19

Attic and other U-0.021 R-49 U-0.021 R-49 U-0.034 R-30

Walls, above Grade

Mass U-0.080 R-13.3 c.i. U-0.071 R-15.2 c.i. U-0.151 [b] R-5.7 c.i. [b]

Metal building U-0.050 R-0 + R-19 c.i. U-0.050 R-0 + R-19 c.i. U-0.094 R-0 + R-9.8 c.i.

Steel-framed U-0.049 R-13 + R-12.5 c.i. U-0.049 R-13 + R-12.5 c.i. U-0.084 R-13 + R-3.8 c.i.

Wood-framed and other U-0.051 R-13 + R-7.5 c.i. or

R-19 + R-5 c.i.

U-0.051 R-13 + R-7.5 c.i. or

R-19 + R-5 c.i.

U-0.089 R-13

Wall, below Grade

Below-grade wall C-0.092 R-10 c.i. C-0.063 R-15 c.i. C-0.119 R-7.5 c.i

Floors

Mass U-0.051 R-16.7 c.i. U-0.051 R-16.7 c.i. U-0.087 R-8.3 c.i.

Steel joist U-0.032 R-38 U-0.032 R-38 U-0.052 R-19

Wood-framed and other U-0.027 R-38 U-0.027 R-38 U-0.051 R-19

Slab-on-Grade Floors

Unheated F-0.510 R-20 for 24 in. F-0.434 R-20 for 48 in F-0.730 NR

Heated F-0.688 R-20 for 48 in. F-0.671 R-25 for 48 in. F-0.860 R-15 for 24 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.370

Nonswinging U-0.310 U-0.310 U-0.360

Assembly

Max. U

Assembly

Max. U

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly

Max. SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.34 0.38 1.10 (for all

0.34 0.38 1.10 (for all

types)

0.39 NR (for all

types)

NR (for all

Operable 0.42 0.34 types) 0.42 0.34 types) 0.48 types) types)

types)

Entrance door 0.63 0.34 0.63 0.34 0.68

Skylight, 0% to 3% of Roof

All types 0.47 0.40 NR 0.50 0.40 NR 0.75 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), Ls = liner system (see Section A2.3.2.4); NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2). b. Exception to Section 5.5.3.2 applies for mass walls above grade .

54 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 57

Open page note

Table 5.5-7 Building Envelope Requirements for Climate Zone 7*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Roofs

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Insulation entirely

above deck

Assembly Maximum

U-0.028 R-35 c.i. U-0.028 R-35 c.i. U-0.039 R-25 c.i.

Metal building [ a] U-0.029 R-30 + R-11 Ls U-0.029 R-30 + R-11 Ls U-0.037 R-19 + R-11 Ls or

R-25 + R-8 Ls

Attic and other U-0.017 R-60 U-0.017 R-60 U-0.027 R-38

Walls, above Grade

Mass U-0.071 R-15.2 c.i. U-0.071 R-15.2 c.i. U-0.123 R-7.6 c.i.

Metal building U-0.044 R-0 + R.22.1 c.i. U-.044 R-0 + R.22.1 c.i. U-0.072 R-0 + R-13 c.i.

Steel-framed U-0.049 R-13 + R-12.5 c.i. U-0.042 R-13 + R-15.6 c.i. U-0.064 R-13 + R-7.5 c.i.

Wood-framed and other U-0.051 R-13 + R-7.5 c.i. or

R-19 + R-5 c.i.

U-0.051 R-13 + R-7.5 c.i. or

R-19 + R-5 c.i.

U-0.064 R-13 + R-3.8 c.i.

Wall, below Grade

Below-grade wall C-0.063 R-15 c.i. C-0.063 R-15 c.i. C-0.119 R-7.5 c.i.

Floors

Mass U-0.042 R-20.9 c.i. U-0.042 R-20.9 c.i. U-0.074 R-10.4 c.i.

Steel joist U-0.032 R-38 U-0.032 R-38 U-0.052 R-19

Wood-framed and other U-0.027 R-38 U-0.027 R-38 U-0.051 R-19

Slab-on-Grade Floors

Unheated F-0.510 R-20 for 24 in. F-0.434 R-20 for 48 in. F-0.730 NR

Heated F-0.671 R-25 for 48 in. F-0.671 R-25 for 48 in. F-0.860 R-15 for 24 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.370

Nonswinging U-0.310 U-0.310 U-0.310

Assembly

Max. U

Assembly

Max. U

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.29 0.40 1.10 (for all

0.29 0.40 1.10 (for all

types)

0.36 NR (for all

types)

NR (for all

Operable 0.36 0.36 types) 0.36 0.36 types) 0.44 types) types)

types)

Entrance door 0.63 0.36 0.63 0.36 0.63

Skylight, 0% to 3% of Roof

All types 0.44 NR NR 0.44 NR NR 0.75 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), Ls = liner system (see Section A2.3.2.4); NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2).

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 55

PDF Page 58

Open page note

Table 5.5-8 Building Envelope Requirements for Climate Zone 8*

Nonresidential Residential Semiheated

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Assembly Maximum

Insulation Min. R-Value

Opaque Elements

Roofs

Insulation entirely

above deck

Assembly Maximum

U-0.028 R-35 c.i. U-0.028 R-35 c.i. U-0.039 R-25 c.i.

Metal building [ a] U-0.026 R-25 + R-11+R-11 Ls U-0.026 R-25 + R-11+R-11 Ls U-0.037 R-19+R-11 Ls or

R-25 + R-8 Ls

Attic and other U-0.017 R-60 U-0.017 R-60 U-0.027 R-38

Walls, above Grade

Mass U-0.048 R-19 c.i. U-0.048 R-19 c.i. U-0.104 R-9.5 c.i.

Metal building U-0.039 R-0 + R-25 c.i. U-0.039 R-0 + R-25 c.i. U-0.060 R-0 + R-15.8 c.i.

Steel-framed U-0.037 R-13 + R-18.8 c.i. U-0.037 R-13 + R-18.8 c.i. U-0.064 R-13 + R-7.5 c.i.

Wood-framed and other U-0.032 R-13 + R-18.8 c.i. U-0.032 R-13 + R-18.8 c.i. U-0.051 R-13 + R-7.5 c.i.

Wall, below Grade

Below-grade wall C-0.063 R-15 c.i. C-0.063 R-15 c.i. C-0.119 R-7.5 c.i.

Floors

Mass U-0.038 R-23 c.i. U-0.038 R-23 c.i. U-0.064 R-12.5 c.i.

Steel joist U-0.032 R-38 U-0.032 R-38 U-0.052 R-19

Wood-framed and other U-0.027 R-38 U-0.027 R-38 U-0.033 R-30

Slab-on-Grade Floors

Unheated F-0.434 R-20 for 48 in. F-0.424 R-25 for 48 in. F-0.540 R-10 for 24 in.

Heated F-0.671 R-25 for 48 in. F-0.373 R-20 full slab F-0.860 R-15 for 24 in.

Opaque Doors

Swinging U-0.370 U-0.370 U-0.370

Nonswinging U-0.310 U-0.310 U-0.310

Assembly

Max. U

Assembly

Max. U

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly Max. SHGC

Assembly

Min. VT/SHGC

Assembly

Max. SHGC

Fenestration

Assembly

Max. U

Vertical Fenestration, 0% to 40% of Wall

Fixed 0.26 0.40 1.10 (for all

0.26 0.40 1.10 (for all

types)

0.36 NR (for all

types)

NR (for all

Operable 0.32 0.36 types) 0.32 0.36 types) 0.44 types) types)

types)

Entrance door 0.63 0.36 0.63 0.36 0.63

Skylight, 0% to 3% of Roof

All types 0.41 NR NR 0.41 NR NR 0.75 NR NR

  • The following definitions apply: c.i. = continuous insulation (see Section 3.2), FC = filled cavity (see Section A2.3.2.5), Ls = liner system (see Section A2.3.2.4); NR = no (insulation) requirement. a. When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2).

56 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 59

Open page note

5.5.3.2 Above-Grade Walls. Above-grade walls shall comply with the insulation values specified in Tables 5.5-0 through 5.5-8. For the purposes of this provision, wall plates, tracks, headers, or bond beams are considered part of the base wall assembly.

Exception to 5.5.3.2: For mass walls, where the requirement in Tables 5.5-0 through 5.5-8 is for a max imum assembly U-0.151 followed by footnote “b,” concrete masonry unit (CMU) walls complying with ASTM C90 that are ungrouted or partially grouted at 32 in. or greater on center vertically and 48 in. or greater on center horizontally, shall have their ungrouted openings (e.g., cores, cells) filled with insulating material having a maximum thermal conductivity of 0.44 Btu·in./h·ft [2] ·°F.

5.5.3.2.1 Walls That Are Both Above and Below Grade. W hen a wall consists of both above-grade and below - grade portions, the entire wall for that story shall be insulated on either the exterior or the interior or be integral.

a. If insulated on the interior, the wall shall be insulated to the above-grade wall requirements. b. If insulated on the exterior or integral, the below-grade wall portion shall be insulated to the below-grade

wall requirements, and the above-grade wall portion shall be insulated to the above-grade wall requirements.

a. A minimum of 75% of the opaque wall area shall have a minimum area-weighted initial solar reflectance

of 0.30 when tested in accordance with ASTM C1549 with AM1.5GV output, or ASTM E903 with the AM1.5GV output, or determined in accordance with generally accepted engineering standards, and a minimum emittance or emissivity of 0.75 when tested in accordance with ASTM C835, C1371, E408, or determined in accordance with generally accepted engineering standards. For the portion of the opaque wall that is glass spandrel area, a minimum solar reflectance of 0.29, determined in accordance with NFRC 300 or ISO 9050, shall be permitted. Area-weighting is permitted only between the south-, east-, and west-oriented walls and only between walls of the same space conditioning category . b. A minimum of 30% of the above-grade wall area shall be shaded through the use of human-made struc-

tures, existing buildings, hillsides, permanent building projections, on-site renewable energy systems, or a combination of these. Shade coverage shall be calculated by projecting the shading surface downward on the wall at an angle of 45 degrees.

Exception to 5.5.3.2.2: Exterior walls of semiheated spaces .

5.5.3.2.3 Insulated Metal Panels. The U-factor of wall assemblies that include insulated metal panels shall not be greater than the U-factors of Tables 5.5-0 through 5.5-8 for the applicable class of construction . U-factors of insulated metal panels shall be determined in accordance with Section A9.4.7.

5.5.3.3 Below-Grade Wall Insulation. Below-grade walls shall have a rated R-value of insulation no less than the insulation values specified in Tables 5.5-0 through 5.5-8.

Exception to 5.5.3.3: Where framing, including metal and wood studs, is used, compliance shall be

based on the maximum assembly C-factor .

5.5.3.4 Floors

5.5.3.4.1 Floor Insulation. All floors shall comply with the insulation values specified in Tables 5.5-0 through 5.5-8.

5.5.3.4.2 Insulated Metal Panels. The U-factor of floor assemblies that include insulated metal pan- els shall not be greater than the U-factors of Tables 5.5-0 through 5.5-8 for the applicable class of construc- tion . U-factors of insulated metal panels shall be determined in accordance with Section A9.4.7.

5.5.3.5 Slabs-on-Grade. All slab-on-grade floors, including heated slab-on-grade floors and unheated slab-on-grade floors, shall comply with the insulation values specified in Tables 5.5-0 through 5.5-8.

5.5.3.6 Opaque Doors. All opaque doors shall have a U-factor not greater than that specified in Tables 5.5-0 through 5.5-8.

Exceptions to 5.5.3.6:

  1. For conditioned spaces, nonswinging doors that are horizontally hinged sectional doors with a single row of fenestration shall have an assembly U-factor less than or equal to 0.440 in Climate Zones 0 through 6 and less than or equal to 0.360 in Climate Zones 7 and 8, provided the fenes- tration area is at least 14% and no more than 25% of the total door area .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 57

PDF Page 60

Open page note

  1. For semiheated spaces, nonswinging doors that are horizontally hinged sectional doors with a single row of fenestration shall have an assembly U-factor less than or equal to 0.440 in Climate Zones 3 through 6 and less than or equal to 0.360 in Climate Zones 7 and 8, provided the fenes- tration area is at least 14% and no more than 25% of the total door area .

5.5.4 Fenestration 5.5.4.1 General. Compliance with U-factors, SHGC, and VT / SHGC shall be demonstrated for the overall fenestration product. Gross wall areas and gross roof areas shall be calculated separately for each space conditioning category for the purposes of determining compliance.

Exceptions to 5.5.4.1:

  1. If there are multiple assemblies within a single class of construction for a single space condition- ing category, it shall be permitted to demonstrate compliance based on a n area-weighted average U-factor, SHGC, VT / SHGC, or LSG . The area-weighted average across multiple classes of con- struction or multiple space conditioning categories shall not be permitted for use to demonstrate compliance.
  2. Vertical fenestration shall be permitted to demonstrate compliance based on an area-weighted average U-factor, SHGC, VT / SHGC, or LSG across multiple classes of construction for a single space conditioning category, but not across multiple space conditioning categories .

Exception to 5.5.4.2.1: Vertical fenestration complying with Section 5.5.4.4.1, Exception 3.

5.5.4.2.2 Maximum Skylight Fenestration Area. The total skylight area shall not be greater than that specified in Tables 5.5-0 through 5.5-8.

Exception to 5.5.4.2.2: The total skylight area is permitted to be increased to no greater than 6% of the

gross roof area, provided the skylights meet all of the criteria in Section 5.5.4.4.2, Exception 1 and the total daylight area under skylights is a minimum of half the floor area of the space .

5.5.4.2.3 Minimum Skylight Fenestration Area. In any enclosed space in a building that is

a. 2500 ft [2] and greater; b. directly under a roof with ceiling heights greater than 15 ft; and c. one of the following space types: office, lobby, atrium, concourse, corridor, storage (including nonrefriger ated warehouse), gymnasium, fitness/exercise area, playing area, gymnasium seating area, convention exhibit/event space, courtroom, automotive service, fire station engine room, manufacturing corridor/ transition and bay areas, retail, library reading and stack areas, distribution/sorting area, transportation baggage and seating areas, or workshop, the total daylight area under skylights shall be a minimum of half the floor area and either

  1. provide a minimum skylight area to daylight area under skylights of 3% with a skylight VT of at least 0.40 or
  2. provide a minimum skylight effective aperture of at least 1%.

These skylights shall have a glazing material or diffuser with a measured haze value greater than 90% when tested according to ASTM D1003. General lighting in the daylight area shall be controlled as described in Section 9.4.1.1(f).

Exceptions to 5.5.4.2.3:

  1. Enclosed spaces in Climate Zones 6 through 8.
  2. Enclosed spaces where it is documented that existing structures or natural objects block directbeam sunlight on at least half of the roof over the enclosed space for more than 1500 daytime hours per year between 8 a.m. and 4 p.m.
  3. Enclosed spaces where the daylight area under roof monitors is greater than 50% of the enclosed space floor area.
  4. Enclosed spaces where it is documented that 90% of the skylight area is shaded on June 21 in the Northern Hemisphere (December 21 in the Southern Hemisphere) at noon by permanent architectural features of the building.
  5. Enclosed spaces where the total area minus the primary sidelighted area and secondary side- lighted area is less than 2500 ft [2] and where the lighting is controlled according to sidelighting requirements described in Section 9.4.1.1(e).

58 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 61

Open page note

Table 5.5.4.4.1 SHGC Multipliers for Permanent Projections

Projection Factor (PF)SHGC Multiplier
(South, East, and West Orientations)
0 to 0.101.00
>0.10 to 0.200.91
>0.20 to 0.300.82
>0.30 to 0.400.74
>0.40 to 0.500.67
>0.50 to 0.600.61
>0.60 to 0.700.56
>0.70 to 0.800.51
>0.80 to 0.900.47
>0.90 to 1.000.44

5.5.4.3 Fenestration U-Factor. Fenestration shall have a U-factor not greater than that specified in Tables 5.5-0 through 5.5-8.

Exception to 5.5.4.3: The U-factor for skylights is permitted to be increased to no greater than 0.90 Btu/

h·ft [2] ·°F in Climate Zones 0 through 3 and 0.75 Btu/h·ft [2] ·°F in Climate Zones 4 through 8, provided the skylights meet all of the criteria in Section 5.5.4.4.2, Exception 1.

5.5.4.4 Fenestration Solar Heat Gain Coefficient (SHGC) 5.5.4.4.1 SHGC of Vertical Fenestration. Vertical fenestration shall have an SHGC not greater than that specified in Tables 5.5-0 through 5.5-8.

Exceptions to 5.5.4.4.1:

  1. For demonstrating compliance for south -, east -, or west-oriented vertical fenestration shaded by opaque permanent projections that will last as long as the building itself, the SHGC of the shaded vertical fenestration in the proposed design is permitted to be reduced by using the multipliers in Table 5.5.4.4.1. Permanent projections consisting of open louvers shall be considered to provide shading, provided that no sun penetrates the louvers during the peak sun angle on June 21.
  2. For demonstrating compliance for south -, east -, or west-oriented vertical fenestration shaded by partially opaque permanent projections (e.g., framing with glass or perforated metal) that will last as long as the building itself, the projection factor ( PF ) shall be reduced by multiplying it by a factor of Os, which is derived as follows:

Os = ( Ai × Oi ) + ( Af × Of )

where Os = percent opacity of the shading device Ai = percent of the area of the shading device that is a partially opaque infill Oi = percent opacity of the infill for glass Oi = (100% – Ts ), where Ts is the solar transmittance as determined in accordance with NFRC 300; for perforated or decorative metal panels, Oi = percentage of solid material Af = percent of the area of the shading device that represents the framing members Of = percent opacity of the framing members; if solid then 100%

The SHGC of the shaded vertical fenestration in the proposed building is permitted to then be reduced by using the multipliers in Table 5.5.4.4.1 for each fenestration product. 3. Vertical fenestration that is located on the street side of the street-level story only, provided that a. the street side of the street-level story does not exceed 20 ft in height, b. the fenestration has a continuous overhang with a weighted average PF greater than 0.5, and c. the fenestration area for the street side of the street-level story is less than 75% of the gross

wall area for the street side of the street-level story .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 59

PDF Page 62

Open page note

When this exception is used, separate calculations shall be performed for these sections of the building envelope, and these values shall not be averaged with any others for compliance purposes. No credit shall be given here or elsewhere in the building for not fully utilizing the fenestration area allowed. 4. For dynamic glazing, the minimum SHGC shall be used to demonstrate compliance with this section. Dynamic glazing shall be considered separately from other vertical fenestration, and areaweighted averaging with other vertical fenestration that is not dynamic glazing shall not be permitted.

5.5.4.4.2 SHGC of Skylights. Skylights shall have an SHGC not greater than that specified in Tables 5.5-0 through 5.5-8. Exceptions to 5.5.4.4.2:

  1. Skylights are exempt from SHGC requirements provided the following: a. They have a glazing material or diffuser with a measured haze value greater than 90% when

tested according to ASTM D1003. b. They have a skylight VT greater than 0.40. c. They have all general lighting in the daylight area under skylights controlled by multilevel

photocontrols in accordance with Section 9.4.1.1(f). 2. For dynamic glazing, the minimum SHGC shall be used to demonstrate compliance with this section. Dynamic glazing shall be considered separately from other skylights, and areaweighted averaging with other skylights that is not dynamic glazing shall not be permitted.

5.5.4.5 Fenestration Orientation. T h e vertical fenestration shall comply with either (a) or (b):

a. For Climate Zones 0 through 8:

AW  ( AT )/4 and AE  ( AT )/4

b. For Climate Zones 0 through 3,

AW × SHGCW  ( AT × SHGCC )/4 and AE × SHGCE  ( AT × SHGCC )/4

where AW = west-oriented vertical fenestration area AE = east-oriented vertical fenestration area AT = total vertical fenestration area SHGCC = SHGC criteria in Tables 5.5-0 through 5.5-8 for each climate zone SHGCE = SHGC for east-oriented fenestration that complies with Section 5.5.4.4.1 SHGCW = SHGC for west-oriented fenestration that complies with Section 5.5.4.4.1

Exceptions to 5.5.4.5:

  1. Buildings with shade on 75% of the east- and west-oriented vertical fenestration areas from permanent projections, existing buildings, existing permanent infrastructure, or topography at 9 a.m. and 3 p.m., respectively, on the summer solstice (June 21 in the northern hemisphere).

  2. Alterations and additions with no increase in vertical fenestration area .

  3. Buildings in Climate Zone 8.

Exceptions to 5.5.4.6:

  1. A light-to-solar-gain ratio ( LSG ) of not less than 1.25 is allowed to be used as an alternative to VT / SHGC . When using this option, the center-of-glass VT and the center-of-glass SHGC shall be deter

60 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 63

Open page note

3

4

mined in accordance with NFRC 300 and NFRC 301, determined by an independent laboratory or included in a database published by a government agency, and certified by the manufacturer . 2. Fenestration not covered in the scope of the NFRC 200. 3. Enclosed spaces where the daylight area under roof monitors is greater than 50% of the enclosed space floor area. 4. Enclosed spaces with skylights that comply with Section 5.5.4.2.3. 5. Enclosed spaces where the sidelighting effective aperture is greater than or equal to 0.15. 6. For dynamic glazing, the VT / SHGC ratio and the LSG shall be determined using the maximum VT and maximum SHGC . Dynamic glazing shall be considered separately from other fenestration, and area-weighted averaging with other fenestration that is not dynamic glazing shall not be permitted.

5.5.5 Linear Thermal Bridges and Point Thermal Bridges. Where linear thermal bridges and point thermal bridges occur as described in Sections 5.5.5.1 through 5.5.5.5, they shall

a. comply with the applicable requirements of Sections 5.5.5.1 through 5.5.5.5 or

Informative Note: For linear thermal bridges and point thermal bridges that fall under the provisions of Section 4.2 and cannot comply prescriptively with the provisions of Sections 5.5.5.1 through 5.5.5.4, projects can use Section 5.5.5.5, Section 12, Normative Appendix C, or Normative Appendix G.

5.5.5.1 Roof and Wall Intersections. Where a roof with insulation entirely above deck intersects an

5.5.5.1.1 Roof Edges. At roof edges without parapets or overhangs, the roof insulation and the wall insulation shall comply with the following, as applicable to the location of the insulation:

a. Where a wall has exterior continuous insulation, the roof insulation shall extend to the exterior of the

wall insulation and the wall insulation shall extend to the roof insulation. b. Where a wall has cavity or integral insulation that represents more than 50% of the total wall insulation

R-value, the roof -to-wall insulation shall comply with one of the following:

  1. The cavity or integral insulation shall extend to the underside of the roof insulation.
  2. The cavity or integral insulation shall extend to the underside of the roof deck, and the roof insulation shall extend to the exterior face of the wall . The wall insulation shall be permitted to be interrupted by roof framing members.
  3. Additional insulation having a rated R-value of insulation not less than R-5 shall extend inward on the underside of the roof deck for not less than 2 ft and be permitted to be interrupted by roof framing members.
  4. Insulation having a rated R-value of insulation not less than R-5 shall be placed at the exterior of the roof edge and be located between the bottom plane of the roof insulation and the plane of the bottom of the roof deck.
  5. The wall insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-1.
  6. The roof insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 61

Exceptions to 5.5.5:

  1. Buildings located in Climate Zones 0 through 3.

  2. Semiheated spaces in buildings located in Climate Zones 0 through 6.

  3. Thermal bridges in uninsulated assemblies.

  4. Linear and point thermal bridges that have a material thermal conductivity less than 3.0 Btu·in/ h·ft [2] ·°F.

  5. Alterations to existing buildings other than additions.

  6. Roofs that project over exterior walls.

PDF Page 64

Open page note

Table 5.5.5.1.1-1 Additional Wall Insulation Required for Mass Walls with Insulation on the Interior or Integral at Intersections with Roof Edges and Parapets

Climate ZoneR-Value IncreaseU-factor % Decrease
4R-1.08%
5R-1.08%
6R-1.510%
7R-1.510%
8R-2.514%

Table 5.5.5.1.1-2 Additional Roof Insulation Required for Mass Walls with Insulation on the Interior or Integral at Intersections with Roof Edges and Parapets

Climate ZoneR-Value IncreaseU-factor % Decrease
4R-7.024%
5R-7.024%
6R-7.026%
7R-9.026%
8R-9.026%

c. Where a mass wall has interior insulation that represents more than 50% of the total wall insulation R-

value, the interior insulation shall extend to the underside of the roof deck, shall be permitted to be interrupted by framing members, and shall comply with one of the following:

  1. Additional insulation having a rated R-value of insulation not less than R-5 shall extend inward on the underside of the roof deck for not less than 2 ft and be permitted to be interrupted by roof framing members.
  2. Additional insulation having a rated R-value of insulation not less than R-5 shall be placed at the exterior of the roof edge and be located between the bottom plane of the roof insulation and the plane of the bottom of the roof assembly in contact with the exterior wall .
  3. The wall insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-1.
  4. The roof insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-2. Informative Note: See Informative Appendix K, Figure K-1.

5.5.5.1.2 Parapets. At roof edges with parapets, the exterior wall insulation shall comply with one or more of the following as applicable to the location of the insulation and wall assembly:

a. Where a wall has exterior continuous insulation, such insulation shall be applied to both vertical sides of

the parapet. Informative Note: See Informative Appendix K, Figure K-2(a). b. Where a wall has cavity or integral insulation that represents more than 50% of the total wall insulation

  1. The wall insulation shall extend within the cavity of the parapet not less than the height of the top of the roof insulation. The wall insulation shall be permitted to be interrupted by roof framing members.
  2. Additional insulation having a rated R-value of insulation not less than R-5 shall extend inward on the underside of the roof deck for not less than 2 ft and be permitted to be interrupted by roof framing members.
  3. Insulation having a rated R-value of insulation not less than R-5 shall be placed at the exterior of the roof edge and be located between the bottom plane of the roof insulation and the plane of the bottom of the roof deck.
  4. The wall insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-1.

62 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

insulation both sides of parapet with exterior wall insulation.

PDF Page 65

Open page note

  1. The roof insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-2. Informative Note: See Informative Appendix K, Figure K-2(b). c. Where a mass wall has interior insulation that represents more than 50% of the total wall insulation R-

value, the interior insulation shall extend to the underside of the roof deck, shall be permitted to be interrupted by framing members, and shall comply with one of the following:

  1. Additional insulation having a rated R-value of insulation not less than R-5 shall extend inward on the underside of the roof deck for not less than 2 ft and be permitted to be interrupted by roof framing members.
  2. Additional insulation having a rated R-value of insulation not less than R-5 shall be placed at the exterior of the roof edge and be located between the bottom plane of the roof insulation and the plane of the bottom of the roof assembly in contact with the exterior wall .
  3. The wall insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-1.
  4. The roof insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.1.1-2. Informative Note: See Informative Appendix K, Figures K-2(c) and K-2(d).

5.5.5.1.3 Parapets within the Field of a Roof. Exterior continuous insulation having a minimum rated R-value of insulation not less than R-5 shall be applied to both vertical sides of the parapet and extend from the coping at the top of the parapet to not less than the top of the roof insulation below.

Informative Notes:

  1. See Informative Appendix K, Figure K-3.
  2. Parapets that are an integral part of a fire-resistance-rated wall, and the exterior continuous insu- lation applied to the parapet, shall comply with the fire resistance ratings of the building code.

5.5.5.2 Walls and Intermediate Floor Intersections. A t floor and exterior wall intersections, the exte- rior wall insulation shall comply with Sections 5.5.5.2.1 and 5.5.5.2.2 as applicable to the type of floor intersection, exterior wall assembly, and location of the exterior wall insulation.

5.5.5.2.1 Intermediate floor edges that do not serve as balconies or floor overhangs shall comply with the following as applicable:

a. Where a wall has exterior continuous insulation, such insulation shall extend continuously past the floor

edge. b. Where a wall has cavity insulation that represents more than 50% of the total wall insulation R-value, the

cavity insulation shall extend to the underside of the floor deck and shall be permitted to be interrupted by floor framing members and wall top and bottom plates or tracks. ( Informative Note: See Informative Appendix K, Figures K-4[a] and K-4[b].) c. Where a mass wall has integral insulation that represents more than 50% of the total wall insulation R-

value, the intermediate floor intersection shall comply with one of the following:

  1. The full thickness of integral insulation shall extend past the floor edge.
  2. Where the intermediate floor deck extends through the integral insulation, insulation having a rated R-value of insulation not less than R-5 shall be maintained to the full depth of the floor edge on the exterior side of the floor edge. See Informative Appendix K, Figures K-4(c) and K-4(d). d. Where a mass wall has interior insulation that represents more than 50% of the total wall insulation R-

value, the interior insulation shall extend to the underside of the floor deck, shall be permitted to be interrupted by framing members, and shall comply with one of the following:

  1. Additional interior insulation having a rated R-value of insulation not less than R-5 shall cover the full depth of the floor edge. Such insulation shall be permitted to be interrupted by floor framing members. Fire safing applied to the full depth of the floor edge meets this requirement.
  2. Additional insulation having a rated R-value of insulation not less than R-5 shall cover the full depth of the floor edge on the exterior side of the wall .
  3. The wall insulation values in Tables 5.5-0 through 5.5-8 shall be adjusted in accordance with Table 5.5.5.2.1. Informative Note: See Informative Appendix K, Figures K-4(e) and K-4(f). e. Where mass walls have not less than 50% of the rated R-value of insulation on the exterior side of the

wall and the remainder on the interior side, the insulation on the interior side of the wall shall be permit

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 63

PDF Page 66

Open page note

with Section 5.5.5.2.1(d)(3)Col2Col3
Climate ZoneR-Value IncreaseU-factor % Decrease
4R-1.513%
5R-2.015%
6R-2.516%
7R-3.020%
8R-4.025%
Climate ZoneMaximum Percent of Building Perimeter
435%
530%
620%
710%
80%

17

18

15

Table 5.5.5.2.1 Additional Wall Insulation Required for Mass Walls With Insulation on the Interior Complying

Table 5.5.5.2.2 Mass Floor Balcony or Floor Overhang Allowances

ted to be interrupted by an intermediate floor . ( Informative Note: See Informative Appendix K, Figure K-4[g].)

5.5.5.2.2 The total length of mass floor assembly projections serving as balconies or floor overhangs that penetrate the building envelope shall not exceed the percentages of the total building perimeter depicted in Table 5.5.5.2.2. For this calculation, total building perimeter is the sum of the perimeters of each above_grade_ floor where it intersects the exterior building envelope .

Exceptions to 5.5.5.2.2:

  1. Mass floor assembly projections located directly above and providing protection to a pedestrian walkway at street-level.
  2. Mass floor assembly projections thermally broken with a continuous thermal spacer block not less than R-12. The thermal spacer block shall be permitted to be interrupted by structural connections.

struction using point connections to accommodate the full depth of any exterior continuous insulation exclusive of the point connections.

Exception to 5.5.5.3: Girts in metal building walls as described in Normative Appendix A.

( Informative Note: See Informative Appendix K, Figure K-5.)

5.5.5.4 Opaque Wall and Vertical Fenestration Intersection. Vertical fenestration shall be installed in accordance with one or more of the following:

a. For vertical fenestration, the outermost glazing layer shall be aligned within the thickness of or within 2

in. of either face of the continuous insulation layer. ( Informative Note: See Informative Appendix K, Figures K-6[a] and K-6[b].) b. For vertical fenestration, where continuous insulation is not present, the outermost glazing layer shall be

aligned within the thickness of the wall insulation layer and not more than 2 in. from the exterior side of the outermost insulation layer. ( Informative Note: See Informative Appendix K, Figure K-6[c].) c. Intersections between vertical fenestration and opaque walls where the surfaces of the rough opening

located between the edge of the frame of the vertical fenestration and the opaque wall insulation shall be

64 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 67

Open page note

Allowable Area per Point Thermal Bridge,
in.2
Common Material Name
3Carbon steel
9Stainless steel
65Concrete and masonry

16

Table 5.5.5.5 Allowable Point Thermal Bridge Cross-Sectional Area

shall have a thermal break with a thermal conductivity of 3.6 Btu·in/ h·ft [2] ·°F or less. Exception to 5.5.5.4: Intersections between vertical fenestration and uninsulated opaque walls .

5.5.5.5 Other Elements and Building Assembly Intersections. Individual point thermal bridges and

Above grade area of the building envelope ≥ ( k 1 × A 1) + ( k 2 × A 2) + ( k 3 × A 3) … (5.5.5.5)

where k 1, k 2, k 3 … = thermal conductivity of material 1, material 2, material 3, etc., expressed in Btu·in./ (ft [2] ·h·°F) for point thermal bridge material 1, material 2, material 3, etc. (e.g., concrete, carbon steel, stainless steel, wood) A 1, A 2, A 3, … = the total cross-sectional area of point thermal bridges and linear thermal bridges of material 1, material 2, material 3, etc., expressed in ft [2]

Exceptions to 5.5.5.5:

  1. Service penetrations, including mechanical, electrical, plumbing, telecommunications, and fire services, that pass through the opaque building envelope .
  2. Insulated roof curbs and blocking.
  3. Individual point thermal bridges that are less than the allowances in Table 5.5.5.5.

( Informative Note: See ASHRAE Handbook—Fundamentals Appendix A, Chapter 26, or Chapter 33 for typical material thermal conductivity.)

5.6 Building Envelope Trade-Off Compliance Path 5.6.1 The building envelope complies with the standard if

a. the proposed design satisfies the provisions of Sections 5.1, 5.4, 5.7, 5.8, and 5.9 and b. the proposed envelope performance factor of the proposed design is less than or equal to the proposed

envelope performance factor of the base design .

5.6.1.1 All components of the building envelope shown on architectural drawings or installed in existing buildings shall be modeled in the proposed design . The simulation program model fenestration and opaque

5.6.1.2 Trade-Offs Limited to Building Permit. When the building permit being sought applies to less than the whole building, parameters relating to unmodified existing conditions or to future building components shall be identical for both the proposed envelope performance factor and the base envelope perfor- mance factor . Future building components shall meet the prescriptive requirements of Section 5.5.

5.6.1.3 Envelope performance factor shall be calculated using the procedures of Normative Appendix C.

5.7 Submittals 5.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 65

PDF Page 68

Open page note

a. A report complying with Section 4.2.5.1.2 providing the results of continuous air barrier compliance

with whole- building pressurization testing in accordance with Section 5.4.3.1.4 or verification of the building envelope in accordance with Section 5.9.1.2. b. Insulation documentation in accordance with Section 5.8.1.11.

5.7.3.2 Manuals. Construction documents shall require that an operating manual and a maintenance manual be provided to the building owner, or the designated representative of the building owner, within 90 days after the date of building envelope acceptance. These manuals shall be in accordance with industryaccepted standards (see Informative Appendix E) and shall include, at a minimum, operation manuals and maintenance manuals for each component of the building envelope requiring maintenance, except components not furnished as part of the project. Required routine maintenance actions shall be clearly identified.

5.8.1.1 Labeling of Building Envelope Insulation. The rated R-value of insulation shall be clearly identified by an identification mark applied by the manufacturer to each piece of building envelope insulation.

Exceptions to 5.8.1.1: When insulation does not have such an identification mark, the rated R-value of

insulation and the additional information specified below shall be identified by the manufacturer on each package, shipping container, or bundle of insulation. Insulation documentation shall be provided in accordance with Section 5.8.1.11 and the following:

  1. For batts and blankets of any type: The rated R-value of insulation, length, width, thickness.
  2. For boardstock: The rated R-value of insulation, length, width, and thickness of the boards in the package.
  3. For all loose-fill insulation: The minimum settled thickness, initial installed thickness, maximum net coverage area, number of bags per 1000 ft [2] and minimum weight per ft [2] at R-values of 13, 19, 30, 38, and 49. The package shall also state the minimum net weight of the insulation in the package.
  4. For spray-applied polyurethane foam: The R-value for the insulation at a 1 in. thickness and additional inch increments up to the maximum thickness allowed.

5.8.1.2 Manufacturer’s Installation Instructions. Insulation materials shall be installed in accordance with the manufacturer ’s recommendations and in such a manner as to achieve the rated R-value of insulation .

Exceptions to 5.8.1.2:

  1. The R-value of compressed cavity insulation is determined in accordance with Table A9.4.3.
  2. Where metal building roof or wall insulation is compressed between the steel structure and the metal roof or wall panels, the overall assembly U-factor is determined in accordance with Section A2.3, Section A3.2, or Section A9.4.6.

66 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 69

Open page note

5.8.1.3 Loose-Fill Insulation Limitation. Open-blown or poured loose-fill insulation shall not be used in attic roof spaces when the slope of the ceiling is more than three in twelve.

5.8.1.4 Baffles. When eave vents are installed, baffling of the vent openings shall be provided to deflect the incoming air above the surface of the insulation.

5.8.1.5 Substantial Contact. Insulation shall be installed in a permanent manner in substantial contact with the inside surface in accordance with the manufacturer ’s recommendations for the framing system used. Flexible batt insulation installed in floor cavities shall be supported in a permanent manner by supports no greater than 24 in. on center.

Exception to 5.8.1.5: Insulation materials that rely on air spaces adjacent to reflective surfaces for their

rated performance.

5.8.1.6 Recessed Equipment. Lighting fixtures ; heating, ventilating, and air-conditioning equipment, including wall heaters, ducts, and plenums ; and other equipment shall not be recessed in such a manner as to affect the insulation thickness unless

a. the total combined area affected (including necessary clearances) is less than 1% of the opaque area of

the assembly, b. the entire roof, wall, or floor is covered with insulation to the full depth required, or c. the effects of reduced insulation are included in calculations using an area-weighted-average method and

compressed insulation values obtained from Table A9.4.3.

In all cases, air leakage through or around the recessed equipment to the conditioned space shall be limited in accordance with Section 5.4.3.

5.8.1.7 Insulation Protection. Exterior insulation shall be covered with a protective material to prevent damage from sunlight, moisture, landscaping operations, equipment maintenance, and wind.

5.8.1.7.1 In attics and mechanical rooms, a way to access equipment that prevents damaging or compressing the insulation shall be provided.

5.8.1.7.2 Foundation vents shall not interfere with the insulation. 5.8.1.7.3 Insulation materials in ground contact shall have a water absorption rate no greater than 0.3% when tested in accordance with ASTM C272.

5.8.1.8 Location of Roof Insulation. The roof insulation shall not be installed on a suspended ceiling with removable ceiling panels.

5.8.1.9 Extent of Insulation. Insulation shall extend over the full component area to the required rated R-value of insulation, U-factor, C-factor, or F-factor, unless otherwise allowed in Section 5.8.1.

5.8.1.10 Joints in Rigid Insulation. Where two or more layers of rigid insulation board are used in a construction assembly, the edge joints between each layer of boards shall be staggered.

5.8.2.1 Rating of Fenestration Products. The U-factor, SHGC, VT, and air leakage rate for all manufactured fenestration products shall be determined by a laboratory accredited by a nationally recognized accreditation organization, such as the National Fenestration Rating Council.

5.8.2.2 Labeling of Fenestration and Door Products. All manufactured and site -built fenestration and

Exception to 5.8.2.2: Doors with less than 25% glazing are not required to list SHGC and VT .

5.8.2.3 Manufacturer’s Installation Instructions. Fenestration products shall be installed in accordance with manufacturer ’s instructions.

5.8.2.4 U-Factor. U-factors shall be determined in accordance with NFRC 100. U-factors for skylights shall be determined for a slope of 20 degrees above the horizontal.

Exceptions to 5.8.2.4:

  1. U-factors from Section A8.1 shall be an acceptable alternative for determining compliance with the U-factor criteria for skylights . Where credit is being taken for a low-emissivity coating, the emissivity of the coating shall be determined in accordance with NFRC 300. Emissivity shall be verified and certified by the manufacturer .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 67

PDF Page 70

Open page note

  1. U-factors from Section A8.2 shall be an acceptable alternative for determining compliance with the U-factor criteria for vertical fenestration .
  2. U-factors from Section A7 shall be an acceptable alternative for determining compliance with the U-factor criteria for opaque doors .
  3. For sectional garage doors and metal coiling doors, ANSI/DASMA105 shall be an acceptable alternative for determining U-factors .

5.8.2.5 Solar Heat Gain Coefficient. SHGC for the overall fenestration area shall be determined in accordance with NFRC 200.

Exceptions to 5.8.2.5:

  1. Shading coefficient ( SC ) of the center-of-glass multiplied by 0.86 shall be an acceptable alternative for determining compliance with the SHGC requirements for the overall fenestration area . SC shall be determined using a spectral data file determined in accordance with NFRC 300. SC shall be verified and certified by the manufacturer .
  2. SHGC of the center-of-glass shall be an acceptable alternative for determining compliance with the SHGC requirements for the overall fenestration area . SHGC shall be determined using a spectral data file determined in accordance with NFRC 300. SHGC shall be verified and certified by the manufacturer .
  3. SHGC from Section A8.1 shall be an acceptable alternative for determining compliance with the SHGC criteria for skylights . Where credit is being taken for a low-emissivity coating, the emissivity of the coating shall be determined in accordance with NFRC 300. Emissivity shall be verified and certified by the manufacturer .
  4. SHGC from Section A8.2 shall be an acceptable alternative for determining compliance with the SHGC criteria for vertical fenestration .

5.8.2.6 Visible Transmittance. VT shall be determined in accordance with NFRC 200. VT shall be verified and certified by the manufacturer .

Exceptions to 5.8.2.6:

  1. VTannual determined in accordance with NFRC 203 shall be an acceptable alternative for determining compliance with the VT requirements for tubular daylighting devices.
  2. For skylights whose transmittances are not within the scope of NFRC 200, their transmittance shall be the solar photometric transmittance of the skylight glazing materials determined in accordance with ASTM E972.

5.8.3 Air Leakage 5.8.3.1 Testing, Acceptable Materials, and Assemblies. Air leakage for materials or assemblies used as components of the continuous air barrier shall be determined in accordance with the test method and minimum air pressure specified in Table 5.8.3.1 and shall not exceed the maximum air leakage specified in Table 5.8.3.1 when complying with the continuous air barrier design and installation verification program in accordance with Section 5.9.1.2. Air leakage shall be determined by a laboratory accredited by a nationally recognized accreditation organization.

5.8.3.2 Fenestration and Doors. Air leakage for fenestration and doors shall be determined in accordance with the test method and minimum air pressure specified in Table 5.8.3.2 and shall not exceed the maximum air leakage specified in Table 5.8.3.2 when complying with the continuous air barrier design and installation verification program in accordance with Section 5.9.1.2. Air leakage shall be determined by a laboratory accredited by a nationally recognized accreditation organization and shall be labeled and certified by the manufacturer .

Exceptions to 5.8.3.2:

  1. Field-fabricated fenestration and doors .
  2. Metal coiling doors in semiheated spaces in Climate Zones 0 through 6 shall have an air leakage not exceeding 1.0 cfm/ft [2] when tested at a pressure of at least 1.57 psf in accordance with ANSI/ DASMA 105, NFRC 400, or ASTM E283.
  3. Products in buildings that are tested and shown to comply with a whole- building air leakage in accordance with Section 5.4.3.1.4.

5.9 Verification, Testing, and Commissioning 5.9.1 Verification and Testing 5.9.1.1 Building Envelope Performance Verification. The building envelope shall be verified in

68 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 71

Open page note

Table 5.8.3.1 Maximum Air Leakage for Materials and Assemblies

Continuous Air BarrierMaximum Air Leakage,
cfm/ft2
Minimum Test Pressure,
psf
Test Method
Materials a0.0041.57ASTM E2178
Assemblies b0.041.57ASTM E2357, ASTM E1677,
ASTM E1680, ASTM E283

a. The following materials comply with the requirements in Table 5.8.3.1:

  1. Plywood—minimum 3/8 in.

  2. Oriented strand board—minimum 3/8 in.

  3. Extruded polystyrene insulation board—minimum 1/2 in.

  4. Foil-faced polyisocyanurate insulation board—minimum 1/2 in.

  5. Exterior gypsum sheathing or interior gypsum board—minimum 1/2 in.

  6. Cement board—minimum 1/2 in.

  7. Built-up roofing membrane

  8. Modified bituminous roof membrane

  9. Single-ply roof membrane

  10. A Portland cement/sand parge, stucco, or gypsum plaster—minimum 1/2 in. thick

  11. Cast-in-place and precast concrete

  12. Sheet metal

  13. Closed-cell 2 lb/ft [3] nominal density spray polyurethane foam—minimum 1 in. b. The following assemblies comply with the requirements in Table 5.8.3.1:

  14. Concrete masonry walls that are (a) fully grouted or (b)painted to fill the pores

  15. Shale or clay masonry units that are assembled as a solid wall : without weeps, with nominal width of 4 in. or more, and with Type S mortar

Table 5.8.3.2 Maximum Air Leakage for Fenestration and DoorsCol2Col3Col4
Fenestration and Door ProductsMaximum Air
Leakage, cfm/ft2
Minimum Test
Pressure, psf
Test Methods
Glazed swinging_entrance doors_, glazed power-operating sliding_entrance_
doors, glazed power-operated folding_entrance doors_, and revolving_doors_
1.01.57AAMA/WDMA/CSA
101/I.S.2/A440,
NFRC 400,
or ASTM E283;
Curtainwall and storefront glazing0.061.57NRFC 400 or
ASTM 283
Unit_skylights_ having condensation weepage openings0.31.57AAMA/WDMA/CSA
101/I.S.2/A440 or
NFRC 400
Unit_skylights_ having condensation weepage openingsOROROR
Unit_skylights_ having condensation weepage openings0.56.24AAMA/WDMA/CSA
101/I.S.2/A440
Nonswinging doors intended for vehicular access and material
transportation, with a minimum opening rate of 32 in./s
1.31.57ANSI/DASMA 105,
NFRC 400, or ASTM
E283
Other_opaque nonswinging doors_, glazed_sectional garage doors_, and
upward acting glazed_nonswinging_
0.41.57ANSI/DASMA 105,
NFRC 400, or ASTM
E283
All other products0.21.57AAMA/WDMA/CSA
101/I.S.2/A440 or
NFRC 400
All other productsOROROR
All other products0.36.24AAMA/WDMA/CSA
101/I.S.2/A440

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 69

PDF Page 72

Open page note

5.9.1.2 Verification of the Design and Installation of the Continuous Air Barrier. Where verification of the design and installation of the continuous air barrier is used for compliance in Section 5.4.3.1, it shall be determined in accordance with the following:

  1. plan.Verification and “FUNCTIONAL PERFORMANCE TESTING” = VERIFY AB IS FUNCTIONING FPT documentation shall comply with Section 4.2.5.1.2 and the field inspection V&T PROVIDER CERT COMPLETION OF FPT PLAN DEFERRED FPT, TO OWNER. 5.9.1.3 Dynamic Glazing. Dynamic glazing operation shall be tested for conformance with the manu- facturer’s installation instructions.

AB DOC AB FENEST

“FUNCTIONAL PERFORMANCE TESTING” = VERIFY AB IS FUNCTIONING V&T PROVIDER CERT COMPLETION OF FPT PLAN DEFERRED FPT, TO OWNER.

5.9.1.4 Air Curtains. Air curtains shall comply with Section 10.4.5. 5.9.2 Commissioning. The energy performance of the building envelope shall be commissioned i n accordance with Section 4.2.5.2. Commissionin g reporting shall comply with Section 4.2.5.2.2.

Informative Note: See Informative Appendix E and Informative Appendix H for commissioning references and guidance.

70 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 73

Open page note

6. HEATING, VENTILATING, AND AIR CONDITIONING

6.1 General 6.1.1 Scope. Section 6 specifies requirements for mechanical equipment and systems. 6.1.2 New Buildings. Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of new buildings shall comply with the requirements of this section as described in Section 6.2.

6.1.3 Additions to Existing Buildings. Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of additions to existing buildings shall comply with the requirements of this section as described in Section 6.2.

Exception to 6.1.3: When HVACR to an addition is provided by existing HVACR systems and equip-

ment, such existing systems and equipment shall not be required to comply with this standard. However, any new systems or equipment installed must comply with specific requirements applicable to those systems and equipment .

6.1.4 Alterations to Heating, Ventilating, Air Conditioning, and Refrigeration in Existing Buildings 6.1.4.1 New HVACR equipment as a direct replacement of existing HVACR equipment shall comply with the following sections as applicable for the equipment being replaced:

a. 6.3, “Simplified Approach Building Compliance Path for HVAC Systems” b. 6.4.1, “Equipment Efficiencies, Verification, and Labeling Requirements” c. 6.4.3.1, “Zone Thermostatic Controls” d. 6.4.3.2, “Set-Point Overlap Restrictions” e. 6.4.3.3, “Off-Hour Controls” except for Section 6.4.3.3.4, “Zone Isolation” f. 6.4.3.4, “Ventilation System Controls” g. 6.4.3.7, “Freeze Protection and Snow/Ice Melting Systems” h. 6.4.3.8, “Ventilation Controls for High-Occupancy Areas” only for single-zone equipment i. 6.4.3.9, “Heated or Cooled Vestibules or Air Curtains with Integral Heating” j. 6.4.5, “Walk-In Coolers and Walk-In Freezers” k. 6.5.1.1, “Air Economizers” for units located outdoors l. 6.5.1.3, “Integrated Economizer Control” m. 6.5.1.4, “Economizer Heating System Impact” n. 6.5.3.1.3, “Fan Efficiency”

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 71

PDF Page 74

Open page note

o. 6.5.3.2.1, “Supply Fan Airflow Control” p. 6.5.3.6, “Fractional Horsepower Fan Motors” q. 6.5.4.1, “Boiler Turndown” r. 6.5.4.3, “Chiller and Boiler Isolation” s. 6.5.5.2, “Fan Speed Control”

6.1.4.2 New cooling systems installed to serve previously uncooled spaces shall comply with this section as described in Section 6.2.

6.1.4.3 Alterations to existing cooling systems shall not decrease economizer capability unless the sys- tem complies with Section 6.5.1.

6.1.4.4 New and replacement ductwork shall comply with Sections 6.4.4.1 and 6.4.4.2. 6.1.4.5 New and replacement piping shall comply with Section 6.4.4.1. Exceptions to 6.1.4.5: Compliance shall not be required

  1. for equipment that is being modified or repaired but not replaced, provided that such modifications and/or repairs will not result in an increase in the annual energy consumption of the equip- ment using the same energy type;
  2. where a replacement or alteration of equipment requires extensive revisions to other systems, equipment, or elements of a building, and such replaced or altered equipment is a like-for-like replacement;
  3. for a refrigerant change of existing equipment ;
  4. for the relocation of existing equipment ; or
  5. for ducts and piping where there is insufficient space or access to meet these requirements.

6.1.5 Climate. Climate zones shall be determined in accordance with Section 5.1.5.

6.2 Compliance Paths. Mechanical equipment and systems providing heating, cooling, ventilating, or refrigeration shall comply with Sections 6.2.1 and 6.2.2.

6.2.1 Requirements for all Compliance Paths. Mechanical equipment and systems shall comply with all of the following:

a. Section 6.1, “General” b. Section 6.4, “Mandatory Provisions”

Exception to 6.2.1(b): When compliance is shown using Section 6.2.2(a), compliance with Section 6.4

is not required unless required in Section 6.3.2. c. Section 6.7, “Submittals” d. Section 6.8, “Minimum Equipment Efficiency Tables”

6.2.2 Additional Requirements to Comply with Section 6. Refrigeration equipment and systems shall comply with Section 6.5, “Prescriptive Compliance Path.” All building HVAC systems shall comply with one of the following:

a. Section 6.3, “Simplified Approach Building Compliance Path for HVAC Systems” b. Section 6.5, “Prescriptive Compliance Path” c. Section 6.6.1, “Computer Room System Path” d. Section 6.6.2, “Mechanical System Performance Path”

Informative Note: Section 6.3 requires all HVAC systems in the building to qualify for the simplified path. Section 6.6.2 requires all allowable systems to meet Normative Appendix L requirements. Section 6.6.2 does allow part of the building to use the Mechanical System Performance Path and part of the building to use Section 6.5 where there are excluded occupancy types or system types in Section L1.1.1.2. HVAC sys- tems for larger computer rooms may comply with either Section 6.5, Section 6.6.1, or Section 6.6.2.

6.3 Simplified Approach Building Compliance Path for HVAC Systems 6.3.1 Scope. The simplified approach is an optional path for compliance when the following conditions are met:

a. The building is two stories or fewer in height. b. Gross floor area is less than 25,000 ft [2] . c. Each HVAC system in the building complies with the requirements listed in Section 6.3.2.

6.3.2 Criteria. The HVAC system must meet all of the following criteria:

a. The system serves a single HVAC zone . b. The equipment must meet the variable flow requirements of Section 6.5.3.2.1.

72 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 75

Open page note

c. Cooling (if any) shall be provided by a unitary packaged or split- system air conditioner that is either air

cooled or evaporatively cooled, with efficiency meeting the requirements shown in Table 6.8.1-1 (air conditioners), Table 6.8.1-2 (heat pumps), or Table 6.8.1-4 (packaged terminal and room air condition- ers and heat pumps) for the applicable equipment category. Cooling equipment shall also comply with Section 6.4.1.4. d. The system shall have an air economizer meeting the requirements of Sections 6.5.1 and 6.4.3.12. e. Heating (if any) shall be provided by a unitary packaged or split- system heat pump that meets the appli cable efficiency requirements shown in Table 6.8.1-2 (heat pumps) or Table 6.8.1-4 (packaged terminal and room air conditioners and heat pumps), a fuel -fired furnace that meets the applicable efficiency requirements shown in Table 6.8.1-5 (furnaces, duct furnaces, and unit heaters), an electric resistance heater, or a baseboard system connected to a boiler that meets the applicable efficiency requirements shown in Table 6.8.1-6 ( boilers ). Heating equipment shall also comply with Section 6.4.1.4. f. The system shall meet the exhaust air energy recovery requirements of Section 6.5.6.1. g. The system shall be controlled by a manual changeover or dual set-point thermostat . h. If a heat pump equipped with auxiliary internal electric resistance heaters is installed, controls shall be

provided that prevent supplemental heater operation when the heating load can be met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation is permitted during outdoor coil defrost cycles. The heat pump must be controlled by either (1) a digital or electronic thermostat designed for heat pump use that energizes auxiliary heat only when the heat pump has insufficient capacity to maintain set point or to warm up the space at a sufficient rate or (2) a multistage space thermostat and an outdoor air thermostat wired to energize auxiliary heat only on the last stage of the space thermostat and when outdoor air temperature is less than 40°F. Exceptions to 6.3.2.(h): Heat pumps that comply with the following:

  1. Have a minimum efficiency regulated by NAECA.
  2. Meet the requirements in Table 6.8.1-2.
  3. Include all usage of internal electric resistance heating. i. The system controls shall not permit reheat or any other form of simultaneous heating and cooling for humidity control. Exception to 6.3.2(i): Humidity control assisted by hot-gas reheat or heat from 100% site-recovered

energy is permitted. j. Systems serving spaces other than residential spaces, that do not require continuous operation, with a cooling or heating capacity greater than 7000 Btu/h shall comply with Sections 6.4.3.3.1 and 6.4.3.3.2. k. Systems serving residential spaces other than hotel/motel guest rooms shall comply with Sections

6.4.3.3.1 and 6.4.3.3.2 except for electric resistance heaters rated at 2 hp or less with a readily accessible manual control that lowers the set point or turns the unit off. l. Systems serving hotel/motel guest rooms shall comply with Section 6.4.3.3.5. m. Except for piping within manufacturers ’ units, HVAC piping shall be insulated in accordance with

Tables 6.8.3-1 and 6.8.3-2. Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. n. Ductwork and plenums shall be insulated in accordance with Table 6.8.2 and shall be sealed in accor dance with Section 6.4.4.2.1. o. Construction documents shall require a ducted system to be air balanced in accordance with industry

accepted procedures. p. Outdoor air intake and exhaust systems shall meet the requirements of Section 6.4.3.4. q. Where separate heating and cooling equipment serves the same temperature zone, thermostats shall be

interlocked to prevent simultaneous heating and cooling. r. Systems with a design supply air capacity greater than 10,000 cfm shall have optimum start controls . s. The system shall comply with the demand control ventilation requirements in Section 6.4.3.8, occupiedstandby controls in Section 6.5.3.9, and the ventilation design requirements in Section 6.5.3.8. t. The system complies with the door switch requirements in Section 6.5.10.

6.4 Mandatory Provisions 6.4.1 Equipment Efficiencies, Verification, and Labeling Requirements 6.4.1.1 Minimum Equipment Efficiencies—Listed Equipment—Standard Rating and Operating Conditions. Equipment shown in Tables 6.8.1-1 through 6.8.1-21 shall have a minimum performance at the specified rating conditions when tested in accordance with the specified test procedure. Where multiple rating

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 73

PDF Page 76

Open page note

conditions or performance requirements are provided, the equipment shall satisfy all stated requirements unless otherwise exempted by footnotes in the table. Equipment covered under the Federal Energy Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation at minimum capacity or other than standard rating conditions. Equipment used to provide service water-heating functions as part of a combination system shall satisfy all stated requirements for the appropriate space heating or cooling category.

Tables are as follows:

a. Table 6.8.1-1, “Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Effi ciency Requirements” b. Table 6.8.1-2, “Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency Require ments” c. Table 6.8.1-3, “Liquid-Chilling Packages—Minimum Efficiency Requirements” (See Section 6.4.1.2 for

liquid-cooled centrifugal liquid-chilling packages that are designed to operate at nonstandard conditions.) d. Table 6.8.1-4, “Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat

Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air Conditioner Heat Pumps—Minimum Efficiency Requirements” e. Table 6.8.1-5, “Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units,

Warm-Air Duct Furnaces, and Unit Heaters—Minimum Efficiency Requirements” f. Table 6.8.1-6, “Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements” g. Table 6.8.1-7, “Performance Requirements for Heat-Rejection Equipment—Minimum Efficiency

Requirements” h. Table 6.8.1-8, “Electrically Operated Variable-Refrigerant-Flow Air Conditioners—Minimum Effi ciency Requirements” i. Table 6.8.1-9, “Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements j. Table 6.8.1-10, “Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms— Minimum Efficiency Requirements” k. Table 6.8.1-11, “Commercial Refrigerators, Commercial Freezers, and Refrigeration—Minimum Effi ciency Requirements” l. Table 6.8.1-12, “Vapor-Compression-Based Indoor Pool Dehumidifiers—Minimum Efficiency Requirements” m. Table 6.8.1-13, “Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, with out Energy Recovery—Minimum Efficiency Requirements” n. Table 6.8.1-14, “Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, with

Energy Recovery—Minimum Efficiency Requirements” o. Table 6.8.1-15, “Electrically Operated Water-Source Heat Pumps—Minimum Efficiency Requirements” p. Table 6.8.1-16, “Heat Pump and Heat Recovery Water-Chilling Packages—Minimum Efficiency

Requirement” q. Table 6.8.1-17, “Ceiling-Mounted Computer-Room Air Conditioners—Minimum Efficiency Require ments” r. Table 6.8.1-18, “Walk-In Cooler and Freezer Display Door Efficiency Requirements” s. Table 6.8.1-19, “Walk-In Cooler and Freezer Nondisplay Door Efficiency Requirements” t. Table 6.8.1-20, “Walk-In Cooler and Freezer Refrigeration System Efficiency Requirements” u. Table 6.8.1-21, “Ceiling Fan Efficiency Requirements”

6.4.1.2 Minimum Equipment Efficiencies—Listed Equipment—Nonstandard Conditions 6.4.1.2.1 Liquid-Cooled Centrifugal Chilling Package Cooling Efficiency Adjustment. Liquidcooled centrifugal chiller packages not designed for cooling operation at AHRI Standard 550/590 test and rating conditions of 44.00°F leaving and 54.00°F entering chilled-liquid temperatures, and with 85.00°F entering and 94.30°F leaving condenser-liquid temperatures, shall have maximum full-load kW /ton (FL) and part-load cooling energy efficiency ( IPLV .IP) rating requirements, listed in Tables 6.8.1-3 and 6.8.1-16, adjusted using the following equations:

FL.IP adj = FL.IP/ Kadj PLV.IP adj = IPLV .IP/ Kadj

Kadj = A × B

where

74 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 77

Open page note

FL.IP = full-load kW /ton value from Table 6.8.1-3 or 6.8.1-16

FL.IP adj = maximum full-load kW /ton rating, adjusted for nonstandard conditions

IPLV. IP = IPLV. IP value from Table 6.8.1-3 or 6.8.1-16

PLV . IP adj = maximum NPLV. IP rating, adjusted for nonstandard conditions

A = 0.00000014592 × (LIFT) [4] - 0.0000346496 × (LIFT) [3 ] + 0.00314196 × (LIFT) [2] - 0.147199 × (LIFT) + 3.93073

B = 0.0015 × LvgEvap + 0.934

LIFT = LvgCond – LvgEvap

LvgCond = full-load condenser leaving liquid temperature, °F

LvgEvap = full-load evaporator leaving liquid temperature, °F

The FL . IP adj and PLV . IP adj values are only applicable for centrifugal chilling packages meeting all of the following full-load design ranges:

  • 36.00°F  LvgEvap  70.00°F and

  • 60.00°F  LvgCond  135.00°F and

  • 20.00°F  LIFT  80.00°F

Manufacturers shall calculate the FL.IP adj and PLV.IP adj before determining whether to label the chiller per Section 6.4.1.5. Compliance with Standard 90.1-2007, 2010, 2013, 2016, 2019, 2022, or combinations thereof, shall be labeled on chilling packages within the scope of the standard.

Centrifugal chilling packages designed to operate outside of these ranges are not covered by this standard.

6.4.1.2.2 Chilling Packages Employing Freeze-Protection Liquids. Electrically operated chilling packages that employ freeze-protection liquids in any heat exchanger with an application cooling duty evaporator liquid leaving temperature or heating operation source liquid temperature above 32.00°F shall show efficiency compliance in accordance with the applicable requirements in Sections 6.4.1.2.2.1 through 6.4.1.2.2.4. Absorption chilling packages with freeze-protection liquids are exempt from the efficiency requirements listed in Table 6.8.1-3 and shall only show compliance when applied with water.

6.4.1.2.2.1 All electrically operated cooling-only air-cooled and electrically operated positive displacement liquid-cooled chilling packages shall show compliance with the cooling efficiency requirements listed in Table 6.8.1-3when applied within the operating limits of AHRI 550/590 at AHRI 550/590 standard rating conditions when tested or rated with water used as a heat transfer liquid.

6.4.1.2.2.2 All liquid-cooled electrically operated cooling-only centrifugal chilling packages shall show compliance with the cooling efficiency requirements listed in Table 6.8.1-3 when applied within the operating limits defined in AHRI 550/590 at the application rating conditions for a cooling efficiency, adjusted using Kadj as defined in Section 6.4.1.2.1, when tested or rated with water used as a heat transfer liquid.

6.4.1.2.2.3 All electrically operated air source and electrically operated positive displacement liquidsource heat pump and heat recovery chilling packages shall show compliance with the cooling efficiency requirements listed in Table 6.8.1-16 when applied within the operating limits of AHRI 550/590 at AHRI 550/ 590 standard rating conditions when tested or rated with water used as a heat transfer liquid. They also shall show compliance with the heating efficiency requirements listed in Table 6.8.1-16 at one of the AHRI 550/590 standard heating rating conditions when tested or rated with water used as a heat transfer liquid. Heating-only chilling packages shall meet the efficiency requirements at one of the AHRI 550/590 heating liquid temperature rating conditions and are not required to meet the cooling efficiency requirements of Table 6.8.1-16.

6.4.1.2.2.4 All liquid-source centrifugal heat pump and heat recovery chilling packages shall show compliance with the cooling efficiency requirements listed in Table 6.8.1-16 when applied within the operating limits defined in AHRI 550/590 at the application rating conditions for cooling efficiency, adjusted using Kadj as defined in Section 6.4.1.2.1, when tested or rated with water. They also shall show compliance with the heating efficiency requirements in Table 6.8.1-16 at one of the AHRI 550/590 standard rating conditions when tested or rated with water used as a heat-transfer liquid. Heating-only chilling packages shall meet the heating efficiency requirements at one of the AHRI 550/590 heating liquid temperature rating conditions and are not required to meet the cooling efficiency requirements of Table 6.8.1-16.

6.4.1.3 Equipment not Listed. Equipment not listed in the tables referenced in Sections 6.4.1.1 and 6.4.1.2 may be used.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 75

PDF Page 78

Open page note

6.4.1.4 Verification of Equipment Efficiencies. Equipment efficiency information supplied by manu- facturers shall be verified by one of the following:

a. Equipment covered under EPACT shall comply with U.S. Department of Energy certification require ments. b. If a certification program exists for a covered product, and it includes provisions for verification and

challenge of equipment efficiency ratings, then the product shall be listed in the certification program. c. If a certification program exists for a covered product, and it includes provisions for verification and

challenge of equipment efficiency ratings, but the product is not listed in the existing certification program, the ratings shall be verified by an independent laboratory test report. d. If no certification program exists for a covered product, the equipment efficiency ratings shall be sup ported by data furnished by the manufacturer . e. Where components such as indoor or outdoor coils from different manufacturers are used, the system

designer shall specify component efficiencies whose combined efficiency meets the minimum equipment efficiency requirements in Section 6.4.1. 6.4.1.5 Labeling 6.4.1.5.1 Mechanical Equipment. Mechanical equipment that is not covered by the U.S. National Appliance Energy Conservation Act (NAECA) of 1987 shall carry a permanent label installed by the manu- facturer stating that the equipment complies with the requirements of Standard 90.1.

6.4.1.5.2 Packaged Terminal Air Conditioners. Nonstandard-size packaged terminal air condition- ers and heat pumps with existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in. [2] shall be factory labeled as follows: “Manufactured for nonstandard-size applications only: Not to be installed in new construction projects.”

6.4.2 Calculations 6.4.2.1 Load Calculations. Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with ASHRAE/ACCA Standard 183.

6.4.2.2 Pump Head. Pump differential pressure (head) for the purpose of sizing pumps shall be determined in accordance with generally accepted engineering standards and handbooks acceptable to the adopt- ing authority . The pressure drop through each device and pipe segment in the critical circuit at design conditions shall be calculated.

6.4.3 Controls and Diagnostics 6.4.3.1 Zone Thermostatic Controls 6.4.3.1.1 General. The supply of heating and cooling energy to each zone shall be individually controlled by thermostatic controls responding to temperature within the zone. For the purposes of this section, a dwelling unit shall be permitted to be considered a single zone.

Exceptions to 6.4.3.1.1: Independent perimeter systems that are designed to offset only building enve-

lope loads shall be permitted to serve one or more zones also served by an interior system, provided that

  1. the perimeter system includes at least one thermostatic control zone for each building exposure having walls facing only one orientation for 50 contiguous feet or more and
  2. the perimeter system heating and cooling supply is controlled by thermostatic controls located within the zones served by the system .

Exterior walls and semiexterior walls are considered to have different orientations if the exposures they face differ by more than 45 degrees. 6.4.3.1.2 Dead Band. Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.

Exceptions to 6.4.3.1.2:

  1. Thermostats that require manual changeover between heating and cooling modes.
  2. Special occupancy or special applications where wide temperature ranges are not acceptable (such as retirement homes, process applications, museums, some areas of hospitals) and are approved by the authority having jurisdiction .

6.4.3.2 Set-Point Overlap Restriction. Where heating and cooling to a zone are controlled by separate zone thermostatic controls located within the zone, means (such as limit switches; mechanical stops; or, for DDC systems, software programming) shall be provided to prevent the heating set point from exceeding the cooling set point, minus any applicable proportional band.

76 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 79

Open page note

6.4.3.3 Off-Hour Controls. HVAC systems shall have the off-hour controls required by Sections 6.4.3.3.1 through 6.4.3.3.5. Exceptions to 6.4.3.3:

  1. HVAC systems intended to operate continuously.
  2. HVAC systems not serving residential spaces and having a design heating capacity and cooling capacity less than 7000 Btu/h that are equipped with readily accessible manual on/off controls .

6.4.3.3.1 Automatic Shutdown. HVAC systems shall be equipped with at least one of the following:

a. Controls that can start and stop the system under different time schedules for seven different day types

per week, are capable of retaining programming and time setting during loss of power for a period of at least ten hours, and include an accessible manual override or equivalent function that allows temporary operation of the system for up to two hours. b. An occupancy sensor that is capable of shutting the system off when no occupant is sensed for a period

of up to 30 minutes. c. A manually operated timer capable of being adjusted to operate the system for up to two hours. d. An interlock to a security system that shuts the system off when the security system is activated.

Exceptions to 6.4.3.3.1:

  1. Systems serving residential occupancies with controls that can start and stop the system under at least two different time schedules per week.
  2. Systems serving non- residential occupancies where heating or cooling capacity is less than 15,000 Btu/h, with controls that can start and stop the system under at least two different time schedules per week.

6.4.3.3.2 Setback Controls. Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required to maintain zone temperatures above an adjustable heating set point at least 10°F below the occupied heating set point . Cooling systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the mechanical cooling system at the lowest practical fan speed as required to maintain zone temperatures below an adjustable cooling set point at least 5°F above the occupied cooling set point or to prevent maximum space humidity levels as required by Standard 62.1.

Exception to 6.4.3.3.2: Radiant heating systems capable of and configured with a setback heating set

point at least 4°F below the occupied heating set point .

6.4.3.3.3 Optimum Start Controls. Individual heating and cooling systems with setback controls and DDC shall have optimum start controls . The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied set point, the outdoor temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature into the optimum start algorithm.

Exception to 6.4.3.3.3 : Residential spaces are not required to have optimum start controls .

6.4.3.3.4 Zone Isolation. HVAC systems serving zones that are intended to operate or be occupied nonsimultaneously shall be divided into isolation areas. Zones may be grouped into a single isolation area provided it does not exceed 25,000 ft [2] of conditioned floor area nor include more than one story . Each isolation area shall be equipped with isolation devices capable of and configured to automatically shut off the supply of conditioned air and outdoor air to and exhaust air from the area. Each isolation area shall be controlled independently by a device meeting the requirements of Sections 6.4.3.3.1. For central systems and plants, controls and devices shall be provided to allow stable system and equipment operation for any length of time while serving only the smallest isolation area served by the system or plant.

Exceptions to 6.4.3.3.4: Isolation devices and controls are not required for

  1. exhaust air and outdoor air connections to isolation zones when the fan system to which they connect is 5000 cfm and smaller;
  2. exhaust airflow from a single isolation zone of less than 10% of the design airflow of the exhaust system to which it connects; or
  3. zones intended to operate continuously or intended to be inoperative only when all other zones are inoperative.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for zone isolation using logical groups of zone air terminal units serving each isolation area.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 77

PDF Page 80

Open page note

6.4.3.3.5 Automatic Control of HVAC in Hotel/Motel Guest Rooms. Hotels and motels with greater than 50 guest rooms shall be provided with automatic controls for the HVAC equipment serving each guest room capable of and configured according to the requirements in the following subsections.

6.4.3.3.5.1 Guest Room HVAC Set-Point Control. HVAC systems serving hotel guest rooms shall be capable of and configured with three modes of temperature control.

a. Rented and unoccupied. Within 20 minutes of all occupants leaving the guest room, HVAC set points

shall be automatically raised by at least 4°F from the occupant set point in the cooling mode and auto- matically lowered by at least 4°F from the occupant set point in the heating mode. b. Unrented and unoccupied. HVAC set points shall be automatically reset to 80°F or higher in the cool ing mode and to 60°F or lower in the heating mode. The HVAC set points in the unrented and unoccupied guest room modes shall be initiated within 16 hours of the guest room being continuously unoccupied or within 20 minutes of the guest room being continuously unoccupied where a networked guest room control system indicates the guest room is unrented. c. Occupied. HVAC set points shall return to their occupied set points once occupancy is sensed.

Exceptions to 6.4.3.3.5.1:

  1. A networked guest room control system shall be permitted to return the thermostat set points to their default occupied set points 60 minutes prior to the time the room is scheduled to be occupied.
  2. Dehumidification shall be permitted to limit the space humidity levels as required by Standard 62.1 during unoccupied mode for both rented and unrented periods.

6.4.3.3.5.2 Guest Room Ventilation Control. Within 20 minutes of all occupants leaving the guest room, ventilation and exhaust fans shall automatically be turned off, or isolation devices serving each guest room shall automatically shut off the supply of outdoor air to the guest room and shut off exhaust air from the guest room.

Exception to 6.4.3.3.5.2: Guest room ventilation systems shall be permitted to have an automatic

daily preoccupancy purge cycle that provides daily outdoor air ventilation during unrented periods at the design ventilation rate for 60 minutes, or at a rate and duration equivalent to one air change.

6.4.3.4 Ventilation System Controls 6.4.3.4.1 Stair and Elevator Shaft Vent Dampers. Where stair and elevator shafts have vents, they shall be equipped with motorized dampers that are capable of and configured to automatically close during normal building operation and are interlocked to open as required by fire and smoke detection systems or by thermostatic control systems .

Exception to 6.4.3.4.1: Nonmotorized gravity backdraft dampers are acceptable in buildings less than

three stories in height and for buildings of any height located in Climate Zones 0, 1, 2, and 3.

6.4.3.4.2 Shutoff Damper Controls. All outdoor air intake and exhaust systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Out- door air and exhaust/relief dampers shall be capable of and configured to automatically shut off during preoccupancy building warm-up, cooldown, and setback, except when the supply of outdoor air reduces energy costs or when outdoor air must be supplied to meet code requirements.

Exceptions to 6.4.3.4.2:

  1. Nonmotorized (gravity backdraft) dampers are acceptable for exhaust and relief in buildings less than three stories in height and for outdoor air intakes and exhaust and relief dampers in buildings of any height located in Climate Zones 0, 1, 2, and 3. Nonmotorized dampers for out- door air intakes must be protected from direct exposure to wind.
  2. Nonmotorized dampers are acceptable in systems with a design outdoor air intake or exhaust capacity of 300 cfm or less.
  3. Dampers are not required in ventilation or exhaust systems serving unconditioned spaces .
  4. Dampers are not required in exhaust systems serving Type 1 kitchen exhaust hoods.
  5. Dampers are not required in systems intended to operate continuously.

6.4.3.4.3 Damper Leakage. Where outdoor air supply and exhaust/relief dampers are required by Section 6.4.3.4.1, they shall have a maximum leakage rate as indicated in Table 6.4.3.4.3.

6.4.3.4.4 Ventilation Fan Controls. Fans with motors greater than 0.75 hp shall have automatic con- trols complying with Section 6.4.3.3.1 that are capable of and configured to shut off fans when not required.

Exception to 6.4.3.4.4: HVAC systems intended to operate continuously.

78 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 81

Open page note

Table 6.4.3.4.3 Maximum Damper Leakage [a,b] , cfm per ft [2] at 1.0 in. of water

Climate ZoneOutdoor Air IntakeCol3Exhaust/ReliefCol5
Climate ZoneNonmotorized aMotorizedNonmotorized cMotorized

0, 1, 2

Any height 20 4 20 4

3

Any height 20 10 20 10

4, 5B, 5C

Fewer than three
stories
20 d102010
Three or more_stories_20 d1020 d10
5A, 6, 7, 8Col2Col3Col4Col5
Fewer than three
stories
20 d4204
Three or more_stories_20 d420 d4

a. When tested in accordance with AMCA Standard 500-D. b. Dampers smaller than 12 in. in height, width, or diameter need not be tested but shall be of the same design and construction as the smallest tested damper

meeting the listed leakage rate requirement. c. Nonmotorized dampers smaller than 24 in. in height, width, or diameter may have a leakage rate of 40 cfm/ft [2] . d. Where allowed by Section 6.4.3.4.2, Exception 2.

6.4.3.4.5 Parking Garage Ventilation Systems. Parking garage ventilation systems shall meet all of the following:

a. Separate ventilation systems and control systems shall be provided for each parking garage section . b. Control systems for each parking garage section shall automatically detect and control contaminant lev els and shall be capable of and configured to reduce airflow to 20% or less of design capacity . c. The ventilation system for each parking garage section shall have controls and devices that result in fan

motor demand of no more than 30% of design wattage at 50% of the design airflow.

Exception to 6.4.3.4.5: Garage ventilation systems serving a single parking garage section having a

total ventilation system motor nameplate horsepower not exceeding 5 hp at fan system design con- ditions and where the parking garage section has no mechanical cooling or mechanical heating .

6.4.3.5 Heat-Pump Auxiliary Heat Control. Heat pumps equipped with internal electric resistance heaters shall have controls that prevent supplemental heater operation when the heating load can be met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation is permitted during outdoor coil defrost cycles.

Exception to 6.4.3.5: Heat pumps whose minimum efficiency is regulated by NAECA and whose rat ings meet the requirements shown in Table 6.8.1-2 and include all usage of internal electric resis- tance heating. 6.4.3.6 Humidification and Dehumidification Control 6.4.3.6.1 Dehumidification. Humidistatic controls shall not use mechanical cooling to reduce the humidity below the lower of a dew point of 55°F or relative humidity of 60% in the coldest zone served by the system .

Informative Note: Lower humidity is permitted when operating mechanical cooling for temperature control.

6.4.3.6.2 Humidification. Humidistatic controls shall not use fossil fuel or electricity to produce relative humidity above 30% in the warmest zone served by the system .

6.4.3.6.3 Control Interlock. Where a zone is served by a system or systems with both humidification and dehumidification capability, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided capable of and configured to prevent simultaneous operation of humidification and dehumidification equipment .

Exception to 6.4.3.6.1 and 6.4.3.6.2: Systems serving zones where specific humidity levels are

required, such as museums and hospitals, and approved by the authority having jurisdiction or

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 79

PDF Page 82

Open page note

Table 6.4.3.8 Demand Control Ventilation (DCV) Floor Area Thresholds

Climate ZoneOccupant Outdoor Airflow Component (cfm/1000 ft2) aCol3Col4Col5Col6Col7
Climate Zone100 to 199200 to 399400100 to 199200 to 399400
Climate ZoneMinimum Space Floor Area in ft2 where DCV Is RequiredMinimum Space Floor Area in ft2 where DCV Is RequiredMinimum Space Floor Area in ft2 where DCV Is RequiredMinimum Space Floor Area in ft2 where DCV Is RequiredMinimum Space Floor Area in ft2 where DCV Is RequiredMinimum Space Floor Area in ft2 where DCV Is Required
Climate ZoneAreas without Exhaust Air Energy RecoveryAreas without Exhaust Air Energy RecoveryAreas without Exhaust Air Energy RecoveryAreas with Exhaust Air Energy Recovery bAreas with Exhaust Air Energy Recovery bAreas with Exhaust Air Energy Recovery b
7, 8400200150800400250
5A, 6A, 6B6002501501400900400
0A, 0B, 1B,
3A, 4A, 5B, 5C
80040025020001000500
2A, 2B, 4C110060030023001100600
3B, 4B1500700400520023501250
1A24001100600580026001400
3C70003000170012,00060003000

a. Occupant outdoor airflow component in cfm per 1000 ft [2] shall be calculated as the product of default occupant density and outdoor airflow rate per occu pant ( Rp ) as shown in ASHRAE Standard 62.1, Table 6.2.2.1. b. Where exhaust air energy recovery is required by Section 6.5.6.1.

required by accreditation standards, and where humidistatic controls are capable of and configured to maintain a dead band of at least 10% rh where no active humidification or dehumidification takes place.

Exception to 6.4.3.6.1, 6.4.3.6.2, and 6.4.3.6.3: Systems serving zones where humidity levels are

required to be maintained with precision of not more than ±5% rh to comply with applicable codes or accreditation standards or as approved by the authority having jurisdiction .

6.4.3.7 Freeze Protection and Snow/Ice Melting Systems. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of and configured to shut off the systems when outdoor air temperatures are above 40°F or when the conditions of the protected fluid will prevent freezing. Snow and ice melting systems shall include automatic controls capable of and configured to shut off the systems when the pavement temperature is above 50°F and no precipitation is falling, and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F so that the potential for snow or ice accumulation is negligible.

6.4.3.8 Ventilation Controls for High-Occupancy Areas. Demand control ventilation ( DCV ) is required for spaces larger than the floor area shown in Table 6.4.3.8 based on an occupant outdoor airflow component in cfm per 1000 ft [2] and served by systems with one or more of the following:

a. Air economizer b. Automatic modulating control of outdoor air damper c. Design outdoor airflow greater than 3000 cfm

Exceptions to 6.4.3.8:

  1. Multiple-zone systems without DDC of individual zones communicating with a central control panel.
  2. Spaces where >75% of the space design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces .
  3. Spaces with one of the following occupancy categories as defined in ASHRAE Standard 62.1: correctional cells, daycare sickrooms, science labs, barbers, beauty and nail salons, and bowling alley seating.
  4. Spaces where the requirements of ASHRAE Standard 170, applicable codes, or applicable accreditation standards do not allow the reduction of outdoor airflow.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for CO2-based demand control ventilation and how it can be implemented while complying with ASHRAE Standard 62.1.

80 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 83

Open page note

Table 6.4.3.10.1 DDC Applications and Qualifications

Building StatusApplicationQualifications
New_building_Air-handling_system_ and all zones served by the_system_Individual_systems_ supplying more than three zones and
with_fan system bhp of 10_hp and larger
New_building_Chilled-water plant and all coils and_terminal_ units
served by the_system_
Individual plants supplying more than three zones and with
design cooling capacity of 300,000 Btu/h and larger
New_building_Hot-water plant and all coils and_terminal_ units served
by the_system_
Individual plants supplying more than three zones and with
design heating capacity of 300,000 Btu/h and larger
Alteration or
addition
Zone_terminal_ unit such as_VAV_ boxWhere existing zones served by the same air-handling,
chilled-water, or hot-water_system_ have_DDC_
Alteration or
addition
Air-handling_system_ or fan coilWhere existing air-handling_system_s and fan coils served by
the same chilled- or hot-water plant have_DDC_
Alteration or
addition
New air-handling_system_ and all new zones served by
the_system_
Individual_systems_ with_fan system bhp_ of 10 hp and larger
and supplying more than three zones and more than 75% of
zones are new
Alteration or
addition
New or upgraded chilled-water plantWhere all chillers are new and plant design cooling capacity
is 300,000 Btu/h and larger
Alteration or
addition
New or upgraded hot-water plantWhere all_boilers_ are new and plant design heating capacity
is 300,000 Btu/h and larger

6.4.3.9 Heated or Cooled Vestibules or Air Curtains with Integral Heating. Heating systems for vestibules and air curtain units with integral heating shall include automatic controls capable of and configured to shut off the heating system when outdoor air temperatures are above 45°F. Vestibule heating and cooling systems shall be controlled by a thermostat in the vestibule capable of and configured to limit heating to a maximum of 60°F and cooling to a minimum of 85°F.

Exception to 6.4.3.9: Heating or cooling provided by site-recovered energy or by transfer air that

would otherwise be exhausted.

6.4.3.10 Direct Digital Control (DDC) Requirements. Direct digital control shall be required as follows.

6.4.3.10.1 DDC Applications. DDC shall be provided in the applications and qualifications listed in Table 6.4.3.10.1.

Exception to 6.4.3.10.1: DDC is not required for systems using the simplified approach to compliance

in accordance with Section 6.3.

6.4.3.10.2 DDC Controls. Where DDC is required by Section 6.4.3.10.1, the DDC system shall be capable of and configured with all of the following, as required, to provide the control logic required in Section 6.5:

a. Monitoring zone and system demand for fan pressure, pump pressure, heating, and cooling b. Transferring zone and system demand information from zones to air distribution system controllers and

from air distribution systems to heating and cooling plant controllers c. Automatically detecting those zones and systems that may be excessively driving the reset logic and gen erate an alarm or other indication to the system operator d. Readily allowing operator removal of zones from the reset algorithm

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for monitoring zone and system demand, automatically detecting and alarming zones that are excessively driving reset logic, and readily excluding those zones from reset logic.

6.4.3.10.3 DDC Display. Where DDC is required by Section 6.4.3.10.1 for new buildings, the DDC system shall be capable of trending and graphically displaying input and output points.

6.4.3.11 Chilled-Water Plant Monitoring

6.4.3.11.1 Monitoring. For electric-motor-driven chilled-water plants in new buildings, or for new plants in existing buildings, measurement devices shall be installed and shall measure the electric energy use and efficiency of the chilled-water plant for

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 81

PDF Page 84

Open page note

a. water-cooled chilled-water plants larger than 1500 tons peak cooling capacity for Climate Zones 5

through 8, 3C, and 4C, and larger than 1000 tons peak cooling capacity for all other zones; and b. air-cooled chilled-water plants larger than 860 tons peak cooling capacity for Climate Zones 5 through 8,

3C, and 4C, and larger than 570 tons peak cooling capacity for all other zones.

The efficiency shall be calculated in kW /ton (see Informative Appendix E).

6.4.3.11.2 Electric-Motor-Driven Chiller System Recording and Reporting. The electrical energy use efficiency shall be trended every 15 minutes and graphically displayed and include hourly, daily, monthly, and annual data. The system shall maintain all data collected for a minimum of 36 months.

6.4.3.12 Economizer Fault Detection and Diagnostics (FDD). Air-cooled direct-expansion cooling units listed in Tables 6.8.1-1 and 6.8.1-2, where an air economizer is installed in accordance with Section 6.5.1, shall include a fault detection and diagnostics (FDD) system complying with the following:

a. The following temperature sensors shall be permanently installed to monitor system operation:

  1. Outdoor air
  2. Supply air
  3. Return air, where required for economizer control b. The system shall have the capability of displaying the value of each sensor. c. The FDD system or unit controls shall be capable of and configured to provide system status by indicat ing the following:
  4. Free cooling available
  5. Economizer enabled
  6. Compressor enabled
  7. Heating enabled
  8. Mixed-air low-limit cycle active d. The FDD system or unit controls shall have provisions to manually initiate each operating mode so that

the operation of compressors, economizers, fans, and the heating system can be independently tested and verified. e. The FDD system shall be capable of and configured to detect the following faults:

  1. Air temperature sensor failure/fault
  2. Not economizing when the unit should be economizing
  3. Economizing when the unit should not be economizing
  4. Damper not modulating
  5. Excess outdoor air f. The FDD system shall be capable of and configured to report faults to a fault management application or DDC system accessible by operating or service personnel, or annunciated locally on zone thermostats .

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for monitoring and alarming air economizer faults for air economizers that are controlled by DDC systems .

6.4.4 HVAC System Construction and Insulation 6.4.4.1 Insulation 6.4.4.1.1 General. Insulation required by this section shall be installed in accordance with industryaccepted standards (see Informative Appendix E). These requirements do not apply to HVAC equipment . Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance and wind, but not limited to the following:

a. Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet

metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. b. Insulation covering chilled-water piping, refrigerant suction piping, or cooling ducts located outside the

conditioned space shall include a vapor retardant located outside the insulation (unless the insulation is inherently vapor retardant), all penetrations and joints of which shall be sealed.

6.4.4.1.2 Duct and Plenum Insulation. All supply and return ducts and plenums installed as part of an HVAC air distribution system shall be thermally insulated in accordance with Table 6.8.2.

Exceptions to 6.4.4.1.2:

  1. Factory-installed plenums, casings, or ductwork furnished as a part of HVAC equipment tested and rated in accordance with Section 6.4.1.

82 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 85

Open page note

  1. Ducts or plenums located in heated spaces, semiheated spaces, or cooled spaces .
  2. For runouts less than 10 ft in length to air terminals or air outlets, the rated R-value of insula- tion need not exceed R-3.5.
  3. Backs of air outlets and outlet plenums exposed to unconditioned space or indirectly condi- tioned space with face areas exceeding 5 ft [2] need not exceed R-2; those 5 ft [2] or smaller need not be insulated.

6.4.4.1.3 Piping Insulation. Piping shall be thermally insulated in accordance with Tables 6.8.3-1 and 6.8.3-2. Exceptions to 6.4.4.1.3:

  1. Factory-installed piping within HVAC equipment tested and rated in accordance with Section 6.4.1.
  2. Piping that conveys fluids having a design operating temperature range between 60°F and 105°F, inclusive.
  3. Piping that conveys fluids that have not been heated or cooled through the use of fossil fuels or electricity (such as roof and condensate drains, domestic cold-water supply, and natural-gas piping ).
  4. Where heat gain or heat loss will not increase energy use (such as liquid refrigerant piping ).
  5. In piping 1 in. or less, insulation is not required for strainers, control valves, and balancing valves.

6.4.4.1.4 Sensible Heating Panel Insulation. All thermally ineffective panel surfaces of sensible heating panels, including U-bends and headers, shall be insulated with a minimum of R-3.5. Adjacent build- ing envelope insulation counts toward this requirement.

6.4.4.1.5 Radiant Floor Heating. The bottom surfaces of floor structures incorporating radiant heating shall be insulated with a minimum of R-3.5. Adjacent building envelope insulation counts toward this requirement.

Exception to 6.4.4.1.5: See Section 5 requirements for heated slab-on-grade floors incorporating

radiant heating.

6.4.4.2 Ductwork and Plenum Leakage 6.4.4.2.1 Duct Sealing. Ductwork and all plenums with pressure class ratings shall be constructed to Seal Class A . Openings for rotating shafts shall be sealed with bushings or other devices that seal off leaking air. Pressure-sensitive tape shall not be used as the primary sealant unless it has been certified to comply with UL-181A or UL-181B by an independent testing laboratory, and the tape is used in accordance with that certification. All connections shall be sealed, including (but not limited to) spin-ins, taps, other branch connections, access doors, access panels, and duct connections to equipment . Sealing that would void product listings is not required. Spiral lock seams need not be sealed. All duct pressure class ratings shall be designated in the design documents.

6.4.4.2.2 Duct Leakage Tests. Ductwork that is designed to operate at static pressures in excess of 3 in. of water and all ductwork located outdoors shall be leak-tested according to industry-accepted test procedures (see Informative Appendix E). Representative sections totaling no less than 25% of the total installed duct area for the designated pressure class shall be tested. All sections shall be selected by the building owner or the designated representative of the building owner. Positive pressure leakage testing is acceptable for negative pressure ductwork . The maximum permitted duct leakage shall be

Lmax = CLP [0.65]

where Lmax = maximum permitted leakage, cfm per 100 ft [2] of duct surface area CL = 4, duct leakage class, cfm per 100 ft [2] of duct surface area per in. of water [0.65]

P = test pressure, which shall be equal to the design duct pressure class rating, in. of water 6.4.5 Walk-In Coolers and Walk-In Freezers. Site-assembled or site -constructed walk-in coolers and walk-in freezers shall conform to the following requirements:

a. Shall be equipped with automatic door closers that firmly close walk-in doors that have been closed to

within 1 in. of full closure. Exception to 6.4.5(a): Doors wider than 3 ft 9 in. or taller than 7 ft. b. Doorways shall have strip doors (curtains), spring-hinged doors, or other method of minimizing infiltra tion when doors are open.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 83

PDF Page 86

Open page note

c. Walk-in coolers shall contain wall, ceiling, and door insulation of at least R-25 and at least R-32 for

walk-in freezers . Exception to 6.4.5(c): Glazed portions of doors or structural members. d. Walk-in freezers shall contain floor insulation of at least R-28. e. Evaporator fan motors that are less than 1 hp and less than 460 V shall use electronically commutated

motors (brushless direct-current motors) or three-phase motors. f. Lights shall use light sources with an efficacy of 40 lm/W or more, including ballast losses (if any). Light sources with lower efficacy may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people. g. Transparent reach-in doors for walk-in freezers, and windows in walk-in freezer doors, shall be of triple pane glass, either filled with inert gas or with heat-reflective treated glass or vacuum insulating glazing. ( Informative Note: For applications in the U.S., alternate innovative component technologies (e.g., vacuum insulating glazing for transparent reach-in doors) are allowable only if the manufacturer has obtained a waiver from U.S. DOE.) h. Transparent reach-in doors for walk-in coolers, and windows in walk-in cooler doors, shall be double pane glass with heat-reflective treated glass and gas filled, or triple-pane glass, either filled with inert gas or with heat-reflective treated glass or vacuum insulating glazing. ( Informative Note: For applications in the U.S., alternate innovative component technologies (e.g., vacuum insulating glazing for transparent reach-in doors) are allowable only if the manufacturer has obtained a waiver from U.S. DOE.) i. Antisweat heaters without antisweat heater controls shall have a total door rail, glass, and frame heater power draw of  7.1 W/ft [2] of door opening for walk-in freezers and 3.0 W/ft [2] of door opening for walk-in coolers . j. Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or in response to the condensation on the inner glass pane. k. Condenser fan motors that are less than 1 hp shall use electronically commutated motors, permanent

split-capacitor-type motors, or three-phase motors. l. All walk-in freezers shall incorporate temperature-based defrost termination control with a time limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second upon a time limit breach. Exception to 6.4.5(l): Walk-in coolers and walk-in freezers combined in a single enclosure greater than

3000 ft [2] . m. Doors in walk-in coolers and walk-in freezers shall meet the requirements of Tables 6.8.1-18 and 6.8.1 19. Walk-in cooler and walk-in freezer refrigeration systems, except for walk-in process cooling refrigeration systems as defined in 10 CFR 431.302, shall meet the requirements of Table 6.8.1-20.

6.4.6 Refrigerated Display Case

a. All refrigerated display cases shall conform to Section 6.4.1.1 and Table 6.8.1-11. b. Lighting in refrigerated display cases and glass doors installed on walk-in coolers and walk-in freezers

shall be controlled by one of the following:

  1. Automatic time-switch controls to turn off lights during nonbusiness hours: Timed overrides for display cases or walk-in coolers and walk-in freezers may be used to turn the lights on for up to one hour and shall automatically time out to turn the lights off.
  2. Motion sensor controls on each display case or walk-in door section that reduce lighting power by at least 50% within three minutes after the area within the sensor range is vacated. c. All low-temperature display cases shall incorporate temperature-based defrost termination control with a

time-limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second on a time limit breach. d. Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative

humidity in the air outside the door or in response to the condensation on the inner glass pane.

6.4.7 Liquid-to-Liquid Heat Exchangers. Plate-type liquid-to-liquid heat exchangers shall be rated in accordance with AHRI 400. Section 12 contains a complete specification of the referenced test procedure.

6.5 Prescriptive Compliance Path 6.5.1 Economizers. Each cooling system shall include either an air economizer or fluid economizer meeting the requirements of Sections 6.5.1.1 through 6.5.1.5.

Exceptions to 6.5.1: Economizers are not required for the following systems :

  1. Individual fan-cooling units with a supply capacity less than the minimum listed in Table 6.5.1-1.

84 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 87

Open page note

Table 6.5.1-1 Minimum Fan-Cooling Unit Size for which an Economizer Is Required

Climate ZoneCooling Capacity for which an
Economizer Is Required
Application
0A, 0B, 1A, 1BNo economizer requirementAll
2A, 2B, 3A, 4A, 5A, 6A, 3B, 3C, 4B,
4C, 5B, 5C, 6B, 7, 8
33,000 Btu/hFan-cooling units located outside the
building
2A, 2B, 3A, 4A, 5A, 6A, 3B, 3C, 4B,
4C, 5B, 5C, 6B, 7, 8
54,000 Btu/hAll other fan-cooling-unit locations

Table 6.5.1-2 Eliminate Required Economizer for Comfort Cooling by Increasing Cooling Efficiency

Climate ZoneEfficiency Improvement a
2A17%
2B21%
3A27%
3B32%
3C65%
4A42%
4B49%
4C64%
5A49%
5B59%
5C74%
6A56%
6B65%
772%
877%

a. If a unit is rated with an annualized or part-load metric, then to eliminate the required economizer, only the annualized or part-load minimum cooling

efficiency of the unit must be increased by the percentage shown. If the unit is only rated with a full-load metric like EER cooling then these must be increased by the percentage shown. To determine the efficiency required to eliminate the economizer when the unit equipment efficiency is rated with an energy-input divided by a thermal-output metric, the metric shall first be converted to COP by the efficiency improvement percentage shown. The COP shall then be converted back to the original rated metric to establish the efficiency required to eliminate the economizer. Informative Note: Some examples of annualized or part-load metrics are IPLV .IP, IEER, and SEER .

  1. Chilled-water cooling systems without a fan or that use induced airflow, where the total capacity of these systems is less than 1,000,000 Btu/h in Climate Zones 0, 1B, and 2 through 4; less than 1,400,000 Btu/h in Climate Zones 5 through 8; or any size in Climate Zone 1A.
  2. Systems that include nonparticulate air treatment as required by Standard 62.1, Section 6.2.1.
  3. In hospitals and ambulatory surgery centers, where more than 75% of the air designed to be supplied by the system is to spaces that are required to be humidified above 35°F dew-point temperature to comply with applicable codes or accreditation standards; in all other buildings, where more than 25% of the air designed to be supplied by the system is to spaces that are designed to be humidified above 35°F dew-point temperature to satisfy process application needs. This exception does not apply to computer rooms .
  4. Systems that include a condenser heat recovery system with a minimum capacity as defined in Section 6.5.6.2.2.
  5. Systems that serve residential spaces where the system capacity is less than five times the requirement listed in Table 6.5.1-1.
  6. Systems that serve spaces whose sensible cooling load at design conditions, excluding transmission less than or equal to transmission losses at an outdoor temperature of 60°F.
  7. Systems expected to operate fewer than 20 hours per week.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 85

PDF Page 88

Open page note

Table 6.5.1.1.3 High-Limit Shutoff Control Settings for Air Economizers [ a]

Control TypeAllowed Only in Climate Zone
at Listed Set Point
Required High-Limit Set Points (Economizer Off when):Col4
Control TypeAllowed Only in Climate Zone
at Listed Set Point
EquationDescription
Fixed dry-bulb temperature0B, 1B, 2B, 3B, 3C, 4B, 4C,
5B, 5C, 6B, 7, 8
TOA > 75°FOutdoor air temperature exceeds 75°F
Fixed dry-bulb temperature5A, 6ATOA > 70°FOutdoor air temperature exceeds 70°F
Fixed dry-bulb temperature0A, 1A, 2A, 3A, 4A,TOA > 65°FOutdoor air temperature exceeds 65°F
Differential dry-bulb temperature0B, 1B, 2B, 3B, 3C, 4B, 4C,
5A, 5B, 5C, 6A, 6B, 7, 8
TOA >TRAOutdoor air temperature exceeds
return air temperature
Fixed enthalpy with
fixed dry-bulb temperature
AllhOA > 28 Btu/lb b
or_ TOA >_75°F
Outdoor air enthalpy exceeds 28 Btu/lb b of dry
air b or_outdoor air_ temperature exceeds 75°F
Differential enthalpy with fixed
dry-bulb temperature
AllhOA >hRA
or_ TOA >_75°F
Outdoor air enthalpy exceeds return air enthalpy
or_outdoor air_ temperature exceeds 75°F

a. Devices with selectable rather than adjustable set points shall be capable of being set to within 2°F and 2 Btu/lb of the set point listed. b. At altitudes substantially different than sea level, the fixed enthalpy limit shall be set to the enthalpy value at 75°F and 50% rh. As an example, at approximately 6000 ft elevation,

the fixed enthalpy limit is approximately 30.7 Btu/lb.

  1. Where the use of outdoor air for cooling will affect supermarket open refrigerated casework systems .
  2. For comfort cooling, where the cooling efficiency meets or exceeds the efficiency improvement requirements in Table 6.5.1-2.
  3. Systems primarily serving computer rooms where a. the total design cooling load of all computer rooms in the building is less than 3,000,000 Btu/h

and the building in which they are located is not served by a centralized chilled-water plant; b. the room total design cooling load is less than 600,000 Btu/h and the building in which they are

located is served by a centralized chilled-water plant; c. the local water authority does not allow cooling towers; or d. less than 600,000 Btu/h of computer-room cooling equipment capacity is being added to an exist-

ing building . 12. Dedicated systems for computer rooms, where a minimum of 75% of the design load serves a. those spaces classified as an essential facility, b. those spaces having a design of Tier IV as defined by ANSI/TIA-942, c. those spaces classified under NFPA 70 Article 708— Critical Operations Power Systems (COPS),

or d. those spaces where core clearing and settlement services are performed such that their failure to

settle pending financial transactions could present systemic risk as described in “The Interagency Paper on Sound Practices to Strengthen the Resilience of the U.S. Financial System” (April 7, 2003).

6.5.1.1 Air Economizers 6.5.1.1.1 Design Capacity. Air economizer systems shall be capable of and configured to modulate outdoor air and return air dampers to provide up to 100% of the design supply air quantity as outdoor air for cooling.

6.5.1.1.2 Control Signal. Economizer controls shall be capable of and configured to sequence the dampers with the mechanical cooling equipment and shall not be controlled by only mixed-air temperature.

Exception to 6.5.1.1.2: The use of mixed-air temperature limit control shall be permitted for systems

controlled from space temperature (such as single-zone systems ).

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for sequencing air economizers with mechanical cooling using supply air (not mixed air) control loops.

6.5.1.1.3 High-Limit Shutoff. All air economizers shall be capable of and configured to automati- cally reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy use. High-limit shutoff control types and associated set points for specific climate zones shall be chosen from Table 6.5.1.1.3.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for disabling air econ- omizers using all options of high-limit shutoff options with compliant set points .

86 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 89

Open page note

6.5.1.1.4 Dampers. Exhaust/relief, and outdoor air dampers shall meet the requirements of Table 6.4.3.4.3. Return dampers shall meet the requirements of motorized exhaust/relief dampers in Table 6.4.3.4.3.

Exception to 6.5.1.1.4: Exhaust/relief and outdoor air intake dampers on systems intended to operate

continuously.

6.5.1.1.5 Relief of Excess Outdoor Air

a. Systems shall provide one of the following means to relieve excess outdoor air during air economizer

operation to prevent overpressurizing the building :

  1. Return or relief fan(s) meeting the requirements of Section 6.5.3.2.4.
  2. Barometric or motorized damper relief path with a total pressure drop at design relief airflow rate less than 0.10 in. of water from the occupied space to outdoors. Design relief airflow rate shall be the design supply airflow rate minus any continuous exhaust flows, such as toilet exhaust fans, whose makeup is provided by the economizer system . b. The relief air outlet shall be located so as to avoid recirculation into the building .

6.5.1.1.6 Sensor Accuracy. Outdoor air, return air, mixed air, and supply air sensors shall be calibrated within the following accuracies:

a. Dry-bulb and wet-bulb temperatures shall be accurate to ±2°F over the range of 40°F to 80°F. b. Enthalpy and the value of a differential enthalpy sensor shall be accurate to ±3 Btu/lb over the range of

20 to 36 Btu/lb. c. Relative humidity shall be accurate to ±5% over the range of 20% to 80% rh.

6.5.1.2 Fluid Economizers Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for enabling and controlling fluid economizers in water-cooled chilled-water plants.

6.5.1.2.1 Design Capacity. Fluid economizer systems shall be capable of providing up to 100% of the expected system cooling load at outdoor air temperatures of 50°F dry bulb/45°F wet bulb and below.

Exceptions to 6.5.1.2.1:

  1. Systems primarily serving computer rooms in which 100% of the expected system cooling load at the dry-bulb and wet-bulb temperatures listed in Table 6.5.1.2.1 is met with water-cooled fluid economizers .
  2. Systems primarily serving computer rooms in which 100% of the expected system cooling load at the dry-bulb temperatures listed in Table 6.5.1.2.1 is met with air-cooled fluid economizers .
  3. Systems where dehumidification requirements cannot be met using outdoor air temperatures of 50°F dry-bulb/45°F wet-bulb and where 100% of the expected system cooling load at 45°F drybulb/40°F wet-bulb is met with water-cooled fluid economizers .

6.5.1.2.2 Maximum Hydronic Pressure Drop. Precooling coils and fluid-to-water heat exchangers used as part of a fluid economizer system shall either have a water-side pressure drop of less than 15 ft of water, or a secondary loop shall be created so that the coil or heat exchanger pressure drop is not seen by the circulating pumps when the system is in the normal cooling (noneconomizer) mode.

6.5.1.3 Integrated Economizer Control. Economizer systems shall be integrated with the mechanical cooling system and be capable of and configured to provide partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Controls shall not false load the mechanical cooling systems by limiting or disabling the economizer or by any other means, such as hot-gas bypass, except at the lowest stage of mechanical cooling .

Units that include an air economizer shall comply with the following:

a. Unit controls shall have the mechanical cooling capacity control interlocked with the air economizer

controls such that the outdoor air damper is at the 100% open position when mechanical cooling is on, and the outdoor air damper does not begin to close to prevent coil freezing due to minimum compressor run time until the leaving air temperature is less than 45°F. b. DX units with a rated capacity no less than 65,000 Btu/h that control the capacity of the mechanical

cooling directly based on occupied space temperature shall have a minimum of two stages of mechanical cooling capacity. c. All other DX units, including those that control space temperature by modulating the airflow to the

space, shall comply with the requirements of Table 6.5.1.3.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 87

PDF Page 90

Open page note

Table 6.5.1.2.1 Fluid Economizer Sizing Dry-Bulb and Wet-Bulb Requirements for Computer Rooms

Climate ZoneCol2Water CooledCol4Air Cooled
Climate ZoneClimate Zone** Dry Bulb, °F**** Wet Bulb, °F**Dry Bulb, °F
0ANRNRNR
0BNRNRNR
1ANRNRNR
1BNRNRNR
2A40.035.030.0
2B35.030.030.0
3A40.035.025.0
3B30.025.025.0
3C30.025.030.0
4A40.035.025.0
4B30.025.025.0
4C30.025.025.0
5A40.035.020.0
5B30.025.020.0
5C30.025.025.0
6A35.030.020.0
6B30.025.020.0
730.025.020.0
830.025.020.0

NR—Not required

Table 6.5.1.3 DX Cooling Stage Requirements for Modulating Airflow Units

Rating Capacity, Btu/hMinimum Number of Mechanical
Cooling Stages
Minimum Compressor
Displacementa
65,000 and <240,000335% of full load
240,000425% full load

a. For mechanical cooling stage control that does not use variable compressor displacement the percent displacement shall be equivalent to the mechanical

cooling capacity reduction evaluated at the full load rating conditions for the compressor.

6.5.1.4 Economizer Heating System Impact. HVAC system design and economizer controls shall be such that economizer operation does not increase the building heating energy use during normal operation.

Exception to 6.5.1.4: Economizers on VAV systems that cause zone-level heating to increase due to a

reduction in supply air temperature.

6.5.1.5 Economizer Humidification System Impact. Systems with hydronic cooling and humidification systems designed to maintain inside humidity at a dew-point temperature greater than 35°F shall use a fluid economizer if an economizer is required by Section 6.5.1.

6.5.2 Simultaneous Heating and Cooling Limitation

6.5.2.1 Zone Controls. Zone thermostatic control shall prevent

a. reheating ; b. recooling ; c. mixing or simultaneously supplying air that has been previously mechanically heated and air that has

been previously cooled, either by mechanical cooling or by economizer systems ; and d. other simultaneous operation of heating and cooling systems to the same zone.

88 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 91

Open page note

Exceptions to 6.5.2.1:

  1. Zones for which the volume of air that is reheated, recooled, or mixed is less than the larger of the following: a. For systems without DDC, 30% of the zone design peak supply . b. For systems with DDC, the minimum primary airflow rate required to meet the Simplified

Procedure ventilation requirements of ASHRAE Standard 62.1 for the zone, permitted to be the average airflow rate as allowed by ASHRAE Standard 62.1. c. Any higher rate that can be demonstrated to the satisfaction of the authority having jurisdiction

to reduce overall system annual energy use by offsetting reheat / recool energy losses through a reduction in outdoor air intake for the system. d. The airflow rate required to comply with applicable codes or accreditation standards, such as

pressure relationships or minimum air change rates. 2. Zones with DDC that comply with all of the following: a. The airflow rate in dead band between heating and cooling does not exceed the larger of the

following: i. The minimum primary airflow rate required to meet the Simplified Procedure ventilation requirements of ASHRAE Standard 62.1 for the zone, permitted to be the average airflow rate as allowed by ASHRAE Standard 62.1. ii. Any higher rate that can be demonstrated, to the satisfaction of the authority having juris-

diction, to reduce overall system annual energy use by offsetting reheat / recool energy losses through a reduction in outdoor air intake. iii. The airflow rate required to comply with applicable codes or accreditation standards, such

as pressure relationships or minimum air change rates. b. The airflow rate that is reheated, recooled, or mixed shall be less than 50% of the zone design

peak supply rate. c. The first stage of heating consists of modulating the zone supply air temperature set point up to

a maximum set point while the airflow is maintained at the dead band flow rate. d. The second stage of heating consists of modulating the airflow rate from the dead band flow rate

up to the heating maximum flow rate. 3. Laboratory exhaust systems that comply with Section 6.5.7.3. 4. Zones where at least 75% of the energy for reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or on-site renewable energy .

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for minimizing simultaneous heating and cooling for most types of VAV system zone air terminal units including the supply air temperature reheat limit.

6.5.2.1.1 Supply Air Temperature Reheat Limit. Where reheating is permitted by other parts of this standard, zones that have both supply and return/exhaust air openings greater than 6 ft above the floor shall not supply heating air more than 20°F above the space temperature set point .

Exceptions to 6.5.2.1.1:

  1. Laboratory exhaust systems that comply with Section 6.5.7.3.
  2. During preoccupancy building warm-up and setback .

6.5.2.2 Hydronic System Controls. The heating of fluids in hydronic systems that have been previously mechanically cooled, and the cooling of fluids that have been previously mechanically heated, shall be limited in accordance with Sections 6.5.2.2.1 through 6.5.2.2.3.

6.5.2.2.1 Three-Pipe System. Hydronic systems that use a common return system for both hot water and chilled water shall not be used.

6.5.2.2.2 Two-Pipe Changeover System. Systems that use a common distribution system to supply both heated and chilled water are acceptable, provided all of the following are met:

a. The system is designed to allow a dead band between changeover from one mode to the other of at least

15°F outdoor air temperature. b. The system is designed to operate, and is provided with controls that will allow operation, in one mode

for at least four hours before changing over to the other mode. c. Reset controls are provided that allow heating and cooling supply temperatures at the changeover point

to be no more than 30°F apart.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 89

PDF Page 92

Open page note

6.5.2.2.3 Hydronic (Water Loop) Heat Pump Systems. Hydronic heat pumps connected to a common heat-pump water loop with central devices for heat rejection (e.g., cooling tower) and heat addition (e.g., boiler ) shall have the following:

a. Controls that are capable of and configured to provide a heat-pump water supply temperature dead band

of at least 20°F between initiation of heat rejection and heat addition by the central devices (e.g., tower and boiler ). b. For Climate Zones 3 through 8, if a closed-circuit cooling tower (fluid cooler) is used, either an auto-

matic valve shall be installed to bypass all but a minimal flow of water around the tower (for freeze protection) or low-leakage positive closure dampers shall be provided. If an open-circuit cooling tower is used directly in the heat-pump loop, an automatic valve shall be installed to bypass all heat-pump water flow around the tower. If an open-circuit cooling tower is used in conjunction with a separate heat exchanger to isolate the tower from the heat-pump loop, then heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop.

Exception to 6.5.2.2.3: Where a system loop temperature optimization controller is used to determine

the most efficient operating temperature based on real-time conditions of demand and capacity, dead bands of less than 20°F shall be allowed.

6.5.2.3 Dehumidification. Where humidity controls are provided, such controls shall prevent reheating, mixing of hot and cold airstreams, or other means of simultaneous heating and cooling of the same airstream.

Exceptions to 6.5.2.3:

  1. The system is capable of and configured to reduce supply air volume to 50% or less of the design airflow rate or the minimum outdoor air ventilation rate specified in ASHRAE Standard 62.1 or other applicable federal, state, or local code or recognized standard, whichever is larger, before simultaneous heating and cooling takes place.
  2. The individual fan cooling unit has a design cooling capacity of 65,000 Btu/h or less and is capable of and configured to unload to 50% capacity before simultaneous heating and cooling takes place.
  3. The individual mechanical cooling unit has a design cooling capacity of 40,000 Btu/h or less. An individual mechanical cooling unit is a single system comprising a fan or fans and a cooling coil capable of providing mechanical cooling .
  4. Systems serving spaces where specific humidity levels are required to satisfy process application needs, such as vivariums; museums; surgical suites; pharmacies; and buildings with refrigerating systems, such as supermarkets, refrigerated warehouses, and ice arenas, and where the building includes site-recovered energy or on-site renewable energy that provides energy equal to at least 75% of the annual energy for reheating or for providing warm air in mixing systems . This exception does not apply to computer rooms .
  5. At least 90% of the annual energy for reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or on-site renewable energy .
  6. Systems where the heat added to the airstream is the result of the use of a desiccant system, and 75% of the heat added by the desiccant system is removed by a heat exchanger, either before or after the desiccant system, with energy recovery.

6.5.2.4 Humidification 6.5.2.4.1 Humidifiers with preheating jackets mounted in the airstream shall be provided with an auto- matic valve to shut off preheat when humidification is not required.

6.5.2.4.2 Humidification system dispersion-tube hot surfaces in the airstreams of ducts or air-handling units shall be insulated with a product with an insulating value of at least R-0.5.

Exception to 6.5.2.4.2: Systems where mechanical cooling, including economizer operation, does not

occur simultaneously with humidification.

6.5.2.5 Preheat Coils. Preheat coils shall have controls that stop their heat output whenever mechanical cooling, including economizer operation, is occurring.

6.5.2.6 Ventilation Air Heating Control. Units that provide ventilation air to multiple zones and operate in conjunction with zone heating and cooling systems shall not use heating or heat recovery to warm supply air above 60°F when representative building loads or outdoor air temperature indicate that the majority of zones require cooling.

Exception to 6.5.2.6: Units that heat the airstream using only series energy recovery when representative

building loads or outdoor air temperature indicate that the majority of zones require cooling in Climate Zones 0A, 1A, 2A, 3A, and 4A.

90 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 93

Open page note

6.5.3 Air System Design and Control 6.5.3.1 Fan System Power and Efficiency 6.5.3.1.1 Each HVAC system having a total fan system motor nameplate horsepower exceeding 5 hp at fan system design conditions shall not exceed the allowable fan system motor nameplate horsepower (Option 1) or fan system bhp (Option 2) as shown in Table 6.5.3.1-1. This includes supply fans, return/relief fans, exhaust fans, and fan-powered terminal units associated with systems providing heating or cooling capability that operate at fan system design conditions . Single-zone VAV systems shall comply with the constant-volume fan power limitation.

Exceptions to 6.5.3.1.1:

  1. Hospital, vivarium, and laboratory systems that use flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control may use variable-volume fan power limitation.
  2. Individual exhaust fans with motor nameplate horsepower of 1 hp or less.

6.5.3.1.2 Fan Motor Selection

a. For each fan less than 6 bhp, the selected fan motor shall be no larger than the first available motor with

a nameplate rating greater than 1.5 times the fan bhp . b. For each fan 6 bhp and larger, the selected fan motor shall be no larger than the first available motor with

a nameplate rating greater than 1.3 times the fan bhp .

The fan bhp must be indicated on the design documents to allow for compliance verification by the building official .

Exceptions to 6.5.3.1.2:

  1. Motors equipped with electronic speed control devices to vary the fan airflow as a function of load.
  2. Systems complying with Section 6.5.3.1.1 Option 1.
  3. Fans with motor nameplate horsepower of less than 1 hp.
  4. Fans with a fan nameplate electrical input power of less than 0.89 kW .

6.5.3.1.3 Fan Efficiency. Each fan and fan array shall have a fan energy index (FEI) of 1.00 or higher at its highest design airflow rate. Each fan and fan array used for a variable-air-volume system that meets the requirements of Section 6.5.3.2.1 shall have an FEI of 0.95 or higher at its highest design airflow rate. The FEI for fan arrays shall be calculated in accordance with AMCA 208 Annex C.

Exceptions to 6.5.3.1.3:

  1. Fans that are not embedded fans with a motor nameplate horsepower of less than 1.0 hp or with a fan nameplate electrical input power of less than 0.89 kW .
  2. Embedded fans and fan arrays with a combined motor nameplate horsepower of 5 hp or less or with a fan system electrical input power of 4.1 kW or less.
  3. Embedded fans that are part of equipment listed under Section 6.4.1.1.
  4. Embedded fans included in equipment bearing a third-party-certified seal for air performance or energy performance of the equipment package.
  5. Ceiling fans.
  6. Fans used for moving gases at temperatures above 482°F.
  7. Fans used for operation in explosive atmospheres.
  8. Reversible fans used for tunnel ventilation .
  9. Fans outside the scope of AMCA 208.
  10. Fans when operating during emergency conditions.

6.5.3.2 Fan Control 6.5.3.2.1 Supply Fan Airflow Control. Each cooling system listed in Table 6.5.3.2.1 shall be designed to vary the supply fan airflow as a function of load and shall comply with the following requirements:

a. DX and chilled-water cooling units that control the capacity of the mechanical cooling directly based on

space temperature shall have a minimum of two stages of fan control. Low or minimum speed shall not exceed 66% of full speed. At low or minimum speed, the fan system shall draw no more than 40% of the fan power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation -only operation. b. All other units, including DX cooling units and chilled-water units that control the space temperature by

modulating the airflow to the space, shall have modulating fan control. Minimum speed shall not exceed

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 91

PDF Page 94

Open page note

Table 6.5.3.1-1 Fan Power Limitation [a]

Col1LimitConstant VolumeVariable Volume
Option 1: Fan_system_ motor
nameplate hp
Allowable motor_ nameplate hp_hp cfm_S_ × 0.0011hp cfm_S_ × 0.0015
Option 2:fan system bhpAllowable_fan system bhp_bhp cfm_S_ × 0.00094 +Abhp cfm_S_ × 0.0013 +A

a. where

cfm S = maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute hp = maximum combined motor nameplate horsepower bhp = maximum combined fan brake horsepower A = sum of (PD × cfm D /4131) where PD = each applicable pressure drop adjustment from Table 6.5.3.1-2 in in. of water cfm D = the design airflow through each applicable device from Table 6.5.3.1-2 in cubic feet per minute

Table 6.5.3.1-2 Fan Power Limitation Pressure Drop Adjustment

DeviceAdjustment
Credits
Return or exhaust_systems_ required by code or accreditation
standards to be fully ducted, or_systems_ required to maintain air
pressure differentials between adjacent rooms.
Return and/or exhaust airflow_control devices_
Exhaust filters, scrubbers, or other exhaust treatment
Particulate Filtration Credit: MERV 9 through 12
Particulate Filtration Credit: MERV 13 through 15
Particulate Filtration Credit: MERV 16 and greater and
electronically enhanced filters
Carbon and other gas-phase air cleaners
Biosafety cabinet
Energy recovery device, other than coil runaround loop
Coil runaround loop
Evaporative humidifier/cooler in series with another cooling coil
Sound attenuation section (fans serving_spaces_ with design
background noise goals below NC35)
Exhaust_system_ serving fume hoods
Laboratory and vivarium exhaust_systems_ in high-rise_buildings_
0.5 in. of water (2.15 in. of water for laboratory and vivarium
systems)
0.5 in. of water
The pressure drop of device calculated at_fan system design_
condition
0.5 in. of water
0.9 in. of water
Pressure drop calculated at 2× clean filter pressure drop at_fan_
system design condition
Clean filter pressure drop at_fan system design condition_
Pressure drop of device at_fan system design condition_
For each airstream
[(2.2 ×Enthalpy Recovery Ratio) – 0.5] in. of water
0.6 in. of water for each airstream
Pressure drop of device at_fan system design condition_
0.15 in. of water
0.35 in. of water
0.25 in. of water/100 ft of vertical duct exceeding 75 ft
Deductions
Systems without central cooling device
Systems without central heating device
Systems with central_electric resistance_ heat
–0.6 in. of water
–0.3 in. of water
–0.2 in. of water
Table 6.5.3.2.1 Fan Airflow ControlCol2Col3
Cooling System TypeFan Motor Size, hpMechanical Cooling Capacity, Btu/h
DX coolingAny65,000
Chilled-water and evaporative cooling1/4Any

92 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 95

Open page note

50% of full speed. At minimum speed, the fan system shall draw no more than 30% of the power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation -only operation. c. Units that include an air economizer to meet the requirements of Section 6.5.1 shall have a minimum of

two speeds of fan control during economizer operation.

Exceptions to 6.5.3.2.1:

  1. Modulating fan control is not required for chilled-water and evaporative cooling units with <1 hp fan motors if the units are not used to provide ventilation air and if the indoor fan cycles with the load.
  2. If the volume of outdoor air required to meet the ventilation requirements of Standard 62.1 at low speed exceeds the air that would be delivered at the speed defined in Section 6.5.3.2.1(a) or 6.5.3.2.1(b) then the minimum speed shall be selected to provide the required ventilation air.

6.5.3.2.2 VAV Static Pressure Sensor Location. Static pressure sensors used to control VAV fans shall be located such that the controller set point is no greater than 1.2 in. of water. If this results in the sensor being located downstream of major duct splits, sensors shall be installed in each major branch to ensure that static pressure can be maintained in each.

Exception to 6.5.3.2.2: Systems complying with Section 6.5.3.2.3.

6.5.3.2.3 VAV Set-Point Reset. For multiple-zone VAV systems having a total fan system motor name- plate horsepower exceeding 5 hp with DDC of individual zones reporting to the central control panel, static pressure set point shall be reset based on the zone requiring the most pressure; i.e., the set point is reset lower until one zone damper is nearly wide open. Controls shall provide the following:

a. Monitor zone damper positions or other indicator of need for static pressure. b. Automatically detect those zones that may be excessively driving the reset logic and generate an alarm to

the system operator. c. Readily allow operator removal of zones from the reset algorithm.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for resetting static pressure set point based on VAV system zone damper position and other indicators of zone demand, including automatically detecting and alarming zones that are excessively driving reset logic and readily excluding those zones from reset logic.

6.5.3.2.4 Return and Relief Fan Control. Return and relief fans used to meet Section 6.5.1.1.5 shall comply with all of the following:

a. Relief air rate shall be controlled to maintain building pressure either directly, or indirectly through dif ferential supply-return airflow tracking. Systems with constant speed or multispeed supply fans shall also be allowed to control the relief system based on outdoor air damper position. b. Fans shall have variable-speed control or other devices that will result in total return/relief fan system

demand of no more than 30% of total design power at 50% of total design fan flow.

Exceptions to 6.5.3.2.4:

  1. Return or relief fans with total motor size less than or equal to 0.5 hp.
  2. Staged relief fans with a minimum of four stages.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for controlling build- ing pressure using economizer relief systems such as relief dampers, relief fans, and return fans.

6.5.3.3 Multiple-Zone VAV System Ventilation Optimization Control. Multiple-zone VAV systems with DDC of individual zone boxes reporting to a central control panel shall include means to automatically reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency as defined by ASHRAE Standard 62.1, Normative Appendix A.

Exceptions to 6.5.3.3:

  1. VAV systems with zonal transfer fans that recirculate air from other zones without directly mixing it with outdoor air, dual-duct dual-fan VAV systems, and VAV systems with fan-powered terminal units.
  2. Systems where total design exhaust airflow is more than 70% of total design outdoor air intake flow requirements.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for dynamically adjusting minimum ventilation rate set points based on ASHRAE Standard 62.1, Normative Appendix A.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 93

PDF Page 96

Open page note

6.5.3.4 Parallel-Flow Fan-Powered VAV Air Terminal Control. Parallel-flow fan-powered VAV air terminals shall have automatic controls configured to

a. turn off the terminal fan except when space heating is required or if required for ventilation ; b. turn on the terminal fan as the first stage of heating before the heating coil is activated; and c. during heating for warm-up or setback temperature control, either

  1. operate the terminal fan and heating coil without primary air or
  2. reverse the terminal damper logic and provide heating from the central air handler through primary air. Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for both constantspeed and variable-speed parallel fan-powered VAV air terminal units.

6.5.3.5 Supply Air Temperature Reset Controls. Multiple zone HVAC systems shall include controls that are capable of and configured to automatically reset the supply air temperature in response to representative building loads or outdoor air temperature. The controls shall reset the supply air temperature at least 25% of the difference between the design supply air temperature and the design room air temperature. Controls that adjust the reset based on zone humidity are allowed in Climate Zones 0B, 1B, 2B, 3B, 3C, and 4 through 8. HVAC zones that are expected to experience relatively constant loads shall have maximum airflow designed to accommodate the fully reset supply air temperature.

Exceptions to 6.5.3.5:

  1. Systems in Climate Zones 0A, 1A, and 3A with less than 3000 cfm of design outdoor air .
  2. Systems in Climate Zone 2A with less than 10,000 cfm of design outdoor air .
  3. Systems in Climate Zones 0A, 1A, 2A, and 3A with at least 80% outdoor air and employing exhaust air energy recovery complying with Section 6.5.6.1.
  4. Systems that prevent reheating, recooling, or mixing of heated and cooled supply air.
  5. Systems in which at least 75% of the energy for reheating (on an annual basis) is from site recov- ered energy or on-site renewable energy .

Informative Notes:

  1. HVAC zones that are expected to experience relatively constant loads typically include electronic equipment rooms and interior zones.
  2. ASHRAE Guideline 36 includes detailed sequences of control for resetting supply air temperature set point on multiple zone air handling units based on both zone air terminal unit demand and outdoor air temperature.

6.5.3.5.1 Dehumidification Control Interaction. In Climate Zones 0A, 1A, 2A, and 3A, the system design shall allow supply air temperature reset while dehumidification is provided. When dehumidification control is active, air economizers shall be locked out.

Informative Note: Examples of HVAC systems that can allow supply air temperature reset while dehumidifying include cooling of outdoor air with a separate cooling coil, bypassing return air around the cooling coil, a dedicated outdoor air system, and series energy recovery.

6.5.3.6 Fractional Horsepower Fan Motors. Motors for fans that are 1/12 hp or greater and less than 1 hp shall be electronically commutated motors or shall have a minimum motor efficiency of 70% when rated in accordance with DOE 10 CFR 431. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans may use sheave adjustments for airflow balancing in lieu of a varying motor speed.

Exceptions to 6.5.3.6:

  1. Motors in the airstream within fan-coils and terminal units that operate only when providing heating to the space served.
  2. Motors installed in space conditioning equipment certified under Section 6.4.1.
  3. Motors covered by Table 10.8-3 or 10.8-4.

6.5.3.7 Low Power Fans. Fans that are not covered by Section 6.5.3.6 and having a fan nameplate elec- trical input power of less than 180 W, or having a motor nameplate horsepower less than 1/12 hp, shall meet the fan efficacy requirements of Table 6.5.3.7 at one or more rating points.

Exceptions to 6.5.3.7:

  1. Fans in space -conditioning equipment .
  2. Intermittently operating dryer exhaust duct power ventilators, domestic range hoods, and domestic range booster fans.
  3. Fans in radon mitigation systems .
  4. Fans not covered within the scope of the test methods referenced in Table 6.5.3.7.
  5. Ceiling fans regulated under 10 CFR 430 Appendix U.

94 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 97

Open page note

Table 6.5.3.7 Minimum Fan Efficacy for Low-PowerFansCol3
System TypeMinimum Fan Efficacy a, b,
cfm/W
Test Method and
Rating Conditions
HRV c, ERV d, or other system
with exhaust air_energy_ recovery
1.2CAN/CSA 439-18
Transfer fans; in-line e supply or exhaust fan3.8ASHRAE Standard 51
Other exhaust fan, <90 cfm2.82.8
Other exhaust fan,90 cfm and200 cfm3.53.5
Other exhaust fan, >200 cfm4.04.0

a. Fan efficacy is the volumetric fan airflow rate divided by total fan motor electrical input power at a specified static pressure difference. b. Fans shall be tested in accordance with the referenced test method. Fan efficacy shall be reported in the product listing or shall be derived from the fan

motor electrical input power and airflow values reported in the product listing or on the label. Fan efficacy for fully ducted HRV or ERV, balanced, and in-line fans shall be determined at a static pressure difference not less than 0.2 in. of water for each airstream. Fan efficacy for other ducted fan systems shall be determined at a static pressure difference not less than 0.1 in. of water. c. A heat recovery ventilator (HRV) is a mechanically powered ventilating device with separate intake and exhaust airstreams and a heat exchanger to trans fer a portion of the sensible energy, heat, from one airstream to the other. d. An energy recovery ventilator (ERV) is a mechanically powered ventilating device with separate intake and exhaust airstreams and a heat exchanger to

transfer a portion of the total energy, heat and moisture, from one airstream to the other. e. An in-line fan is an exhaust or supply fan installed with ductwork on both the fan inlet and outlet.

6.5.3.8 Ventilation Design. The required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by Standard 62.1, Standard 62.2, Standard 170, or applicable codes or accreditation standards. Outdoor air ventilation systems shall comply with one of the following:

a. Design minimum system outdoor air provided shall not exceed 135% of the required minimum outdoor

air rate. b. Dampers, ductwork, and controls shall be provided that allow the system to supply no more than the

required minimum outdoor air rate with a single set-point adjustment. c. The system includes exhaust air energy recovery complying with Section 6.5.6.1.

6.5.3.9 Occupied-Standby Zone Controls. Zones serving only rooms that are required to have auto- matic partial OFF or automatic full OFF lighting controls per Section 9.4.1.1, where the ASHRAE Standard 62.1 occupancy category permits ventilation air to be reduced to zero when the space is in occupied-standby mode and when using the Ventilation Rate Procedure, shall meet the following within five minutes of all rooms in that zone entering occupied-standby mode .

a. Active heating set point shall be setback at least 1°F. b. Active cooling set point shall be set up at least 1°F. c. All airflow supplied to the zone shall be shut off whenever the space temperature is between the active

heating and cooling set points .

Exception to 6.5.3.9: Multiple zone systems without automatic zone flow control dampers. Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for occupied standby controls of zone air terminal units.

6.5.3.9.1 Occupied-Standby Control of Multiple-Zone Systems. Multiple-zone systems that are capable of resetting the minimum outdoor air set point and that serve zones with occupied-standby zone controls shall reset the minimum outdoor air set point based on a zone outdoor air requirement of zero for all zones in occupied-standby mode .

Informative Note: ASHRAE Guideline 36 includes sequences for this reset . 6.5.4 Hydronic System Design and Control 6.5.4.1 Boiler Turndown. Boiler systems with design input of at least 1,000,000 Btu/h shall comply with the turndown ratio specified in Table 6.5.4.1.

The system turndown requirement shall be met through the use of multiple single-input boilers, one or more modulating boilers, or a combination of single-input and modulating boilers .

All boilers shall meet the minimum efficiency requirements in Table 6.8.1-6. 6.5.4.2 Hydronic Variable Flow Systems. Chilled- and hot-water distribution systems that include three or more control valves designed to modulate or step open and close as a function of load shall be designed for variable fluid flow and shall be capable of and configured to reduce pump flow rates to no more than the larger of 25% of the design flow rate or the minimum flow required by the heating/cooling equip-

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 95

PDF Page 98

Open page note

Table 6.5.4.1 Boiler TurndownCol2
Boiler System Design Input, Btu/hMinimum Turndown Ratio
1,000,000 and5,000,0003 to 1
>5,000,000 and10,000,0004 to 1
>10,000,0005 to 1

Table 6.5.4.2 Pump Flow Control Requirements

Chilled-Water Pumps in These
Climate Zones
Heating Water Pumps in These
Climate Zones
Motor Nameplate Horsepower
0A, 0B, 1A, 1B, 2BNR2 hp
2A, 3BNR3 hp
3A, 3C, 4A, 4B7, 85 hp
4C, 5A, 5B, 5C, 6A, 6B3C, 5A, 5C, 6A, 6B7.5 hp
4C, 5A, 5B, 5C, 6A, 6B4A, 4C, 5B10 hp
7, 84B15 hp
7, 82A, 2B, 3A, 3B25 hp
7, 81B100 hp
7, 80A, 0B, 1A200 hp

ment manufacturer for the proper operation of equipment . Individual or parallel pumps serving variable-flow heating-water or chilled-water systems, where the nameplate horsepower of the motor or combined parallel motors is at least the power shown in Table 6.5.4.2, shall have controls or devices that will result in pump motor demand of no more than 30% of design wattage at 50% of design water flow The controls or devices shall be controlled as a function of desired flow or to maintain a minimum required differential pressure. Differential pressure shall be measured at or near the most remote heat exchanger or the heat exchanger requiring the greatest differential pressure. The differential pressure set point shall be no more than 110% of that required to achieve design flow through the heat exchanger. Where differential pressure control is used to comply with this section and DDC systems are used, the set point shall be reset downward based on valve positions until one valve is nearly wide open.

Exceptions to 6.5.4.2:

  1. Differential pressure set-point reset is not required where valve position is used to comply with Section 6.5.4.4.
  2. Variable- pump flow control is not required on heating-water pumps where more than 50% of annual heat is generated by an electric boiler .
  3. Variable flow is not required for primary pumps in a primary/secondary system .
  4. Variable flow is not required for a coil pump provided for freeze protection.
  5. Variable flow is not required for heat recovery coil runaround loops.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control of variable flow hydronic systems, including resetting differential pressure set point based on control valve position.

6.5.4.3 Chiller and Boiler Isolation Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for chiller and boiler flow isolation and staging.

6.5.4.3.1 When a chilled-water plant includes more than one chiller, provisions shall be made so that all fluid flow through the chiller is automatically shut off when the chiller is shut down. Chillers piped in series for the purpose of increased temperature differential shall be considered as one chiller. Where constant-speed chilled-water or condenser water pumps are used to serve multiple chillers, the number of pumps shall be no less than the number of chillers and staged on and off with the chillers.

6.5.4.3.2 When a boiler plant includes more than one boiler, provisions shall be made so that the flow through the boiler is automatically shut off when the boiler is shut down. Where constant-speed hot-water

96 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 99

Open page note

Table 6.5.4.6 Piping System Design Maximum Flow Rate in GPM

Operating Hours/Year2000 Hours/YearCol3>2000 and 4400 Hours/YearCol5>4400 Hours/YearCol7
Nominal Pipe Size, in.OtherVariable Flow/
Variable Speed
OtherVariable Flow/
Variable Speed
OtherVariable Flow/
Variable Speed
2 1/21201808513068110
3180270140210110170
4350530260400210320
5410620310470250370
67401100570860440680
81200180090014007001100
10180027001300200010001600
12250038001900290015002300
Maximum velocity for pipes
over 14 to 24 in. in size
8.5 ft/s13.0 ft/s6.5 ft/s9.5 ft/s5.0 ft/s7.5 ft/s

pumps are used to serve multiple boilers, the number of pumps shall be no less than the number of boilers and staged on and off with the boilers .

6.5.4.4 Chilled- and Hot-Water Temperature Reset Controls. Chilled- and hot-water systems with a design capacity exceeding 300,000 Btu/h supplying chilled or heated water to comfort conditioning systems shall include controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature. Where DDC is used to control valves, the set point shall be reset based on valve positions until one valve is nearly wide open or set-point limits of the system equipment or application have been reached.

Exceptions to 6.5.4.4:

  1. Where chilled-water supply is already cold, such as chilled water supplied from a district cooling or thermal energy storage system, such that blending would be required to achieve the reset chilledwater supply temperature.
  2. Where a specific temperature is required for a process application .
  3. Water temperature reset is not required where valve position is used to comply with Section 6.5.4.2.

Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for resetting chilledwater and hot-water system temperature set points based on control valve position.

6.5.4.5 Hydronic (Water Loop) Heat Pumps and Water-Cooled Unitary Air Conditioners

6.5.4.5.1 Each hydronic heat pump and water-cooled unitary air conditioner shall have a two-position automatic valve interlocked to shut off water flow when the compressor is off.

Exception to 6.5.4.5.1: Units employing a fluid economizer.

6.5.4.5.2 Hydronic heat pumps and water-cooled unitary air conditioners having a total pump system power exceeding 5 hp shall have controls and/or devices (such as variable-speed control) that will result in pump motor demand of no more than 30% of design wattage at 50% of design water flow.

6.5.4.6 Pipe Sizing. All chilled-water and condenser-water piping shall be designed such that the design flow rate in each piping segment shall not exceed the values listed in Table 6.5.4.6 for the appropriate total annual hours of operation. Piping size selections for systems that operate under variable flow conditions (e.g., modulating two-way control valves at coils) and that contain variable-speed pump motors are allowed to be made from the “Variable Flow/Variable Speed” columns. All others shall be made from the “Other” columns.

Exceptions to 6.5.4.6:

  1. Design flow rates exceeding the values in Table 6.5.4.6 are allowed in specific sections of piping if the piping in question is not in the critical circuit at design conditions and is not predicted to be in the critical circuit during more than 30% of operating hours.
  2. Piping systems that have equivalent or lower total pressure drop than the same system constructed with standard weight steel pipe with piping and fittings sized per Table 6.5.4.6.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 97

PDF Page 100

Open page note

6.5.4.7 Chilled-Water Coil Selection. Chilled-water cooling coils shall be selected to provide a 15°F or higher temperature difference between leaving and entering water temperatures and a minimum of 57°F leaving water temperature at design conditions .

Exceptions to 6.5.4.7:

  1. Chilled-water cooling coils that have an air-side pressure drop exceeding 0.70 in. of water when rated at 500 fpm face velocity and dry conditions (no condensation).
  2. Individual fan-cooling units with a design supply airflow rate 5000 cfm and less.
  3. Constant-air-volume systems .
  4. Coils selected at the maximum temperature difference allowed by the chiller.
  5. Passive coils (no mechanically supplied airflow).
  6. Coils with design entering chilled-water temperatures of 50°F and higher.
  7. Coils with design entering air dry-bulb temperatures of 65°F and lower.

6.5.4.8 Buildings with High-Capacity Space-Heating Gas Boiler Systems. New buildings with gas hot-water boiler systems for space heating with a total system input of at least 1,000,000 Btu/h but not more than 10,000,000 Btu/h shall comply with Sections 6.5.4.8.1 and 6.5.4.8.2.

Exceptions to 6.5.4.8:

  1. Where 25% of the annual space heating requirement is provided by on-site renewable energy, site-recovered energy, or heat recovery chillers.
  2. Space heating boilers installed in individual dwelling units .
  3. Where 50% or more of the design heating load is served using perimeter convective heating, radiant ceiling panels, or both.
  4. Individual gas boilers with input capacity less than 300,000 Btu/h shall not be included in the calculations of the total system input or total system efficiency .

6.5.4.8.1 Boiler Efficiency. Gas hot-water boilers shall have a minimum thermal efficiency ( Et ) of 90% when rated in accordance with the test procedures in Table 6.8.1-6. Systems with multiple boilers are allowed to meet this requirement if the space heating input provided by equipment with thermal efficiency ( Et ) above and below 90% provides an input capacity-weighted average thermal efficiency of at least 90%. For boilers rated only for combustion efficiency, the calculation for the input capacity-weighted average thermal efficiency shall use the combustion efficiency value.

6.5.4.8.2 Hot-Water Distribution System Design. The hot-water distribution system shall be designed to meet all of the following:

a. Coils and other heat exchangers shall be selected so that at design conditions the hot-water return tem perature entering the boilers is 120°F or less. b. Under all operating conditions, the water temperature entering the boiler is 120°F or less, or the flow rate

of supply hot water that recirculates directly into the return system, such as by three-way valves or minimum flow bypass controls, shall be no greater than 20% of the design flow of the operating boilers .

6.5.5 Heat-Rejection Equipment 6.5.5.1 General. Section 6.5.5 applies to heat-rejection equipment used in comfort cooling systems, such as air-cooled condensers, dry coolers, open-circuit cooling towers, closed-circuit cooling towers, and evaporative condensers.

Exception to 6.5.5.1: Heat-rejection devices whose energy use is included in the equipment efficiency

ratings listed in Tables 6.8.1-1 through 6.8.1-4, Tables 6.8.1-8 through 6.8.1-14, and Tables 6.8.1-16, 6.8.1-17, and 6.8.1-20. 6.5.5.2 Fan Speed Control Informative Note: ASHRAE Guideline 36 includes detailed sequences of control for staging and controlling variable-speed cooling tower cells and fans.

6.5.5.2.1 The fan system on a heat-rejection device powered by an individual motor or an array of motors with a connected power, including the motor service factor, totaling 5 hp or more shall have controls and/or devices (such as variable-speed control) that shall result in fan motor demand of no more than 30% of design wattage at 50% of the design airflow and that shall automatically modulate the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat-rejection device.

Exceptions to 6.5.5.2.1:

  1. Condenser fans serving multiple refrigerant or fluid cooling circuits.
  2. Condenser fans serving flooded condensers.

98 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 101

Open page note

6.5.5.2.2 Multicell heat-rejection equipment with variable-speed fan drives shall

a. operate the maximum number of fans allowed that comply with the manufacturer ’s requirements for all

system components and b. control all fans to the same fan speed required for the instantaneous cooling duty, as opposed to staged

(on/off) operation. Minimum fan speed shall comply with the minimum allowable speed of the fan drive system per the manufacturer ’s recommendations.

6.5.5.3 Limitation on Centrifugal Fan Open-Circuit Cooling Towers. Centrifugal fan open-circuit cooling towers with a combined rated capacity of 1100 gpm or greater at 95°F condenser water return, 85°F condenser water supply, and 75°F outdoor air wet-bulb temperature shall meet the energy efficiency requirement for axial fan open-circuit cooling towers listed in Table 6.8.1-7.

Exception to 6.5.5.3: Centrifugal open-circuit cooling towers that are ducted (inlet or discharge) or

require external sound attenuation. 6.5.5.4 Tower Flow Turndown. Open-circuit cooling towers used on water-cooled chiller systems that are configured with multiple- or variable-speed condenser water pumps shall be designed so that all opencircuit cooling tower cells can be run in parallel with the larger of

a. the flow that is produced by the smallest pump at its minimum expected flow rate or b. 50% of the design flow for the cell.

6.5.6 Energy Recovery 6.5.6.1 Exhaust Air Energy Recovery 6.5.6.1.1 Nontransient Dwelling Units. Nontransient dwelling units shall be provided with outdoor air energy recovery ventilation systems . For nontransient dwelling units, energy recovery systems shall result in an enthalpy recovery ratio of at least 50% at the cooling design condition.

At the heating design condition, energy recovery performance shall be as follows:

a. Where active humidification is provided to spaces served by the system, energy recovery systems shall

result in an enthalpy recovery ratio of at least 60%. b. Where active humidification is not provided to spaces served by the system, energy recovery systems

shall result in a sensible energy recovery ratio of at least 60%.

The energy recovery system shall provide the required enthalpy recovery ratio or sensible energy recov- ery ratio at both heating and cooling design conditions, unless one mode is not required for the climate zone by the exceptions below.

Exceptions to 6.5.6.1.1:

  1. Nontransient dwelling units in Climate Zone 3C.
  2. Nontransient dwelling units with no more than 500 ft [2] of gross conditioned floor area in Climate Zone 0, 1, 2, 3, 4C, and 5C.
  3. Energy recovery performance requirements at heating design condition in Climate Zones 0, 1, and 2.
  4. Enthalpy recovery ratio requirements at cooling design condition in Climate Zones 4, 5, 6, 7, 8.

6.5.6.1.2 Spaces Other than Nontransient Dwelling Units. Each fan system serving spaces other than nontransient dwelling units shall have an energy recovery system where the design supply fan airflow rate exceeds the value listed in Tables 6.5.6.1.2-1 and 6.5.6.1.2-2, based on the climate zone and percentage of outdoor air at design airflow conditions. Table 6.5.6.1.2-1 shall be used for all ventilation systems that operate less than 8000 hours per year, and Table 6.5.6.1.2-2 shall be used for all ventilation systems that operate 8000 or more hours per year.

Exceptions to 6.5.6.1.2:

  1. Laboratory systems meeting Section 6.5.7.3.
  2. Systems serving spaces that are not cooled and that are heated to less than 60°F.
  3. Heating energy recovery where more than 60% of the outdoor air heating energy is provided from site-recovered energy or on-site renewable energy in Climate Zones 5 through 8.
  4. Enthalpy recovery ratio requirements at heating design condition in Climate Zones 0, 1, and 2.
  5. Enthalpy recovery ratio requirements at cooling design condition in Climate Zones 3C, 4C, 5B, 5C, 6B, 7, and 8.
  6. Where the sum of the airflow rates exhausted and relieved within 20 ft of each other is less than 75% of the design outdoor airflow rate, excluding exhaust air that is a. used for another energy recovery system,

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 99

PDF Page 102

Open page note

Table 6.5.6.1.2-1 Exhaust Air Energy Recovery Requirements for Ventilation SystemsOperating Less than 8000 Hours per Year

Climate Zone% Outdoor Air at Full Design Airflow RateCol3Col4Col5Col6Col7Col8Col9
Climate Zone10% and
** <20%**
20% and
** <30%**
30% and
<40%
40% and
<50%
50% and
<60%
60% and
<70%
70% and
<80%
80%
Climate ZoneDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfm
3B, 3C, 4B,
4C, 5B
NRNRNRNRNRNRNRNR
0B, 1B, 2B,5CNRNRNRNR26,00012,00050004000
6B28,00026,50011,00055004500350025001500
0A, 1A, 2A,
3A, 4A, 5A,
6A
26,00016,00055004500350020001000120
7,8450040002500100014012010080

NR—Not required

Table 6.5.6.1.2-2 Exhaust Air Energy Recovery Requirements for Ventilation SystemsOperating Greater than or Equal to 8000 Hours per Year

Climate Zone% Outdoor Air at Full Design Airflow RateCol3Col4Col5Col6Col7Col8Col9
Climate Zone10% and
<20%
20% and
<30%
30% and
<40%
40% and
<50%
50% and
<60%
60% and
<70%
70% and
< 80%
80%
Climate ZoneDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfmDesign Supply Fan Airflow Rate, cfm
3CNRNRNRNRNRNRNRNR
0B, 1B, 2B,
3B, 4C, 5C
NR19,50090005000400030001500120
0A, 1A, 2A,
3A, 4B, 5B
25002000100050014012010080
4A, 5A, 6A,
6B, 7, 8
2001301008070605040

NR—Not required

b. not allowed by ASHRAE/ASHE Standard 170 for use in energy recovery systems with leak age potential, or c. of Class 4 as defined in ASHRAE Standard 62.1. 7. Systems in Climate Zones 0 through 4 requiring dehumidification that employ series energy recovery and have a minimum SERR of 0.40. 8. Systems expected to operate less than 20 hours per week at the outdoor air percentage covered by Table 6.5.6.1.2-1. 9. Indoor pool dehumidifiers meeting Section 6.5.6.4.

6.5.6.1.2.1 Minimum Enthalpy Recovery Ratio. Energy recovery systems required by this section shall result in an enthalpy recovery ratio of at least 50% at the cooling design condition.

At the heating design condition, energy recovery performance shall be as follows:

a. Where active humidification is provided to spaces served by the system, energy recovery systems shall

result in an enthalpy recovery ratio of at least 50%. b. Where active humidification is not provided to spaces served by the system, energy recovery systems

shall result in a sensible energy recovery ratio of at least 50%.

The energy recovery system shall provide the required enthalpy recovery ratio or sensible energy recov- ery ratio at both heating and cooling design conditions unless one mode is not required for the climate zone by the exception to Section 6.5.6.1.2.

100 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 103

Open page note

6.5.6.1.2.2 Provision for Air Economizer or Bypass Operation. Provision shall be made for both outdoor air and exhaust air to bypass or control the energy recovery system to enable economizer operation as required by Section 6.5.1.1. The bypass or control shall meet the following criteria:

a. For energy recovery systems where the transfer of energy cannot be stopped, bypass provision shall pre vent the total airflow rate of either outdoor air or exhaust air through the energy recovery exchanger from exceeding 10% of the full design airflow rate. b. The pressure drop of the outdoor air through the energy recovery exchanger shall not exceed 0.4 in. of

water; the pressure drop of the exhaust air through the energy recovery exchanger shall not exceed 0.4 in. of water.

Exception to 6.5.6.1.2.2: Energy recovery systems with 80% or more outdoor air at full design air flow rate and not exceeding 10,000 cfm.

6.5.6.2 Heat Recovery for Service Water Heating 6.5.6.2.1 Condenser heat recovery systems shall be installed for heating or preheating of service hot water provided all of the following are true:

a. The facility operates 24 hours a day. b. The total installed heat-rejection capacity of the water-cooled systems exceeds 6,000,000 Btu/h of heat

rejection. c. The design service water-heating load exceeds 1,000,000 Btu/h.

6.5.6.2.2 The required heat recovery system shall have the capacity to provide the smaller of

a. 60% of the peak heat-rejection load at design conditions or b. preheat of the peak service hot-water draw to 85°F.

Exceptions to 6.5.6.2.2:

  1. Facilities that employ condenser heat recovery for space heating with a heat recovery design exceeding 30% of the peak water-cooled condenser load at design conditions .
  2. Facilities that provide 60% of their service water heating from on-site renewable energy or site- recovered energy or from other sources.

6.5.6.3 Heat Recovery for Space Conditioning. Where heating water is used for space heating, a heatpump chiller meeting the requirements of Table 6.8.1-16 for heat recovery that uses the cooling system return water as the heat source shall be installed, provided all of the following are true:

a. The building is an acute inpatient hospital, where the building or portion of a building is used on a 24 hour basis for the inpatient medical, obstetric, or surgical care for patients. b. The total design chilled-water capacity for the acute inpatient hospital, either air cooled or water cooled,

required at cooling design conditions exceeds 3,600,000 Btu/h of cooling. c. Simultaneous heating, including reheat, and cooling occurs above 60°F outdoor air temperature.

The required heat recovery system shall have a cooling capacity that is at least 7% of the total design chilled-water capacity of the acute inpatient hospital at peak design conditions .

Exception to 6.5.6.3: Buildings in Climate Zones 5C, 6B, 7, and 8. 6.5.6.4 Indoor Pool Dehumidifier Energy Recovery. An indoor pool dehumidifier serving a natatorium with a heated indoor pool over 500 ft [2] in size shall include one of the following:

a. An exhaust air sensible energy recovery system with a sensible energy recovery ratio of at least 50% b. A condenser heat recovery system capable of and configured to use 100% of the heat generated through

dehumidification to heat the pool water when there is a pool water heating load c. An exhaust air energy recovery system that results in an enthalpy recovery ratio of at least 50%

Exception to 6.5.6.4: Natatoriums heated by on-site renewable energy or site recovered energy capable

of and configured to provide at least 60% of the annual heating energy required. 6.5.7 Exhaust Systems 6.5.7.1 Transfer Air. Conditioned supply air delivered to any space with mechanical exhaust shall not exceed the greater of

a. the supply flow required to meet the space heating or cooling load; b. the ventilation rate required by the authority having jurisdiction, the facility Environmental Health and

Safety department, or ASHRAE Standard 62.1; or

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 101

PDF Page 104

Open page note

Table 6.5.7.2.2 Maximum Net Exhaust Flow Rate, cfm per Linear Foot of Hood Length

Type of HoodLight-Duty
Equipment
Medium-Duty
Equipment
Heavy-Duty
Equipment
Extra-Heavy-Duty
Equipment
Wall-mounted canopy140210280385
Single island280350420490
Double island (per side)175210280385
Eyebrow175175NANA
Backshelf/pass-over210210280NA

NA = Not allowed

c. the mechanical exhaust flow minus the available transfer air from conditioned spaces or return air ple-

nums on the same story, not in different smoke or fire compartments, and that at their closest point are within 15 ft of each other. Available transfer air is that portion of outdoor ventilation air that

  1. is not required to satisfy other exhaust needs,

  2. is not required to maintain pressurization of other spaces, and

  3. is transferable according to applicable codes and standards and to the class of air recirculation limitations in ASHRAE Standard 62.1. Exceptions to 6.5.7.1:

  4. Biosafety level 3 classified laboratories or higher.

  5. Vivarium spaces .

  6. Spaces that are required by applicable codes and standards to be maintained at positive pressure relative to adjacent spaces . For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy .

  7. Spaces where the demand for transfer air may exceed the available transfer airflow rate and where the spaces have a required negative pressure relationship. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated airhandling unit and shall be used whenever economizer or other options do not save more energy .

6.5.7.2 Kitchen Exhaust Systems 6.5.7.2.1 Replacement air introduced directly into the hood cavity of kitchen exhaust hoods shall not exceed 10% of the hood exhaust airflow rate.

6.5.7.2.2 If a kitchen/dining facility has a total kitchen hood exhaust airflow rate greater than 5000 cfm then each hood shall have an exhaust rate that complies with Table 6.5.7.2.2. If a single hood or hood section is installed over appliances with different duty ratings then the maximum allowable flow rate for the hood or hood section shall not exceed the Table 6.5.7.2.2 values for the highest appliance duty rating under the hood or hood section. Refer to ASHRAE Standard 154 for definitions of hood type, appliance duty, and net exhaust flow rate.

Exception to 6.5.7.2.2: At least 75% of all the replacement air is transfer air that would otherwise be

exhausted.

6.5.7.2.3 If a kitchen/dining facility has a total kitchen hood exhaust airflow rate greater than 5000 cfm then it shall have one of the following:

a. At least 50% of all replacement air is transfer air that would otherwise be exhausted. b. Demand ventilation systems on at least 75% of the exhaust air. Such systems shall be capable of and con figured to provide at least 50% reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent, and combustion products during cooking and idle. c. Listed energy recovery devices that result in a sensible energy recovery ratio of not less than 40% on at

least 50% of the total exhaust airflow. A 40% sensible energy recovery ratio shall mean a change in the dry-bulb temperature of the outdoor air supply equal to 40% of the difference between the outdoor air and entering exhaust air dry-bulb temperatures at design conditions .

6.5.7.2.4 Performance Testing. An approved field test method shall be used to evaluate design airflow rates and demonstrate proper capture and containment performance of installed commercial kitchen

102 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 105

Open page note

Table 6.5.9 Hot-Gas Bypass LimitationCol2
Rated CapacityMaximum Hot-Gas Bypass, % of Total Capacity
240,000 Btu/h15%
>240,000 Btu/h10%

exhaust systems . Where demand ventilation systems are used to meet Section 6.5.7.2.3, additional performance testing shall be required to demonstrate proper capture and containment at minimum airflow.

6.5.7.3 Laboratory Exhaust Systems. Buildings with laboratory exhaust systems having a total exhaust rate greater than 5000 cfm shall include at least one of the following features:

a. VAV laboratory exhaust and room supply system capable of and configured to reduce exhaust and

makeup airflow rates and/or incorporate a heat recovery system to precondition makeup air from laboratory exhaust that shall meet the following:

A + B × ( E / M )  50% where A = percentage that the exhaust and makeup airflow rates can be reduced from design conditions B = sensible energy recovery ratio E = exhaust airflow rate through the heat recovery device at design conditions M = makeup airflow rate of the system at design conditions b. VAV laboratory exhaust and room supply systems that are required to have minimum circulation rates to

comply with code or accreditation standards shall be capable of and configured to reduce zone exhaust and makeup airflow rates to the regulated minimum circulation values or the minimum required to maintain pressurization relationship requirements. Systems serving nonregulated zones shall be capable of and configured to reduce exhaust and makeup airflow rates to 50% of the zone design values or the minimum required to maintain pressurization relationship requirements. c. Direct makeup (auxiliary) air supply equal to at least 75% of the exhaust airflow rate, heated no warmer

than 2°F below room set point, cooled to no cooler than 3°F above room set point, no humidification added, and no simultaneous heating and cooling used for dehumidification control.

6.5.8 Radiant Heating Systems 6.5.8.1 Heating Unenclosed Spaces. Radiant heating shall be used when heating is required for unen- closed spaces .

Exception to 6.5.8.1: Loading docks equipped with air curtains. 6.5.8.2 Heating Enclosed Spaces. Radiant heating systems that are used as primary or supplemental heating for enclosed spaces must be in conformance with the governing provisions of the standard, including but not limited to the following:

a. Radiant hydronic ceiling or floor panels (used for heating or cooling) b. Combination or hybrid systems incorporating radiant heating (or cooling) panels c. Radiant heating (or cooling) panels used in conjunction with other systems such as VAV or thermal stor age systems

6.5.9 Hot-Gas Bypass Limitation. Cooling systems shall not use hot-gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot-gas bypass shall be limited as indicated in Table 6.5.9 for VAV units. Hot-gas bypass shall not be used on constant-volume units.

6.5.10 Door Switches. Any conditioned space with a door, including doors with more than one-half glass, opening to the outdoors shall be provided with controls that, when any such door is open,

a. disable mechanical heating or reset the heating set point to 55°F or lower within five minutes of the door

opening and b. disable mechanical cooling or reset the cooling set point to 90°F or greater within five minutes of the

door opening. Mechanical cooling may remain enabled if outdoor air temperature is below space temperature.

Exceptions to 6.5.10:

  1. Building entries with automatic closing devices.
  2. Any space without a thermostat .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 103

PDF Page 106

Open page note

  1. Alterations to existing buildings .
  2. Loading docks.

6.5.11 Refrigeration Systems. Refrigeration systems that comprise refrigerated display cases, walk-in coolers, or walk-in freezers connected to remote compressors, remote condensers, or remote condensing units shall meet the requirements of Sections 6.5.11.1 and 6.5.11.2.

Exception to 6.5.11: Systems using transcritical refrigeration cycle or ammonia refrigerant. 6.5.11.1 Condensers Serving Refrigeration Systems. Fan-powered condensers shall conform to the following requirements:

a. Design saturated condensing temperatures for air-cooled condensers shall be less than or equal to the

design dry-bulb temperature plus 10°F for low-temperature refrigeration systems and less than or equal to the design dry-bulb temperature plus 15°F for medium-temperature refrigeration systems .

  1. Saturated condensing temperature for blend refrigerants shall be determined using the average of liquid and vapor temperatures as converted from the condenser drain pressure. b. Condenser fan motors that are less than 1 hp shall use electronically commutated motors, permanent

split-capacitor-type motors, or three-phase motors. c. All condenser fans for air-cooled condensers, evaporatively cooled condensers, and air- or water-cooled

fluid coolers or cooling towers shall incorporate one of the following continuous variable-speed fan control approaches and shall reduce fan motor demand to no more than 30% of design wattage at 50% of design air volume:

  1. Refrigeration system condenser control for air-cooled condensers shall use variable set-point control logic to reset the condensing temperature set point in response to ambient dry-bulb temperature.
  2. Refrigeration system condenser control for evaporatively cooled condensers shall use variable set- point control logic to reset the condensing temperature set point in response to ambient wet-bulb temperature. d. Multiple fan condensers shall be controlled in unison. e. The minimum condensing temperature set point shall be no greater than 70°F.

6.5.11.2 Compressor Systems. Refrigeration compressor systems shall conform to the following requirements:

a. Compressors and multiple-compressor systems suction groups shall include control systems that use

floating suction pressure control logic to reset the target suction pressure temperature based on the temperature requirements of the attached refrigeration display cases or walk-ins. Exceptions to 6.5.11.2(a):

  1. Single-compressor systems that do not have variable-capacity capability.
  2. Suction groups that have a design saturated suction temperature equal to or greater than 30°F, suction groups that comprise the high stage of a two-stage or cascade system, or suction groups that primarily serve chillers for secondary cooling fluids.

b. Liquid subcooling shall be provided for all low-temperature compressor systems with a design cooling

capacity equal to or greater than 100,000 Btu/h with a design saturated suction temperature equal to or less than –10°F. The subcooled liquid temperature shall be controlled at a maximum temperature set point of 50°F at the exit of the subcooler using either compressor economizer (interstage) ports or a separate compressor suction group operating at a saturated suction temperature equal to or greater than 18°F.

  1. Subcooled liquid lines are subject to the insulation requirements of Table 6.8.3-2. c. All compressors that incorporate internal or external crankcase heaters shall provide a means to cycle the

heaters off during compressor operation.

6.6 Alternative Compliance Path 6.6.1 Computer Rooms Systems Path. The Computer Room System Path is an optional path for compliance where the following conditions are met:

a. HVAC systems that only serve the heating, cooling, or ventilating needs of a computer room with IT

equipment load greater than 10 kW shall comply with ASHRAE Standard 90.4, Energy Standard for Data Centers . b. All other HVAC systems shall comply with the applicable requirements in Section 6.5.

6.6.2 Mechanical System Performance Path 6.6.2.1 Scope. The Mechanical System Performance Path is an optional path for compliance where the following conditions are met:

104 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 107

Open page note

Table 6.6.2.2 Mechanical Performance Factors (MPF)

Building TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Office
(small and
medium)a
0.720.710.700.700.680.650.710.660.620.690.640.650.720.660.650.740.700.750.77
Office (large)a0.830.830.840.840.790.820.720.840.780.690.800.670.720.750.670.730.730.710.70
Retail0.600.570.500.550.460.460.430.460.380.400.450.480.410.500.470.440.390.400.36
Hotel/motel0.620.620.630.630.620.680.610.710.730.590.660.650.550.590.680.510.540.470.40
Multifamily/
dormitory
0.640.630.670.630.650.640.590.680.540.590.570.520.580.530.480.570.530.550.52
School/education0.820.810.800.790.750.720.710.720.680.670.710.650.720.680.600.750.690.720.68

a. Office sizes defined in Section L1.1.1.1.

a. All HVAC systems in the building that meet the criteria in Section L1.1.1 shall comply with Section

6.6.2.2. b. All other HVAC systems shall comply with one of the following:

  1. HVAC systems shall comply with the applicable requirements in Section 6.5.
  2. HVAC systems that only serve the heating, cooling, or ventilating needs of a computer room with IT equipment load greater than 10 kW shall be permitted to comply with ANSI/ASHRAE Standard 90.4, Energy Standard for Data Centers . 6.6.2.2 Criteria. HVAC systems in new buildings, additions, or alterations shall comply with the requirements in Section L2, “Mechanical System Performance Rating Method.” The proposed design total system performance ratio ( TSPRp ) of the HVAC systems using this method shall be greater than or equal to the total system performance ratio of the TSPR reference building design ( TSPRr ) divided by the mechanical performance factor (MPF) when calculated in accordance with the following:

TSPRp - TSPRr /MPF

where TSPR p = proposed TSPR calculated in accordance with Normative Appendix L TSPR r = reference TSPR calculated in accordance with Normative Appendix L MPF = mechanical performance factor from Table 6.6.2.2 based on climate zone and building use type

Where a building has multiple building use types, MPF shall be area weighted as follows:

MPF = ( A 1 × MPF1 + A 2 × MPF2 + … + An × MPF n )/( A 1 + A 2 + … + An )

where MPF1, MPF2, …, MPF n = mechanical performance factors from Table 6.6.2.2 based on climate zone and building use types 1 through n A 1, A 2, …, An = gross conditioned floor areas for building use types 1 through n Informative Note: The Mechanical System Performance Rating Method is a simplified performance trade-off approach for HVAC systems that does not require using the whole- building trade-off approaches in Section 12 or Normative Appendix G. HVAC systems that are allowed to use this approach will not need to comply with all of the prescriptive requirements in Section 6.5. For example, an HVAC system without a required outdoor air economizer can show compliance with Section 6 by demonstrating improved cooling efficiency or reduced fan energy use compared to a reference HVAC system that meets all prescriptive requirements, including outdoor air economizers . This approach does not allow HVAC system efficiency trade-offs with building envelope, plug loads , or lighting systems .

6.7 Submittals 6.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

6.7.2 Permit Application Documentation (Not Used) 6.7.3 Completion Requirements

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 105

PDF Page 108

Open page note

6.7.3.1 Record Documents. Construction documents shall require that, within 90 days after the date of system acceptance, record documents be provided to the building owner or the designated representative of the building owner. Record documents shall include, as a minimum, the location and performance data on each piece of equipment ; general configuration of the duct and pipe distribution system, including sizes; and the terminal air or water design flow rates.

6.7.3.2 Manuals. Construction documents shall require that an operating manual and a maintenance manual be provided to the building owner or the designated representative of the building owner within 90 days after the date of system acceptance. These manuals shall be in accordance with industry-accepted standards (see Informative Appendix E) and shall include, at a minimum, the following:

a. Submittal data stating equipment size and selected options for each piece of equipment requiring mainte nance. b. Operation manuals and maintenance manuals for each piece of equipment and system requiring mainte nance, except equipment not furnished as part of the project. Required routine maintenance actions shall be clearly identified. c. Names and addresses of at least one service agency . d. HVAC controls system maintenance and calibration information, including wiring diagrams, schematics,

and control sequence descriptions. Desired or field-determined set points shall be permanently recorded on control drawings at control devices or, for digital control systems, in programming comments. e. A complete narrative of how each system is intended to operate, including suggested set points .

6.7.3.3 System Balancing 6.7.3.3.1 General. Construction documents shall require that all HVAC systems be balanced in accordance with generally accepted engineering standards (see Informative Appendix E). Construction docu- ments shall require that a written balance report be provided to the building owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 ft [2] .

6.7.3.3.2 Air System Balancing. Air systems shall be balanced in a manner to first minimize throttling losses. Then, for fans with fan system power greater than 1 hp, fan speed shall be adjusted to meet design flow conditions.

6.7.3.3.3 Hydronic System Balancing. Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.

Exceptions to 6.7.3.3.3: Impellers need not be trimmed nor pump speed adjusted

  1. for pumps with pump motors of 10 hp or less or
  2. when throttling results in no greater than 5% of the nameplate horsepower draw, or 3 hp, whichever is greater, above that required if the impeller was trimmed.

6.8 Minimum Equipment Efficiency Tables 6.8.1 Minimum Efficiency Requirement Listed Equipment—Standard Rating and Operating Conditions

6.8.2 Duct Insulation Tables 6.8.3 Piping Insulation Tables. Hot-water heating, steam heating, and steam condensate piping shall be insulated to the minimum thickness required in Tables 6.8.3-1 and 6.8.3-2 and shall either utilize insulation within the thermal conductivity ranges in the tables, or, when the insulation thermal conductivity is not within the range in the tables, the following equation shall be used to calculate the minimum insulation thickness:

t alt = r [(1 + ttable / r ) × kalt / kupper - 1]

where talt = minimum insulation thickness of the alternate material, in. r = actual outside radius of pipe, in. ttable = insulation thickness listed in Table 6.8.3-1 or Table 6.8.3-2 for applicable fluid temperature and pipe size kalt = thermal conductivity of the alternate material at mean rating temperature indicated for the applicable fluid temperature, Btu·in/h·ft [2] ·°F kupper = upper value of the thermal conductivity range listed in this table for the applicable fluid temperature, Btu·in/h·ft [2] ·°F Exception to 6.8.3: For nonmetallic piping thicker than Schedule 80 and having thermal resistance

greater than that of steel pipe, reduced insulation thicknesses are permitted if documentation is pro

106 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 109

Open page note

vided showing that the pipe with the proposed insulation has no more heat transfer per foot than a steel pipe of the same size with the insulation thickness shown in the tables.

6.9 Verification, Testing, and Commissioning 6.9.1 Verification and Testing. HVAC control systems shall be tested in accordance with this section and Section 4.2.5.1. Testing shall verify that systems and control elements are calibrated, adjusted, configured, and operating in accordance with applicable requirements of Sections 6.3, 6.4, and 6.5. FPT and verification documentation shall comply with Section 4.2.5.1.2.

6.9.2 Commissioning. The performance of the mechanical systems shall be commissioned in accordance with Section 4.2.5.2. Commissioning reporting shall comply with Section 4.2.5.2.2.

Informative Note: See Informative Appendix E for commissioning references.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 107

PDF Page 110

Open page note

Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Efficiency Requirements

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedurea
Air conditioners,
air cooled
<65,000 Btu/hbAllSplit_system_, three
phase and applications
outside U.S. single
phase b
13.0_SEER_
before 1/1/2023
13.4_SEER2_
after 1/1/2023
AHRI210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air conditioners,
air cooled
<65,000 Btu/hbAllSingle-package, three
phase and applications
outside U.S. single
phase b
14.0_SEER_
before 1/1/2023
13.4_SEER2_
after 1/1/2023
14.0_SEER_
before 1/1/2023
13.4_SEER2_
after 1/1/2023
Space constrained,
air cooled
30,000 Btu/hbAllSplit_system_, three
phase and applications
outside U.S. single
phase b
12.0_SEER_
before 1/1/2023
11.7_SEER2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Space constrained,
air cooled
30,000 Btu/hbAllSingle package, three
phase and applications
outside U.S. single
phase b
12.0_SEER_
before 1/1/2023
11.7_SEER2_
after 1/1/2023
12.0_SEER_
before 1/1/2023
11.7_SEER2_
after 1/1/2023
Small duct,
high velocity,
air cooled
<65,000 Btu/hbAllSplit_system_, three
phase and applications
outside U.S. single
phase b
12.0_SEER_
before 1/1/2023
12.0_SEER2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air conditioners,
air cooled
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
Split_system_ and
single package
11.2_EER_
12.9_IEER_
before 1/1/2023
14.8_IEER_
after 1/1/2023
AHRI 340/360
Air conditioners,
air cooled
65,000 Btu/h and
<135,000 Btu/h
All otherAll other11.0_EER_
12.7_IEER_
before 1/1/2023
14.6_IEER_
after 1/1/2023
11.0_EER_
12.7_IEER_
before 1/1/2023
14.6_IEER_
after 1/1/2023
Air conditioners,
air cooled
135,000 Btu/h and
<240,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
11.0_EER_
12.4_IEER_
before 1/1/2023
14.2_IEER_
after 1/1/2023
11.0_EER_
12.4_IEER_
before 1/1/2023
14.2_IEER_
after 1/1/2023
Air conditioners,
air cooled
135,000 Btu/h and
<240,000 Btu/h
All otherAll other10.8_EER_
12.2_IEER_
before 1/1/2023
14.0_IEER_
after 1/1/2023
10.8_EER_
12.2_IEER_
before 1/1/2023
14.0_IEER_
after 1/1/2023

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled air conditioners <65,000 Btu/h are regulated as consumer products by the U.S. Code of Federal Regulations 10 CFR 430. SEER and SEER2 values

for single-phase products are set by the U.S. Department of Energy. Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum efficiency requirements of single-phase air conditioners for U.S. applications.

108 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 111

Open page note

Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedurea
Air conditioners,
air cooled (continued)
240,000 Btu/h and
<760,000 Btu/h
Electric resistance
(or none)
Split_system_ and
single package
10.0_EER_
11.6_IEER_
before 1/1/2023
13.2_IEER_
after 1/1/2023
AHRI 340/360
Air conditioners,
air cooled (continued)
240,000 Btu/h and
<760,000 Btu/h
All otherAll other9.8_EER_
11.4_IEER_
before 1/1/2023
13.0_IEER_
after 1/1/2023
9.8_EER_
11.4_IEER_
before 1/1/2023
13.0_IEER_
after 1/1/2023
Air conditioners,
air cooled (continued)
760,000 Btu/hElectric resistance
(or none)
Electric resistance
(or none)
9.7_EER_
11.2_IEER_
before 1/1/2023
12.5_IEER_
after 1/1/2023
9.7_EER_
11.2_IEER_
before 1/1/2023
12.5_IEER_
after 1/1/2023
Air conditioners,
air cooled (continued)
760,000 Btu/hAll otherAll other9.5_EER_
11.0_IEER_
before 1/1/2023
12.3_IEER_
after 1/1/2023
9.5_EER_
11.0_IEER_
before 1/1/2023
12.3_IEER_
after 1/1/2023
Air conditioners,
water cooled
<65,000 Btu/hAllSplit_system_ and
single package
12.1_EER_
12.3_IEER_
AHRI 210/240
Air conditioners,
water cooled
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.1_EER_
13.9_IEER_
AHRI 340/360
Air conditioners,
water cooled
65,000 Btu/h and
<135,000 Btu/h
All otherAll other11.9_EER_
13.7_IEER_
11.9_EER_
13.7_IEER_
Air conditioners,
water cooled
135,000 Btu/h and
<240,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.5_EER_
13.9_IEER_
12.5_EER_
13.9_IEER_
Air conditioners,
water cooled
135,000 Btu/h and
<240,000 Btu/h
All otherAll other12.3_EER_
13.7_IEER_
12.3_EER_
13.7_IEER_
Air conditioners,
water cooled
240,000 Btu/h and
<760,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.4_EER_
13.6_IEER_
12.4_EER_
13.6_IEER_
Air conditioners,
water cooled
240,000 Btu/h and
<760,000 Btu/h
All otherAll other12.2_EER_
13.4_IEER_
12.2_EER_
13.4_IEER_
Air conditioners,
water cooled
760,000 Btu/hElectric resistance
(or none)
Electric resistance
(or none)
12.2_EER_
13.5_IEER_
12.2_EER_
13.5_IEER_
Air conditioners,
water cooled
760,000 Btu/hAll otherAll other12.0_EER_
13.3_IEER_
12.0_EER_
13.3_IEER_

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled air conditioners <65,000 Btu/h are regulated as consumer products by the U.S. Code of Federal Regulations 10 CFR 430. SEER and SEER2 values

for single-phase products are set by the U.S. Department of Energy. Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum efficiency requirements of single-phase air conditioners for U.S. applications.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 109

PDF Page 112

Open page note

Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedurea
Air conditioners,
evaporatively cooled
<65,000 Btu/hbAllSplit_system_ and
single package
12.1_EER_
12.3_IEER_
AHRI 210/240
Air conditioners,
evaporatively cooled
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.1_EER_
12.3_IEER_
AHRI 340/360
Air conditioners,
evaporatively cooled
65,000 Btu/h and
<135,000 Btu/h
All otherAll other11.9_EER_
12.1_IEER_
11.9_EER_
12.1_IEER_
Air conditioners,
evaporatively cooled
135,000 Btu/h and
<240,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.0_EER_
12.2_IERR_
12.0_EER_
12.2_IERR_
Air conditioners,
evaporatively cooled
135,000 Btu/h and
<240,000 Btu/h
All otherAll other11.8_EER_
12.0_IEER_
11.8_EER_
12.0_IEER_
Air conditioners,
evaporatively cooled
240,000 Btu/h and
<760,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
11.9_EER_
12.1_IEER_
11.9_EER_
12.1_IEER_
Air conditioners,
evaporatively cooled
240,000 Btu/h and
<760,000 Btu/h
All otherAll other11.7_EER_
11.9_IEER_
11.7_EER_
11.9_IEER_
Air conditioners,
evaporatively cooled
760,000 Btu/hElectric resistance
(or none)
Electric resistance
(or none)
11.7_EER_
11.9_IEER_
11.7_EER_
11.9_IEER_
Air conditioners,
evaporatively cooled
760,000 Btu/hAll otherAll other11.5_EER_
11.7_IEER_
11.5_EER_
11.7_IEER_
Condensing units,
air cooled
135,000 Btu/h10.5_EER_
11.8_IEER_
AHRI 365
Condensing units,
water cooled
135,000 Btu/h13.5_EER_
14.0_IEER_
AHRI 365
Condensing units,
evaporatively cooled
135,000 Btu/h13.5_EER_
14.0_IEER_
AHRI 365

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled air conditioners <65,000 Btu/h are regulated as consumer products by the U.S. Code of Federal Regulations 10 CFR 430. SEER and SEER2 values

for single-phase products are set by the U.S. Department of Energy. Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum efficiency requirements of single-phase air conditioners for U.S. applications.

110 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 113

Open page note

Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency Requirements

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedurea
Air cooled
(cooling mode)
<65,000 Btu/hAllSplit_system_, three
phase and
applications outside
U.S. single phase b
14.0_SEER_
before 1/1/2023
14.3_SEER2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air cooled
(cooling mode)
<65,000 Btu/hAllSingle package, three
phase and
applications outside
U.S. single phase b
14.0_SEER_
before 1/1/2023
13.4_SEER2_
after 1/1/2023
14.0_SEER_
before 1/1/2023
13.4_SEER2_
after 1/1/2023
Space constrained,
air cooled
(cooling mode)
30,000 Btu/hAllSplit_system_, three
phase and
applications outside
U.S. single phase b
12.0_SEER_
before 1/1/2023
11.7_SEER2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Space constrained,
air cooled
(cooling mode)
30,000 Btu/hAllSingle package, three
phase and
applications outside
U.S. single phase b
12.0_SEER_
before 1/1/2023
11.7_SEER2_
after 1/1/2023
12.0_SEER_
before 1/1/2023
11.7_SEER2_
after 1/1/2023
Small duct, high
velocity, air cooled
(cooling mode)
<65,000 Btu/hAllSplit_System_, three
phase and
applications outside
U.S. single phase b
12.0_SEER_
before 1/1/2023
12.0_SEER2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
Split_system_ and
single package
11.0_EER_
12.2_IEER_
before 1/1/2023
14.1_IEER_
after 1/1/2023
AHRI 340/360
Air cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
All otherAll other10.8_EER_
12.0_IEER_
before 1/1/2023
13.9_IEER_
after 1/1/2023
10.8_EER_
12.0_IEER_
before 1/1/2023
13.9_IEER_
after 1/1/2023
Air cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
10.6_EER_
11.6_IEER_
before 1/1/2023
13.5_IEER_
after 1/1/2023
10.6_EER_
11.6_IEER_
before 1/1/2023
13.5_IEER_
after 1/1/2023
Air cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
All otherAll other10.4_EER_
11.4_IEER_
before 1/1/2023
13.3_IEER_
after 1/1/2023
10.4_EER_
11.4_IEER_
before 1/1/2023
13.3_IEER_
after 1/1/2023
Air cooled
(cooling mode)
240,000 Btu/hElectric resistance
(or none)
Electric resistance
(or none)
9.5_EER_
10.6_IEER_
before 1/1/2023
12.5_IEER_
after 1/1/2023
9.5_EER_
10.6_IEER_
before 1/1/2023
12.5_IEER_
after 1/1/2023
Air cooled
(cooling mode)
240,000 Btu/hAll otherAll other9.3_EER_
10.4_IEER_
before 1/1/2023
12.3_IEER_
after 1/1/2023
9.3_EER_
10.4_IEER_
before 1/1/2023
12.3_IEER_
after 1/1/2023

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled heat pumps <65,000 Btu/h are regulated as consumer products by the U.S. Code of Federal Regulations 10 CFR 430. SEER, SEER2, and HSPF values

for single-phase products are set by the U.S. Department of Energy. Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 111

PDF Page 114

Open page note

Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedurea
Air cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Split_system_, three
phase and
applications outside
U.S. single phase b
8.2_HSPF_
before 1/1/2023
7.5_HSPF2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Single package, three
phase and
applications outside
U.S. single phase b
8.0_HSPF_
before 1/1/2023
6.7_HSPF2_
after 1/1/2023
8.0_HSPF_
before 1/1/2023
6.7_HSPF2_
after 1/1/2023
Space constrained,
air cooled
(heating mode)
30,000 Btu/h
(cooling capacity)
Split_system_, three
phase and
applications outside
U.S. single phase b
7.4_HSPF_
before 1/1/2023
6.3_HSPF2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Space constrained,
air cooled
(heating mode)
30,000 Btu/h
(cooling capacity)
Single package, three
phase and
applications outside
U.S. single phase b
7.4_HSPF_
before 1/1/2023
6.3_HSPF2_
after 1/1/2023
7.4_HSPF_
before 1/1/2023
6.3_HSPF2_
after 1/1/2023
Small duct high
velocity, air cooled
(heating mode)
<65,000 Btu/hSplit_system_, three
phase and
applications outside
U.S. single phase b
7.2_HSPF_
before 1/1/2023
6.1_HSPF2_
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.30_COPH_
before 1/1/2023
3.40_COPH_
after 1/1/2023
AHRI 340/360
Air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.25_COPH_2.25_COPH_
Air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
47°F db/43°F wb
outdoor air
3.20_COPH_
before 1/1/2023
3.30_COPH_
after 1/1/2023
3.20_COPH_
before 1/1/2023
3.30_COPH_
after 1/1/2023
Air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
135,000 Btu/h
(cooling capacity)
and <240,000 Btu/h
17°F db/15°F wb
outdoor air
2.05_COPH_2.05_COPH_
Air cooled
(heating mode)
240,000 Btu/h
(cooling capacity)
240,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.20_COPH_3.20_COPH_
Air cooled
(heating mode)
240,000 Btu/h
(cooling capacity)
240,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.05_COPH_2.05_COPH_

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled heat pumps <65,000 Btu/h are regulated as consumer products by the U.S. Code of Federal Regulations 10 CFR 430. SEER, SEER2, and HSPF values

for single-phase products are set by the U.S. Department of Energy. Informative Note: See Informative Appendix F for the U.S. Department of Energy minimum.

112 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 115

Open page note

Table 6.8.1-3 Liquid-Chilling Packages—Minimum Efficiency Requirements [a,b,e]

Equipment TypeSize CategoryUnitsPath APath BTest Procedurec
Air-cooled<150 tonsEER(Btu/Wh)10.100 FL9.700 FLAHRI 550/590
Air-cooled<150 tonsEER(Btu/Wh)13.700_ IPLV_.IP15.800_IPLV_.IP15.800_IPLV_.IP
Air-cooled150 tons150 tons10.100 FL9.700 FL9.700 FL
Air-cooled150 tons150 tons14.000_IPLV_.IP16.100_IPLV_.IP16.100_IPLV_.IP
Air-cooled without
condenser, electrically
operated
All capacitiesEER(Btu/Wh)Air-cooled without condenser must be rated
with matching condensers and comply with
air-cooled chiller_efficiency_ requirements.
Air-cooled without condenser must be rated
with matching condensers and comply with
air-cooled chiller_efficiency_ requirements.
AHRI 550/590
Liquid-cooled,
electrically operated
positive displacement
<75 tonskW/ton0.750 FL0.780 FLAHRI 550/590
Liquid-cooled,
electrically operated
positive displacement
<75 tonskW/ton0.600_IPLV_.IP0.500_IPLV_.IP0.500_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
75 tons and
<150 tons
75 tons and
<150 tons
0.720 FL0.750 FL0.750 FL
Liquid-cooled,
electrically operated
positive displacement
75 tons and
<150 tons
75 tons and
<150 tons
0.560_IPLV_.IP0.490_IPLV_.IP0.490_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
150 tons and
<300 tons
150 tons and
<300 tons
0.660 FL0.680 FL0.680 FL
Liquid-cooled,
electrically operated
positive displacement
150 tons and
<300 tons
150 tons and
<300 tons
0.540_IPLV_.IP0.440_IPLV_.IP0.440_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
300 tons and
<600 tons
300 tons and
<600 tons
0.610 FL0.625 FL0.625 FL
Liquid-cooled,
electrically operated
positive displacement
300 tons and
<600 tons
300 tons and
<600 tons
0.520_IPLV_.IP0.410_IPLV_.IP0.410_IPLV_.IP
Liquid-cooled,
electrically operated
positive displacement
600 tons600 tons0.560 FL0.585 FL0.585 FL
Liquid-cooled,
electrically operated
positive displacement
600 tons600 tons0.500_IPLV_.IP0.380_IPLV_.IP0.380_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
<150 tonskW/ton0.610 FL0.695 FLAHRI 550/590
Liquid-cooled,
electrically operated
centrifugal
<150 tonskW/ton0.550_IPLV_.IP0.440_IPLV_.IP0.440_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
150 tons and
<300 tons
150 tons and
<300 tons
0.610 FL0.635 FL0.635 FL
Liquid-cooled,
electrically operated
centrifugal
150 tons and
<300 tons
150 tons and
<300 tons
0.550_IPLV_.IP0.400_IPLV_.IP0.400_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
300 tons and
<400 tons
300 tons and
<400 tons
0.560 FL0.595 FL0.595 FL
Liquid-cooled,
electrically operated
centrifugal
300 tons and
<400 tons
300 tons and
<400 tons
0.520_IPLV_.IP0.390_IPLV_.IP0.390_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
400 tons and
<600 tons
400 tons and
<600 tons
0.560 FL0.585 FL0.585 FL
Liquid-cooled,
electrically operated
centrifugal
400 tons and
<600 tons
400 tons and
<600 tons
0.500_IPLV_.IP0.380_IPLV_.IP0.380_IPLV_.IP
Liquid-cooled,
electrically operated
centrifugal
600 tons600 tons0.560 FL0.585 FL0.585 FL
Liquid-cooled,
electrically operated
centrifugal
600 tons600 tons0.500_IPLV_.IP0.380_IPLV_.IP0.380_IPLV_.IP
Air-cooled absorption,
single effect
All capacitiesCOP (W/W)0.600 FLNAdAHRI 560
Liquid-cooled
absorption,
single effect
All capacitiesCOP (W/W)0.700 FLNAdAHRI 560
Absorption double
effect, indirect fired
All capacitiesCOP (W/W)1.000 FLNAdAHRI 560
Absorption double
effect, indirect fired
All capacitiesCOP (W/W)1.050_IPLV_.IP1.050_IPLV_.IP1.050_IPLV_.IP
Absorption double
effect,
direct fired
All capacitiesCOP (W/W)1.000 FLNAdAHRI 560
Absorption double
effect,
direct fired
All capacitiesCOP (W/W)1.000_IPLV_1.000_IPLV_1.000_IPLV_

a. The requirements for centrifugal chilling packages shall be adjusted for nonstandard rating conditions per Section 6.4.1.2.1 and are only applicable for the range of conditions listed

there. The requirements for air-cooled, liquid-cooled positive displacement and absorption chilling packages are at standard rating conditions defined in the reference test procedure. b. Both the full-load and IPLV .IP requirements must be met or exceeded to comply with this standard. When there is a Path B, compliance can be with either Path A or Path B for

any application. c. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. d. NA means the requirements are not applicable for Path B, and only Path A can be used for compliance. e. FL is the full-load performance requirements, and IPLV .IP is for the part-load performance requirements. f. Electrically operated chilling packages employing a freeze-protection liquid in accordance with Section 6.4.1.2.2 shall be tested or rated with water for the purpose of compliance

with the requirements of this table.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 113

PDF Page 116

Open page note

Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single- Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air- Conditioner Heat Pumps—Minimum Efficiency Requirements

Equipment TypeSize
Category (Input)
Subcategory or
Rating Condition
Minimum EfficiencydTest Procedurea
PTAC (cooling mode)
standard size
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
11.9_EER_
AHRI 310/380
PTAC (cooling mode)
standard size
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
14.0 – (0.300 × Cap/1000)_EER_e14.0 – (0.300 × Cap/1000)_EER_e
PTAC (cooling mode)
standard size
>15,000 Btu/h>15,000 Btu/h9.5_EER_9.5_EER_
PTAC (cooling mode)
nonstandard sizeb
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
9.4_EER_
AHRI 310/380
PTAC (cooling mode)
nonstandard sizeb
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
10.9 – (0.213 × Cap/1000)_EER_e10.9 – (0.213 × Cap/1000)_EER_e
PTAC (cooling mode)
nonstandard sizeb
>15,000 Btu/h>15,000 Btu/h7.7_EER_7.7_EER_
PTHP (cooling mode)
standard size
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
11.9_EER_
AHRI 310/380
PTHP (cooling mode)
standard size
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
14.0 – (0.300 × Cap/1000)_EER_e14.0 – (0.300 × Cap/1000)_EER_e
PTHP (cooling mode)
standard size
>15,000 Btu/h>15,000 Btu/h9.5_EER_9.5_EER_
PTHP (cooling mode)
nonstandard sizeb
<7000 Btu/h95°F db/75°F wb
_outdoor air_c
9.3_EER_
AHRI 310/380
PTHP (cooling mode)
nonstandard sizeb
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
10.8 – (0.213 × Cap/1000)_EER_e10.8 – (0.213 × Cap/1000)_EER_e
PTHP (cooling mode)
nonstandard sizeb
>15,000 Btu/h>15,000 Btu/h7.6_EER_7.6_EER_
PTHP (heating mode)
standard size
<7000 Btu/h47°F db/43°F wb
outdoor air
3.3_COPH_
AHRI 310/380
PTHP (heating mode)
standard size
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
3.7 – (0.052 × Cap/1000)COPH
e
3.7 – (0.052 × Cap/1000)COPH
e
PTHP (heating mode)
standard size
>15,000 Btu/h>15,000 Btu/h2.90_COPH_2.90_COPH_
PTHP (heating mode)
nonstandard sizeb
<7000 Btu/h47°F db/43°F wb
outdoor air
2.7_COPH_
AHRI 310/380
PTHP (heating mode)
nonstandard sizeb
7000 Btu/h and
15,000 Btu/h
7000 Btu/h and
15,000 Btu/h
2.9 – (0.026 × Cap/1000)COPH
e
2.9 – (0.026 × Cap/1000)COPH
e
PTHP (heating mode)
nonstandard sizeb
>15,000 Btu/h>15,000 Btu/h2.5_COPH_2.5_COPH_
SPVAC (cooling mode)
single and three phase
<65,000 Btu/h95°F db/75°F wb
_outdoor air_c
11.0_EER_AHRI 390
SPVAC (cooling mode)
single and three phase
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
10.0_EER_10.0_EER_
SPVAC (cooling mode)
single and three phase
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
10.0_EER_10.0_EER_
SPVHP (cooling mode)<65,000 Btu/h95°F db/75°F wb
_outdoor air_c
11.0_EER_AHRI 390
SPVHP (cooling mode)65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
10.0_EER_
SPVHP (cooling mode)135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
10.0_EER_
SPVHP (heating mode)<65,000 Btu/h47°F db/43°F wb
outdoor air
3.3_COPH_AHRI 390
SPVHP (heating mode)65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
3.0_COPH_3.0_COPH_
SPVHP (heating mode)135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
3.0_COPH_3.0_COPH_

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Nonstandard size units must be factory labeled as follows: “MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS.” Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in. [2] . c. The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil. d. Room air conditioners are regulated as consumer products by 10 CFR 430. For U.S. applications of room air conditioners, refer to Informative Appendix F, Table F-3, for the

U.S. DOE minimum efficiency requirements for U.S. applications. e. “Cap” in EER and COPH equations for PTAC s and PTHP s means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.

114 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 117

Open page note

Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single- Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air- Conditioner Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize
Category (Input)
Subcategory or
Rating Condition
Minimum EfficiencydTest Procedurea
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
<6000 Btu/h11.0_CEER_ANSI/AHAM
RAC-1
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
6000 Btu/h and
<8000 Btu/h
6000 Btu/h and
<8000 Btu/h
11.0_CEER_11.0_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
8000 Btu/h and
<14,000 Btu/h
8000 Btu/h and
<14,000 Btu/h
10.9_CEER_10.9_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
14,000 Btu/h and
<20,000 Btu/h
14,000 Btu/h and
<20,000 Btu/h
10.7_CEER_10.7_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
20,000 Btu/h and
<28,000 Btu/h
20,000 Btu/h and
<28,000 Btu/h
9.4_CEER_9.4_CEER_
Room air conditioners without reverse
cycle with louvered sides for
applications outside U.S. d
28,000 Btu/h28,000 Btu/h9.0_CEER_9.0_CEER_
Room air conditioners
without louvered sides
<6000 Btu/h<6000 Btu/h10.0_CEER_ANSI/AHAM
RAC-1
Room air conditioners
without louvered sides
6000 Btu/h and
<8000 Btu/h
6000 Btu/h and
<8000 Btu/h
10.0_CEER_10.0_CEER_
Room air conditioners
without louvered sides
8000 Btu/h and
<11,000 Btu/h
8000 Btu/h and
<11,000 Btu/h
9.6_CEER_9.6_CEER_
Room air conditioners
without louvered sides
11,000 Btu/h and
<14,000 Btu/h
11,000 Btu/h and
<14,000 Btu/h
9.5_CEER_9.5_CEER_
Room air conditioners
without louvered sides
14,000 Btu/h and
<20,000 Btu/h
14,000 Btu/h and
<20,000 Btu/h
9.3_CEER_9.3_CEER_
Room air conditioners
without louvered sides
20,000 Btu/h20,000 Btu/h9.4_CEER_9.4_CEER_
Room air conditioners with reverse
cycle, with louvered sides for
applications outside U.S. d
<20,000 Btu/h<20,000 Btu/h9.8_CEER_ANSI/AHAM
RAC-1
Room air conditioners with reverse
cycle, with louvered sides for
applications outside U.S. d
20,000 Btu/h20,000 Btu/h9.3_CEER_9.3_CEER_
Room air conditioners with reverse
cycle without louvered sides for
applications outside U.S. d
<14,000 Btu/h<14,000 Btu/h9.3_CEER_ANSI/AHAM
RAC-1
Room air conditioners with reverse
cycle without louvered sides for
applications outside U.S. d
14,000 Btu/h14,000 Btu/h8.7_CEER_8.7_CEER_
Room air conditioners, casement only
for applications outside U.S. d
AllAll9.5_CEER_ANSI/AHAM
RAC-1
Room air conditioners, casement
slider for applications outside U.S. d
AllAll10.4_CEER_ANSI/AHAM
RAC-1

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Nonstandard size units must be factory labeled as follows: “MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS.” Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in. [2] . c. The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil. d. Room air conditioners are regulated as consumer products by 10 CFR 430. For U.S. applications of room air conditioners, refer to Informative Appendix F, Table F-3, for the

U.S. DOE minimum efficiency requirements for U.S. applications. e. “Cap” in EER and COPH equations for PTAC s and PTHP s means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 115

PDF Page 118

Open page note

Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct

Furnaces, and Unit Heaters—Minimum Efficiency RequirementsCol2Col3Col4Col5Col6Col7Col8Col9
Equipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeMinimum
Efficiency b
Test
Procedure a
DescriptionFuelElectric
Power Phase
Application
Location
Heating
Capacity
(input),
Btu/h b
Combo-Unit
Cooling
Capacity,
Btu/h
SubtypeSubtypeSubtype
Warm-air
furnace
Gas1Inside U.S.<225,000<65,000See Informative Appendix F, Table F-4f
See Informative Appendix F, Table F-4f
See Informative Appendix F, Table F-4f
Warm-air
furnace
Gas1Inside U.S.<225,000≥65,000Nonweatherized80%AFUEAppendix N g
Warm-air
furnace
Gas1Inside U.S.<225,000≥65,000Weatherized81%AFUE or
80%Et
c
Appendix N g
Warm-air
furnace
Gas1Inside U.S.<225,000≥65,000Weatherized81%AFUE or
80%Et
c
ANSI Z21.47
Warm-air
furnace
Gas1Outside U.S.<225,000AllNonweatherized80%AFUEAppendix N g
Warm-air
furnace
Gas1Outside U.S.<225,000AllWeatherized81%_AFUE_or
80%Et
c
Appendix N g
Warm-air
furnace
Gas1Outside U.S.<225,000AllWeatherized81%_AFUE_or
80%Et
c
ANSI Z21.47
Warm-air
furnace
Gas3All<225,000AllNonweatherized80%AFUEAppendix N g
Warm-air
furnace
Gas3All<225,000AllWeatherized81%_AFUE_or
80%Et
c
Appendix N g
Warm-air
furnace
Gas3All<225,000AllWeatherized81%_AFUE_or
80%Et
c
ANSI Z21.47
Warm-air
furnace
GasAllAll≥ 225,000 and
≤ 400,000
AllAll80%Et
c
before 1/1/2023
81%Et
c
after 1/1/2023
ANSI Z21.47
Warm-air
furnace
GasAllInside U.S.> 400,000AllAll80%Et
c
before 1/1/2023
81%Et
c
after 1/1/2023
ANSI Z21.47
Warm-air
furnace
GasAllOutside U.S.> 400,000AllAll
80%Et
c
before 1/1/2023
81%Et
c
after 1/1/2023
ANSI Z21.47
or
ANSI Z83.8
Warm-air
furnace
Oil1Inside U.S.<225,000<65,000See Informative Appendix F, Table F-4 f
See Informative Appendix F, Table F-4 f
See Informative Appendix F, Table F-4 f
Warm-air
furnace
Oil1Inside U.S.<225,000≥65,000Nonweatherized83%AFUEAppendix N g
Warm-air
furnace
Oil1Inside U.S.<225,000≥65,000Weatherized78%AFUE or
80%Et
d
Appendix N g
Warm-air
furnace
Oil1Inside U.S.<225,000≥65,000Weatherized78%AFUE or
80%Et
d
Section 42
UL 727
Warm-air
furnace
Oil1Outside U.S.<225,000AllNonweatherized83%AFUEAppendix N g
Warm-air
furnace
Oil1Outside U.S.<225,000AllWeatherized78%AFUE or
80%_Et _
d
Appendix N g
Warm-air
furnace
Oil1Outside U.S.<225,000AllWeatherized78%AFUE or
80%_Et _
d
Section 42
UL 727

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. For this table, the following applies:

  • Appendix N = 10 CFR 430 Appendix N

  • ANSI Z21.47 = Section 2.39, Thermal Efficiency, ANSI Z21.47

  • ANSI Z83.3 = Section 2.10, Efficiency, ANSI Z83.3

  • UL 727 = Section 42, Combustion, UL 727

  • UL 731 = Section 40, Combustion, UL 731 b. Compliance of multiple firing rate units shall be at the maximum firing rate. c. Et = thermal efficiency . Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating, and have either

power venting or a flue damper . A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space . d. Ec = combustion efficiency (100% less flue losses). See test procedure for detailed discussion. e. Units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper . f. Includes combination units with cooling capacity <65,000 Btu/h. For U.S. applications of federally covered <225,000 Btu/h products, see Informative Appendix F, Table F-4. g. 10 CFR 430 is limited to-single phase equipment that is not contained within the same cabinet with a central air conditioner whose rated cooling capacity is above 65,000 Btu/

h but for the test and rating procedures are not impacted for three-phase and can be used for AFUE ratings for ASHRAE/IES Standard 90.1 three-phase products and single-phase products with a cooling capacity greater than 65,000 Btu/h.

116 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 119

Open page note

Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct

Furnaces, and Unit Heaters—Minimum Efficiency Requirements (Continued)Col2Col3Col4Col5Col6Col7Col8Col9
Equipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeEquipment TypeMinimum
Efficiency b

Test
Procedure a
DescriptionFuelElectric
Power Phase
Application
Location
Heating
Capacity
(input),
Btu/h b
Combo-Unit
Cooling
Capacity,
Btu/h
SubtypeSubtypeSubtype
Warm-air
furnace
Oil3All<225,000AllNonweatherized83%AFUEAppendix N g
Warm-air
furnace
Oil3All<225,000AllWeatherized78%AFUE or
80%Et
d
Appendix N g
Warm-air
furnace
Oil3All<225,000AllWeatherized78%AFUE or
80%Et
d
Section 42
UL 727
Warm-air
furnace
OilAllAll≥225,000AllAll
81%Et
d
before 1/1/2023
82%Et
d
after 1/1/2023
Section 42
UL 727
Warm-air
furnace
Electric1Inside U.S.<225,000<65,000See Informative Appendix F, Table F-4 f
See Informative Appendix F, Table F-4 f
See Informative Appendix F, Table F-4 f
Warm-air
furnace
Electric1Inside U.S.<225,000≥65,000All96%AFUEAppendix N g
Warm-air
furnace
Electric1Outside U.S.<225,000AllAll96%AFUEAppendix N g
Warm-air
furnace
Electric3All<225,000AllAll96%AFUE
Appendix N g
Warm-air
duct furnaces
GasAllAllAllAllAll80%Ec
d
ANSI Z83.8
Warm-air
unit heaters
GasAllAllAllAllAll80%Ec
d,e
ANSI Z83.8
Warm-air
unit heaters
OilAllAllAllAllAll80%Ec
d,e
Section 40
UL 731

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. For this table, the following applies:

  • Appendix N = 10 CFR 430 Appendix N

  • ANSI Z21.47 = Section 2.39, Thermal Efficiency, ANSI Z21.47

  • ANSI Z83.3 = Section 2.10, Efficiency, ANSI Z83.3

  • UL 727 = Section 42, Combustion, UL 727

  • UL 731 = Section 40, Combustion, UL 731 b. Compliance of multiple firing rate units shall be at the maximum firing rate. c. Et = thermal efficiency . Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating, and have either

power venting or a flue damper . A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space . d. Ec = combustion efficiency (100% less flue losses). See test procedure for detailed discussion. e. Units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper . f. Includes combination units with cooling capacity <65,000 Btu/h. For U.S. applications of federally covered <225,000 Btu/h products, see Informative Appendix F, Table F-4. g. 10 CFR 430 is limited to-single phase equipment that is not contained within the same cabinet with a central air conditioner whose rated cooling capacity is above 65,000 Btu/

h but for the test and rating procedures are not impacted for three-phase and can be used for AFUE ratings for ASHRAE/IES Standard 90.1 three-phase products and single-phase products with a cooling capacity greater than 65,000 Btu/h.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 117

PDF Page 120

Open page note

Table 6.8.1-6 Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements

Equipment Type aSubcategory or
Rating Condition
Size Category
(Input)
Minimum
Efficiency i
Efficiency as of
3/2/2022
Test Procedure
Boilers,
hot water
Gas fired h<300,000 Btu/h f,g for
applications outside
U.S. i
82%AFUE82%AFUE10 CFR 430
Appendix N
Boilers,
hot water
Gas fired h300,000 Btu/h and
2,500,000 Btu/hd
80%Et
c
80%Et
c
10 CFR 431.86
Boilers,
hot water
Gas fired h>2,500,000 Btu/h d82%Ec
b
82%Ec
b
82%Ec
b
Boilers,
hot water
Oil fired e<300,000 Btu/h f,g for
applications outside
U.S. i
84%AFUE84%AFUE10 CFR 430
Appendix N
Boilers,
hot water
Oil fired e300,000 Btu/h and
2,500,000 Btu/hd
82%Et
c
82%Et
c
10 CFR 431.86
Boilers,
hot water
Oil fired e>2,500,000 Btu/h d84%Ec
b
84%Ec
b
84%Ec
b
Boilers,
steam
Gas fired<300,000 Btu/hf for
applications outside
U.S. i
80%AFUE80%AFUE10 CFR 430
Appendix N
Boilers,
steam
Gas fired—
all, except
natural draft
300,000 Btu/h and
2,500,000 Btu/hd
79%Et
c
79%Et
c
10 CFR 431.86
Boilers,
steam
Gas fired—
all, except
natural draft
>2,500,000 Btu/h d79%Et
c
79%Et
c
79%Et
c
Boilers,
steam
Gas fired—
natural draft
300,000 Btu/h and
2,500,000 Btu/hd
77%Et
c
79%Et
c
79%Et
c
Boilers,
steam
Gas fired—
natural draft
>2,500,000 Btu/h d77%Et
c
79%Et
c
79%Et
c
Boilers,
steam
Oil fired e<300,000 Btu/h f for
applications outside
U.S. i
82%AFUE82%AFUE10 CFR 430
Appendix N
Boilers,
steam
Oil fired e300,000 Btu/h and
2,500,000 Btu/hd
81%Et
c
81%Et
c
10 CFR 431.86
Boilers,
steam
Oil fired e>2,500,000 Btu/h d81%Et
c
81%Et
c
81%Et
c

a. These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers . Minimum efficiency requirements for

boilers cover all capacities of packaged boilers . b. Ec = combustion efficiency (100% less flue losses). See reference document for detailed information. c. Et = thermal efficiency . See reference document for detailed information. d. Maximum capacity—minimum and maximum ratings as provided for and allowed by the unit’s controls. e. Includes oil-fired (residual). f. Boilers shall not be equipped with a constant burning pilot light. g. A boiler not equipped with a tankless domestic water-heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental

change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied. h. For new construction, refer to Section 6.4.1.1 for additional system compliance requirements. i. See Informative Appendix F, Table F-4, for U.S. minimum efficiencies for residential products covered by U.S. DOE requirements for U.S. applications.

118 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 121

Open page note

Table 6.8.1-7 Performance Requirements for Heat Rejection Equipment—Minimum Efficiency Requirements

Equipment TypeTotal System
Heat-Rejection Capacity
at Rated Conditions
Subcategory or
Rating Condition h
Performance
Required a,b,c,f,g
Test Procedure d,e
Propeller or axial fan
open-circuit cooling
towers
All95°F entering water
85°F leaving water
75°F entering wb
40.2 gpm/hpCTI ATC-105 and
CTI STD-201 RS
Centrifugal fan
open-circuit cooling
towers
All95°F entering water
85°F leaving water
75°F entering wb
20.0 gpm/hpCTI ATC-105 and
CTI STD-201 RS
Propeller or axial fan
closed-circuit cooling
towers
All102°F entering water
90°F leaving water
75°F entering wb
16.1 gpm/hpCTI ATC-105S and
CTI STD-201 RS
Centrifugal fan closed-
circuit cooling towers
All102°F entering water
90°F leaving water
75°F entering wb
7.0 gpm/hpCTI ATC-105S and
CTI STD-201 RS
Propeller or axial fan
dry coolers
(air-cooled fluid coolers)
All115°F entering water
105°F leaving water
95°F entering db
4.5 gpm/hpCTI ATC-105DS
Propeller or axial fan
evaporative condensers
AllR-448A test fluid
165°F entering gas temperature
105°F condensing temperature
75°F entering wb
160,000 Btu/h·hpCTI ATC-106
Propeller or axial fan
evaporative condensers
AllAmmonia test fluid
140°F entering gas temperature
96.3°F condensing temperature
75°F entering wb
134,000 Btu/h·hpCTI ATC-106
Centrifugal fan
evaporative condensers
AllR-448A test fluid
165°F entering gas temperature
105°F condensing temperature
75°F entering wb
137,000 Btu/h·hpCTI ATC-106
Centrifugal fan
evaporative condensers
AllAmmonia test fluid
140°F entering gas temperature
96.3°F condensing temperature
75°F entering wb
110,000 Btu/h·hpCTI ATC-106
Air-cooled condensersAll125°F condensing temperature
190°F entering gas temperature
15°F subcooling
95°F entering db
176,000 Btu/h·hpAHRI 460

a. For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the thermal rating condition listed in Table 6.8.1-7 divided

by the fan motor nameplate power. b. For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the thermal rating condition listed in Table 6.8.1-7

divided by the sum of the fan motor nameplate power and the integral spray pump motor nameplate power. c. For purposes of this table, dry-cooler performance is defined as the process water flow rating of the unit at the thermal rating condition listed in Table 6.8.1-7 divided by the total

fan motor nameplate power of the unit, and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the total fan motor nameplate power of the unit. d. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. e. The efficiencies and test procedures for both open- and closed-circuit cooling towers are not applicable to hybrid cooling towers that contain a combination of separate wet and

dry heat exchange sections. The certification requirements do not apply to field-erected cooling towers. f. All cooling towers shall comply with the minimum efficiency listed in the table for that specific type of tower with the capacity effect of any project-specific accessories and/or

options included in the capacity of the cooling tower. g. For purposes of this table, evaporative condenser performance is defined as the heat rejected at the specified rating condition in the table, divided by the sum of the fan motor name plate power and the integral spray pump nameplate power. h. Requirements for evaporative condensers are listed with ammonia (R-717) and R-448A as test fluids in the table. Evaporative condensers intended for use with halocarbon refrig erants other than R-448A must meet the minimum efficiency requirements listed above with R-448A as the test fluid. For ammonia, the condensing temperature is defined as the saturation temperature corresponding to the refrigerant pressure at the condenser entrance. For R-448A, which is a zeotropic refrigerant, the condensing temperature is defined as the arithmetic average of the dew point and the bubble point temperatures corresponding to the refrigerant pressure at the condenser entrance.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 119

PDF Page 122

Open page note

Table 6.8.1-8 Electrically Operated Variable-Refrigerant-Flow Air Conditioners—Minimum Efficiency Requirements

Equipment TypeaSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF air conditioners,
air cooled
<65,000 Btu/h
Three-phase for
applications in the U.S.
and single- and three-
phase for applications
outside the U.S.
AllVRF multisplit_system_13.0_SEER_
Before 1/1/23
SEER2 = 13.4
On or after 1/1/23
AHRI 1230-2014 with
Addendum 1
before 1/1/2023
AHRI 210/240-2023
on or after 1/1/2023
VRF air conditioners,
air cooled
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
VRF multisplit_ system_11.2_EER_
15.5_IEER_
Before 1/1/2024
10.5_EER_
15.5_IEER_
On or after 1/1/24
AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF air conditioners,
air cooled
135,000 Btu/h and
<240,000 Btu/h
Electric resistance
(or none)
VRF multisplit_system_11.0_EER_
14.9_IEER_
Before 1/1/2024
10.3_EER_
14.9_IEER_
On or after 1/1/24
11.0_EER_
14.9_IEER_
Before 1/1/2024
10.3_EER_
14.9_IEER_
On or after 1/1/24
VRF air conditioners,
air cooled
240,000 Btu/hElectric resistance
(or none)
VRF multisplit_system_10.0_EER_
13.9_IEER_
Before 1/1/2024
9.5_EER_
13.9_IEER_
On or after 1/1/24
10.0_EER_
13.9_IEER_
Before 1/1/2024
9.5_EER_
13.9_IEER_
On or after 1/1/24

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF air conditioners, air-cooled systems less than 65,000 Btu/h see Informative Appendix F, Table F-1 for the U.S. Department of Energy mini mum.

120 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 123

Open page note

Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF air cooled
(cooling mode)
<65,000 Btu/h
Three-phase for
applications in the U.S.
and single- and three-
phase for applications
outside the U.S.
AllVRF multisplit_system_13.0_SEER_
Before 1/1/2023
SEER2 = 13.4
On or after 1/1/2023
AHRI 1230-2014 with
Addendum 1
before 1/1/2023
AHRI 210/240-2023
on or after 1/1/2023
VRF air cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
11.0_EER_
14.6_IEER_
Before 1/1/2024
10.3_EER_
14.6_IEER_
On or after 1/1/24
AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF air cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
Electric resistance
(or none)
VRF multisplit_system_
with heat recovery
10.8_EER_
14.4_IEER_
Before 1/1/2024
10.1_EER_
14.4_IEER_
On or after 1/1/24
10.8_EER_
14.4_IEER_
Before 1/1/2024
10.1_EER_
14.4_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_10.6_EER_
13.9_IEER_
Before 1/1/2024
9.9_EER_
13.9_IEER_
On or after 1/1/24
10.6_EER_
13.9_IEER_
Before 1/1/2024
9.9_EER_
13.9_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_
with heat recovery
10.4_EER_
13.7_IEER_
Before 1/1/2024
9.7_EER_
13.7_IEER_
On or after 1/1/24
10.4_EER_
13.7_IEER_
Before 1/1/2024
9.7_EER_
13.7_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_9.5_EER_
12.7_IEER_
Before 1/1/2024
9.1_EER_
12.7_IEER_
On or after 1/1/24
9.5_EER_
12.7_IEER_
Before 1/1/2024
9.1_EER_
12.7_IEER_
On or after 1/1/24
VRF air cooled
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_
with heat recovery
9.3_EER_
12.5_IEER_
Before 1/1/2024
8.9_EER_
12.5_IEER_
On or after 1/1/24
9.3_EER_
12.5_IEER_
Before 1/1/2024
8.9_EER_
12.5_IEER_
On or after 1/1/24

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF multisplit system less than 65,000 Btu/h, see Informative Appendix F, Table F-1 for the U.S. Department of Energy minimum.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 121

PDF Page 124

Open page note

Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF water source
(cooling mode)
<65,000 Btu/hAllVRF multisplit_systems_
86°F entering water
12.0_EER_
16.0_IEER_
AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF water source
(cooling mode)
<65,000 Btu/hAllVRF multisplit_systems_
with heat recovery
86°F entering water
11.8_EER_
15.8_IEER_
11.8_EER_
15.8_IEER_
VRF water source
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
VRF multisplit_system_
86°F entering water
12.0_EER_
16.0_IEER_
12.0_EER_
16.0_IEER_
VRF water source
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
VRF multisplit_system_
with heat recovery
86°F entering water
11.8_EER_
15.8_IEER_
11.8_EER_
15.8_IEER_
VRF water source
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_
86°F entering water
10.0_EER_
14.0_IEER_
10.0_EER_
14.0_IEER_
VRF water source
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
VRF multisplit_system_
with heat recovery
86°F entering water
9.8_EER_
13.8_IEER_
9.8_EER_
13.8_IEER_
VRF water source
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_
86°F entering water
10.0_EER_
12.0_IEER_
10.0_EER_
12.0_IEER_
VRF water source
(cooling mode)
240,000 Btu/h240,000 Btu/hVRF multisplit_system_
with heat recovery
86°F entering water
9.8_EER_
11.8_IEER_
9.8_EER_
11.8_IEER_
VRF groundwater
source (cooling
mode)
<135,000 Btu/hAllVRF multisplit_system_
59°F entering water
16.2_EER_AHRI 1230- 2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF groundwater
source (cooling
mode)
<135,000 Btu/hAllVRF multisplit_system_
with heat recovery
59°F entering water
16.0_EER_16.0_EER_
VRF groundwater
source (cooling
mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
59°F entering water
13.8_EER_13.8_EER_
VRF groundwater
source (cooling
mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
with heat recovery
59°F entering water
13.6_EER_13.6_EER_
VRF ground source
(cooling mode)
<135,000 Btu/hAllVRF multisplit_system_
77°F entering water
13.4_EER_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF ground source
(cooling mode)
<135,000 Btu/hAllVRF multisplit_system_
with heat recovery
77°F entering water
13.2_EER_13.2_EER_
VRF ground source
(cooling mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
77°F entering water
11.0_EER_11.0_EER_
VRF ground source
(cooling mode)
135,000 Btu/h135,000 Btu/hVRF multisplit_system_
with heat recovery
77°F entering water
10.8_EER_10.8_EER_

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF multisplit system less than 65,000 Btu/h, see Informative Appendix F, Table F-1 for the U.S. Department of Energy minimum.

122 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 125

Open page note

Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements (Continued)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
VRF air cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Three-phase for
applications in the U.S.
and single- and three-
phase for applications
outside the U.S.
VRF multisplit_system_7.7_HSPF_
Before 1/1/2023
On or after 1/1/2023
HSPF2 = 7.5
AHRI 1230-2014 with
Addendum 1
before 1/1/2023
AHRI 210/240-2023
on or after 1/1/2023
VRF air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
47°F db/43°F wb
outdoor air
3.3_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF air cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.25_COPH_2.25_COPH_
VRF air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
47°F db/43°F wb
outdoor air
3.2_COPH_3.2_COPH_
VRF air cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.05_COPH_2.05_COPH_
VRF water source
(heating mode)
<65,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
4.3_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF water source
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
4.3_COPH_4.3_COPH_
VRF water source
(heating mode)
135,000 Btu/h and
<240,000 Btu/h
(cooling capacity)
135,000 Btu/h and
<240,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
4.0_COPH_4.0_COPH_
VRF water source
(heating mode)
240,000 Btu/h
(cooling capacity)
240,000 Btu/h
(cooling capacity)
VRF multisplit_system_
68°F entering water
3.9_COPH_3.9_COPH_
VRF groundwater
source (heating
mode)
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
50°F entering water
3.6_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF groundwater
source (heating
mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
50°F entering water
3.3_COPH_3.3_COPH_
VRF ground source
(heating mode)
<135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
32°F entering water
3.1_COPH_AHRI 1230-2014 with
Addendum 1
before 1/1/2024
AHRI 1230-2021
on or after 1/1/2024
VRF ground source
(heating mode)
135,000 Btu/h
(cooling capacity)
135,000 Btu/h
(cooling capacity)
VRF multisplit_system_
32°F entering water
2.8_COPH_2.8_COPH_

a. VRF outdoor units can be combined with innumerable indoor unit combinations, which will vary by application, building type, building size, operating conditions, and comfort

level goals. Selection of indoor units tested during the test is considered to be representative of commonly sold applications and is detailed in AHRI 1230. Informative Note: For single-phase VRF multisplit system less than 65,000 Btu/h, see Informative Appendix F, Table F-1 for the U.S. Department of Energy minimum.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 123

PDF Page 126

Open page note

Table 6.8.1-10 Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms—

Minimum EfficiencyRequirementsCol3Col4Col5Col6
Equipment TypeStandard ModelNet Sensible
Cooling Capacity
Minimum Net
Sensible COP
Rating Conditions
Return Air
(dry-bulb/dew-point)
Test Procedure
Air cooledDownflow<80,000 Btu/h2.7085°F/52°F (Class 2)AHRI 1360
Air cooledDownflow80,000 Btu/h and
<295,000 Btu/h
2.582.582.58
Air cooledDownflow295,000 Btu/h2.362.362.36
Air cooledUpflow—ducted<80,000 Btu/h2.672.672.67
Air cooledUpflow—ducted80,000 Btu/h and
<295,000 Btu/h
2.552.552.55
Air cooledUpflow—ducted295,000 Btu/h2.332.332.33
Air cooledUpflow—nonducted<65,000 Btu/h2.1675°F/52°F (Class 1)75°F/52°F (Class 1)
Air cooledUpflow—nonducted65,000 Btu/h and
<240,000 Btu/h
2.042.042.04
Air cooledUpflow—nonducted240,000 Btu/h1.891.891.89
Air cooledHorizontal<65,000 Btu/h2.6595°F/52°F (Class 3)95°F/52°F (Class 3)
Air cooledHorizontal65,000 Btu/h and
<240,000 Btu/h
2.552.552.55
Air cooledHorizontal240,000 Btu/h2.472.472.47
Air cooled with
fluid economizer
Downflow<80,000 Btu/h2.7085°F/52°F (Class 1)AHRI 1360
Air cooled with
fluid economizer
Downflow80,000 Btu/h and
<295,000 Btu/h
2.582.582.58
Air cooled with
fluid economizer
Downflow295,000 Btu/h2.362.362.36
Air cooled with
fluid economizer
Upflow—ducted<80,000 Btu/h2.672.672.67
Air cooled with
fluid economizer
Upflow—ducted80,000 Btu/h and
<295,000 Btu/h
2.552.552.55
Air cooled with
fluid economizer
Upflow—ducted295,000 Btu/h2.332.332.33
Air cooled with
fluid economizer
Upflow—nonducted<65,000 Btu/h2.0975°F/52°F (Class 1)75°F/52°F (Class 1)
Air cooled with
fluid economizer
Upflow—nonducted65,000 Btu/h and
<240,000 Btu/h
1.991.991.99
Air cooled with
fluid economizer
Upflow—nonducted240,000 Btu/h1.811.811.81
Air cooled with
fluid economizer
Horizontal<65,000 Btu/h2.6595°F/52°F (Class 3)95°F/52°F (Class 3)
Air cooled with
fluid economizer
Horizontal65,000 Btu/h and
<240,000 Btu/h
2.552.552.55
Air cooled with
fluid economizer
Horizontal240,000 Btu/h2.472.472.47

124 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 127

Open page note

Table 6.8.1-10 Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms—Minimum Efficiency Requirements (Continued)

Equipment TypeStandard ModelNet Sensible
Cooling Capacity
Minimum Net
Sensible COP
Rating Conditions
Return Air
(dry-bulb/dew-point)
Test Procedure
Water cooledDownflow<80,000 Btu/h2.8285°F/52°F (Class 1)AHRI 1360
Water cooledDownflow80,000 Btu/h and
<295,000 Btu/h
2.732.732.73
Water cooledDownflow295,000 Btu/h2.672.672.67
Water cooledUpflow—ducted<80,000 Btu/h2.792.792.79
Water cooledUpflow—ducted80,000 Btu/h and
<295,000 Btu/h
2.702.702.70
Water cooledUpflow—ducted295,000 Btu/h2.642.642.64
Water cooledUpflow—nonducted<65,000 Btu/h2.4375°F/52°F (Class 1)75°F/52°F (Class 1)
Water cooledUpflow—nonducted65,000 Btu/h and
<240,000 Btu/h
2.322.322.32
Water cooledUpflow—nonducted240,000 Btu/h2.202.202.20
Water cooledHorizontal<65,000 Btu/h2.7995°F/52°F (Class 3)95°F/52°F (Class 3)
Water cooledHorizontal65,000 Btu/h and
<240,000 Btu/h
2.682.682.68
Water cooledHorizontal240,000 Btu/h2.602.602.60
Water cooled with
fluid economizer
Downflow<80,000 Btu/h2.7785°F/52°F (Class 1)AHRI 1360
Water cooled with
fluid economizer
Downflow80,000 Btu/h and
<295,000 Btu/h
2.682.682.68
Water cooled with
fluid economizer
Downflow295,000 Btu/h2.612.612.61
Water cooled with
fluid economizer
Upflow—ducted<80,000 Btu/h2.742.742.74
Water cooled with
fluid economizer
Upflow—ducted80,000 Btu/h and
<295,000 Btu/h
2.652.652.65
Water cooled with
fluid economizer
Upflow—ducted295,000 Btu/h2.582.582.58
Water cooled with
fluid economizer
Upflow—nonducted<65,000 Btu/h2.3575°F/52°F (Class 1)75°F/52°F (Class 1)
Water cooled with
fluid economizer
Upflow—nonducted65,000 Btu/h and
<240,000 Btu/h
2.242.242.24
Water cooled with
fluid economizer
Upflow—nonducted240,000 Btu/h2.122.122.12
Water cooled with
fluid economizer
Horizontal<65,000 Btu/h2.7195°F/52°F (Class 3)95°F/52°F (Class 3)
Water cooled with
fluid economizer
Horizontal65,000 Btu/h and
<240,000 Btu/h
2.602.602.60
Water cooled with
fluid economizer
Horizontal240,000 Btu/h2.542.542.54

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 125

PDF Page 128

Open page note

Table 6.8.1-10 Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms—Minimum Efficiency Requirements (Continued)

Equipment TypeStandard ModelNet Sensible
Cooling Capacity
Minimum Net
Sensible COP
Rating Conditions
Return Air
(dry-bulb/dew-point)
Test Procedure
Glycol cooledDownflow<80,000 Btu/h2.5685°F/52°F (Class 1)AHRI 1360
Glycol cooledDownflow80,000 Btu/h and
<295,000 Btu/h
2.242.242.24
Glycol cooledDownflow295,000 Btu/h2.212.212.21
Glycol cooledUpflow—ducted<80,000 Btu/h2.532.532.53
Glycol cooledUpflow—ducted80,000 Btu/h and
<295,000 Btu/h
2.212.212.21
Glycol cooledUpflow—ducted295,000 Btu/h2.182.182.18
Glycol cooledUpflow—nonducted<65,000 Btu/h2.0875°F/52°F (Class 1)75°F/52°F (Class 1)
Glycol cooledUpflow—nonducted65,000 Btu/h and
<240,000 Btu/h
1.901.901.90
Glycol cooledUpflow—nonducted240,000 Btu/h1.811.811.81
Glycol cooledHorizontal<65,000 Btu/h2.4895°F/52°F (Class 3)95°F/52°F (Class 3)
Glycol cooledHorizontal65,000 Btu/h and
<240,000 Btu/h
2.182.182.18
Glycol cooledHorizontal240,000 Btu/h2.182.182.18
Glycol cooled with
fluid economizer
Downflow<80,000 Btu/h2.5185°F/52°F (Class 1)AHRI 1360
Glycol cooled with
fluid economizer
Downflow80,000 Btu/h and
<295,000 Btu/h
2.192.192.19
Glycol cooled with
fluid economizer
Downflow295,000 Btu/h2.152.152.15
Glycol cooled with
fluid economizer
Upflow—ducted<80,000 Btu/h2.482.482.48
Glycol cooled with
fluid economizer
Upflow—ducted80,000 Btu/h and
<295,000 Btu/h
2.162.162.16
Glycol cooled with
fluid economizer
Upflow—ducted295,000 Btu/h2.122.122.12
Glycol cooled with
fluid economizer
Upflow—nonducted<65,000 Btu/h2.0075°F/52°F (Class 1)75°F/52°F (Class 1)
Glycol cooled with
fluid economizer
Upflow—nonducted65,000 Btu/h and
<240,000 Btu/h
1.821.821.82
Glycol cooled with
fluid economizer
Upflow—nonducted240,000 Btu/h1.731.731.73
Glycol cooled with
fluid economizer
Horizontal<65,000 Btu/h2.4495°F/52°F (Class 3)95°F/52°F (Class 3)
Glycol cooled with
fluid economizer
Horizontal65,000 Btu/h and
<240,000 Btu/h
2.102.102.10
Glycol cooled with
fluid economizer
Horizontal240,000 Btu/h2.102.102.10

126 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 129

Open page note

Table 6.8.1-11 Commercial Refrigerators, Commercial Freezers, and Refrigeration—Minimum Efficiency Requirements

Equipment
Category
Condensing Unit
Configuration
Equipment
Family
Rating
Temp., °F
Operating
Temp., °F
Equipment
Classificationc
Maximum Daily
Energy Consumption,
kWh/dayd,e
Test
Procedure
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Vertical open
(VOP)
38 (M)32VOP.RC.M0.64 × TDA + 4.07AHRI 1200
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Vertical open
(VOP)
0 (L)<32VOP.RC.L2.20 × TDA + 6.852.20 × TDA + 6.85
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Semivertical open
(SVO)
38 (M)32SVO.RC.M0.66 × TDA + 3.180.66 × TDA + 3.18
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Semivertical open
(SVO)
0 (L)<32SVO.RC.L2.20 × TDA + 6.852.20 × TDA + 6.85
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Horizontal open
(HZO)
38 (M)32HZO.RC.M0.35 × TDA + 2.880.35 × TDA + 2.88
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Horizontal open
(HZO)
0 (L)<32HZO.RC.L0.55 × TDA + 6.880.55 × TDA + 6.88
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Vertical closed
transparent (VCT)
38 (M)32VCT.RC.M0.15 × TDA + 1.950.15 × TDA + 1.95
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Vertical closed
transparent (VCT)
0 (L)<32VCT.RC.L0.49 × TDA + 2.610.49 × TDA + 2.61
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Horizontal closed
transparent (HCT)
38 (M)32HCT.RC.M0.16 × TDA + 0.130.16 × TDA + 0.13
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Horizontal closed
transparent (HCT)
0 (L)<32HCT.RC.L0.34 × TDA + 0.260.34 × TDA + 0.26
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Vertical closed
solid (VCS)
38 (M)32VCS.RC.M0.10 ×V + 0.260.10 ×V + 0.26
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Vertical closed
solid (VCS)
0 (L)<32VCS.RC.L0.21 ×V + 0.540.21 ×V + 0.54
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Horizontal closed
solid (HCS)
38 (M)32HCS.RC.M0.10 ×V + 0.260.10 ×V + 0.26
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Horizontal closed
solid (HCS)
0 (L)<32HCS.RC.L0.21 ×V + 0.540.21 ×V + 0.54
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Service over
counter (SOC)
38 (M)32SOC.RC.M0.44 × TDA + 0.110.44 × TDA + 0.11
Remote
condensing
commercial
refrigerators
and commercial
freezers
Remote (RC)Service over
counter (SOC)
0 (L)<32SOC.RC.L0.93 × TDA + 0.220.93 × TDA + 0.22
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Vertical open
(VOP)
38 (M)32VOP.SC.M1.69 × TDA + 4.71AHRI 1200
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Vertical open
(VOP)
0 (L)<32VOP.SC.L4.25 × TDA + 11.824.25 × TDA + 11.82
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Semivertical open
(SVO)
38 (M)32SVO.SC.M1.70 × TDA + 4.591.70 × TDA + 4.59
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Semivertical open
(SVO)
0 (L)<32SVO.SC.L4.26 × TDA + 11.514.26 × TDA + 11.51
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Horizontal open
(HZO)
38 (M)32HZO.SC.M0.72 × TDA + 5.550.72 × TDA + 5.55
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Horizontal open
(HZO)
0 (L)<32HZO.SC.L1.90 × TDA + 7.081.90 × TDA + 7.08
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Vertical closed
transparent (VCT)
38 (M)32VCT.SC.M0.10 ×V + 0.860.10 ×V + 0.86
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Vertical closed
transparent (VCT)
0 (L)<32VCT.SC.L0.29 ×V + 2.950.29 ×V + 2.95
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Vertical closed
solid (VCS)
38 (M)32VCS.SC.M0.05 ×V + 1.360.05 ×V + 1.36
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Vertical closed
solid (VCS)
0 (L)<32VCS.SC.L0.22 ×V + 1.380.22 ×V + 1.38
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Horizontal closed
transparent (HCT)
38 (M)32HCT.SC.M0.06 ×V + 0.370.06 ×V + 0.37
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Horizontal closed
transparent (HCT)
0 (L)<32HCT.SC.L0.08 ×V + 1.230.08 ×V + 1.23
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Horizontal closed
solid (HCS)
38 (M)32HCS.SC.M0.05 ×V + 0.910.05 ×V + 0.91
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Horizontal closed
solid (HCS)
0 (L)<32HCS.SC.L0.06 ×V + 1.120.06 ×V + 1.12
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Service over
counter (SOC)
38 (M)32SOC.SC.M0.52 × TDA + 1.000.52 × TDA + 1.00
Self-contained
commercial
refrigerators and
commercial
freezers with and
without doors
Self-contained (SC)Service over
counter (SOC)
0 (L)<32SOC.SC.L1.10 × TDA + 2.101.10 × TDA + 2.10

a. The meaning of the letters in this column is indicated in the columns to the left. b. “Ice-cream freezer” is defined in 10 CFR 431.62 as a commercial freezer that is designed to operate at or below –5°F and that the manufacturer designs, markets, or intends for

the storing, displaying, or dispensing of ice cream. c. Equipment class designations consist of a combination (in sequential order separated by periods (AAA).(BB).(C)) of the following: 

(AAA)—An equipment family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical closed transparent doors, VCS = vertical closed solid doors, HCT = horizontal closed transparent doors, HCS = horizontal closed solid doors, and SOC = service over counter); (BB)—An operating mode code (RC = remote condensing and SC = self-contained); and (C)—A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [–15°F]). For example, “VOP.RC.M” refers to the “vertical open, remote condensing, medium temperature” equipment class. d. V is the volume of the case (ft [3] ) as measured in AHRI Standard 1200, Appendix C. e. TDA is the total display area of the case (ft [2] ) as measured in AHRI Standard 1200, Appendix D.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 127

PDF Page 130

Open page note

Table 6.8.1-11 Commercial Refrigerators, Commercial Freezers, and Refrigeration—Minimum Efficiency Requirements (Continued)

Equipment
Category
Condensing Unit
Configuration
Equipment
Family
Rating
Temp., °F
Operating
Temp., °F
Equipment
Classificationc
Maximum Daily
Energy Consumption,
kWh/dayd,e
Test
Procedure
Self-contained
commercial
refrigerators with
transparent doors
for pull-down
temperature
applications
Self-contained (SC)Pull-down (PD)38 (M)32PD.SC.M0.11 ×V + 0.81AHRI 1200
Commercial
ice-cream
freezers
Remote (RC)Vertical open
(VOP)
–15 (I)–5bVOP.RC.I2.79 × TDA + 8.70AHRI 1200
Commercial
ice-cream
freezers
Remote (RC)Semivertical open
(SVO)
Semivertical open
(SVO)
Semivertical open
(SVO)
SVO.RC.I2.79 × TDA + 8.702.79 × TDA + 8.70
Commercial
ice-cream
freezers
Remote (RC)Horizontal open
(HZO)
Horizontal open
(HZO)
Horizontal open
(HZO)
HZO.RC.I0.70 × TDA + 8.740.70 × TDA + 8.74
Commercial
ice-cream
freezers
Remote (RC)Vertical closed
transparent (VCT)
Vertical closed
transparent (VCT)
Vertical closed
transparent (VCT)
VCT.RC.I0.58 × TDA + 3.050.58 × TDA + 3.05
Commercial
ice-cream
freezers
Remote (RC)Horizontal closed
transparent (HCT)
Horizontal closed
transparent (HCT)
Horizontal closed
transparent (HCT)
HCT.RC.I0.40 × TDA + 0.310.40 × TDA + 0.31
Commercial
ice-cream
freezers
Remote (RC)Vertical closed
solid (VCS)
Vertical closed
solid (VCS)
Vertical closed
solid (VCS)
VCS.RC.I0.25 × V + 0.630.25 × V + 0.63
Commercial
ice-cream
freezers
Remote (RC)Horizontal closed
solid (HCS)
Horizontal closed
solid (HCS)
Horizontal closed
solid (HCS)
HCS.RC.I0.25 × V + 0.630.25 × V + 0.63
Commercial
ice-cream
freezers
Remote (RC)Service over
counter (SOC)
Service over
counter (SOC)
Service over
counter (SOC)
SOC.RC.I1.09 × TDA + 0.261.09 × TDA + 0.26
Commercial
ice-cream
freezers
Self-contained (SC)Vertical open
(VOP)
Vertical open
(VOP)
Vertical open
(VOP)
VOP.SC.I5.40 × TDA + 15.02AHRI 1200
Commercial
ice-cream
freezers
Self-contained (SC)Semivertical open
(SVO)
Semivertical open
(SVO)
Semivertical open
(SVO)
SVO.SC.I5.41 × TDA + 14.635.41 × TDA + 14.63
Commercial
ice-cream
freezers
Self-contained (SC)Horizontal open
(HZO)
Horizontal open
(HZO)
Horizontal open
(HZO)
HZO.SC.I2.42 × TDA + 9.002.42 × TDA + 9.00
Commercial
ice-cream
freezers
Self-contained (SC)Vertical closed
transparent (VCT)
Vertical closed
transparent (VCT)
Vertical closed
transparent (VCT)
VCT.SC.I0.62 × TDA + 3.290.62 × TDA + 3.29
Commercial
ice-cream
freezers
Self-contained (SC)Horizontal closed
transparent (HCT)
Horizontal closed
transparent (HCT)
Horizontal closed
transparent (HCT)
HCT.SC.I0.56 × TDA + 0.430.56 × TDA + 0.43
Commercial
ice-cream
freezers
Self-contained (SC)Vertical closed
solid (VCS)
Vertical closed
solid (VCS)
Vertical closed
solid (VCS)
VCS.SC.I0.34 × V + 0.880.34 × V + 0.88
Commercial
ice-cream
freezers
Self-contained (SC)Horizontal closed
solid (HCS)
Horizontal closed
solid (HCS)
Horizontal closed
solid (HCS)
HCS.SC.I0.34 × V + 0.880.34 × V + 0.88
Commercial
ice-cream
freezers
Self-contained (SC)Service over
counter (SOC)
Service over
counter (SOC)
Service over
counter (SOC)
SOC.SC.I1.53 × TDA + 0.361.53 × TDA + 0.36

a. The meaning of the letters in this column is indicated in the columns to the left. b. “Ice-cream freezer” is defined in 10 CFR 431.62 as a commercial freezer that is designed to operate at or below –5°F and that the manufacturer designs, markets, or intends for

the storing, displaying, or dispensing of ice cream. c. Equipment class designations consist of a combination (in sequential order separated by periods (AAA).(BB).(C)) of the following: 

(AAA)—An equipment family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical closed transparent doors, VCS = vertical closed solid doors, HCT = horizontal closed transparent doors, HCS = horizontal closed solid doors, and SOC = service over counter); (BB)—An operating mode code (RC = remote condensing and SC = self-contained); and (C)—A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [–15°F]). For example, “VOP.RC.M” refers to the “vertical open, remote condensing, medium temperature” equipment class. d. V is the volume of the case (ft [3] ) as measured in AHRI Standard 1200, Appendix C. e. TDA is the total display area of the case (ft [2] ) as measured in AHRI Standard 1200, Appendix D.

128 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 131

Open page note

Table 6.8.1-12 Vapor-Compression-Based Indoor Pool Dehumidifiers—Minimum Efficiency Requirements

Equipment TypeSubcategory or Rating ConditionMinimum EfficiencyTest Procedure
Single package indoor
(with or without economizer)
Rating Conditions: A or C3.5_MRE_AHRI 910
Single package indoor water-cooled
(with or without economizer)
Rating Conditions: A, B, or C3.5_MRE_3.5_MRE_
Single package indoor air-cooled
(with or without economizer)
Rating Conditions: A, B, or C3.5_MRE_3.5_MRE_
Split_system_ indoor air-cooled
(with or without economizer)
Rating Conditions: A, B, or C3.5_MRE_3.5_MRE_

Table 6.8.1-13 Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser,

without Energy Recovery—Minimum EfficiencyRequirementsCol3Col4
Equipment TypeSubcategory or Rating ConditionMinimum EfficiencyTest Procedure
Air cooled (dehumidification mode)4.0_ISMRE_AHRI 920
Air source heat pumps (dehumidification mode)4.0_ISMRE_AHRI 920
Water cooled (dehumidification mode)Cooling tower condenser water4.9_ISMRE_AHRI 920
Water cooled (dehumidification mode)Chilled Water6.0_ISMRE_6.0_ISMRE_
Air source heat pump (heating mode)2.7_ISCOP_AHRI 920
Water source heat pump (dehumidification mode)Ground source, closed loop4.8_ISMRE_AHRI 920
Water source heat pump (dehumidification mode)Ground-water source5.0_ISMRE_5.0_ISMRE_
Water source heat pump (dehumidification mode)Water source4.0_ISMRE_4.0_ISMRE_
Water source heat pump (heating mode)Ground source, closed loop2.0_ISCOP_AHRI 920
Water source heat pump (heating mode)Ground-water source3.2_ISCOP_3.2_ISCOP_
Water source heat pump (heating mode)Water source3.5_ISCOP_3.5_ISCOP_

Table 6.8.1-14 Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser,with Energy Recovery—Minimum Efficiency Requirements

Equipment TypeSubcategory or Rating ConditionMinimum EfficiencyTest Procedure
Air cooled (dehumidification mode)
Air source heat pumps (dehumidification mode)
5.2_ISMRE_
5.2_ISMRE_
AHRI 920
AHRI 920
Water cooled (dehumidification mode)Cooling tower condenser water5.3_ISMRE_AHRI 920
Water cooled (dehumidification mode)Chilled water6.6_ISMRE_6.6_ISMRE_
Air source heat pump (heating mode)3.3_ISCOP_AHRI 920
Water source heat pump (dehumidification mode)Ground source, closed loop5.2_ISMRE_AHRI 920
Water source heat pump (dehumidification mode)Ground-water source5.8_ISMRE_5.8_ISMRE_
Water source heat pump (dehumidification mode)Water source4.8_ISMRE_4.8_ISMRE_
Water source heat pump (heating mode)Ground source, closed loop3.8_ISCOP_AHRI 920
Water source heat pump (heating mode)Ground-water source4.0_ISCOP_4.0_ISCOP_
Water source heat pump (heating mode)Water source4.8_ISCOP_4.8_ISCOP_

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 129

PDF Page 132

Open page note

Table 6.8.1-15 Electrically Operated Water-Source Heat Pumps—Minimum Efficiency Requirements [ b]

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test
Procedurea
Water-to-air, water loop
(cooling mode)
<17,000 Btu/hAll86°F entering water12.2_EER_ISO 13256-1
Water-to-air, water loop
(cooling mode)
17,000 Btu/h and
<65,000 Btu/h
17,000 Btu/h and
<65,000 Btu/h
17,000 Btu/h and
<65,000 Btu/h
13.0_EER_13.0_EER_
Water-to-air, water loop
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
13.0_EER_13.0_EER_
Water-to-air, groundwater (cooling
mode)
<135,000 Btu/hAll59°F entering water18.0_EER_ISO 13256-1
Brine-to-air, ground loop (cooling
mode)
<135,000 Btu/hAll77°F entering water14.1_EER_ISO 13256-1
Water-to-water, water loop
(cooling mode)
<135,000 Btu/hAll86°F entering water10.6_EER_ISO 13256-2
Water-to-water, groundwater
(cooling mode)
<135,000 Btu/hAll59°F entering water16.3_EER_ISO 13256-2
Brine-to-water, ground loop
(cooling mode)
<135,000 Btu/hAll77°F entering water12.1_EER_ISO 13256-2
Water-to-air, water loop
(heating mode)
<135,000 Btu/h
(cooling capacity)
68°F entering water4.3_COPH_ISO 13256-1
Water-to-air, groundwater (heating
mode)
<135,000 Btu/h
(cooling capacity)
50°F entering water3.7_COPH_ISO 13256-1
Brine-to-air, ground loop (heating
mode)
<135,000 Btu/h
(cooling capacity)
32°F entering water3.2_COPH_ISO 13256-1
Water-to-water, water loop
(heating mode)
<135,000 Btu/h
(cooling capacity)
68°F entering water3.7_COPH_ISO 13256-1
Water-to-water, groundwater
(heating mode)
<135,000 Btu/h
(cooling capacity)
50°F entering water3.1_COPH_ISO 13256-2
Brine-to-water, ground loop
(heating mode)
<135,000 Btu/h
(cooling capacity)
32°F entering water2.5_COPH_ISO 13256-2

a. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. b. Single-phase, U.S. air-cooled heat pumps <65,000 Btu/h are regulated as consumer products by 10 CFR 430. SEER, SEER2, HPSF and HPSF2 values for single-phase products

are set by the U.S. DOE. Informative Note: See Informative Appendix F for the U.S. DOE minimum.

130 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 133

Open page note

Table 6.8.1-16 Heat Pump and Heat Recovery Water-Chilling Packages—Minimum Efficiency Requirements

Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Col4Heating Operation Efficiency,b,e,jCol6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Test
Procedure
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Heating Source
Conditions
(leaving liquid) or
OAT (db/wb)g,, °F
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Heating Source
Conditions
(leaving liquid) or
OAT (db/wb)g,, °F
Entering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid Temperature** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Heating Source
Conditions
(leaving liquid) or
OAT (db/wb)g,, °F
LowMediumHighBoostLowMediumHighBoostLowMediumHot-
Water 1
Hot-
Water 2
Hot-
Water 2
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Path APath BPath B95.00°F/
105.00°F
105.00°F/
120.00°F
120.00°F/
140.00°F
120.00°F/
140.00°F
95.00°F/
105.00°F
105.00°F/
120.00°F
120.00°F/
140.00°F
120.00°F/
140.00°F
95.00°F/
105.00°F
105.00°F/
120.00°F
90.00°F/
140.00°F
120.00°F/
140.00°F
120.00°F/
140.00°F
Air source<150.0≥9.595 FL
≥13.02_IPLV_.IP
≥9.215 FL
≥15.01_IPLV_.IP
47.00 db
43.00 wbl
≥3.290≥2.770≥2.310NA~~ p~~
NA~~ p~~
NA~~ p~~
NA~~ p~~
NA~~ p~~
NA~~ p~~
NA~~ p~~
NA~~ p~~
NA~~ p~~
AHRI
550/590
Air source<150.0≥9.595 FL
≥13.02_IPLV_.IP
≥9.215 FL
≥15.01_IPLV_.IP
17.00 db
15.00 wbl
≥2.029≥1.775≥1.483NA p
NA p
NA p
NA p
NA p
NA p
NA p
NA p
NA p
NA p
Air source≥150.0
≥9.595 FL
≥13.30_IPLV_.IP
≥9.215 FL
≥15.30_IPLV_.IP
47.00 db
43.00 wbl
≥3.290≥2.770≥2.310NA p
NA p
NA p
NA p
NA p
NA p
NA p
NA p
NA p
NA p
Air source≥150.0
≥9.595 FL
≥13.30_IPLV_.IP
≥9.215 FL
≥15.30_IPLV_.IP
17.00 db
15.00 wbl
≥2.029≥1.775≥1.483NA p
NA pNA pNA pNA p
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
positive
displacement
≥11.25q and
<150.00
≤ 0.7895 FL
≤0.6316_IPLV_.IP
≤0.8211FL
≤0.5263
IPLV.IP
44.00m
≥4.640
≥3.680
≥2.680
NA p≥8.330
≥6.410
≥4.420
NA p≥8.330
≥6.410
≥4.862
≥4.420
AHRI
550/590
Liquid-
source
electrically
operated
positive
displacement
≥11.25q and
<150.00
≤ 0.7895 FL
≤0.6316_IPLV_.IP
≤0.8211FL
≤0.5263
IPLV.IP
65.00 m
NA pNA pNA p≥3.550
NA pNA pNA p≥6.150
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
positive
displacement
≥150.0 and
<300.0
≤0.7579 FL
≤0.5895_IPLV_.IP
≤0.7895 FL
≤0.5158
IPLV.IP
44.00m
≥4.640
≥3.680
≥2.680
NA p≥8.330
≥6.410
≥4.420
NA p≥8.330
≥6.410
≥4.862
≥4.420
≥4.420
Liquid-
source
electrically
operated
positive
displacement
≥150.0 and
<300.0
≤0.7579 FL
≤0.5895_IPLV_.IP
≤0.7895 FL
≤0.5158
IPLV.IP
65.00 m
NA pNA pNA p≥3.550
NA pNA pNA p≥6.150
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
positive
displacement
≥300.0 and
<400.0
≤0.6947 FL
≤0.5684_IPLV_.IP
≤0.7158 FL
≤0.4632
IPLV.IP
44.00m
≥4.640
≥3.680
≥2.680
NA p≥8.330
≥6.410
≥4.420
NA p≥8.330
≥6.410
≥4.862
≥4.420
≥4.420
Liquid-
source
electrically
operated
positive
displacement
≥300.0 and
<400.0
≤0.6947 FL
≤0.5684_IPLV_.IP
≤0.7158 FL
≤0.4632
IPLV.IP
65.00 m
NA pNA pNA p≥3.550
NA pNA pNA p≥6.150
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
positive
displacement
≥400.0 and
<600.0
≤0.6421 FL
≤0.5474_IPLV_.IP
≤0.6579 FL
≤0.4316
IPLV.IP
44.00m
≥4.930
≥3.960
≥2.970
NA p≥8.900
≥6.980
≥5.000
NA p≥8.900
≥6.980
≥5.500
≥5.000
≥5.000
Liquid-
source
electrically
operated
positive
displacement
≥400.0 and
<600.0
≤0.6421 FL
≤0.5474_IPLV_.IP
≤0.6579 FL
≤0.4316
IPLV.IP
65.00 m
NA pNA pNA p≥3.900
NA pNA pNA p≥6.850
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
positive
displacement
≥600.0≤0.5895 FL
≤0.5263_IPLV_.IP
≤0.6158 FL
≤0.4000
IPLV.IP
44.00m
≥4.930
≥3.960
≥2.970
NA p≥8.900
≥6.980
≥5.000
NA p≥8.900
≥6.980
≥5.500
≥5.000
≥5.000
Liquid-
source
electrically
operated
positive
displacement
≥600.0≤0.5895 FL
≤0.5263_IPLV_.IP
≤0.6158 FL
≤0.4000
IPLV.IP
65.00 mNA pNA pNA p≥3.900NA pNA pNA p≥6.850NA pNA pNA pNA pNA p

a. Cooling rating conditions are standard rating conditions defined in AHRI 550/590 (I-P), Table 4, except for liquid-cooled centrifugal chilling packages which can adjust cooling efficiency for nonstandard rating conditions using Kadj procedure in accordance with 

Section 6.4.1.2.1. b. Heating full-load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4; includes the impact of defrost for air source heating ratings. c. For liquid-source heat recovery chilling packages that have capabilities for heat rejection to a heat recovery condenser and a tower condenser the COPHR applies to operation at full load with 100% heat recovery (no tower rejection). Units that only have capabilities

for partial heat recovery shall meet the requirements of Table 6.8.1-3. d. For cooling operation, compliance with both the FL and IPLV is required, but only compliance with Path A or Path B cooling efficiency is required. e. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required. f. For applications where the chilling package is installed to operate only in heating, compliance only with the heating performance COPH is required at only one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance

with cooling performance is not required. g. For air source heat pumps, compliance with both the 47.00°F and 17.00°F heating source outdoor air temperature (OAT) rating efficiency is required for heating. h. For heat-pump chilling package applications where the cooling capacity is not being used for conditioning, compliance with the heating performance COPH is only required at one of the four heating AHRI 550/590 standard ratings conditions of Low, Medium, High,

or Boost. Compliance with the cooling performance is required as defined in footnotes (a) and (d), except as noted in footnote (f). i. For simultaneous cooling and heating chillers applications where there is simultaneous cooling and heating, compliance with the simultaneous cooling performance heat recovery COPSHC is only required at one of the four simultaneous cooling and heating AHRI 550/

590 (I-P) standard ratings conditions of Low, Medium, High, or Boost. Compliance with the cooling only performance is required as defined in footnotes (a) and (d). j. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recovery COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low,

Medium, Hot-Water 1, or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes a and d. k. Chilling packages employing a freeze-protection liquid in accordance with Section 6.4.1.2.2 shall be tested or rated with water for the purpose of compliance with the requirements of this table. l. Outdoor air entering dry-bulb (db) temperature and wet-bulb (wb) temperature. m. Source-leaving liquid temperature.

  • The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air-to-water heat pump shall be the flow rate determined during the full-load cooling rating.

  • The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating.

  • For heating-only fluid-to-fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54.00°F and a leaving liquid temperature of 44.00°F shall be used. n. The size category is the full-load net refrigerating cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chilling package.

  • A heat recovery condenser at its maximum load point must remove enough heat from the refrigerant to cool the refrigerant to remove all superheat energy and begin condensation of the refrigerant. A heat recovery system where only the superheat is reduced is not

covered by Table 6.8.1-16 and is considered a desuperheater, and the chiller package must comply with Table 6.8.1-3. p. “NA” means the requirements are not applicable. q. Water-to-water heat pumps with a capacity less than 135,000 Btu/h are covered by Table 6.8.1-15.

PDF Page 134

Open page note

Table 6.8.1-16 Heat Pump and Heat Recovery Water-Chilling Packages—Minimum Efficiency Requirements

Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Col4Heating Operation Efficiency,b,e,jCol6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Test
Procedure
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Heating Source
Conditions
(leaving liquid) or
OAT (db/wb)g,, °F
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Heat Pump Heating Full-Load Heating
Efficiency (COP****H)f,h, W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Simultaneous Cooling and Heating
Full-Load Efficiency (COP****SHC)b,i,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Heat Recovery Heating Full-Load
Efficiency (COP****HR)c,j,W/W
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Heating Source
Conditions
(leaving liquid) or
OAT (db/wb)g,, °F
Entering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid TemperatureEntering/Leaving Heating Liquid Temperature** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**** Entering/Leaving Heating Liquid Temperature**
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Cooling Operation Efficiencya,d,e,j
Air Source EER (FL/IPLV), Btu/W·h
Liquid-Source Power Input per Capacity
(FL/IPLV), kW/tonR
Heating Source
Conditions
(leaving liquid) or
OAT (db/wb)g,, °F
LowMediumHighBoostLowMediumHighBoostLowMediumHot-
Water 1
Hot-
Water 2
Hot-
Water 2
Equipment
Type
Size Category
Refrigerating
Capacityn,
tonR
Path APath BPath B95.00°F/
105.00°F
105.00°F/
120.00°F
120.00°F/
140.00°F

120.00°F/
140.00°F
95.00°F/
105.00°F
105.00°F/
120.00°F
120.00°F/
140.00°F

120.00°F/
140.00°F
95.00°F/
105.00°F
105.00°F/
120.00°F
90.00°F/
140.00°F
120.00°F/
140.00°F
120.00°F/
140.00°F
Liquid-
source
electrically
operated
centrifugal
≥11.25q and
<150.0
≤0.6421 FL
≤0.5789_IPLV_.IP
≤0.7316 FL
≤0.4632_IPLV_.IP
44.00m
≥4.640
≥3.680
≥2.680
NA~~ p~~≥8.330
≥6.410
≥4.420
NA~~ p~~≥8.330
≥6.410
≥4.862
≥4.420
AHRI
550/590
Liquid-
source
electrically
operated
centrifugal
≥11.25q and
<150.0
≤0.6421 FL
≤0.5789_IPLV_.IP
≤0.7316 FL
≤0.4632_IPLV_.IP
65.00 m
NA pNA pNA p≥3.550
NA pNA pNA p≥6.150
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
centrifugal
≥150.0 and
<300.0
≤0.6190 FL
≤0.5748_IPLV_.IP
≤0.6684 FL
≤0.4211_IPLV_.IP
44.00m
≥4.640
≥3.680
≥2.680
NA p≥8.330
≥6.410
≥4.420
NA p≥8.330
≥6.410
≥4.862
≥4.420
≥4.420
Liquid-
source
electrically
operated
centrifugal
≥150.0 and
<300.0
≤0.6190 FL
≤0.5748_IPLV_.IP
≤0.6684 FL
≤0.4211_IPLV_.IP
65.00 m
NA pNA pNA p≥3.550
NA pNA pNA p≥6.150
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
centrifugal
≥300.0 and
<400.0
≤0.5895 FL
≤0.5526_IPLV_.IP
≤0.6263 FL
≤0.4105_IPLV_.IP
44.00m
≥4.640
≥3.680
≥2.680
NA p≥8.330
≥6.410
≥4.420
NA p≥8.330
≥6.410
≥4.862
≥4.420
≥4.420
Liquid-
source
electrically
operated
centrifugal
≥300.0 and
<400.0
≤0.5895 FL
≤0.5526_IPLV_.IP
≤0.6263 FL
≤0.4105_IPLV_.IP
65.00 m
NA pNA pNA p≥3.550
NA pNA pNA p≥6.150
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
centrifugal
≥400.0 and
<600.0
≤0.5895 FL
≤0.5263_IPLV_.IP
≤0.6158 FL
≤0.4000_IPLV_.IP
44.00m
≥4.930
≥3.960
≥2.970
NA p≥8.900
≥6.980
≥5.000
NA p≥8.900
≥6.980
≥5.500
≥5.000
≥5.000
Liquid-
source
electrically
operated
centrifugal
≥400.0 and
<600.0
≤0.5895 FL
≤0.5263_IPLV_.IP
≤0.6158 FL
≤0.4000_IPLV_.IP
65.00 m
NA pNA pNA p≥3.900
NA pNA pNA p≥6.850
NA pNA pNA pNA pNA p
Liquid-
source
electrically
operated
centrifugal
≥600.0≤0.5895 FL
≤0.5263_IPLV_.IP
≤0.6158 FL
≤0.4000_IPLV_.IP
44.00m
≥4.930
≥3.960
≥2.970
NA p≥8.900
≥6.980
≥5.000
NA p≥8.900
≥6.980
≥5.500
≥5.000
≥5.000
Liquid-
source
electrically
operated
centrifugal
≥600.0≤0.5895 FL
≤0.5263_IPLV_.IP
≤0.6158 FL
≤0.4000_IPLV_.IP
65.00 mNA pNA pNA p≥3.900NA pNA pNA p≥6.850NA pNA pNA pNA pNA p

a. Cooling rating conditions are standard rating conditions defined in AHRI 550/590 (I-P), Table 4, except for liquid-cooled centrifugal chilling packages which can adjust cooling efficiency for nonstandard rating conditions using Kadj procedure in accordance with 

Section 6.4.1.2.1. b. Heating full-load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4; includes the impact of defrost for air source heating ratings. c. For liquid-source heat recovery chilling packages that have capabilities for heat rejection to a heat recovery condenser and a tower condenser the COPHR applies to operation at full load with 100% heat recovery (no tower rejection). Units that only have capabilities

for partial heat recovery shall meet the requirements of Table 6.8.1-3. d. For cooling operation, compliance with both the FL and IPLV is required, but only compliance with Path A or Path B cooling efficiency is required. e. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required. f. For applications where the chilling package is installed to operate only in heating, compliance only with the heating performance COPH is required at only one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance

with cooling performance is not required. g. For air source heat pumps, compliance with both the 47.00°F and 17.00°F heating source outdoor air temperature (OAT) rating efficiency is required for heating. h. For heat-pump chilling package applications where the cooling capacity is not being used for conditioning, compliance with the heating performance COPH is only required at one of the four heating AHRI 550/590 standard ratings conditions of Low, Medium, High,

or Boost. Compliance with the cooling performance is required as defined in footnotes (a) and (d), except as noted in footnote (f). i. For simultaneous cooling and heating chillers applications where there is simultaneous cooling and heating, compliance with the simultaneous cooling performance heat recovery COPSHC is only required at one of the four simultaneous cooling and heating AHRI 550/

590 (I-P) standard ratings conditions of Low, Medium, High, or Boost. Compliance with the cooling only performance is required as defined in footnotes (a) and (d). j. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recovery COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low,

Medium, Hot-Water 1, or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes a and d. k. Chilling packages employing a freeze-protection liquid in accordance with Section 6.4.1.2.2 shall be tested or rated with water for the purpose of compliance with the requirements of this table. l. Outdoor air entering dry-bulb (db) temperature and wet-bulb (wb) temperature. m. Source-leaving liquid temperature.

  • The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air-to-water heat pump shall be the flow rate determined during the full-load cooling rating.

  • The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating.

  • For heating-only fluid-to-fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54.00°F and a leaving liquid temperature of 44.00°F shall be used. n. The size category is the full-load net refrigerating cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chilling package.

  • A heat recovery condenser at its maximum load point must remove enough heat from the refrigerant to cool the refrigerant to remove all superheat energy and begin condensation of the refrigerant. A heat recovery system where only the superheat is reduced is not

covered by Table 6.8.1-16 and is considered a desuperheater, and the chiller package must comply with Table 6.8.1-3. p. “NA” means the requirements are not applicable. q. Water-to-water heat pumps with a capacity less than 135,000 Btu/h are covered by Table 6.8.1-15.

PDF Page 135

Open page note

Table 6.8.1-17 Ceiling-Mounted Computer-Room Air Conditioners—Minimum Efficiency Requirements

Equipment TypeStandard
Model
Net Sensible
Cooling Capacity
Minimum Net
Sensible COP
Rating Conditions
Return Air
(dry bulb/dew point)
Test Procedure
Air cooled with free air
discharge condenser
Ducted<29,000 Btu/h2.0575°F/52°F (Class 1)AHRI 1360
Air cooled with free air
discharge condenser
Ducted29,000 Btu/h and
<65,000 Btu/h
2.022.022.02
Air cooled with free air
discharge condenser
Ducted65,000 Btu/h1.921.921.92
Air cooled with free air
discharge condenser
Nonducted<29,000 Btu/h2.082.082.08
Air cooled with free air
discharge condenser
Nonducted29,000 Btu/h and
<65,000 Btu/h
2.052.052.05
Air cooled with free air
discharge condenser
Nonducted65,000 Btu/h1.941.941.94
Air cooled with free air
discharge condenser
with_fluid economizer_
Ducted<29,000 Btu/h2.0175°F/52°F (Class 1)AHRI 1360
Air cooled with free air
discharge condenser
with_fluid economizer_
Ducted29,000 Btu/h and
<65,000 Btu/h
1.971.971.97
Air cooled with free air
discharge condenser
with_fluid economizer_
Ducted65,000 Btu/h1.871.871.87
Air cooled with free air
discharge condenser
with_fluid economizer_
Nonducted<29,000 Btu/h2.042.042.04
Air cooled with free air
discharge condenser
with_fluid economizer_
Nonducted29,000 Btu/h
and <65,000 Btu/h
2.002.002.00
Air cooled with free air
discharge condenser
with_fluid economizer_
Nonducted65,000 Btu/h1.891.891.89
Air cooled with ducted
condenser
Ducted<29,000 Btu/h1.8675°F/52°F (Class 1)AHRI 1360
Air cooled with ducted
condenser
Ducted29,000 Btu/h
and <65,000 Btu/h
1.831.831.83
Air cooled with ducted
condenser
Ducted65,000 Btu/h1.731.731.73
Air cooled with ducted
condenser
Nonducted<29,000 Btu/h1.891.891.89
Air cooled with ducted
condenser
Nonducted29,000 Btu/h
and <65,000 Btu/h
1.861.861.86
Air cooled with ducted
condenser
Nonducted65,000 Btu/h1.751.751.75
Air cooled with_fluid_
economizer
and ducted condenser
Ducted<29,000 Btu/h1.8275°F/52°F (Class 1)AHRI 1360
Air cooled with_fluid_
economizer
and ducted condenser
Ducted29,000 Btu/h
and <65,000 Btu/h
1.781.781.78
Air cooled with_fluid_
economizer
and ducted condenser
Ducted65,000 Btu/h1.681.681.68
Air cooled with_fluid_
economizer
and ducted condenser
Nonducted<29,000 Btu/h1.851.851.85
Air cooled with_fluid_
economizer
and ducted condenser
Nonducted29,000 Btu/h
and <65,000 Btu/h
1.811.811.81
Air cooled with_fluid_
economizer
and ducted condenser
Nonducted65,000 Btu/h1.701.701.70
Water cooledDucted<29,000 Btu/h2.3875°F/52°F (Class 1)AHRI 1360
Water cooledDucted29,000 Btu/h and
<65,000 Btu/h
2.282.282.28
Water cooledDucted65,000 Btu/h2.182.182.18
Water cooledNonducted<29,000 Btu/h2.412.412.41
Water cooledNonducted29,000 Btu/h and
<65,000 Btu/h
2.312.312.31
Water cooledNonducted65,000 Btu/h2.202.202.20

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 133

PDF Page 136

Open page note

Table 6.8.1-17 Ceiling-Mounted Computer-Room Air Conditioners—Minimum Efficiency Requirements (Continued)

Equipment TypeStandard
Model
Net Sensible
Cooling Capacity
Minimum Net
Sensible COP
Rating Conditions
Return Air
(dry bulb/dew point)
Test Procedure
Water cooled with_fluid_
economizer
Ducted<29,000 Btu/h2.3375°F/52°F (Class 1)AHRI 1360
Water cooled with_fluid_
economizer
Ducted29,000 Btu/h and
<65,000 Btu/h
2.232.232.23
Water cooled with_fluid_
economizer
Ducted65,000 Btu/h2.132.132.13
Water cooled with_fluid_
economizer
Nonducted<29,000 Btu/h2.362.362.36
Water cooled with_fluid_
economizer
Nonducted29,000 Btu/h and
<65,000 Btu/h
2.262.262.26
Water cooled with_fluid_
economizer
Nonducted65,000 Btu/h2.162.162.16
Glycol cooledDucted<29,000 Btu/h1.9775°F/52°F (Class 1)AHRI 1360
Glycol cooledDucted29,000 Btu/h and
<65,000 Btu/h
1.931.931.93
Glycol cooledDucted65,000 Btu/h1.781.781.78
Glycol cooledNonducted<29,000 Btu/h2.002.002.00
Glycol cooledNonducted29,000 Btu/h and
<65,000 Btu/h
1.981.981.98
Glycol cooledNonducted65,000 Btu/h1.811.811.81
Glycol cooled with
fluid economizer
Ducted<29,000 Btu/h1.9275°F/52°F (Class 1)AHRI 1360
Glycol cooled with
fluid economizer
Ducted29,000 Btu/h and
<65,000 Btu/h
1.881.881.88
Glycol cooled with
fluid economizer
Ducted65,000 Btu/h1.731.731.73
Glycol cooled with
fluid economizer
Nonducted<29,000 Btu/h1.951.951.95
Glycol cooled with
fluid economizer
Nonducted29,000 Btu/h and
<65,000 Btu/h
1.931.931.93
Glycol cooled with
fluid economizer
Nonducted65,000 Btu/h1.761.761.76

Table 6.8.1-18 Walk-In Cooler and Freezer Display Door Efficiency Requirements

Class DescriptorClassMaximum Energy
Consumption, kWh/daya
Test Procedure
Display door, medium temperatureDD, M0.04 ×Add + 0.4110 CFR 431
Display door, low temperatureDD, L0.15 ×Add + 0.2910 CFR 431

a. Add is the surface area (ft [2] ) of the display door.

Table 6.8.1-19 Walk-In Cooler and Freezer Nondisplay Door Efficiency Requirements

Class DescriptorClassMaximum Energy
Consumption, kWh/daya
Test Procedure
Passage door, medium temperaturePD, M0.05 ×And + 1.710 CFR 431
Passage door, low temperaturePD, L0.14 ×And + 4.810 CFR 431
Freight door, medium temperatureFD, M0.04 ×And + 1.910 CFR 431
Freight door, low temperatureFD, L0.12_And_ + 5.610 CFR 431

a. And is the surface area (ft [2] ) of the non-display door.

134 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 137

Open page note

Table 6.8.1-20 Walk-In Cooler and Freezer Refrigeration System Efficiency Requirements

Class DescriptorClassMinimum Annual
Walk-In Energy Factor AWEF,
Btu/W·h a
Test
Procedure
Compliance Date:
Equipment Manufactured
Starting On
Dedicated condensing, medium
temperature, indoor system
DC.M.I5.61AHRI 1250June 5, 2017
Dedicated condensing, medium
temperature, outdoor system
DC.M.O7.60AHRI 1250June 5, 2017
Dedicated condensing, low
temperature, indoor system, net
capacity (qnet) < 6500 Btu/h
DC.L.I
<6500 Btu/h
9.091 × 10–5 ×qnet + 1.81AHRI 1250July 10, 2020
Dedicated condensing, low
temperature, indoor system, net
capacity (qnet)  6500 Btu/h
DC.L.I,
6500 Btu/h
2.40AHRI 1250July 10, 2020
Dedicated condensing, low
temperature, outdoor system, net
capacity (qnet) < 6500 Btu/h
DC.L.O,
<6500 Btu/h
6.522 × 10–5 ×qnet + 2.73AHRI 1250July 10, 2020
Dedicated condensing, low
temperature, outdoor system, net
capacity (qnet) 6500 Btu/h
DC.L.O,
6500 Btu/h
3.15AHRI 1250July 10, 2020
Unit cooler, mediumUC.M9.00AHRI 1250July 10, 2020
Unit cooler, low temperature, net
capacity (qnet) < 15,500 Btu/h
UC.L,
<15,500 Btu/h
1.575 × 10–5 ×qnet + 3.91AHRI 1250July 10, 2020
Unit cooler, low temperature, net
capacity (qnet)  15,500 Btu/h
UC.L,
15,500 Btu/h
4.15AHRI 1250July 10, 2020

a. qnet is net capacity (Btu/h) as determined in accordance with AHRI 1250.

Table 6.8.1-21 Ceiling FanEfficiency Requirements aCol3Col4
Equipment TypeSize CategoryMinimum EfficiencybTest Procedurec
Large-diameter ceiling fan
for applications outside the
U.S.
Blade span ≥ 84.5 in.CFEI ≥ 1.00 at high (maximum) speed; and
CFEI ≥ 1.31 at 40% of high speed or the nearest
speed that is not less than 40% of high speed
10 CFR 430 Appendix U
or AMCA Standard 230
and AMCA Standard 208

a. The minimum efficiency requirements at both high speed and 40% of maximum speed must be met or exceeded to comply with this standard. b. Ceiling fans are regulated in the U.S. as consumer products under 10 CFR 430. For U.S. applications of large-diameter ceiling fans, refer to Informative Appendix F, Table F-6,

for the U.S. DOE minimum efficiency requirements. c. Section 13 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 135

PDF Page 138

Open page note

Table 6.8.2 Minimum Duct Insulation R-Value [a]

Climate Zone

Duct Location

Exterior [ b] Unconditioned Space and Buried Ducts Indirectly Conditioned Space [ c,d]

Supply and Return Ducts for Heating and Cooling

0 to 4 R-8 R-6 R-1.9

5 to 8 R-12 R-6 R-1.9

Supply and Return Ducts for Heating Only

0 to 1 None None None

2 to 4 R-6 R-6 R-1.9

5 to 8 R-12 R-6 R-1.9

Supply and Return Ducts for Cooling Only

0 to 6 R-8 R-6 R-1.9

7 to 8 R-1.9 R-1.9 R-1.9

a. Insulation R-values, measured in h·ft [2] ·°F/Btu, are for the insulation as installed and do not include film resistance. The required minimum thicknesses

do not consider water vapor transmission and possible surface condensation. Where portions of the building envelope are used as a plenum enclosure, building envelope insulation shall be as required by the most restrictive condition of Section 6.4.4.1 or Section 5, depending on whether the plenum is located in the roof, wall, or floor . Insulation resistance measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75°F at the installed thickness. b. Includes attics above insulated ceilings, parking garages and crawl spaces . c. Includes return air plenums with or without exposed roofs above. d. Return ducts in this duct location do not require insulation.

Table 6.8.3-1 Minimum Piping Insulation Thickness Heating and Hot-Water Systems [a,b,c,d] []

(Steam, Steam Condensate, Hot-Water Heating and Domestic Water Systems)

Insulation Thermal ConductivityNominal Pipe or Tube Size, in.

Fluid Operating Temperature Range (F)

and Usage

Conductivity, Btu·in/h·ft [2] ·F

Mean Rating Temperature,F

<1 1 to <1-1/2 1-1/2 to <4 4 to <88

Insulation Thickness, in.

350 0.32 to 0.34 250 4.5 5.0 5.0 5.0 5.0

251 to 350 0.29 to 0.32 200 3.0 4.0 4.5 4.5 4.5

201 to 250 0.27 to 0.30 150 2.5 2.5 2.5 3.0 3.0

141 to 200 0.25 to 0.29 125 1.5 1.5 2.0 2.0 2.0

105 to 140 0.22 to 0.28 100 1.0 1.0 1.5 1.5 1.5

For service water heating systems, see Table 7.4-2.

a. These thicknesses are based on energy efficiency considerations only. Additional insulation is sometimes required relative to safety issues/surface temperature. b. For piping smaller than 1.5 in. and located in partitions within conditioned spaces, reduction of these thicknesses by 1 in. shall be permitted (before thickness adjustment required

in footnote [a]) but not to thicknesses below 1 in. c. For direct-buried heating and hot-water system piping, reduction of these thicknesses by 1.5 in. shall be permitted (before thickness adjustment required in footnote [a]) but not

to thicknesses below 1 in. d. Piping that also serves service water heating systems shall comply with Section 7.4.

Table 6.8.3-2 Minimum Piping Insulation Thickness Cooling Systems (Chilled Water, Brine, and Refrigerant) [a,b]

Insulation Thermal Conductivity Nominal Pipe or Tube Size, in.

Fluid Operating

Temperature Range (F) and Usage

<1 1 to <1-1/2 1-1/2 to <4 4 to <88

Insulation Thickness, in.

Conductivity, Btu·in/h·ft [2] ·F

Mean Rating Temperature,F

40 to 60 0.21 to 0.27 75 0.5 0.5 1.0 1.0 1.0

<40 0.20 to 0.26 50 0.5 1.0 1.0 1.0 1.5

a. These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders or addi tional insulation. b. For direct-buried cooling system piping, insulation is not required.

136 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 139

Open page note

7. SERVICE WATER HEATING

7.1 General 7.1.1 Service Water-Heating Scope. Section 7 specifies requirements for service water-heating systems and equipment.

7.1.2 New Buildings. Service water-heating systems and equipment shall comply with the requirements of Section 7.2.

7.1.3 Additions to Existing Buildings. Service water-heating systems and equipment shall comply with the requirements of Section 7.2.

Exception to 7.1.3: When the service water heating to an addition is provided by existing service

water-heating systems and equipment, such systems and equipment shall not be required to comply with this standard. However, any new systems or equipment installed must comply with specific requirements applicable to those systems and equipment .

7.1.4 Alterations to Service Water-Heating Systems and Equipment. Building service water heating equipment installed as a direct replacement for existing building service water heating equipment shall comply with the requirements of Section 7 applicable to the equipment being replaced. New and replacement piping shall comply with Section 7.4.3.

Exception to 7.1.4: Compliance shall not be required where there is insufficient space or access to meet

these requirements.

7.2 Compliance Paths. Service water heating systems and equipment shall comply with Sections 7.2.1 and 7.2.2. 7.2.1 Requirements for All Compliance Paths. Service water heating systems and equipment shall comply with Sections 7.1, “General”; 7.4, “Mandatory Provisions”; 7.7, “Submittals”; and 7.8, “Product Information.”

7.2.2 Additional Requirements to Comply with Section 7. Service water heating systems and equip- ment shall comply with Section 7.5, “Prescriptive Compliance Path.”

7.3 Simplified Building Compliance Path (Not Used)

7.4 Mandatory Provisions 7.4.1 Load Calculations. Service water heating system design loads for the purpose of sizing systems and equipment shall be determined in accordance with the manufacturer ’s published sizing guidelines or

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 137

PDF Page 140

Open page note

generally accepted engineering standards and handbooks acceptable to the adopting authority (e.g., ASHRAE Handbook—HVAC Applications ).

7.4.2 Equipment Efficiency. All water-heating equipment, hot-water supply boilers used solely for heating potable water, pool heaters, and hot-water storage tanks shall meet the criteria listed in Table 7.4-1. Where multiple criteria are listed, all criteria shall be met. Omission of minimum performance requirements for certain classes of equipment does not preclude use of such equipment where appropriate. Equipment not listed in Table 7.4-1 has no minimum performance requirements.

Exceptions to 7.4.2: All water heaters and hot-water supply boilers having more than 140 gal of storage

capacity are not required to meet the standby loss (SL) requirements of Table 7.4-1 when

  1. the tank surface is thermally insulated to R-12.5,
  2. a standing pilot light is not installed, and
  3. gas- or oil-fired storage water heaters have a flue damper or fan-assisted combustion.

7.4.3 Service Water Heating System Piping Insulation. Service water heating system piping shall be surrounded by uncompressed insulation of the thickness shown in Table 7.4-2. When the insulation thermal conductivity is not within the range in the table, the following equation shall be used to calculate the minimum insulation thickness:

talt = r [(1 + ttable / r ) × kalt / kupper - 1]

where talt = minimum insulation thickness of the alternate material, in. r = actual outside radius of pipe, in. ttable = insulation thickness listed in Table 7.4-2 for applicable fluid temperature and pipe size kalt = thermal conductivity of the alternate material at mean rating temperature indicated for the applicable fluid temperature, Btu·in/h·ft [2] ·°F kupper = upper value of the thermal conductivity range listed in this table for the applicable fluid temperature, Btu·in/h·ft [2] ·°F Exception to 7.4.3: For nonmetallic piping thicker than Schedule 80 and having thermal resistance

greater than that of steel pipe, reduced insulation thicknesses are permitted if documentation is provided showing that the pipe with the proposed insulation has no more heat transfer per foot than a steel pipe of the same size with the insulation thickness shown in the table.

7.4.3.1 The following piping shall be insulated per the requirements of this section:

a. Recirculating system piping, including the supply and return piping b. The first 8 ft of outlet piping from

  1. storage water heaters,
  2. hot-water storage tanks, and
  3. any water heater and hot-water supply boiler containing 10 gal or more of water heated by a direct heat source, an indirect heat source, or both a direct heat source and an indirect heat source. c. The first 8 ft of branch piping connecting to recirculated, heat traced, or impedance heated piping. d. The make-up water inlet piping between heat traps (see Section 7.4.6) and the storage water heaters and

the storage tank they are serving, in a nonrecirculating service water heating system . e. Hot-water piping between multiple water heaters, between multiple hot-water storage tanks, and

between water heaters and hot-water storage tanks. f. Piping that is externally heated (such as heat trace or impedance heating).

Exceptions to 7.4.3.1:

  1. Factory-installed piping within water heaters and hot-water storage tanks tested and rated in accordance with Section 6.4.1.
  2. Piping that conveys hot water that has not been heated through the use of fossil fuels or electricity.
  3. For piping 1 in. or less, insulation is not required for valves or strainers.
  4. Piping in existing buildings where alterations are made to existing service water heating systems where there is insufficient space or access to meet the requirements.
  5. Insulation is not required at the point where piping passes through a framing member if it requires increasing the size of the framing member.
  6. Insulation is not required on piping at the point where a vertical support of the piping is installed.

138 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 141

Open page note

Table 7.4-1 Performance Requirements for Water-Heating Equipment—Minimum Efficiency Requirements

Equipment TypeSize Category
(Input)
Subcategory or
Rating Condition
Performance Required aTest
Procedureb,c
Electric table-top
water heaters
12_kW_<4000 (Btu/h)/gal
20 gal and120 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Electric storage
water heaters
12_kW_<4000 (Btu/h)/gal
20 gal and55 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Electric storage
water heaters
12_kW_<4000 (Btu/h)/gal
>55 gal and120 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Electric storage
water heaters
>12_kW_<4000 (Btu/h)/galSL  0.3 + 27/Vm %/h10 CFR 431.106
Electric
instantaneous_water_
heaters
12_kW_4000 (Btu/h)/gal
<2 gal
For applications outside US, see footnote (h).
For US applications, see footnote (g).
10 CFR 430
Appendix E
Electric
instantaneous_water_
heaters
>12_kW_ and
58.6_kW_ c
4000 (Btu/h)/gal
2 gal
180°F
Very small DP: UEF = 0.80
Low DP: UEF = 0.80
Medium DP: UEF = 0.80
High DP: UEF = 0.80
10 CFR 430
Appendix E
Electric
instantaneous_water_
heaters
58.6_kW_ c4000 (Btu/h)/gal
<10 gal
No requirementNo requirement
Electric
instantaneous_water_
heaters
58.6_kW_ c4000 (Btu/h)/gal
10 gal
No requirementNo requirement
Gas storage
water heaters
75,000 Btu/h<4000 (Btu/h)/gal
20 gal and55 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Gas storage
water heaters
75,000 Btu/h<4000 (Btu/h)/gal
>55 gal and100 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Gas storage
water heaters
>75,000 Btu/h and
105,000 Btu/h d
<4000 (Btu/h)/gal
120 gal
180°F
Very small DP: UEF = 0.2674 – (0.0009 ×Vr)
Low DP: UEF = 0.5362 – (0.0012 ×Vr)
Medium DP: UEF = 0.6002 – (0.0011 ×Vr)
High DP: UEF = 0.6597 – (0.0009 ×Vr)
10 CFR 430
Appendix E
Gas storage
water heaters
>105,000 Btu/h d,f<4000 (Btu/h)/gal80%_Et _
SL(Q/800 + 110
), Btu/h
V
10 CFR 431.106
Gas instantaneous
water heaters
>50,000 Btu/h and
200,000 Btu/h
4000 (Btu/h)/gal
<2 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Gas instantaneous
water heaters
200,000 Btu/h d,f4000 (Btu/h)/gal
<10 gal
80%Et10 CFR 431.106
Gas instantaneous
water heaters
200,000 Btu/h f4000 (Btu/h)/gal
10 gal
80%Et
SL(Q/800 + 110
), Btu/h
V
80%Et
SL(Q/800 + 110
), Btu/h
V
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 139

PDF Page 142

Open page note

Table 7.4-1 Performance Requirements for Water-Heating Equipment—Minimum Efficiency Requirements (Continued)

Equipment TypeSize Category
(Input)
Subcategory or
Rating Condition
Performance Required aTest
Procedureb,c
Oil storage
water heaters
105,000 Btu/h<4000(Btu/h)/gal
50 gal
For applications outside U.S., see footnote (h).
For U.S. applications, see footnote (g).
10 CFR 430
Appendix E
Oil storage
water heaters
105,000 Btu/h and
140,000 Btu/h e
120 gal
<4000 (Btu/h)/gal
180°F
Very small DP: UEF = 0.2932 – (0.0015 ×Vr)
Low DP: UEF = 0.5596 – (0.0018 ×Vr)
Medium DP: UEF = 0.6194 – (0.0016 ×Vr)
High DP: UEF = 0.6740 – (0.0013 ×Vr)
10 CFR 430
Appendix E
Oil storage
water heaters
>140,000 Btu/h<4000 (Btu/h)/gal80%Et
SL(Q/800 + 110
), Btu/h
V
10 CFR 431.106
Oil instantaneous
water heaters
210,000 Btu/h4000 (Btu/h)/gal
<2 gal
80%Et
EF  0.59 – 0.0005 ×V
10 CFR 430
Appendix E
Oil instantaneous
water heaters
>210,000 Btu/h4000 (Btu/h)/gal
<10 gal
80%Et10 CFR 431.106
Oil instantaneous
water heaters
>210,000 Btu/h4000 (Btu/h)/gal
10 gal
78%_Et _
SL(Q/800 + 110
), Btu/h
V
78%_Et _
SL(Q/800 + 110
), Btu/h
V
Hot-water supply
boilers, gas and oil f
300,000 Btu/h and
<12,500,000 Btu/h
4000 (Btu/h)/gal
<10 gal
80%Et10 CFR 431.106
Hot-water supply
boilers, gas f
300,000 Btu/h and
<12,500,000 Btu/h
4000 (Btu/h)/gal
10 gal
80%Et
SL(Q/800 + 110
), Btu/h
V
10 CFR 431.106
Hot-water supply
boilers, oil
300,000 Btu/h and
<12,500,000 Btu/h
4000 (Btu/h)/gal
10 gal
78%Et
SL(Q/800 + 110
), Btu/h
V
10 CFR 431.106
Pool heaters, gasAll82%Et for commercial_pool_ heaters and for
applications outside U.S. For U.S.
applications, see footnote (g).
10 CFR 430
Appendix P
Heat pump_pool_
heaters
All50°F db 44.2°F wb
outdoor air
80.0°F entering water
4.0_COP_10 CFR 430
Appendix P
Unfired storage tanksAllR-12.5(none)
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.
a. Thermal_efficiency_ (Et) is a minimum requirement, while standby loss is a maximum requirement. In the standby loss equation,V is the rated volume in gallons and_Q_ is the name-
plate input rate in Btu/h.Vm is the measured volume in the tank in gallons. Standby loss for electric water heaters is in terms of %/h and denoted by the term “S,” and standby loss
for gas and oil water heaters is in terms of Btu/h and denoted by the term “SL.” Draw pattern (DP) refers to the water draw profile in the uniform_energy factor_ (UEF) test. UEF
and_energy factor_ (EF) are minimum requirements. In the UEF standard equations,Vr refers to the rated volume in gallons.
b. Section 13 contains a complete specification, including the year version, of the referenced test procedure.
c. Electric instantaneous water heaters with input capacity >12 kW and58.6 kW must comply with the requirements for the 58.6 kW if the water heater either (1) has a storage volume
>2 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power.
d. Gas storage water heaters with input capacity >75,000 Btu/h and105,000 Btu/h must comply with the requirements for the >105,000 Btu/h if the water heater either (1) has a
storage volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
e. Oil storage water heaters with input capacity >105,000 Btu/h and140,000 Btu/h must comply with the requirements for the >140,000 Btu/h if the water heater either (1) has a storage
volume >120 gal; (2) is designed to provide outlet hot water at temperatures greater than 180°F; or (3) uses three-phase power
f. Refer to Section 7.5.3 for additional requirements for gas storage and instantaneous_water heaters_ and gas_hot-water supply boilers_.
g. Water heaters or gas_pool_ heaters in this category or subcategory are regulated as consumer products by the U.S. DOE as defined in 10 CFR 430.
h. Where this standard is being applied to a building outside the U.S. and Canada and water heaters in this subcategory are being installed in that building, those water heaters shall
meet the local efficiency requirements. If there are no local efficiency standards for residential water heaters, consideration should be given to using the U.S. DOE efficiency require-
ments shown in Informative Appendix F, Table F-2.

140 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 143

Open page note

Table 7.4-2 Minimum Piping Insulation Thickness for Service Water Heating Systems [ a,b]

Service Hot-Water
Temperature Range
Insulation Thermal ConductivityCol3Nominal Pipe or Tube Size, in.Col5Col6Col7Col8
Service Hot-Water
Temperature Range
Conductivity,
Btu·in/h·ft2·°F
Mean Rating
Temperature, °F
<11 to <1-1/21-1/2 to <44 to <8≥8
Service Hot-Water
Temperature Range
Conductivity,
Btu·in/h·ft2·°F
Mean Rating
Temperature, °F
Insulation Thickness, in.Insulation Thickness, in.Insulation Thickness, in.Insulation Thickness, in.Insulation Thickness, in.

Service Water Heating System Piping not Located in Partitions within Conditioned Spaces

105°F to 140°F0.22 to 0.281001.01.01.52.02.0
>140°F to 200°F0.25 to 0.291251.51.52.52.52.5
>200°F0.27 to 0.301502.52.53.03.03.0

Service Water Heating System Piping Located in Partitions within Conditioned Spaces

105°F to 140°F0.22 to 0.281001.01.01.51.51.5
>140°F to 200°F0.25 to 0.291251.01.02.02.02.0
>200°F0.27 to 0.301501.51.52.53.03.0

a. These thicknesses are based on energy efficiency considerations only. Additional insulation may be necessary for safety. b. For direct-buried service water heating system piping, reduction of these thicknesses by 1.5 in. shall be permitted (before thickness adjustment required in Section 7.4.3 but not

to thicknesses less than 1 in.).

7.4.4 Service Water-Heating System Controls Informative Note: Service water heating system control settings and operating temperatures should be determined in accordance with the ASHRAE Standard 188 building water systems water management program for the building, or with generally accepted engineering standards and guidance (e.g., ASHRAE Guideline 12).

7.4.4.1 Temperature Controls. Temperature controls shall be provided that allow for storage temperature adjustment from 120°F or lower to a maximum temperature compatible with the intended use.

Exception to 7.4.4.1: When the manufacturers ’ installation instructions specify a higher minimum ther-

mostat setting to minimize condensation and resulting corrosion.

7.4.4.2 Temperature Maintenance Controls. Systems designed to maintain usage temperatures in hotwater pipes, such as recirculating hot-water systems or heat trace, shall be equipped with automatic time switches or other controls that can be set to switch off the usage temperature maintenance system during extended periods when hot water is not required.

7.4.4.3 Outlet Temperature Controls. Temperature controlling means shall be provided to limit the maximum temperature of water delivered from lavatory faucets in public facility restrooms to 110°F.

7.4.4.4 Circulating Pump Controls. When used to maintain storage tank water temperature, recirculating pumps shall be equipped with controls limiting operation to a period from the start of the heating cycle to a maximum of five minutes after the end of the heating cycle.

7.4.5 Pools 7.4.5.1 Pool Heaters. Pool heaters shall be equipped with a readily accessible on/off switch to allow shutting off the heater without adjusting the thermostat setting. Pool heaters fired by natural gas shall not have continuously burning pilot lights.

7.4.5.2 Pool Covers. Heated pools shall be equipped with a vapor retardant pool cover on or at the water surface. Pools heated to more than 90°F shall have a pool cover with a minimum insulation value of R-12.

Exception to 7.4.5.2: Pools deriving over 60% of the energy for heating from site-recovered energy or

on-site renewable energy .

7.4.5.3 Time Switches. Time switches shall be installed on swimming pool heaters and pumps . Exceptions to 7.4.5.3:

  1. Where public health standards require 24-hour pump operation.
  2. Where pumps are required to operate solar and waste heat recovery pool heating systems.

7.4.6 Heat Traps. Vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and serving a nonrecirculating system shall have heat traps on both the inlet and outlet piping as close as practical to the storage tank. A heat trap is a means to counteract the natural convection of heated water in a vertical pipe run. The means is either (a) a device specifically designed for the purpose or an

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 141

PDF Page 144

Open page note

arrangement of tubing that forms a loop of 360 degrees, or (b) piping that from the point of connection to the water heater (inlet or outlet) includes a length of piping directed downward before connection to the vertical piping of the supply water or hot-water distribution system, as applicable.

7.5 Prescriptive Compliance Path 7.5.1 Space Heating and Service Water Heating. The use of a gas-fired or oil-fired space -heating boiler system otherwise complying with Section 6 to provide the total space heating and service water heating for a building is allowed when one of the following conditions is met:

a. The single space -heating boiler, or the component of a modular or multiple boiler system that is heating

the service water, has a standby loss in Btu/h not exceeding

(13.3  pmd + 400)/ n where pmd is the probable maximum demand in gal/h determined in accordance with the procedures described in generally accepted engineering standards and handbooks, and n is the fraction of the year when the outdoor daily mean temperature is greater than 64.9°F.

The standby loss is to be determined for a test period of 24 hours duration while maintaining a boiler water temperature of at least 90°F above ambient, with an ambient temperature between 60°F and 90°F. For a boiler with a modulating burner, this test shall be conducted at the lowest input. b. It is demonstrated to the satisfaction of the authority having jurisdiction that the use of a single heat

source will consume less energy than separate units. c. The energy input of the combined boiler and water heater system is less than 150,000 Btu/h.

7.5.2 Service Water-Heating Equipment. Service water-heating equipment used to provide the additional function of space heating as part of a combination (integrated) system shall satisfy all stated requirements for the service water-heating equipment .

7.5.3 Large Service Water-Heating Systems. New buildings with service water-heating systems with a total installed input capacity of 1,000,000 Btu/h or greater, provided by high-capacity gas-fired service water-heating equipment, shall meet either or both of the following requirements:

a. Where a single unit of high-capacity gas-fired service water-heating equipment is installed, it shall have

a minimum thermal efficiency ( Et ) of 92%. b. Multiple units of high-capacity gas-fired service water-heating equipment connected to the same service

water-heating system shall have a total input capacity-weighted average thermal efficiency ( Et ) of at least 90%, and a minimum of 30% of the input of the high-capacity gas-fired service water-heating equipment in the service water heating-system shall have a thermal efficiency ( Et ) of at least 92%.

High-capacity gas-fired service water-heating equipment comprises gas-fired instantaneous water heat- ers with a rated input both greater than 200,000 Btu/h and not less than 4000 Btu/h per gallon of stored water, and gas-fired storage water heaters with a rated input both greater than 105,000 Btu/h and less than 4000 Btu/h per gallon of stored water. Exceptions to 7.5.3:

  1. Water heaters installed in individual dwelling units .
  2. Individual gas water heaters with input capacity not greater than 100,000 Btu/h.

7.6 Alternative Compliance Path (Not Used)

7.7 Submittals 7.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

7.7.2 Permit Application Documentation (Not Used) 7.7.3 Completion Requirements 7.7.3.1 Record Documents. Construction documents shall require that, within 90 days after the date of building envelope acceptance, record documents be provided to the building owner or the designated representative of the building owner.

7.7.3.2 Manuals. Construction documents shall require that an operating manual and a maintenance manual be provided to the building owner, or the designated representative of the building owner, within 90 days after the date of system acceptance. These manuals shall be in accordance with industry-accepted standards and shall include, at a minimum, operation manuals and maintenance manuals for each component of the system requiring maintenance, except components not furnished as part of the project. Required routine maintenance actions shall be clearly identified.

142 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 145

Open page note

7.8 Product Information

7.9 Verification, Testing, and Commissioning 7.9.1 Verification and Testing. Service hot-water controls shall be verified and tested in accordance with this section and Section 4.2.5.1. Testing shall verify that systems and controls are configured and operating in accordance with applicable requirements of

a. service water heating system temperature controls (Sections 7.4.4.1 and 7.4.4.3), b. recirculation pump or heat trace controls (Section 7.4.4.2), or c. pool time switch controls (Section 7.4.5.3).

Verification and FPT documentation shall comply with Section 4.2.5.1.2. 7.9.2 Commissioning. The energy performance of the service water heating systems shall be commis- sioned in accordance with Section 4.2.5.2, and reporting shall comply with Section 4.2.5.2.2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 143

PDF Page 146

Open page note

8. POWER

8.1 General

8.1.1 Scope. This section applies to all building power distribution systems and only to equipment described below.

8.1.2 New Building or Site System or Equipment. Building power distribution equipment installed shall comply with the requirements of Section 8.2.

8.1.3 Addition to Existing Systems and Equipment. Building power distribution equipment installed in addition to existing buildings and existing sites shall comply with the requirements of Section 8.2.

8.1.4 Alterations to Existing Service Equipment or Systems

Exception to 8.1.4: Compliance shall not be required for the relocation or reuse of existing equipment at

the same site .

8.1.4.1 Alterations to building service equipment shall comply with the requirements of Section 8, as applicable to those specific portions of the building that are being altered.

8.1.4.2 Alterations to systems shall comply with the requirements of Section 8, as applicable to those specific portions that are being altered.

8.1.4.3 Any new equipment subject to the requirements of Section 8 that is installed in conjunction with the alterations as a direct replacement of existing equipment shall comply with the specific requirements, as applicable to that equipment .

8.2 Compliance Paths. Power distribution systems and equipment shall comply with Sections 8.2.1 and 8.2.2.

8.2.1 Requirements for All Compliance Paths. Power distribution systems and equipment only shall comply with Sections 8.1, “General”; 8.4, “Mandatory Provisions”; and 8.7, “Submittals.”

Exception to 8.2.1: Power distribution systems and equipment only serving a computer room with IT

equipment load greater than 10 kW shall be permitted to comply with Section 8.6, “Alternative Compliance Path.”

8.2.2 Additional Requirements to Comply with Section 8 (Not Used)

8.3 Simplified Building Compliance Path (Not Used)

8.4 Mandatory Provisions

144 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 147

Open page note

8.4.1 Voltage Drop. The feeder conductors and branch circuits combined shall be sized for a maximum of 5% voltage drop total.

8.4.2 Automatic Receptacle Control. The following shall be automatically controlled:

a. At least 50% of all 125 V, 15 and 20 amp receptacles in all private offices, conference rooms, rooms used

primarily for printing and/or copying functions, break rooms, classrooms, and individual workstations. b. At least 25% of branch circuit feeders installed for modular furniture not shown on the construction doc-

uments.

This control shall function on

a. a scheduled basis using a time-of-day operated control device that turns receptacles off at specific pro grammed times—an independent program schedule shall be provided for controlled areas of no more than 5000 ft [2] and not more than one floor (the occupant shall be able to manually override the control device for up to two hours); b. an occupancy sensor that shall turn receptacles off within 20 minutes of all occupants leaving a space ; or c. an automated signal from another control or alarm system that shall turn receptacles off within 20 min utes after determining that the area is unoccupied.

All controlled receptacles shall be permanently marked to visually differentiate them from uncontrolled receptacles and are to be uniformly distributed throughout the space . Plug-in devices shall not be used to comply with Section 8.4.2.

Exceptions to 8.4.2: Receptacles for the following shall not require an automatic control device :

  1. Receptacles specifically designated for equipment requiring continuous operation (24/day, 365 days/year).
  2. Spaces where an automatic control would endanger the safety or security of the room or building occupants.

8.4.3 Electrical Energy Monitoring 8.4.3.1 Monitoring. Measurement devices shall be installed in new buildings to monitor the electrical energy use for each of the following separately:

a. Total electrical energy b. HVAC systems c. Interior lighting d. Exterior lighting e. Receptacle circuits f. Refrigeration systems

For buildings with tenants, these systems shall be separately monitored for the total building and (excluding shared systems ) for each individual tenant.

Exception to 8.4.3.1: Where the design load of any of the categories (b) through (f) are less than 10% of

the whole-building load, these categories shall be allowed to be combined with other categories.

8.4.3.2 Recording and Reporting. The electrical energy use for all loads specified in Section 8.4.3.1 shall be recorded a minimum of every 15 minutes and reported at least hourly, daily, monthly, and annually. The data for each tenant space shall be made available to that tenant. In buildings with a digital control sys- tem installed to comply with Section 6.4.3.10, the energy use data shall be transmitted to the digital control system and graphically displayed. The system shall be capable of maintaining all data collected for a minimum of 36 months.

Exceptions to 8.4.3.1 and 8.4.3.2:

  1. Building less than 25,000 ft [2] .
  2. Individual tenant spaces less than 10,000 ft [2] .
  3. Dwelling units .
  4. Residential buildings with less than 10,000 ft [2] of common area.
  5. Critical equipment and life-safety branches of NFPA 70, Article 517.

8.4.4 Low-Voltage Dry-Type Distribution Transformers. Low-voltage dry-type distribution transform- ers shall comply with the requirements shown in Table 8.4.4. Transformers that are not included in the definition of distribution transformers as defined in 10 CFR 431.192 have no performance requirements in this section and are listed for ease of reference as exceptions.

Exception to 8.4.4: Transformers that meet any of the following exclusions in the U.S. DOE definition of

“distribution transformers” found in 10 CFR 431.192:

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 145

PDF Page 148

Open page note

Table 8.4.4 Minimum Nominal Efficiency Levels for Low-Voltage Dry-Type Distribution Transformers [ a,b]

Single-Phase TransformersCol2Three-Phase TransformersCol4
kVA cEfficiency,% dkVA cEfficiency,% d
1597.701597.89
2598.003098.23
37.598.204598.40
5098.307598.60
7598.50112.598.74
10098.6015098.83
16798.7022598.94
25098.8030099.02
33398.9050099.14
75099.23
100099.28

a. A low-voltage dry-type distribution transformer is a transformer that is air-cooled, does not use oil as a coolant, has an input voltage  600 V, and is rated

for operation at a frequency of 60 Hz. b. A low-voltage dry-type distribution transformer with a kVA rating not listed in the table shall have its minimum efficiency level determined by linear

interpolation of the kVA and efficiency values listed in the table immediately above and below its kVA rating. Extrapolation shall not be used below the minimum values or above the maximum values shown for single-phase transformers and three-phase transformers . b. Kilovolt-ampere rating. c. Nominal efficiencies shall be established in accordance with the 10 CFR 431.193 test procedure for low-voltage dry-type distribution transformers .

  1. Transformers with tap range of 20% or more.
  2. Drive (isolation) transformer .
  3. Rectifier transformer .
  4. Auto- transformer .
  5. Uninterruptible power supply transformer .
  6. Special impedance transformer .
  7. Regulating transformer .
  8. Sealed and nonventilating transformer .
  9. Machine-tool (control) transformer .
  10. Welding transformer .
  11. Grounding transformer .
  12. Testing transformer .
  13. Nonventilated transformer.

8.5 Prescriptive Path (Not Used)

8.6 Alternative Compliance Path 8.6.1 Computer Room Systems. Power distribution systems and equipment only serving a computer room with IT equipment load greater than 10 kW shall comply with ASHRAE Standard 90.4, Energy Stan- dard for Data Centers.

8.7 Submittals 8.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

8.7.2 Permit Application Documentation (Not Used) 8.7.3 Completion Requirements 8.7.3.1 Record Documents. Construction documents shall require that within 90 days after the date of system acceptance, record documents shall be provided to the property owner, including

a. a single-line diagram of the property electrical distribution system, b. floor plans indicating location and area served for all distribution, and c. site plans indicating location and area served for all distribution.

146 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 149

Open page note

8.7.3.2 Manuals. Construction documents shall require that an operating manual and maintenance manual be provided to the property owner. The manuals shall include, at a minimum, the following:

a. Submittal data stating equipment rating and selected options for each piece of equipment requiring main tenance. b. Operation manuals and maintenance manuals for each piece of equipment requiring maintenance.

Required routine maintenance actions shall be clearly identified. c. Names and addresses of at least one qualified service agency . d. A complete narrative of how each system is intended to operate.

Enforcement agencies should only check to ensure that the construction documents require this information to be transmitted to the owner and should not expect copies of any of the materials.

8.8 Product Information (Not Used)

8.9 Verification, Testing, and Commissioning 8.9.1 Verification and Testing. Building power distribution systems and applicable equipment shall be verified and tested in accordance with this section and provisions of Section 4.2.5.1. Testing shall verify that control elements are configured and operating in accordance with applicable requirements of

a. automatic receptacles controls (Section 8.4.2) and b. energy monitoring (Section 8.4.3).

Verification and FPT documentation shall comply with Section 4.2.5.1. 8.9.2 Commissioning. The energy performance of the power systems shall be commissioned in accordance with Section 4.2.5.2, and reporting shall comply with Section 4.2.5.2.2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 147

PDF Page 150

Open page note

9. LIGHTING

9.1 General 9.1.1 Scope 9.1.1.1 New Building or Site System or Equipment. Lighting equipment and systems serving the lighting needs of new buildings or new site systems and equipment shall comply with the requirements of this section as described in Section 9.2.

This section shall apply to the following:

a. Lighting equipment and systems serving interior spaces of buildings . b. Lighting equipment and systems serving exterior applications.

Exceptions to 9.1.1.1:

  1. Emergency lighting that is automatically off during normal operation.
  2. Lighting, including exit signs, that is specifically designated as required by a health or life safety statute, ordinance, or regulation.
  3. Decorative gas lighting systems . 9.1.1.2 Additions to Existing Systems and Equipment. Lighting equipment and systems installed in addition to existing buildings and existing sites shall comply with the requirements of Section 9.1.1.1.

9.1.1.3 Alterations to Existing Systems and Equipment. The alteration of lighting equipment and sys- tems in an interior space shall comply with Section 9.1.1.3.1. The alteration of a lighting system in an exterior application shall comply with Section 9.1.1.3.2.

The maintenance of an existing lighting system to return it to working order shall not be considered an alteration . Retrofitting a luminaire for which the original lamps and ballast/driver are replaced with a new lamp/light source and driver / ballast that was not a component of the original luminaire shall be considered an alteration .

9.1.1.3.1 Alterations for Interior Building Spaces. The alteration of a lighting system in an interior space shall meet one of the following requirements:

a. The alteration shall comply with Section 9.2 when the total wattage of all new and retrofitted luminaires

is greater than 2000 W. b. When the total wattage of all new and retrofitted luminaires is 2000 W or less, each altered space shall

comply with the LPA of Tables 9.5.2.1-1 and 9.5.2.1-2 and Section 9.5.2.2, or the alteration shall result

148 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 151

Open page note

in a new wattage at least 50% below the original wattage of each altered lighting system . Additionally, the new and retrofitted lighting shall comply with the control requirements of Sections 9.4.1.1(a), 9.4.1.1(h), 9.4.1.1(i) as applicable to each altered space as shown in Tables 9.5.2.1-1 and 9.5.2.1-2 and Section 9.5.2.2.

9.1.1.3.2 Lighting Alterations for Exterior Building Areas. The alteration of a lighting system for an exterior area shall use only the area-specific allowances in Table 9.4.2-2 and shall not use the base site allowances to determine the LPA . Additionally, the exterior alteration shall meet one of the following:

a. The alteration shall comply with Section 9.2 when the total number of new and retrofitted luminaires is

greater than 10 or where the combined length of new and retrofitted linear luminaires is greater than 20 linear feet. b. Where the total number of new and retrofitted luminaires is not greater than 10, or where the combined

length of new and retrofitted linear luminaires is not greater than 20 linear feet of linear luminaires, the total wattage of the alteration shall be no greater than the maximum LPA permitted by Table 9.4.2-2, or the total new wattage shall be at least 50% below the total original wattage of that lighting system . Additionally, the new and retrofitted lighting shall comply with the control requirements of Section 9.4.1.4(a).

9.1.2 Climate. Climate zones shall be determined in accordance with Section 5.1.5. 9.1.3 Installed Lighting Power. The luminaire wattage for all interior and exterior applications shall include all power used by the luminaires, including lamps, ballasts / drivers, transformers, and control devices, except as specifically exempted in Section 9.1.1, 9.2.2.1, or 9.2.2.2.

Exception to 9.1.3: If two or more independently operating lighting systems in a space are capable of

being controlled to prevent simultaneous user operation, the installed interior lighting power or the installed exterior lighting power shall be based solely on the lighting system with the highest wattage.

9.1.4 Interior and Exterior Luminaire Wattage. The wattage of lighting equipment, when used to calculate either installed interior lighting power or installed exterior lighting power, shall be determined in accordance with the following criteria:

a. The wattage of lighting equipment connected to line voltage shall be the manufacturerslabeled maxi mum wattage. b. The wattage of line voltage lighting equipment with remote ballasts / drivers or similar devices shall be

the total input wattage of all line voltage components in the system . Exception to 9.1.4(b): Lighting power calculations for ballasts with adjustable ballast factors shall be

based on the ballast factor that will be used in the space, provided that the ballast factor is not user field-changeable. c. The wattage of line-voltage lighting track and plug-in busway designed to allow the addition and/or relo cation of lighting equipment without altering the wiring of the system shall be the lesser of

  1. the specified wattage of the lighting equipment included in the system with a minimum of 10 W/lin ft or
  2. the wattage limit of permanent current-limiting devices on the system . d. The wattage of low-voltage lighting track, cable conductor, rail conductor, and other flexible lighting

systems that allow the addition and/or relocation of lighting equipment without altering the wiring of the system shall be the specified wattage of the ballast/driver or transformer supplying the system . e. The wattage of a DC low-voltage lighting system that employs flexible cabling for plug-in connection of

the lighting equipment and a remote power supply shall be labeled maximum wattage of the system power supply. For systems that also provide power to equipment other than lighting, the wattage shall be labeled maximum wattage of the system power supply reduced by the wattage of the nonlighting equip- ment connected to the system . f. The wattage of a retrofitted luminaire shall be the manufacturer’s labeled input power of the new light source plus driver. g. The wattage of all other miscellaneous lighting equipment shall be the specified wattage of the lighting

equipment .

9.2 Compliance Paths. Lighting systems and equipment shall comply with Section 9.2.1. 9.2.1 Requirements for All Compliance Paths. Lighting systems and equipment shall comply with Sections 9.1 “General”; 9.7, “Submittals”; 9.9, “Verification, Testing, and Commissioning”; and one of the following:

a. Section 9.3, “Simplified Building Method Compliance Path” or b. Section 9.4, “Mandatory Provisions”, and Section 9.5.1, “Building Area Method Compliance Path” or

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 149

PDF Page 152

Open page note

c. Section 9.4, “Mandatory Provisions,” and Section 9.5.2, “Space-by-Space Method Compliance Path” or d. Section 9.4, “Mandatory Provisions,” and Section 9.6 “Alternative Compliance Path,” or e. Section 9.4, “Mandatory Provisions,” and Section 12, “Energy Cost Budget Method,” or f. Section 9.4, “Mandatory Provisions,” and Normative Appendix G, “Performance Rating Method.”

The installed lighting power identified in accordance with Section 9.1.3 shall not exceed the lighting power allowance developed in accordance with Section 9.2.1(a), (b), or (c).

9.2.2 Prescriptive Requirements 9.2.2.1 Interior Lighting Power Allowance. The interior lighting power allowance for a building or a separately metered or permitted portion of a building shall be determined by either Simplified Building Method described in Section 9.3, the Building Area Method described in Section 9.5.1, or the Space-by-Space Method described in Section 9.5.2.

Trade-offs of lighting power allowance among portions of the building for which a different calculation method has been used for compliance are not permitted.

Exception to 9.2.2.1: When using the compliance methods in Section 9.5.1 or 9.5.2 only, the lighting

equipment and applications listed in Table 9.2.2.1 shall not be considered when determining the inte- rior lighting power allowance developed in accordance with Section 9.5.1 or 9.5.2, nor shall the wattage for such lighting be included in the installed interior lighting power identified in accordance with Section 9.1.3. This exemption shall only apply when the lighting and controls are in compliance with the requirements of Table 9.2.2.1. Lighting controls noted in this table are the only required controls for this equipment and these applications.

9.2.2.2 Exterior Lighting Power Allowance. The exterior lighting power allowance shall be determined by

a. Section 9.3.2, “Simplified Building Method of Calculating Exterior Lighting Power Allowance,” when

using Section 9.3 to determine the interior lighting power allowance, or b. Section 9.4.2, “Exterior Lighting Power.”

9.3 Simplified Building Method Compliance Path. The Simplified Building Method contains the requirements for interior lighting in Section 9.3.1 and exterior lighting in Section 9.3.2 and shall be allowed to be used where at least 80% of the floor area supports either office buildings, retail buildings, or school buildings . The Simplified Building Method shall be used for new buildings or tenants improvements of less than 25,000 ft [2] . Interior and exterior wattage allowances shall be calculated and complied with separately.

9.3.1 Simplified Building Method of Calculating Interior Lighting Power Allowance. Buildings (new and alterations ) shall comply with the lighting power allowance and control requirements of Table 9.3.1-1, Table 9.3.1-2, or Table 9.3.1-3.

9.3.2 Simplified Building Method of Calculating Exterior Lighting Power Allowance. For all building types listed in Section 9.3, exterior areas (new and alterations ) shall comply with the lighting power allowance and control requirements of Table 9.3.2.

9.4 Mandatory Provisions 9.4.1 Lighting Control. Lighting controls shall be installed to meet the provisions of Section 9.4.1.1, 9.4.1.2, 9.4.1.3, and 9.4.1.4. 9.4.1.1 Interior Lighting Controls. For each space in the building, all of the lighting control functions indicated in Tables 9.5.2.1-1 and 9.5.2.1-2, for the appropriate space type in the first column, and as described below, shall be implemented. All control functions indicated as “REQ” are mandatory and shall be implemented. If a space type has control functions indicated as “ADD1,” then at least one of those functions shall be implemented. If a space type has control functions indicated as “ADD2,” then at least one of those functions shall be implemented. For space types not listed, select a reasonably equivalent type.

If using the Space-by-Space Method, the space type used for determining control requirements shall be the same space type that is used for determining the LPD allowance.

a. Local control: There shall be one or more manual lighting control device that provides ON and OFF control

of all lighting in the space . Each control device shall control an area (1) no larger than 2500 ft [2] if the space is  10,000 ft [2] and (2) no larger than 10,000 ft [2] otherwise. The device installed to comply with this provision shall be readily accessible and located so that the occupants can see the controlled lighting when using the control device . Exception to 9.4.1.1(a): Remote location of this local control device or devices shall be permitted for

reasons of safety or security when each remote control device has an indicator pilot light as part of or next to the control device and the control device is clearly labeled to identify the controlled lighting.

150 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 153

Open page note

Table 9.2.2.1 Exceptions to Interior Lighting Power and Minimum Control Requirements

Item #Equipment/ApplicationIn Addition to and
Controlled Separately
from General Lighting
Required Controls
1Lighting that is integral to_equipment_, medical_equipment_ or
instrumentation, and is installed by its_manufacturer_
YESNo control requirements
2Power for only the germicidal function in_luminaires_ or sourcesYESNo control requirements
3Lighting specifically designed for use only during medical or
dental procedures
YES9.4.1.1(a)—Local control
4Lighting specifically designed for the research or support of
nonhuman life forms except for horticultural production or
cultivation
YES9.4.1.1(a)—Local control
5Lighting for video broadcasting, video or film production, or live
performance
YES9.4.1.1(a)—Local control
6Lighting that is an integral part of advertising or directional
signage
YES9.4.1.1(i)—Scheduled shutoff
7Lighting integral to both open and glass-enclosed refrigerator and
freezer cases
YES9.4.1.1(h)—Automatic fullOFF
or
9.4.1.1(i)—Scheduled shutoff
8Lighting in retail display windows, provided the display area is
enclosed by ceiling-height partitions
YES9.4.1.1(a)—Local control and
9.4.1.1(i)—Scheduled shutoff
9Display or accent lighting that is an essential element for the
function performed in galleries, museums, and monuments
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
10Lighting integral to food warming and food preparation
equipment
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
11Lighting that is for sale or lighting educational demonstration
systems
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
12Mirror lighting in makeup or dressing areas used for theatrical or
broadcast functions
YES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
13Accent lighting in religious pulpit and choir areasYES9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
14Lighting in interior_spaces_ that have been specifically designated
as a registered interior_historic_ landmark
NO9.4.1.1(a)—Local control
and either
9.4.1.1(h)—Automatic fullOFF or
9.4.1.1(i)—Scheduled shutoff
15Furniture-mounted supplemental_task lighting_YES9.4.1.1(a)—Local control
and
9.4.1.1(h)—Automatic fullOFF

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 151

PDF Page 154

Open page note

Table 9.2.2.2 Exceptions to Exterior Lighting Power and Minimum Control Zones

Item #Equipment/ApplicationControlled
Separately from
General Lighting
Required
Controls
1Specialized signal, directional, and marker lighting associated with transportationYes9.4.1.4(a)
2Lighting integral to_equipment_ or instrumentation and installed by its_manufacturer_Yes9.4.1.4(a)
3Temporary lightingYes9.4.1.4(a)
4SearchlightsYes9.4.1.4(a)
5Lighting for hazardous locationsYes9.4.1.4(a)
6Lighting integral to public art aYes9.4.1.4(a)
7Lighting used to highlight features of public monuments, public art a displays, and
registered_historic_ landmark_structure_ or_buildings_.
Yes9.4.1.4(b)
8Lighting for theatrical purposes, including performance, stage, film production, and
video production
Yes9.4.1.4(a)
9Lighting for athletic playing areas for colleges and professional sports venuesYes9.4.1.4(a)
10Lighting for athletic playing areasYes9.4.1.4(a),
(b), or (c)
11Lighting for swimming_pools_Yes9.4.1.4(a)
12Lighting for water featuresYes9.4.1.4(b) or
(c)
13Theme elements in theme/amusement parksYes9.4.1.4(c)
14Lighting that is integral to signage and installed in the signage by the_manufacturer_Yes9.4.1.4(d)
15Lighting for industrial production, material handling, transportation sites, and
associated storage areas
Yes9.4.1.4(b),
(d), or (e)

a. Informative Note: “Public art” means art funded either with public or private funds but intended and accessible for the general public.

b. Restricted to manual ON: None of the lighting shall be automatically turned on.

Exception to 9.4.1.1(b): Manual ON is not required where manual ON operation of the general lighting

would endanger the safety or security of the room or building occupants. c. Restricted to partial automatic ON: No more than 50% of the lighting power for the general lighting shall

be allowed to be automatically turned on, and none of the remaining lighting shall be automatically turned on.

Offices greater than 300 ft [2], shall have the following requirements:

  1. Control zones for general lighting shall be limited to 600 ft [2] .
  2. Control zones for general lighting shall be permitted to automatically turn on, up to full power upon occupancy.
  3. General lighting in other unoccupied control zones shall be permitted to automatically turn on to no more than 20% of full power. d. Multilevel lighting control: The general lighting in the space shall be manually controlled with continu-

ous dimming to 10% or less of full lighting power in addition to full ON and full OFF. e. Automatic daylight responsive controls for sidelighting: In any space where the combined input power of

all general lighting completely or partially within the primary sidelighted areas is 75 W or greater, the gen- eral lighting in the primary sidelighted areas shall be controlled by photocontrols.

In any space where the combined input power of all general lighting completely or partially within the primary sidelighted area and secondary sidelighted area is 150 W or greater, the general lighting in the primary sidelighted area and secondary sidelighted area shall be controlled by photocontrols. Gen- eral lighting in the secondary sidelighted area shall be controlled independently of the general lighting in the primary sidelighted area .

The control system shall have the following characteristics:

  1. The calibration adjustment control shall be located no higher than 11 ft above the finished floor . Calibration shall not require the physical presence of a person at the sensor while it is processing.

152 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 155

Open page note

Table 9.3.1-1 Simplified Building Method for Office BuildingsCol2
Interior Space Type and LPAControls
All_spaces_ in office_buildings_ other than parking garages
The total_LPA_for the_ building_other than parking garages shall not
exceed 0.56 W/ft2.
All lighting shall be_automatically_controlled to turn off when
individual_spaces_are either unoccupied or scheduled to be
unoccupied. (Exception: Lighting load not exceeding 0.02 W/ft2
multiplied by the gross lighted area of the_space_ shall be permitted to
operate at all times.)
Each_space_ shall have a_manual control device_ that allows the
occupant to reduce lighting power by a minimum of 50% and to turn
the lighting off.
Office_spaces_ 150 ft2, classrooms, conference rooms, meeting
rooms, training rooms, storage rooms, and break rooms
These_spaces_ shall also be controlled by_manual_-ON occupant
sensors.
Office_spaces_ >150 ft2 and restroomsThese_spaces_ shall also be controlled by_occupant sensors_.
Stairwells and corridors in office_buildings_These_spaces_ shall also be controlled by_occupant sensors_ that
reduce the lighting power by a minimum of 50% when no activity is
detected for not longer than 15 minutes and be controlled to turn off
when the_building_ is either unoccupied or scheduled to be
unoccupied.
Parking garages: The_LPA_shall not exceed 0.14 W/ft2 for the interior
parking floors.
Uncovered floors of a garage shall use_LPA_and control requirements
in Table 9.3.2 for parking lots.
All lighting shall be controlled by_occupant sensors_. Controls shall
reduce the power by a minimum of 50% when no activity is detected
for not longer than 15 minutes. No device shall_control_ more than
3600 ft2.
Table 9.3.1-2 Simplified Building Method for Retail BuildingsCol2
Interior Space TypeControls
All_spaces_ in retail_buildings_ other than parking garages
The total_LPA_for the_building_other than parking garages shall not
exceed 0.70 W/ft2.
All lighting shall be_automatically_controlled to turn off when
individual_spaces_are either unoccupied or scheduled to be
unoccupied. (Exception: Lighting load not exceeding 0.02 W/ft2
multiplied by the gross lighted area of the_space_ shall be permitted to
operate at all times.)
Each_space_ shall have a_manual_ control device that allows the
occupant to reduce lighting power by a minimum of 50% and to turn
the lighting off.
Sales areaThese_spaces_ shall also be_automatically_controlled to
• reduce the_general lighting_ power by a minimum of 75% during
nonbusiness hours,
• to turn off all lighting other than_general lighting_ during nonbusi-
ness hours, and
• by_continuous daylight dimming_ controls in_spaces_ with_toplighting_.
Stock rooms, dressing/fitting rooms, locker rooms, and restroomsThese_spaces_ shall also be controlled by; auto-ON or_manual_-ON
occupant sensors, and_continuous daylight dimming_ controls in
spaces with_toplighting_.
Office_spaces_, conference rooms, meeting rooms, training rooms,
storage rooms, break rooms, and utility_spaces_
These_spaces_ shall also be controlled by;manual-ON occupant
sensors, and_continuous daylight dimming_ controls in_spaces_ with
toplighting.
Stairwells and corridors in retail_buildings_These_spaces_ shall also be controlled by_occupant sensors_ that
reduce the lighting power by a minimum of 50% when no activity is
detected for not longer than 15 minutes and be controlled to turn off
when the_building_is either unoccupied or scheduled to be
unoccupied.
Parking garages: The_LPA_shall not exceed 0.14 W/ft2 for the
interior parking floors.
Uncovered floors of a garage shall use_LPA_and control requirements
in Table 9.3.2 for parking lots.
All lighting shall be controlled by_occupant sensors_. Controls shall
reduce the power by a minimum of 50% when no activity is detected
for not longer than 15 minutes. No device shall_control_ a more than
3600 ft2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 153

PDF Page 156

Open page note

Table 9.3.1-3 Simplified Building Method for School Buildings

Interior Space TypeControls
All_spaces_ in school_buildings_ other than parking garages
The total_LPA_for the_building_other than parking garages shall not
exceed 0.63 W/ft2
All lighting shall be_automatically_controlled to turn off when
individual_spaces_are either unoccupied or scheduled to be unoccupied.
(Exception: Lighting load not exceeding 0.02 W/ft2 multiplied by the
gross lighted area of the_space_ shall be permitted to operate at all
times.)
Each_space_ shall have a_manual_ control device that allows the occupant
to reduce lighting power by a minimum of 50% and to turn the lighting
off.
Classrooms, offices_spaces_, conference rooms, meeting rooms,
library, storage rooms, and break rooms
These_spaces_ shall also be controlled by_manual_-ON occupant sensors.
Gymnasiums and cafeteriasThese_spaces_ shall also be controlled by_occupant sensors_.
RestroomsThese_spaces_ shall also be controlled by_occupant sensors_.
Stairwells and corridors in school_buildings_ and parking garagesThese_spaces_ shall also be controlled by_occupant sensors_ that reduce
the lighting power by a minimum of 50% when no activity is detected
for not longer than 15 minutes and be controlled to turn off when the
_building_is either unoccupied or scheduled to be unoccupied.
Parking Garages: The_LPA_shall not exceed 0.14 W/ft2 for the
interior parking floors.
Uncovered floors of a garage shall use_LPA_and control
requirements in Table 9.3.2 for parking lots.
All lighting shall be controlled by_occupant sensors_. Controls shall
reduce the power by a minimum of 50% when no activity is detected
for not longer than 15 minutes. No device shall_control_ a more than
3600 ft2.

Table 9.3.2 Simplified Building Method for Building Exteriors

Exterior Area TypeExterior
Lighting Power
Allowance a,b
Controls
All exterior areasAll lighting shall be_automatically_controlled to shut off the lighting when daylight is
available.
Base allowance200 WLuminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Façade lighting0.10 W/ft2Luminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Roof terraces, special
feature areas, walkways,
plazas and ramps
0.07 W/ft2_Luminaires_shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Landscape0.036 W/ft2Luminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
Entry doors14 W/linear ftLuminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.
StairsExemptNo additional controls required.
Parking lots and drives0.037 W/ft2Luminaires mounted 25 ft or less above_grade_ shall be controlled to reduce the power by at
least 50% when no activity is detected for not longer than 15 minutes.
All other areas not listed0.20 W/ft2Luminaires shall be turned off or the power reduced by a minimum of 75% during
nonoperating hours.

a. To calculate the exterior allowance, multiply the space or area square footage by the allowed W/ft [2] and sum the exterior allowances and the base allowance. Façade lighting shall

be calculated separately by multiplying the facade area by the allowed W/ft [2] . Façade allowance shall not be traded with other exterior areas or between separate facade areas . b. For buildings in Lighting Zone 2, as defined in Table 9.4.2-1, multiply exterior allowances by 0.7. For buildings in Lighting Zone 4, as defined in Table 9.4.2-1, multiply exterior

allowances by 1.4.

154 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 157

Open page note

  1. The photocontrol shall reduce electric lighting power in response to available daylight using continu- ous daylight dimming to 20% or less and off.

  2. When an automatic reduction control has reduced the lighting power to the unoccupied set point in accordance with Section 9.4.1.1(g), the daylight responsive control shall adjust the electric light in response to available daylight, but it shall not allow the lighting power to be above the unoccupied set point . Exceptions to 9.4.1.1(e): The following areas are exempted from Section 9.4.1.1(e):

  3. Primary sidelighted areas where the top of any existing adjacent structure or natural object is at least twice as high above the windows as its horizontal distance away from the windows.

  4. Sidelighted areas where the total glazing area is less than 20 ft [2] .

  5. Primary sidelighted areas adjacent to vertical fenestration that have external projections and no vertical fenestration above the external projection, where the external projection has a projection factor greater than 1.0 for north-oriented projections or where the external projection has a pro- jection factor greater than 1.5 for all other orientations (see Figure 3.2-6). f. Automatic daylight responsive controls for toplighting : In any space where the combined input power for all general lighting completely or partially within daylight area under skylights and daylight area under roof monitors is 75 W or greater, general lighting in the daylight area shall be controlled by photocontrols. The control system shall have the following characteristics:

  6. The calibration adjustment control shall be located no higher than 11 ft above the finished floor . Calibration shall not require the physical presence of a person at the sensor while it is processing.

  7. The photocontrol shall reduce lighting power in response to available daylight using continuous day- light dimming to 20% or less and off.

  8. When an automatic reduction control has reduced the lighting power to the unoccupied set point in accordance with Section 9.4.1.1(g) the daylight responsive control shall adjust the electric light in response to available daylight, but it shall not allow the lighting power to be above the unoccupied set point .

  9. General lighting in overlapping toplighted and sidelighted daylight areas shall be controlled together with general lighting in the daylight area under skylights or daylight area under roof monitors . Exceptions to 9.4.1.1(f): The following areas are exempted from Section 9.4.1.1(f):

  10. Daylight area under skylights where it is documented that existing adjacent structures or natural objects block direct sunlight for more than 1500 daytime hours per year between 8 a.m. and 4 p.m.

  11. Daylight area under skylights where the overall skylight effective aperture for the enclosed space is less than 0.006.

  12. In each space within buildings in Climate Zone 8 where the input power of the general lighting within daylight areas is less than 200 W. g. Automatic reduction control (full OFF complies): The general lighting power in the space shall be auto-

matically reduced by at least 50% within 20 minutes of all occupants leaving the space .

In offices greater than 300 ft [2], control zones for general lighting shall

  1. be limited to 600 ft [2] and
  2. automatically reduce general lighting by at least 80% of full power within 20 minutes of all occupants leaving a control zone. h. Automatic full OFF control: All lighting in the space, including lighting connected to emergency circuits,

shall be automatically shut off within 20 minutes of all occupants leaving the space . A control device meeting this requirement shall control no more than 5000 ft [2] . Exceptions to 9.4.1.1(h): The following lighting is not required to be automatically shut off:

  1. Lighting required for 24/7 continuous operation.
  2. Lighting in spaces where patient care is rendered.
  3. General lighting and task lighting in spaces where automatic shutoff would endanger the safety or security of the room or building occupants.
  4. Lighting load not exceeding 0.02 W/ft [2] multiplied by the gross lighted floor area of the building . i. Scheduled shutoff : All lighting in the space, including lighting connected to emergency circuits, shall be automatically shut off during periods when the space is scheduled to be unoccupied using either (1) a time-of-day operated control device that automatically turns the lighting off at specific programmed times or (2) a signal from another automatic control device or alarm/security system . The control device or system shall provide independent control sequences that (1) control the lighting for an area of no more than 25,000 ft [2], (2) include no more than one floor, and (3) shall be programmed to account for weekends and holidays. Any manual control installed to provide override of the scheduled shutoff control

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 155

PDF Page 158

Open page note

shall not turn the lighting on for more than two hours per activation during scheduled off periods and shall not control more than 5000 ft [2] . Exceptions to 9.4.1.1(i): The following lighting is not required to be on scheduled shutoff:

  1. Lighting required for 24/7 continuous operation.
  2. Lighting in spaces where patient care is rendered.
  3. General lighting and task lighting in spaces where automatic shutoff would endanger the safety or security of the room or building occupants.
  4. Lighting load not exceeding 0.02 W/ft [2] multiplied by the gross lighted floor area of the building . j. Scheduled OFF during nonbusiness hours : Lighting shall be scheduled to provide automatic OFF control so that lights are turned off at the end of business hours, using either (1) a time-of-day operated control device that automatically turns the lighting off at specific programmed times or (2) a signal from another automatic control device or alarm/security system . Any manual control installed to provide override of the scheduled control shall not turn the lighting on for more than two hours per activation during scheduled off periods.

9.4.1.2 Parking Garage Lighting Control. Lighting for parking garages shall comply with the following requirements:

a. Parking garage lighting shall have automatic lighting shutoff per Section 9.4.1.1(i). b. Lighting power of each luminaire shall be automatically reduced by a minimum of 50% when there is no

activity detected within a lighting zone for 10 minutes. Lighting zones for this requirement shall be no larger than 3600 ft [2] . c. Parking garage daylight transition zone lighting shall be separately controlled to automatically reduce

the lighting to no more than the general light level from sunset to sunrise. d. The power to any luminaire within 20 ft of perimeter wall openings totaling at least 24 ft [2] shall be auto-

matically reduced through continuous dimming in response to available daylight. Exceptions to 9.4.1.2(d):

  1. Parking garage daylight transition zone lighting.
  2. Where permanent screens or architectural elements obstruct more than 50% of the opening.
  3. Where the top of any existing adjacent structure or natural object is at least twice as high above the openings as its horizontal distance from the opening.

9.4.1.3 Special Applications. Lighting controls noted in this section are the only required controls for this equipment and these applications. Lighting exempt from interior lighting power shall be controlled in accordance with Table 9.2.2.1. Lighting using additional interior lighting power applications shall be controlled in accordance with Section 9.5.2.2.

a. Lighting used for the following applications shall be equipped with a local control independent of the

control of the general lighting in accordance with Section 9.4.1.1(a). In addition, such lighting shall be controlled in accordance with Section 9.4.1.1(h) or Section 9.4.1.1(i).

  1. Display or accent lighting

  2. Lighting in display cases b. Guestrooms

  3. All lighting and switched receptacles in guestrooms and suites in hotels, motels, boarding houses, or similar buildings shall be automatically controlled such that the power to the lighting and switched receptacles in each enclosed space will be turned off within 20 minutes after all occupants leave that space . Card key controls shall not be used to comply with this provision.

  4. Bathrooms shall have a separate control device installed to automatically turn off the bathroom lighting within 30 minutes after all occupants have left the bathroom. Exception to 9.4.1.3(b)(2): Night lighting of up to 5 W per bathroom is exempt. c. Supplemental task lighting, including permanently installed undershelf or undercabinet lighting, shall be

controlled from either

  1. a control device integral to the luminaires or
  2. a local control independent of the control of the general lighting in accordance with Section 9.4.1.1(a).

In addition, such lighting shall be controlled in accordance with Section 9.4.1.1(h) or Section 9.4.1.1(i).

156 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 159

Open page note

Table 9.4.2-1 Exterior Lighting Zones

Lighting ZoneDescription
0Undeveloped areas within national parks, state parks, forest land, rural areas, and other
undeveloped areas as defined by the_authority having jurisdiction_
1Developed areas of national parks, state parks, forest land, and rural areas
2Areas predominantly consisting of_residential_ zoning, neighborhood business districts, light
industrial with limited nighttime use and_residential_ mixed use areas
3All other areas
4High-activity commercial districts in major metropolitan areas as designated by the local
jurisdiction

9.4.1.4 Exterior Lighting Control. For each surface or area, all of the lighting control functions indicated in Table 9.4.2-2 shall be implemented. Lighting for exterior applications not exempted in Section 9.1 shall meet the requirements defined here and listed in Table 9.4.2-2:

a. OFF control: There shall be one or more lighting control(s) that turns off all of the lighting in the area or surface. b. Daylight OFF control: Lighting shall automatically turn off when sufficient daylight is available or within

30 minutes of sunrise. c. Scheduled OFF control: Lighting shall be automatically shut off between midnight or business closing,

whichever is later, and 6 a.m. or business opening, whichever comes first, or between times established by the authority having jurisdiction . d. Scheduled light reduction control: Lighting and signage shall be controlled to automatically reduce the

connected lighting power by at least 50% from midnight or within one hour of the end of business operations, whichever is later, until 6 a.m. or the beginning of business operations, whichever is earlier. e. Occupancy-sensing light reduction control: Lighting shall be controlled to automatically reduce the con nected lighting power by a minimum of 50% when no activity has been detected in the area illuminated by the controlled luminaires for a time of no longer than 15 minutes. No more than 1500 W of lighting power shall be controlled together.

All time switches shall be capable of retaining programming and the time setting during loss of power for a period of at least ten hours .

9.4.2 Exterior Lighting Power. The total exterior lighting power allowance for all exterior applications is the sum of the base site allowance plus the individual allowances for areas that are designed to be illuminated and are permitted in Table 9.4.2-2 for the applicable lighting zone in Table 9.4.2-1. The installed exte- rior lighting power identified in accordance with Section 9.1.3 shall not exceed the exterior lighting power allowance developed in accordance with this section. Trade-offs are allowed only among exterior lighting applications listed in the Table 9.4.2-2 “Tradable Surfaces” section. The lighting zone for exterior applications is determined from Table 9.4.2-1 unless otherwise specified by the local jurisdiction.

9.4.3 Dwelling Units. Dwelling unit lamps, luminaires, and lighting controls shall be installed to meet the provisions of Sections 9.4.3.1, 9.4.3.2, and 9.4.3.3. No other provisions of Section 9 apply to dwelling units .

9.4.3.1 Lamp and Luminaire Efficacy. At least 75% of the permanently installed luminaires shall use lamps with an efficacy of at least 75 lm/W or have a total luminaire efficacy of at least 50 lm/W.

9.4.3.2 Interior Lighting Controls. Fifty percent (50%) of permanently installed interior luminaires shall be controlled with dimmers or shall automatically be shut off within 20 minutes of all occupants leaving a space .

9.4.3.3 Exterior Lighting Controls. Permanently installed exterior luminaires dedicated to a dwelling unit shall be provided with manual controls and be automatically shut off through time of day, available daylight, or when no activity has been detected for 15 minutes.

Exception to 9.4.3.3: Applications with a total rated luminaire wattage of no greater than 8 W.

9.4.4 Horticultural Lighting. Greenhouse horticultural lighting shall follow the requirements of Section 9.4.4.1. Indoor grow horticultural lighting shall follow the requirements of Section 9.4.4.2. 9.4.4.1 Luminaires in greenhouse buildings with at least 40 kW of connected load for horticultural light- ing shall have a photosynthetic photon efficacy ( PPE ) of at least 1.7 µmol/J for integrated, nonserviceable luminaires, or a PPE of at least 1.7 µmol/J for lamps in luminaires with removable or serviceable lamps .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 157

PDF Page 160

Open page note

Table 9.4.2-2 Individual Lighting Power Allowances for Building Exteriors Applications

Base Site Allowance (Base allowance may be used in tradable or non-tradable surfaces.)

No allowance 160 W 280 W 400 W 560 W

Tradable Surfaces ( LPD for uncovered parking areas, building grounds, building entrances, exits and loading docks, canopies and overhangs, and outdoor sales areas may be traded.)

Uncovered Parking Areas

Parking areas and drivesNo allowance0.015 W/ft20.026W/ft20.037 W/ft20.052 W/ft2(b) and either
(d) or (e)
Parking areas and drives with
luminaires >78W and mounting
height <24 ft
No allowance0.015 W/ft20.026 W/ft20.037 W/ft20.052 W/ft2(b) and (e)
GroundsCol2Col3Col4Col5Col6Col7
Walkways/rampsNo allowance0.5 W/linear ft0.5 W/linear ft0.55W/linear ft0.60 W/linear
ft
(b) and either
(d) or (e)
Plaza areasNo allowance0.028 W/ft20.049 W/ft20.070 W/ft20.098 W/ft2(b) and either
(d) or (e)
Roof terraces and special featuresNo allowance0.04 W/ft20.07 W/ft20.10 W/ft20.140 W/ft2(b) and either
(d) or (e)
Dining areasNo allowance0.156 W/ft20.273 W/ft20.390 W/ft20.546 W/ft2(b) and either
(d) or (e)
Pedestrian tunnelsNo allowance0.063 W/ft20.110 W/ft20.157 W/ft20.220 W/ft2(d) or (e)
LandscapingNo allowance0.014 W/ft20.025 W/ft20.036 W/ft20.050 W/ft2(b) and (c)

Building Entrances, Exits, and Loading Docks

Pedestrian and vehicular entrances
and exits
No allowance5.6 W/linear ft
of opening
9.8W/linear ft
of opening
14.0 W/linear
ft of opening
19.6 W/linear
ft of opening
(b) and either
(d) or (e)
Entry canopiesNo allowance0.072 W/ft20.126 W/ft20.180 W/ft20.252 W/ft2(b) and either
(d) or (e)
Loading docksNo allowance0.104 W/ft20.182 W/ft20.260 W/ft20.364 W/ft2(b) and either
(d) or (e)

Sales Canopies

Outdoor SalesCol2Col3Col4Col5Col6Col7
Open areas (including vehicle sales
lots)
No allowance0.072 W/ft20.126 W/ft20.180 W/ft20.252 W/ft2(b) and either
(d) or (e)
Street frontage for vehicle sales lots in
addition to “open area” allowance
No allowanceNo allowance7.2 W/linear ft10.3 W/linear
ft
14.4 W/linear
ft
(b) and either
(d) or (e)

Nontradable Surfaces ( LPD for the following applications can be used only for the specific application and cannot be traded between surfaces or with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the “Tradable Surfaces” section of this table.)

Stairways Exempt Exempt Exempt Exempt Exempt (b)

158 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 161

Open page note

Table 9.4.2-2 Individual Lighting Power Allowances for Building Exteriors Applications (Continued)

Col1Zone 0Zone 1Zone 2Zone 3Zone 4Section
9.4.1.4
Required
Controls
Building_facades
(The allowance for each illuminated
facade_orientation_shall be calculated
by multiplying the allowable value by
the entire_facade area
or facades
length for that_orientation_.)
No allowance0.056 /ft2 of
facade area or
1.4 W/linear ft
of facade
length
0.098 W/ft2 of
_facade area_or
2.4 W/linear ft
of facade
length
0.140 W/ft2 of
_facade area_or
3.4 W/ linear ft
of facade
length
0.196 W/ft2 of
_facade area_or
4.8 W/linear ft
of facade
length
(b) and (c)
Automated teller machines and night
depositories
No allowance90 W per
location plus
35 W per
additional
ATM per
location
90 W per
location plus
35 W per
additional
ATM per
location
90 W per
location plus
35 W per
additional
ATM per
location
90 W per
location plus
35 W per
additional
ATM per
location
(b)
Uncovered entrances and gatehouse
inspection stations at guarded
facilities
No allowance0.144 W/ft20.252 W/ft20.360 W/ft20.504 W/ft2(b) and either
(d) or (e)
Uncovered loading areas for law
enforcement, fire, ambulance, and
other emergency service vehicles
No allowance0.104 W/ft20.182 W/ft20.260 W/ft20.364 W/ft2(b) and either
(d) or (e)
Drive-through windows/doorsNo allowance53 W per
drive-through
92 W per
drive-through
132 W per
drive-through
185 W per
drive-through
(b) and either
(d) or (e)
Parking near 24-hour retail entrancesNo allowance80 W per
main entry
140 W per
main entry
200 W per
main entry
280 W per
main entry
(b) and either
(d) or (e)
For areas that are not listed in this
table or are not comparable to areas
listed in this table, use the comparable
interior_space_type from Tables
9.5.2.1-1 and 9.5.2.1-2 as modified by
factors in this row.
No allowance22% of the
interior
lighting power
allowance
value
39% of the
interior
lighting power
allowance
value
55% of the
interior
lighting power
allowance
value
77% of the
interior
lighting power
allowance
value
(b) and either
(d) or (e)
Roadway/parking entry, trail head,
and toilet facility, or other locations
approved by the_authority having_
jurisdiction.
A single
_luminaire_of 10
W or less
No additional
allowance
No additional
allowance
No additional
allowance
No additional
allowance
(b) and either
(d) or (e)

Horticultural lighting in greenhouse spaces shall be controlled by a device that automatically turns off the horticultural lighting at specific programmed times.

9.4.4.2 Luminaires in indoor grow spaces used for horticultural lighting shall have a PPE of at least 1.9 µmol/J for integrated, nonserviceable luminaires, or a PPE of at least 1.9 µmol/J for lamps in lumi- naires with removable or serviceable lamps . Horticultural lighting in indoor grow spaces shall be controlled by a device that automatically turns off the horticultural lighting at specific programmed times.

Exception to 9.4.4.2: Indoor grow buildings with less than 40 kW of connected load for horticultural

lighting shall have a PPE of at least 1.7 µmol/J for integrated, nonserviceable luminaires, or a PPE of at least 1.7 µmol/J for lamps in luminaires with removable or serviceable lamps .

9.5 Prescriptive Compliance Path. Interior lighting power shall comply with either Section 9.5.1 or 9.5.2. Lighting control requirements shall comply with Section 9.4.1 and Tables 9.5.2.1-1 and 9.5.2.1-2.

9.5.1 Building Area Method Compliance Path . Use the following steps to determine the interior light- ing power allowance by the Building Area Method:

a. Determine the appropriate building area type from Table 9.5.1 and the corresponding LPD allowance. For

building area types not listed, selection of a reasonably equivalent type shall be permitted. b. Determine the gross lighted floor area in ft [2] of the building area type. c. Multiply the gross lighted floor areas of the building area types times the LPD .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 159

PDF Page 162

Open page note

Table 9.5.1 Lighting Power Density Allowances Using the Building Area Method

Building Area TypeaLPD, W/ft2
Automotive facility0.73
Convention center0.64
Courthouse0.75
Dining: Bar lounge/leisure0.74
Dining: Cafeteria/fast food0.70
Dining: Family0.65
Dormitory0.52
Exercise center0.72
Fire station0.56
Gymnasium0.75
Health care clinic0.77
Hospital0.92
Hotel/motel0.53
Library0.83
Manufacturing facility0.82
Motion picture theater0.43
Multifamily0.46
Museum0.56
Office0.62
Parking garage0.17
Penitentiary0.65
Performing arts theater0.82
Police station0.62
Post office0.64
Religious facility0.66
Retail0.78
School/university0.70
Sports arena0.73
Town hall0.67
Transportation0.56
Warehouse0.45
Workshop0.86

a. In cases where both a general building area type and a specific building area type are listed, the specific building area type shall apply.

d. The interior lighting power allowance for the building is the sum of the lighting power allowances of all

building area types. Trade-offs among building area types are permitted, provided that the total installed interior lighting power does not exceed the interior lighting power allowance .

9.5.2 Space-by-Space Method Compliance Path

9.5.2.1 Space-by-Space Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power allowance by the Space-by-Space Method:

160 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 163

Open page note

a. For each space enclosed by partitions that are 80% of the ceiling height or taller, determine the appropri ate space type and the corresponding LPD allowance from Tables 9.5.2.1-1 and 9.5.2.1-2. If a space has multiple functions, where more than one space type is applicable, that space shall be broken up into smaller subspaces, each using its own space type from Tables 9.5.2.1-1 and 9.5.2.1-2. Any of these subspaces that are smaller in floor area than 20% of the original space and less than 1000 ft [2] need not be broken out. Include the floor area of balconies and other projections in this calculation. b. In calculating the area of each space and subspace, the limits of the area are defined by the centerline of

interior walls, the dividing line between subspaces, and the outside surface of exterior walls or semiexte- rior walls . For the purposes of this section, semiexterior walls that separate semiheated space from con- ditioned space shall be considered interior walls. c. Based on the space type selected for each space or subspace, determine the lighting power allowance of

each space or subspace by multiplying the calculated area of the space or subspace by the appropriate LPD allowance determined in Section 9.5.2.1(a). For space types not listed, selection of a reasonable equivalent category shall be permitted. d. The interior lighting power allowance is the sum of lighting power allowances of all spaces and sub spaces. Trade-offs among spaces and subspaces are permitted, provided that the total installed interior lighting power does not exceed the interior lighting power allowance .

9.5.2.2 Additional Interior Lighting Power. When using the Space-by-Space Method, an increase in the interior lighting power allowance is allowed for specific lighting functions. Additional power shall be allowed only if the specified lighting is installed and controlled independently of the general lighting in accordance with Table 9.5.2.2. This additional power shall be used only for the specified luminaires and shall not be used for any other purpose unless otherwise indicated. Lighting control requirements referenced in Section 9.5.2.2 are the only required controls for these applications.

An increase in the interior lighting power allowance is permitted in the following cases:

a. For each space in which lighting is installed in addition to the general lighting for the purpose of decora tive appearance or for highlighting art or exhibits not exempted in Table 9.2.2.1, provided that the additional lighting power shall not exceed the value in Table 9.5.2.2 . b. For lighting equipment installed in sales areas and specifically designed and directed to highlight mer chandise, provided that the additional lighting power shall not exceed the value in Table 9.5.2.2. c. For spaces in which lighting is installed for the purpose of videoconferencing and the lighting in that

space meets ANSI/IES/AVIXA RP-38, additional lighting power shall be allowed per Table 9.5.2.2.

Exception to 9.5.2.2: Other merchandise categories may be included in Retail Areas 2 through 4 above,

provided that justification documenting the need for additional lighting power based on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction .

9.5.2.3 Additional Interior Lighting Power Using Nonmandatory Controls. An additional lighting power allowance shall be permitted for space types with nonmandatory controls installed as identified in Table 9.5.2.3 when all mandatory controls are used according to Section 9.4. This allowance is added to the interior lighting power allowance and is calculated as follows:

Additional Interior Lighting Power Allowance = Lighting Power Under Control × Control Factor where Lighting Power Under Control = the total input watts of all lamps being controlled using the control method indicated Control Factor = the value given in Table 9.5.2.3 for the corresponding space type and control method 9.5.2.4 Room Geometry Adjustment. When using the Space-by-Space Method, an adjustment of the space LPD allowance is permitted for individual spaces where room cavity ratio ( RCR ) calculated for the empty room is documented to be greater than the RCR threshold for that space type shown in Tables 9.5.2.1-1 and 9.5.2.1-2.

RCR = 2.5 × Room Cavity Height × Room Perimeter Length/Room Area where Room Cavity Height = Luminaire Mounting Height – Workplane.

For corridor/transition spaces, this adjustment is allowed when the corridor is less than 8 ft wide, regardless of the RCR .

The LPD allowance for these spaces may be increased by the following amount:

LPD Increase = Base Space LPD × 0.20 where Base Space LPD = the applicable LPD allowance from Tables 9.5.2.1-1 and 9.5.2.1-2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 161

PDF Page 164

Open page note

9.6 Alternate Compliance Path (Reserved)

9.7 Submittals 9.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2.

9.7.2 Permit Application Documentation (Not Used) 9.7.3 Completion Requirements 9.7.3.1 Record Documents. Construction documents shall require that within 90 days after the date of system acceptance, record documents be provided to the property owner or the designated representative of the property owner. Record documents shall include, as a minimum, the location, luminaire identifier, control, and circuiting for each piece of lighting equipment .

9.7.3.2 Manuals. Construction documents shall require for all lighting equipment and lighting controls that an operating manual and maintenance manual be provided to the property owner or the designated representative of the property owner within 90 days after the date of system acceptance. These manuals shall include, at a minimum, the following:

a. Submittal data indicating all selected options for each piece of lighting equipment, including but not lim ited to lamps, ballasts, drivers, and lighting controls. b. Operation and maintenance manuals for each piece of lighting equipment and lighting controls with rou tine maintenance clearly identified including, as a minimum, a recommended relamping/cleaning program and a schedule for inspecting and recalibrating all lighting controls. c. A complete narrative of how each lighting control system is intended to operate, including recommended

settings.

9.7.3.3 Daylighting Documentation. The design documents shall identify all luminaires for general lighting that are located within daylight areas under skylights, daylight areas under roof monitors, and pri- mary sidelighted area and secondary sidelighted areas .

9.8 Product Information (Not Used)

9.9 Verification, Testing, and Commissioning 9.9.1 Verification and Testing. Lighting control devices and control systems shall be tested in accordance with this section and Section 4.2.5.1 to verify that control hardware and software are calibrated, adjusted, programmed, and in proper working condition in accordance with the construction documents and manufac- turer ’s installation instructions. The following procedures shall be performed for the type of controls listed:

a. Occupancy Sensors

  1. Certify that the sensor has been located and aimed in accordance with manufacturer recommendations.
  2. For projects with up to seven (7) occupancy sensors, all occupancy sensors shall be tested.
  3. For projects with more than seven (7) occupancy sensors, testing shall be performed for each unique combination of sensor type and space geometry. i. For each sensor to be tested, verify the following: (a) Status indicator (as applicable) operates correctly. (b) Controlled lights turn off or down to the permitted level within the required time. (c) For auto-ON occupancy sensors, the lights turn on to the permitted level when someone enters

the space. (d) For manual -ON sensors, the lights turn on only when manually activated. (e) The lights are not incorrectly turned on by movement in nearby areas or by HVAC operation. b. Automatic Time Switches

  1. Confirm that the automatic time-switch control is programmed with weekday, weekend, and holiday (as applicable) schedules.
  2. Document for the owner automatic time-switch programming, including weekday, weekend, and holiday schedules, as well as all setup and preference program settings.
  3. Verify that correct time and date are properly set in the time switch.
  4. Verify that any battery backup (as applicable) is installed and energized.
  5. Verify that the override time limit is set to no more than two (2) hours.
  6. Simulate occupied condition. Verify and document the following: i. All lights can be turned on and off by their respective area control switch.

162 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 165

Open page note

ii. The switch only operates lighting in the enclosed space in which the switch is located.

  1. Simulate unoccupied condition. Verify and document the following: i. All nonexempt lighting turns off. ii. Manual override switch allows only the lights in the enclosed space where the override switch is located to turn on or remain on until the next scheduled shut off occurs. c. Daylight Controls

  2. All control devices (photocontrols) have been properly located and field-calibrated, to set points and threshold light levels.

  3. Daylight controlled lighting loads adjust in response to available daylight.

  4. The location where calibration adjustments are made is readily accessible only to authorized personnel. d. High-End Trim and Lumen Maintenance Controls

  5. The initial maximum set point for power or light output for each control group of luminaires shall be documented.

  6. The tuned maximum set point for power or light output for each control group of luminaires shall be documented.

  7. Measurement of high-end trim in daylight areas shall be conducted at night.

  8. Where lumen maintenance controls are included, the automatic rate of increase in lighting power shall be no more than 1.0% per year.

  9. The high-end trim and lumen maintenance control documentation shall show the initial and tuned set point and area for each control group and summarize the overall percentage of lighting output or power reduction from tuning. The rate of increase for lumen maintenance shall be shown for each control group. e. Verification and FPT documentation shall comply with Section 4.2.5.1.2.

9.9.2 Commissioning. The energy performance of the lighting systems shall be commissioned in accordance with Section 4.2.5.2, and reporting shall comply with Section 4.2.5.2.2.

Informative Note: See Informative Appendix E and Informative Appendix H for commissioning references and guidance.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 163

PDF Page 166

Open page note

Table 9.5.2.1-1 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

Informative Note: This table covers common space types typically found in multiple building types. Table 9.5.2.1-2 covers building -specific space types typically found in a single building type.

LPD, Common Space Types [a] W/ft [2] RCR

Atrium

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

<20 ft in height 0.32 NA REQ ADD1 ADD1 REQ REQ ADD2 ADD2

 20 ft and  40 ft in height 0.41 NA REQ ADD1 ADD1 REQ REQ ADD2 ADD2

40 ft in height 0.51 11 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Audience Seating Area

Auditorium 0.57 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Gymnasium 0.23 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Motion picture theater 0.27 4 REQ ADD1 ADD1 REQ ADD2 ADD2

Performing arts theater 1.10 8 REQ ADD1 ADD1 REQ ADD2 ADD2

Sports arena 0.27 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

All other audience seating areas 0.23 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Banking Activity Area 0.56 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Classroom/Lecture Hall/Training Room

Shop classroom 1.17 6 REQ ADD1 ADD1 REQ REQ REQ

All other classrooms/lecture halls/training rooms 0.72 4 REQ ADD1 ADD1 REQ REQ REQ REQ

Computer Room 0.75 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Conference/Meeting/Multipurpose Rooms 0.88 6 REQ ADD1 ADD1 REQ REQ REQ REQ

Control/Editing Room or Booth 0.73 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Copy/Print Room 0.56 6 REQ ADD1 ADD1 REQ REQ REQ

Corridor 0.44 width <8 ft REQ REQ REQ REQ ADD2 ADD2

Courtroom 1.08 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Dining Areas

Bar/lounge or leisure dining 0.76 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

a. Where both a common space type and a building -specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-2 for building -specific space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.

PDF Page 167

Open page note

Table 9.5.2.1-1 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

Informative Note: This table covers common space types typically found in multiple building types. Table 9.5.2.1-2 covers building -specific space types typically found in a single building type.

LPD, Common Space Types [a] W/ft [2] RCR

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Cafeteria or fast-food dining 0.36 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Family dining 0.52 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

All other dining areas 0.42 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Electrical/Mechanical Room 0.71 6 REQ

Emergency Vehicle Garage 0.51 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Equipment Room 0.73 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Food Preparation Area 1.19 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Guest Room 0.41 6 See Section 9.4.1.3(b).

Laboratory

In or as a classroom 1.05 6 REQ ADD1 ADD1 REQ REQ REQ REQ ADD2 ADD2

All other laboratories 1.21 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Laundry/Washing Area 0.51 4 REQ ADD1 ADD1 REQ REQ REQ REQ

Loading Dock, Interior 0.87 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Lobby

Elevator 0.64 6 REQ REQ REQ ADD2 ADD2

Hotel 0.48 4 REQ REQ REQ ADD2 ADD2

Motion picture theater 0.20 4 REQ REQ REQ ADD2 ADD2

Performing arts theater 1.21 6 REQ REQ REQ ADD2 ADD2

All other lobbies 0.80 4 REQ REQ REQ REQ ADD2 ADD2

Locker Room 0.43 6 REQ ADD1 ADD1 REQ REQ REQ REQ

Lounge/Breakroom

Mother’s/wellness room 0.68 6 REQ ADD1 ADD1 REQ REQ

All other lounges/breakrooms 0.55 4 REQ ADD1 ADD1 REQ REQ REQ REQ

a. Where both a common space type and a building -specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-2 for building -specific space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.

PDF Page 168

Open page note

Table 9.5.2.1-1 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

Informative Note: This table covers common space types typically found in multiple building types. Table 9.5.2.1-2 covers building -specific space types typically found in a single building type.

LPD, Common Space Types [a] W/ft [2] RCR

Office

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Office  150 ft [2] 0.73 8 REQ ADD1 ADD1 REQ REQ

Office >150 and  300 ft [2] 0.66 8 REQ ADD1 ADD1 REQ REQ

Offices >300 ft [2] 0.56 4 REQ ADD1 ADD1 REQ REQ REQ REQ REQ

Parking Garage

Daylight transition zone 1.06 4 See Section 9.4.1.2.

All other parking and drive areas 0.11 4 See Section 9.4.1.2.

Pharmacy Area 1.59 6 REQ ADD1 ADD1 REQ ADD2 ADD2

Restroom 0.74 8 REQ

Sales Area (For accent lighting, see Section 9.5.2.2[b].) 0.85 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Seating Area, General 0.21 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Security Screening

Airport/bus/ship/train/transportation screening 0.93 6 REQ REQ REQ ADD2 ADD2

Airport/bus/ship/train/transportation screening queue 0.56 6 REQ REQ REQ ADD2 ADD2

General security screening 0.64 6 REQ REQ REQ ADD2 ADD2

Stairway The space containing the stairway shall determine the LPD and control requirements for the stairway.

Stairwell 0.47 10 REQ REQ REQ ADD2 ADD2

Storage Room

<50 ft [2] 0.49 9 REQ REQ REQ

 50 ft [2] 0.35 6 REQ REQ

Vehicular Maintenance Area 0.59 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Workshop (including workshop classrooms) 1.17 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

a. Where both a common space type and a building -specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-2 for building -specific space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.

PDF Page 169

Open page note

Table 9.5.2.1-2 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

Informative Note: This table covers building- specific space types typically found in a single building type. Table 9.5.2.1-1 covers common space types typically found in multiple building types.

LPD, Building-Specific Space Types [a] W/ft [2] RCR

Casino—Gaming Area

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Betting/sportsbook/keno/bingo area 0.82 5 REQ ADD2 ADD2

High-limit game area 1.68 4 REQ ADD2 ADD2

Slot machine/digital gaming area 0.54 5 REQ ADD2 ADD2

Table games area 1.09 5 REQ ADD2 ADD2

Convention Center—Exhibit Space 0.50 4 REQ ADD1 ADD1 REQ REQ REQ REQ

Correctional Facilities

Audience seating area 0.56 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Classroom/lecture hall/training room 0.74 4 REQ ADD1 ADD1 REQ REQ REQ

Confinement cells 0.60 6 REQ REQ

Dining area 0.35 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Dormitory—Living Quarters 0.48 8 REQ

Facility for the Visually Impaired  (A facility for the visually impaired is a facility that can be documented as being designed to comply with the light levels in ANSI/IES RP-28 and that is or will be licensed by local/state authorities for senior long-term care, adult daycare, senior support, and/or people with special visual needs.)

Chapel (used primarily by residents) 0.58 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Corridor (used primarily by residents) 0.71 width <8 ft REQ REQ REQ REQ ADD2 ADD2

Dining (used primarily by residents) 1.22 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Lobby 1.44 4 REQ REQ REQ REQ ADD2 ADD2

Recreation room/common living room  (used primarily by residents)

1.20 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Restroom (used primarily by residents) 0.96 8 REQ REQ REQ

Fire Station—Sleeping Quarters 0.22 6 REQ

a. Where both a common space type and a building specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-1 for common space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.

PDF Page 170

Open page note

Table 9.5.2.1-2 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

Informative Note: This table covers building- specific space types typically found in a single building type. Table 9.5.2.1-1 covers common space types typically found in multiple building types.

LPD, Building-Specific Space Types [a] W/ft [2] RCR

Gymnasium/Fitness Center

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Exercise area 0.82 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Playing area 0.82 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Health Care Facility

Control room (MRI/CT/radiology/PET) 0.78 8 REQ REQ REQ REQ

Exam/treatment room 1.33 8 REQ REQ REQ REQ ADD2 ADD2

Hospital corridor 0.61 width <8 ft REQ REQ REQ ADD2 ADD2 ADD2

Imaging room 0.94 6 REQ REQ ADD2 ADD2

Lounge 0.77 6 REQ ADD1 ADD1 REQ REQ REQ REQ

Medical supply room 0.56 6 REQ ADD1 ADD1 REQ

Nursery 0.87 6 REQ REQ REQ REQ ADD2 ADD2

Nurse’s station 1.07 6 REQ REQ REQ REQ ADD2 ADD2

Operating room 2.31 6 REQ REQ

Patient room 0.78 6 REQ REQ

Physical therapy room 0.82 6 REQ REQ REQ REQ ADD2 ADD2

Recovery room 1.18 6 REQ REQ ADD2 ADD2

Telemedicine 1.44 8 REQ ADD1 ADD1 REQ REQ REQ REQ

Library

Reading area 0.86 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Stacks 1.18 4 REQ ADD1 ADD1 REQ ADD2 ADD2

Manufacturing Facility

Detailed manufacturing area 0.75 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Extra-high bay area (>50 ft floor -to-ceiling height) 1.36 8 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

a. Where both a common space type and a building specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-1 for common space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.

PDF Page 171

Open page note

Table 9.5.2.1-2 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

Informative Note: This table covers building- specific space types typically found in a single building type. Table 9.5.2.1-1 covers common space types typically found in multiple building types.

LPD, Building-Specific Space Types [a] W/ft [2] RCR

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

High bay area (25 to 50 ft floor -to-ceiling height) 1.24 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Low bay area (<25 ft floor -to-ceiling height) 0.85 3 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Museum

General exhibition area 0.31 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Restoration area 1.24 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Performing Arts Theater—Dressing Room 0.39 6 REQ ADD1 ADD1 REQ REQ

Post Office—Sorting Area 0.71 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Religious Facility

Audience seating area 0.72 4 REQ REQ REQ REQ ADD2 ADD2

Fellowship hall 0.50 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Worship/pulpit/choir area 0.75 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Retail Facilities

Dressing/fitting room 0.45 8 ADD2 ADD2

Hair care 0.65 6 REQ ADD1 ADD1 ADD2 ADD2

Mall concourse 0.57 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Massage 0.81 8 REQ ADD1 ADD1 REQ ADD2 ADD2

Nail care 0.75 6 REQ ADD1 ADD1 ADD2 ADD2

Sports Arena—Playing Area (Class of play as defined by ANSI/IES RP-6)

Class I facility 2.86 4 REQ REQ REQ REQ REQ

Class II facility 1.98 4 REQ REQ REQ REQ REQ

Class III facility 1.29 4 REQ REQ REQ REQ REQ

Class IV facility 0.85 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

a. Where both a common space type and a building specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-1 for common space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.

PDF Page 172

Open page note

Table 9.5.2.1-2 Space-by-Space Lighting Power Density Allowances and Minimum Control Requirements Using Either Method

Informative Note: This table covers building- specific space types typically found in a single building type. Table 9.5.2.1-1 covers common space types typically found in multiple building types.

LPD, Building-Specific Space Types [a] W/ft [2] RCR

Natatorium (Class of play as defined by IES RP-6)

The control functions below shall be implemented in accordance with the descriptions found within Section 9.4.1.1. For each space type:

(1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented.

Auto Full OFF

Daylight Response

Sidelight

Daylight Response

Toplight

Auto Reduction

(Full OFF complies)

Local Control

Manual

ON

Partial Auto ON

Multilevel

Lighting

Control

Scheduled

Shutoff

9.4.1.1(a) 9.4.1.1(b) 9.4.1.1(c) 9.4.1.1(d) 9.4.1.1(e) [ b] 9.4.1.1(f) [ b] 9.4.1.1(g) 9.4.1.1(h) 9.4.1.1(i)

Class I facility 2.20 4 REQ REQ REQ REQ REQ

Class II facility 1.47 4 REQ REQ REQ REQ REQ

Class III facility 0.99 4 REQ REQ REQ REQ REQ

Class IV facility 0.59 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Transportation Facility

Airport hanger 1.36 4 REQ REQ REQ REQ REQ

Baggage/carousel area 0.28 4 REQ REQ ADD2 ADD2

Concourse 0.49 4 REQ REQ ADD2 ADD2

Passenger loading area 0.71 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Ticket counter 0.40 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

Warehouse—Storage Area

Medium-to-bulky, palletized items 0.33 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Smaller items, picking areas 0.69 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

a. Where both a common space type and a building specific space type are listed, the building specific space type shall apply (see Table 9.5.2.1-1 for common space types) . b. Automatic daylight responsive controls are mandatory only if the space meets the requirements of the specified sections.

PDF Page 173

Open page note

Table 9.5.2.2 Additional Lighting Power

Section 9.4.1.1(j)

9.5.2.1-2 space types for required controls.

Notes:

DescriptionAdditional Lighting Power
Decorative0.70 W/ft2
Retail sales750 W + (Retail Area 1 × 0.40 W/ft2) + (Retail Area 2 × 0.40 W/ft2) +
(Retail Area 3 × 0.70 W/ft2) + (Retail Area 4 × 1.00 W/ft2)
Video conferencing0.50 W/ft2

Retail Area 1 = the floor area for all products not listed in Retail Areas 2, 3, or 4 Retail Area 2 = the floor area used for the sale of vehicles, sporting goods, and small electronics Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics, and artwork Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china

Table 9.5.2.3 Control Factors Used in Calculating Additional Interior Lighting Power Allowance

Additional Control Method 
(in Addition to Mandatory Requirements)
Space TypeCol3Col4Col5Col6
Additional Control Method
(in Addition to Mandatory Requirements)
Open
Office
Private
Office
Conference
Room,
Meeting Room,
Classroom
(Lecture/
Training)
Retail
Sales
Area
Lobby, Atrium,
Dining Area,
Corridors/
Stairways, Gym/
Pool, Mall
Concourse,
Parking Garage
Programmable multilevel dimming control using programmable
time scheduling
0.050.050.100.100.10
Occupancy sensors controlling the downlight component of
workstation specific_luminaires_ with continuous dimming to off
capabilities
0.25a0000
Occupancy sensors controlling the downlight component of
workstation specific_luminaires_ with continuous dimming to off
operation, in combination with personal continuous dimming
control of downlight illumination by workstation occupant
0.30a,b0000

a. Control factor is limited to workstation-specific luminaires in partitioned single occupant work spaces contained within an open office environment (i.e. direct-indirect luminaires

with separately controlled downlight and uplight components, with the downward component providing illumination to a single occupant in an open plan workstation). Within 30 minutes of the occupant leaving the space, the downward component shall continuously dim to off over a minimum of two minutes. Upon the occupant entering the space, the downward component shall turn on at the minimum level and continuously raise the illumination to a preset level over a minimum of 30 seconds. The uplight component of workstation specific luminaire shall comply with Section 9.4.1.1(h) ( automatic full OFF). b. In addition to the requirements described in footnote (a), the control shall allow the occupant to select their preferred light level via a personal computer, handheld device, or simi larly accessible device located within the workstation.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 171

PDF Page 174

Open page note

10. OTHER EQUIPMENT

10.1 General 10.1.1 Scope. This section applies to other equipment as described in Section 10.4. 10.1.2 New Building or Site System or Equipment. Other equipment installed in new buildings shall comply with the requirements of Section 10.2.

10.1.3 Additions to Existing Systems and Equipment. Other equipment installed in additions to exist- ing buildings and existing sites shall comply with the requirements of Section 10.2.

10.1.4 Alterations to Existing Service Equipment or Systems 10.1.4.1 Alterations to other building service equipment shall comply with the requirements of Section 10.2 as applicable to those specific portions of the building that are being altered. 10.1.4.2 Alterations to systems shall comply with the requirements of Section 10.2, as applicable to those specific portions that are being altered.

10.1.4.3 Any new equipment subject to the requirements of Section 10 that is installed in conjunction with the alterations as a direct replacement of existing equipment or control devices shall comply with the specific requirements applicable to that equipment or control devices .

Exception to 10.1.4.3: Compliance shall not be required for the relocation or reuse of existing equip-

ment .

10.1.5 Climate. Climate zones shall be determined in accordance with Section 5.1.5 .

10.2 Compliance Paths. Other equipment shall comply with Sections 10.2.1 and 10.2.2. 10.2.1 Requirements for All Compliance Paths. Other equipment shall comply with Sections 10.1, “General”; 10.4, “Mandatory Provisions”; 10.5, “Prescriptive Path”, and 10.8, “Product Information.”

10.2.2 Additional Requirements to Comply with Section 10 (Not Used)

10.3 Simplified Building Compliance Path (Not Used)

10.4 Mandatory Provisions 10.4.1 Electric Motors. Electric motors manufactured alone or as a component of another piece of equip- ment with a rated motor power of 1 hp or more, and less than or equal to 200 hp, shall comply with the requirements shown in Table 10.8-1 for NEMA Design A motors, NEMA Design B motors, and IEC Design N motors, and Table 10.8-2 for NEMA Design C motors and IEC Design H motors .

172 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 175

Open page note

General purpose small electric motors with an rated motor power of 0.25 hp or more, and less than or equal to 3 hp, shall have a minimum average full-load efficiency that is not less than as shown in Table 10.83 for polyphase small electric motors and Table 10.8-4 for capacitor-start capacitor-run small electric motors and capacitor-start induction-run small electric motors .

Fire pump electric motors shall have a minimum nominal full-load efficiency that is not less than that shown in Table 10.8-5.

Exception to 10.4.1: The standards in this section do not apply to the following exempt electric motors:

  1. Air-over electric motors.
  2. Component sets of an electric motor.
  3. Liquid-cooled electric motors.
  4. Submersible electric motors.
  5. Inverter-only electric motors.

10.4.2 Service Water Pressure Booster Systems. Service water pressure booster systems shall be designed such that the following apply:

a. One or more pressure sensors shall be used to vary pump speed and/or start and stop pumps . The sensors

shall either be located near the critical fixtures that determine the pressure required, or logic shall be employed that adjusts the set point to simulate operation of remote sensors. b. No devices shall be installed for the purpose of reducing the pressure of all of the water supplied by any

booster system pump or booster system, except for safety devices. c. No booster system pumps shall operate when there is no service water flow.

10.4.3 Elevators. Elevator systems shall comply with the requirements of this section.

10.4.3.1 Cab Lighting Power. For the luminaires in each elevator cab, not including power for germicidal function, signals, and displays, the sum of the lumens divided by the sum of the watts (as described in Section 9.1.4) shall be no less than 50 lm/W.

Exception to 10.4.3.1: This requirement does not apply to elevators in an essential facility where spe cial lighting needs are required.

10.4.3.2 Ventilation Efficacy. Cab ventilation for elevators, except elevators with air conditioning or MERV 13 or greater filters, shall have an efficacy of at least 4.0 cfm/W at maximum speed.

10.4.3.3 Standby Mode. The elevator cab lighting shall be automatically de-energized in accordance with ASME A17.1/CSA B44 Requirement 2.14.7.2.2. Cab ventilation fans for elevators without air conditioning shall also be de-energized.

When stopped and unoccupied with doors closed for over 15 minutes, cab interior lighting and ventila- tion shall be de-energized until required for operation.

Exception to 10.4.3.3: Forced ventilation shall meet the requirements of ASME A17.1/CSA B44

Requirement 2.14.2.3.3.

10.4.3.4 Energy Use. New elevators shall meet the following requirements:

a. Usage category as defined in ISO 25745-2 between 1 and 6. The usage category shall be in accordance

with Annex B. b. The energy efficiency class shall be E or better per ISO 25745-2, Table 7.

10.4.4 Escalators and Moving Walks. Escalators and moving walks shall automatically slow to the minimum permitted speed in accordance with ASME A17.1/CSA B44 or applicable local code when not conveying passengers.

10.4.5 Air Curtains. Air curtain unit performance shall be tested in accordance with ANSI/AMCA 220 or ISO 27327-1 and shall have a jet speed of not less than 6.6 ft/s at 6.0 in. above the floor . Automatic controls shall be provided that will operate the air curtain unit with the opening and closing of the door and comply with Section 6.4.3.9. To ensure proper operation, each air curtain unit shall be commissioned in accordance with the manufacturer ’s instructions, including airstream split location and direction.

10.4.6 Compressed Air Systems. All compressed air systems in factory industrial occupancies shall meet the requirements of Sections 10.4.6.1 through 10.4.6.5. These requirements apply to the compressors, related piping systems, and controls that provide compressed air. This section does not apply to any equip- ment or controls that use or process the compressed air.

Exception to 10.4.6: Medical air systems .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 173

PDF Page 176

Open page note

10.4.6.1 Part-Load Controls and Efficiency. Compressed air systems where the total motor power is 25 hp or more shall be equipped with appropriately sized trim compressor(s) and primary storage. The compressed air system shall comply with either of the following:

a. The compressed air system shall include one or more variable-speed-drive (VSD) compressors. For sys-

tems with more than one compressor, the total combined capacity of the VSD compressor(s) acting as trim compressors must be at least 1.25 times the largest net capacity increment between combinations of compressors. The compressed air system shall include primary storage of at least 3 gal per actual cubic feet per minute (acfm) of the largest trim compressor . b. The total effective trim capacity of a compressor system is the size of the continuous operational range

where the specific power of the compressor(s) ( kW /100 acfm) is within 15% of the specific power at their most efficient operating point. The total effective trim capacity of the system is the sum of the effective trim capacity of the trim compressors .

Systems shall include primary storage of at least 4 gal/acfm of the largest trim compressor and meet (1) or (2) as follows:

  1. S ystems with more than one compressor, not including backup compressors, shall include a compressor or set of compressors with total effective trim capacity at least the size of the largest net capacity increment between combinations of compressors, or the size of the smallest compressor, whichever is larger.

  2. For s ystems with one compressor, not including backup compressors, the total effective trim capacity shall include the range from 70% to 100% of rated capacity. Exceptions to 10.4.6.1:

  3. Alterations where the total combined added or replaced compressor motor power is less than the average per-compressor power of all compressors in the system .

  4. Alterations where all added or replaced compressors are VSD compressors and the compressed air system includes primary storage of at least 3 gal/acfm of the largest trim compressor.

  5. Compressed air systems that have been approved by the authority having jurisdiction as having demonstrated that the system serves loads for which typical air demand fluctuates less than 10%.

  6. Alterations of existing compressed air systems that include one or more centrifugal compressors.

10.4.6.2 Controls. Compressed air systems with three or more compressors, including backup compressors, with a combined input power of more than 150 hp shall operate with controls that are able to choose the most energy -efficient combination and loading of compressors in the system based on the current compressed air demand.

10.4.6.3 Monitoring. Compressed air systems having a combined input power rating equal to or greater than 150 hp shall have an energy and air demand monitoring system with the following minimum requirements:

a. Measurement of system pressure b. Measurement or calculation of current or power of each compressor c. Measurement or determination of total airflow from all compressors in acfm d. Data logging of pressure, power in kW, airflow in acfm, and compressed air system specific power in kW /

100 acfm at intervals of five minutes or less e. The equipment shall be configured to record not less than six months of data and shall be capable of

exporting the data. f. Visual trending display of each recorded point, load, and specific power.

10.4.6.4 Leak Testing of Compressed Air Piping. Compressed air system piping shall be pressure tested after being isolated from the compressed air supply, storage tanks, and end uses. The piping shall be pressurized to the design operating pressure and the pressure allowed to stabilize. Test pressures shall be held for no less than 30 minutes, with no loss of pressure greater than 1.0%.

For piping less than or equal to 50 adjoining feet in length, connections shall optionally be tested with a noncorrosive leak-detecting fluid or other leak detecting methods at the discretion of the authority having jurisdiction .

10.4.6.5 Pipe Sizing. For new systems and additions to systems with operating pressures above 50 psig, compressed air piping greater than 50 adjoining feet in length shall be designed and installed to minimize frictional losses in the distribution network.

Service line piping that delivers compressed air from distribution piping to end uses shall have inner diameters greater than or equal to 1 in.

Added or replaced piping in existing systems shall meet the requirements of Section 10.4.6.5(a). New systems shall meet the requirements of either Section 10.4.6.5(a) or (b).

174 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 177

Open page note

a. Piping section average velocity: Compressor room interconnection and main header piping shall be sized

so that at coincident peak flow conditions the average velocity in the segment of pipe is no greater than 20 ft/s. Compressor room interconnection and main header piping are the pipes that deliver compressed air from the compressor outlets to the inlet to the distribution piping . Each segment of distribution and service piping shall be sized so that at coincident peak flow conditions the average velocity in the segment of pipe is no greater than 30 ft/s. Distribution piping is pipes that deliver compressed air from the compressor room interconnection piping or main header piping to the service line piping . b. Piping total pressure drop : Piping shall be designed such that piping frictional pressure loss at coincident

peak loads are less than 5% of operating pressure between the compressor and connection at point of use, prior to any end-use regulators.

10.4.7 Whole-Building Energy Monitoring. Measurement devices shall be installed at the building site to monitor the energy use of each new building .

10.4.7.1 Monitoring. Measurement devices shall be installed to monitor the building use of the following types of energy supplied by a utility, energy provider, or plant that is not within the building :

a. Natural gas b. Fuel oil c. Propane d. Steam e. Chilled water f. Hot water

10.4.7.2 Recording and Reporting. The energy use of each building on the building site shall be recorded at a minimum of every 60 minutes and reported at least hourly, daily, monthly, and annually. The system shall be capable of maintaining all data collected for a minimum of 36 months and creating user reports showing at least hourly, daily, monthly, and annual energy consumption and demand .

Exceptions to 10.4.7.1 and 10.4.7.2:

  1. Buildings or additions less than 25,000 ft [2] .
  2. Individual tenant spaces less than 10,000 ft [2] .
  3. Dwelling units .
  4. Residential buildings with less than 10,000 ft [2] of common area.
  5. Fuel used for on- site emergency equipment .

10.4.8 Pumps. Clean water pumps meeting the following criteria shall comply with the requirements shown in Table 10.8-6:

a. A flow rate of 25 gal/min or greater at its best efficiency point (BEP) at full impeller diameter b. Maximum head of 459 ft at its BEP at full impeller diameter and the number of stages required for testing c. Design temperature range from 14°F to 248°F d. Designed to operate with either

  1. a 2- or 4-pole induction motor or

  2. a noninduction motor with a speed of rotation operating range that includes speeds of rotation between 2880 and 4320 rpm and/or 1440 and 2160 rpm, and

  3. in either (1) or (2), the driver and impeller must rotate at the same speed e. For submersible turbine pumps, a 6 in. or smaller bowl diameter f. For end-suction close-coupled pumps and end-suction frame-mounted/own bearings pumps, specific speed less than or equal to 5000 rpm when calculated using U.S. customary units Exceptions to 10.4.8: The standards in this section do not apply to the following pumps :

  4. Fire pumps .

  5. Self-priming pump .

  6. Prime-assist pumps .

  7. Magnet-driven pumps .

  8. Pumps designed to be used in a nuclear facility subject to 10 CFR 50, “Domestic Licensing of Production and Utilization Facilities.”

  9. Pumps meeting the design and construction requirements set forth in U.S. Military Specification MIL-P-17639F, “Pumps, Centrifugal, Miscellaneous Service, Naval Shipboard Use” (as amended); MIL-P-17881D, “Pumps, Centrifugal, Boiler Feed, (Multi-Stage)” (as amended); MIL-P-17840C, “Pumps, Centrifugal, Close-Coupled, Navy Standard (For Surface Ship Application)” (as amended); MIL-P-18682D, “Pump, Centrifugal, Main Condenser Circulating, Naval Shipboard”

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 175

PDF Page 178

Open page note

(as amended); MIL-P-18472G, “Pumps, Centrifugal, Condensate, Feed Booster, Waste Heat Boiler, And Distilling Plant” (as amended).

Informative Note: Informative Appendix E contains additional information on pump nomenclature and definitions which are available from ANSI-HI 1.1-1.2-2014 and ANSI-HI 2.1-2.2-2014.

10.5 Prescriptive Compliance Path 10.5.1 Renewable Energy Resources . Buildings shall be served by renewable energy resources complying with Section 10.5.1.1.

10.5.1.1 On-Site Renewable Energy. The building site shall have equipment for on-site renewable energy with a rated capacity of not less than 0.50 W/ft [2] or 1.7 Btu/ft [2] multiplied by the sum of the gross con- ditioned floor area for all floors up to the three largest floors.

Exceptions to 10.5.1.1:

  1. Any building located where an unshaded flat plate collector oriented toward the equator and tilted at an angle from horizontal equal to the latitude receives an annual daily average incident solar radiation less than 1.1 kBtu/ft [2] ·day.
  2. Any building where more than 80% of the roof area is covered by any combination of equipment other than for on-site renewable energy systems, planters, vegetated space, skylights, or occupied roof deck.
  3. Any building where more than 50% of roof area is shaded from direct-beam sunlight by natural objects or by structures that are not part of the building for more than 2500 annual hours between 8:00 a.m. and 4:00 p.m.
  4. New construction or additions in which the sum of the gross conditioned floor area of the three largest floors of the new construction or addition is less than 10,000 ft [2] .
  5. Alterations .

10.6 Alternative Compliance Path (Not Used)

10.7 Submittals 10.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

10.7.2 Permit Application Documentation (Not Used) 10.7.3 Completion Requirements 10.7.3.1 Record Documents. Construction documents shall require that within 90 days after the date of system acceptance, record documents shall be provided to the building owner.

10.7.3.2 Manuals (Not Used)

10.8 Product Information

10.9 Verification, Testing, Commissioning, and Documentation 10.9.1 Verification and Testing. Other applicable equipment shall be verified and tested in accordance with this section and Section 4.2.5.1. Testing shall verify that control elements and monitoring systems are configured and operating in accordance with Section 10.4.2, 10.4.3.3, 10.4.5, and 4.2.5.2. FPT documentation shall comply with applicable requirements of

a. service water pressure-booster system controls (Section 10.4.2), b. elevator standby mode (Section 10.4.3.3), c. air curtains (Section 10.4.5), d. whole- building energy monitoring (Section 10.4.7), and e. pumps (Section 10.4.8).

Verification and FPT documentation shall comply with Section 4.2.5.1.2. 10.9.2 Commissioning. The energy performance of the other equipment systems shall be commissioned in accordance with Section 4.2.5.2 and reporting shall comply with Section 4.2.5.2.2.

Informative Note: See Informative Appendix E and Informative Appendix H for commissioning resources.

10.9.3 Documentation. Design documents shall list the following for new elevators:

a. The usage category as defined in ISO 25745-2 between 1 and 6. The usage category shall be in accor dance with Annex B. b. The energy efficiency class per ISO 25745-2, Table 7.

176 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 179

Open page note

Table 10.8-1 Minimum Nominal Full-Load Efficiency for NEMA Design A, NEMA Design B, and IEC Design N Motors (Excluding Fire Pump Electric Motors) at 60 Hz [a,b]

Motor Horsepower, hpNominal Full-Load Efficiency, %Col3Col4Col5Col6Col7Col8Col9
Motor Horsepower, hp2-Pole2-Pole4-Pole4-Pole6-Pole6-Pole8-Pole8-Pole
Motor Horsepower, hpEnclosedOpenEnclosedOpenEnclosedOpenEnclosedOpen
177.077.085.585.582.582.575.575.5
1.584.084.086.586.587.586.578.577.0
285.585.586.586.588.587.584.086.5
386.585.589.589.589.588.585.587.5
588.586.589.589.589.589.586.588.5
7.589.588.591.791.091.090.286.589.5
1090.289.591.791.791.091.789.590.2
1591.090.292.493.091.791.789.590.2
2091.091.093.093.091.792.490.291.0
2591.791.793.693.693.093.090.291.0
3091.791.793.694.193.093.691.791.7
4092.492.494.194.194.194.191.791.7
5093.093.094.594.594.194.192.492.4
6093.693.695.095.094.594.592.493.0
7593.693.695.495.094.594.593.694.1
10094.193.695.495.495.095.093.694.1
12595.094.195.495.495.095.094.194.1
15095.094.195.895.895.895.494.194.1
20095.495.096.295.895.895.494.594.1
25095.895.096.295.895.895.895.095.0
30095.895.496.295.895.895.8NRNR
35095.895.496.295.895.895.8NRNR
40095.895.896.295.8NRNRNRNR
45095.896.296.296.2NRNRNRNR
50095.896.296.296.2NRNRNRNR

a. Nominal efficiencies shall be established in accordance with DOE 10 CFR 431. b. For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilo-

watt ratings listed in this table, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows:

  1. A horsepower at or above the midpoint between the two consecutive horsepowers shall be rounded up to the higher of the two horsepowers.
  2. A horsepower below the midpoint between the two consecutive horsepowers shall be rounded down to the lower of the two horsepowers.
  3. A kilowatt rating shall be directly converted from kilowatts to horsepower using the formula 1 kilowatt = (1/0.746) horsepower. The conversion should be calculated to three significant decimal places, and the resulting horsepower shall be rounded in accordance with paragraph (1) or (2), whichever applies. c. NR = no requirement.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 177

PDF Page 180

Open page note

Table 10.8-2 Minimum Nominal Full-Load Efficiency for NEMA Design C and IEC Design H Motors at 60 Hz [ a,b]

Motor Horsepower, hpNominal Full-Load Efficiency, %Col3Col4Col5Col6Col7
Motor Horsepower, hp4-Pole4-Pole6-Pole6-Pole8-Pole8-Pole
Motor Horsepower, hpEnclosedOpenEnclosedOpenEnclosedOpen
185.585.582.582.575.575.5
1.586.586.587.586.578.577.0
286.586.588.587.584.086.5
389.589.589.588.585.587.5
589.589.589.589.586.588.5
7.591.791.091.090.286.589.5
1091.791.791.091.789.590.2
1592.493.091.791.789.590.2
2093.093.091.792.490.291.0
2593.693.693.093.090.291.0
3093.694.193.093.691.791.7
4094.194.194.194.191.791.7
5094.594.594.194.192.492.4
6095.095.094.594.592.493.0
7595.495.094.594.593.694.1
10095.495.495.095.093.694.1
12595.495.495.095.094.194.1
15095.895.895.895.494.194.1
20096.295.895.895.494.594.1

a. Nominal efficiencies shall be established in accordance with DOE 10 CFR 431. b. For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilo-

watt ratings listed in this table, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows: 1.A horsepower at or above the midpoint between the two consecutive horsepowers shall be rounded up to the higher of the two horsepowers. 2.A horsepower below the midpoint between the two consecutive horsepowers shall be rounded down to the lower of the two horsepowers. 3.A kilowatt rating shall be directly converted from kilowatts to horsepower using the formula 1 kilowatt = (1/0.746) horsepower. The conversion should be calculated to three significant decimal places, and the resulting horsepower shall be rounded in accordance with paragraph (1) or (2), whichever applies.

Table 10.8-3 Minimum Average Full-Load Efficiency for Polyphase Small Electric Motors [ a]

Number of Poles Full-Load Efficiency, %Col3Col4
Number of PolesOpen MotorsOpen MotorsOpen Motors
Number of Poles246
**Synchronous Speed (RPM)**360018001200
Motor Size, hpCol2Col3Col4
0.2565.669.567.5
0.3369.573.471.4
0.5073.478.275.3
0.7576.881.181.7
177.083.582.5
1.584.086.583.8
285.586.5N/A
385.586.9N/A

a. Average full-load efficiencies shall be established in accordance with 10 CFR 431.

178 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 181

Open page note

Table 10.8-4 Minimum Average Full-Load Efficiency for Capacitor-Start Capacitor-Run andCapacitor-Start Induction-Run Small Electric Motors [a]

Number of Poles Full-Load Efficiency, %Col3Col4
Number of PolesOpen MotorsOpen MotorsOpen Motors
Number of Poles246
**Synchronous Speed (RPM)**360018001200
Motor Size, hpCol2Col3Col4
0.2566.668.562.2
0.3370.572.466.6
0.5072.476.276.2
0.7576.281.880.2
180.482.681.1
1.581.583.8N/A
282.984.5N/A
384.1N/AN/A

a. Average full-load efficiencies shall be established in accordance with 10 CFR 431.

Table 10.8-5 Minimum Nominal Full-Load Efficiency for Fire Pump Electric Motors [a]

Number of Poles Full-Load Efficiency, %Col3Col4Col5Col6Col7Col8Col9
Number of PolesOpen Drip-Proof MotorsOpen Drip-Proof MotorsOpen Drip-Proof MotorsOpen Drip-Proof MotorsTotally Enclosed Fan-Cooled MotorsTotally Enclosed Fan-Cooled MotorsTotally Enclosed Fan-Cooled MotorsTotally Enclosed Fan-Cooled Motors
Number of Poles24682468
**Synchronous Speed (RPM)**360018001200900360018001200900
Motor Size, hpCol2Col3Col4Col5Col6Col7Col8Col9
1NR82.580.074.075.582.580.074.0
1.582.584.084.075.582.584.085.577.0
284.084.085.585.584.084.086.582.5
384.086.586.586.585.587.587.584.0
585.587.587.587.587.587.587.585.5
7.587.588.588.588.588.589.589.585.5
1088.589.590.289.589.589.589.588.5
1589.591.090.289.590.291.090.288.5
2090.291.091.090.290.291.090.289.5
2591.091.791.790.291.092.491.789.5
3091.092.492.491.091.092.491.791.0
4091.793.093.091.091.793.093.091.0
5092.493.093.091.792.493.093.091.7
6093.093.693.692.493.093.693.691.7
7593.094.193.693.693.094.193.693.0
10093.094.194.193.693.694.594.193.0
12593.694.594.193.694.594.594.193.6
15093.695.094.593.694.595.095.093.6
20094.595.094.593.695.095.095.094.1
25094.595.495.494.595.495.095.094.5

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 179

PDF Page 182

Open page note

Table 10.8-5 Minimum Nominal Full-Load Efficiency for Fire Pump Electric Motors [a] (Continued)

Number of Poles Full-Load Efficiency, %Col3Col4Col5Col6Col7Col8Col9
Number of PolesOpen Drip-Proof MotorsOpen Drip-Proof MotorsOpen Drip-Proof MotorsOpen Drip-Proof MotorsTotally Enclosed Fan-Cooled MotorsTotally Enclosed Fan-Cooled MotorsTotally Enclosed Fan-Cooled MotorsTotally Enclosed Fan-Cooled Motors
Number of Poles24682468
**Synchronous Speed (RPM)**360018001200900360018001200900
Motor Size, hpCol2Col3Col4Col5Col6Col7Col8Col9
30095.095.495.4NR95.495.495.0NR
35095.095.495.4NR95.495.495.0NR
40095.495.4NRNR95.495.4NRNR
45095.895.8NRNR95.495.4NRNR
50095.895.8NRNR95.495.8NRNR

a. Nominal efficiencies shall be established in accordance with DOE 10 CFR 431. b. For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilo-

watt ratings listed in this table, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows: 1.A horsepower at or above the midpoint between the two consecutive horsepowers shall be rounded up to the higher of the two horsepowers. 2.A horsepower below the midpoint between the two consecutive horsepowers shall be rounded down to the lower of the two horsepowers. 3.A kilowatt rating shall be directly converted from kilowatts to horsepower using the formula 1 kilowatt = (1/0.746) horsepower. The conversion should be calculated to three significant decimal places, and the resulting horsepower shall be rounded in accordance with paragraph (1) or (2), whichever applies. NR—No requirement

Table 10.8-6 Maximum Pump Energy Index (PEI)

Maximum PEI for Pumps Manufactured on or after January 27, 2020

Pump TypeNominal Speed of
Rotation (RPM)
Operating ModeMaximum PEI aC-Value bTest Procedure
End suction, close coupled1800Constant load1.00128.4710 CFR Part 431
End suction, close coupled3600Constant load1.00130.4210 CFR Part 431
End suction, close coupled1800Variable load1.00128.4710 CFR Part 431
End suction, close coupled3600Variable load1.00130.4210 CFR Part 431
End suction, frame mounted1800Constant load1.00128.8510 CFR Part 431
End suction, frame mounted3600Constant load1.00130.9910 CFR Part 431
End Suction, frame mounted1800Variable load1.00128.8510 CFR Part 431
End suction, frame mounted3600Variable load1.00130.9910 CFR Part 431
In-line1800Constant load1.00129.3010 CFR Part 431
In-line3600Constant load1.00133.8410 CFR Part 431
In-line1800Variable load1.00129.3010 CFR Part 431
In-line3600Variable load1.00133.8410 CFR Part 431
Radially split, vertical1800Constant load1.00129.6310 CFR Part 431
Radially split, vertical3600Constant load1.00133.2010 CFR Part 431
Radially split, vertical1800Variable load1.00129.6310 CFR Part 431
Radially split, vertical3600Variable load1.00133.2010 CFR Part 431
Submersible turbine1800Constant load1.00138.7810 CFR Part 431
Submersible turbine3600Constant load1.00134.8510 CFR Part 431
Submersible turbine1800Variable load1.00138.7810 CFR Part 431
Submersible turbine3600Variable load1.00134.8510 CFR Part 431

a. For pumps with the constant load operating mode, the relevant PEI is PEICL . For pumps with the variable load operating mode, the relevant PEI is PEIVL . b. The C-values shown in this table shall be used in the equation for PEISTD when calculating PEICL or PEIVL.

180 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 183

Open page note

11. ADDITIONAL EFFICIENCY REQUIREMENTS

11.1 General

a. HVAC systems that account for more than 50% of the capacity serving either the heating or cooling loads

of the alteration area. This includes HVAC unitary systems, HVAC terminal units, or components of HVAC central heating or cooling equipment, not including ductwork or piping . HVAC terminal units, for the purposes of this section, can include VAV boxes, fan-coil units, VRF room units, or water-loop heat pumps. b. Fifty percent (50%) or more of the luminaires in the alteration area c. Twenty-five percent (25%) or more of the building envelope area of the alteration portion of the build-

ing, including new exterior cladding, fenestration, or insulation

Informative Note: Substantial alterations are intended to include a major renovation of part or all of an existing building that extends the life of the building and includes major replacement of at least two major building systems .

11.1.4.2 Initial Build-Out Construction. The building envelope, equipment, and systems in initial build-out construction exceeding 1000 ft [2] of gross floor area in buildings where the alteration did not have final lighting or HVAC systems installed under a prior building permit shall comply with the requirements of Section 11.2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 181

PDF Page 184

Open page note

10

11

11.1.5 Climate. Climate zones shall be determined in accordance with Section 5.1.5.

11.2 Compliance Paths. New buildings, additions, substantial alterations as described in Section 11.1.4.1,

11.2.2 Additional Requirements to Comply with Section 11 (Not used)

11.3 Simplified Building Compliance Path (Not used)

Informative Note: The energy credit values in Table 11.5.1-1 and Tables 11.5.3-1 through 11.5.3-9 represent about 0.1% total building annual energy cost savings per point.

11.5.1 Energy Credits Required. Projects shall achieve the total of credits required in Table 11.5.1-1 based on the building use type and climate zone. Projects with multiple building use types, unconditioned or semiheated buildings, parking garages, projects using on-site renewable energy, alterations, and buildings with separate shell-and-core and initial build-out construction permits shall comply as follows:

a. Where a project contains multiple building use types or situations covered in items (b), (c), and (d)

  1. The building core and shell project shall achieve at least 50% of the energy credits required in Table 11.5.1-1 where the core and shell project includes a central HVAC system or service water heating system that includes chillers, boilers, service water heating equipment, or loop pumping systems with heat rejection. Otherwise, the building core and shell project shall achieve at least 33% of the energy credits required in Table 11.5.1-1. The building core and shell permit shall not be eligible for credits from measures involving nonpermanent services in future build-out areas, such as freeze protection and limited lighting.
  2. Initial build-out construction, as described in Section 11.1.4.2, shall be deemed to comply with this section where one of the following applies: i. Where the initial build-out project includes HVAC heating and cooling generation equipment, the energy credits achieved under the initial build-out project are not less than 50% of the credits required in Table 11.5.1-1. ii. Where the initial build-out project receives heating and cooling services from the core and shell

building —excluding condenser loop water—the energy credits achieved under the initial buildout project are not less than 25% of the credits required in Table 11.5.1-1. iii. The energy credits achieved under the initial build-out project, plus the energy credits achieved

under a prior core and shell permit—not including core and shell credits from measures L02, L03, L04, L05, L06, G01, or G02—total at least the credits required in Table 11.5.1-1.

d. Unconditioned spaces, semiheated spaces, and parking garages shall achieve 50% of the credits required

for the “Other” building use type in Table 11.5.1-1. e. Where roof space or insolation available for on-site renewable energy is limited according to the defini tion of RA net in Equation 11.5.1, the energy credit requirement in Table 11.5.1-1 shall be adjusted and EC adj used in place of EC req, where EC adj is determined using one of the following:

  1. Where the project meets any exception to Section 10.5.1.1, the PV adj credits shall be subtracted from the credits required for the climate zone to find EC adj .
  2. Otherwise, energy credits adjusted for renewable energy resource availability shall be determined as follows:

182 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 185

Open page note

12

Table 11.5.1-1 Energy Credit Requirements by Building Use Type

Building Use
Type a
Climate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Use
Typea
0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamilyb50505050505046505048504650504950505050
Health carec50464746474549475046465050505050505050
Hotel/motel50454746494846475048505047464749465050
Officed50505050505050505050505050505050505050
Restaurante50505050505050505050505050505050505050
Retail50505050505050505050505049504748454246
Educationf50505050505050505050505050505050505046
Warehouseg50505050505050505050505050505050505050
Otherh39363737353430323328323029313029302929

a. All building use types include supporting functions such as corridors, break rooms, lobbies, restrooms, mechanical rooms, storage rooms, conference rooms, individual equipment

and computer rooms with loads ≤10 kW, minor snack and beverage service without a commercial kitchen, and up to 10% of gross floor area of other building use types such as an office area less than 2000 ft [2] in a nonoffice building use type. b. “Multifamily” includes apartments, condominiums, dormitories, retirement living facilities, nontransient lodging, and residential portions of institutional care facilities, excluding

prisons. c. “Health Care” includes buildings within the scope of ASHRAE Standard 170 ventilation requirements that are dedicated to patient care, including related support areas of health

care facilities, hospitals, nursing facilities, outpatient facilities, and surgery centers. d. Office includes offices or clinics where medical, dental, psychotherapy, physical therapy or other services are provided that are not within the scope of ASHRAE Standard 170

ventilation requirements. e. Restaurants with commercial kitchens and dining areas that are separate buildings or constructed under separate permits shall meet restaurant building use type requirements. Where

restaurants are part of a larger building and are not seeking credit for either measure W01, W02, W03, or Q02, their area is permitted to be included with the larger building use type. f. Education includes schools, lecture halls, gymnasiums, and libraries. g. Warehouse that are conditioned spaces, including storage and distribution building s, refrigerated warehouses, and storage rental facilities. h. All other buildings, including any building use not covered in the eight listed building use types above and data centers using Standard 90.4, shall use the energy credits required

and available for the “Other” category.

Table 11.5.1-2 Renewable Adjustment Credits

Building Use
Type
PV by Climate Zone
adj
Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20PV,
incl
W/ft2
Building Use
Type
0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B788
Multifamily6787818161920131314691367650.1
Health care33333434757323333220.1
Hotel/motel48999121013891088129910850.1
Office6677128891079768767650.1
Restaurant11111212212111111110.1
Retail5566781417167141210141210121070.1
Education5676791614121111911119121012100.1
Warehouse202020202020202020192020142020121712100.1
Other66777879979758767540.1

EC adj = EC req - PV adj   1 - -------------------------------------------------- Gfloor  RAPV netincl  0.20 - 

(11.5.1)

where EC adj = adjusted energy credit requirement used instead of the energy credit requirement from Table 11.5.1-1 EC req = energy credit requirement from Table 11.5.1-1 PV adj = PV adj for building type from Table 11.5.1-2 RA net = horizontal projection of roof area available for renewable energy resources not covered by any

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 183

PDF Page 186

Open page note

13

combination of equipment other than for on-site renewable energy systems, planters, vegetated space, skylights, or occupied roof deck after meeting requirements of Section 10.5.1 Gfloor = gross floor area of building, ft [2]

PV incl = PV incl for building type from Table 11.5.1-2, W/ft [2]

Exceptions to 11.5.1:

  1. Portions of buildings devoted to manufacturing or industrial use not including office areas.

  2. Where the core/shell complies in accordance with Normative Appendix G or Section 12, the initial build-out alterations do not need to achieve any energy credits. Informative Notes:

  3. Under Section 11.5.1(a), a building may be split into multiple building use types unless there is a small area less than 10% of the gross floor area of a different use type. Examples: A small managers office in a multifamily building, retail, or hotel would be included with the main multifamily or other use type, while a large administrative wing of a hospital (>10% of gross building area or greater than 2000 ft [2] ) would be a separate building use type. A coffee bar in the lobby of an office building or bookstore would be included with the office or retail use type, while a restaurant with a commercial kitchen in a hotel seeking hot water or kitchen equipment measures would be a separate building use type, regardless of relative size.

Where office areas 2000 ft [2] or more are associated with a larger building of a different type, such as a data center, warehouse, or hospital, the office area should be separated for energy credit treatment in the office building category, even if the special use was less than 10% of the total project building area. 2. The energy credit requirements in Table 11.5.1-1 are based on a cost-effectiveness analysis of a selection of credits that would typically be applied to each building use type. In all cases, photovoltaic renewable credits are included. The renewable credit adjustment in item (e) (based on Table 11.5.1-2) is included so that, where on-site renewable energy is not feasible, the required credits are appropriately reduced to match a typical cost-effective package of measures.

types, credits achieved for each building use type shall be weighted by the gross floor area of each building

a. The measure energy credit shall be the base energy credit for the measure, where no adjustment factor or

formula is shown in the measure description (e.g., EC H02_base ). b. The measure energy credit shall be the base energy credit for the measure, adjusted by a factor or formula

as stated in the measure description in this section. Where adjustments are applied, each measure energy credit shall be rounded to the nearest whole number (e.g., EC H02_adj ). c. The measure energy credit shall be by direct formula as stated in the measure description in this section,

where each measure credit shall be rounded to the nearest whole number (e.g., EC H02_calc ).

Informative Note: The number of energy credits achieved for each individual measure is determined in

one of three ways:

  1. The base energy credit for the measure shown in Tables 11.5.3-1 through 11.5.3-9 for the building use type and climate zone where no adjustment factor or formula is shown in the measure description. This applies to the following measures:

    • H04: 11.5.2.2.4, “Residential Space HVAC Control”

    • H07: 11.5.2.2.7, “Improved HVAC Sequence of Operations”

    • W01: 11.5.2.3.1(a), “Heat Recovery for Service Hot-Water Preheating”

    • W05: 11.5.2.3.3(a), “Point-of-Use Water Heater”

    • W06: 11.5.2.3.3(b), “Thermostatic Balancing Valves”

    • W07: 11.5.2.3.4, “Dwelling-Unit Service Hot-Water Submeters”

    • W08: 11.5.2.3.5, “Right Sizing the Hot-Water Distribution System”

    • P01: 11.5.2.4, “Energy Monitoring”

184 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 187

Open page note

  • L03: 11.5.2.5.3, “Occupancy Sensor Control Areas”

    - Q02: 11.5.2.7.2, “Efficient Kitchen Equipment”
    
    - Q03: 11.5.2.7.3, “Fault Detection and Diagnostics System”
    
    - G02: 11.5.2.8.2, “HVAC Load Management”
    
    - G03: 11.5.2.8.3, “Automated Shading Load Management”
    
    - G07: 11.5.2.8.7, “Building Thermal Mass”
    
  1. The base credit for the measure shown in Tables 11.5.3-1 through 11.5.3-9 for the building use type and climate zone adjusted by proration factor or formula as stated in the measure description in this section. This applies to the following measures:

    • H02: 11.5.2.2.2, “HVAC Heating Performance Improvement”

    • H03: 11.5.2.2.3, “HVAC Cooling Performance Improvement”

    • H05: 11.5.2.2.5, “Ground-Source Heat-Pump System”

    • H06: 11.5.2.2.6, “Dedicated Outdoor Air System with Zone Fan Control”

    • W02: 11.5.2.3.1(b), “Heat-Pump Water Heater”

    • W03: 11.5.2.3.1(c), “Efficient Gas Water Heater”

    • W04: 11.5.2.3.2, “Service Hot-Water Piping Insulation Increase”

    • W09: 11.5.2.3.6, “Shower Drain Heat Recovery”

    • L02: 11.5.2.5.2, “Continuous Dimming and High-End Trim”

    • L04: 11.5.2.5.4, “Increased Daylighting Control Area”

    • L05: 11.5.2.5.5, “Lighting Control for Multifamily Buildings”

    • L06: 11.5.2.5.6, “Reduce Interior Lighting Power”

    • R01: 11.5.2.6, “On-Site Renewable Energy”

    • Q01: 11.5.2.7.1, “Efficient Elevator Equipment”

    • G01: 11.5.2.8.1, “Lighting Load Management”

    • G04: 11.5.2.8.4, “Electric Energy Storage”

    • G05: 11.5.2.8.5, “HVAC Cooling Energy Storage”

    • G06: 11.5.2.8.6, “Service Hot-Water Thermal Storage”

  2. By direct formula, as stated in the measure description in this section. This applies to the following measure:

    • E01: 11.5.2.1, “Improved Envelope Performance” 11.5.2.1 E01: Improved Envelope Performance. To achieve this credit, building envelope measures shall be installed to improve the energy performance of the project. Measure energy credits for improvement of the building envelope energy performance shall be determined based on the following:

EC E01 _ calc = 1000  EPF---------------------------------------------------- E01_base EPF E01_base - EPF prop -

where EC E01_calc = energy credits achieved for improved envelope performance EPF E01_base = base envelope performance factor calculated in accordance with Normative Appendix C EPF prop = proposed envelope performance factor calculated in accordance with Normative Appendix C 11.5.2.2 Improved HVAC Performance. To achieve these credits, equipment shall provide HVAC performance improvement in accordance with Section 11.5.2.2.2, 11.5.2.2.3, 11.5.2.2.4, 11.5.2.2.5, or 11.5.2.2.6. Equipment shall also meet applicable requirements of Sections 6.4 and 6.5. Credits shall be as shown in Section 11.5.3 or as specified in each subsection for building use types where base credits are included in Section 11.5.3 tables. Use of multiple credits from this section shall be allowed. 11.5.2.2.1 H01: HVAC System Performance Improvement (Reserved) 11.5.2.2.2 H02: HVAC Heating Performance Improvement. To achieve this credit, space heating equipment shall exceed the minimum heating efficiency requirements by 5% or more than listed in the tables in Section 6.8.1. The measure energy credit for heating efficiency improvement (EC HE ) shall be determined as follows:

= EC H02 _ base  ------------0.05 -

EC H02 _ adj = EC H02 _ base

EI heat

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 185

PDF Page 188

Open page note

where EC H02_adj = energy credits achieved for heating efficiency improvement EC H02_base = H02 base energy credit from Section 11.5.3 EI heat = lesser of the percentage improvement (as a fraction) above minimum heating efficiency

requirements or 20% (0.20). Where heating equipment with different minimum efficiencies are included in the building, a heating capacity weighted-average improvement shall be used. Where electric resistance primary heating or reheat is included in the building, it shall be included in the weighted-average improvement with an EI heat of 0. Supplemental gas and electric heat for heat-pump systems shall be excluded from the weighted EI heat . For heat pumps rated at multiple ambient temperatures, use the efficiency at 47  F. Gas-fired boiler systems that are required to meet provisions of Section 6.5.4.8 shall use the minimum system efficiency as defined in Section 6.5.4.8.1. Gas-fired boiler systems that are required to meet provisions of Section 6.5.4.8 shall use the minimum system efficiency as defined in Section 6.5.4.8.1.

For metrics that increase as efficiency increases, EI heat shall be calculated as follows:

EI heat

= ----------------HM des - 1 HM min

where HM des = design heating efficiency metric, part-load or annualized where available HM min = minimum required heating efficiency metric, part-load or annualized where available from Section 6.8.1 or Informative Appendix F Informative Note: An example of an annualized or part-load heating efficiency is AFUE rather than Et or Ec . Where only one efficiency rating is provided for equipment in Section 6.8.1 or Informative Appendix F, use that metric.

11.5.2.2.3 H03: HVAC Cooling Performance Improvement. To achieve this credit, space cooling equipment shall exceed the minimum cooling efficiency requirements by 5% or more than listed in the tables in Section 6.8.1 or Informative Appendix F. For water-cooled chiller plants, heat rejection efficiency shall also exceed the minimum efficiency listed in Table 6.8.1-7 by at least the percentage improvement in the chiller efficiency . The measure energy credit (EC CE ) for cooling efficiency improvement shall be determined as follows:

= EC H03 _ base  ------------0.05 -

EC H03 _ adj = EC H03 _ base

EI cool

where EC H03_adj = energy credits achieved for cooling efficiency improvement EC H03_base = H03 base energy credits from Section 11.5.3 EI cool = lesser of the percentage improvement (as a fraction) above minimum cooling efficiency requirements or 20% (0.20). Where cooling equipment with different minimum efficiencies are included in the building, a cooling capacity weighted-average improvement shall be used. Where multiple cooling performance requirements are provided, the equipment shall exceed the annualized energy or part-load requirement. Meeting both part-load and full-load efficiencies is not required. For metrics that increase as efficiency increases, EI cool shall be calculated as follows:

EI cool

= --------------CM des - - 1 CM min

For metrics that decrease as efficiency increases, EI cool shall be calculated as follows:

EI cool

= CM-------------- min - - 1 CM des

where CM min = minimum required cooling efficiency metric, part-load or annualized where available from Section 6.8 or Informative Appendix F CM des = design cooling efficiency metric, part-load or annualized where available

186 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 189

Open page note

Table 11.5.2.2.5 GSHP HeatRejection AdjustmentsCol3Col4
Climate ZonesHR****adj by Field Source CapacityHR****adj by Field Source CapacityHR****adj by Field Source Capacity
Climate ZonesFull-Sized Bore Field
with no Heat Rejection
90% Hours Source Size;
Dry-Cooler Heat Rejection
90% Hours Source Size;
Evaporative Heat Rejection
0A, 1B, 2B, 3A, 3B, 4A, 4B3.32.6
0B, 1A, 2A, 3C7.65.3
4C, 5A, 5B, 5C2.31.5
6A, 6B, 7, 81.41.1
All climate zones1.0

For data centers using Standard 90.4, EI cool shall be calculated as follows:

EI cool

= AMLC----------------------- max - - 1 AMLC des

where AMLC max = maximum annualized mechanical load component from Standard 90.4, Table 6.5 AMLC des = as-designed annualized mechanical load component calculated in accordance with Standard 90.4, Section 6.5 Informative Note: An example of an annualized or part-load cooling efficiency is IEER rather than EER, or IPLV kW /ton rather than FL kW /ton. Where only one efficiency rating is provided for equipment in Section 6.8.1 or Informative Appendix F, use that metric.

11.5.2.2.4 H04: Residential Space HVAC Control. To achieve this credit, in buildings with nontran- sient residential spaces, HVAC system s serving dwelling units shall be controlled to automatically activate the setback condition with one of the following:

a. A main control by each dwelling-unit main entrance that initiates setback and non- ventilation mode for all

HVAC units serving the dwelling unit and that is clearly identified as “Heating/Cooling Master Setback.” b. Occupancy sensors in each room of the dwelling unit combined with a door switch to initiate setback and

non- ventilation mode for all HVAC units in the dwelling within 20 minutes of a door switch operation followed by all spaces being vacant. Where separate room HVAC units are used, individual occupancy sensors shall meet this requirement. c. An advanced learning thermostat or controller that recognizes occupant presence and automatically cre ates a schedule for occupancy and provides a dynamic setback schedule based on when the spaces are generally unoccupied. Where ventilation is provided by a separate system, it shall also have occupancy sensor control .

11.5.2.2.5 H05: Ground-Source Heat-Pump System. To achieve this credit, a ground-source heatpump system shall provide cooling and heating for at least 25% of the gross conditioned building area . The ground-source heat-pump systems shall include building ground-loop HVAC systems coupled with a closedbore ground-heat exchanger, submerged heat exchanger using water-based fluid as a heat transfer medium, groundwater (well), or fluid infrastructure (such as effluent and wastewater), and shall comply with the following:

a. Loop pump(s) shall have controls and/or devices that will result in pump motor demand of no more than

30% of design wattage at 50% of design water flow and allow turndown to 15% flow. Alternatively, a separate field-loop pump shall be provided, with either a variable-speed building pump or individual pumps for each ground-source heat pump. b. The geothermal-source exchanger shall be sized based on the heating and cooling loads served by the

ground-source heat-pump system and shall comply with one of the following:

  1. A closed bore field shall have at least 400 lineal ft of bore piping per 12,000 Btu/h of system cooling or heating capacity, whichever is greater. The system shall not include additional heat rejection or addition devices.
  2. The ground source shall be sized such that the loop heat pumps provide 100% of the heating and cooling loads for at least 90% of both the cooling and heating system annual operating hours without requiring any supplemental heating or heat rejection from nonground sources, as demonstrated by an

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 187

PDF Page 190

Open page note

Table 11.5.2.2.6 DOAS Energy Recovery Adjustments

ERE adj Based on Lower of Actual Heating or Cooling Energy Recovery Effectiveness where Required

Cooling ERR Is ≥Heating Enthalpy Recovery Ratio
(ERR) or Sensible Energy Recovery
Ratio Is ≥
Energy Recovery Effectiveness Adjustment
(ERE )
adj
65%65%1.00
60%60%0.67
55%55%a0.33
50%50% a0.25

a. In climate zones where heating recovery is required for this measure, for multifamily buildings heating energy recovery effectiveness below 60% is not

allowed.

analysis approved by the authority having jurisdiction . Heat rejection shall include a two-speed or variable-speed fan.

The allowed credits are based on serving 25% of gross conditioned building area and including dry-cooler partial heat rejection. Adjust the base credits as follows:

= EC H05 _ base  ------------------------0.25  HR adj

EC H05 _ adj = EC H05 _ base

Floor GSHP

where EC H05_adj = energy credits achieved for ground-source heat-pump system EC H05_base = H05 base energy credit from Section 11.5.3 Floor GSHP = fraction of whole-project gross conditioned floor area with heating and cooling provided by the ground-source heat pump. HR adj = heat-rejection adjustment factor by climate zone from Table 11.5.2.2.5 11.5.2.2.6 H06: Dedicated Outdoor Air System with Zone Fan Control. Credits for this measure are only allowed where single-zone HVAC units are not required to have multispeed or variable-speed fans in accordance with Section 6.5.3.2.1. HVAC controls and ventilation systems shall include all of the following:

a. Zone controls shall cycle the heating/cooling-unit fans off when not providing required heating and cool ing or shall limit fan power to 0.12 W/cfm of air delivered to the zone by the unit. b. Outdoor air shall be supplied by an independent ventilation system designed to provide no more than

110% of the minimum outdoor air to each individual occupied space as specified by Standard 62.1 c. The ventilation system shall have energy recovery with an enthalpy recovery ratio ( ERR ) of 65% or more

at heating design conditions in Climate Zones 3 through 8 and an ERR of 65% or more at cooling design conditions in Climate Zones 0, 1, 2, 3A, 3B, 4A, 4B, 5A, and 6A. In “A” climate zones, energy recovery shall include latent recovery. Where no humidification is provided, heating energy recovery effectiveness is permitted to be based on sensible energy recovery ratio . Where energy recovery effectiveness is less than the 65% required for full credit, adjust the credits from Section 11.5.3 by the factors in Table 11.5.2.2.6. d. Where the ventilation system serves multiple zones, partial economizer cooling through an outdoor air

bypass shall automatic ally reset the energy recovery leaving air temperature at 55  F or 100% outdoor air bypass when a majority of zones require cooling and outdoor air temperature is below 70  F. Recoverywheel speed control or other means are permitted to allow partial economizer cooling. Partial economizer cooling is not required in a latent recovery outdoor air dehumidification mode. e. Ventilation systems providing mechanical dehumidification shall use recovered energy for reheat within

the limits of item (d). This shall not limit the use of latent energy recovery for dehumidification.

Where only a portion of the building is served by constant-air-volume (CAV) units or the ERR or sensi- ble energy recovery ratio is less than 65%, the base energy credit shown in Section 11.5.3 shall be prorated as follows:

EC H06 _ adj = EC H06 _ base  Floor CAV  ERE adj

where EC H06_adj = energy credits achieved for dedicated outdoor air system with zone fan control EC H06_base = H06 base energy credit from Section 11.5.3

188 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 191

Open page note

Floor CAV = fraction of whole-project gross conditioned floor area where constant-air-volume singlespeed fans are allowed and meet measure requirements

ERE adj = energy recovery adjustment from Table 11.5.2.2.6 based on the lower of actual cooling or heating ERR or sensible energy recovery ratio where required for the climate zone

11.5.2.2.7 H07: Improved HVAC Sequence of Operations. To achieve this credit, all applicable control sequences shall be based on ASHRAE Guideline 36. Credits for this measure are only allowed where the HVAC system includes at least one of the following: a VAV air handler serving at least five (5) zone terminals, a chilled-water plant with at least two chillers, or a hot-water plant with at least two boilers or heat pumps.

11.5.2.3 Reduced Energy Use in Service Water Heating. Energy credits described in Section 11.5.2.3.1 through 11.5.2.3.6 are available in any combination described in those sections for building use types where base credits are included in Section 11.5.3 tables.

11.5.2.3.1 Improved Service Water Heating Effectiveness. Service water heating effectiveness energy credits are permitted to be achieved in building use types where credits are available in Section 11.5.3 for one of the following:

a. W01: Heat Recovery for Service Hot-Water Preheating. To achieve this credit, the service water

heating system shall have waste heat recovery from service hot water, heat recovery chillers, building equipment, or process equipment that is sized to provide not less than 30% of the annual hot-water requirements or sized to provide not less than 70% of the annual hot-water requirements if the building is required to comply with Section 7.5.3. b. W02: Heat-Pump Water Heater. To achieve this credit, air source heat-pump water heater s shall be

installed according to the manufacturer ’s instructions, and at least 30% of design end-use service water heating requirements shall be met using only heat-pump heating at an ambient condition of 67.5°F db without supplemental electric resistance or fossil fuel heating. For a hybrid heat-pump water heater, the heat-pump-only capacity shall be deemed at 40% of first hour draw. Where the heat-pump-only capacity exceeds 50% of the design end-use load, excluding recirculating system losses, the credits from the Section 11.5.3 tables shall be prorated as follows:

EC W02 _ calc = EC W02 _ base  -----------------------------------EndLoadCap HPWH  0.5  not greater than 2 

where

EC W02_calc = energy credits achieved for heat-pump water heater

EC W02_base = W02 base energy credit from Section 11.5.3 Cap HPWH = heat-pump-only capacity at 50  F entering air and 70  F without supplemental electric resistance or fossil fuel heat, Btu/h

EndLoad = end-use peak hot-water load, excluding load for heat trace or recirculation, Btu/h

The heat-pump service water heating system shall comply with the following requirements:

  1. For central systems with an installed total output capacity of more than 100,000 Btu/h at an ambient condition of 67.5  F db, a preheat storage tank with ≥0.75 gal per 1000 Btu/h of design end-use ser- vice water heating requirements shall be heated only with heat-pump heating when the ambient temperature is >45  F.
  2. For systems with piping temperature maintenance, either a heat trace system or a separate water heater in series for recirculating system and final heating shall be installed.
  3. Heat-pump water heater efficiency shall meet or exceed one of the following: i. Output-capacity-weighted-average uniform energy factor (UEF) of 3.0 with a medium draw pattern in accordance with 10 CFR 430 Appendix E. ii. Output-capacity-weighted-average COP of not less than 4.0 tested at 50  F entering air and 70  F

entering water in accordance with AHRI Standard 1300. Informative Note: Service water heating system control settings and operating temperatures should be determined in accordance with the ASHRAE Standard 188 building water systems water management program for the building or with generally accepted engineering standards and guidance (e.g., ASHRAE Guideline 12). c. W03: Efficient Gas Water Heater. To achieve this credit, the combined input-capacity-weighted-average

equipment rating of all gas water heating equipment in the building shall be not less than 95% Et or 0.93 UEF. Buildings required to comply with Section 7.5.3 shall receive 29.6% of the Section 11.5.3 W03

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 189

PDF Page 192

Open page note

credit. Buildings where the installed service water heating capacity is less than 200,000 Btu/h and weighted UEF is not less than 0.82 shall achieve 25% of the base table W03 credit. d. Combination service water heating systems shall achieve credits as follows:

  1. (W01 + W02) Where service water heating employs both energy recovery and heat-pump water heating, W01 is permitted to be combined with W02 and receive the sum of both credits.
  2. (W01 + W03) Where service water heating employs both energy recovery and efficient gas water heating, W01 is permitted to be combined with W03 and receive the sum of the W01 credit and the portion of the W03 credit based on item (4).
  3. (W02 + W03) Where service water heating employs both heat-pump water heating and efficient gas water heating, W02 is permitted to be combined with W03 and receive the sum of the W02 credit and the portion of the W03 credit based on item (4).
  4. For items (2) and (3), the portion of W03 credit shall be the Section 11.5.3 W03 credit multiplied by the share of total water heating installed capacity served by gas water heating with not less than 95% Et or 0.93 UEF. In no case shall it exceed 60% of the W03 credit in Section 11.5.3. In buildings that have a service water heating design generating capacity greater than 900,000 Btu/h, that proportioned W03 credit shall be further multiplied by 29.6%. 11.5.2.3.2 W04: Service Hot-Water Piping Insulation Increase. To achieve this credit, where service hot water is provided by a central water heating system, the hot-water pipe insulation thickness shall be at least 1.5 times the thickness required in Table 6.8.3-1. All service hot-water piping shall be insulated from the hot-water source to the fixture shutoff. Where no more than 50% of hot-water piping does not have increased insulation due to installation in partitions, the credit shall be prorated as a percentage of lineal feet of piping with increased insulation.

11.5.2.3.3 Improved Service Hot-Water Temperature Maintenance. To achieve this credit, hotwater distribution temperature maintenance shall comply with one of the following:

a. W05: Point-of-Use Water Heater. Credits are available for office or school buildings larger than 10,000

ft [2] . Fixtures requiring hot water shall be supplied from a localized source of hot water with no recirculating system or heat trace piping . Supply piping from the water heater to the termination of the fixture supply pipe shall be insulated to the levels shown in Table 6.8.3-1 without exception. The volume from the water heater to the termination of the fixture supply pipe shall be limited as follows:

  1. Nonresidential lavatories: not more than 2 oz
  2. All other plumbing fixtures or appliances: not more than 0.25 gal Exception to 11.5.2.3.3(a): Where all remotely located hot-water uses meet the requirements for mea sure W05, separate water heater s serving commercial kitchens or showers in locker rooms shall be permitted to have a local recirculating system or heat trace piping . b. W06: Thermostatic Balancing Valves. Credits are available where service water heating is provided

centrally and distributed throughout the building . Each recirculating system branch return connection to the main service hot-water supply piping shall have an automatic thermostatic balancing valve set to a minimal return water flow when the branch return temperature is greater than 125  F.

11.5.2.3.4 W07: Dwelling-Unit Service Hot-Water Submeters. To achieve this credit, each individual dwelling unit in a multifamily building served by a central service water heating system shall be provided with a service hot-water meter connected to a reporting system that provides individual dwelling unit reporting of actual domestic hot-water use. Recording of preheated water serving the cold water inlet to showers need not be metered.

11.5.2.3.5 W08: Right Sizing the Service Hot-Water Distribution System. To achieve this credit, where multifamily, dormitory, retirement, or hotel/motel buildings are served by a central service hot-water system, the distribution system serving dwelling units and guest rooms shall be sized using IAPMO/ANSI WE•Stand, Appendix C. Plumbing fixtures in residential spaces that are connected to the service water heat- ing system shall have a flow or consumption rating less than or equal to the values shown in Table 11.5.2.3.5.

Informative Note: Where low water supply pressures are anticipated, user satisfaction may be enhanced if flow restrictors are specified to provide ≥80% of the rated flow at 20 psi. Where the distribution sizing protocol is applied to other than multifamily residential buildings, a variance to the plumbing code may be needed.

11.5.2.3.6 W09: Shower Drain Heat Recovery. To achieve this credit, cold water serving building showers shall be preheated by shower drain heat recovery units that comply with CSA B55.2. Potable waterside pressure loss shall be less than 10 psi at maximum design flow. The efficiency of drain heat recovery units shall be 54% or greater measured in accordance with CSA B55.1. Full credits are applicable to the fol

190 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 193

Open page note

Table 11.5.2.3.5 Maximum Flow Rating for Residential Plumbing Fixtures with Heated Water

Plumbing FixtureMaximum Flow Rate
Faucet for private lavatory a, hand sinks, or bar sinks1.50 gpm at 60 psi
Faucet for_residential_ kitchen sink a, b, c1.8 gpm at 60 psi
Shower head (including hand-held shower spray) a, b, d2.0 gpm at 80 psi

a. Shower heads, lavatory faucets, and kitchen faucets are subject to U.S. federal requirements listed in 10 CFR 430.32(o) through (p). b. Maximum flow allowed is less than required by flow rates listed in U.S. 10 CFR 430.32(o) through (p) for shower heads and kitchen faucets. c. A residential kitchen faucet is permitted to temporarily increase the flow above the maximum rate but not above 2.2 gal/min at 60 psi and must default

to the maximum flow rate listed. d. When a shower is served by multiple shower heads, the combined flow rate of all shower heads controlled by a single valve shall not exceed the maximum

flow rate listed, or the shower shall be designed to allow only one shower head to operate at a time.

lowing building use types: health clinic, hospital, hotel, motel, multifamily, retirement facility, dormitory, and schools with more than eight showers. Partial credits are applicable to buildings where all but groundfloor showers are served, where the base energy credit is adjusted by the following factor:

= EC W09 _ base  --------------------------------------------------------------------------------Total showers in building

EC W09 _ adj = EC W09 _ base

Showers with drain heat recovery

11.5.2.4 P01: Energy Monitoring. To achieve this credit, projects not required to have electrical energy monitoring systems installed in accordance with Section 8.4.3 shall be equipped to measure, monitor, record, and report energy consumption data in compliance with Section 8.4.3.

11.5.2.5 Lighting Efficiency Measures. To achieve these credits, interior lighting in the project shall meet measure requirements in accordance with Sections 11.5.2.5.2, 11.5.2.5.3, 11.5.2.5.4, 11.5.2.5.5, or 11.5.2.5.6. Credits shall be as shown in Section 11.5.3 or as specified in each subsection. Use of multiple credits from this section shall be allowed. Functional testing of lighting controls shall comply with Section 9.9.

Informative Note: Where lighting efficiency measures include reductions in lighting power, the lighting design should achieve ANSI/IES recommended practice for illuminance levels as referenced at www.ies.org/ standards/lighting-library/the-interactive-illuminance-selector or in relevant IES recommended practice (RP) standards.

11.5.2.5.1 L01: Lighting System Performance Improvement (Reserved) 11.5.2.5.2 L02: Continuous Dimming and High-End Trim. To achieve this credit, general lighting in 75% or more of gross lighted floor area shall have luminaires configured for continuous dimming with the following:

a. High-end trim shall be implemented, and construction documents shall state that maximum light output

or power of controlled lighting shall be initially reduced by at least 15% from full output. The average maximum light output or power of the controlled lighting shall be documented without high-end trim and with high-end trim in accordance with Section 9.9.1 to verify reduction of light output or power by at least 15% when tuned. b. Where lumen maintenance control without lighting sensors is used, controls shall be configured to limit

the initial maximum lumen output or maximum lighting power to 85% or less of full light output or full power draw. c. High-end trim and lumen maintenance controls shall be accessible only to authorized personnel. d. Where this credit is taken, the additional interior lighting power allowance in Section 9.5.2.3 related to

dimming control is not permitted to be used. For hotel and multifamily building use types, the gross lighted floor area is for common areas not including dwelling units or guest rooms. Where general light- ing in less than 75% but at least 50% of the gross lighted floor area receives high-end trim, the base credits from the tables in Section 11.5.3 shall be prorated as follows:

% Tuned area of gross lighted floor area

--------------------------------------------------------------------------------------------------  Base energy credits for L02 75%

11.5.2.5.3 L03: Occupancy Sensor Control Areas. To achieve this credit, either buildings shall use Section 9.3, “Simplified Building Method Compliance Path,” or in all spaces where automatic partial OFF (See Section 9.4.1.1[g]) or automatic full OFF (See Section 9.4.1.1[h]) is not required, it shall be installed as follows:

a. Automatic shutoff or light reduction shall occur within 15 minutes of all occupants leaving each control

zone.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 191

PDF Page 194

Open page note

Table 11.5.2.5.4 Added Daylighting ParametersCol2Col3
Building Use TypeDLA****typDLA****max
Small office ≤5000 ft210%20%
Office >5000 ft221%31%
Single-floor retail ≤3000 ft2 or retail with ≤1000 ft2 roof area0%20%
Retail >3000 ft2 of single-floor area60%80%
School42%52%
Warehouse and semiheated50%70%
Medical, hotel, multifamily, dormitory, and otherNANA

b. For spaces with multiple control zones or automatic partial OFF control, automatic full shutoff shall

occur within 15 minutes of all occupants leaving the space . c. For spaces with one control zone, automatic full OFF control shall be used. d. All areas of the project with automatic partial OFF or automatic full OFF control shall have one control

device for every 600 ft [2] of gross lighted area .

Where this credit is taken, additional interior lighting power allowance in Section 9.5.2.3 related to occupancy sensor control shall not be used.

Exception to 11.5.2.5.3: Exception to automatic full OFF control requirement: stairwells.

11.5.2.5.4 L04: Increased Daylighting Control Area. To achieve this credit, the total daylight area of the project (DLA bldg ) with continuous daylight dimming meeting the requirements of Section 9.4.1.1(e) or 9.4.1.1(f) shall be at least 5% greater than the typical daylit area (DLA typ ). Where the actual daylight area includes additional daylit areas beyond the primary sidelighted areas, secondary sidelighted areas, daylight area under skylights, or daylight area under roof monitor, both of the following shall apply:

a. An analysis based on IES LM83 shall be submitted demonstrating that the spatial daylight autonomy is

at least 200, 60% for the additional actual daylight area . b. Additional daylit areas shall be separately controlled by automatic daylighting controls.

Credits shall be determined based on the following:

EC L04 _ adj = EC L04 _ base  20   DLA-------------------GLFA bldg - - DLA typ 

where EC L04_adj = energy credits achieved for increased daylighting control area EC L04_base = L04 base energy credit from Section 11.5.3 DLA bldg = lesser of actual daylight area of the project with continuous daylight dimming, ft [2], and (GLFA

× DLA max ); see Table 11.5.2.5.4 GLFA = project gross lighted floor area, ft [2]

DLA typ = typical % of building area with daylight control (as a fraction) from Table 11.5.2.5.4 or 0

where nonretail buildings use Section 9.3 Informative Note: In IES LM83, “spatial daylight autonomy” (sDA) means the amount of daylight received in a space over a portion of operating hours each year. It is written as sDA#,YY% where the indicates the desired lux provided by the daylight. YY% indicates the portion of operating hours per year to receive that daylight. It also includes an area requirement or statement. For example, “sDA200,60% for 30% of regularly occupied spaces” means that 30% of regularly occupied spaces receive at least 200 lux for at least 60% of the operating hours each year.

11.5.2.5.5 L05: Lighting Control for Multifamily Buildings

a. Common-area restrooms, laundry rooms, storage rooms, utility rooms, and garages shall have automatic

full OFF control in accordance with Section 9.4.1.1(h). b. Stairwells, lobbies, and corridors shall have automatic partial OFF in accordance with Section 9.4.1.1(g)

controls that shall reduce general lighting power in the space by at least 66% of full lighting power within 15 minutes of all occupants leaving the space .

192 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 195

Open page note

c. Each dwelling unit shall have a main control by the main entrance that turns off all the lights and all

switched receptacles in the dwelling unit . Not less than two switched receptacles shall be provided in living and sleeping rooms or areas and clearly identified. All switched receptacles shall be located within 12 in. of an unswitched receptacle. The main control shall be permitted to have two controls, one for permanently wired lighting and one for switched receptacles. The main controls should be clearly identified as “lights master off” and “switched outlets master off”. Alternatively, where all permanently wired lighting is controlled by occupancy sensors, only the switched outlets are required to be master switched.

Alternatively, stairwells are permitted to be excluded from item (b) and measure credits shall be one less than L05 base credits from Section 11.5.3.

11.5.2.5.6 L06: Reduce Interior Lighting Power. To achieve this credit, the installed interior light- ing power, less any additional lighting allowed from Section 9.5.2.2, shall be 95% or less than the interior lighting power allowance, less any additional lighting allowed in Section 9.5.2.2. In multifamily, dormitory, hotel, and motel buildings, the credit is calculated for common areas other than dwelling units and guest rooms. Energy credits shall not be greater than two times the L06 base credit from Section 11.5.3 and shall be determined as follows:

EC L06 _ adj = EC sim + EC L06 _ base  20  LPA----------------------------------LPA net - net LP net -

where EC L06_adj = energy credits achieved for lighting power reduction EC sim = EC L06_base where buildings use Section 9.3, otherwise EC sim = 0 EC L06_base = L06 base energy credit from Section 11.5.3 LPA net = net interior lighting power allowance calculated in accordance with the method used to meet

the requirements of Section 9.2.2.1, W, excluding any additional interior lighting allowances in Section 9.5.2.2 LP net = net installed interior lighting power calculated in accordance with Sections 9.1.3 and 9.1.4,

W, excluding any additional interior lighting allowances in Section 9.5.2.2 11.5.2.6 R01: On-Site Renewable Energy. To achieve this credit, the total minimum ratings of on-site renewable energy systems in addition to the requirements of Section 10.5.1.1 shall be not less than 0.1 W/ft [2]

of gross floor area . Additional energy credits shall be determined as follows:

= EC R01 _ base  -------------------------------------0.1  PGFA

EC R01 _ adj = EC R01 _ base

RR total - RR req

where EC R01_adj = energy credits achieved for on-site renewable energy EC R01_base = R01 base energy credit from Section 11.5.3 RR total = actual total minimum rating of on-site renewable energy systems, W RR req = minimum rating of on-site renewable energy systems required by Section 10.5.1.1 without

exception, W PGFA = project gross floor area Informative Note: On-site renewable energy may include thermal service water heating or pool water heating in which case ratings in Btu/h can be converted to W, where W = Btu/h/3.413.

11.5.2.7 Equipment Efficiency Measures. Energy credits for equipment efficiency shall be determined in accordance with Sections 11.5.2.7.1, 11.5.2.7.2, and 11.5.2.7.3. Use of multiple credits from this section shall be allowed.

11.5.2.7.1 Q01: Efficient Elevator Equipment. To achieve this credit, qualifying elevators in the project shall be energy efficiency Class A per ISO 25745-2, Table 7. Elevators with regeneration capability shall have the means to absorb the regenerated electricity by other building loads or be able to export the energy to the utility grid. The electrical system shall not absorb regenerated electricity with electric resis- tance load banks. Base credits shall be adjusted based on qualified elevators in the building as follows:

EC Q01 _ adj = EC Q01 _ baseF ---- FAB -

where EC Q01_adj = energy credits achieved for efficient elevator equipment

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 193

PDF Page 196

Open page note

Table 11.5.2.7.2-1 Minimum Efficiency Requirements: Commercial Fryers

Col1Heavy-Load Cooking
Energy Efficiency
Idle Energy RateTest Procedure
Standard open deep-fat gas fryers≥50%≤9000 Btu/hASTM Standard F1361-07
Standard open deep-fat electric fryers≥83%≤800 W≤800 W
Large-vat open deep-fat gas fryers≥50%≤12,000 Btu/hASTM Standard F2144-17
Large-vat open deep-fat electric fryers≥80%≤1100 W≤1100 W

Table 11.5.2.7.2-2 Minimum Efficiency Requirements: Commercial Steam Cookers

Fuel TypePan CapacityCooking Energy
Efficiencya
Idle RateTest Procedure
Electric steam3-pan≥50%≤400 WASTM Standard
F1484-18
Electric steam4-pan≥50%≤530 W≤530 W
Electric steam5-pan≥50%≤670 W≤670 W
Electric steam6-pan and larger≥50%≤800 W≤800 W
Gas steam3-pan≥38%≤6250 Btu/h≤6250 Btu/h
Gas steam4-pan≥38%≤8350 Btu/h≤8350 Btu/h
Gas steam5-pan≥38%≤10,400 Btu/h≤10,400 Btu/h
Gas steam6-pan and larger≥38%≤12,500 Btu/h≤12,500 Btu/h

a. Cooking energy efficiency is based on heavy load (potato) cooking capacity.

EC Q01_base = Q01 base energy credit from Section 11.5.3

FA = sum of floors served by each Class A elevator

FB = sum of floors served by all building elevators and escalators

Informative Note: For example, sum of floors is 10 where Elevator 1 serves five (5) floors, Elevator 2 serves three (3) floors, and an escalator serves two (2) floors: 5 + 3 + 2 = 10.

11.5.2.7.2 Q02: Efficient Kitchen Equipment. To achieve this credit, in projects or facilities that include a commercial kitchen with at least one gas or electric fryer, all fryers, dishwashers, steam cookers, and ovens shall comply with all of the following:

a. Achieve performance levels in accordance with the equipment specifications listed in Tables 11.5.2.7.2-1

through 11.5.2.7.2-4 when rated in accordance with the applicable test procedure. b. Be installed prior to the issuance of the certificate of occupancy. c. Have associated performance levels listed on the construction documents submitted for permitting.

Energy credits for efficient kitchen equipment shall be as stated in Section 11.5.3. Informative Note: Where a commercial kitchen is included in a building where credits for efficient kitchen equipment are excluded, such as a cafeteria in an office building, treat the kitchen and dining area as a restaurant building use type following the weighted-average method in Section 11.5.1(a).

11.5.2.7.3 Q03: Fault Detection and Diagnostics System. To achieve this credit, where not otherwise required in Sections 6 through 10, a fault detection and diagnostics (FDD) system shall be installed to monitor the HVAC system ’s performance and automatically identify faults. This installation is in addition to and more comprehensive than existing requirements in Section 6.4.3.12. The FDD system shall include all of the following:

a. Utilize sensors or devices to directly or indirectly monitor the HVAC system ’s central plant equipment,

zone terminal equipment, and associated mechanical components, including (but not limited to) motors, actuators, valves, and dampers. Control device positions or air and fluid flows shall be permitted to be estimated based on related sensed inputs. b. Sample the sensors and devices at least once per 15 minutes.

194 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 197

Open page note

Table 11.5.2.7.2-3 Minimum Efficiency Requirements: Commercial Dishwashers

Machine TypeHigh-Temp Efficiency RequirementsCol3Low-Temp Efficiency RequirementsCol5Test Procedure
Machine TypeIdle
Energy Rate a
Water
Consumption b
Idle
Energy Rate a
Water
Consumption b
Water
Consumption b
Under counter≤0.50_kW_≤0.86 GPR≤0.50_kW_≤1.19 GPRASTM Standard
F1696-18
ASTM Standard
F1920-15
Stationary single-tank door≤0.70_kW_≤0.89 GPR≤0.60_kW_≤1.18 GPR≤1.18 GPR
Pot, pan, and utensil≤1.20_kW_≤0.58 GPR≤1.00_kW_≤0.58 GPSF≤0.58 GPSF
Single-tank conveyor≤1.50_kW_≤0.70 GPR≤1.50_kW_≤0.79 GPR≤0.79 GPR
Multiple-tank conveyor≤2.25_kW_≤0.54 GPR≤2.00_kW_≤0.54 GPR≤0.54 GPR
Single-tank flight typeReportedGPH ≤ 2.975_x_ + 55.00ReportedGPH ≤ 2.975_x_ + 55.00GPH ≤ 2.975_x_ + 55.00
Multiple-tank flight typeReportedGPH ≤ 4.96_x_ + 17.00ReportedGPH ≤ 4.96_x_ + 17.00GPH ≤ 4.96_x_ + 17.00

a. Idle results should be measured with the door closed and represent the total idle energy consumed by the machine including all tank heater(s) and controls. Internal or external

booster heater energy consumption shall not be part of this measurement unless it cannot be separately monitored. b. GPR = gallons per rack; GPSF = gallons per square foot of rack; GPH = gallons per hour; x = square feet of conveyor belt (i.e., width × length)/min (max conveyor speed).

Table 11.5.2.7.2-4 Minimum Efficiency Requirements: Commercial Ovens

Col1Col2Convection OvensCol4Col5
GasFull size≤12,000 Btu/h≥46ASTM F1496-13
ElectricHalf size≤1.0_kW_≥71≥71
ElectricFull size≤1.60_kW_≤1.60_kW_≤1.60_kW_

Combination Ovens [ a]

GasSteam mode≤200P + 6511 Btu/h≥41ASTM F2861-17
GasConvection mode≤150P + 5425 Btu/h≥56≥56
ElectricSteam mode≤0.133P + 0.6400_kW_≥55≥55
ElectricConvection mode≤0.080P + 0.4989_kW_≥76≥76

Rack Ovens

GasSingle≤25,000 Btu/h≥48ASTM F2093-18
GasDouble≤30,000 Btu/h≥52≥52

a. P = pan capacity, the number of steam table pans the combination oven is able to accommodate as per ASTM F1495-14a.

c. Automatically identify HVAC system faults using algorithmic-based analysis that performs rule-based,

time-series trend-based, statistically based, or model-based diagnostics, including (where applicable) identification of, at a minimum, the following faults that affect energy performance:

  1. Simultaneous heating and cooling above an expected threshold or short-term cycling between heating and cooling

  2. System operation outside of scheduled hours above an expected threshold

  3. Air or fluid flows not modulating when designed to be variable

  4. Significant changes in energy use as a function of ambient or other conditions

d. Automatically provide authorized personnel with prioritized recommendations for fault repair of identi fied faults based on estimated excess energy consumption or cost of non- repair.

e. Be capable of transmitting the prioritized fault repair recommendations to remotely located authorized

personnel.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 195

PDF Page 198

Open page note

The FDD system requirements of items (a) through (e) shall be allowed to be incorporated into a building management system (BMS) or building automation system (BAS). Where credit is also taken for H07, all of the applicable automatic fault detection and diagnostics (AFDD) specified in Guideline 36 shall be included in FDD reporting and all necessary AFDD sensors recommended by Guideline 36 for applicable HVAC sys- tems shall be installed.

Informative Note: FDD is in addition to standard BAS/BMS monitoring and alarming functionality. Faults identified may also include failing or failed system components, poor air or fluid flow, inoperable valves and dampers, sensors and devices out of calibration, undermaintained equipment and filters, failing or failed bearings, or unresponsive actuators and devices.

11.5.2.8 Load Management Systems. Energy credits for load management measures in Sections 11.5.2.8.1 through 11.5.2.8.7 are available in any combination to projects in buildings that have at least one of the following:

a. A serving electric utility that has any of these programs available:

  1. A demand response program
  2. Real-time or next-day pricing
  3. A time-of-use price schedule applicable to the building b. Local building -level electrical demand monitoring and control integrated into the building control system c. Buildings or additions that have ≤25,000 ft [2] of gross floor area with a central group time control sched ule for lighting or HVAC set points

Where credits are taken for measures in Section 11.5.2.8, the following additional requirements shall apply:

a. Where the serving utility has an interface requirement for participation in items (a)(1) through (a)(3)

above, an interface compliant with serving utility requirements shall be installed. b. The building shall have a building automation control system configured with automatic load manage ment controls that are activated by either a utility demand response signal, real-time or next-day peakprice-period notifications, or local building peak electrical demand monitoring. Buildings or additions that have ≤25,000 ft [2] of gross floor area shall be permitted to use a centralized group time control schedule for load management control. c. Load management control sequences shall be implemented so that they are activated in response to either

an automated serving utility signal; local building peak electrical demand monitoring; or, where buildings or additions have ≤25,000 ft [2] of gross floor area, on a schedule where peak-price-period dates and times shall be adjustable without reprogramming.

11.5.2.8.1 G01: Lighting Load Management. To achieve this credit, luminaires shall have dimming capability, and load management controls shall gradually, over a period of not more than 15 minutes, reduce general lighting power with continuous dimming in 75% of the project area by at least 20% during peakprice periods coincident with high building load. It shall be permitted to substitute decorative and displaylighting equivalent power reductions for general lighting reductions. Where less than 75% but at least 50% of the project general lighting is controlled, the base credits from the tables in Section 11.5.3 shall be prorated as follows:

Portion of project with lighting load management, %

------------------------------------------------------------------------------------------------------------------------------  G01 table credits 75%

Exception to 11.5.2.8.1: Warehouse, semiheated, or retail storage areas with load management con trols shall be permitted to switch off at least 25% of lighting power in 75% of the project area without dimming.

11.5.2.8.2 G02: HVAC Load Management. To achieve this credit, load management controls shall be configured to

a. gradually increase cooling set point by at least 3  F or reduce effective cooling capacity to 60% of

installed capacity during the period of coincident high building load and summer peak prices; b. where electric heating is used, gradually reduce heating set point by at least 3  F or reduce effective heat ing capacity to 60% of installed capacity during the period of coincident high building load and winter peak prices; and c. provide excess outdoor air preceding the peak summer price period and reduce outdoor air by at least

30% during the period of coincident high building load and summer peak prices, in accordance with ASHRAE Standard 62.1, Section 6.2.5.2.

196 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 199

Open page note

11.5.2.8.3 G03: Automated Shading Load Management. To achieve this credit, movable exterior shading devices shall be installed to reduce solar gain through south-oriented and west-oriented fenestration by at least 50% with load management controls that operate during peak summer electrical price periods.

Informative Note: This credit can be met by exterior roller, movable blind, or movable shutter shading devices; however, base overhang, screen or shutter, shading will not meet the requirement. Roller shades that reject solar gain but still allow a view are allowed as long as they provide an effective 50% reduction in net solar gain—e.g., have a shading coefficient of less than 0.5 for the shading material itself. Interior shading devices will not meet the requirement.

11.5.2.8.4 G04: Electric Energy Storage. To achieve this credit, electric storage devices such as batteries or flywheel devices shall be charged by load management controls to store electricity during off-peak periods and use stored energy during on-peak periods to reduce building peak period demand . Electric storage devices shall have a capacity between 0.5 Wh/ft [2] and 15 Wh/ft [2] based on project gross floor area . For capacity other than 1.0 Wh/ft [2], credits can be prorated as follows:

Installed electric storage capacity, Wh/ft [2]

---------------------------------------------------------------------------------------------------  G04 table credits 1.0

11.5.2.8.5 G05: HVAC Cooling Energy Storage. To achieve this credit, ice or chilled-water storage equipment shall be installed and load management controls configured to reduce electric cooling peak demand . Storage tank(s) shall be demonstrated through analysis to have less than 2% loss of stored capacity over a 24-hour period for the cooling design day.

Base energy credits in Section 11.5.3 are for storage capacity of 1.0 ton-hours storage per ton of designday cooling load with a 1.15 sizing factor. Prorate energy credits for other installed storage systems sized between 0.5 and 4.0 ton-hours storage per ton of design-day cooling load. Larger storage shall be permitted; however, credits are limited to 4.0 ton-hours storage per ton of design-day cooling load. Energy credits shall be determined as follows:

 1.44  SR + 0.71 

EC G05 _ adj = EC G05 _ base  ---------------------------------------------2.15

where

EC G05_adj = energy credits achieved for HVAC cooling energy storage

EC G05_base = G05 base energy credit for building use type and climate zone based on ton-hours storage per

ton of design-day cooling load

SR = storage ratio in ton-hours storage per ton of design-day cooling load, where 0.5 ≤ SR ≤ 4.0

11.5.2.8.6 G06: Service Hot-Water Thermal Storage. To achieve this credit, where service hot water is heated by electricity, automatic controls activated by utility demand response signal, peak price period time control, or local building demand monitoring shall preheat stored service hot water before the peakprice period and suspend electric water heating during the period of peak prices coincident with peak build- ing load. Storage capacity shall be provided by either of the following:

a. Preheating water above 140  F delivery temperature with at least 1.2 kWh of energy storage per kW of

water heating capacity. Tempering valves shall be provided at the water heater delivery location. This option is not available where heat-pump water heating is used. b. Providing additional heated water tank storage capacity above peak service hot-water demand with

equivalent peak storage capacity to item (a).

11.5.2.8.7 G07: Building Thermal Mass. To achieve this credit, the project shall have both additional passive interior mass and a night flush control of the HVAC system . The credit is only available to projects that have at least 80% of gross floor area unoccupied between midnight and 6:00 a.m.

a. Interior to the building envelope insulation, provide 10 lb/ft [2] of project conditioned floor area of passive

thermal mass in the building interior wall, the inside of the exterior wall, or interior floor construction . Mass construction shall have mass surfaces directly contacting the air in conditioned spaces with directly attached gypsum panels allowed. Mass with carpet or furred gypsum panels, or exterior wall mass that is on the exterior of the insulation layer (e.g., the portion of CMU block on the exterior of insulation filled cell cavities), shall not be included toward the building mass required. b. HVAC units for 80% or more of the supply airflow in the project shall be equipped with outdoor air

economizers and fans that have variable or low speed capable of operating at 66% or lower airflow and be included in the night flush control sequence.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 197

PDF Page 200

Open page note

19

c. Night flush controls shall be configured with the following sequence, or another night flush strategy shall

be permitted where it is demonstrated to be effective, avoids added morning heating, and is approved by the authority having jurisdiction .

  1. Summer mode shall be activated when outdoor air temperature exceeds 70  F and shall continue uninterrupted until deactivated when outdoor air temperature falls below 45  F. During summer mode, the occupied cooling set point shall be set 1  F higher than normal, and the occupied heating set point shall be reset 2  F lower than normal.
  2. Night flush shall be activated when all of the following conditions exist: i. Summer mode is active in accordance with item (c)(1). ii. Outdoor air temperature is 5  F or more below indoor average zone temperature. iii. Indoor average zone temperature is greater than morning occupied heating set point . iv. In climate zones 0A through 3A, outdoor dew point is below 50  F, or outdoor air enthalpy is less than indoor air enthalpy. v. Local time is between 10:00 pm and 6:00 am.
  3. When night flush is active, automatic night flush controls shall operate outdoor air economizers at low fan speed not exceeding 66% during the unoccupied period with mechanical cooling and heating locked out. d. The project shall demonstrate a contractual obligation for postoccupancy commissioning and control tun ing in the spring or fall season to tune the summer mode activation set points and occupied heating set point, or other algorithms to achieve minimal morning heating due to night flush activation, while maintaining comfort conditions. Commissioning shall include monitoring of time-series space temperature, heating, and cooling operation to demonstrate both night cooling and minimization of morning heating along with monitoring of post-tuning operation to verify tuned parameters. Operating manuals shall include recommendations for tuned parameters and narrative training for operating staff on night flush automated settings.

Informative Note: The simplified night flush sequence described will operate in summer mode below the 70  F outdoor air trigger temperature until outdoor air of 45  F is reached and summer mode is deactivated. Summer mode is reestablished when the outdoor air rises above 70  F again. These set points need to be tuned under actual occupancy conditions, as building load characteristics vary. Other strategies may be implemented that cool the space below the heating set point and adjust the morning heating set point to avoid morning reheating.

11.5.3 Base Energy Credits Available. Base energy credits are shown in Tables 11.5.3-1 through 11.5.3-9, where the table is selected for the building use type, and the base credit is selected for the climate zone of the building .

11.6 Alternative Compliance Path (Not used)

11.7 Submittals 11.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

11.7.2 Permit Application Documentation. Construction documents shall list which credits w ere used to meet the requirements of Section 11.5 for this project.

11.7.3 Completion Requirements. Construction documents shall require that equipment, controls, or sys- tems installed to meet the requirements of Section 11.5 shall meet completion requirements as specified in Sections 5.7.3, 6.7.3, 7.7.3, 8.7.3, 9.7.3, and 10.7.3.

11.8 Product Information (Not used)

11.9 Verification, Testing, and Commissioning. Building envelope components, equipment, controls, or systems installed to meet the requirements of Section 11.5 shall meet verification, testing, and commission- ing requirements as specified in Sections 5.9, 6.9, 7.9, 8.9, 9.9, and 10.9.

198 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 201

Open page note

14

Table 11.5.3-1 Energy Credits for Multifamily

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2××××××1××4×25216469
H03Cooling Efficiency11.5.2.2.3191714141196734523423322
H04Residential HVAC Controls11.5.2.2.410118121012891291179117101088
H05Ground-Source Heat Pump11.5.2.2.59857445421056139418131616
H06DOAS/Fan Controls11.5.2.2.6×××××××××××××××××××
H07Guideline 36 Sequences11.5.2.2.73333222212212212222
W01SHW Preheat Recovery11.5.2.3.1(a)10111313151619182321212422222521232323
W02Heat-Pump Water Heater11.5.2.3.1(b)16172020242530293633333936364135373738
W03Efficient Gas Water Heater11.5.2.3.1(c)12131615181923222725252926273026272727
W04SWH Pipe Insulation11.5.2.3.22233333343333333333
W05Point-of-Use Water Heaters11.5.2.3.3(a)×××××××××××××××××××
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.43444557687788898888
W08SHW Distribution Sizing11.5.2.3.510111313161620192422222523232723242424
W09Shower Drain Heat Recovery11.5.2.3.6991111131417162019192220202320212121
P01Energy Monitoring11.5.2.43333222222222222222
L02Lighting Dimming and Tuning11.5.2.5.21111111121111111111
L03Increase Occupancy Sensor11.5.2.5.3×××××××××××××××××××
L04Increase Daylight Area11.5.2.5.4×××××××××××××××××××
L05Residential Light Controls11.5.2.5.599109101091011991079107886
L06Light Power Reduction11.5.2.5.62222222222222222211
R01On-Site Renewable Energy11.5.2.61213151415181619211319141117131214119
Q01Efficient Elevator Equipment11.5.2.7.14455555565565565555
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.33333222212212212222
G01Lighting Load Management11.5.2.8.1×××××××××××××××××××
G02HVAC Load Management11.5.2.8.2×××××××××××××××××××
G03Shading Load Management11.5.2.8.311×718101341312×13681111×6514
G04Electric Energy Storage11.5.2.8.4789810910111413101311101311101112
G05HVAC Cooling Energy Storage11.5.2.8.52252712191819331011209714861513
G06SHW Thermal Storage11.5.2.8.621212121212121212121212121212121212121
G07Building Mass/Night Flush11.5.2.8.7×××××××××××××××××××

× = Credits excluded from this building use type and climate zone.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 199

PDF Page 202

Open page note

Table 11.5.3-2 Energy Credits for Health Care Buildings

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.21111222223234346579
H03Cooling Efficiency11.5.2.2.31816151514109887655535442
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.5314×1414119101211101111101514141615
H06DOAS/Fan Controls11.5.2.2.62019181817161515151315131114109962
H07Guideline 36 Sequences11.5.2.2.74333333323323323333
W01SHW Preheat Recovery11.5.2.3.1(a)1111122222222222222
W02Heat-Pump Water Heater11.5.2.3.1(b)1111111111111111111
W03Efficient Gas Water Heater11.5.2.3.1(c)1111111111111111111
W04SWH Pipe Insulation11.5.2.3.21111111111111111111
W05Point-of-Use Water Heaters11.5.2.3.3(a)×××××××××××××××××××
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.5×××××××××××××××××××
W09Shower Drain Heat Recovery11.5.2.3.6×××××××××××××××××××
P01Energy Monitoring11.5.2.44333333333333333333
L02Lighting Dimming and Tuning11.5.2.5.26666666676776776655
L03Increase Occupancy Sensor11.5.2.5.31111122122122121111
L04Increase Daylight Area11.5.2.5.4×××××××××××××××××××
L05Residential Light Controls11.5.2.5.5×××××××××××××××××××
L06Light Power Reduction11.5.2.5.6788888991089108997876
R01On-Site Renewable Energy11.5.2.65555576775754655543
Q01Efficient Elevator Equipment11.5.2.7.12222222222222222222
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.34333333323323323333
G01Lighting Load Management11.5.2.8.1×××××××××××××××××××
G02HVAC Load Management11.5.2.8.2×××××××××××××××××××
G03Shading Load Management11.5.2.8.31111×××1××2××2××11×
G04Electric Energy Storage11.5.2.8.491010101011101111101112101111101099
G05HVAC Cooling Energy Storage11.5.2.8.592125971014106875754811
G06SHW Thermal Storage11.5.2.8.61111111111111111111
G07Building Mass/Night Flush11.5.2.8.7×××××××××××××××××××

× = credits excluded from this building use type and climate zone.

200 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 203

Open page note

Table 11.5.3-3 Energy Credits for Hotel/Motel

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2××××××××××××21×3135
H03Cooling Efficiency11.5.2.2.3242219191512101077735535442
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.51310710764596448641391415
H06DOAS/Fan Controls11.5.2.2.6×××××××××××××××××××
H07Guideline 36 Sequences11.5.2.2.74433332222222222222
W01SHW Preheat Recovery11.5.2.3.1(a)3444556677788898889
W02Heat-Pump Water Heater11.5.2.3.1(b)55768810101112111313121413131414
W03Efficient Gas Water Heater11.5.2.3.1(c)44556687898101091010101010
W04SWH Pipe Insulation11.5.2.3.21111122222222222222
W05Point-of-Use Water Heaters11.5.2.3.3(a)×××××××××××××××××××
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.53444567678798899999
W09Shower Drain Heat Recovery11.5.2.3.63344456566677787788
P01Energy Monitoring11.5.2.43333333333323323333
L02Lighting Dimming and Tuning11.5.2.5.21122122221222222222
L03Increase Occupancy Sensor11.5.2.5.33444455454454454443
L04Increase Daylight Area11.5.2.5.4×××××××××××××××××××
L05Residential Light Controls11.5.2.5.5×××××××××××××××××××
L06Light Power Reduction11.5.2.5.62222222232332232222
R01On-Site Renewable Energy11.5.2.6789991210131391310812991087
Q01Efficient Elevator Equipment11.5.2.7.12333334444444444443
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.34433332222222222222
G01Lighting Load Management11.5.2.8.1×××××××××××××××××××
G02HVAC Load Management11.5.2.8.2×××××××××××××××××××
G03Shading Load Management11.5.2.8.3222312324321×1312××
G04Electric Energy Storage11.5.2.8.4677879912111191112111411101011
G05HVAC Cooling Energy Storage11.5.2.8.5185251119172233201419121216891923
G06SHW Thermal Storage11.5.2.8.631313131313131313131313131313131313131
G07Building Mass/Night Flush11.5.2.8.7×××××××××××××××××××

× = credits excluded from this building use type and climate zone.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 201

PDF Page 204

Open page note

Table 11.5.3-4 Energy Credits for Office Buildings

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2××××××1××21253275710
H03Cooling Efficiency11.5.2.2.31818151612108876534424231
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.598585475210671510821151920
H06DOAS/Fan Controls11.5.2.2.619191718161611141291385107363×
H07Guideline 36 Sequences11.5.2.2.73333332222212212222
W01SHW Preheat Recovery11.5.2.3.1(a)1122222222222232222
W02Heat-Pump Water Heater11.5.2.3.1(b)1111111122222222222
W03Efficient Gas Water Heater11.5.2.3.1(c)2222222233333333333
W04SWH Pipe Insulation11.5.2.3.21111111111121121111
W05Point-of-Use Water Heaters11.5.2.3.3(a)×44444433323212111×
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.5×××××××××××××××××××
W09Shower Drain Heat Recovery11.5.2.3.6×××××××××××××××××××
P01Energy Monitoring11.5.2.43333333333333333333
L02Lighting Dimming and Tuning11.5.2.5.25566666776776675655
L03Increase Occupancy Sensor11.5.2.5.35666766686676676655
L04Increase Daylight Area11.5.2.5.477888899108898887886
L05Residential Light Controls11.5.2.5.5×××××××××××××××××××
L06Light Power Reduction11.5.2.5.67788898898998897876
R01On-Site Renewable Energy11.5.2.61111141314161518191318141116131214129
Q01Efficient Elevator Equipment11.5.2.7.14444555565565565555
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.33333332222212212222
G01Lighting Load Management11.5.2.8.15566667766776786766
G02HVAC Load Management11.5.2.8.210107138131412814151414171411171511
G03Shading Load Management11.5.2.8.38131515141714151610161613151613151421
G04Electric Energy Storage11.5.2.8.419192121222427262727283126283322272523
G05HVAC Cooling Energy Storage11.5.2.8.5226291321192237221321121216892023
G06SHW Thermal Storage11.5.2.8.67777777777777777777
G07Building Mass/Night Flush11.5.2.8.7416391412142011202019202016262512

× = credits excluded from this building use type and climate zone.

202 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 205

Open page note

Table 11.5.3-5 Energy Credits for Restaurant Buildings

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2×××××13215348551081317
H03Cooling Efficiency11.5.2.2.32018151613108735413313221
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.5119697688413111114151419172017
H06DOAS/Fan Controls11.5.2.2.6×××××××××××××××××××
H07Guideline 36 Sequences11.5.2.2.74333322212212212233
W01SHW Preheat Recovery11.5.2.3.1(a)557678991110111211111211111110
W02Heat-Pump Water Heater11.5.2.3.1(b)23334566787999109101010
W03Efficient Gas Water Heater11.5.2.3.1(c)678891011111413131413131513131312
W04SWH Pipe Insulation11.5.2.3.2×××××××××××××××××××
W05Point-of-Use Water Heaters11.5.2.3.3(a)×××××××××××××××××××
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.5×××××××××××××××××××
W09Shower Drain Heat Recovery11.5.2.3.6×××××××××××××××××××
P01Energy Monitoring11.5.2.43322222212212222222
L02Lighting Dimming and Tuning11.5.2.5.23333333333332322222
L03Increase Occupancy Sensor11.5.2.5.32233333332222222221
L04Increase Daylight Area11.5.2.5.4×××××××××××××××××××
L05Residential Light Controls11.5.2.5.5×××××××××××××××××××
L06Light Power Reduction11.5.2.5.64444444444433433332
R01On-Site Renewable Energy11.5.2.62222232332322222221
Q01Efficient Elevator Equipment11.5.2.7.11111111111111111111
Q02Efficient Kitchen Equipment11.5.2.7.219212422242626273127283026273024262322
Q03Fault Detection and Diagnostics11.5.2.7.34333322212212212233
G01Lighting Load Management11.5.2.8.1×××××××××××××××××××
G02HVAC Load Management11.5.2.8.2×××××××××××××××××××
G03Shading Load Management11.5.2.8.322222322112111×111×
G04Electric Energy Storage11.5.2.8.43344554443433433332
G05HVAC Cooling Energy Storage11.5.2.8.541524346223112×12××
G06SHW Thermal Storage11.5.2.8.619191919191919191919191919191919191919
G07Building Mass/Night Flush11.5.2.8.72×314645113774953641

× = credits excluded from this building use type and climate zone.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 203

PDF Page 206

Open page note

Table 11.5.3-6 Energy Credits for Retail Buildings

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2××××××31×7251066129913
H03Cooling Efficiency11.5.2.2.3262421221815111157724514331
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.5161391387108218111619181923201815
H06DOAS/Fan Controls11.5.2.2.62930262824251823231222157171331052
H07Guideline 36 Sequences11.5.2.2.75544433323323323334
W01SHW Preheat Recovery11.5.2.3.1(a)4454667787787786776
W02Heat-Pump Water Heater11.5.2.3.1(b)1111222232232232222
W03Efficient Gas Water Heater11.5.2.3.1(c)2232334444444443443
W04SWH Pipe Insulation11.5.2.3.2×××××××××××××××××××
W05Point-of-Use Water Heaters11.5.2.3.3(a)×××××××××××××××××××
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.5×××××××××××××××××××
W09Shower Drain Heat Recovery11.5.2.3.6×××××××××××××××××××
P01Energy Monitoring11.5.2.45555666666666666666
L02Lighting Dimming and Tuning11.5.2.5.26666665664553443322
L03Increase Occupancy Sensor11.5.2.5.36666665664553443422
L04Increase Daylight Area11.5.2.5.47787776774654543443
L05Residential Light Controls11.5.2.5.5×××××××××××××××××××
L06Light Power Reduction11.5.2.5.6111112121212111214101198898876
R01On-Site Renewable Energy11.5.2.699111113161418191217131015121012107
Q01Efficient Elevator Equipment11.5.2.7.13344455565555554444
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.35544433323323323334
G01Lighting Load Management11.5.2.8.19810101111111212101212111112111198
G02HVAC Load Management11.5.2.8.214131414121010757136××7461
G03Shading Load Management11.5.2.8.32463642×8×122××××31
G04Electric Energy Storage11.5.2.8.4586791010911108981099786
G05HVAC Cooling Energy Storage11.5.2.8.524635152623284018152391016381622
G06SHW Thermal Storage11.5.2.8.65555555555555555555
G07Building Mass/Night Flush11.5.2.8.741628141114329202016201813232110

× = credits excluded from this building use type and climate zone.

204 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 207

Open page note

Table 11.5.3-7 Energy Credits for Education Buildings

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2××××××11122334254711
H03Cooling Efficiency11.5.2.2.32423192118151212109956736552
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.5131281287685691171361291212
H06DOAS/Fan Controls11.5.2.2.6282725262323192119171913141413111392
H07Guideline 36 Sequences11.5.2.2.75444433323323323333
W01SHW Preheat Recovery11.5.2.3.1(a)1121222233333333333
W02Heat-Pump Water Heater11.5.2.3.1(b)1111111122222233333
W03Efficient Gas Water Heater11.5.2.3.1(c)1122223333344443444
W04SWH Pipe Insulation11.5.2.3.21111111111111111111
W05Point-of-Use Water Heaters11.5.2.3.3(a)1222222232333332322
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.5×××××××××××××××××××
W09Shower Drain Heat Recovery11.5.2.3.61111112222222222222
P01Energy Monitoring11.5.2.44444433333333333333
L02Lighting Dimming and Tuning11.5.2.5.25566676787787776665
L03Increase Occupancy Sensor11.5.2.5.34455666777766675654
L04Increase Daylight Area11.5.2.5.467877889108898897886
L05Residential Light Controls11.5.2.5.5×××××××××××××××××××
L06Light Power Reduction11.5.2.5.677888991011991099108987
R01On-Site Renewable Energy11.5.2.610111312141816202115211613191514161310
Q01Efficient Elevator Equipment11.5.2.7.13444555666666676665
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.35444433323323323333
G01Lighting Load Management11.5.2.8.12333343433442454333
G02HVAC Load Management11.5.2.8.26586686656865834742
G03Shading Load Management11.5.2.8.39131612181716181311171610151412101515
G04Electric Energy Storage11.5.2.8.412121313141616172016181817181815171514
G05HVAC Cooling Energy Storage11.5.2.8.526737173028364038233722202813163234
G06SHW Thermal Storage11.5.2.8.68888888888888888888
G07Building Mass/Night Flush11.5.2.8.7416281411142010202019301916202010

× = credits excluded from this building use type and climate zone.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 205

PDF Page 208

Open page note

Table 11.5.3-8 Energy Credits for Warehouses

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2××××××51×14682113724182324
H03Cooling Efficiency11.5.2.2.313139107634112×11×××××
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.5×××××××××××××××××××
H06DOAS/Fan Controls11.5.2.2.6×××××××××××××××××××
H07Guideline 36 Sequences11.5.2.2.73323222213224324344
W01SHW Preheat Recovery11.5.2.3.1(a)2232333343332332222
W02Heat-Pump Water Heater11.5.2.3.1(b)1111111111111111111
W03Efficient Gas Water Heater11.5.2.3.1(c)1111222221221221111
W04SWH Pipe Insulation11.5.2.3.2×××××××××××××××××××
W05Point-of-Use Water Heaters11.5.2.3.3(a)×××××××××××××××××××
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.5×××××××××××××××××××
W09Shower Drain Heat Recovery11.5.2.3.6×××××××××××××××××××
P01Energy Monitoring11.5.2.45566666665665666666
L02Lighting Dimming and Tuning11.5.2.5.2×××××××××××××××××××
L03Increase Occupancy Sensor11.5.2.5.36676777796775685654
L04Increase Daylight Area11.5.2.5.415141816181817182114171712151711141210
L05Residential Light Controls11.5.2.5.5×××××××××××××××××××
L06Light Power Reduction11.5.2.5.614141716171716181913161711141711141110
R01On-Site Renewable Energy11.5.2.644415449566252677238644528494224332419
Q01Efficient Elevator Equipment11.5.2.7.35455655665564563433
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type
in accordance with Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.33323222213224324344
G01Lighting Load Management11.5.2.8.16787898996896795755
G02HVAC Load Management11.5.2.8.2×××××××××××××××××××
G03Shading Load Management11.5.2.8.3×××××××××××××××××××
G04Electric Energy Storage11.5.2.8.433344035413940434934404229344222282324
G05HVAC Cooling Energy Storage11.5.2.8.540154032404032401712264512137××
G06SHW Thermal Storage11.5.2.8.64444444444444444444
G07Building Mass/Night Flush11.5.2.8.74163915121420920201420191020156

× = credits excluded from this building use type and climate zone.

206 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 209

Open page note

Table 11.5.3-9 Energy Credits for Other Buildings

IDEnergy Credit
Abbreviated Title
SectionClimate ZoneCol5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
IDEnergy Credit
Abbreviated Title
Section**0A ****0B ****1A ****1B ****2A ****2B ****3A ****3B ****3C ****4A ****4B ****4C ****5A ****5B ****5C ****6A **6B78
E01Improved Envelope Performance11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1Determined in accordance with Section 11.5.2.1
H02Heating Efficiency11.5.2.2.2××××××2××53475497912
H03Cooling Efficiency11.5.2.2.32017141512107755533424332
H04Residential HVAC Controls11.5.2.2.4×××××××××××××××××××
H05Ground-Source Heat Pump11.5.2.2.51111710867751181013121018151717
H06DOAS/Fan Controls11.5.2.2.6×××××××××××××××××××
H07Guideline 36 Sequences11.5.2.2.74433332223223323333
W01SHW Preheat Recovery11.5.2.3.1(a)3454566687787787777
W02Heat-Pump Water Heater11.5.2.3.1(b)4444567688798898999
W03Efficient Gas Water Heater11.5.2.3.1(c)4455567787788898888
W04SWH Pipe Insulation11.5.2.3.21111122222222222222
W05Point-of-Use Water Heaters11.5.2.3.3(a)1333333333333232222
W06Thermostatic Balancing Valves11.5.2.3.3(b)1111111111111111111
W07SHW Submeters11.5.2.3.4×××××××××××××××××××
W08SHW Distribution Sizing11.5.2.3.5×××××××××××××××××××
W09Shower Drain Heat Recovery11.5.2.3.6445567889991010101110101010
P01Energy Monitoring11.5.2.44444444433433434444
L02Lighting Dimming and Tuning11.5.2.5.24444444554554444433
L03Increase Occupancy Sensor11.5.2.5.34454555564554454433
L04Increase Daylight Area11.5.2.5.499111010101011129101089107986
L05Residential Light Controls11.5.2.5.599109101091011991079107886
L06Light Power Reduction11.5.2.5.66666676786776665654
R01On-Site Renewable Energy11.5.2.61313151416191621221320151117141113118
Q01Efficient Elevator Equipment11.5.2.7.13344444454454454444
Q02Efficient Kitchen Equipment11.5.2.7.2Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Commercial kitchens and dining areas are a restaurant_building_ use type in accordance with
Section 11.5.1(a).
Q03Fault Detection and Diagnostics11.5.2.7.34433332223223323333
G01Lighting Load Management11.5.2.8.16677787886886797766
G02HVAC Load Management11.5.2.8.21091011910108698881397985
G03Shading Load Management11.5.2.8.3567899799687781176713
G04Electric Energy Storage11.5.2.8.412131413151516171816161715161813141313
G05HVAC Cooling Energy Storage11.5.2.8.521626132119223017122010914771523
G06SHW Thermal Storage11.5.2.8.612121212121212121212121212121212121212
G07Building Mass/Night Flush11.5.2.8.74152813101220819201425161220188

× = credits excluded from this building use type and climate zone.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 207

PDF Page 210

Open page note

12. ENERGY COST BUDGET METHOD

12.1 General

12.1.1 Energy Cost Budget Method Scope. The building Energy Cost Budget Method is an alternative to the prescriptive provisions of this standard. It may be employed for evaluating the compliance of all pro- posed designs except designs with no mechanical system .

12.1.2 Trade-Offs Limited to Building Permit. When the building permit being sought applies to less than the whole building, only the calculation parameters related to the systems to which the permit applies shall be allowed to vary. Parameters relating to unmodified existing conditions or to future building components shall be identical for both the energy cost budget and the design energy cost calculations. Future build- ing components shall meet the prescriptive requirements of Sections 5.5, 6.5, 7.5, and 9.5.

b. The design energy cost shall comply with the following:

Design Energy CostEnergy Cost Budget   1 - EC------------1000 req -Aadj 

where

EC req = energy credits required for the building in accordance with Section 11.5.1

Aadj = where the project includes additions or alterations use an adjustment factor as follows; otherwise use 1.0:

DESIGN SUBMITTED FIRST FOR APPROVAL FROM AHJ… THEN SUBMIT ENERGY COST BUDGET METHOD RESULTS TO AHJ.

Aadj

Addition Gross Floor Area + Alteration Gross Floor Area = ------------------------------------------------------------------------------------------------------------------------------------------Modeled gross floor area

208 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 211

Open page note

Design energy cost = as calculated in Section 12.5 Energy cost budget = as calculated in Section 12.5 c. The energy efficiency level of installed components and systems that meets or exceeds the efficiency lev els used to calculate the design energy cost . d. For new buildings, one of the following is met:

  1. The building envelope complies with Section 5.5, “Prescriptive Building Envelope Compliance Path.”
  2. Using Section 5.6, “Building Envelope Trade-Off Compliance Option,” the proposed envelope per- formance factor shall not exceed the base envelope performance factor by more than 15% in multifamily residential, hotel/motel, and dormitory building area types. For all other building area types, the limit shall be 7%. For buildings with both residential and nonresidential occupancies, the limit shall be based on the area-weighted average of the gross conditioned floor area . e. Verification, testing, and commissioning requirements of Section 4.2.5 shall be met. f. Proposed building systems, controls , or building envelope documented in Table 12.7.2(d) that do not have criteria in Sections 5 through 10 shall have verification or testing to document proper installation and operation in accordance with Section 4.2.5. Informative Note: The energy cost budget and the design energy cost calculations are applicable only for determining compliance with this standard. They are not predictions of actual energy consumption or costs of the proposed design after construction . Actual experience will differ from these calculations due to variations such as occupancy, building operation and maintenance, weather, energy use not covered by this standard, changes in energy rates between design of the building and occupancy, and precision of the calculation tool.

12.3 Simplified Option (Not Used)

12.4 Simulation General Requirements 12.4.1 Simulation Program. The simulation program shall be a computer-based program for the analysis of energy consumption in buildings . For components that cannot be modeled by the simulation program, the exceptional calculation methods requirements in Section 12.4.5 shall be used.

Exception to 12.4.1: When approved by the adopting authority, a separate computer-based program shall

be permitted to be used to calculate on-site renewable energy .

Informative Note: ASHRAE Standing Standard Project Committee 90.1 recommends that the simula- tion program implement the rules of Section 12 that control simulation inputs and outputs be adopted for the purposes of easier use and simpler compliance.

12.4.1.1 The simulation program shall be approved by the adopting authority and shall, at a minimum, have the ability to explicitly model all of the following:

a. 8760 hours per year b. Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat set points,

humidity set points, and HVAC system operation, defined separately for each day of the week and holidays c. Thermal mass effects d. Ten or more thermal zones e. Part-load performance curves for mechanical equipment f. Capacity and efficiency correction curves for mechanical heating and mechanical cooling equipment g. Air-side economizer and fluid economizer with integrated control h. The budget building design characteristics unless otherwise specified in Section 12.5

12.4.1.2 The simulation program shall have the ability to either

a. directly determine the design energy cost and energy cost budget or b. produce hourly reports of energy use by energy source suitable for determining the design energy cost

and energy cost budget using a separate calculation.

12.4.1.3 The simulation program shall be capable of performing design load calculations to determine required HVAC equipment capacities and air and water flow rates in accordance with Section 6.4.2 for both the proposed design and the budget building design .

12.4.1.4 Simulation Program Testing Requirements 12.4.1.4.1 The simulation program shall be tested according to ASHRAE Standard 140, except for Sections 7 and 8 of Standard 140. The required tests shall include building thermal envelope and fabric load tests (Sections 5.2.1, 5.2.2, and 5.2.3), ground coupled slab-on- grade analytical verification tests (Section 5.2.4),

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 209

PDF Page 212

Open page note

space -cooling equipment performance tests (Section 5.3), space -heating equipment performance tests (Section 5.4), and air-side HVAC equipment analytical verification tests (Section 5.5), along with the associated reporting (Section 6).

12.4.1.4.2 The test results and modeler reports shall be posted on a publicly available website and shall include the test results of the simulation program and input files used for generating results along with the results of the other simulation programs included in ASHRAE Standard 140, Annexes B8 and B16. The modeler report in Standard 140, Annex A2, Attachment A2.7, shall be completed for results exceeding the maximum or falling below the minimum of the reference values and for omitted results.

12.4.1.4.3 The testing shall be performed for the version of the simulation program used to calculate the design energy cost and energy cost budget .

Informative Notes:

  1. There are no pass/fail criteria established by this requirement.
  2. Based on the Section 3.2 definition, simulation program includes the simulation engine and the corresponding user interface. The testing of a simulation program only meets the requirements of Section 12.4.1.4 for that simulation program and cannot be used as proxy for documenting compliance of another simulation program that uses the same simulation engine .

12.4.2 Climatic Data. The simulation program shall perform the simulation using hourly values of climatic data, including temperature, humidity, solar radiation, and wind speed and direction from representative climatic data, for the site in which the proposed design is to be located. For locations for which several climatic data sources are available or where weather data are not available, the designer shall select available weather data that best represent the climate at the construction site . The selected weather data shall be approved by the authority having jurisdiction .

12.4.3 Renewable, Recovered, and Purchased Energy

12.4.3.1 On-Site Renewable Energy and Site-Recovered Energy. Site-recovered energy shall not be considered purchased energy and shall be subtracted from the proposed design energy consumption prior to calculating the design energy cost . On-site renewable energy shall be subtracted from the proposed design energy consumption prior to calculating the design energy cost, provided that the building owner

a. owns the on-site renewable energy system, b. has signed a lease agreement for the on-site renewable energy system for at least 15 years, or c. has signed a contractual agreement to purchase energy generated by the on-site renewable energy system

for at least 15 years.

The reduction in design energy cost associated with on-site renewable energy that exceeds the on-site renewable energy required by Section 10.5.1.1 shall be no more than 5% of the calculated energy cost budget .

On-site renewable energy included in the budget building design shall be subtracted from the budget building design energy consumption prior to calculating the energy cost budget.

12.4.3.2 Annual Energy Costs. The design energy cost and energy cost budget shall be determined using rates for purchased energy (such as electricity, gas, oil, propane, steam, and chilled water) that are approved by the adopting authority . Where on-site renewable energy or site-recovered energy is in excess of what is required in the budget building design by Table 12.5.1, the budget building design shall be based on the energy source used as the backup energy source, or electricity if no backup energy source has been specified. Where the proposed design includes on-site electricity generation systems other than on-site renew- able energy systems, the baseline design shall include the same generation systems excluding its site- recovered energy .

12.4.4 Compliance Calculations. The design energy cost and energy cost budget shall be calculated using

a. the same simulation program, b. the same weather data, and c. the same purchased energy rates .

12.4.5 Exceptional Calculation Methods. When the simulation program does not model a design, material, or device, an exceptional calculation method shall be used as approved by the authority having jurisdic- tion to demonstrate compliance with Section 12.

Where there are multiple designs, materials, or devices that the simulation program does not model, each shall be calculated separately and exceptional savings determined for each. All applications for approval of an exceptional method shall include the following:

210 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 213

Open page note

a. Theoretical and empirical information verifying the method’s accuracy, and step-by-step documentation

of the exceptional calculation method performed, detailed enough to reproduce the results. b. Copies of all spreadsheets used to perform the calculations. c. A sensitivity analysis of energy consumption when each of the input parameters that are estimated is var ied from half to double the value assumed. d. The calculations shall be performed on a time-step basis consistent with the simulation program used. e. The energy cost budget and design energy cost calculated with and without the exceptional calculation

methods.

12.5 Calculation of Design Energy Cost and Energy Cost Budget 12.5.1 The simulation model for calculating the design energy cost and the energy cost budget shall be developed in accordance with the requirements in Table 12.5.1.

Exception to 12.5.1: Energy used to recharge or refuel vehicles that are used for off- site transportation

purposes shall not be modeled for the design energy cost or the energy cost budget .

12.5.2 HVAC Systems. The HVAC system type and related performance parameters for the budget build- ing design shall be determined from Figure 12.5.2, the system descriptions in Table 12.5.2-1 and accompanying notes, and the following rules:

a. Budget Building Systems Not Listed. Components and parameters not listed in Figure 12.5.2 and Table

12.5.2-1 or otherwise specifically addressed in this subsection shall be identical to those in the proposed design . Exception to 12.5.2(a): Where there are specific requirements in Sections 6.4 and 6.5, the component

efficiency in the budget building design shall be adjusted to the lowest efficiency level allowed by the requirement for that component type. b. Minimum Equipment Efficiency. All HVAC and service water-heating equipment in the budget build-

ing design shall be modeled at the minimum efficiency levels, both part load and full load, in accordance with Sections 6.4, 6.5.4.8, 7.4, and 7.5 based on the budget system type determined following Section 12.5.2(j) and capacity determined following Section 12.5.2(i). Chillers shall use Path A efficiencies as shown in Table 6.8.1-3 and be modeled using the performance curves specified in Table J-1 and included in Normative Appendix J. When using performance curves from Normative Appendix J, chiller minimum part-load ratio (ratio of load to available capacity at a given simulation time step) and minimum compressor unloading ratio (part-load ratio below which the chiller capacity cannot be reduced by unloading and chiller is false loaded) shall be equal to 0.25. Simulation programs that do not use performance curves are permitted to use an alternative simulation method that results in the same performance as the curves described in Normative Appendix J. c. Supply Fan Energy in Certain Package Equipment. Where efficiency ratings include supply fan

energy, the efficiency rating shall be adjusted to remove the supply fan energy . For budget system Types 3, 4, 6, 8, 9, 10, and 11, calculate the minimum COPnfcooling and COPnfheating using the equation for the applicable performance rating as indicated in Tables 6.8.1-1, 6.8.1-2, 6.8.1-4, and 6.8.1-15. Where a fulland part-load efficiency rating is provided in Tables 6.8.1-1, 6.8.1-2, 6.8.1-4, and 6.8.1-15, the full-load equation below shall be used:

COPnfcooling = 7.84E-8 × EER × Q + 0.338 × EER

COPnfcooling = –0.0076 × SEER [2] + 0.3796 × SEER

(applies to cooling efficiency only) COPnfheating = 1.48E-7 × COP47 × Q + 1.062 × COP47

(applies to Systems 6 and 9 heating efficiency only)

COPnfheating = –0.0296 × HSPF [2] + 0.7134 × HSPF

COPnfcooling = 0.3322 × EER - 0.2145 (applies to Systems 8 and 10 cooling efficiency only)

COPnfheating = 1.1329 × COP - 0.214 (applies to System 8 heating efficiency only)

where COPnfcooling and COPnfheating are the packaged HVAC equipment cooling and heating energy effi- ciency, respectively, to be used in the budget building design, which excludes supply fan power, and Q is the AHRI-rated cooling capacity in Btu/h. If Q is greater than 760,000 Btu/h, use 760,000 Btu/h in the calculation.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 211

PDF Page 214

Open page note

EER, SEER, COP, and HSPF shall be at AHRI test conditions. Fan energy shall be modeled separately according to Section 12.5.2(h). Supply and return/relief system fans shall be modeled as operating at least whenever the spaces served are occupied, except as specifically noted in Table 12.5.2-1. d. Minimum Outdoor Air Ventilation Rate. Minimum outdoor air ventilation rates shall be the same for

both the budget building design and proposed design . Exhaust air energy recovery shall be modeled for the budget building design in accordance with Section 6.5.6.1. Exceptions to 12.5.2(d):

  1. When modeling demand control ventilation in the proposed design for spaces where demand con- trol ventilation is not required per Section 6.4.3.8.
  2. Where the minimum outdoor air intake flow in the proposed design is provided in excess of the amount required by Section 6.5.3.8, the baseline building design shall be modeled to reflect the minimum amount required by Section 6.5.3.8. e. Economizers. All budget building systems as listed in Table 12.5.2-1 shall have air economizers in

accordance with Section 6.5.1 and Section 12.5.2(i). The high-limit shutoff shall be in accordance with Table 12.5.2-4. f. Preheat Coils. If the proposed design system has a preheat coil, the budget building design ’s system shall be modeled with a preheat coil controlled in the same manner. g. Supply Airflow Rates. System design supply air rates for the budget building design shall be based on a

supply-air-to-room temperature set-point difference of 20°F or the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is greater. For systems with multiple zone thermostat set points, use the design set point that will result in the lowest supply air cooling set point or highest supply air heating set point . If return or relief fans are specified in the proposed design, the budget building design shall also be modeled with fans serving the same functions and sized for the budget system supply fan air quantity less the minimum outdoor air, or 90% of the supply fan air quantity, whichever is larger. Exceptions to 12.5.2(g):

  1. For systems serving laboratory spaces, airflow rate shall be based on a supply-air-to-room temperature set-point difference of 17°F or the required ventilation air or makeup air, whichever is greater.
  2. If the proposed design HVAC system airflow rate based on latent loads is greater than the design airflow rate based on sensible loads, then the same supply-air-to-room-air humidity ratio difference (lb) used to calculate the proposed design airflow shall be used to calculate design airflow rates for the budget building design . h. Fan System Efficiency. Fan system efficiency (bhp per cfm of supply air, including the effect of belt

losses but excluding motor and motor drive losses) shall be the same as the proposed design or up to the limit prescribed in Section 6.5.3.1, whichever is smaller. If this limit is reached, each fan shall be proportionally reduced in brake horsepower until the limit is met. Fan electrical power shall then be determined by adjusting the calculated fan hp by the minimum motor efficiency prescribed by Section 10.4.1 for the appropriate motor size for each fan. Exception to 12.5.2(h): When a proposed design includes energy recovery but it is not required in the

budget building design per Section 12.5.2(d), the fan power of those baseline systems shall be equal to either the proposed design system or the fan power limit in Section 6.5.3.1 calculated without fan power credit for energy recovery, whichever is less. i. Equipment Capacities. The equipment capacities for the budget building design shall be sized proportionally to the capacities in the proposed design based on sizing runs, i.e., the ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and budget building design . Where multiple HVAC zones are combined into a single thermal block or modeled as identical thermal blocks to which multipliers are applied in accordance with Table 12.5.1, the equipment capacities for the budget building design shall be determined as follows:

  1. For budget system Types 8 and 10, equipment capacity shall be 9000 Btu/h.
  2. For budget system Types 5, 6, 7, 9, and 11, equipment capacity shall be based on the load of the ther- mal block divided by the number of combined HVAC zones .
  3. For budget system Types 1, 2, 3, and 4, equipment capacity shall be based on the total load of all associated thermal blocks, including multipliers, divided by the total number of corresponding HVAC systems specified in the design documents.

Unmet load hours for the proposed design or baseline building designs shall not exceed 300 hours (of the 8760 hours simulated). The unmet load hours for the proposed design shall not exceed the unmet

212 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 215

Open page note

load hours for the budget building design . Alternatively, unmet load hours exceeding these limits may be approved by the building official, provided that sufficient justification is given indicating that the accuracy of the simulation is not significantly compromised by these unmet loads. j. Determining the HVAC System. Each HVAC system in a proposed design is mapped on a one-to-one correspondence with one of eleven HVAC systems in the budget building design . To determine the budget building system, do the following:

  1. Enter Figure 12.5.2 at “Water/Ground” if the proposed design system condenser is water or evaporatively cooled; enter Figure 12.5.2 at “Air/None” if the condenser is air cooled. Closed-circuit dry coolers shall be considered air cooled. Systems utilizing district cooling shall be treated as if the condenser water type were “Water.” If no mechanical cooling is specified or the mechanical cooling sys- tem in the proposed design does not require heat rejection, the system shall be treated as if the condenser water type were “Air.” For proposed designs with ground-source or groundwater-source heat pumps, the budget system shall be water-source heat pump ( System 6).
  2. Select the path that corresponds to the proposed design heat source: electric resistance, heat pump (including air source and water source), or fuel -fired. Systems utilizing district heating (steam or hot water) shall be treated as if the heating system type were “Fossil Fuel.” Systems with no heating capability shall be treated as if the heating system type were “Fossil Fuel.” For systems with mixed fuel heating sources, the system or systems that use the secondary heating source type (the one with the smallest total installed output capacity for the spaces served by the system ) shall be modeled identically in the budget building design, and the primary heating source type shall be used in Figure 12.5.2 to determine budget system type.
  3. Select the budget building design system category. The system under “Single-Zone Residential System” shall be selected if the HVAC system in the proposed design is a single-zone system and serves a residential space . The system under “Single-Zone Nonresidential System” shall be selected if the HVAC system in the proposed design is a single-zone system and serves other than residential spaces . The system under “All Other” shall be selected for all other cases. k. Kitchen Exhaust. For kitchens with a total exhaust hood airflow rate greater than 5000 cfm, use a

demand ventilation system on 75% of the exhaust air. The system shall reduce exhaust and replacement air system airflow rates by 50% for one half of the kitchen occupied hours in the baseline building design . If the proposed design uses demand ventilation, the same airflow rate schedule shall be used. The maximum exhaust flow rate allowed for the hood or hood section shall meet the requirements of Section 6.5.7.2.2 for the numbers and types of hoods and appliances provided in the proposed design .

12.5.3 Modeling Building Envelope Air Leakage. The air leakage rate of the building envelope ( I75Pa ) at a pressure differential of 75 Pa (0.30 in. of water) shall be converted to appropriate units for the simulation program using one of the following formulas:

a. For methods describing air leakage as a function of floor area,

IFLR = 0.112 × I75Pa × S/AFLR b. For methods describing air leakage as a function of the area of above-grade walls that separate condi-

tioned spaces and semiheated spaces from the exterior,

IAGW = 0.112 × I75Pa × S/AAGW c. When using the measured air leakage rate of the building envelope at a pressure differential of 75 Pa

(0.30 in. of water) for the proposed design, the air leakage rate shall be calculated as follows:

I75Pa = Q/S

where I75Pa = air leakage rate of the building envelope in cfm/ft [2] at a fixed building pressure differential of 75 Pa (0.30 in. of water) Q = volume of air in cfm flowing through the building envelope when subjected to a pressure differential of 75 Pa (0.30 in. of water), in accordance with ASTM E779, ASTM E1827, or ASTM E3158 S = total area of the building envelope in ft [2], including the lowest floor, any below-grade walls or above-grade walls, and roof (including vertical fenestration and skylights ) IFLR = adjusted air leakage rate of the building envelope cfm/ft [2] at a reference wind speed of 10 mph and relative to the gross floor area AFLR = gross floor area, ft [2]

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 213

PDF Page 216

Open page note

IAGW = adjusted air leakage rate of the building envelope cfm/ft [2] at a reference wind speed of 10 mph and relative to the area of the above-grade walls of the building envelope AAGW = total area of above-grade walls of the building envelope, ft [2]

Exception to 12.5.3: A multizone airflow model alternative method to modeling building envelope air

leakage may be used, provided the following criteria are met:

  1. Where the calculations are made independently of the energy simulation program, the proposed method must comply with Section 12.4.5.
  2. The method for converting the air leakage rate of the building envelope at 75 Pa (0.30 in. of water) to the appropriate units for the simulation program is fully documented and submitted to the rating authority for approval.

12.6 Alternative Compliance Path (Not Used)

12.7 Submittals 12.7.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

12.7.2 Permit Application Documentation. Compliance shall be documented and submitted to the building official . The information submitted shall include the following:

a. The energy cost budget for the budget building design and the design energy cost for the proposed design . b. The simulation program used and the version of the simulation program . c. An overview of the project that includes the number of stories (above and below grade ), the typical floor

size, the uses in the building (e.g., office, cafeteria, retail, parking, etc.), the gross area of each use, and whether each use is conditioned . d. A list of the energy -related features that are included in the design and on which compliance with the

provisions of Section 12 is based. This list shall document all energy features that differ between the models used in the energy cost budget and the design energy cost calculations. e. A list showing compliance for the proposed design with all the requirements of Sections 5.4, 6.4, 7.4,

8.4, 9.4, and 10.4 (mandatory provisions). f. Building elevations and floor plans. g. A diagram showing the thermal blocks used in the computer simulation. h. An explanation of any significant modeling assumptions. i. Backup calculations and material to support data inputs (e.g., U-factors for building envelope assemblies, NFRC ratings for fenestration, end uses identified in Table 12.5.1(1)(a). j. Reports from the simulation program showing

  1. a breakdown of energy usage by at least the following components: lights, internal equipment loads, service water-heating equipment, space -heating equipment, space cooling and heat-rejection equip- ment, fans, and other HVAC equipment (such as pumps );
  2. the amount of time any loads are not met by the HVAC system for both the proposed design and bud- get building design ; and
  3. a description of energy -related features of the budget building design and the proposed design to support requirements of Section 12.7.2(d). k. Purchased energy rates used in the simulations. l. An explanation of any error messages noted in the simulation program output. m. For any exceptional calculation methods employed, document the predicted energy savings by energy

type, the energy cost savings, a narrative explaining the exceptional calculation method performed, and theoretical or empirical information supporting the accuracy of the method. n. The reduction in design energy cost associated with on-site renewable energy . o. The version of the software and the link to the website that contains the ASHRAE Standard 140 results

for the version used in accordance with Section 12.4.1.4. p. Simulation input files for the budget building design and the proposed design shall be made available if

requested by the building official.

12.7.3 Completion Requirements. Completion requirements shall be in compliance with Sections 5.7.3, 6.7.3, 7.7.3, 8.7.3, 9.7.3, and 10.7.3.

12.8 Product Information (Not Used)

214 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 217

Open page note

Table 12.5.1 Modeling Requirements for Calculating Design Energy Cost and Energy Cost Budget

1. Design Model

2. Additions and Alterations

3. Space Use Classification

4. Schedules

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 215

PDF Page 218

Open page note

Table 12.5.1 Modeling Requirements for Calculating Design Energy Cost and Energy Cost Budget (Continued)

4. Schedules (continued)

5. Building Envelope

216 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 219

Open page note

Table 12.5.1 Modeling Requirements for Calculating Design Energy Cost and Energy Cost Budget (Continued)

5. Building Envelope (continued)

6. Lighting

7. Thermal Blocks—HVAC Zones Designed

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 217

PDF Page 220

Open page note

Table 12.5.1 Modeling Requirements for Calculating Design Energy Cost and Energy Cost Budget (Continued)

8. Thermal Blocks—HVAC Zones not Designed

9. Thermal Blocks—Multifamily Residential Buildings

10. HVAC Systems

218 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 221

Open page note

Table 12.5.1 Modeling Requirements for Calculating Design Energy Cost and Energy Cost Budget (Continued)

11. Service Water-Heating Systems

12. Miscellaneous Loads

13. Refrigeration

14. Modeling Exceptions

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 219

PDF Page 222

Open page note

Table 12.5.1 Modeling Requirements for Calculating Design Energy Cost and Energy Cost Budget (Continued)

14. Modeling Exceptions (continued)Col2
**Exception:**Components and_systems_ in the_proposed design_ may be
excluded from the simulation model provided that
1.
component_energy_ use does not affect the_energy_ use of_systems_
and components that are being considered for trade-off and
2.
the applicable prescriptive requirements of Sections 5.5, 6.5, 7.5,
and 9.5 applying to the excluded components are met.
15. On-Site Renewable Energy
On-site renewable energy_in the_proposed design shall be determined as
follows:
a.
Where a complete_system_ providing_on-site renewable energy_ exists, the
model shall reflect the actual_ system_ type using actual component capaci-
ties and efficiencies.
b.
Where a_system_ providing_on-site renewable energy_has been designed,
the_system_ model shall be consistent with design documents.
c.
Where no_system_ exists or is specified to provide_on-site renewable_
energy, no_system_ shall be modeled.
On-site renewable energy_shall be included in the_budget building
design when required by Section 10.5.1, and shall be determined as
follows:
a.
Where a_system_ providing_on-site renewable energy_ has been
modeled in the_proposed design_, the same_system_ shall be
modeled identically in the_budget building design_, except the
rated capacity shall meet the requirements of Section 10.5.1.1.
Where more than one type of_on-site renewable_ energy system
is modeled, the total capacities shall be allocated in the same
proportion as in the_proposed design_.
b.
Where no_system_ exists or is specified to provide_on-site_
renewable energy in the_proposed design_, on-site renewable
energy shall be modeled as an unshaded photovoltaic system
with the following physical characteristics:

Size: Rated capacity per Section 10.5.1.1

Module Type: Crystalline silicon panel with a glass cover,
19.1% nominal efficiency and temperature coefficient of
–0.19%/°F; performance shall be based on a reference tem-
perature of 77°F and irradiance of 317 Btu/ft2·h.

Array Type: Rack-mounted array with installed nominal
operating cell temperature (INOCT) of 103°F

Total system losses (DC output to AC output): 11.3%

Tilt: 0-degrees (mounted horizontally)

Azimuth:180 degrees
If the_on-site renewable energy system_ cannot be modeled in the
simulation program, Section 12.4.5 shall be used.

220 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 223

Open page note

Figure 12.5.2 HVAC systems map.

Table 12.5.2-1Budget System DescriptionsCol3Col4Col5
System No.System TypeFan ControlCooling TypeHeating Type
1VAV with parallel fan-powered boxesaVAV dChilled watereElectric resistance
2VAV with reheatbVAV dChilled watereHot-water_fossil fuel_ boilerf
3Packaged_VAV_ with parallel fan-powered boxesaVAV dDirect expansioncElectric resistance
4Packaged_VAV_ with reheatbVAV dDirect expansioncHot-water_fossil fuel_ boilerf
5Two-pipe fan coilSingle- or two-speed fani,jChilled watereElectric resistance
6Water-source heat pumpSingle- or two-speed fani,jDirect expansioncElectric heat pump and boilerg
7Four-pipe fan-coilSingle- or two-speed fani,jChilled watereHot-water_fossil fuel_ boilerf
8Packaged terminal heat pumpSingle-speed faniDirect expansioncElectric heat pumph
9Packaged rooftop heat pumpSingle- or two-speed fani,jDirect expansioncElectric heat pumph
10Packaged terminal air conditionerSingle-speed faniDirect expansionHot-water_fossil fuel_ boilerf
11Packaged rooftop air conditionerSingle- or two-speed fani,jDirect expansionFossil fuel furnace
a. VAV with Parallel Fan-Powered Boxes: Fans in parallel_VAV_ fan-powered boxes shall be sized for 50% of the peak design flow rate and shall be modeled with 0.35 W/cfm fan power. Minimum
volume_set points_ for fan-powered boxes shall be equal to the minimum rate for the_space_ required for_ventilation_ consistent with Section 6.5.2.1, Exception 1(b). Supply air temperature_set point_
shall be constant at the_design condition_ (see Section 12.5.2[g]).
b. VAV with Reheat: Minimum volume_set points_ for_VAV_ reheat boxes shall be the larger of the following: (1) the minimum primary outdoor airflow rate required to meet the Simplified Procedure
ventilation requirements of ASHRAE Standard 62.1 for the zone or (2) the airflow rate required to comply with applicable codes or accreditation standards, including, but not limited to, pressure
relationships or minimum air change rates. The supply air temperature for cooling shall be_reset_ higher by 5°F under the minimum cooling load conditions.
c. Direct Expansion: The_fuel_ type for the cooling_system_ shall match that of the cooling_system_ in the_proposed design_.
d. VAV: The supply, return, or relief fan motor shall be modeled assuming a variable-speed drive and shall meet the_VAV_ fan part-load performance requirements of Section G3.2.3.15. If the_proposed_
design’s_system_ has a_DDC_ system at the zone level, static pressure_set-point_ reset based on zone requirements in accordance with Section 6.5.3.2.3 shall be modeled.
e. Chilled Water: For_systems_ using purchased chilled water, the chillers are not explicitly modeled, and chilled-water costs shall be based as determined in Section 12.4.3. Otherwise, the_budget_
building design’s chiller plant shall be modeled with chillers having the number as indicated in Table 12.5.2-2 as a function of_budget building design_ chiller plant load and type as indicated in
Table 12.5.2-3 as a function of individual chiller load. Where chiller_fuel_ source is mixed, the_system_ in the_budget building design_ shall have chillers with the same_fuel_ types and with capacities
having the same proportional capacity as the_proposed design_’s chillers for each_fuel_ type. Chilled-water supply temperature shall be modeled at 44°F design supply temperature and 56°F return
temperature.Piping losses shall not be modeled in either_building_ model. Chilled-water supply water temperature shall be_reset_ in accordance with Section 6.5.4.4.Pump system power for each
pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no chilled-water_pumps_, the_budget building design_ pump power shall be 22 W/gpm (equal to a_pump_ oper-
ating against a 75 ft head, 65% combined impeller and motor_efficiency_). The chilled-water_system_ shall be modeled as primary-only variable flow with flow maintained at the design rate through
each chiller using a bypass. Chilled-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required in Section 6.5.4.2. The heat-rejection device shall be an
open-circuit axial-fan cooling tower with variable-speed fan control, if required in Section 6.5.5, and shall meet the performance requirements of Table 6.8.1-7. Condenser water design supply
temperature shall be calculated using the cooling tower approach to the 0.4% evaporation design wet-bulb temperature as generated by the formula below, with a design temperature rise of 10°F:
Approach_10°FRange_ = 25.72 – (0.24 × WB)
where WB is the 0.4%evaporation design wet-bulb temperature in °F, valid for wet bulbs from 55°F to 90°F.
The tower shall be controlled to maintain a cooling tower leaving water temperature, where weather permits, per Table 12.5.2-4, floating up to the design leaving water temperature for the cooling
tower.Pump system power for each pumping_system_ shall be the same as the_proposed design_; if the_proposed design_ has no condenser water_pumps_, the_budget building design_ pump power shall
be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). Each chiller shall be modeled with separate condenser water and chilled-water_pumps_
interlocked to operate with the associated chiller.
f. Fossil Fuel Boiler: For_systems_ using purchased hot water or steam, the_boilers_ are not explicitly modeled and hot-water or steam costs shall be based on actual utility rates. Otherwise, the_boiler_
plant shall use the same_fuel_ as the_proposed design_ and shall be natural draft. The_budget building design_ boiler plant shall be modeled with a single_boiler_ if the_budget building design_ plant load
is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers shall be staged as required by the load. For_boiler systems_ meeting the requirements
of Section 6.5.4.8, the hot-water supply temperature shall be modeled at 170°F design supply temperature and 120°F return temperature. For all other boiler systems, the hot-water supply tempera-
ture shall be modeled at 180°F design supply temperature and 130°F return temperature.Piping losses shall not be modeled in either_building_ model. Hot-water supply water temperature shall
be_reset_ in accordance with Section 6.5.4.4.Pump system power for each pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no hot-water_pumps_, the_budget_
building design pump power shall be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). The hot-water_system_ shall be modeled as primary-
only with continuous variable flow. Hot-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required by Section 6.5.4.2.
g. Electric Heat Pump and Boiler: Water-source heat pumps shall be connected to a common heat-pump water loop controlled to maintain temperatures between 60°F and 90°F. Heat rejection from
the loop shall be provided by a closed-circuit axial-fan evaporative fluid cooler with fan-speed control as required in Section 6.5.5.2. Heat addition to the loop shall be provided by a_boiler_ that
uses the same_fuel_ as the_proposed design_ and shall be natural draft. If no_boilers_ exist in the_proposed design_, the budget_building_ boilers shall be_fossil fuel_. The_budget building design_ boiler
plant shall be modeled with a single_boiler_ if the_budget building design_ plant load is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers
shall be staged as required by the load.Piping losses shall not be modeled in either_building_ model.Pump system power shall be the same as for the_proposed design_; if the_proposed design_ has
no_pumps_, the_budget building design_ pump power shall be 22 W/gpm, which is equal to a_pump_ operating against a 75 ft head, with a 65% combined impeller and motor_efficiency_. Loop flow
shall be variable with flow shutoff at each heat pump when its compressor cyclesOFF as required by Section 6.5.4.5 Loop_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed
drives when required by Section 6.5.4.2.
h. Electric Heat Pump: Electric air source heat pumps shall be modeled with electric auxiliary heat. The_system_ shall be controlled with a multistage_space_ thermostat and an_outdoor air_ thermostat
wired to energize auxiliary heat only on the last_thermostat_ stage and when_outdoor air_ temperature is less than 40°F.
i.
**Fan System Operation:**Fans shall be controlled in the same manner as in the_proposed design_; i.e., fan operation whenever the_space_ is occupied or fan operation cycledON calls for heating and
cooling.
j.
**Fan Speed Control:**Fans shall operate as one or two speed as required by Section 6.5.3.2, regardless of the fan speed control used in the_proposed_ design.
a. VAV with Parallel Fan-Powered Boxes: Fans in parallel_VAV_ fan-powered boxes shall be sized for 50% of the peak design flow rate and shall be modeled with 0.35 W/cfm fan power. Minimum
volume_set points_ for fan-powered boxes shall be equal to the minimum rate for the_space_ required for_ventilation_ consistent with Section 6.5.2.1, Exception 1(b). Supply air temperature_set point_
shall be constant at the_design condition_ (see Section 12.5.2[g]).
b. VAV with Reheat: Minimum volume_set points_ for_VAV_ reheat boxes shall be the larger of the following: (1) the minimum primary outdoor airflow rate required to meet the Simplified Procedure
ventilation requirements of ASHRAE Standard 62.1 for the zone or (2) the airflow rate required to comply with applicable codes or accreditation standards, including, but not limited to, pressure
relationships or minimum air change rates. The supply air temperature for cooling shall be_reset_ higher by 5°F under the minimum cooling load conditions.
c. Direct Expansion: The_fuel_ type for the cooling_system_ shall match that of the cooling_system_ in the_proposed design_.
d. VAV: The supply, return, or relief fan motor shall be modeled assuming a variable-speed drive and shall meet the_VAV_ fan part-load performance requirements of Section G3.2.3.15. If the_proposed_
design’s_system_ has a_DDC_ system at the zone level, static pressure_set-point_ reset based on zone requirements in accordance with Section 6.5.3.2.3 shall be modeled.
e. Chilled Water: For_systems_ using purchased chilled water, the chillers are not explicitly modeled, and chilled-water costs shall be based as determined in Section 12.4.3. Otherwise, the_budget_
building design’s chiller plant shall be modeled with chillers having the number as indicated in Table 12.5.2-2 as a function of_budget building design_ chiller plant load and type as indicated in
Table 12.5.2-3 as a function of individual chiller load. Where chiller_fuel_ source is mixed, the_system_ in the_budget building design_ shall have chillers with the same_fuel_ types and with capacities
having the same proportional capacity as the_proposed design_’s chillers for each_fuel_ type. Chilled-water supply temperature shall be modeled at 44°F design supply temperature and 56°F return
temperature.Piping losses shall not be modeled in either_building_ model. Chilled-water supply water temperature shall be_reset_ in accordance with Section 6.5.4.4.Pump system power for each
pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no chilled-water_pumps_, the_budget building design_ pump power shall be 22 W/gpm (equal to a_pump_ oper-
ating against a 75 ft head, 65% combined impeller and motor_efficiency_). The chilled-water_system_ shall be modeled as primary-only variable flow with flow maintained at the design rate through
each chiller using a bypass. Chilled-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required in Section 6.5.4.2. The heat-rejection device shall be an
open-circuit axial-fan cooling tower with variable-speed fan control, if required in Section 6.5.5, and shall meet the performance requirements of Table 6.8.1-7. Condenser water design supply
temperature shall be calculated using the cooling tower approach to the 0.4% evaporation design wet-bulb temperature as generated by the formula below, with a design temperature rise of 10°F:
Approach_10°FRange_ = 25.72 – (0.24 × WB)
where WB is the 0.4%evaporation design wet-bulb temperature in °F, valid for wet bulbs from 55°F to 90°F.
The tower shall be controlled to maintain a cooling tower leaving water temperature, where weather permits, per Table 12.5.2-4, floating up to the design leaving water temperature for the cooling
tower.Pump system power for each pumping_system_ shall be the same as the_proposed design_; if the_proposed design_ has no condenser water_pumps_, the_budget building design_ pump power shall
be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). Each chiller shall be modeled with separate condenser water and chilled-water_pumps_
interlocked to operate with the associated chiller.
f. Fossil Fuel Boiler: For_systems_ using purchased hot water or steam, the_boilers_ are not explicitly modeled and hot-water or steam costs shall be based on actual utility rates. Otherwise, the_boiler_
plant shall use the same_fuel_ as the_proposed design_ and shall be natural draft. The_budget building design_ boiler plant shall be modeled with a single_boiler_ if the_budget building design_ plant load
is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers shall be staged as required by the load. For_boiler systems_ meeting the requirements
of Section 6.5.4.8, the hot-water supply temperature shall be modeled at 170°F design supply temperature and 120°F return temperature. For all other boiler systems, the hot-water supply tempera-
ture shall be modeled at 180°F design supply temperature and 130°F return temperature.Piping losses shall not be modeled in either_building_ model. Hot-water supply water temperature shall
be_reset_ in accordance with Section 6.5.4.4.Pump system power for each pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no hot-water_pumps_, the_budget_
building design pump power shall be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). The hot-water_system_ shall be modeled as primary-
only with continuous variable flow. Hot-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required by Section 6.5.4.2.
g. Electric Heat Pump and Boiler: Water-source heat pumps shall be connected to a common heat-pump water loop controlled to maintain temperatures between 60°F and 90°F. Heat rejection from
the loop shall be provided by a closed-circuit axial-fan evaporative fluid cooler with fan-speed control as required in Section 6.5.5.2. Heat addition to the loop shall be provided by a_boiler_ that
uses the same_fuel_ as the_proposed design_ and shall be natural draft. If no_boilers_ exist in the_proposed design_, the budget_building_ boilers shall be_fossil fuel_. The_budget building design_ boiler
plant shall be modeled with a single_boiler_ if the_budget building design_ plant load is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers
shall be staged as required by the load.Piping losses shall not be modeled in either_building_ model.Pump system power shall be the same as for the_proposed design_; if the_proposed design_ has
no_pumps_, the_budget building design_ pump power shall be 22 W/gpm, which is equal to a_pump_ operating against a 75 ft head, with a 65% combined impeller and motor_efficiency_. Loop flow
shall be variable with flow shutoff at each heat pump when its compressor cyclesOFF as required by Section 6.5.4.5 Loop_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed
drives when required by Section 6.5.4.2.
h. Electric Heat Pump: Electric air source heat pumps shall be modeled with electric auxiliary heat. The_system_ shall be controlled with a multistage_space_ thermostat and an_outdoor air_ thermostat
wired to energize auxiliary heat only on the last_thermostat_ stage and when_outdoor air_ temperature is less than 40°F.
i.
**Fan System Operation:**Fans shall be controlled in the same manner as in the_proposed design_; i.e., fan operation whenever the_space_ is occupied or fan operation cycledON calls for heating and
cooling.
j.
**Fan Speed Control:**Fans shall operate as one or two speed as required by Section 6.5.3.2, regardless of the fan speed control used in the_proposed_ design.
a. VAV with Parallel Fan-Powered Boxes: Fans in parallel_VAV_ fan-powered boxes shall be sized for 50% of the peak design flow rate and shall be modeled with 0.35 W/cfm fan power. Minimum
volume_set points_ for fan-powered boxes shall be equal to the minimum rate for the_space_ required for_ventilation_ consistent with Section 6.5.2.1, Exception 1(b). Supply air temperature_set point_
shall be constant at the_design condition_ (see Section 12.5.2[g]).
b. VAV with Reheat: Minimum volume_set points_ for_VAV_ reheat boxes shall be the larger of the following: (1) the minimum primary outdoor airflow rate required to meet the Simplified Procedure
ventilation requirements of ASHRAE Standard 62.1 for the zone or (2) the airflow rate required to comply with applicable codes or accreditation standards, including, but not limited to, pressure
relationships or minimum air change rates. The supply air temperature for cooling shall be_reset_ higher by 5°F under the minimum cooling load conditions.
c. Direct Expansion: The_fuel_ type for the cooling_system_ shall match that of the cooling_system_ in the_proposed design_.
d. VAV: The supply, return, or relief fan motor shall be modeled assuming a variable-speed drive and shall meet the_VAV_ fan part-load performance requirements of Section G3.2.3.15. If the_proposed_
design’s_system_ has a_DDC_ system at the zone level, static pressure_set-point_ reset based on zone requirements in accordance with Section 6.5.3.2.3 shall be modeled.
e. Chilled Water: For_systems_ using purchased chilled water, the chillers are not explicitly modeled, and chilled-water costs shall be based as determined in Section 12.4.3. Otherwise, the_budget_
building design’s chiller plant shall be modeled with chillers having the number as indicated in Table 12.5.2-2 as a function of_budget building design_ chiller plant load and type as indicated in
Table 12.5.2-3 as a function of individual chiller load. Where chiller_fuel_ source is mixed, the_system_ in the_budget building design_ shall have chillers with the same_fuel_ types and with capacities
having the same proportional capacity as the_proposed design_’s chillers for each_fuel_ type. Chilled-water supply temperature shall be modeled at 44°F design supply temperature and 56°F return
temperature.Piping losses shall not be modeled in either_building_ model. Chilled-water supply water temperature shall be_reset_ in accordance with Section 6.5.4.4.Pump system power for each
pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no chilled-water_pumps_, the_budget building design_ pump power shall be 22 W/gpm (equal to a_pump_ oper-
ating against a 75 ft head, 65% combined impeller and motor_efficiency_). The chilled-water_system_ shall be modeled as primary-only variable flow with flow maintained at the design rate through
each chiller using a bypass. Chilled-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required in Section 6.5.4.2. The heat-rejection device shall be an
open-circuit axial-fan cooling tower with variable-speed fan control, if required in Section 6.5.5, and shall meet the performance requirements of Table 6.8.1-7. Condenser water design supply
temperature shall be calculated using the cooling tower approach to the 0.4% evaporation design wet-bulb temperature as generated by the formula below, with a design temperature rise of 10°F:
Approach_10°FRange_ = 25.72 – (0.24 × WB)
where WB is the 0.4%evaporation design wet-bulb temperature in °F, valid for wet bulbs from 55°F to 90°F.
The tower shall be controlled to maintain a cooling tower leaving water temperature, where weather permits, per Table 12.5.2-4, floating up to the design leaving water temperature for the cooling
tower.Pump system power for each pumping_system_ shall be the same as the_proposed design_; if the_proposed design_ has no condenser water_pumps_, the_budget building design_ pump power shall
be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). Each chiller shall be modeled with separate condenser water and chilled-water_pumps_
interlocked to operate with the associated chiller.
f. Fossil Fuel Boiler: For_systems_ using purchased hot water or steam, the_boilers_ are not explicitly modeled and hot-water or steam costs shall be based on actual utility rates. Otherwise, the_boiler_
plant shall use the same_fuel_ as the_proposed design_ and shall be natural draft. The_budget building design_ boiler plant shall be modeled with a single_boiler_ if the_budget building design_ plant load
is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers shall be staged as required by the load. For_boiler systems_ meeting the requirements
of Section 6.5.4.8, the hot-water supply temperature shall be modeled at 170°F design supply temperature and 120°F return temperature. For all other boiler systems, the hot-water supply tempera-
ture shall be modeled at 180°F design supply temperature and 130°F return temperature.Piping losses shall not be modeled in either_building_ model. Hot-water supply water temperature shall
be_reset_ in accordance with Section 6.5.4.4.Pump system power for each pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no hot-water_pumps_, the_budget_
building design pump power shall be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). The hot-water_system_ shall be modeled as primary-
only with continuous variable flow. Hot-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required by Section 6.5.4.2.
g. Electric Heat Pump and Boiler: Water-source heat pumps shall be connected to a common heat-pump water loop controlled to maintain temperatures between 60°F and 90°F. Heat rejection from
the loop shall be provided by a closed-circuit axial-fan evaporative fluid cooler with fan-speed control as required in Section 6.5.5.2. Heat addition to the loop shall be provided by a_boiler_ that
uses the same_fuel_ as the_proposed design_ and shall be natural draft. If no_boilers_ exist in the_proposed design_, the budget_building_ boilers shall be_fossil fuel_. The_budget building design_ boiler
plant shall be modeled with a single_boiler_ if the_budget building design_ plant load is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers
shall be staged as required by the load.Piping losses shall not be modeled in either_building_ model.Pump system power shall be the same as for the_proposed design_; if the_proposed design_ has
no_pumps_, the_budget building design_ pump power shall be 22 W/gpm, which is equal to a_pump_ operating against a 75 ft head, with a 65% combined impeller and motor_efficiency_. Loop flow
shall be variable with flow shutoff at each heat pump when its compressor cyclesOFF as required by Section 6.5.4.5 Loop_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed
drives when required by Section 6.5.4.2.
h. Electric Heat Pump: Electric air source heat pumps shall be modeled with electric auxiliary heat. The_system_ shall be controlled with a multistage_space_ thermostat and an_outdoor air_ thermostat
wired to energize auxiliary heat only on the last_thermostat_ stage and when_outdoor air_ temperature is less than 40°F.
i.
**Fan System Operation:**Fans shall be controlled in the same manner as in the_proposed design_; i.e., fan operation whenever the_space_ is occupied or fan operation cycledON calls for heating and
cooling.
j.
**Fan Speed Control:**Fans shall operate as one or two speed as required by Section 6.5.3.2, regardless of the fan speed control used in the_proposed_ design.
a. VAV with Parallel Fan-Powered Boxes: Fans in parallel_VAV_ fan-powered boxes shall be sized for 50% of the peak design flow rate and shall be modeled with 0.35 W/cfm fan power. Minimum
volume_set points_ for fan-powered boxes shall be equal to the minimum rate for the_space_ required for_ventilation_ consistent with Section 6.5.2.1, Exception 1(b). Supply air temperature_set point_
shall be constant at the_design condition_ (see Section 12.5.2[g]).
b. VAV with Reheat: Minimum volume_set points_ for_VAV_ reheat boxes shall be the larger of the following: (1) the minimum primary outdoor airflow rate required to meet the Simplified Procedure
ventilation requirements of ASHRAE Standard 62.1 for the zone or (2) the airflow rate required to comply with applicable codes or accreditation standards, including, but not limited to, pressure
relationships or minimum air change rates. The supply air temperature for cooling shall be_reset_ higher by 5°F under the minimum cooling load conditions.
c. Direct Expansion: The_fuel_ type for the cooling_system_ shall match that of the cooling_system_ in the_proposed design_.
d. VAV: The supply, return, or relief fan motor shall be modeled assuming a variable-speed drive and shall meet the_VAV_ fan part-load performance requirements of Section G3.2.3.15. If the_proposed_
design’s_system_ has a_DDC_ system at the zone level, static pressure_set-point_ reset based on zone requirements in accordance with Section 6.5.3.2.3 shall be modeled.
e. Chilled Water: For_systems_ using purchased chilled water, the chillers are not explicitly modeled, and chilled-water costs shall be based as determined in Section 12.4.3. Otherwise, the_budget_
building design’s chiller plant shall be modeled with chillers having the number as indicated in Table 12.5.2-2 as a function of_budget building design_ chiller plant load and type as indicated in
Table 12.5.2-3 as a function of individual chiller load. Where chiller_fuel_ source is mixed, the_system_ in the_budget building design_ shall have chillers with the same_fuel_ types and with capacities
having the same proportional capacity as the_proposed design_’s chillers for each_fuel_ type. Chilled-water supply temperature shall be modeled at 44°F design supply temperature and 56°F return
temperature.Piping losses shall not be modeled in either_building_ model. Chilled-water supply water temperature shall be_reset_ in accordance with Section 6.5.4.4.Pump system power for each
pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no chilled-water_pumps_, the_budget building design_ pump power shall be 22 W/gpm (equal to a_pump_ oper-
ating against a 75 ft head, 65% combined impeller and motor_efficiency_). The chilled-water_system_ shall be modeled as primary-only variable flow with flow maintained at the design rate through
each chiller using a bypass. Chilled-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required in Section 6.5.4.2. The heat-rejection device shall be an
open-circuit axial-fan cooling tower with variable-speed fan control, if required in Section 6.5.5, and shall meet the performance requirements of Table 6.8.1-7. Condenser water design supply
temperature shall be calculated using the cooling tower approach to the 0.4% evaporation design wet-bulb temperature as generated by the formula below, with a design temperature rise of 10°F:
Approach_10°FRange_ = 25.72 – (0.24 × WB)
where WB is the 0.4%evaporation design wet-bulb temperature in °F, valid for wet bulbs from 55°F to 90°F.
The tower shall be controlled to maintain a cooling tower leaving water temperature, where weather permits, per Table 12.5.2-4, floating up to the design leaving water temperature for the cooling
tower.Pump system power for each pumping_system_ shall be the same as the_proposed design_; if the_proposed design_ has no condenser water_pumps_, the_budget building design_ pump power shall
be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). Each chiller shall be modeled with separate condenser water and chilled-water_pumps_
interlocked to operate with the associated chiller.
f. Fossil Fuel Boiler: For_systems_ using purchased hot water or steam, the_boilers_ are not explicitly modeled and hot-water or steam costs shall be based on actual utility rates. Otherwise, the_boiler_
plant shall use the same_fuel_ as the_proposed design_ and shall be natural draft. The_budget building design_ boiler plant shall be modeled with a single_boiler_ if the_budget building design_ plant load
is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers shall be staged as required by the load. For_boiler systems_ meeting the requirements
of Section 6.5.4.8, the hot-water supply temperature shall be modeled at 170°F design supply temperature and 120°F return temperature. For all other boiler systems, the hot-water supply tempera-
ture shall be modeled at 180°F design supply temperature and 130°F return temperature.Piping losses shall not be modeled in either_building_ model. Hot-water supply water temperature shall
be_reset_ in accordance with Section 6.5.4.4.Pump system power for each pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no hot-water_pumps_, the_budget_
building design pump power shall be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). The hot-water_system_ shall be modeled as primary-
only with continuous variable flow. Hot-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required by Section 6.5.4.2.
g. Electric Heat Pump and Boiler: Water-source heat pumps shall be connected to a common heat-pump water loop controlled to maintain temperatures between 60°F and 90°F. Heat rejection from
the loop shall be provided by a closed-circuit axial-fan evaporative fluid cooler with fan-speed control as required in Section 6.5.5.2. Heat addition to the loop shall be provided by a_boiler_ that
uses the same_fuel_ as the_proposed design_ and shall be natural draft. If no_boilers_ exist in the_proposed design_, the budget_building_ boilers shall be_fossil fuel_. The_budget building design_ boiler
plant shall be modeled with a single_boiler_ if the_budget building design_ plant load is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers
shall be staged as required by the load.Piping losses shall not be modeled in either_building_ model.Pump system power shall be the same as for the_proposed design_; if the_proposed design_ has
no_pumps_, the_budget building design_ pump power shall be 22 W/gpm, which is equal to a_pump_ operating against a 75 ft head, with a 65% combined impeller and motor_efficiency_. Loop flow
shall be variable with flow shutoff at each heat pump when its compressor cyclesOFF as required by Section 6.5.4.5 Loop_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed
drives when required by Section 6.5.4.2.
h. Electric Heat Pump: Electric air source heat pumps shall be modeled with electric auxiliary heat. The_system_ shall be controlled with a multistage_space_ thermostat and an_outdoor air_ thermostat
wired to energize auxiliary heat only on the last_thermostat_ stage and when_outdoor air_ temperature is less than 40°F.
i.
**Fan System Operation:**Fans shall be controlled in the same manner as in the_proposed design_; i.e., fan operation whenever the_space_ is occupied or fan operation cycledON calls for heating and
cooling.
j.
**Fan Speed Control:**Fans shall operate as one or two speed as required by Section 6.5.3.2, regardless of the fan speed control used in the_proposed_ design.
a. VAV with Parallel Fan-Powered Boxes: Fans in parallel_VAV_ fan-powered boxes shall be sized for 50% of the peak design flow rate and shall be modeled with 0.35 W/cfm fan power. Minimum
volume_set points_ for fan-powered boxes shall be equal to the minimum rate for the_space_ required for_ventilation_ consistent with Section 6.5.2.1, Exception 1(b). Supply air temperature_set point_
shall be constant at the_design condition_ (see Section 12.5.2[g]).
b. VAV with Reheat: Minimum volume_set points_ for_VAV_ reheat boxes shall be the larger of the following: (1) the minimum primary outdoor airflow rate required to meet the Simplified Procedure
ventilation requirements of ASHRAE Standard 62.1 for the zone or (2) the airflow rate required to comply with applicable codes or accreditation standards, including, but not limited to, pressure
relationships or minimum air change rates. The supply air temperature for cooling shall be_reset_ higher by 5°F under the minimum cooling load conditions.
c. Direct Expansion: The_fuel_ type for the cooling_system_ shall match that of the cooling_system_ in the_proposed design_.
d. VAV: The supply, return, or relief fan motor shall be modeled assuming a variable-speed drive and shall meet the_VAV_ fan part-load performance requirements of Section G3.2.3.15. If the_proposed_
design’s_system_ has a_DDC_ system at the zone level, static pressure_set-point_ reset based on zone requirements in accordance with Section 6.5.3.2.3 shall be modeled.
e. Chilled Water: For_systems_ using purchased chilled water, the chillers are not explicitly modeled, and chilled-water costs shall be based as determined in Section 12.4.3. Otherwise, the_budget_
building design’s chiller plant shall be modeled with chillers having the number as indicated in Table 12.5.2-2 as a function of_budget building design_ chiller plant load and type as indicated in
Table 12.5.2-3 as a function of individual chiller load. Where chiller_fuel_ source is mixed, the_system_ in the_budget building design_ shall have chillers with the same_fuel_ types and with capacities
having the same proportional capacity as the_proposed design_’s chillers for each_fuel_ type. Chilled-water supply temperature shall be modeled at 44°F design supply temperature and 56°F return
temperature.Piping losses shall not be modeled in either_building_ model. Chilled-water supply water temperature shall be_reset_ in accordance with Section 6.5.4.4.Pump system power for each
pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no chilled-water_pumps_, the_budget building design_ pump power shall be 22 W/gpm (equal to a_pump_ oper-
ating against a 75 ft head, 65% combined impeller and motor_efficiency_). The chilled-water_system_ shall be modeled as primary-only variable flow with flow maintained at the design rate through
each chiller using a bypass. Chilled-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required in Section 6.5.4.2. The heat-rejection device shall be an
open-circuit axial-fan cooling tower with variable-speed fan control, if required in Section 6.5.5, and shall meet the performance requirements of Table 6.8.1-7. Condenser water design supply
temperature shall be calculated using the cooling tower approach to the 0.4% evaporation design wet-bulb temperature as generated by the formula below, with a design temperature rise of 10°F:
Approach_10°FRange_ = 25.72 – (0.24 × WB)
where WB is the 0.4%evaporation design wet-bulb temperature in °F, valid for wet bulbs from 55°F to 90°F.
The tower shall be controlled to maintain a cooling tower leaving water temperature, where weather permits, per Table 12.5.2-4, floating up to the design leaving water temperature for the cooling
tower.Pump system power for each pumping_system_ shall be the same as the_proposed design_; if the_proposed design_ has no condenser water_pumps_, the_budget building design_ pump power shall
be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). Each chiller shall be modeled with separate condenser water and chilled-water_pumps_
interlocked to operate with the associated chiller.
f. Fossil Fuel Boiler: For_systems_ using purchased hot water or steam, the_boilers_ are not explicitly modeled and hot-water or steam costs shall be based on actual utility rates. Otherwise, the_boiler_
plant shall use the same_fuel_ as the_proposed design_ and shall be natural draft. The_budget building design_ boiler plant shall be modeled with a single_boiler_ if the_budget building design_ plant load
is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers shall be staged as required by the load. For_boiler systems_ meeting the requirements
of Section 6.5.4.8, the hot-water supply temperature shall be modeled at 170°F design supply temperature and 120°F return temperature. For all other boiler systems, the hot-water supply tempera-
ture shall be modeled at 180°F design supply temperature and 130°F return temperature.Piping losses shall not be modeled in either_building_ model. Hot-water supply water temperature shall
be_reset_ in accordance with Section 6.5.4.4.Pump system power for each pumping_system_ shall be the same as for the_proposed design_; if the_proposed design_ has no hot-water_pumps_, the_budget_
building design pump power shall be 19 W/gpm (equal to a_pump_ operating against a 60 ft head, 60% combined impeller and motor_efficiency_). The hot-water_system_ shall be modeled as primary-
only with continuous variable flow. Hot-water_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed drives when required by Section 6.5.4.2.
g. Electric Heat Pump and Boiler: Water-source heat pumps shall be connected to a common heat-pump water loop controlled to maintain temperatures between 60°F and 90°F. Heat rejection from
the loop shall be provided by a closed-circuit axial-fan evaporative fluid cooler with fan-speed control as required in Section 6.5.5.2. Heat addition to the loop shall be provided by a_boiler_ that
uses the same_fuel_ as the_proposed design_ and shall be natural draft. If no_boilers_ exist in the_proposed design_, the budget_building_ boilers shall be_fossil fuel_. The_budget building design_ boiler
plant shall be modeled with a single_boiler_ if the_budget building design_ plant load is 600,000 Btu/h or less and with two equally sized_boilers_ for plant capacities exceeding 600,000 Btu/h.Boilers
shall be staged as required by the load.Piping losses shall not be modeled in either_building_ model.Pump system power shall be the same as for the_proposed design_; if the_proposed design_ has
no_pumps_, the_budget building design_ pump power shall be 22 W/gpm, which is equal to a_pump_ operating against a 75 ft head, with a 65% combined impeller and motor_efficiency_. Loop flow
shall be variable with flow shutoff at each heat pump when its compressor cyclesOFF as required by Section 6.5.4.5 Loop_pumps_ shall be modeled as riding the_pump_ curve or with variable-speed
drives when required by Section 6.5.4.2.
h. Electric Heat Pump: Electric air source heat pumps shall be modeled with electric auxiliary heat. The_system_ shall be controlled with a multistage_space_ thermostat and an_outdoor air_ thermostat
wired to energize auxiliary heat only on the last_thermostat_ stage and when_outdoor air_ temperature is less than 40°F.
i.
**Fan System Operation:**Fans shall be controlled in the same manner as in the_proposed design_; i.e., fan operation whenever the_space_ is occupied or fan operation cycledON calls for heating and
cooling.
j.
**Fan Speed Control:**Fans shall operate as one or two speed as required by Section 6.5.3.2, regardless of the fan speed control used in the_proposed_ design.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 221

PDF Page 224

Open page note

Table 12.5.2-2 Number of Chillers

Table 12.5.2-3 Water Chiller Types

Table 12.5.2-4 Cooling Tower Leaving Water Temperature

222 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 225

Open page note

13. NORMATIVE REFERENCES

Reference Section

Air Conditioning, Heating and Refrigeration Institute (AHRI)2311 Wilson Blvd., Arlington, VA 22201

AHRI 210/240 (2017) with addendum 1 Unitary Air Conditioning and Air-Source Heat Pump Equipment  (applicable before 1/1/2023)

AHRI 210/240-2023 (2020) Unitary Air Conditioning and Air-Source Heat Pump Equipment (applicable on or after 1/1/2023)

Table 6.8.1-1, Table 6.8.1-2,

Table F-1, Table G3.5.1,

Table G3.5.2

Table 6.8.1-1, Table 6.8.1-8, Table 6.8.1-9,

Table F-1

AHRI 310/380 (2017) Packaged Terminal Air-Conditioners and Heat Pumps Table 6.8.1-4,

Table G3.5.4

AHRI 340/360 (I-P/2022) Performance Rating of Commercial and Industrial Unitary  Air-Conditioning and Heat Pump Equipment

ANSI/AHRI 365 (I-P/2009) Commercial and Industrial Unitary Air-Conditioning Condensing Units

AHRI 390 (I-P/2021) Performance Rating of Single Packaged Vertical Air-Conditioners  and Heat Pumps

Table 6.8.1-1, Table 6.8.1-2,

Table G3.5.1,

Table G3.5.2

Table 6.8.1-1

Table 6.8.1-4

ANSI/AHRI 400 (I-P/2015) Performance Rating of Liquid-to-Liquid Heat Exchangers 6.4.7

ANSI/AHRI 460 (2005) Remote Mechanical Draft Air Cooled Refrigerant Condensers Table 6.8.1-7

AHRI 550/590 (I-P/2020)  (with Addendum 1)

Performance Rating of Water-Chilling and Heat-Pump Water-Heating Packages Using the Vapor Compression Cycle

6.4.1.2.1, 6.4.1.2.2.1, 6.4.1.2.2.2, 6.4.1.2.2.3, 6.4.1.2.2.4, Table 6.8.1-3, Table 6.8.1-16,

Table G3.5.3

AHRI 560 (2000) Absorption Water Chilling and Water Heating Packages Table 6.8.1-3

ANSI/AHRI 910 (I-P/2014) Performance Rating of Indoor Pool Dehumidifiers Table 6.8.1-12

ANSI/AHRI 920 (I-P/2015) Performance Rating of DX-Dedicated Outdoor Air System Units 3.2, Table 6.8.1-13, Table 6.8.1-14

ANSI/AHRI 1200 (I-P/2013) Performance Rating of Commercial Refrigerated Display Merchandisers and Storage Cabinets

ANSI/AHRI 1230 (I-P/2014)  (with Addendum 1)

Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment

Table 6.8.1-11,

Table 12.5.1,

Table G3.1, Table G3.10.1,

Table G3.10.2

Table 6.8.1-8,

Table 6.8.1-9

Table 6.8.1-8,

Table 6.8.1-9

ANSI/AHRI 1230 (I-P/2021) Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split  Air-Conditioning and Heat Pump Equipment

AHRI Standard 1250 (I-P/2020) Performance Rating of Walk-In Coolers and Freezers Table 6.8.1-20

AHRI Standard 1300 (I-P/2013) Performance Rating of Commercial Heat Pump Water Heaters 11.5.2.3.1

AHRI Standard 1360 (I-P/2017) Performance Rating of Computer and Data Processing Room Air Conditioners

Table 6.8.1-10,

Table 6.8.1-17

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 223

PDF Page 226

Open page note

Reference Section

Air Movement and Control Association International (AMCA)30 West University Drive, Arlington Heights, IL 60004-1806

ANSI/AMCA 208-18 Calculation of the Fan Energy Index 3.2, 6.5.3.1.3, Table 6.8.1-21

ANSI/AMCA 220-21 Laboratory Methods of Testing Air Curtains for Aerodynamic Performance Ratings

ANSI/AMCA Standard 230-15 with errata Laboratory Methods of Testing Air Circulating Fans for Rating and Certification

10.4.5

Table 6.8.1-21

ANSI/AMCA Standard 500-D-18 Laboratory Methods of Testing Dampers for Rating Table 6.4.3.4.3

American Architectural Manufacturers Association (AAMA) Fenestration and Glazing Industry Alliance (FGIA) 1900 E. Golf Rd, Suite 1250, Schaumburg, IL 60173-4268

Canadian Standards Association (CSA) 78 Rexdale Blvd., Toronto, On, Canada M9W 1R3

Window and Door Manufacturers Association (WDMA) 2025 M Street, NW, Suite 800, Washington, DC 20036

AAMA/WDMA/CSA 101/I.S.2/A440-17 NAFS-North American Fenestration Standard/Specification for Windows, Doors, and Skylights

American Iron and Steel Institute (AISI) 25 Massachusetts Avenue, NW, Suite 800 Washington, DC 20001

ANSI/AISI S250-2021 North American Standard for Thermal Transmittance of Building Envelopes with Cold-Formed Steel Framing

American National Standards Institute (ANSI)1899 L Street, NW, 11th Floor, Washington, DC 20036

Table 5.8.3.2

A2.5.3, A9.2

ANSI Z21.47-2021/CSA 2.3-2021 Gas-Fired Central Furnaces Table G3.5.5,

Table 6.8.1-5

ANSI Z83.8-2016/CSA 2.6-2016 (R2021) Gas Unit Heaters, Gas Packaged Heaters, Gas Utility Heaters And Gas-Fired Duct Furnaces

American Society of Mechanical Engineers (ASME)Two Park Avenue, New York, NY 10016-5990

Table G3.5.5,

Table 6.8.1-5

ASME A17.1-2019/CSA B44-16 Safety Code for Elevators and Escalators 10.4.3.3, 10.4.4

ASHRAE180 Technology Parkway, Peachtree Corners, GA 30092

ANSI/ASHRAE Standard 51-2016 Laboratory Methods of Testing Fans for Certified Aerodynamic Performance Rating

Table 6.5.3.7

ANSI/ASHRAE Standard 55-2020 Thermal Environmental Conditions for Human Occupancy Table G3.1

ANSI/ASHRAE Standard 62.1-2019 Ventilation for Acceptable Indoor Air Quality 6.4.3.3.2, 6.4.3.3.5.1, 6.4.3.8, Table 6.4.3.8, 6.5.1, 6.5.2.1, 6.5.2.3, 6.5.3.2.1, 6.5.3.3, 6.5.3.8, 6.5.3.9, 6.5.6.1.2, 6.5.7.1, 11.5.2.2.6, 11.5.2.8.2, Table 12.5.2-1, G3.2.2.4, G3.2.2.5,

Table L2.2.3

ANSI/ASHRAE Standard 62.2-2019 Ventilation and Acceptable Indoor Air Quality in Residential Buildings 6.5.3.8

ANSI/ASHRAE/IESNA Standard 90.1-2007 Energy Standard for Buildings Except Low-Rise Residential Buildings 6.4.1.2.1

224 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 227

Open page note

Reference Section

ANSI/ASHRAE/IESNA Standard 90.1-2010 Energy Standard for Buildings Except Low-Rise Residential Buildings 6.4.1.2.1

ANSI/ASHRAE/IESNA Standard 90.1-2013 Energy Standard for Buildings Except Low-Rise Residential Buildings 6.4.1.2.1

ANSI/ASHRAE/IES Standard 90.1-2016 Energy Standard for Buildings Except Low-Rise Residential Buildings 6.4.1.2.1

ANSI/ASHRAE/IES Standard 90.1-2019 Energy Standard for Buildings Except Low-Rise Residential Buildings 6.4.1.2.1

ANSI/ASHRAE/IES Standard 90.4-2019 (with addenda a, b, d, e, and f)

Energy Standard for Data Centers 6.6.1, 6.6.2.1, 8.6.1, Table 11.5.1-1,

11.5.2.2.3

ANSI/ASHRAE Standard 140-2020 Method of Test for Evaluating Building Performance Simulation Software

12.4.1.4.1, 12.4.1.4.2, 12.7.2, C2.8, C3.1.4.1, C3.1.4.2, G1.3.2, G2.2.4.1, G2.2.4.2,

L3.2.4.1, L3.2.4.2,

L3.4

ANSI/ASHRAE Standard 154-2016 Ventilation for Commercial Cooking Operations 6.5.7.2.2

ANSI/ASHRAE Standard 169-2013 Climatic Data for Building Design Standards 5.1.5.1, 5.1.5.2

ANSI/ASHRAE/ASHE Standard 170-2021 Ventilation of Health Care Facilities 6.4.3.8, 6.5.3.8, 6.5.6.1.2, Table 11.5.1-1

ANSI/ASHRAE/ACCA Standard 183-2007 (RA 2020)

Peak Cooling and Heating Load Calculations in Buildings Except  Low-Rise Residential Buildings

6.4.2.1

ASHRAE/IES Standard 202-2018 Commissioning Process for Buildings and Systems 4.2.5.2, 4.2.5.2.2

Association of Home Appliance Manufacturers (AHAM)1111 19th Street NW, Suite 402, Washington, DC 20036

ANSI/AHAM HRF-1-2016 Energy and Internal Volume of Refrigerating Appliances Table G3.10.1

ANSI/AHAM RAC-1-2020 Room Air Conditioners Table 6.8.1-4

ASTM International100 Barr Harbor Dr., West Conshohocken, PA 19428-2959

ASTM C90-16A Standard Specification for Loadbearing Concrete Masonry Units 5.5.3.2, A3.1.1, A9.4.4

ASTM C177-19 Standard Test Method for Steady-State Heat Flux Measurements and Thermal Transmittance Properties by Means of the Guarded-HotPlate Apparatus

ASTM C272/C272M-18 Standard Test Method for Water Absorption of Core Materials for Sandwich Constructions

ASTM C518-21 Standard Test Method for Steady-State Thermal Transmittance Properties by Means of the Heat Flow Meter Apparatus

ASTM C835-06 (2013) e1 Standard Test Method for Total Hemispherical Emittance of Surfaces up to 1400°C

ASTM C1224 (2020) Standard Specification for Reflective Insulation for Building Applications

ASTM C1363-19 Standard Test Method for the Thermal Performance of Building Assemblies by Means of a Hot Box Apparatus

ASTM C1371-15 Standard Test Method for Determination of Emittance of Materials Near Room Temperature using Portable Emissometers.

ASTM C1549-16 Standard Test Method for Determination of Solar Reflectance Near Ambient Temperature Using a Portable Solar Reflectometer

A9.3.1

5.8.1.7.3

Table 6.8.2, A9.3.1

5.5.3.2.2

A9.4.2, Table A9.4.2-2

A3.3.3.2, A9.3.1,

A9.3.2, A10.1

5.5.3.2.2

5.5.3.2.2

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 225

PDF Page 228

Open page note

Reference Section

ASTM D1003-21 Standard Test Method for Haze and Luminous Transmittance of Transparent Plastics

ASTM E283/E283M-19 Standard Test Method for Determining Rate of Air Leakage through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen

ASTM E408-13 (2019) Standard Test Methods for Total Normal Emittance of Surfaces Using Inspection-Meter Techniques

ASTM E3158-18 Standard Test Method for Measuring the Air Leakage Rate of a Large or Multizone Building

ASTM E779-19 Standard Test Method for Determining Air Leakage Rate by Fan Pressurization

ASTM E972-96 (2021) Standard Test Method for Solar Photometric Transmittance of Sheet Materials Using Sunlight

ASTM E1677-19 Standard Specification for an Air Retarder (AR) Material or System for Low-Rise Framed Building Walls

ASTM E1680-16 Standard Test Method for Rate of Air Leakage through Exterior Metal Roof Panel Systems

ASTM E1827-11 (2017) Standard Test Methods for Determining Airtightness of Buildings Using an Orifice Blower Door

ASTM E1980-11 (2019) Standard Practice for Calculating Solar Reflectance Index of Horizontal and Low Sloped Opaque Surfaces

5.5.4.2.3, 5.5.4.4.2

Table 5.8.3.1, 5.8.3.2

5.5.3.2.2

5.4.3.1.4, 12.5.3, G3.2.1.7

5.4.3.1.4, 12.5.3

5.8.2.6

Table 5.8.3.1

Table 5.8.3.1

5.4.3.1.4, 12.5.3, G3.2.1.7

5.4.3.1.4

ASTM E2178-21a Standard Test Method for Air Permeance of Building Materials Table 5.8.3.1

ASTM E2357-18 Standard Test Method for Determining Air Leakage of Air Barrier Assemblies

Table 5.8.3.1

ASTM F1361-17 Standard Test Method for Performance of Open Deep Fat Fryers Table 11.5.2.7.2-1

ASTM F1484-18 Standard Test Method for Performance of Steam Cookers Table 11.5.2.7.2-2

ASTM F1495-14a Standard Specification for Combination Oven Electric or Gas Fired Table 11.5.2.7.2-4

ASTM F1496-13 Standard Test Method for Performance of Convection Ovens Table 11.5.2.7.2-4

ASTM F1696-18 Standard Test Method for Energy Performance of Stationary-Rack, Door-Type Commercial Dishwashing Machines

ASTM F1920-15 Standard Test Method for Performance of Rack Conveyor Commercial Dishwashing Machines

Table 11.5.2.7.2-3

Table 11.5.2.7.2-3

ASTM F2093-18 Standard Test Method for Performance of Rack Ovens Table 11.5.2.7.2-4

ASTM F2144-17 Standard Test Method for Performance of Large Open Vat Fryers Table 11.5.2.7.2-1

ASTM F2861-17 Standard Test Method for Enhanced Performance of Combination Oven in Various Modes

Cool Roof Rating Council (CRRC) 2435 N. Lombard St., Portland, OR 97217, United States

ANSI/CRRC S100 (2021) Standard Test Methods for Determining Radiative Properties of Materials

Cooling Technology Institute (CTI)3845 Cypress Creek Parkway, Suite 420, Houston, TX 77068; P.O. Box 681807, Houston, TX 77268

Table 11.5.2.7.2-4

5.5.3.1.4

CTI ATC-105 (19) Acceptance Test Code for Water Cooling Towers Table 6.8.1-7

CTI ATC-105DS (18) Acceptance Test Code for Dry Fluid Coolers Table 6.8.1-7

226 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 229

Open page note

Reference Section

CTI ATC-105S (11) Acceptance Test Code for Closed-Circuit Cooling Towers Table 6.8.1-7

CTI ATC-106 (11) Acceptance Test Code for Mechanical Draft Evaporative Vapor Condensers

Table 6.8.1-7

CTI STD-201 RS (21) Performance Rating of Evaporative Heat Rejection Equipment Table 6.8.1-7

Door and Access Systems Manufacturers Association (DASMA)1300 Sumner Avenue, Cleveland, OH 44115-2851

ANSI/DASMA 105-2020 Test Method for Thermal Transmittance and Air Infiltration of Garage Doors

International Association of Plumbing and Mechanical Officials (IAPMO) 4755 E. Philadelphia Street, Ontario, CA 91761-2816

5.8.3.2, Table 5.8.3.2

IAPMO/ANSI WE·Stand-2017 Water Efficiency and Sanitation Standard for the Built Environment 11.5.2.3.5

International Organization for Standardization (ISO) ISO Central Secretariat BIBC IIChemin de Blandonnet 8, CP 401, 1214, Vernier, Geneva, Switzerland

ISO 9050 (2003) Glass in Building—Determination of Light Transmittance, Solar Direct Transmittance, Total Solar Energy Transmittance, Ultraviolet Transmittance and Related Glazing Factors

ISO 10211 (2017) Thermal bridges in building construction—Heat flows and surface temperatures—Detailed calculations

ANSI/AHRI/ASHRAE/ISO 13256-1:1998 (2021)

ANSI/AHRI/ASHRAE/ISO 13256-2:1998 (2021)

Water-Source Heat Pumps—Testing and Rating for Performance— Part 1: Water-to-Air and Brine-to-Air Heat Pumps

Water-Source Heat Pumps—Testing and Rating for Performance— Part 2: Water-to-Water and Brine-to-Water Heat Pumps

ISO 14683 (2017) Thermal bridges in building construction—Linear thermal transmittance—Simplified methods and default values

ISO 25745-2:2015 Energy Performance of Lifts, Escalators and Moving Walks—Part 2: Energy Calculation and Classification for Lifts (Elevators)

National Electrical Manufacturers Association (NEMA)1300 N. 17th Street, Suite 900, Arlington, VA 22209

5.5.3.2.2

A10.1

Table 6.8.1-15

Table 6.8.1-15

A10.1

10.4.3.4, 10.9.3, 11.5.2.7.1

ANSI/NEMA MG 1-2016, with 2021 Revisions

Motors and Generators 3.2

National Fenestration Rating Council (NFRC)6305 Ivy Lane, Suite 140, Greenbelt, MD 20770-6323

ANSI/NFRC 100-2020 Procedure for Determining Fenestration Product U-Factors 5.8.2.4

ANSI/NFRC 200-2020 Procedure for Determining Fenestration Product Solar Heat Gain Coefficients and Visible Transmittance at Normal Incidence

ANSI/NFRC 203-2020 Procedure for Determining Visible Transmittance of Tubular Daylighting Devices

NFRC 300-2020 Test Method for Determining the Solar Optical Properties of Glazing Materials and Systems

5.5.4.6, 5.8.2.5 5.8.2.6

5.8.2.6

5.8.2.6

NFRC 301-2020 Standard Test Method for Emittance of Glazing Products 5.5.4.6

ANSI/NFRC 400-2020 Procedure for Determining Fenestration Product Air Leakage Table 5.8.3.2, 5.8.3.2

National Fire Protection Association (NFPA)1 Battery March Park, Quincy, MA 02269-9101; P.O. Box 9101

NFPA 70-2020 National Electric Code 6.5.1, 8.4.3.1, 8.4.3.2

NFPA 96-2021 Ventilation Control and Fire Protection of Commercial Cooking Operations

G3.2.2.9

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 227

PDF Page 230

Open page note

Reference Section

Telecommunications Industry Association (TIA)1320 North Courthouse Road, Suite 200

ANSI/TIA-942-REV B, July 12, 2017 Telecommunication Infrastructure Standard for Data Centers 6.5.1

UL, LLC333 Pfingsten Rd., Northbrook, IL 60062

UL 181A-2021 Closure Systems for Use with Rigid Air Ducts and Air Connectors 6.4.4.2.1

UL 181B-2021 Closure Systems for Use with Flexible Air Ducts and Air Connectors 6.4.4.2.1

UL 727-2018 UL Standard for Safety—Oil Fired Central Furnaces Table 6.8.1-5

UL 731-2021 UL Standard for Safety—Oil-Fired Unit Heaters Table 6.8.1-5

U.S. Department of Defense 3010 Defense Pentagon, Washington, DC 20301

MIL-P-17639F (1996) Pumps, Centrifugal, Miscellaneous Service, Naval Shipboard Use 10.4.8

MIL-P-17840C (1986) Pumps, Centrifugal, Close-Coupled, Navy Standard (for Surface Ship Application)

10.4.8

MIL-P-17881D (1972) Pumps, Centrifugal, Boiler Feed (Multi-Stage) 10.4.8

MIL-P-18472 (1989) Pumps, Centrifugal, Condensate, Feed Booster, Waste Heat Boiler, and Distilling Plant

10.4.8

MIL-P-18682D Pump, Centrifugal, Main Condenser Circulating, Naval Shipboard 10.4.8

U.S. Department of Energy (DOE)1000 Independence Avenue, SW, Washington, DC 20585

10 CFR Part 430, App N Uniform Test Method for Measuring the Energy Consumption of Furnaces

10 CFR Part 430, App U Uniform Test Method for Measuring the Energy Consumption of Ceiling Fans

10 CFR Part 430 Subpart B App U Uniform Test Method for Measuring the Energy Consumption of Ceiling Fans

10 CFR Part 431.304 Uniform Test Method for the Measurement of Energy Consumption of Walk-In Coolers and Walk-In Freezers

10 CFR 431 Subpart K, App A Uniform Test Method for Measuring the Energy Consumption of Distribution Transformers

10 CFR Part 431, Subpart B, App B Uniform Test Method for Measuring Nominal Full-Load Efficiency  of Electric Motors

10 CFR Part 431, Subpart Y Pumps: Definitions, Energy Conservation Standards, and Uniform Test Method of the Measurement of Energy Consumption of Pumps

Table 6.8.1-5, Table 6.8.1-6,

Table F-4

6.5.3.7, Table 6.8.1-21,

Table F-6

F3

42 USC 6831, et seq., Public Law 102-486 Energy Policy Act of 1992, EPACT 2005, and EISA 2007 6.4.1.1

U.S. Security and Exchange Commission (SEC)100 F Street, NE, Washington, DC 20549

The Interagency Paper on Sound Practices to Strengthen the Resilience of the US Financial System

The Interagency Paper on Sound Practices to Strengthen the Resilience of the US Financial System, April 7, 2003

6.5.1

228 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 231

Open page note

(This is a normative appendix and is part of this standard.)

NORMATIVE APPENDIX A RATED R-VALUE OF INSULATION AND ASSEMBLYU-FACTOR, C-FACTOR, AND F-FACTOR DETERMINATIONS

A1. GENERAL

Where using Normative Appendix A to demonstrate compliance with Section 5.5, the thermal performance of building envelopes shall be determined in accordance with Section A1.1 or A1.2.

A1.1 Precalculated Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities. Precalculated U- factors, C-factors, F-factors, and heat capacities for typical building envelope assemblies shall be used for assemblies consistent with the specifications in Sections A2 through A8. These precalculated values shall be permitted to be used to demonstrate compliance for a building envelope assembly with any type of exterior covering or interior finish.

Interpolation between values in a particular table in Normative Appendix A shall be permitted for rated R-values of insulation, including insulated sheathing. Extrapolation beyond values in a table in Normative Appendix A is not allowed.

A1.2 Applicant-Determined Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities. Testing, calculation, and modeling procedures in Section A9 shall be used to determine U-factors, C-factors, F-factors or heat capacities for assemblies that are not addressed by or are different from the assembly specifications listed in Sections A2 through A8 and the associated precalculated values.

A1.3 Applicant-Determined Psi-Factors and Chi-Factors for Thermal Bridges. The applicant shall determine values for point thermal bridges and linear thermal bridges using the assumptions in Section A10.

A2. ROOFS

A2.1 General. The buffering effect of suspended ceilings or attic spaces shall not be included in U-factor calculations.

A2.2 Roofs with Insulation Entirely Above Deck

A2.2.1 General. For the purpose of Section A1.2, the base assembly is continuous insulation over a structural deck. The U-factor includes R-0.17 for exterior air film, R-0 for metal deck, and R-0.61 for interior air film heat flow up. Added insulation is continuous and uninterrupted by framing. The framing factor is zero.

A2.2.2 Rated R-Value of Insulation. For roofs with insulation entirely above deck, the rated R-value of insulation is for continuous insulation .

Exception to A2.2.2: Interruptions for framing and pads for mechanical equipment are permitted with a

combined total area not exceeding one percent of the total opaque assembly area.

A2.2.3 U-Factor. U-factors for roofs with insulation entirely above deck shall be taken from Table A2.2.3. It is not acceptable to use these U-factors if the insulation is not entirely above deck or not continuous.

A2.3 Metal Building Roofs

A2.3.1 General. For the purpose of Section A1.2, the base assembly is a roof with thermal spacer blocks where the insulation is draped over the steel structure (purlins), spaced nominally 5 ft on center and compressed when the metal roof panels are attached to the steel structure (purlins).

A2.3.2 Rated R-Value of Insulation

A2.3.2.1 Single Layer. The rated R-value of insulation is for insulation installed perpendicular to and draped over purlins and then compressed when the metal roof panels are attached. A minimum R-3 thermal spacer block between the purlins and the metal roof panels is required unless compliance is shown by the overall assembly U-factor .

A2.3.2.2 Double Layer. The first rated R-value of insulation is for insulation installed perpendicular to and draped over purlins. The second rated R-value of insulation is for unfaced insulation installed above the first layer and parallel to the purlins and then compressed when the metal roof panels are attached. A minimum R-3 thermal spacer block between the purlins and the metal roof panels is required unless compliance is shown by the overall assembly U-factor .

A2.3.2.3 Continuous Insulation. For assemblies with continuous insulation the continuous insulation is installed above or below the purlins, uncompressed and uninterrupted by framing members.

A2.3.2.4 Liner System (Ls). A continuous membrane is installed below the purlins and uninterrupted by framing members. Uncompressed, unfaced insulation rests on top of the membrane between the purlins. For multilayer installations, the last rated R-Value of insulation is for unfaced insulation draped over purlins and

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 229

PDF Page 232

Open page note

then compressed when the metal roof panels are attached. A minimum R-3 thermal spacer block between the purlins and the metal roof panels is required unless compliance is shown by the overall assembly U-factor .

A2.3.2.5 Filled Cavity. The first rated R-value of insulation represents faced or unfaced insulation installed between the purlins. The second rated R-value of insulation represents unfaced insulation installed above the first layer, perpendicular to the purlins and compressed when the metal roof panels are attached. A supporting structure retains the bottom of the first layer at the prescribed depth required for the full thickness of insulation. A minimum R-5 thermal spacer block between the purlins and the metal roof panels is required unless compliance is shown by the overall assembly U-factor .

A2.3.3 U-Factors for Metal Building Roofs. U-factors for metal building roofs shall be taken from Table A2.3.3 or determined in accordance with Section A9.2, provided the average purlin spacing for systems with compressed insulation is at least 52 in. U-factors for metal building roof assemblies with average purlin spacing less than 52 in. shall be determined in accordance with Section A9.2. U-factors in Table A2.3.3 shall not be used where the insulation is substantially compressed by the bracing between the purlins.

A2.4 Attic Roofs with Wood Joists

A2.4.1 General. For the purpose of Section A1.2, the base attic roof assembly is a roof with nominal 4 in. deep wood as the lower chord of a roof truss or ceiling joist. The ceiling is attached directly to the lower chord of the truss, and the attic space above is ventilated. Insulation is located directly on top of the ceiling, first filling the cavities between the wood and later covering both the wood and cavity areas. No credit is given for roofing materials. The single-rafter roof is similar to the base attic roof, with the key difference being that there is a single, deep rafter to which both the roof and the ceiling are attached. The heat flow path through the rafter is calculated to be the same depth as the insulation. Additional assemblies include continu- ous insulation uncompressed and uninterrupted by framing. The U-factors include R-0.46 for semiexterior air film, R-0.56 for 0.625 in. gypsum board, and R-0.61 for interior air film heat flow up. U-factors are provided for the following configurations:

a. Attic roof, standard framing: Insulation is tapered around the perimeter with a resultant decrease in ther-

mal resistance . Weighting factors are 85% full-depth insulation, 5% half-depth insulation, and 10% joists. b. Attic roof, advanced framing: Full and even depth of insulation extending to the outside edge of walls .

Weighting factors are 90% full-depth insulation and 10% joists. c. Single-rafter roof : An attic roof where the roof sheathing and ceiling are attached to the same rafter.

Weighting factors are 90% full-depth insulation and 10% joists.

A2.4.2 Rated R-Value of Insulation

A2.4.2.1 For attics and other roofs, the rated R-value of insulation is for insulation installed both inside and outside the roof or entirely inside the roof cavity.

A2.4.2.2 Occasional interruption by framing members is allowed but requires that the framing members be covered with insulation when the depth of the insulation exceeds the depth of the framing cavity.

A2.4.2.3 Insulation in such roofs shall be permitted to be tapered at the eaves where the building struc- ture does not allow full depth.

A2.4.2.4 For single-rafter roofs, the requirement is the lesser of the values for attics and other roofs and those listed in Table A2.4.2.

A2.4.3 U-Factors for Attic Roofs with Wood Joists. U-factors for attic roofs with wood joists shall be taken from Table A2.4.3. It is not acceptable to use these U-factors if the framing is not wood. For attic roofs with steel j oists , see Secti on A2.5.

A2.5 Attic Roofs with Steel Joists

A2.5.1 General. For the purpose of Section A1.2, the base assembly is a roof supported by steel joists with insulation between the joists. The assembly represents a roof in many ways similar to a roof with insu- lation entirely above deck and a metal building roof . It is distinguished from the metal building roof category in that there is no metal exposed to the exterior. It is distinguished from the roof with insulation entirely above deck in that the insulation is located below the deck and is interrupted by metal trusses that provide thermal bypasses to the insulation. The U-factors include R-0.17 for exterior air film, R-0 for metal deck, and R-0.61 for interior air film heat flow up. The performance of the insulation/framing layer is calculated using the values in Table A9.2-1.

A2.5.2 U-factors for attic roofs with steel joists shall be taken from Table A2.5.2. It is acceptable to use these U-factors for any attic roof with steel joists .

A2.5.3 U-factors for attic roofs constructed of cold-formed-steel conventional C-shape framing or coldformed steel trusses, where the insulation is located at the ceiling joist or the bottom chord, and where the framing spacing does not exceed 24 in. on-center, shall be determined in accordance with AISI S250.

230 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 233

Open page note

Table A2.2.3 Assembly U-Factors for Roofs with Insulation Entirely Above Deck

Rated R-Value of Insulation AloneOverall U-Factor for Entire Assembly
R-0U-1.282
R-1U-0.562
R-2U-0.360
R-3U-0.265
R-4U-0.209
R-5U-0.173
R-6U-0.147
R-7U-0.129
R-8U-0.114
R-9U-0.102
R-10U-0.093
R-11U-0.085
R-12U-0.078
R-13U-0.073
R-14U-0.068
R-15U-0.063
R-16U-0.060
R-17U-0.056
R-18U-0.053
R-19U-0.051
R-20U-0.048
R-21U-0.046
R-22U-0.044
R-23U-0.042
R-24U-0.040
R-25U-0.039
R-26U-0.037
R-27U-0.036
R-28U-0.035
R-29U-0.034
R-30U-0.032
R-35U-0.028
R-40U-0.025
R-45U-0.022
R-50U-0.020
R-55U-0.018
R-60U-0.016

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 231

PDF Page 234

Open page note

Table A2.3.3 Assembly U-Factors for Metal Building Roofs

Insulation
System
Rated
R-Value of
Insulation
Overall
U-Factor
for Entire
Base Roof
Assembly
Overall U-Factor for Assembly of Base Roof Plus Continuous Insulation
(Uninterrupted by Framing)
Col5Col6Col7Col8Col9Col10Col11Col12
Insulation
System
Rated
R-Value of
Insulation
Overall
U-Factor
for Entire
Base Roof
Assembly
Rated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous Insulation
Insulation
System
Rated
R-Value of
Insulation
Overall
U-Factor
for Entire
Base Roof
Assembly
R-6.5
R-9.8
R-13
R-15.8
R-19
R-22.1R-25R-32R-38
Single layerNone1.2800.1370.0950.0730.0600.0510.0440.0390.0310.026
Single layerR-100.1150.0660.0540.0460.0410.0360.0320.0300.0250.021
Single layerR-110.1070.0630.0520.0450.0400.0350.0320.0290.0240.021
Single layerR-130.1010.0610.0510.0440.0390.0350.0310.0290.0240.021
Single layerR-160.0960.0590.0490.0430.0380.0340.0310.0280.0240.021
Single layerR-190.0820.0530.0450.0400.0360.0320.0290.0270.0230.020
Double layerR-10 + R-100.0880.0560.0470.0410.0370.0330.0300.0280.0230.020
Double layerR-10 + R-110.0860.0550.0470.0410.0360.0330.0300.0270.0230.020
Double layerR-11 + R-110.0850.0550.0460.0400.0360.0330.0300.0270.0230.020
Double layerR-10 + R-130.0840.0540.0460.0400.0360.0320.0290.0270.0230.020
Double layerR-11 + R-130.0820.0530.0450.0400.0360.0320.0290.0270.0230.020
Double layerR-13 + R-130.0750.0500.0430.0380.0340.0310.0280.0260.0220.019
Double layerR-10 + R-190.0740.0500.0430.0380.0340.0310.0280.0260.0220.019
Double layerR-11 + R-190.0720.0490.0420.0370.0340.0300.0280.0260.0220.019
Double layerR-13 + R-190.0680.0470.0410.0360.0330.0300.0270.0250.0210.019
Double layerR-16 + R-190.0650.0460.0400.0350.0320.0290.0270.0250.0210.019
Double layerR-19 + R-190.0600.0430.0380.0340.0310.0280.0260.0240.0210.018
Liner systemR-19 + R-110.037
Liner systemR-25 + R-80.0370.0370.0370.0370.0370.0370.0370.0370.0370.037
Liner systemR-25 + R-110.0310.0310.0310.0310.0310.0310.0310.0310.0310.031
Liner systemR-30 + R-110.0290.0290.0290.0290.0290.0290.0290.0290.0290.029
Liner systemR-25 + R-11 + R-110.0260.0260.0260.0260.0260.0260.0260.0260.0260.026

Filled Cavity with Thermal Spacer Blocks [c]

Col1R-10 + R-190.0410.0320.0290.0270.0250.0230.0220.0200.0180.016
R-19 + R-110.037

Standing Seam Roofs without Thermal Spacer Blocks

Liner system R-19 + R-11 0.040

Through-Fastened Roofs without Thermal Spacer Blocks

Col1R-100.1840.0840.0660.0540.0470.0410.0360.0330.0270.023
R-110.1820.0830.0650.0540.0470.0410.0360.0330.0270.023
R-130.1740.0820.0640.0530.0460.0400.0360.0330.0260.023
R-160.1570.0780.0620.0520.0450.0390.0350.0320.0260.023
R-190.1510.0760.0610.0510.0450.0390.0350.0320.0260.022
Liner systemR-19+R-110.044

(Multiple R-values are listed in order from inside to outside)

a. A standing seam roof clip that provides a minimum 1.5 in. distance between the top of the purlins and the underside of the metal roof panels is required. b. A minimum R-3 thermal spacer block is required. c. A minimum R-5 thermal spacer block is required.

232 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 235

Open page note

Table A2.4.2 Single-Rafter Roofs

Climate ZoneMinimum Insulation R-Value or Maximum Assembly U-FactorCol3Col4
Climate ZoneWood Rafter Depth,****d (Actual)Wood Rafter Depth,****d (Actual)Wood Rafter Depth,****d (Actual)
Climate Zoned 8 in.8 < d** 10 in.**10 < d** 12 in.**
0 to 7R-19/U-0.055R-30/U-0.036R-38/U-0.028
8R-21/U-0.052R-30/U-0.036R-38/U-0.028

Table A2.4.3 Assembly U-Factors for Attic Roofs with Wood Joists

Rated R-Value of Insulation AloneOverall U-Factor for Entire AssemblyCol3Col4Col5
Wood-Framed Attic, Standard FramingWood-Framed Attic, Standard FramingWood-Framed Attic, Standard FramingWood-Framed Attic, Standard FramingWood-Framed Attic, Standard Framing
NoneU-0.613U-0.613U-0.613U-0.613
R-11U-0.091U-0.091U-0.091U-0.091
R-13U-0.081U-0.081U-0.081U-0.081
R-19U-0.053U-0.053U-0.053U-0.053
R-30U-0.034U-0.034U-0.034U-0.034
R-38U-0.027U-0.027U-0.027U-0.027
R-49U-0.021U-0.021U-0.021U-0.021
R-60U-0.017U-0.017U-0.017U-0.017
R-71U-0.015U-0.015U-0.015U-0.015
R-82U-0.013U-0.013U-0.013U-0.013
R-93U-0.011U-0.011U-0.011U-0.011
R-104U-0.010U-0.010U-0.010U-0.010
R-115U-0.009U-0.009U-0.009U-0.009
R-126U-0.008U-0.008U-0.008U-0.008
Wood-Framed Attic, Advanced FramingWood-Framed Attic, Advanced FramingWood-Framed Attic, Advanced FramingWood-Framed Attic, Advanced FramingWood-Framed Attic, Advanced Framing
NoneU-0.613U-0.613U-0.613U-0.613
R-11U-0.088U-0.088U-0.088U-0.088
R-13U-0.078U-0.078U-0.078U-0.078
R-19U-0.051U-0.051U-0.051U-0.051
R-30U-0.032U-0.032U-0.032U-0.032
R-38U-0.026U-0.026U-0.026U-0.026
R-49U-0.020U-0.020U-0.020U-0.020
R-60U-0.016U-0.016U-0.016U-0.016
R-71U-0.014U-0.014U-0.014U-0.014
R-82U-0.012U-0.012U-0.012U-0.012
R-93U-0.011U-0.011U-0.011U-0.011
R-104U-0.010U-0.010U-0.010U-0.010
R-115U-0.009U-0.009U-0.009U-0.009
R-126U-0.008U-0.008U-0.008U-0.008
Wood Joists, Single-Rafter RoofWood Joists, Single-Rafter RoofWood Joists, Single-Rafter RoofWood Joists, Single-Rafter RoofWood Joists, Single-Rafter Roof
Cavity Insulation R-ValueOverall U-Factor for Assembly of Base Roof Plus Continuous Insulation (Uninterrupted by Framing)Overall U-Factor for Assembly of Base Roof Plus Continuous Insulation (Uninterrupted by Framing)Overall U-Factor for Assembly of Base Roof Plus Continuous Insulation (Uninterrupted by Framing)Overall U-Factor for Assembly of Base Roof Plus Continuous Insulation (Uninterrupted by Framing)
Cavity Insulation R-ValueRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous Insulation
Cavity Insulation R-ValueNoneR-5R-10R-15
NoneU-0.417U-0.135U-0.081U-0.057
R-11U-0.088U-0.061U-0.047U-0.038
R-13U-0.078U-0.056U-0.044U-0.036
R-15U-0.071U-0.052U-0.041U-0.034
R-19U-0.055U-0.043U-0.035U-0.030
R-21U-0.052U-0.041U-0.034U-0.029
R-25U-0.042U-0.035U-0.030U-0.026
R-30U-0.036U-0.030U-0.026U-0.023
R-38U-0.029U-0.025U-0.022U-0.020

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 233

PDF Page 236

Open page note

Table A2.5.2 Assembly U-Factors for Attic Roofs with Steel Joists (4.0 ft on Center)

Rated R-Value of Insulation AloneOverall U-Factor for Entire Assembly
R-0U-1.282
R-4U-0.215
R-5U-0.179
R-8U-0.120
R-10U-0.100
R-11U-0.093
R-12U-0.086
R-13U-0.080
R-15U-0.072
R-16U-0.068
R-19U-0.058
R-20U-0.056
R-21U-0.054
R-24U-0.049
R-25U-0.048
R-30U-0.041
R-35U-0.037
R-38U-0.035
R-40U-0.033
R-45U-0.031
R-50U-0.028
R-55U-0.027

234 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 237

Open page note

A3. ABOVE-GRADE WALLS

A3.1 Mass Wall

A3.1.1 General. For the purpose of Section A1.2, the base assembly is a masonry or concrete wall . Con- tinuous insulation is installed on the interior or exterior or within the masonry units, or it is installed on the interior or exterior of the concrete. The brick cavity wall has continuous insulation between the brick and the concrete or masonry. The U-factors include R-0.17 for exterior air film and R-0.68 for interior air film, vertical surfaces. For insulated walls, the U-factor also includes R-0.45 for 0.5 in. gypsum board. For the cavity wall, the U-factor includes R-0.74 for brick. U-factors are provided for the following configurations:

a. Concrete wall : 8 in. normal weight concrete wall with a density of 145 lb/ft [3] . b. Solid grouted concrete block wall : 8 in. medium weight ASTM C90 concrete block with a density of 115

lb/ft [3 ] and solid grouted cores. c. Partially grouted concrete block wall : 8 in. medium weight ASTM C90 concrete block with a density of

115 lb/ft [3] having reinforcing steel every 32 in. vertically and every 48 in. horizontally, with cores grouted in those areas only. Other cores are filled with insulating material only if there is no other insulation.

A3.1.2 Mass Wall Rated R-Value of Insulation

A3.1.2.1 Mass wall HC shall be determined from Table A3.1-2 or A3.1-3. A3.1.2.2 The rated R-value of insulation is for continuous insulation uninterrupted by framing other than 20 gage 1 in. metal clips spaced no closer than 24 in. on center horizontally and 16 in. on center vertically. A3.1.2.3 Where other framing, including metal and wood studs, is used, compliance shall be based on the maximum assembly U-factor .

A3.1.2.4 Where rated R-value of insulation is used for concrete sandwich panels, the insulation shall be continuous throughout the entire panel.

A3.1.3 Mass Wall U-Factor

A3.1.3.1 U-factors for mass walls shall be taken from Table A3.1-1 or determined by the procedure in this subsection. It is acceptable to use the U-factors in Table A3.1-1 for all mass walls, provided that the grouting is equal to or less than that specified. HC for mass walls shall be taken from Table A3.1-2 or A3.1-3.

A3.1.3.2 Determination of Mass Wall U-Factors. If not taken from Table A3.1-1, mass wall U-factors shall be determined from Tables A3.1-2, A3.1-3, or A3.1-4 using the following procedure:

a. If the mass wall is uninsulated or only the cells are insulated:

  1. For concrete walls, determine the U-factor from Table A3.1-2 based on the concrete density and wall thickness.

  2. For concrete block walls, determine the U-factor from Table A3.1-3 based on the block size, concrete density, degree of grouting in the cells, and whether the cells are insulated. b. If the mass wall has additional insulation:

  3. For concrete walls, determine the Ru from Table A3.1-2 based on the concrete density and wall thickness. Next, determine the effective R-value for the insulation/framing layer from Table A3.1-4 based on the rated R-value of insulation installed, the thickness of the insulation, and whether it is installed between wood or metal framing or with no framing. Then, determine the U-factor by adding the Ru and the effective R-value together and taking the inverse of the total.

  4. For concrete block walls, determine the Ru from Table A3.1-3 based on the block size, concrete density, degree of grouting in the cells, and whether the cells are insulated. Next, determine the effective R-value for the insulation/framing layer from Table A3.1-4 based on the rated R-value of insulation installed, the thickness of the insulation, and whether it is installed between wood or metal framing or with no framing. Then, determine the U-factor by adding the Ru and the effective R-value together and taking the inverse of the total.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 235

PDF Page 238

Open page note

A3.2.2.3 Single-Layer in Cavity. The insulation is installed in the cavity between the girts, not compressed by the framing. A membrane or facing, installed separately or adhered to the insulation, is installed inside of the girts to form a continuous layer. A thermal spacer block or thermal break strip between the girts and metal wall panels is required when specified in Table A3.2.3.

A3.2.2.4 Double-Layer. The first rated R-value of insulation is for insulation installed in the cavity between the girts, not compressed by the framing. The second rated R-value of insulation is for insulation compressed between metal wall panels and the steel structure. A membrane or facing, installed separately or adhered to the insulation, is installed inside of the girts to form a continuous layer. A thermal spacer block or thermal break strip between the girts and metal wall panels is required when specified in Table A3.2.3.

A3.2.3 U-Factors for Metal Building Walls. U-factors for metal building walls shall be taken from Table A3.2.3 or determined in accordance with Section A9.2, provided the average girt spacing is at least 52 in. U-factors for metal building wall assemblies with average girt spacing less than 52 in. shall be determined in accordance with Section A9.2.

STANDARD U-VALUES FOR TYPICAL MATERIALS

A3.3.1 General. For the purpose of Section A1.2, the base assembly is a wall where the insulation is installed within the cavity of the cold-formed steel stud framing. The steel stud framing thickness is up to 54

using the values in Table A9.2-2. Additional assemblies include continuous insulation uncompressed and uninterrupted by framing.

A3.3.2 Rated R-Value of Insulation for Steel-Framed Walls

A3.3.2.1 Steel stud framing spaced at 16 in. on-center with cavities filled with 16 in. wide insulation for both 3.5 in. deep and 6.0 in. deep wall cavities serve as the basis for the R-value compliance values in Tables 5.5-0 through 5.5-8.

A3.3.2.2 The first rated R-value of insulation is for uncompressed insulation installed in the cavity between steel studs. It is acceptable for this insulation to also be continuous insulation uninterrupted by framing.

A3.3.2.3 If there are two values, the second rated R-value of insulation is for continuous insulation uninterrupted by framing, etc., to be installed in addition to the first insulation.

A3.3.2.4 Opaque mullions in spandrel glass shall be covered with insulation complying with the steel- framed wall requirements.

A3.3.3 U-Factors for Steel-Framed Walls

A3.3.3.1 U-factors for steel-framed walls shall be determined from one of the following methods:

a. Table A3.3.3.1 b. Testing or calculation methods listed in Section A9.2(b)(3)

A3.3.3.2 Where steel-framed wall framing is spaced greater than 24 in. on center, the U-factor shall be permitted to be determined based on the 24 in. on-center spacing options from Section A3.3.3.1 or based on ASTM C1363 testing at the actual frame spacing used.

A3.3.3.3 Where steel framed wall assemblies contain no cavity insulation, and where the building enve- lope assembly uses continuous insulation to satisfy the minimum R-value for the relevant climate zone in Tables 5.5-0 through 5.5-8, the on-center framing spacing is permitted to be at any dimension.

A3.4 Wood-Framed Walls

A3.4.1 General. For the purpose of Section A1.2, the base assembly is a wall where the insulation is installed between 2 in. nominal wood framing. Cavity insulation is full depth, but values are taken from Table A9.4.3 for R-19 insulation, which is compressed when installed in a 5.5 in. cavity. Headers are double 2 in. nominal wood framing. The U-factors include R-0.17 for exterior air film, R-0.08 for stucco, R-0.56 for 0.625 in. gypsum board on the exterior, R-0.56 for 0.625 in. gypsum board on the interior, and R-0.68 for interior air film, vertical surfaces. Additional assemblies include continuous insulation uncompressed and uninterrupted by framing. U-factors are provided for the following configurations:

a. Standard framing: Wood framing at 16 in. on center with cavities filled w ith 14.5 in. wide insulation for

both 3.5 in. deep and 5.5 in. deep wall cavities. Double headers leave no cavity. Weighting factors are 75% insulated cavity, 21% studs, plates, and sills, and 4% headers.

236 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 239

Open page note

b. Advanced framing: Wood framing at 24 in. on center with cavities filled with 22.5 in. wide insulation for

both 3.5 in. deep and 5.5 in. deep wall cavities. Double headers leave uninsulated cavities. Weighting factors are 78% insulated cavity, 18% studs, plates, and sills, and 4% headers. c. Advanced framing with insulated headers: Wood framing at 24 in. on center with cavities filled with 22.5

in. wide insulation for both 3.5 in. deep and 5.5 in. deep wall cavities. Double header cavities are insulated. Weighting factors are 78% insulated cavity, 18% studs, plates, and sills, and 4% headers.

A3.4.2 Rated R-Value of Insulation for Wood-Framed and Other Walls

A3.4.2.1 The first rated R-value of insulation is for uncompressed insulation installed in the cavity between wood studs. It is acceptable for this insulation to also be continuous insulation uninterrupted by framing.

A3.4.2.2 If there are two values, the second rated R-value of insulation is for continuous insulation uninterrupted by framing, etc., to be installed in addition to the first insulation.

A3.4.3 U-Factors for Wood-Framed Walls

A3.4.3.1 U-factors for wood-framed walls shall be taken from Table A3.4.3.1. A3.4.3.2 For wood-framed walls with framing at less than 24 in. on center, use the standard framing values as described in Section A3.4.1(a).

A3.4.3.3 For wood-framed walls with framing from 24 to 32 in. on center, use the advanced framing values as described in Section A3.4.1(b) if the headers are uninsulated, or the advanced framing with insulated header values as described in Section A3.4.1(c) if the headers are insulated.

A3.4.3.4 For wood-framed walls with framing greater than 32 in. on center, U-factors shall be determined in accordance with Section A9.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 237

PDF Page 240

Open page note

Table A3.1-1 Assembly U-Factors for Above-Grade Concrete Walls and Masonry Walls

Framing Type
and Depth
Rated R-Value of
Insulation Alone
Assembly U-Factors
for 8 in. Normal Weight
145 lb/ft3 Solid Concrete Walls
Assembly U-Factors for 8 in.
Medium Weight 115 lb/ft3
Concrete Block Walls: Solid
Grouted
Assembly U-Factors for
8 in. Medium Weight
115 lb/ft3 Concrete Block
Walls: Partially Grouted
(Cores Uninsulated Except
Where Specified)
No FramingR-0U-0.740U-0.580U-0.480
No FramingUngrouted Cores
Filled with
Loose-Fill Insulation
NANAU-0.350

Continuous Metal Framing at 24 in. on Center Horizontally

1.0 in.R-0U-0.414U-0.359U-0.318
1.0 in.R-3.8U-0.325U-0.290U-0.263
1.0 in.R-5U-0.314U-0.281U-0.255
1.0 in.R-6.5U-0.305U-0.274U-0.249
1.5 in.R-11U-0.267U-0.243U-0.223
2.0 in.R-7.6U-0.230U-0.212U-0.197
2.0 in.R-10U-0.219U-0.202U-0.188
2.0 in.R-13U-0.210U-0.195U-0.182
3.0 in.R-11.4U-0.178U-0.167U-0.157
3.0 in.R-15U-0.168U-0.158U-0.149
3.0 in.R-19.0U-0.161U-0.152U-0.144
3.5 in.R-11.0U-0.168U-0.158U-0.149
3.5 in.R-13.0U-0.161U-0.152U-0.144
3.5 in.R-15.0U-0.155U-0.147U-0.140
4.5 in.R-17.1U-0.133U-0.126U-0.121
4.5 in.R-22.5U-0.124U-0.119U-0.114
4.5 in.R-25.2U-0.122U-0.116U-0.112
5.0 in.R-19.0U-0.122U-0.117U-0.112
5.0 in.R-25.0U-0.115U-0.110U-0.106
5.0 in.R-28.0U-0.112U-0.107U-0.103
5.0 in.R-32.0U-0.109U-0.105U-0.101
5.5 in.R-19.0U-0.118U-0.113U-0.109
5.5 in.R-20.9U-0.114U-0.109U-0.105
5.5 in.R-21.0U-0.113U-0.109U-0.105
5.5 in.R-27.5U-0.106U-0.102U-0.099
5.5 in.R-30.8U-0.104U-0.100U-0.096
6.0 in.R-22.8U-0.106U-0.102U-0.098
6.0 in.R-30.0U-0.099U-0.095U-0.092
6.0 in.R-33.6U-0.096U-0.093U-0.090
6.5 in.R-24.7U-0.099U-0.096U-0.092
7.0 in.R-26.6U-0.093U-0.090U-0.087
7.5 in.R-28.5U-0.088U-0.085U-0.083
8.0 in.R-30.4U-0.083U-0.081U-0.079

238 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 241

Open page note

Table A3.1-1 Assembly U-Factors for Above-Grade Concrete Walls and Masonry Walls (Continued)

Framing Type
and Depth
Rated R-Value of
Insulation Alone
Assembly U-Factors
for 8 in. Normal Weight
145 lb/ft3 Solid Concrete Walls
Assembly U-Factors for 8 in.
Medium Weight 115 lb/ft3
Concrete Block Walls: Solid
Grouted
Assembly U-Factors for
8 in. Medium Weight
115 lb/ft3 Concrete Block
Walls: Partially Grouted
(Cores Uninsulated Except
Where Specified)
No FramingR-0U-0.740U-0.580U-0.480
No FramingUngrouted Cores
Filled with
Loose-Fill Insulation
NANAU-0.350

1 in. Metal Clips at 24 in. on Center Horizontally and 16 in. Vertically

1.0 in.R-3.8U-0.210U-0.195U-0.182
1.0 in.R-5.0U-0.184U-0.172U-0.162
1.0 in.R-5.6U-0.174U-0.163U-0.154
1.5 in.R-5.7U-0.160U-0.151U-0.143
1.5 in.R-7.5U-0.138U-0.131U-0.125
1.5 in.R-8.4U-0.129U-0.123U-0.118
2.0 in.R-7.6U-0.129U-0.123U-0.118
2.0 in.R-10.0U-0.110U-0.106U-0.102
2.0 in.R-11.2U-0.103U-0.099U-0.096
2.5 in.R-9.5U-0.109U-0.104U-0.101
2.5 in.R-12.5U-0.092U-0.089U-0.086
2.5 in.R-14.0U-0.086U-0.083U-0.080
3.0 in.R-11.4U-0.094U-0.090U-0.088
3.0 in.R-15.0U-0.078U-0.076U-0.074
3.0 in.R-16.8U-0.073U-0.071U-0.069
3.5 in.R-13.3U-0.082U-0.080U-0.077
3.5 in.R-17.5U-0.069U-0.067U-0.065
3.5 in.R-19.6U-0.064U-0.062U-0.061
4.0 in.R-15.2U-0.073U-0.071U-0.070
4.0 in.R-20.0U-0.061U-0.060U-0.058
4.0 in.R-22.4U-0.057U-0.056U-0.054
5.0 in.R-28.0U-0.046U-0.046U-0.045
6.0 in.R-33.6U-0.039U-0.039U-0.038
7.0 in.R-39.2U-0.034U-0.034U-0.033
8.0 in.R-44.8U-0.030U-0.030U-0.029
9.0 in.R-50.4U-0.027U-0.027U-0.026
10.0 in.R-56.0U-0.024U-0.024U-0.024
11.0 in.R-61.6U-0.022U-0.022U-0.022

Continuous Insulation Uninterrupted by Framing

No framingR-1.0U-0.425U-0.367U-0.324
No framingR-2.0U-0.298U-0.269U-0.245
No framingR-3.0U-0.230U-0.212U-0.197
No framingR-4.0U-0.187U-0.175U-0.164

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 239

PDF Page 242

Open page note

Table A3.1-1 Assembly U-Factors for Above-Grade Concrete Walls and Masonry Walls (Continued)

Framing Type
and Depth
Rated R-Value of
Insulation Alone
Assembly U-Factors
for 8 in. Normal Weight
145 lb/ft3 Solid Concrete Walls
Assembly U-Factors for 8 in.
Medium Weight 115 lb/ft3
Concrete Block Walls: Solid
Grouted
Assembly U-Factors for
8 in. Medium Weight
115 lb/ft3 Concrete Block
Walls: Partially Grouted
(Cores Uninsulated Except
Where Specified)
No FramingR-0U-0.740U-0.580U-0.480
No FramingUngrouted Cores
Filled with
Loose-Fill Insulation
NANAU-0.350
No framingR-5.0U-0.157U-0.149U-0.141
No framingR-6.0U-0.136U-0.129U-0.124
No framingR-7.0U-0.120U-0.115U-0.110
No framingR-8.0U-0.107U-0.103U-0.099
No framingR-9.0U-0.097U-0.093U-0.090
No framingR-10.0U-0.088U-0.085U-0.083
No framingR-11.0U-0.081U-0.079U-0.076
No framingR-12.0U-0.075U-0.073U-0.071
No framingR-13.0U-0.070U-0.068U-0.066
No framingR-14.0U-0.065U-0.064U-0.062
No framingR-15.0U-0.061U-0.060U-0.059
No framingR-16.0U-0.058U-0.056U-0.055
No framingR-17.0U-0.054U-0.053U-0.052
No framingR-18.0U-0.052U-0.051U-0.050
No framingR-19.0U-0.049U-0.048U-0.047
No framingR-20.0U-0.047U-0.046U-0.045
No framingR-21.0U-0.045U-0.044U-0.043
No framingR-22.0U-0.043U-0.042U-0.042
No framingR-23.0U-0.041U-0.040U-0.040
No framingR-24.0U-0.039U-0.039U-0.038
No framingR-25.0U-0.038U-0.037U-0.037
No framingR-30.0U-0.032U-0.032U-0.031
No framingR-35.0U-0.028U-0.027U-0.027
No framingR-40.0U-0.024U-0.024U-0.024
No framingR-45.0U-0.022U-0.021U-0.021
No framingR-50.0U-0.019U-0.019U-0.019
No framingR-55.0U-0.018U-0.018U-0.018
No framingR-60.0U-0.016U-0.016U-0.016

Brick Cavity Wall with Continuous Insulation

No framingR-0U-0.337U-0.299U-0.270
No framingR-3.8U-0.148U-0.140U-0.133
No framingR-5.0U-0.125U-0.120U-0.115
No framingR-6.5U-0.106U-0.102U-0.098
No framingR-7.6U-0.095U-0.091U-0.088

240 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 243

Open page note

Table A3.1-1 Assembly U-Factors for Above-Grade Concrete Walls and Masonry Walls (Continued)

Framing Type
and Depth
Rated R-Value of
Insulation Alone
Assembly U-Factors
for 8 in. Normal Weight
145 lb/ft3 Solid Concrete Walls
Assembly U-Factors for 8 in.
Medium Weight 115 lb/ft3
Concrete Block Walls: Solid
Grouted
Assembly U-Factors for
8 in. Medium Weight
115 lb/ft3 Concrete Block
Walls: Partially Grouted
(Cores Uninsulated Except
Where Specified)
No FramingR-0U-0.740U-0.580U-0.480
No FramingUngrouted Cores
Filled with
Loose-Fill Insulation
NANAU-0.350
No framingR-10U-0.077U-0.075U-0.073
No framingR-10.5U-0.079U-0.077U-0.075
No framingR-11.4U-0.070U-0.068U-0.066
No framingR-15U-0.056U-0.055U-0.053
No framingR-16.5U-0.054U-0.053U-0.052
No framingR-19.0U-0.046U-0.045U-0.044
No framingR-22.5U-0.041U-0.040U-0.039
No framingR-28.5U-0.033U-0.032U-0.032

Continuous Insulation Uninterrupted by Framing with Stucco and Continuous Metal Framing at 24 in. on Center Horizontally

1.0 in.R-0+R-19.0 c.i.U-0.047U-0.046U-0.045
1.0 in.R-3.8+R-19.0_c.i._U-0.045U-0.044U-0.044
1.0 in.R-5+R-19.0_c.i._U-0.045U-0.044U-0.043
1.0 in.R-6.5+R-19.0_c.i._U-0.045U-0.044U-0.043
1.5 in.R-11+R-19.0_c.i._U-0.044U-0.043U-0.043
2.0 in.R-7.6+R-19.0_c.i._U-0.043U-0.042U-0.041
2.0 in.R-10+R-19.0_c.i._U-0.042U-0.041U-0.041
2.0 in.R-13+R-19.0_c.i._U-0.042U-0.041U-0.041
3.0 in.R-11.4+R-19.0_c.i._U-0.041U-0.040U-0.039
3.0 in.R-15+R-19.0_c.i._U-0.040U-0.039U-0.039
3.0 in.R-19.5+R-19.0_c.i._U-0.040U-0.039U-0.038
3.5 in.R-11.0+R-19.0_c.i._U-0.040U-0.039U-0.039
3.5 in.R-13.0+R-19.0_c.i._U-0.040U-0.039U-0.038
5.0 in.R-19.0+R-19.0_c.i._U-0.037U-0.036U-0.036
5.0 in.R-25+R-19.0_c.i._U-0.036U-0.035U-0.035
5.0 in.R-32.5+R-19.0_c.i._U-0.035U-0.035U-0.034
5.5 in.R-19.0+R-19.0_c.i._U-0.036U-0.036U-0.035
5.5 in.R-21.0+R-19.0_c.i._U-0.035U-0.035U-0.035

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 241

PDF Page 244

Open page note

Table A3.1-2 Assembly U-Factors, C-Factors, Ru , Rc , and HC for Concrete

Density, lb/ft3PropertiesThickness, in.Col4Col5Col6Col7Col8Col9Col10Col11Col12
Density, lb/ft3Properties3456789101112
20U-factor0.220.170.140.120.100.090.080.070.070.06
20C-factor0.270.200.160.130.110.100.090.080.070.07
20Ru4.605.857.108.359.6010.8512.1013.3514.6015.85
20Rc3.755.006.257.508.7510.0011.2512.5013.7515.00
20HC1.01.31.72.02.32.73.03.33.74.0
30U-factor0.280.220.190.160.140.120.110.100.090.09
30C-factor0.370.280.220.180.160.140.120.110.100.09
30Ru3.584.495.406.307.218.129.039.9410.8511.76
30Rc2.733.644.555.456.367.278.189.0910.0010.91
30HC1.52.02.53.03.54.04.55.05.56.0
40U-factor0.330.270.230.190.170.150.140.130.110.11
40C-factor0.470.350.280.230.200.180.160.140.130.12
40Ru2.993.714.425.145.856.567.287.998.719.42
40Rc2.142.863.574.295.005.716.437.147.868.57
40HC2.02.73.34.04.75.36.06.77.38.0
50U-factor0.380.310.260.230.200.180.160.150.140.13
50C-factor0.570.430.340.280.240.210.190.170.150.14
50Ru2.613.203.794.384.975.566.146.737.327.91
50Rc1.762.352.943.534.124.715.295.886.477.06
50HC2.53.34.25.05.86.77.58.39.210.0
85U-factor0.650.560.500.440.400.370.340.310.290.27
85C-factor1.431.080.860.710.610.540.480.430.390.36
85Ru1.551.782.012.252.482.712.943.183.413.64
85Rc0.700.931.161.401.631.862.092.332.562.79
85HC4.35.77.18.59.911.312.814.215.617.0
95U-factor0.720.640.570.520.480.440.410.380.360.33
95C-factor1.851.411.120.930.800.700.620.560.510.47
95Ru1.391.561.741.922.102.282.462.642.812.99
95Rc0.540.710.891.071.251.431.611.791.962.14
95HC4.86.37.99.511.112.714.315.817.419.0
105U-factor0.790.710.650.590.540.510.470.440.420.39
105C-factor2.381.791.431.181.010.880.790.710.650.59
105Ru1.271.411.561.701.841.982.122.262.402.54
105Rc0.420.560.700.850.991.131.271.411.551.69
105HC5.37.08.810.512.314.015.817.519.321.0
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.

242 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 245

Open page note

Table A3.1-2 Assembly U-Factors, C-Factors, Ru , Rc , and HC for Concrete (Continued)

Density, lb/ft3PropertiesThickness, in.Col4Col5Col6Col7Col8Col9Col10Col11Col12
Density, lb/ft3Properties3456789101112
115U-factor0.840.770.700.650.610.570.530.500.480.45
115C-factor2.942.221.751.471.251.100.980.880.800.74
115Ru1.191.301.421.531.651.761.871.992.102.21
115Rc0.340.450.570.680.800.911.021.141.251.36
115HC5.87.79.611.513.415.317.319.221.123.0
125U-factor0.880.820.760.710.670.630.600.560.530.51
125C-factor3.572.702.171.791.541.351.201.030.980.90
125Ru1.131.221.311.411.501.591.681.781.871.96
125Rc0.280.370.460.560.650.740.830.931.021.11
125HC6.38.310.412.514.616.718.820.822.925.0
135U-factor0.930.870.820.770.730.690.660.630.600.57
135C-factor4.553.332.702.221.921.671.491.331.221.11
135Ru1.071.151.221.301.371.451.521.601.671.75
135Rc0.220.300.370.450.520.600.670.750.820.90
135HC6.89.011.313.515.818.020.322.524.827.0
144U-factor0.960.910.860.810.780.740.710.680.650.63
144C-factor5.264.003.232.632.272.001.791.591.451.33
144Ru1.041.101.161.231.291.351.411.481.541.60
144Rc0.190.250.310.380.440.500.560.630.690.75
144HC7.29.612.014.416.819.221.624.026.428.8
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.
The_U-factors_ and_Ru_ include standard air film resistances.
The_C-factors_ and_Rc_ are for the same assembly without air film resistances.
Note that the following assemblies do not qualify as a_mass wall_ or_mass floor_: 3 in. thick concrete with densities of 85, 95, 125, and 135 lb/ft3.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 243

PDF Page 246

Open page note

Table A3.1-3 Assembly U-Factors, C-Factors, Ru , Rc , and HC for Concrete Block Walls

Product Size,
in.
Density,
lb/ft3
PropertiesConcrete Block Grouting and Cell TreatmentCol5Col6Col7Col8
Product Size,
in.
Density,
lb/ft3
PropertiesSolid
Grouted
Partly Grouted,
Cells Empty
Partly Grouted,
Cells Insulated
Unreinforced,
Cells Empty
Unreinforced,
Cells Insulated
6 in. block85U-factor0.570.460.340.400.20
6 in. block85C-factor1.110.750.470.600.23
6 in. block85Ru1.752.182.972.525.13
6 in. block85Rc0.901.332.121.674.28
6 in. block85HC10.96.77.04.24.6
6 in. block95U-factor0.610.490.360.420.22
6 in. block95C-factor1.250.830.530.650.27
6 in. block95Ru1.652.062.752.384.61
6 in. block95Rc0.801.211.901.533.76
6 in. block95HC11.47.27.54.75.1
6 in. block105U-factor0.640.510.390.440.24
6 in. block105C-factor1.380.910.580.710.30
6 in. block105Ru1.571.952.562.264.17
6 in. block105Rc0.721.101.711.413.32
6 in. block105HC11.97.77.95.15.6
6 in. block115U-factor0.660.540.410.460.26
6 in. block115C-factor1.520.980.640.760.34
6 in. block115Ru1.511.872.412.163.79
6 in. block115Rc0.661.021.561.312.94
6 in. block115HC12.38.18.45.66.0
6 in. block125U-factor0.700.560.450.490.30
6 in. block125C-factor1.701.080.730.840.40
6 in. block125Ru1.441.782.232.043.38
6 in. block125Rc0.590.931.381.192.53
6 in. block125HC12.88.68.86.06.5
6 in. block135U-factor0.730.600.490.530.35
6 in. block135C-factor1.941.230.850.950.49
6 in. block135Ru1.361.672.021.902.89
6 in. block135Rc0.510.821.171.052.04
6 in. block135HC13.29.09.36.56.9
8 in. block85U-factor0.490.410.280.370.15
8 in. block85C-factor0.850.630.370.530.17
8 in. block85Ru2.032.433.552.726.62
8 in. block85Rc1.181.582.701.875.77
8 in. block85HC15.09.09.45.46.0
8 in. block95U-factor0.530.440.310.390.17
8 in. block95C-factor0.950.700.410.580.20
8 in. block95Ru1.902.293.272.575.92
8 in. block95Rc1.051.442.421.725.07
8 in. block95HC15.59.610.06.06.6

244 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 247

Open page note

Table A3.1-3 Assembly U-Factors, C-Factors, Ru , Rc , and HC for Concrete Block Walls (Continued)

Product Size,
in.
Density,
lb/ft3
PropertiesConcrete Block Grouting and Cell TreatmentCol5Col6Col7Col8
Product Size,
in.
Density,
lb/ft3
PropertiesSolid
Grouted
Partly Grouted,
Cells Empty
Partly Grouted,
Cells Insulated
Unreinforced,
Cells Empty
Unreinforced,
Cells Insulated
8 in. block105U-factor0.550.460.330.410.19
8 in. block105C-factor1.050.760.460.630.22
8 in. block105Ru1.812.173.042.445.32
8 in. block105Rc0.961.322.191.594.47
8 in. block105HC16.110.210.66.67.2
8 in. block115U-factor0.580.480.350.430.21
8 in. block115C-factor1.140.820.500.680.25
8 in. block115Ru1.722.072.842.334.78
8 in. block115Rc0.871.221.991.483.93
8 in. block115HC16.710.811.27.27.8
8 in. block125U-factor0.610.510.380.450.24
8 in. block125C-factor1.270.900.570.740.30
8 in. block125Ru1.641.962.622.204.20
8 in. block125Rc0.791.111.771.353.35
8 in. block125HC17.311.411.87.88.4
8 in. block135U-factor0.650.550.420.490.28
8 in. block135C-factor1.441.020.670.830.37
8 in. block135Ru1.541.832.352.053.55
8 in. block135Rc0.690.981.501.202.70
8 in. block135HC17.912.012.48.49.0
10 in. block85U-factor0.440.380.250.350.13
10 in. block85C-factor0.700.570.310.500.14
10 in. block85Ru2.292.614.052.847.87
10 in. block85Rc1.441.763.201.997.02
10 in. block85HC19.011.211.76.57.3
10 in. block95U-factor0.470.410.270.370.14
10 in. block95C-factor0.770.620.350.550.16
10 in. block95Ru2.152.463.732.676.94
10 in. block95Rc1.301.612.881.826.09
10 in. block95HC19.711.912.47.38.1
10 in. block105U-factor0.490.430.290.390.16
10 in. block105C-factor0.850.680.390.590.19
10 in. block105Ru2.032.333.452.546.17
10 in. block105Rc1.181.482.601.695.32
10 in. block105HC20.412.613.18.08.8
10 in. block115U-factor0.520.450.310.410.18
10 in. block115C-factor0.920.730.420.640.21
10 in. block115Ru1.942.223.212.425.52
10 in. block115Rc1.091.372.361.574.67
10 in. block115HC21.113.413.98.79.5

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 245

PDF Page 248

Open page note

Table A3.1-3 Assembly U-Factors, C-Factors, Ru , Rc , and HC for Concrete Block Walls (Continued)

Product Size,
in.
Density,
lb/ft3
PropertiesConcrete Block Grouting and Cell TreatmentCol5Col6Col7Col8
Product Size,
in.
Density,
lb/ft3
PropertiesSolid
Grouted
Partly Grouted,
Cells Empty
Partly Grouted,
Cells Insulated
Unreinforced,
Cells Empty
Unreinforced,
Cells Insulated
10 in. block125U-factor0.540.480.340.440.21
10 in. block125C-factor1.010.800.480.700.25
10 in. block125Ru1.842.102.952.284.81
10 in. block125Rc0.991.252.101.433.96
10 in. block125HC21.814.114.69.410.2
10 in. block135U-factor0.580.510.380.470.25
10 in. block135C-factor1.140.900.560.790.32
10 in. block135Ru1.721.962.642.124.00
10 in. block135Rc0.871.111.791.273.15
10 in. block135HC22.614.815.310.211.0
12 in. block85U-factor0.400.360.220.340.11
12 in. block85C-factor0.590.520.270.480.12
12 in. block85Ru2.532.774.592.939.43
12 in. block85Rc1.681.923.742.088.58
12 in. block85HC23.113.314.07.58.5
12 in. block95U-factor0.420.380.240.360.12
12 in. block95C-factor0.660.570.300.520.13
12 in. block95Ru2.302.604.222.768.33
12 in. block95Rc1.531.753.371.917.48
12 in. block95HC23.914.214.88.39.3
12 in. block105U-factor0.440.410.260.380.14
12 in. block105C-factor0.710.620.330.570.15
12 in. block105Ru2.252.473.902.627.35
12 in. block105Rc1.401.623.051.776.50
12 in. block105HC24.715.015.69.110.2
12 in. block115U-factor0.470.420.280.400.15
12 in. block115C-factor0.770.660.360.610.18
12 in. block115Ru2.152.363.632.496.54
12 in. block115Rc1.301.512.781.645.69
12 in. block115HC25.615.816.410.011.0
12 in. block125U-factor0.490.450.300.420.18
12 in. block125C-factor0.840.720.400.660.21
12 in. block125Ru2.042.233.342.365.68
12 in. block125Rc1.191.382.491.514.83
12 in. block125HC26.416.617.310.811.8
12 in. block135U-factor0.520.480.340.460.21
12 in. block135C-factor0.940.810.470.740.26
12 in. block135Ru1.912.082.982.194.67
12 in. block135Rc1.061.232.131.343.82
12 in. block135HC27.217.518.111.612.6

246 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 249

Open page note

Table A3.1-4 Effective R-Values for Insulation/Framing Layers Added to Above-Grade Mass Walls and Below-Grade Walls

Depth,

in.

Framing
Type
Col2Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22Col23Col24Col25Col26
Framing
Type
0123456789101112131415161718192021222324

Effective R-value if Continuous Insulation Uninterrupted by Framing (Includes Gypsum Board)

None 0.5 1.5 2.5 3.5 4.5 5.5 6.5 7.5 8.5 9.5 10.5 11.5 12.5 13.5 14.5 15.5 16.5 17.5 18.5 19.5 20.5 21.5 22.5 23.5 24.5 25.5

Effective R-value if Insulation is Installed in Cavity between Framing (Includes Gypsum Board)

0.5Wood1.31.31.92.42.7NANANANANANANANANANANANANANANANANANANANANA
0.5Metal0.90.91.11.11.2NANANANANANANANANANANANANANANANANANANANANA
0.75Wood1.41.42.12.73.13.53.8NANANANANANANANANANANANANANANANANANANA
0.75Metal1.01.01.31.41.51.51.6NANANANANANANANANANANANANANANANANANANA
1.0Wood1.31.52.22.93.43.94.34.64.9NANANANANANANANANANANANANANANANANA
1.0Metal1.01.11.41.61.71.81.81.91.9NANANANANANANANANANANANANANANANANA
1.5Wood1.31.52.43.13.84.44.95.45.86.26.56.87.1NANANANANANANANANANANANANA
1.5Metal1.11.21.61.92.12.22.32.42.52.52.62.62.7NANANANANANANANANANANANANA
2.0Wood1.41.52.53.34.04.75.35.96.46.97.37.78.18.48.79.09.3NANANANANANANANANA
2.0Metal1.11.21.72.12.32.52.72.82.93.03.13.23.23.33.33.43.4NANANANANANANANANA
2.5Wood1.41.52.53.44.24.95.66.36.87.47.98.48.89.29.610.010.310.610.911.211.5NANANANANA
2.5Metal1.21.31.82.32.62.83.03.23.33.53.63.63.73.83.93.94.04.04.14.14.1NANANANANA
3.0Wood1.41.52.53.54.35.15.86.57.27.88.38.99.49.910.310.711.111.511.912.212.512.9NANANANA
3.0Metal1.21.31.92.42.83.13.33.53.73.84.04.14.24.34.44.44.54.64.64.74.74.8NANANANA
3.5Wood1.41.52.63.54.45.26.06.77.48.18.79.39.810.410.911.311.812.212.613.013.413.814.114.514.815.1
3.5Metal1.21.32.02.52.93.23.53.84.04.24.34.54.64.74.84.95.05.15.15.25.25.35.45.45.45.5
4.0Wood1.41.62.63.64.55.36.16.97.68.39.09.610.210.811.311.912.412.813.313.714.214.614.915.315.716.0
4.0Metal1.21.32.02.63.03.43.74.04.24.54.64.85.05.15.25.35.45.55.65.75.85.85.95.96.06.0
4.5Wood1.41.62.63.64.55.46.27.17.88.59.29.910.511.211.712.312.813.313.814.314.815.215.716.116.516.9
4.5Metal1.21.32.12.63.13.53.94.24.54.74.95.15.35.45.65.75.85.96.06.16.26.36.46.46.56.6
5.0Wood1.41.62.63.64.65.56.37.28.08.79.410.110.811.512.112.713.213.814.314.815.315.816.316.717.217.6
5.0Metal1.21.42.12.73.23.74.14.44.75.05.25.45.65.85.96.16.26.36.56.66.76.86.86.97.07.1
5.5Wood1.41.62.63.64.65.56.47.38.18.99.610.311.011.712.413.013.614.214.715.315.816.316.817.317.818.2
5.5Metal1.31.42.12.83.33.84.24.64.95.25.45.75.96.16.36.46.66.76.87.07.17.27.37.47.57.6

PDF Page 250

Open page note

Table A3.2.3 Assembly U-Factors for Metal Building Walls

Insulation
System
Rated
R-Value of
Insulation
Overall U-Factor
for Entire Base
Wall Assembly
Overall U-Factor for Assembly of Base Wall Plus Continuous Insulation
(Uninterrupted by Framing)
Col5Col6Col7Col8Col9Col10Col11Col12
Insulation
System
Rated
R-Value of
Insulation
Overall U-Factor
for Entire Base
Wall Assembly
R-6.5R-9.8R-13R-15.8R-19R-22.1R-25R-32R-38
Continuous
insulation
only
R-01.1800.1360.0940.0720.0600.0500.0440.0390.0300.026
Single
compressed
layer
R-100.1860.0840.0660.0540.0470.0410.0360.0330.0270.023
Single
compressed
layer
R-110.1850.0840.0660.0540.0470.0410.0360.0330.0270.023
Single
compressed
layer
R-130.1620.0790.0630.0520.0460.0400.0350.0320.0260.023
Single
compressed
layer
R-160.1550.0770.0620.0510.0450.0390.0350.0320.0260.022
Single
compressed
layer
R-190.1470.0750.0600.0500.0440.0390.0350.0310.0260.022
Single layer
in cavity
R-25a0.0590.0440.0390.0350.0320.0290.0270.0250.0210.019
Single layer
in cavity
R-30b0.0520.0420.0370.0330.0310.0280.0260.0240.0210.019
Double layerR-25 + R-100.0470.0380.0340.0310.0280.0260.0240.0230.0200.018
Double layerR-25 + R-160.0420.0360.0320.0290.0270.0250.0230.0220.0190.018
Double layerR-25 + R-10c0.0390.0320.0290.0270.0250.0230.0220.0210.0180.017
Double layerR-30 + R-160.0390.0360.0320.0290.0270.0250.0230.0220.0190.017

(Multiple R-values are listed in order from inside to outside.) a. A minimum R-0.375 thermal spacer block or thermal break strip is required when installed without continuous insulation . b. A minimum R-0.75 thermal spacer block or thermal break strip is required when installed without continuous insulation . c. A minimum R-3 thermal spacer block is required.

248 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 251

Open page note

Table A3.3.3.1 Assembly U-Factors for Steel-Frame Walls

SO DE-RATE PRIOR TO ENTERING

Framing

Type

and Spacing

Width (Actual

Depth)

Cavity
Insulation
R-Value:
Rated
(Effective
Installed [see
Table A9.2-2])
Overall
U-Factor
for Entire
Base Wall
Assembly
Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22
Cavity
Insulation
R-Value:
Rated
(Effective
Installed [see
Table A9.2-2])
Overall
U-Factor
for Entire
Base Wall
Assembly
**R-1.00 ****R-2.00 ****R-3.00 ****R-4.00 ****R-5.00 ****R-6.00 **
2”
**R-6.00 **
2”
**R-8.00 **
-8.4
**R-9.00 ****R-10.00 ****R-11.00 ****R-12.00 ****R-13.00 ****R-14.00 ****R-15.00 ****R-20.00 ****R-25.00 ****R-30.00 ****R-35.00 **
Cavity
Insulation
R-Value:
Rated
(Effective
Installed [see
Table A9.2-2])
Overall
U-Factor
for Entire
Base Wall
Assembly
**R-1.00 ****R-2.00 ****R-3.00 ****R-4.00 ****R-5.00 ****R-6.00 **
2”
2”mineral: R-8.4-8.4-8.4-8.4-8.4-8.4-8.4-8.4-8.4-8.4-8.4-8.4
Cavity
Insulation
R-Value:
Rated
(Effective
Installed [see
Table A9.2-2])
Overall
U-Factor
for Entire
Base Wall
Assembly
**R-1.00 ****R-2.00 ****R-3.00 ****R-4.00 ****R-5.00 ****R-6.00 **
2”
2”**R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 ****R-7.00 **
3.5 in.
depth
None (0.0)0.3520.2600.2070.1710.1460.1280.1130.102Col110.0920.0840.0780.0720.0670.0630.0590.0560.0440.0360.0300.0260.023
3.5 in.
depth
R-11 (5.5)0.1320.1170.1050.0950.0870.0800.0740.0690.0690.0640.0600.0570.0540.0510.0490.0460.0440.0360.0310.0270.0240.021
3.5 in.
depth
R-13 (6.0)0.1240.1110.1000.0910.0830.0770.0710.0660.0660.0620.0590.0550.0520.0500.0480.0450.0430.0360.0300.0260.0230.021
3.5 in.
depth
R-15 (6.4)0.1180.1060.0960.0870.0800.0740.0690.0650.0650.0610.0570.0540.0510.0490.0470.0450.0430.0350.0300.0260.0230.021
6.0
in.depth
R-19 (7.1)0.1090.0990.0900.0820.0760.0710.0660.062
U-0
0.062
U-0
0.058
.0582
0.0550.0520.0500.0470.0450.0430.0410.0340.0290.0260.0230.020
6.0
in.depth
R-19 (7.1)0.1090.0990.0900.0820.0760.0710.0660.062
U-0

U-0

.0582

.0582

.0582

.0582

.0582

.0582

.0582

.0582

.0582

.0582

.0582

.0582

.0582
6.0
in.depth
R-21 (7.4)0.1060.0960.0870.0800.0740.0690.0650.061
0.061
0.057
0.0540.0510.0490.0470.0450.0430.0410.0340.0290.0250.0220.020

Steel Framing at 24 in. on Center

Steel Framing at 16 in. on Center

3.5 in.
depth
None (0.0)0.3380.2530.2020.1680.1440.1260.1120.1000.0910.0840.0770.0720.0670.0630.0590.0560.0440.0360.0300.0260.023
3.5 in.
depth
R-11 (6.6)0.1160.1040.0940.0860.0790.0730.0680.0640.0600.0570.0540.0510.0480.0460.0440.0420.0350.0300.0260.0230.021
3.5 in.
depth
R-13 (7.2)0.1080.0980.0890.0820.0750.0700.0660.0620.0580.0550.0520.0490.0470.0450.0430.0410.0340.0290.0250.0230.020
3.5 in.
depth
R-15 (7.8)0.1020.0920.0840.0780.0720.0670.0630.0590.0560.0530.0500.0480.0460.0440.0420.0400.0340.0290.0250.0220.020
6.0 in.
depth
R-19 (8.6)0.0940.0860.0790.0730.0680.0640.0600.0570.0540.0510.0480.0460.0440.0420.0410.0390.0330.0280.0250.0220.020
6.0 in.
depth
R-21 (9.0)0.0900.0830.0770.0710.0660.0620.0590.0550.0520.0500.0480.0450.0430.0420.0400.0380.0320.0280.0240.0220.020

PDF Page 252

Open page note

Table A3.4.3.1 Assembly U-Factors for Wood-Frame Walls

SO DE-RATE PRIOR TO ENTERING.

Framing Type and

Spacing

Width (Actual

Depth)

Cavity
Insulation
R-Value:
Rated
(Effective
Installed [see
Table A9.4.3])
Overall
U-Factor
for Entire
Base Wall
Assembly
Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21
Cavity
Insulation
** R-Value:
Rated
(Effective**
Installed [see
Table A9.4.3])
Overall
U-Factor
for Entire
Base Wall
Assembly
**R-1.00 ****R-2.00 ****R-3.00 ****R-4.00 ****R-5.00 ****R-6.00 ****R-7.00 ****R-8.00 ****R-9.00 ****R-10.00 ****R-11.00 ****R-12.00 ****R-13.00 ****R-14.00 ****R-15.00 ****R-20.00 ****R-25.00 ****R-30.00 ****R-35.00 **
Cavity
Insulation
** R-Value:
Rated
(Effective**
Installed [see
Table A9.4.3])
R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21R-21 IS 5.5” THICK AND GOES IN 5.5” STUD SO R-21
3.5 in. depthNone (0.0)0.2920.2230.1810.1520.1320.1160.1040.0940.0860.0790.0730.0680.0640.0600.0560.0530.0420.0350.0300.0260.023
3.5 in. depthR-11 (11.0)0.0960.0870.0790.0730.0680.0630.0590.0560.0530.0500.0480.0460.0440.0420.0400.0380.0320.0280.0240.0220.020
3.5 in. depthR-13 (13.0)0.0890.0800.0740.0680.0630.0590.0560.0530.0500.0470.0450.0430.0410.0400.0380.0370.0310.0270.0240.0210.019
3.5 in. depthR-15 (15.0)0.0830.0750.0690.0640.0600.0560.0530.0500.0470.0450.0430.0410.0390.0380.0360.0350.0300.0260.0230.0200.019
5.5 in.depthR-19 (18.0)0.0670.0620.0580.0540.0510.0480.0460.0440.0420.0400.0380.0370.0360.0340.0330.0320.0270.0240.0210.0190.018
5.5 in.depthR-21 (21.0)0.0630.0580.0540.0510.0480.0450.0430.0410.0390.0380.0360.0350.0340.0320.0310.0300.0260.0230.0210.0190.017
+ R-10
headers
R-19 (18.0)0.0630.0590.0550.0520.0490.0470.0450.0430.0410.0390.0380.0360.0350.0340.0330.0310.0270.0240.0210.0190.017
+ R-10
headers
R-21 (21.0)0.0590.0550.0510.0490.0460.0440.0420.0400.0380.0370.0350.0340.0330.0320.0310.0300.0260.0230.0200.0180.017

Wood Studs at 24 in. on Center

3.5 in. depthNone (0.0)0.2980.2270.1830.1540.1330.1170.1050.0950.0860.0790.0740.0680.0640.0600.0570.0540.0420.0350.0300.0260.023
3.5 in. depthR-11 (11.0)0.0940.0850.0780.0720.0670.0620.0590.0550.0520.0500.0470.0450.0430.0410.0400.0380.0320.0270.0240.0220.019
3.5 in. depthR-13 (13.0)0.0860.0780.0720.0670.0620.0580.0550.0520.0490.0470.0450.0430.0410.0390.0380.0360.0310.0260.0230.0210.019
3.5 in. depthR-15 (15.0)0.0800.0730.0670.0620.0580.0550.0520.0490.0460.0440.0420.0400.0390.0370.0360.0350.0290.0260.0230.0200.018
5.5 in. depthR-19 (18.0)0.0650.0600.0560.0530.0500.0470.0450.0430.0410.0390.0380.0360.0350.0340.0330.0320.0270.0240.0210.0190.018
5.5 in. depthR-21 (21.0)0.0600.0560.0520.0490.0460.0440.0420.0400.0380.0370.0360.0340.0330.0320.0310.0300.0260.0230.0200.0180.017
+ R-10
headers
R-19 (18.0)0.0620.0580.0540.0510.0480.0460.0440.0420.0400.0390.0370.0360.0340.0330.0320.0310.0270.0240.0210.0190.017
+ R-10
headers
R-21 (21.0)0.0570.0530.0500.0470.0450.0430.0410.0390.0370.0360.0350.0330.0320.0310.0300.0290.0250.0230.0200.0180.017

PDF Page 253

Open page note

A4. BELOW-GRADE WALLS

A4.1 General. For the purpose of Section A1.2, the base assembly is 8 in. medium-weight concrete block with a density of 115 lb/ft [3] and solid grouted cores. Continuous insulation is installed on the interior or exterior. In contrast to the U-factor for above-grade walls, the C-factor for below-grade walls does not include R-values for exterior or interior air films or for soil. For insulated walls, the C-factor does include R-0.45 for 0.5 in. gypsum board.

A4.2 C-Factors for Below-Grade Walls

A4.2.1 C-factors for below-grade walls shall be taken from Table A4.2.1 or determined by the procedure described in this subsection.

A4.2.2 It is acceptable to use the C-factors in Table A4.2.1 for all below-grade walls . A4.2.3 If not taken from Table A4.2.1, below-grade wall C-factors shall be determined from Table A3.1-3, A3.1-2, or A3.1-4 using the following procedure:

a. If the below-grade wall is uninsulated or only the cells are insulated:

  1. For concrete walls, determine the C-factor from Table A3.1-2 based on the concrete density and wall thickness.

  2. For concrete block walls, determine the C-factor from Table A3.1-3 based on the block size, concrete density, degree of grouting in the cells, and whether the cells are insulated. b. If the mass wall has additional insulation:

  3. For concrete walls, determine the Rc from Table A3.1-2 based on the concrete density and wall thickness. Next, determine the effective R-value for the insulation/framing layer from Table A3.1-3 based on the rated R-value of insulation installed, the thickness of the insulation, and whether it is installed between wood or metal framing or with no framing. Then determine the C-factor by adding the Rc and the effective R-value together and taking the inverse of the total.

  4. For concrete block walls, determine the Rc from Table A3.1-3 based on the block size, concrete density, degree of grouting in the cells, and whether the cells are insulated. Next, determine the effective R-value for the insulation/framing layer from Table A3.1-4 based on the rated R-value of insulation installed, the thickness of the insulation, and whether it is installed between wood or metal framing or with no framing. Then determine the C-factor by adding the Rc and the effective R-value together and taking the inverse of the total.

A5. FLOORS

A5.1 General. The buffering effect of crawlspaces or parking garages shall not be included in U-factor calculations. See Section A6 for slab-on-grade floors .

A5.2 Mass Floors

A5.2.1 General. For the purpose of Section A1.2, the base assembly is continuous insulation over or under a solid concrete floor . The U-factors include R-0.92 for interior air film, heat flow down; R-1.23 for carpet and rubber pad; R-0.50 for 8 in. concrete; and R-0.46 for semiexterior air film. Added insulation is continuous and uninterrupted by framing. Framing factor is zero.

A5.2.2 Rated R-Value of Insulation for Mass Floors

A5.2.2.1 The rated R-value of insulation is for continuous insulation uninterrupted by framing. A5.2.2.2 Where framing, including metal and wood joists, is used, compliance shall be based on the maximum assembly U-factor rather than the minimum rated R-value of insulation .

A5.2.2.3 For waffle-slab floors, the floor shall be insulated either on the interior above the slab or on all exposed surfaces of the waffle.

A5.2.2.4 For floors with beams that extend below the floor slab, the floor shall be insulated either on the interior above the slab or on the exposed floor and all exposed surfaces of the beams that extend 24 in. and less below the exposed floor .

A5.2.3 U-Factors for Mass Floors

A5.2.3.1 The U-factors for mass walls shall be taken from Table A5.2.3.1. A5.2.3.2 It is not acceptable to use the U-factors in Table A5.2.3.1 if the insulation is not continuous.

A5.3 Steel-Joist Floors

A5.3.1 General. For the purpose of Section A1.2, the base assembly is a floor where the insulation is either placed between the steel joists or is sprayed on the underside of the floor and the joists. In both cases, the steel

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 251

PDF Page 254

Open page note

provides a thermal bypass to the insulation. The U-factors include R-0.92 for interior air film, heat flow down; R-1.23 for carpet and pad; R-0.25 for 4 in. concrete; R-0 for metal deck; and R-0.46 for semiexterior air film. The performance of the insulation/framing layer is calculated using the values in Table A9.2-1.

A5.3.2 Rated R-Value of Insulation for Steel-Joist Floors

A5.3.2.1 The first rated R-value of insulation is for uncompressed insulation installed in the cavity between steel joists or for spray-on insulation.

A5.3.2.2 It is acceptable for this insulation to also be continuous insulation uninterrupted by framing. All continuous insulation shall be installed either on the interior above the floor structure or below a framing cavity completely filled with insulation.

A5.3.3 U-Factors for Steel-Joist Floors

A5.3.3.1 The U-factors for steel-joist floors shall be taken from Table A5.3.3.1. A5.3.3.2 It is acceptable to use these U-factors for any steel-joist floor .

A5.4 Wood-Framed and Other Floors

A5.4.1 General. For the purpose of Section A1.2, the base assembly is a floor attached directly to the top of the wood joist with insulation located directly below the floor and ventilated air space below the insulation. The heat flow path through the joist is calculated to be the same depth as the insulation. The U-factors include R-0.92 for interior air film, heat flow down; R-1.23 for carpet and pad; R-0.94 for 0.75 in. wood subfloor; and R-0.46 for semiexterior air film. The weighting factors are 91% insulated cavity and 9% framing.

A5.4.2 Rated R-Value of Insulation for Wood-Framed and Other Floors. The first rated R-value of insulation is for uncompressed insulation installed in the cavity between wood joists.

A5.4.2.1 It is acceptable for this insulation to also be continuous insulation uninterrupted by framing. All continuous insulation shall be installed either on the interior above the floor structure or below a framing cavity completely filled with insulation.

A5.4.3 U-Factors for Wood-Framed Floors

A5.4.3.1 The U-factors for wood-framed floors shall be taken from Table A5.4.3.1. A5.4.3.2 It is not acceptable to use these U-factors if the framing is not wood.

A6. SLAB-ON-GRADE FLOORS

A6.1 General. For the purpose of Section A1.2, the base assembly is a slab-on-grade floor of 6 in. concrete poured directly on to the earth, the bottom of the slab is at grade line, and soil conductivity is 0.75 Btu/h·ft·°F. In contrast to the U-factor for floors, the F-factor for slab-on-grade floors is expressed per linear foot of building perimeter. F-factors are provided for unheated slabs and for heated slabs. Unheated slab-on-grade floors do not have heating elements, and heated slab-on-grade floors do have heating elements within or beneath the slab. F-factors are provided for five insulation configurations:

a. Horizontal Insulation: Continuous insulation is applied directly to the underside of the slab and extends

inward horizontally from the perimeter for the distance specified, or continuous insulation is applied downward from the top of the slab and then extends horizontally to the interior or the exterior from the perimeter for the distance specified. b. Vertical Insulation: Continuous insulation is applied directly to the slab exterior, extending downward

from the top of the slab for the distance specified. c. Fully Insulated Slab: Continuous insulation extends downward from the top of the slab and along the

entire perimeter and completely covers the entire area under the slab. d. Under-Slab Insulation only: Insulation installed under the entire slab. The slab edge remains uninsulated. e. Uninsulated: Slabs without insulation under the slab and at the slab edge.

A6.2 Rated R-Value of Insulation for Slab-on-Grade Floors

A6.2.1 The rated R-value of insulation shall be installed around the perimeter of the slab-on-grade floor to the distance specified.

Exception to A6.2.1: For a monolithic slab-on-grade floor, the insulation shall extend from the top of the

slab-on- grade to the bottom of the footing.

A6.2.2 Insulation installed inside the foundation wall shall extend downward from the top of the slab a minimum of the distance specified or to the top of the footing, whichever is less.

A6.2.3 Insulation installed outside the foundation wall shall extend from the top of the slab or downward to at least the bottom of the slab and then horizontally to a minimum of the distance specified. In all cli

252 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 255

Open page note

mates, the horizontal insulation extending outside of the foundation shall be covered by pavement or by soil a minimum of 10 in. thick.

A6.3 F-Factors for Slab-on-Grade Floors

A6.3.1 F-factors for slab-on-grade floors shall be taken from Table A6.3.1-1 or Table A6.3.1-2. A6.3.2 These F-factors are acceptable for all slab-on-grade floors .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 253

PDF Page 256

Open page note

Table A4.2.1 Assembly C-Factors forBelow-Grade WallsCol3
Framing Type and DepthRated R-Value of Insulation AloneSpecified C-Factors
(Wall Only, without Soil and Air
Films)
No framingR-0C-1.140

Exterior Insulation, Continuous and Uninterrupted by Framing

No framingR-5.0C-0.170
No framingR-7.5C-0.119
No framingR-10.0C-0.092
No framingR-12.5C-0.075
No framingR-15.0C-0.063
No framingR-17.5C-0.054
No framingR-20.0C-0.048
No framingR-25.0C-0.039
No framingR-30.0C-0.032
No framingR-35.0C-0.028
No framingR-40.0C-0.025
No framingR-45.0C-0.022
No framingR-50.0C-0.020

Continuous Metal Framing at 24 in. on Center Horizontally

3.5 in.R-11.0C-0.182
3.5 in.R-13.0C-0.174
3.5 in.R-15.0C-0.168
5.5 in.R-19.0C-0.125
5.5 in.R-21.0C-0.120

1 in. Metal Clips at 24 in. on Center Horizontally and 16 in. Vertically

1.0 in.R-3.8C-0.233
1.0 in.R-5.0C-0.201
1.0 in.R-5.6C-0.189
1.5 in.R-5.7C-0.173
1.5 in.R-7.5C-0.147
1.5 in.R-8.4C-0.138
2.0 in.R-7.6C-0.138
2.0 in.R-10.0C-0.116
2.0 in.R-11.2C-0.108
2.5 in.R-9.5C-0.114
2.5 in.R-12.5C-0.096
2.5 in.R-14.0C-0.089
3.0 in.R-11.4C-0.098
3.0 in.R-15.0C-0.082
3.0 in.R-16.8C-0.076
3.5 in.R-13.3C-0.085
3.5 in.R-17.5C-0.071
3.5 in.R-19.6C-0.066
4.0 in.R-15.2C-0.076
4.0 in.R-20.0C-0.063
4.0 in.R-22.4C-0.058

254 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 257

Open page note

Table A5.2.3.1 Assembly U-Factors for Mass Floors

Framing

Type

Cavity
Insulation R-
Value: Rated
(Effective
Installed)
Overall
U-Factor
for Entire
Base Floor
Assembly
Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21
Cavity
Insulation R-
Value: Rated
(Effective
Installed)
Overall
U-Factor
for Entire
Base Floor
Assembly
**R-1.00 ****R-2.00 ****R-3.00 ****R-4.00 ****R-5.00 ****R-6.00 ****R-7.00 ****R-8.00 ****R-9.00 ****R-10.00 ****R-11.00 ****R-12.00 ****R-13.00 ****R-14.00 ****R-15.00 ****R-20.00 ****R-25.00 ****R-30.00 ****R-35.00 **

Concrete Floor with Rigid Foam

and Spacing

Width (Actual

Depth)

None (0.0) 0.322 0.243 0.196 0.164 0.141 0.123 0.110 0.099 0.090 0.083 0.076 0.071 0.066 0.062 0.058 0.055 0.043 0.036 0.030 0.026 0.023

Concrete Floor with Pinned Boards

Col1R-4.2 (4.2)0.1370.1210.1080.0970.0890.0810.0750.0700.0650.0610.0580.0550.0520.0490.0470.0450.0370.0310.0270.0240.021
R-6.3 (6.3)0.1070.0960.0880.0810.0750.0700.0650.0610.0580.0540.0520.0490.0470.0450.0430.0410.0340.0290.0250.0230.020
R-8.3 (8.3)0.0870.0800.0740.0690.0650.0610.0570.0540.0510.0490.0470.0450.0430.0410.0390.0380.0320.0270.0240.0220.019
R-10.4(10.4)0.0740.0690.0640.0600.0570.0540.0510.0490.0460.0440.0420.0410.0390.0380.0360.0350.0300.0260.0230.0210.019
R-12.5 (12.5)0.0640.0600.0570.0540.0510.0480.0460.0440.0420.0410.0390.0380.0360.0350.0340.0330.0280.0250.0220.0200.018
R-14.6 (14.6)0.0560.0530.0510.0480.0460.0440.0420.0400.0390.0370.0360.0350.0340.0330.0320.0310.0270.0230.0210.0190.017
R-16.7 (16.7)0.0510.0480.0460.0440.0420.0400.0390.0370.0360.0350.0340.0320.0310.0300.0300.0290.0250.0220.0200.0180.017

Concrete Floor with Spray-On Insulation

1 in.R-4 (4.0)0.1410.1230.1100.0990.0900.0830.0760.0710.0660.0620.0580.0550.0520.0500.0470.0450.0370.0310.0270.0240.021
2 in.R-8 (8.0)0.0900.0830.0760.0710.0660.0620.0580.0550.0520.0500.0470.0450.0430.0410.0400.0380.0320.0280.0240.0220.020
3 in.R-12 (12.0)0.0660.0620.0580.0550.0520.0500.0470.0450.0430.0410.0400.0380.0370.0360.0340.0330.0280.0250.0220.0200.018
4 in.R-16 (16.0)0.0520.0500.0470.0450.0430.0410.0400.0380.0370.0360.0340.0330.0320.0310.0300.0290.0260.0230.0200.0180.017
5 in.R-20 (20.0)0.0430.0410.0400.0380.0370.0360.0340.0330.0320.0310.0300.0290.0280.0280.0270.0260.0230.0210.0190.0170.016
6 in.R-24 (24.0)0.0370.0360.0340.0330.0320.0310.0300.0290.0280.0280.0270.0260.0260.0250.0240.0240.0210.0190.0180.0160.015

PDF Page 258

Open page note

Table A5.3.3.1 Assembly U-Factors for Steel-Joist Floors

Framing
Type and
Spacing
Width
(Actual
Depth)
Cavity
Insulation
R-Value:
Rated
(Effective
Installed [See
Table A9.2-1])
Overall
U-Factor
for Entire
Base
Floor
Assembly
Overall U-Factor for Assembly of Base Floor Plus Continuous Insulation (Uninterrupted by Framing)Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21Col22Col23
Framing
Type and
Spacing
Width
(Actual
Depth)
Cavity
Insulation
R-Value:
Rated
(Effective
Installed [See
Table A9.2-1])
Overall
U-Factor
for Entire
Base
Floor
Assembly
Rated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous InsulationRated R-Value of Continuous Insulation
Framing
Type and
Spacing
Width
(Actual
Depth)
Cavity
Insulation
R-Value:
Rated
(Effective
Installed [See
Table A9.2-1])
Overall
U-Factor
for Entire
Base
Floor
Assembly
**R-1.00 ****R-2.00 ****R-3.00 ****R-4.00 ****R-5.00 ****R-6.00 ****R-7.00 ****R-8.00 **R-9.00R-
10.00
R-
11.00
R-
12.00
R-
13.00
R-
14.00
R-
15.00
**R-20.00 ****R-25.00 ****R-30.00 ****R-35.00 **R-40.00

Steel-Joist Floor with Rigid Foam

None (0.0) 0.350 0.259 0.206 0.171 0.146 0.127 0.113 0.101 0.092 0.084 0.078 0.072 0.067 0.063 0.059 0.056 0.044 0.036 0.030 0.026 0.023

Steel-Joist Floor with Spray-on Insulation

1 in.R-4 (3.88)0.1480.1290.1140.1030.0930.0850.0780.0730.0680.0640.0600.0560.0530.0510.0480.0460.0370.0320.0270.0240.021
2 in.R-8 (7.52)0.0960.0880.0810.0750.0700.0650.0610.0580.0540.0520.0490.0470.0450.0430.0410.0390.0330.0280.0250.0220.020
3 in.R-12 (10.80)0.0730.0680.0640.0600.0570.0540.0510.0480.0460.0440.0420.0410.0390.0380.0360.0350.0300.0260.0230.0210.019
4 in.R-16 (13.92)0.0600.0560.0530.0510.0480.0460.0440.0420.0400.0390.0370.0360.0350.0340.0320.0310.0270.0240.0210.0190.018
5 in.R-20 (17.00)0.0500.0480.0460.0440.0420.0400.0390.0370.0360.0350.0330.0320.0310.0300.0300.0290.0250.0220.0200.0180.017
6 in.R-24 (19.68)0.0440.0420.0410.0390.0380.0360.0350.0340.0330.0320.0310.0300.0290.0280.0270.0270.0240.0210.0190.0170.016

Steel-Joist Floor with Batt Insulation

Col1None (0.0)0.3500.2590.2060.1710.1460.1270.1130.1010.0920.0840.0780.0720.0670.0630.0590.0560.0440.0360.0300.0260.023
R-11 (10.01)0.0780.0720.0670.0630.0590.0560.0530.0500.0480.0460.0440.0420.0400.0390.0370.0360.0300.0260.0230.0210.019
R-13 (11.70)0.0690.0640.0600.0570.0540.0510.0490.0460.0440.0420.0410.0390.0380.0360.0350.0340.0290.0250.0220.0200.018
R-15 (13.20)0.0620.0590.0550.0520.0500.0470.0450.0430.0420.0400.0380.0370.0360.0340.0330.0320.0280.0240.0220.0200.018
R-19 (16.34)0.0520.0500.0470.0450.0430.0410.0400.0380.0370.0350.0340.0330.0320.0310.0300.0290.0260.0230.0200.0180.017
R-21 (17.64)0.0490.0470.0440.0430.0410.0390.0380.0360.0350.0340.0330.0320.0310.0300.0290.0280.0250.0220.0200.0180.017
R-25 (20.25)0.0430.0410.0400.0380.0370.0360.0340.0330.0320.0310.0300.0290.0280.0280.0270.0260.0230.0210.0190.0170.016
R-30C (23.70)0.0380.0360.0350.0340.0330.0320.0310.0300.0290.0280.0270.0270.0260.0250.0250.0240.0210.0190.0180.0160.015
R-30 (23.70)0.0380.0360.0350.0340.0330.0320.0310.0300.0290.0280.0270.0270.0260.0250.0250.0240.0210.0190.0180.0160.015
R-38C (28.12)0.0320.0310.0300.0290.0290.0280.0270.0260.0260.0250.0240.0240.0230.0230.0220.0220.0200.0180.0160.0150.014
R-38 (28.12)0.0320.0310.0300.0290.0290.0280.0270.0260.0260.0250.0240.0240.0230.0230.0220.0220.0200.0180.0160.0150.014

PDF Page 259

Open page note

Table A5.4.3.1 Assembly U-Factors for Wood-Joist Floors

Framin

g Type

and Spacing

Width (Actual

Depth)

Cavity
Insulation
R-Value:
Rated
(Effective
Installed)
Overall
U-Factor
for Entire
Base Floor
Assembly
Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20Col21
Cavity
Insulation
** R-Value:
Rated
(Effective**
Installed)
Overall
U-Factor
for Entire
Base Floor
Assembly
**R-1.00 ****R-2.00 ****R-3.00 ****R-4.00 ****R-5.00 ****R-6.00 ****R-7.00 ****R-8.00 ****R-9.00 ****R-10.00 ****R-11.00 ****R-12.00 ****R-13.00 ****R-14.00 ****R-15.00 ****R-20.00 ****R-25.00 ****R-30.00 ****R-35.00 **

Wood-Joist

5.5 in.None (0.0)0.2820.2200.1800.1530.1320.1170.1050.0950.0870.0800.0740.0690.0640.0600.0570.0540.0420.0350.0300.0260.023
R-11 (11.0)0.0740.0690.0640.0600.0570.0540.0510.0480.0460.0440.0420.0400.0390.0370.0360.0350.0300.0260.0230.0200.019
R-13 (13.0)0.0660.0620.0580.0550.0520.0490.0470.0450.0430.0410.0390.0380.0360.0350.0340.0330.0280.0250.0220.0200.018
R-15 (15.0)0.0600.0570.0530.0500.0480.0460.0440.0420.0400.0380.0370.0360.0340.0330.0320.0310.0270.0240.0210.0190.017
R-19 (18.0)0.0510.0480.0460.0440.0420.0400.0380.0370.0360.0340.0330.0320.0310.0300.0290.0280.0250.0220.0200.0180.017
R-21 (21.0)0.0460.0430.0420.0400.0380.0370.0350.0340.0330.0320.0310.0300.0290.0280.0270.0270.0230.0210.0190.0170.016
7.25 in.R-25 (25.0)0.0390.0370.0360.0350.0330.0320.0310.0300.0290.0280.0280.0270.0260.0250.0250.0240.0220.0190.0180.0160.015
R-30C (30.0)0.0340.0330.0320.0310.0300.0290.0280.0270.0260.0260.0250.0240.0240.0230.0230.0220.0200.0180.0160.0150.014
9.25 in.R-30 (30.0)0.0330.0320.0310.0300.0290.0280.0270.0270.0260.0250.0240.0240.0230.0230.0220.0220.0200.0180.0160.0150.014
11.25 in.R-38C (38.0)0.0270.0260.0250.0250.0240.0240.0230.0220.0220.0210.0210.0200.0200.0200.0190.0190.0170.0160.0150.0140.013
13.25 in.R-38 (38.0)0.0260.0260.0250.0240.0240.0230.0230.0220.0220.0210.0210.0200.0200.0190.0190.0190.0170.0160.0150.0140.013

PDF Page 260

Open page note

Table A6.3.1-1 Assembly F-Factors for Slab-on-Grade Floors

Col1Col2Unheated SlabsCol4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14
Uninsulated: 0.73
12 in. horizontal0.720.710.710.71
24 in. horizontal24 in. horizontal0.700.700.700.690.690.690.690.690.690.690.690.69
36 in. horizontal36 in. horizontal0.680.670.660.660.660.660.660.660.660.660.660.66
48 in. horizontal48 in. horizontal0.670.650.640.630.630.630.630.630.630.630.630.63
12 in. vertical0.610.600.580.570.5670.5650.564
24 in. vertical24 in. vertical0.580.560.540.520.5100.5050.5020.5020.5020.5020.5020.502
36 in. vertical36 in. vertical0.560.530.510.480.4720.4640.4600.4600.4600.4600.4600.460
48 in. vertical48 in. vertical0.540.510.480.450.4340.4240.4190.4190.4190.4190.4190.419
Fully insulated slab0.460.410.360.300.2610.2330.2130.1980.1860.1760.1680.161

Heated Slabs

Uninsulated: 1.35Col2Col3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14
12 in. horizontal1.311.311.301.30
24 in. horizontal24 in. horizontal1.281.271.261.25
36 in. horizontal36 in. horizontal1.241.211.201.18
48 in. horizontal48 in. horizontal1.201.171.131.11
12 in. vertical1.061.021.000.980.9680.9640.961
24 in. vertical24 in. vertical0.990.950.900.860.8430.8320.827
36 in. vertical36 in. vertical0.950.890.840.790.7620.7470.740
48 in. vertical48 in. vertical0.910.850.780.720.6880.6710.659
Fully insulated slab0.740.640.550.440.3730.3260.2960.2730.2550.2390.2270.217
Underslab
insulation only
1.061.010.950.900.820.76

Table A6.3.1-2 Assembly F-Factors for Fully Insulated Heated Slab-on-Grade Floors

Insulation DescriptionRated R-Value of Edge InsulationCol3Col4Col5Col6Col7Col8Col9
Insulation DescriptionR-3.5R-5R-7.5R-10R-15R-20R-25R-30

Heated Slabs

R-3.5 under slab0.810.780.740.710.690.6710.6700.669
R-5 under slab0.770.740.690.660.620.6020.6020.601
R-7.5 under slab0.710.670.640.600.580.5660.5640.563
R-10 under slab0.660.620.580.550.510.4960.4940.493
R-15 under slab0.570.540.500.470.450.4330.4320.431
R-20 under slab0.510.480.440.410.390.3710.3700.369

258 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 261

Open page note

A7. OPAQUE DOORS

All opaque doors with U-factors determined, certified, and labeled in accordance with NFRC 100 or ANSI/ DASMA 105 shall be assigned those U-factors .

A7.1 Unlabeled Opaque Doors. Unlabeled opaque doors shall be assigned the following U-factors :

a. Uninsulated single-layer metal swinging doors or nonswinging doors, including single-layer uninsulated

access hatches and uninsulated smoke vents: U-1.45. b. Insulated double-layer metal coiling doors : U-1.00. c. Uninsulated double-layer metal swinging doors or nonswinging doors, including double-layer uninsu lated access hatches and uninsulated smoke vents: U-0.70. d. Insulated metal swinging doors, including fire-rated doors, insulated access hatches, insulated smoke

vents, and other insulated metal nonswinging doors : U-0.50. e. Wood doors, minimum nominal thickness of 1.75 in., including panel doors with minimum panel thick ness of 1.125 in., solid core flush doors, and hollow core flush doors : U-0.50. f. Any other wood door : U-0.60.

A8. FENESTRATION

All fenestration with U-factors, SHGC, or visible transmittance determined, certified, and labeled in accordance with NFRC 100, 200, and 300, respectively, shall be assigned those values.

A8.1 Unlabeled Skylights. Unlabeled skylights shall be assigned the U-factors in Table A8.1-1 and are allowed to use the SHGCs and VTs in Table A8.1-2. The metal with thermal break frame category shall not be used unless all frame members have a thermal break equal to or greater than 0.25 in.

A8.2 Unlabeled Vertical Fenestration. Unlabeled vertical fenestration, both operable and fixed, shall be assigned the U-factors, SHGCs, and VTs in Table A8.2.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 259

PDF Page 262

Open page note

Table A8.1-1 Assembly U-Factors for Unlabeled Skylights

Product TypeCol2Sloped InstallationCol4Col5Col6Col7Col8Col9
Product TypeProduct TypeUnlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight without Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight without Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight without Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Frame TypeFrame TypeAluminum
without
Thermal
Break
Aluminum
with
Thermal
Break
Reinforced
Vinyl/
Aluminum
Clad Wood
Wood/
Vinyl
Aluminum
without
Thermal Break
Aluminum with
Thermal Break
Structural
Glazing
IDGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing Type
Single GlazingSingle GlazingSingle GlazingSingle GlazingSingle GlazingSingle GlazingSingle GlazingSingle Glazing
11/8 in. glass1.981.891.751.471.361.251.25
21/4 in. acrylic/
polycarb
1.821.731.601.311.211.101.10
31/8 in. acrylic/
polycarb
1.901.811.681.391.291.181.18
Double GlazingDouble GlazingDouble GlazingDouble GlazingDouble GlazingDouble GlazingDouble GlazingDouble Glazing
41/4 in. air space1.311.111.050.840.820.700.66
51/2 in. air space1.301.101.040.840.810.690.65
61/4 in. argon space1.271.071.000.800.770.660.62
71/2 in. argon space1.271.071.000.800.770.660.62
Double Glazing,****_e _= 0.60 on surface 2 or 3Double Glazing,****_e _= 0.60 on surface 2 or 3Double Glazing,****_e _= 0.60 on surface 2 or 3Double Glazing,****_e _= 0.60 on surface 2 or 3Double Glazing,****_e _= 0.60 on surface 2 or 3Double Glazing,****_e _= 0.60 on surface 2 or 3Double Glazing,****_e _= 0.60 on surface 2 or 3Double Glazing,****_e _= 0.60 on surface 2 or 3
81/4 in. air space1.271.081.010.810.780.670.63
91/2 in. air space1.271.071.000.800.770.660.62
101/4 in. argon space1.231.030.970.760.740.630.58
111/2 in. argon space1.231.030.970.760.740.630.58
Double Glazing,****_e _= 0.40 on surface 2 or 3Double Glazing,****_e _= 0.40 on surface 2 or 3Double Glazing,****_e _= 0.40 on surface 2 or 3Double Glazing,****_e _= 0.40 on surface 2 or 3Double Glazing,****_e _= 0.40 on surface 2 or 3Double Glazing,****_e _= 0.40 on surface 2 or 3Double Glazing,****_e _= 0.40 on surface 2 or 3Double Glazing,****_e _= 0.40 on surface 2 or 3
121/4 in. air space1.251.050.990.780.760.640.60
131/2 in. air space1.241.040.980.770.750.640.59
141/4 in. argon space1.180.990.920.720.700.580.54
151/2 in. argon space1.201.000.940.740.710.600.56
Double Glazing,****_e _= 0.20 on surface 2 or 3Double Glazing,****_e _= 0.20 on surface 2 or 3Double Glazing,****_e _= 0.20 on surface 2 or 3Double Glazing,****_e _= 0.20 on surface 2 or 3Double Glazing,****_e _= 0.20 on surface 2 or 3Double Glazing,****_e _= 0.20 on surface 2 or 3Double Glazing,****_e _= 0.20 on surface 2 or 3Double Glazing,****_e _= 0.20 on surface 2 or 3
161/4 in. air space1.201.000.940.740.710.600.56
171/2 in. air space1.201.000.940.740.710.600.56
181/4 in. argon space1.140.940.880.680.650.540.50
191/2 in. argon space1.150.950.890.680.660.550.51
Double Glazing,****_e _= 0.10 on surface 2 or 3Double Glazing,****_e _= 0.10 on surface 2 or 3Double Glazing,****_e _= 0.10 on surface 2 or 3Double Glazing,****_e _= 0.10 on surface 2 or 3Double Glazing,****_e _= 0.10 on surface 2 or 3Double Glazing,****_e _= 0.10 on surface 2 or 3Double Glazing,****_e _= 0.10 on surface 2 or 3Double Glazing,****_e _= 0.10 on surface 2 or 3
201/4 in. air space1.180.990.920.720.700.580.54
211/2 in. air space1.180.990.920.720.700.580.54
221/4 in. argon space1.110.910.850.650.630.520.47
231/2 in. argon space1.130.930.870.670.650.530.49
Double Glazing,****_e _= 0.05 on surface 2 or 3Double Glazing,****_e _= 0.05 on surface 2 or 3Double Glazing,****_e _= 0.05 on surface 2 or 3Double Glazing,****_e _= 0.05 on surface 2 or 3Double Glazing,****_e _= 0.05 on surface 2 or 3Double Glazing,****_e _= 0.05 on surface 2 or 3Double Glazing,****_e _= 0.05 on surface 2 or 3Double Glazing,****_e _= 0.05 on surface 2 or 3
241/4 in. air space1.170.970.910.700.680.570.52
251/2 in. air space1.170.980.910.710.690.580.53
261/4 in. argon space1.090.890.830.630.610.500.45
271/2 in. argon space1.110.910.850.650.630.520.47

260 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 263

Open page note

Table A8.1-1 Assembly U-Factors for Unlabeled Skylights (Continued)

Product TypeCol2Sloped InstallationCol4Col5Col6Col7Col8Col9
Product TypeProduct TypeUnlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight with Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight without Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight without Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Unlabeled Skylight without Curb
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Frame TypeFrame TypeAluminum
without
Thermal
Break
Aluminum
with
Thermal
Break
Reinforced
Vinyl/
Aluminum
Clad Wood
Wood/
Vinyl
Aluminum
without
Thermal Break
Aluminum with
Thermal Break
Structural
Glazing
IDGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing Type
Triple GlazingTriple GlazingTriple GlazingTriple GlazingTriple GlazingTriple GlazingTriple GlazingTriple Glazing
281/4 in. air spaces1.120.890.840.640.640.530.48
291/2 in. air spaces1.100.870.810.610.620.510.45
301/4 in. argon
space_s_
1.090.860.800.600.610.500.44
311/2 in. argon
space_s_
1.070.840.790.590.590.480.42
Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5Triple Glazing,****_e _= 0.20 on surface 2,3,4, or 5
321/4 in. air space1.080.850.790.590.600.490.43
331/2 in. air space1.050.820.770.570.570.460.41
341/4 in. argon space1.020.790.740.540.550.440.38
351/2 in. argon space1.010.780.730.530.540.430.37
Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.20 on surfaces 2 or 3 and 4 or 5
361/4 in. air space1.030.800.750.550.560.450.39
371/2 in. air space1.010.780.730.530.540.430.37
381/4 in. argon space0.990.750.700.500.510.400.35
391/2 in. argon space0.970.740.690.490.500.390.33
Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Triple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5
401/4 in. air space1.010.780.730.530.540.430.37
411/2 in. air space0.990.760.710.510.520.410.36
421/4 in. argon space0.960.730.680.480.490.380.32
431/2 in. argon space0.950.720.670.470.480.370.31
Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5Quadruple Glazing,****_e _= 0.10 on surfaces 2 or 3 and 4 or 5
441/4 in. air space0.970.740.690.490.500.390.33
451/2 in. air space0.940.710.660.460.470.360.30
461/4 in. argon space0.930.700.650.450.460.350.30
471/2 in. argon space0.910.680.630.430.440.330.28
481/4 in. krypton
space_s_
0.880.650.600.400.420.310.25

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 261

PDF Page 264

Open page note

Table A8.1-2 Assembly SHGCs and Assembly Visible Transmittances (VTs) for Unlabeled Skylights

Glass
Type
Glazing Type:
Number of Glazing Layers
Number and Emissivity of Coatings
(Glazing is Glass Except where Noted)
Unlabeled Skylights
(Includes Glass/Plastic, Flat/Domed, Fixed/Operable)
Col4Col5Col6Col7Col8Col9
Glass
Type
Glazing Type:
Number of Glazing Layers
Number and Emissivity of Coatings
(Glazing is Glass Except where Noted)
Frame:Metal without
Thermal Break
Metal without
Thermal Break
Metal with
Thermal Break
Metal with
Thermal Break
Wood/Vinyl/
Fiberglass
Wood/Vinyl/
Fiberglass
Glass
Type
Glazing Type:
Number of Glazing Layers
Number and Emissivity of Coatings
(Glazing is Glass Except where Noted)
Characteristic:SHGCVTSHGCVTSHGCVT
ClearSingle glazing, 1/8 in. glass0.820.760.780.760.730.73
ClearSingle glazing, 1/4 in. glass0.780.750.740.750.690.72
ClearSingle glazing, acrylic/polycarbonate0.830.920.830.920.830.92
ClearDouble glazing0.680.660.640.660.590.64
ClearDouble glazing,e = 0.40 on surface 2 or 30.710.650.670.650.620.63
ClearDouble glazing,e = 0.20 on surface 2 or 30.660.610.620.610.570.59
ClearDouble glazing,e = 0.10 on surface 2 or 30.590.630.550.630.510.61
ClearDouble glazing, acrylic/polycarbonate0.770.890.770.890.770.89
ClearTriple glazing0.600.590.560.590.520.57
ClearTriple glazing,e = 0.40 on surface 2, 3, 4, or 50.640.600.600.600.560.57
ClearTriple glazing,e = 0.20 on surface 2, 3, 4, or 50.590.550.550.550.510.53
ClearTriple glazing,e = 0.10 on surface 2, 3, 4, or 50.540.560.500.560.460.54
ClearTriple glazing,e = 0.40 on surfaces 3 and 50.620.570.580.570.530.55
ClearTriple glazing,e = 0.20 on surfaces 3 and 50.560.510.520.510.480.49
ClearTriple glazing,e = 0.10 on surfaces 3 and 50.470.540.430.540.400.52
ClearTriple glazing, acrylic/polycarbonate0.710.850.710.850.710.85
ClearQuadruple glazing,e = 0.10 on surfaces 3 and 50.410.480.370.480.330.46
ClearQuadruple glazing, acrylic/polycarbonate0.650.810.650.810.650.81
TintedSingle glazing, 1/8 in. glass0.700.580.660.580.620.56
TintedSingle glazing, 1/4 in. glass0.610.450.560.450.520.44
TintedSingle glazing, acrylic/polycarbonate0.460.270.460.270.460.27
TintedDouble glazing0.500.400.460.400.420.39
TintedDouble glazing,e = 0.40 on surface 2 or 30.590.500.550.500.500.48
TintedDouble glazing,e = 0.20 on surface 2 or 30.470.370.430.370.390.36
TintedDouble glazing,e = 0.10 on surface 2 or 30.430.380.390.380.350.37
TintedDouble glazing, acrylic/polycarbonate0.370.250.370.250.370.25
TintedTriple glazing0.420.220.370.220.340.21
TintedTriple glazing,e = 0.40 on surface 2, 3, 4, or 50.530.450.490.450.450.44
TintedTriple glazing,e = 0.20 on surface 2, 3, 4, or 50.420.330.380.330.350.32
TintedTriple glazing,e = 0.10 on surface 2, 3, 4, or 50.390.340.350.340.310.33
TintedTriple glazing,e = 0.40 on surfaces 3 and 50.510.430.470.430.430.42
TintedTriple glazing,e = 0.20 on surfaces 3 and 50.400.310.360.310.320.29
TintedTriple glazing,e = 0.10 on surfaces 3 and 50.340.320.300.320.270.31
TintedTriple glazing, acrylic/polycarbonate0.300.230.300.230.300.23
TintedQuadruple glazing,e = 0.10 on surfaces 3 and 50.300.290.260.290.230.28
TintedQuadruple glazing, acrylic/polycarbonate0.270.250.270.250.270.25

262 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 265

Open page note

Table A8.2 Assembly U-Factors, Assembly SHGCs, and Assembly Visible Transmittances (VTs)

Wood, vinyl, or fiberglass frames

Metal and other

frame types

enestrationCol2Col3Col4Col5Col6
Glazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing TypeGlazing Type
Glazing TypeClear GlassClear GlassClear GlassClear GlassClear Glass
Glazing TypeU-FactorSHGCVTU-FactorSHGC
Single glazing1.250.820.761.250.70
Glass block0.600.560.56NANA
Double glazing0.600.590.640.600.42
Triple glazing0.450.520.570.450.34
Double glazing0.900.680.660.900.50
Triple glazing0.700.600.590.700.42

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 263

PDF Page 266

Open page note

A9. DETERMINATION OF ALTERNATE ASSEMBLY U-FACTORS, C-FACTORS,F-FACTORS, OR HEAT CAPACITIES

A9.1 General. Alternative assembly U-factors, C-factors, F-factors or heat capacities for opaque assemblies shall be determined in accordance with Section A9. The procedures required for each class of construc- tion are specified in Section A9.2. Testing shall be performed in accordance with Section A9.3. Calculations shall be performed in accordance with Section A9.4.

A9.2 Required Procedures. Two- or three-dimensional finite difference and finite volume computer models shall be an acceptable alternative method to calculating the thermal performance values for all assemblies and constructions listed below. The following procedures shall also be permitted to determine all alternative U-factors, F-factors, and C-factors :

a. Roofs

  1. Roofs with insulation entirely above deck : Testing or series calculation method.

  2. Metal building roofs : Testing, or for single-layer and double-layer systems, calculation method in Section A9.4.6.

  3. Attic roofs, wood joists: Testing or parallel path calculation method.

  4. Attic roofs, steel joists : Testing or parallel path calculation method using the insulation/framing layer adjustment factors in Table A9.2-1 or modified zone calculation method.

  5. Attic roofs, concrete joists: Testing or parallel path calculation method if concrete is solid and uniform, or isothermal planes calculation method if concrete has hollow sections.

  6. Other attic roofs and other roofs : Testing or two-dimensional calculation method. b. Above-Grade Walls

  7. Mass walls : Testing or isothermal planes calculation method or two-dimensional calculation method. The parallel path calculation method is not acceptable.

  8. Metal building walls : Testing, or for single-layer compressed, single-layer in cavity, double-layer sys i. Where the steel-framed wall contains no cavity insulation and uses continuous insulation to satisfy the U-factor maximum, the steel-framed wall member spacing is permitted to be installed at any on-center spacing. ii. Where the steel-framed wall contains framing at 24 in. on center with a 23% framing factor or

iii. Where the steel-framed wall contains less than 23% framing factors, AISI S250 shall be used without any modifications. iv. Where the steel-framed wall contains other than standard C-shape framing members, the AISI S250 calculation option for other than standard C-shape framing is permitted to be used. 4. Wood-framed walls : Testing or parallel path calculation method. 5. Other walls : Testing or two-dimensional calculation method. c. Below-Grade Walls

  1. Mass walls : Testing or isothermal planes calculation method or two-dimensional calculation method. The parallel path calculation method is not acceptable.

  2. Other walls : Testing or two-dimensional calculation method. d. Floors

  3. Mass floors : Testing or parallel path calculation method if concrete is solid and uniform or isothermal planes calculation method if concrete has hollow sections.

  4. Steel-joist floors : Testing or modified zone calculation method.

  5. Wood-joist floors : Testing or parallel path calculation method or isothermal planes calculation method.

  6. Other floors : Testing or two-dimensional calculation method. e. Slab-on-Grade Floors

  7. No testing or calculations allowed.

A9.3 Testing Procedures

A9.3.1 Building Material Thermal Properties. If building material R-values or thermal conductivities are determined by testing, one of the following test procedures shall be used:

264 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 267

Open page note

a. ASTM C177 b. ASTM C518 c. ASTM C1363

For concrete, the oven-dried conductivity shall be multiplied by 1.2 to reflect the moisture content as typically installed.

A9.3.2 Assembly U-Factors. If assembly U-factors are determined by testing, ASTM C1363 test procedures shall be used.

Product samples tested shall be production-line material or representative of material as purchased by the consumer or contractor. If the assembly is too large to be tested at one time in its entirety then either a representative portion shall be tested or different portions shall be tested separately and a weighted average determined. To be representative, the portion tested shall include edges of panels, joints with other panels, typical framing percentages, and thermal bridges .

A9.4 Calculation Procedures and Assumptions. The following procedures and assumptions shall be used for all calculations. R-values for air films, air spaces, insulation, and building materials shall be taken from Sections A9.4.1 through A9.4.4, respectively. In addition, applicable assumptions listed in Sections A2 through A8, including framing factors, shall be used.

A9.4.1 Air Films. Prescribed R-values for air films shall be as follows:

R-Value Condition 0.17 All exterior surfaces 0.46 All semiexterior surfaces 0.61 Interior horizontal surfaces, heat flow up 0.92 Interior horizontal surfaces, heat flow down 0.68 Interior vertical surfaces

A9.4.1.1 Exterior surfaces are areas exposed to the wind. A9.4.1.2 Semiexterior surfaces are protected surfaces that face attics, crawlspaces, and parking garages with natural or mechanical ventilation .

A9.4.1.3 Interior surfaces are surfaces within enclosed spaces . A9.4.2 Air Spaces. The R-value for air spaces shall be taken from Table A9.4.2-1 based on the effective emittance of the surfaces facing the air space from Table A9.4.2-2, provided the following criteria are satisfied:

a. The air space shall be an enclosed and unventilated cavity designed to minimize airflow into and out of

the enclosed air space. Airflow shall be deemed minimized when the enclosed air space is located on the interior of the continuous air barrier and bounded on all sides by building components. b. Reflective insulation as defined in ASTM C1224, where used, shall be fitted closely around all non-heat producing components and taped or otherwise sealed to eliminate gaps or voids through which air, dust, or water vapor has the potential to pass. c. Nonparallel spaces shall use the average distance to determine the thickness of the air space. d. Air spaces less than 0.5 in. thickness shall have no R-value . e. The R-value for 3.5 in. air spaces shall be used for air spaces of that thickness or greater, provided that air

space does not exceed 12 in. between the surfaces at any point.

For material emissivity properties not listed in Table A9.4.2-2, Equation A9.4-1 shall be permitted to calculate the effective emissivity for the air space.

1/ eeff = 1/ e 1 + 1/ e 2 – 1 (A9.4-1)

where eeff = effective emittance for the air space e 1 = surface 1 emittance e 2 = surface 2 emittance A9.4.3 Insulation R-Values. Insulation R-values shall be determined as follows:

a. For insulation that is not compressed, the rated R-value of insulation shall be used. b. For calculation purposes, the effective R-value for insulation that is uniformly compressed in confined

cavities shall be taken from Table A9.4.3. c. For calculation purposes, the effective R-value for insulation installed in cavities in attic roofs with steel

joists shall be taken from Table A9.2-1.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 265

PDF Page 268

Open page note

Figure A9.4.6.1 Geometry of single-layer fiberglass batt.

where X = distance from edge of purlin or girt, ft Y = distance from edge of roof panel or wall panel, ft L = length from edge of purlin or girt to centerline of cavity, ft wf = width of purlin or girt flange, ft Yo = distance between purlin or girt and the roof panel or wall panel, ft Ym = distance from edge of roof panel or wall panel at the cavity centerline, ft

d. For calculation purposes, the effective R-value for insulation installed in cavities in steel-framed walls

shall be taken from Table A9.2-2.

A9.4.4 Building Material Thermal Properties. R-values for building materials shall be taken from Table A9.4.4-1. Concrete block R-values shall be calculated using the isothermal planes method or a twodimensional calculation program, thermal conductivities from Table A9.4.2-2, and dimensions from ASTM C90. The parallel path calculation method is not acceptable.

Exception to A9.4.4: R-values for building materials or thermal conductivities determined from testing

in accordance with Section A9.3.

A9.4.5 Building Material Heat Capacities. The HC of assemblies shall be calculated using published values for the unit weight and specific heat of all building material components that make up the assembly.

A9.4.6 Metal Building U-Factor Equations. The calculation procedures in this section shall use a fixed purlin and girt spacing of 60 in., and the results shall be permitted to be used in accordance with Sections A2.3.3 and A3.2.3. For single-layer metal building roof and single-layer compressed metal building wall systems, the calculation procedure outlined in Section A9.4.6.1 shall be used to calculate the assembly U- factor . For double-layer metal building roof systems, the calculation procedure outlined in Section A9.4.6.2 shall be used to calculate the assembly U-factor . For single-layer in cavity and double-layer metal build- ing wall systems, the calculation procedure outlined in Section A9.4.6.3 shall be used to calculate the assembly U-factor . Each of the above insulation methods and calculation procedures also shall be used where continuous insulation is applied to the assembly. The calculation procedures outlined in this section shall not be used for other metal building roof and wall systems.

A9.4.6.1 Single-Layer Roof and Single-Layer Compressed Wall. The U-factor of metal building roofs or metal building walls that are insulated with a single layer of fiberglass insulation (see Figure A9.4.6.1) shall be calculated using the procedure outlined in this section. The procedure assumes the insulation is compressed over the purlin or girt. There may also be a thermal spacer block present.

There are six steps in the calculation process:

 - Step 1—Characterize the thermal conductivity of the fiberglass.

 - Step 2—Determine the _U-factor_ for the insulation in the cavity.

 - Step 3—Determine the _U-factor_ over the structural framing member.

 - Step 4—Area weight the _U-factors_ calculated in Steps 2 and 3.

 - Step 5—Determine the _U-factor_ from the finite element analysis results.

 - Step 6—Determine the _U-factor_ for any _continuous insulation_ if present.

Step 1: The thermal conductivity of the fiberglass batt insulation is represented by a thermal curve of the form in Equation A9.4-2:

266 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 269

Open page note

C k = A + B  +

[—]  [-]

where k = thermal conductivity, Btu/h·ft·°F  = density, lb/ft [3]

A = 0.014917 B = 0.0004377 C = 0.0056897 Step 2: Assume the fiberglass batt forms a parabolic profile defined by Equation A9.4-3:

  X

Y = Yo +  Ym - Yo  [X] [---] L  2 - [---] L

Determine the cavity U-factor ( Uc ) using Equation A9.4-4:

(A9.4-2)

(A9.4-3)

(A9.4-4)

Boto

Uc

oto 2 YoYm

Ym - Yo   1 + ---------------- -   --------------------------- Ym   1 - Y ---------------- m - Y - o   Y

1 + Y ---------------- m - Y - o

--------------------------- Ym

1 - Y ---------------- m - Y - o

  • ---------------- -

--------------------------- Ym

  • Y ---------------- m - Y - o Ym

where  o = reference density of the fiberglass, lb/ft [3]

to = reference thickness of the fiberglass, ft The properties of fiberglass insulation are presented in Table A9.4.6.1. Include the thermal resistance s of the interior ( Ri ) and exterior ( Re ) air films to calculate the overall cavity U-factor ( Uco ) using Equation A9.4-5:

Uco

1 = -----------------------------1 ---- U - c + Ri + Re

(A9.4-5)

Step 3: Determine the U-factor ( Ufo ) over the structural framing member. The variable Yo represents the total combined thickness of the thermal spacer block and the compressed insulation. The density of the compressed insulation is determined by Equation A9.4-6:

c

=  --------- oto tc

where

c = density of the compressed insulation over the framing member, lb/ft [3 ] tc = thickness of the compressed insulation over the framing member, ft Determine the thermal resistance of the compressed insulation ( Rc ) using Equation A9.4-7:

(A9.4-6)

(A9.4-7)

Rc

= ------------------------------------- tc - A + Bc + C   c

Determine the overall framing U-factor ( Ufo ) at the structural framing member, including the air film resistances, using Equation A9.4-8:

Ufo

1 = -------------------------------------------RTB + Rc + Ri + Re

(A9.4-8)

where Ufo = U-factor over the structural framing member, Btu/h·ft [2] ·°F RTB = R-value of the thermal spacer block, h·ft [2] ·°F/Btu Rc = R-value of the compressed insulation, h·ft [2] ·°F/Btu

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 267

PDF Page 270

Open page note

Figure A9.4.6.2-1 Geometry of double layers of fiberglass batts.

where X = distance from edge of purlin or girt, ft Y = distance from edge of roof panel or wall panel, ft L = length from edge of purlin or girt to centerline of cavity, ft wf = width of purlin or girt flange, ft Yo = distance between purlin or girt and the roof panel or wall panel, ft Ym = distance from edge of roof panel or wall panel at the cavity centerline, ft

Step 4: Determine the overall area-weighted U-factor for the entire system using Equation A9.4-9:

Ues

= L ------------------------------------------------------  Uco +  wf  2   Ufo - L +  wf  2 

where

Ues = area-weighted U-factor for the entire system, Btu/h·ft [2] ·°F

wf = width of purlin or girt flange, ft

Step 5: Calculate the adjusted overall U-factor ( Uadj ) using Equation A9.4-10:

(A9.4-9)

(A9.4-10)

Uadj

1 = --------------------------------------------------0.8676  Ues + 1.1423

where

Uadj = adjusted overall U-factor represented by correlation with the finite element modeling, Btu/h·ft [2] ·°F

Step 6: If there is any continuous insulation present, calculate the overall U-factor using Equation A9.4-11:

1 U = ---------------------- - 1 -------- Uadj - + Rci

(A9.4-11)

A9.4.6.2 Double-Layer Roof. The U-factor of metal building roofs that are insulated with double layers of fiberglass insulation (see Figure A9.4.6.2-1) shall be calculated using the procedure outlined in this section. The procedure assumes the insulation is compressed over the purlin and there may be a thermal spacer block present.

There are six steps in the calculation process:

 - Step 1—Characterize the thermal conductivity of the fiberglass.

 - Step 2—Determine the _U-factor_ for the insulation in the cavity.

 - Step 3—Determine the _U-factor_ over the structural framing member.

 - Step 4—Area weight the _U-factors_ calculated in Steps 2 and 3.

 - Step 5—Determine the _U-factor_ from the finite element analysis results.

 - Step 6—Determine the _U-factor_ for any _continuous insulation_ if present.

Step 1: The thermal conductivity of the fiberglass batt insulation is represented by a thermal curve of the form in Equation A9.4-12:

268 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 271

Open page note

Figure A9.4.6.2-2 Compression of double layers of fiberglass insulation.

C k = A + B  +

[—]  [-]

where k = thermal conductivity, Btu/h·ft [2] ·°F  = density, lb/ft [3]

(A9.4-12)

A = 0.014917 B = 0.0004377 C = 0.0056897 Step 2: Assume the double-layer fiberglass batt forms a parabolic profile defined by Equation A9.4-13:

  X

Y = Yo +  Ym - Yo  [X] [---] L  2 - [---] L

(A9.4-13)

The presence of two layers of fiberglass adds complexity because each layer has distinct reference properties (see Table A9.4.6.1). As the double layers are compressed, the thickness of each layer needs to be determined by considering that each layer achieves the same compressive force. Instead of having a closedform analytical solution that predicts the U-factor for the cavity, the double-layer system requires that the parabolic profile be numerically integrated. The compression of the double-layer system is presented in Figure A9.4.6.2-2.

The thickness of the second layer ( Y 2) is described by Equation A9.4-14:

Y -----2   Yc

---------------------------------------------------- - - 1   o 21 -  o 22  Yc  12 

o 2 1

2 -  o 2

1 2

Y -----2  -  o 2 W 2  Yc    o 21 -  o 22

2 -  o 2

1 2

(A9.4-14)

(A9.4-15a)

(A9.4-15b)

where Yc = compressed thickness of the double layers, ft  o 1 = reference density of first layer, lb/ft [3]

o 2 = reference density of second layer, lb/ft [3]

W 1 = reference weight of first layer, lb/ft [2]

W 2 = reference weight of second layer, lb/ft [2]

The solutions to Equation A9.4-14 are Equations A9.4-15a and A9.4-15b:

where a = 1

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 269

PDF Page 272

Open page note

b =

c =

---------------------------------------------------- - - 1   o 21 -  o 22  Yc  12 

----------------------------------------------- -   o 21 -  o 22  Yc  12

o 2 W 2  o 2 -  o 2 1 2

o 1 W 1 +  o 2 W 2

2 -  o 2

1 2

o 2 1

2 -  o 2

1 2

Select the smaller value of Y 2, a and Y 2, b as Y 2. Y 1 shall be calculated as the difference between Yc and Y 2. Next, the R-values for the two compressed layers of insulation shall be calculated and converted to a U-factor . This process shall be repeated along the entire profile and the results numerically integrated using maximum 0.04167 ft increments. It is important to note that Equation A9.4-14 does not apply when the two layers of insulation are the same material. In this case, each compressed layer has the same thickness, which simplifies the U-factor calculations. The numerical integration still needs to be completed to determine the Uco .

Step 3: Determine the U-factor over the structural framing member. The variable Yo represents the thickness of the thermal spacer block and the thickness of the compressed insulation. The density of the compressed insulation is determined by Equation A9.4-16:

c

=  --------- oto tc

where

c = density of the compressed insulation over the framing member, lb/ft [3]

tc = thickness of the compressed insulation over the framing member, ft The thermal resistance of the compressed insulation is determined by Equation A9.4-17:

(A9.4-16)

(A9.4-17)

Rc

= ------------------------------------- tc - A + Bc + C   c

Determine the overall framing U-factor ( Ufo ) at the structural framing member, including the air film resistances, using Equation A9.4-18:

Ufo

1 = ------------------------------------------- - RTB + Rc + Ri + Re

(A9.4-18)

where Ufo = U-factor over the structural framing member, Btu/h·ft [2] ·°F RTB = R-value of the thermal spacer block, h·ft [2] ·°F/Btu Rc = R-value of the compressed insulation, h·ft [2] ·°F/Btu Step 4: Determine the overall area-weighted U-factor for the entire system using Equation A9.4-19:

Ues

= L --------------------------------------------------------  Uco +  wf  2   Ufo L +  wf  2 

where Ues = area-weighted U-factor for the entire system, Btu/h·ft [2] ·°F

Step 5: Calculate the adjusted overall U-factor ( Uadj ) using Equation A9.4-20:

(A9.4-19)

(A9.4-20)

Uadj

1 = --------------------------------------------------0.8676  Ues + 1.1423

where Uadj = adjusted overall U-factor represented by correlation with the finite element modeling, Btu/h·ft [2] ·°F Step 6: If there is any continuous insulation present, calculate the overall U-factor using Equation A9.4-21:

Uo

1 = ---------------------- - 1 -------- Uadj - + Rci

(A9.4-21)

A9.4.6.3 Single-Layer in Cavity and Double-Layer Walls. The U-factor of metal building walls that are insulated with a single-layer in cavity or multiple layers of mineral fiber insulation (see Figure A9.4.6.3) shall be calculated using the procedure outlined in this section. For double-layer walls, the procedure assumes that the outer layer of insulation is compressed between the wall panel and girt. There may also be

270 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 273

Open page note

a thermal spacer block or continuous insulation present. Air spaces may also exist depending on the specific drape profiles.

There are nine steps in the calculation process:

  • Step 1—Characterize the thermal conductivity of the mineral fiber insulation.

  • Step 2—Define the parabolic profiles for each insulation layer.

  • Step 3—Calculate the R-values for insulation and air spaces in cavity both outside and inside insulation layers, including air films.

  • Step 4—Calculate the R-value inside the girt and adjacent to the web.

  • Step 5—Calculate the R-value outside the girt.

  • Step 6—Add the R-values inside and outside the girt, including air films.

  • Step 7—Calculate the overall insulation assembly using the R-values in Steps 3 and 6.

  • Step 8—Calculate the U-factor from the finite element analysis results.

  • Step 9—Calculate the U-factor for any continuous insulation if present.

Step 1: The thermal conductivity of the mineral fiber insulation is represented by a thermal curve of the form in Equation A9.4-22:

(A9.4-22)

= A + B --------- o - o + C --------- y - yoo

k = A + B

oo

where k = thermal conductivity, Btu·ft/h·ft [2] ·°F  - = nominal density, lb/ft [3]

 - = nominal thickness, ft y = thickness of insulation, ft A = 0.014917 B = 0.0004377 C = 0.0056897 Step 2: Assume that each layer of mineral fiber has a parabolic profile defined by Equation A9.4-23:

---------------- y - Yo - = ----- x  2 - ----- xYm - Yo xmxm

(A9.4-23)

where x = distance from edge of girt, ft y = distance from edge of wall panel, ft Yo = insulation thickness at x = 0, ft Ym = insulation thickness at x = Xm, ft Step 3: Calculate R-values for the insulation and air spaces in the cavity both inside and outside insulation layers, including air films.

Because the configuration can possibly consist of both mineral fiber insulation and an air space, the composite is given by Equation A9.4-24:

R = ---- x 1 a  x 0 a  k ---- ya + Y ------------- mk – y

xa  ---- y + Y ------------- m - y -  dx + ------------ Ym -

0  ka kkYm

1 xa

= ---- 

 ---- y + ------------- m -  dx  k k

(A9.4-24)

where ka is the thermal conductivity of air in Btu·ft/h·ft [2] ·°F.

The trapezoidal integration method is used to evaluate the integral and calculate R and is given by Equation A9.4-25:

b

 f  x dx

a

 12 [-] [-]  Nk = 1  xk + 1 – xk  yk + yk + 1 

(A9.4-25)

where xk = point to analyze along the x -axis, ft xk +1 = point ahead of the point being analyzed, ft yk = thickness at point being analyzed, ft yk +1 = thickness at point ahead of the point being analyzed, ft

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 271

PDF Page 274

Open page note

Figure A9.4.6.3 Geometry of single cavity layer or double-layer wall.

The integral represents the combined R-value of the air space and insulation over the region 0 < x < Xa . Because the thermal conductivity of air is independent of the thickness, Equation A9.4-25 can be simplified using the air space mean thickness ( Ya ) to produce Equation A9.4-26:

 ------------- m -  dx  K

R

= ---- Ya - + -----1  xa

---- KYa - a + ----- X 1 a  x 0 a  Y ------------- mK – y

xaY ------------- m - y -  dx + --------------- Ym

0  KKYm

(A9.4-26)

However, if the air space is characterized by convection instead of conduction then the term Ya / ka can be replaced by the R-value for convection (R-0.92 h·ft [2] ·°F/Btu for walls ). Adding the inside and outside layers is expressed in Equation A9.4-27:

RBP = R 1 BP + R 2 BP

(A9.4-27)

Add the air film resistances at the exterior ( RAT ) and interior ( RAB ), which are defined as Equation A9.4-28:

RAB

1 = -------hAB

where hAB is the air film heat transfer coefficient at the exterior in Btu/h·ft [2] ·°F.

(A9.4-28)

(A9.4-29)

RAT

1 = ------ - hAT

where hAT is the air film heat transfer coefficient at the interior in Btu/h·ft [2] ·°F.

The sum of the R-values for the insulation and air films beyond the girt are expressed in Equation A9.4-30.

RBP + air = RBP + RAB + RAT

(A9.4-30)

272 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 275

Open page note

Step 4: Calculate the R-values inside the girt and adjacent to the web. The R-values inside the girt are the air space (RAUP) added in series with the insulation (R2UP); their combined value is then added in parallel to RPUP. Depending on the thickness of the air space, it can be modeled as conduction as shown in Equation A9.4-31:

H 3 RAUP = ------ ka

(A9.4-31)

where H 3 = thickness of the air space, ft ka = thermal conductivity of air, Btu·ft/h·ft [2] ·°F When appropriate, the air space can be modeled as convection, which is a constant R-0.92 h·ft [2] ·°F/Btu for walls .

The R-value for R2UP is expressed in Equation A9.4-32. The insulation thickness is also not limited by the girt height and can extend beyond it.

H 4 R2UP =

= ----------------------------------------------

(A9.4-32)

  • B --------- - + C --------- -

H 4  oo

A + B

oo

--------- o - o + C --------- [H] [4] H 4  

where H 4 is the thickness of the mineral fiber at x = 0 in feet.

The R-value of the web (RPUP) is calculated using 26.2 h·ft [2] ·°F/Btu as the thermal conductivity of the girt in Equation A9.4-33:

Web Height RPUP = --------------------------- -

kp

(A9.4-33)

where kp = thermal conductivity of the girt, Btu·ft/h·ft [2] ·°F Web Height = height of the girt, ft The addition of the air space and insulation in series are combined to be in parallel with the girt, which is expressed as Equation A9.4-34:

----------- Lf = ----------------------------------- Lf - tp - + ------------- tp - RUP RAUP + R2UP RPUP

Equation A9.4-34 can be rearranged and solved for RUP as presented in Equation A9.4-35:

 RAUP + R2UP  RPUP RUP = ---------------------------------------------------------------------------------------  Lf - tp  RPUP + tp  RAUP + R2UP  Lf

(A9.4-34)

(A9.4-35)

Because the thickness of the girt is significantly less than the flange width ( Lf ), Equation A9.4-35 can be simplified as Equation A9.4-36. However it is important to note that RUP will be close to 2 or lower (depending on how the air is modeled) because of the significant effects of the steel girt:

 RAUP + R2UP  RPUP RUP = ------------------------------------------------------------------------ Lf RPUP + tp  RAUP + R2UP  Lf

(A9.4-36)

Step 5: Calculate the R-value outside the girt. Typical construction above the girt consists of a thermal spacer block and compressed mineral fiber insulation. These two insulations are in series, and the total R-value ( ROPI ) is expressed as Equation A9.4-37. If there is thermal break tape present it is included as the third insulation in this series.

(A9.4-37)

ROPI

= ------- + ------ kf kI

H 1

H 1 H 2

------- + ------kf kI

where H 1 = thickness of thermal spacer block, ft H 2 = thickness of compressed mineral fiber insulation, ft kf = thermal conductivity of the thermal spacer block, Btu·ft/h·ft [2] ·°F kI = thermal conductivity of the compressed mineral fiber insulation, Btu·ft/h·ft [2] ·°F

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 273

PDF Page 276

Open page note

The impact of the thermal bridging associated with the outside of the girt and the insulation is to reduce the thermal resistance of the insulation. The reduction is calculated using Equation A9.4-38:

(A9.4-38)

1 + ---------------------------- Lf

ROP = ROPI

1

Step 6 : Add the R-values inside and outside the girt including air films. The total thermal resistance associated with the girt is the sum of the R-values inside and outside the girt as shown in Equation A9.4-39:

RTP = RUP + ROP

(A9.4-39)

The next calculation is to add the inside and outdoor air film coefficients using Equation A9.4-40:

RTP + air = RTP + RAB + RAT

Step 7: Calculate the overall insulation assembly using the R-values in Steps 3 and 6. The overall insulation system R-value is determined using Equation A9.4-41:

Rinsul - sys

= --------------------------------------------------------------  2 L 1 + LfRBP + airRTP + air - 2 L 1 RTP + air + LfRBP + air

Step 8: Calculate the U-factor from the finite element analysis results. The overall U-factor for the insulation assembly is determined using Equation A9.4-42:

(A9.4-40)

(A9.4-41)

(A9.4-42)

Uadj

1 = ---------------------------------------------------------- - 0.8627 Rinsul - sys + 1.132

where Uadj = adjusted overall U-factor represented by the correlation with the finite element modeling in Btu/ h·ft [2] ·°F. Step 9: Calculate the overall U-factor for any continuous insulation if present. If there is any continuous insulation present, first calculate the R-value adjacent to the flange using Equation A9.4-43:

= R ----------------------------

RBFci = Rci

1 + 2--------------  hci

1

(A9.4-43)

  • ------------- Lf

where RBFci = thermal resistance of continuous insulation adjacent to the flange, h·ft [2] ·°F/Btu Rci = thermal resistance of the continuous insulation, h·ft [2] ·°F/Btu hci = thickness of the continuous insulation, ft Next, calculate the area-weighted R-value for the continuous insulation using Equation A9.4-44:

Roci

=  ---------------------------------------------2 L 1 + LfRBPciRci 2 L 1 RBPci + LfRci

where Roci = overall thermal resistance of continuous insulation in h·ft [2] ·°F/Btu Finally, calculate the overall U-factor using Equation A9.4-45:

(A9.4-44)

(A9.4-45)

Uo

1 = -------------------------1 -------- Uadj - + Roci

A9.4.7 Insulated Metal Panels. U-factors of insulated metal panels shall be determined by two- or threedimensional finite difference or finite volume computer models or by testing in accordance with Section A9.3.2 and shall include panel side joints.

A10. THERMAL BRIDGING CHI FACTORS AND PSI FACTORS

A10.1 Determination of Psi-Factors and Chi-Factors. Psi-factor (ψ) and chi-factor (χ) values representative of an as-designed thermal bridging condition shall be determined in accordance with one of the following:

274 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 277

Open page note

a. From simulation models compliant with ISO 10211 using details representative of the actual construc tion and modeling assumptions consistent with generally accepted architectural and engineering practice. b. From ISO 14683. c. From testing of the assembly in accordance with ASTM C1363 with and without the presence of the

thermal bridge condition to determine a linear transmittance value or point transmittance value for the thermal bridge condition. d. From application of heat transfer theory in accordance with generally accepted engineering practice and

where approved by the a uthority having jurisdiction . e. As indicated in Table A10.1. The default column shall be used where the thermal bridge meets prescrip tive requirements. The unmitigated column shall be used where the thermal bridge does not meet the prescriptive requirements.

( Informative Note: In Table A10.1, the values for thermal bridge details prescribed in Section 5.5.5 are based on data from ASHRAE Research Project 1365 and the BC Hydro Thermal Bridging Guide listed in Informative Appendix E.)

A10.2 Assembly U-Factor Adjustment for Simulation of Thermal Bridges. For the purpose of incorporating the effects of thermal bridges in simulations as required by Section 12 and Normative Appendix G, where a thermal bridge is not modeled as a separate element, the clear-field U-factors of modeled assemblies shall be modified in accordance with Equation A10.2. This modification shall be achieved in the simulation model by altering the conductance value assigned to any one or more insulation layers within the modeled assembly without altering the properties of modeled building material layers.

Utot = {[(∑ψ i × Li ) + (∑χ j × nj )]/ Atotal ) + Uo } (A10.2)

where Utot = overall thermal transmittance, including the effect of linear thermal bridges and point thermal bridges not included in the construction assembly Uo -factor, Btu/(h·ft [2] ·°F) Uo = clear-field thermal transmittance of the construction assembly as determined in accordance with Section 5, Btu/(h·ft [2] ·°F) Atotal = total opaque projected surface area of the construction assembly, ft [2]

ψ i = psi-factor, thermal transmittance for each type of linear thermal bridge, Btu/(h·ft [2] ·°F) Li = length of a particular linear thermal bridge as measured on the outside surface of the building envelope, ft [2]

χ i = chi-factor, thermal transmittance for each detail type of point thermal bridge, Btu/(h·°F) ni = number of occurrences a particular type of point thermal bridge

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 275

PDF Page 278

Open page note

Table A9.2-1 Effective Insulation/Framing Layer R-Values for Roof and Floor Insulation Installedbetween Metal Framing (4 ft on Center)

Rated R-Value of
Insulation
Correction
Factor
Framing/Cavity
R-Value
0.001.000.00
4.000.973.88
5.000.964.80
8.000.947.52
10.000.929.20
11.000.9110.01
12.000.9010.80
13.000.9011.70
15.000.8813.20
16.000.8713.92
19.000.8616.34
Rated R-Value of
Insulation
Correction
Factor
Framing/Cavity
R-Value
20.000.8517.00
21.000.8417.64
24.000.8219.68
25.000.8120.25
30.000.7923.70
35.000.7626.60
38.000.7428.12
40.000.7329.20
45.000.7131.95
50.000.6934.50
55.000.6736.85

Table A9.2-2 Effective Insulation/Framing Layer R-Values for Wall Insulation Installed Between Steel Framing

Empty Cavity, No Insulation

4 3.5 R-0.91 0.79 0.91

Insulated Cavity

43.5R-115.56.6
43.5R-136.07.2
43.5R-156.47.8
66.0R-197.18.6
66.0R-217.49.0
88.0R-257.89.6

Table A9.4.2-1 R-Values for Cavity Air Spaces [ a]

ComponentAir Space
Thickness,
in.
Climate Zone 1 Effective
Emittance
Col4Col5Col6Climate Zone 2 Effective
Emittance
Col8Col9Col10Climate Zone 3 Effective
Emittance
Col12Col13Col14
ComponentAir Space
Thickness,
in.
0.050.200.500.820.050.200.500.820.050.200.500.82
Roof0.502.51.91.20.92.41.81.20.92.21.71.10.9
Roof0.753.52.41.41.03.22.21.41.02.82.01.30.9
Roof1.505.63.11.71.14.92.91.61.14.22.51.51.0
Roof3.508.03.81.91.27.03.41.71.15.93.01.61.1
Wall0.502.51.81.20.92.51.81.20.92.51.81.20.9
Wall0.752.82.01.30.92.82.01.30.92.82.01.30.9
Wall1.502.51.81.20.92.51.81.20.92.51.81.20.9
Wall3.502.61.91.30.92.61.91.30.92.61.91.30.9

a. Interpolation shall be permitted to be used for effective emittance values and air space thicknesses between those listed. Extrapolation below an effective emittance of 0.05 is not

permitted.

276 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 279

Open page note

Table A9.4.2-1 R-Values for Cavity Air Spaces [ a] (Continued)

Component
Floor
Component
Air Space
Thickness,
in.
Climate Zone 1 Effective
Emittance
Col4Col5Col6Climate Zone 2 Effective
Emittance
Col8Col9Col10Climate Zone 3 Effective
Emittance
Col12Col13Col14
Floor
Component
Component
Air Space
Thickness,
in.
0.050.200.500.820.050.200.500.820.050.200.500.82
Floor
Component
Component
0.501.61.31.00.81.81.41.00.81.91.51.10.8
Floor
Component
Component
0.751.71.41.00.82.01.51.10.82.41.71.20.9
Floor
Component
Component
1.501.91.51.10.82.51.81.20.93.22.11.30.9
Floor
Component
Component
3.502.11.61.10.83.22.01.20.94.32.41.41.0
Floor
Component
Component
Air Space
Thickness,
in.
average?
Climate Zone 4 Effective
Emittance
Climate Zone 4 Effective
Emittance
Climate Zone 4 Effective
Emittance
Climate Zone 4 Effective
Emittance
Climate Zone 5 Effective
Emittance
Climate Zone 5 Effective
Emittance
Climate Zone 5 Effective
Emittance
Climate Zone 5 Effective
Emittance
Climate Zone 6 Effective
Emittance
Climate Zone 6 Effective
Emittance
Climate Zone 6 Effective
Emittance
Climate Zone 6 Effective
Emittance
Floor
Component
Component
Air Space
Thickness,
in.
average?
0.050.200.500.820.050.200.500.820.050.200.500.82
2 facing layers e ittenceaverage?average?average?average?average?average?average?average?average?average?average?average?average?
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.502.01.61.10.81.91.51.10.81.81.41.00.8
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.752.51.81.20.92.31.71.10.92.11.61.10.8
Roof
Wall
Floor
Component
Roof
Wall
Floor
1.503.52.21.30.93.12.01.30.92.81.91.20.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
3.504.72.61.41.04.12.41.41.03.62.21.30.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.502.51.81.20.92.51.81.20.92.51.81.20.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.752.82.01.30.92.82.01.30.92.82.01.30.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
1.502.51.81.20.92.51.81.20.92.51.81.20.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
3.502.61.91.30.92.61.91.30.92.61.91.30.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.502.11.61.10.82.21.71.10.92.31.71.20.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.752.71.91.20.92.92.01.30.93.12.11.31.0
Roof
Wall
Floor
Component
Roof
Wall
Floor
1.503.92.41.41.04.32.61.51.04.72.71.51.1
Roof
Wall
Floor
Component
Roof
Wall
Floor
3.505.52.91.51.16.03.11.61.16.63.31.71.1
Roof
Wall
Floor
Component
Roof
Wall
Floor
Air Space
Thickness,
in.
Climate Zone 7 Effective
Emittance
Climate Zone 7 Effective
Emittance
Climate Zone 7 Effective
Emittance
Climate Zone 7 Effective
Emittance
Climate Zone 8 Effective
Emittance
Climate Zone 8 Effective
Emittance
Climate Zone 8 Effective
Emittance
Climate Zone 8 Effective
Emittance
Roof
Wall
Floor
Component
Roof
Wall
Floor
Air Space
Thickness,
in.
0.050.200.500.820.050.200.500.820.820.820.820.82
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.501.81.41.00.81.61.31.00.80.80.80.80.8
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.752.01.61.10.81.81.41.00.80.80.80.80.8
Roof
Wall
Floor
Component
Roof
Wall
Floor
1.502.61.81.20.92.11.61.10.80.80.80.80.8
Roof
Wall
Floor
Component
Roof
Wall
Floor
3.50
0.50
3.2
2.5
2.0
1.8
1.3
1.2
0.9
0.9
2.4
2.5
1.7
1.8
1.2
1.2
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.752.82.01.30.92.82.01.30.90.90.90.90.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
1.502.51.81.20.92.51.81.20.90.90.90.90.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
3.502.61.91.30.92.61.91.30.90.90.90.90.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.502.31.81.20.92.51.81.20.90.90.90.90.9
Roof
Wall
Floor
Component
Roof
Wall
Floor
0.753.22.21.41.03.42.31.41.01.01.01.01.0
Roof
Wall
Floor
Component
Roof
Wall
Floor
1.504.92.81.61.15.43.11.71.11.11.11.11.1
Roof
Wall
Floor
Component
Roof
Wall
Floor
3.506.93.41.71.17.73.71.81.21.21.21.21.2

a. Interpolation shall be permitted to be used for effective emittance values and air space thicknesses between those listed. Extrapolation below an effective emittance of 0.05 is not

permitted.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 277

PDF Page 280

Open page note

Table A9.4.2-2 Emittance Values of Various Surfaces and Effective Emittances of Air Spaces

SurfaceAverage
Emissivity e
Effective Emissivity of Air SpaceCol4
SurfaceAverage
Emissivity****e
One Surface****e; Other, 0.9Both Surfaces Emissivity****e
Aluminum foil, bright0.050.050.03a
Metalized film, testedb0.050.050.03a
Aluminum sheet0.120.120.06
Aluminum coated paper, polished0.200.200.11
Steel, galv., bright0.250.240.14
Aluminum paint0.500.470.32
Building materials: wood, paper, masonry,
nonmetallic paints
0.900.820.82
Regular glass0.840.770.72
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.
a. When referencing Table A9.4.2-1, use an effective_emittance_ of 0.05.
b. Tested_emittance_ in accordance with ASTM C1224 at 0.05 or less.

Table A9.4.3 Effective R-Values for Fiberglass

Insulation R-Value at Standard Thickness

Rated R-ValueCol23830222119151311
Standard Thickness, in.Standard Thickness, in.129.56.55.563.53.53.5
Nominal Lumber Size, in.Actual Depth of
Cavity, in.
Effective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined CavityEffective Insulation R-Values when Installed in a Confined Cavity
2  1211.2537
2  109.253230
2 87.252726222119
2 65.521202118
2  43.51413151311
2  42.59.8
2  41.56.36

278 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 281

Open page note

Table A9.4.4-1 R-Values for Building MaterialsCol2Col3
MaterialActual Size, in.R-Value
Carpet and Rubber Pad1.23
Concrete at R-0.0625/in.20.13
Concrete at R-0.0625/in.40.25
Concrete at R-0.0625/in.60.38
Concrete at R-0.0625/in.80.5
Concrete at R-0.0625/in.100.63
Concrete at R-0.0625/in.120.75
Gypsum board0.50.45
Gypsum board0.6250.56
Metal Deck0
Roofing, built-up0.3750.33
Soil at R-0.104/in.121.25
Steel, Mild10.0031807
Stucco0.750.08
Wood panels, 7/16 in.0.4380.62
Wood subfloor0.750.94
Wood, 2 4 at R-1.25/in.3.54.38
Wood, 2 6 at R-1.25/in.5.56.88
Wood, 2 8 at R-1.25/in.7.259.06
Wood, 2 10 at R-1.25/in.9.2511.56
Wood, 2 12 at R-1.25/in.11.2514.06
Wood, 2 14 at R-1.25/in.13.2516.56

Table A9.4.4-2 Thermal Conductivity of Concrete Block Material

Concrete Block Density, lb/ft3Thermal Conductivity, Btu·in/h·ft2·°F
803.7
854.2
904.7
955.1
1005.5
1056.1
1106.7
1157.2
1207.8
1258.9
13010.0
13511.8
14013.5

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 279

PDF Page 282

Open page note

Table A9.4.6.1 Fiberglass Reference Properties

R-Value, h·ft2·°F/BtuWeight, lb/ft2Density, lb/ft3Thickness, ft
100.1490.6050.2458
110.1680.6300.2667
130.1990.6280.3167
160.2430.6340.3833
190.2970.6530.4542
250.4270.7420.5750
300.5200.7660.6792

Table A10.1 Thermal Bridging Psi-Factors and Chi-Factors for Thermal Bridges

Col1Col2Col3UnmitigatedCol5DefaultCol7
Class of
Construction—
Wall, above
Grade
Thermal Bridge TypeSectionPsi-Factor,
Btu/(h·ft·°F)
Chi-Factor,
Btu/(h·°F)
Psi-Factor,
Btu/(h·ft·°F)
Chi-Factor,
Btu/(h·°F)
_Steel framed_and
metal buildings
Roof edge5.5.5.1.10.450N/A0.140N/A
_Steel framed_and
metal buildings
Parapet5.5.5.1.20.2890.1510.151
_Steel framed_and
metal buildings
Intermediate floor to_wall_ intersection5.5.5.2.10.4870.1770.177
_Steel framed_and
metal buildings
Intermediate floor balcony or overhang to opaque
wall intersection
5.5.5.2.20.4870.1770.177
_Steel framed_and
metal buildings
Intermediate floor balcony in contact with
vertical fenestration
5.5.5.2.20.9740.1770.177
_Steel framed_and
metal buildings
Cladding support5.5.5.30.3140.2170.217
_Steel framed_and
metal buildings
Wall to_vertical fenestration_ intersection5.5.5.40.2620.1120.112
_Steel framed_and
metal buildings
Other element and assembly intersections5.5.5.5N/A1.73N/A0.91
Mass
(exterior or
integral)
Roof edge5.5.5.1.10.500N/A0.100N/A
Mass
(exterior or
integral)
Parapet5.5.5.1.20.2380.1250.125
Mass
(exterior or
integral)
Intermediate floor to_wall_ intersection5.5.5.20.4760.1790.179
Mass
(exterior or
integral)
Intermediate floor balcony or overhang to opaque
wall intersection
5.5.5.2.20.4760.1790.179
Mass
(exterior or
integral)
Intermediate floor balcony in contact with
vertical fenestration
5.5.5.20.9740.1770.177
Mass
(exterior or
integral)
Cladding support5.5.5.30.2700.1860.186
Mass
(exterior or
integral)
Wall to_vertical fenestration_ intersection5.5.5.40.1880.1310.131
Mass
(exterior or
integral)
Other element and assembly intersections5.5.5.5N/A0.91N/A0.19

N/A = not applicable

280 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 283

Open page note

Class of Construction—

Wall, above

Chi-Factor,

Btu/(h·°F)

Wood-framed

and other

N/A = not applicable

Col1Col2Bridges (Continued)Col4Col5
UnmitigatedUnmitigatedUnmitigated
Thermal Bridge TypeSectionPsi-Factor,
Btu/(h·ft·°F)
Chi-Factor,
Btu/(h·°F)
Psi-Factor,
Btu/(h·ft·°F)
Roof edge5.5.5.1.10.500N/A0.100
Parapet5.5.5.1.20.5110.227
Intermediate floor to_wall_ intersection5.5.5.20.4760.286
Intermediate floor balcony or overhang to opaque
wall intersection
5.5.5.2.20.4760.286
Intermediate floor balcony in contact with
vertical fenestration
5.5.5.20.9740.177
Cladding support5.5.5.35.5.5.35.5.5.35.5.5.3
Wall to_vertical fenestration_ intersection5.5.5.40.313N/A0.083
Other element and assembly intersections5.5.5.55.5.5.55.5.5.55.5.5.5
Roof edge5.5.5.1.10.450N/A0.140
Parapet5.5.5.1.20.0320.032
Intermediate floor to_wall_ intersection5.5.5.2.10.3360.049
Cladding support5.5.5.30.1860.043
Wall to_vertical fenestration_ intersection5.5.5.40.1500.099
Other element and assembly intersections5.5.5.5N/A0.33N/A

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 281

PDF Page 284

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI require- ments for a standard and may contain material that has not been subject to public review or a consen- sus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX B (RETAINED FOR FUTURE USE)

Climatic data are no longer contained in this appendix. See Section 5.1.4 for requirements. Annex 1 of this standard contains

a. an extraction of ASHRAE Standard 169, Table B-1, “U.S. Climate Zones by State and County” (which is

normative for Standard 90.1), b. an extraction of ASHRAE Standard 169, Figure B-1, “Climate Zone for United States Counties” (which

is informative for Standard 90.1), c. an extraction of ASHRAE Standard 169, Table A-5, “Canada Stations and Climate Zones” (which is nor mative for Standard 90.1), d. an extraction of ASHRAE Standard 169, Table A-6, “International Stations and Climate Zones” (which

is normative for Standard 90.1), e. an extraction of ASHRAE Standard 169, Section A3, “Climate Zone Definitions” (which is normative

for Standard 90.1), f. an extraction of ASHRAE Standard 169, Table A-3, “Thermal Climate Zone Definitions” (which is normative for Standard 90.1), g. an extraction of ASHRAE Standard 169, Figure A-1, “Thermal Climate Zones as a Function of Heating

and Cooling Degree Days” (which is informative for Standard 90.1), and h. an extraction of ASHRAE Standard 169, Figure C-2, “World Climate Zones Map” (which is informative

for Standard 90.1).

282 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 285

Open page note

(This is a normative appendix and is part of this standard.)

NORMATIVE APPENDIX C METHODOLOGY FOR BUILDING ENVELOPE TRADE-OFF OPTION IN SECTION 5.6

C1. MINIMUM INFORMATION

The following minimum information shall be specified for the proposed design .

C1.1 At the Building Level. The floor area, broken down by space conditioning categories and building area type, shall be specified. Each building area type shall be chosen from Table 9.5.1.

C1.2 At the Exterior and Semiexterior Surface Level. The building envelope assembly type, gross area, orientation, tilt, and associated space conditioning category and building area type shall be specified. The surface shall be designated as exterior or semiexterior. A semiexterior surface separating a conditioned space from a semiheated space shall be specified with two associated space conditioning categories . A semiexterior surface separating a conditioned space from an unconditioned space shall be specified with an associated space conditioning category and with an adjacency to an unconditioned space . Exterior surfaces with the same building envelope assembly type and associated space conditioning category and building area type whose orientations differ by no more than 22.5 degrees and whose tilts differ by no more than 22.5 degrees are allowed to be described as a single surface.

C1.2.1 For Roofs. The class of construction, opaque area, U-factor, HC, and insulation position shall be specified. Where three-year-aged test data for the solar reflectance and three-year-aged thermal emittance of the exterior roof surface are available, the three-year-aged solar reflectance and three-year-aged thermal emittance shall be specified.

C1.2.2 For Above-Grade Walls. The class of construction, opaque area, U-factor, HC, and insulation position shall be specified.

C1.2.3 For Below-Grade Walls. The opaque area, average depth to the bottom of the wall, C-factor, HC, and insulation position shall be specified.

C1.2.4 For Floors. The class of construction, opaque area, U-factor, HC, and insulation position shall be specified.

C1.2.5 For Slab-on-Grade Floors. The class of construction, perimeter length, F-factor, and HC shall be specified.

C1.2.6 For Uninsulated Assemblies. All uninsulated assemblies (e.g., projecting balconies, perimeter edges of intermediate floor slabs, concrete floor beams over parking garages, roof parapet) shall be separately modeled.

C1.2.7 For Thermal Bridges Identified in Section 5.5.5. Thermal bridge inputs and specifications shall be individually identified for the thermal bridges indicated in Section 5.5.5 according to one of the following:

a. Where the thermal bridge complies with one of the requirements of Sections 5.5.5.1 through 5.5.5.5, no

additional inputs shall be required. b. Where the thermal bridge does not comply with one or more of the requirements of Sections 5.5.5.1

through 5.5.5.5, the linear thermal bridge type or point thermal bridge type, length or count, the assembly interrupted by this thermal bridge, and the psi-factor or chi-factor shall be specified. The input shall be a user-defined value or one of the unmitigated values from Table A10.1. c. Where Section 5.5.5 and Sections 5.5.5.1 through 5.5.5.5, including exceptions, are not applicable to the

thermal bridge, no additional inputs shall be required.

C1.3 For Opaque Doors. The class of construction, area, and U-factor shall be specified. Each opaque door shall be associated with a surface as described in Section C1.2 and shall have the orientation of that surface.

C1.4 For Fenestration. The class of construction, area, assembly U-factor, assembly SHGC, VT, and PF shall be specified for fenestration . Each fenestration element shall be associated with a surface as defined in Section C1.2 and shall have the orientation of that surface.

C1.5 For Continuous Air Barriers. The method of compliance used for continuous air barriers, either whole- building pressurization testing or verification, shall be specified.

C2. OUTPUT REQUIREMENTS

Output reports shall contain the following information.

C2.1 Name and contact information of the entity executing the simulation, and date of report.

C2.2 Location of the building, including street address and climate zone.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 283

PDF Page 286

Open page note

Figure C1.4 Skylight well dimensions.

C2.3 Location corresponding to the weather data used to perform the simulation.

C2.4 Simulation program used to perform the simulation.

C2.5 Tables summarizing the minimum information described in Section C1.

C2.6 All differences between the proposed envelope performance factor and the base envelope perfor- mance factor .

C2.7 Peak heating and cooling loads for building classes of constructions .

C2.8 The version of the software and the link to the website that contains the ASHRAE Standard 140 results for the version used in accordance with Section C3.1.4.

C2.9 For thermal bridges,

a. confirmation that the proposed design complies with the each of the requirements of Sections 5.5.5.1

through 5.5.5.5 including exceptions or b. where the proposed design does not comply with each of the individual requirements of Sections 5.5.5.1

through 5.5.5.5, list the thermal bridges, the proposed psi-factors, proposed chi-factors, and source information.

C3. SIMULATION GENERAL REQUIREMENTS

C3.1 Simulation Program. The simulation program shall be a computer-based software program for the analysis of energy consumption in buildings . The simulation program shall include calculation methodologies for the building components being modeled.

Informative Note: Examples of simulation programs include, but are not limited to, EnergyPlus and DOE-2.

C3.1.1 The simulation program shall be approved by the adopting authority and shall, at minimum, have the ability to explicitly model all of the following:

a. The base envelope performance factor, using only the input for the proposed envelope performance fac-

tor . The calculation procedure shall not allow the user to directly modify the building component characteristics of the base design. b. 8760 hours per year. c. Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat set points,

and HVAC system operation, defined separately for each day of the week and holidays. d. Thermal mass effects. e. The number of thermal zones in the proposed design or nine thermal zones, whichever is greater. f. Air economizers with integrated control. g. Continuous daylight dimming controls and photosensors .

C3.1.2 The simulation program shall have the ability to determine the proposed envelope performance factor and base envelope performance factor by calculating annual energy costs.

Informative Note: Neither the proposed envelope performance factor nor the base envelope perfor- mance factor are predictions of actual energy consumption or costs for the proposed design after construc- tion . Actual experience will differ from these calculations due to variations such as occupancy, building

284 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 287

Open page note

operation and maintenance, weather, energy use not covered by this procedure, changes in energy rates between design of the building and occupancy, and the precision of the calculation tool.

C3.1.3 The simulation program shall be capable of performing design load calculations to determine required HVAC equipment capacities and airflow rates in accordance with Section 6.4.2 for both the pro- posed design building envelope and the base design building envelope .

C3.1.4 Simulation Program Testing Requirements

C3.1.4.1 The simulation program shall be tested according to ASHRAE Standard 140, except for Sections 7 and 8, of Standard 140. The required tests shall include building thermal envelope and fabric load tests (Sections 5.2.1, 5.2.2, and 5.2.3), ground coupled slab-on- grade analytical verification tests (Section 5.2.4), space -cooling equipment performance tests (Section 5.3), space -heating equipment performance tests (Section 5.4), and air-side HVAC equipment analytical verification tests (Section 5.5), along with the associated reporting (Section 6).

C3.1.4.2 The test results and modeler reports shall be posted on a publicly available website and shall include the test results of the simulation program and input files used for generating the results along with the results of the other simulation programs included in ASHRAE Standard 140, Annexes B8 and B16. The modeler report in Standard 140, Annex A2, Attachment A2.7 shall be completed for results exceeding the maximum or falling below the minimum of the reference values and for omitted results.

C3.1.4.3 The testing shall be performed for the version of the simulation program used to calculate the proposed envelope performance factor and base envelope performance factor .

Informative Notes:

  1. There are no pass/fail criteria established by this requirement.
  2. Based on the Section 3 definition, simulation program includes the simulation engine and the corresponding user interface. The testing of a simulation program only meets the requirements of Section C3.1.4 for that simulation program and cannot be used as proxy for documenting compliance of another simulation program that uses the same simulation engine .

C3.2 Climatic Data. The simulation program shall perform the simulation using hourly values of climatic data, including temperature, humidity, solar radiation, and wind speed and direction from representative climatic data, for the proposed design building envelope location. For cities or urban regions for which several climatic data sources are available and for locations for which weather data are not available, the designer shall select available weather data that represent the climate at the construction site . Selected weather data shall be approved by the authority having jurisdiction .

C3.2.1 Surface Exposure. Semiexterior surfaces separating conditioned spaces from unconditioned spaces shall be simulated as exterior surfaces with no exposure to wind or solar radiation.

C3.3 Purchased Energy Rates. The following rates for purchased energy shall be used to determine the proposed envelope performance factor and the base envelope performance factor :

a. Electricity: 0.98/therm

Exception to C3.3: Where approved by the authority having jurisdiction, actual annual rates for purchased

energy or state average energy prices published by the Department of Energy’s Energy Information Administration shall be permitted. The same rates shall be used for both the proposed envelope perfor- mance factor and the base envelope performance factor .

C3.4 Compliance Calculations. The proposed envelope performance factor and base envelope perfor- mance factor shall be calculated using the same

a. simulation program, b. climatic data, and c. purchased energy rates .

C3.5 Calculation of Proposed Envelope Performance Factor. The simulation model for calculating the proposed envelope performance factor shall be developed in accordance with Sections C3.5.1 through C3.5.11.

C3.5.1 Space Conditioning. All conditioned spaces in the proposed design shall be simulated as being both heated and cooled, even if no cooling or heating system is being installed. Temperature control set points and schedules shall be consistent with those in the building envelope trade-off schedules and loads for the applicable building area type. All semiheated spaces shall be simulated as being heated and not cooled. The heating temperature control set point shall be 50°F for all hours.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 285

PDF Page 288

Open page note

C3.5.2 Model Geometry and Thermal Zones. The building model shall be divided into thermal zones described as follows:

a. Determine the ratio ( Rc ) of the floor area to the gross wall area for each unique combination of space

conditioning category and building area type. The index “c” refers to a combination of space condition- ing category and building area type as defined for each surface. b. Create a perimeter zone for each unique combination of building area type, above - grade - wall orienta-

tion, and space conditioning category . If there is more than one above - grade - wall assembly for a build- ing area type and orientation, each above - grade - wall assembly shall be placed end-to-end in the order it is defined. The area of each perimeter zone shall be the gross wall area of the zone times Rc or 1.25, whichever is smaller. c. For each unique combination of space conditioning category and building area type with Rc greater than

1.25, interior zones shall be created and used in the trade-off procedure. The area of the interior zone shall be the total area for the unique combination of space conditioning category and building area type less the area of the perimeter zones for that combination of space conditioning category and building area type. d. Create a below- grade zone for each unique combination of space conditioning category and building

area type associated with below-grade walls . If there is more than one below - grade - wall assembly for a building area type, each below- grade - wall assembly shall be placed end-to-end in the order it is defined. The area of each below- grade zone shall be the gross wall area of the zone times Rc or 1.25, whichever is smaller. e. The wall height and the height of each thermal zone shall be 15 ft. f. Roof area and floor area associated with each building area type shall be prorated among all zones of the corresponding building area type in proportion to the zone area of each zone. Roof area and floor area in each zone shall be centered in the horizontal plane of the zone with the same aspect ratio as the horizontal plane of the zone. g. Slab-on-grade floor perimeter associated with each building area type shall be prorated among perimeter

zones of the corresponding building area type in proportion to the area of each zone. h. Vertical fenestration area shall be assigned to the associated surface as described in Section C1.4. Verti-

cal fenestration shall be centered on the associated surface with the same aspect ratio as the associated surface. Windows with equivalent U-factor, SHGC, and VT that do not include fins may be combined into a single window on the associated surface. i. Skylight area shall be assigned to the associated surface as described in Section C1.4 and Figure C1.4, prorated among interior zones containing the roof area with which the skylight area is associated, in proportion to the associated roof area. If the total skylight area exceeds the associated roof area in interior zones, the remaining skylight area shall be prorated among perimeter zones containing the roof area with which the skylight area is associated, in proportion to the associated roof area. j. Each zone shall be modeled as being fully enclosed. Zone boundaries not created as described above shall be modeled as adiabatic interior surfaces.

C3.5.3 Daylight Area and Photosensor Location. Daylight areas and photosensors shall not be modeled in residential zones. In each nonresidential zone, daylight areas and photosensor locations shall be modeled in accordance with the following:

a. For each nonresidential zone associated with vertical fenestration, the daylight area shall be modeled as

directly adjacent to the vertical fenestration with a width equal to the width of the vertical fenestration and a depth equal to the head height of the vertical fenestration . b. In each nonresidential zone associated with skylights, the daylight area under skylights shall be modeled

as bounded, in each direction, by the edge of the skylight area plus 10 ft or the distance to the edge of the zone, whichever is less. c. For each daylight area associated with vertical fenestration, a photosensor shall be modeled as located at

the center of the width of the daylight area, at the depth of the daylight area and at a height of 3 ft. d. For each daylight area associated with a skylight, a photosensor shall be modeled as located at the center

of the horizontal plane of the skylight and at a height of 5 ft.

C3.5.4 Schedules. The schedule types listed in Section C3.1.1(c) shall be required input. The schedules shall be consistent with those in the building envelope trade-off schedules and loads [1] for the applicable building area type.

1 Schedules and internal loads by building area type are found at http://sspc901.ashraepcs.org/documents.php.

286 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 289

Open page note

C3.5.5 Building Envelope. The building envelope shall reflect the information specified in Section C1. Exception to C3.5.5: Where three-year-aged test data for the solar reflectance and three-year-aged ther mal emittance of the exterior roof surface are unavailable, the exterior roof surface shall be modeled with a solar reflectance of 0.30 and a thermal emittance of 0.90.

C3.5.5.1 Shading. Manually operated interior shades shall be modeled on all vertical fenestration . Shades shall be modeled to be in the lowered position when either the transmitted luminance is greater than 200 cd/ft [2] or the direct solar transmitted energy exceeds 30 Btu/h·ft [2] and then remain lowered for rest of the day. Shades shall be modeled with visible light transmittance of 0.10, visible light reflectance of 0.40, solar transmittance of 0.21, and solar reflectance of 0.23. Permanent shading devices such as fins and overhangs shall be modeled.

C3.5.5.2 Dynamic Glazing. Automatically controlled dynamic glazing is allowed to be modeled. Manually controlled dynamic glazing shall use the average of the minimum and maximum values for both SHGC and VT .

C3.5.5.3 Air Leakage. The air leakage rate of the building envelope ( I75Pa ) at a pressure differential of 75 Pa (0.30 in. of water) shall be 0.35 cfm/ft [2] of building envelope area when air leakage compliance is based on whole- building pressurization testing and shall be 0.45 cfm/ft [2] of building envelope area when air leakage compliance is based on verification. The air leakage of the building envelope shall be converted to the appropriate units to describe the air leakage as a function of the area of walls that separate conditioned spaces and semiheated spaces from the exterior as follows:

IAGW = 0.112 × I75Pa × S / AAGW where

I75Pa = air leakage rate of the building envelope (cfm/ft [2] ) at a fixed building pressure differential of 75 Pa (0.30 in. of water)

S = total area of the building envelope (ft [2] ) including the lowest floor, any below-grade walls or above-grade walls, and roof (including vertical fenestration and skylights )

IAGW = adjusted air leakage rate of the building envelope (cfm/ft [2] ) at a reference wind speed of 10 mph and relative to the area of the above-grade walls

AAGW = the total area of above-grade walls that comprise the building envelope, ft [2]

Exception to C3.5.5.3: If the simulation program cannot simulate air leakage as a function of the area

of walls that separate conditioned spaces and semiheated spaces from the exterior, the air leakage of the building envelope shall be converted to the appropriate units to describe the air leakage as a function of gross floor area as follows:

IFLR = 0.112 × I75Pa × S / AFLR where

IFLR = adjusted air leakage rate of the building envelope (cfm/ft [2] ) at a reference wind speed of 10 mph

and relative to the gross floor area

AFLR = gross floor area, ft [2]

C3.5.5.3.1 Air Leakage Schedule. To simulate air leakage as described in Section 5.4.3, infiltration shall be adjusted in accordance with the infiltration schedule in the building envelope trade-off schedules and loads for the applicable building area type.

C3.5.5.4 Thermal Bridges. Linear and point thermal bridges in the proposed design shall be either of the following:

a. Not modeled where option (a) or (c) is selected in Section C1.2.7. b. Entered as individual thermal bridge inputs of length or count where option (b) is selected in Section

C1.2.7 and addressed as follows:

  1. Individual thermal bridges in the proposed design that are indicated to comply with the requirements of Sections 5.5.5.1 through 5.5.5.5 need not be modeled.
  2. Individual thermal bridges in the proposed design that are indicated to not comply with the requirements of Sections 5.5.5.1 through 5.5.5.5 shall be modeled.
  3. Individual thermal bridges in the proposed design that are indicated to be not applicable with the requirements of Sections 5.5.5.1 through 5.5.5.5 need not be modeled. C3.5.6 Interior Surfaces. Interior surfaces shall be modeled with visible light reflectances of 0.80 for ceilings, 0.50 for walls, and 0.20 for floors. Interior surfaces shall be modeled with a thermal emittance of 0.90.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 287

PDF Page 290

Open page note

C3.5.7 Lighting. The modeled lighting power shall be determined using the lighting power density allowances in Table 9.5.1 for the applicable building area type. The modeled lighting power shall be adjusted in accordance with the lighting schedule in the building envelope trade-off schedules and loads for the applicable building area type. Fifty percent (50%) of lighting in daylight areas shall be modeled with continuous daylight dimming controls such that when sufficient daylight is available at the corresponding photosensor, lighting power is reduced to maintain a minimum 50 fc for conditioned spaces and 30 fc for semiheated spaces . The minimum light output for the continuous daylight dimming shall be 6% of peak light output. Power input shall be modeled as 20% of lighting power at the minimum light output and scaled linearly to 100% of lighting power at peak light output. C3.5.8 HVAC Systems. One HVAC system shall be provided for each thermal zone and shall have the following characteristics:

a. Constant-volume fan control. b. Electrically provided cooling with EER from Table 6.8.1-1, based on requirements for split- system air

conditioners with heating section type “all other” between 65,000 Btu/h and 135,000 Btu/h. The EER shall be adjusted to remove the fan power in accordance with Section 12.5.2(c). c. Gas furnace with constant thermal efficiency equal to the minimum AFUE allowed for gas-fired warm air furnaces with maximum capacity <225,000 Btu/h, in accordance with Table 6.8.1-5. d. The ventilation rate for each building area type shall be consistent with the ventilation rate in the build-

ing envelope trade-off schedules and loads for the applicable building area type. e. Air economizers, except in Climate Zones 0 and 1. The high-limit shutoff shall be “Fixed Dry Bulb” type

as described in Table 6.5.1.1.3. f. System design supply air rates shall be based on a supply-air-to-room-air temperature difference of 20°F in cooling. g. System capacities used in the annual simulation shall be 1.5 times the capacities determined by the sizing

simulations. h. Fans shall cycle ON whenever the space calls for heating or cooling. The fan power shall be 0.3 W/cfm,

and the fan energy shall be modeled explicitly.

C3.5.9 Miscellaneous Loads. Miscellaneous loads shall be modeled as included in the building envelope trade-off schedules and loads for the applicable building area type.

C3.5.10 Occupant Density. The occupant density shall be modeled according to the peak occupant density and the occupancy rate schedule in the building envelope trade-off schedules and loads for the applicable building area type.

C3.5.11 Heat Gain from Occupants. The sensible and latent heat gain due to occupants shall be modeled as included in the building envelope trade-off schedules and loads for the applicable building area type.

C3.6 Calculation of Base Envelope Performance Factor. The simulation model for calculating the base envelope performance factor shall modify the simulation model for calculating the proposed envelope perfor- mance factor as follows:

a. All opaque assemblies shall be modeled with the U-factor not greater than that required in Section 5.5.3

for the appropriate class of construction, space conditioning category, and climate zone. Mass walls and mass floors shall be modeled with HC equal to 7.2 Btu/ft [2] ·°F. All other opaque assemblies shall be modeled with the same HC as the proposed design . Mass walls shall be modeled with equal mass on each side of the insulation. All other opaque assemblies shall be modeled with insulation on the exterior. b. Thermal bridges :

  1. Where option (a) is selected in Section C1.2.7, no modifications to the assembly U-factors are required.
  2. Where option (b) is selected in Section C1.2.7, the U-factor of the assembly interrupted shall be modified per Section A10.2 using the default values in Table A10.1 for the appropriate class of construc- tion . Each of the linear thermal bridges or point thermal bridges identified in Sections 5.5.5.1 through 5.5.5.5 shall be modeled in the simulation model for calculating the proposed envelope performance. Where the balcony length in the proposed design is greater than allowed by Section 5.5.5.2.2, the area shall be reduced proportionally along each exposure until the limit set in Section 5.5.5.2.2 is met.
  3. Where option (c) is selected in Section C1.2.7, no modifications to the assembly U-factors are required. c. The exterior roof surfaces shall be modeled with a solar reflectance and thermal emittance as required in

Section 5.5.3.1.4(a). All other roofs, including roofs exempted from the requirements in Section 5.5.3.1.4, shall be modeled the same as in the proposed design . The above-grade wall surfaces of buildings shall be

288 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 291

Open page note

modeled with a solar reflectance and thermal emittance as required in Section 5.5.3.2.2 and Section 5.5.3.2.2(a). All other above-grade walls, including those exempt from the requirements in Section 5.5.3.2.2, shall be modeled the same as the proposed design . d. Fenestration shall be assumed to be flush with the wall or roof . Fenestration U-factor and SHGC shall

be the maximum allowed for the appropriate class of construction, space conditioning category, and climate zone in accordance with Section 5.5.4. Where there is no SHGC requirement, the SHGC shall be equal to 0.40 for all vertical fenestration and 0.55 for skylights . The VT for fenestration in the base envelope design shall be equal to 1.10 times the SHGC . The fenestration area for new buildings or additions shall be modeled the same as the proposed building unless the following apply:

  1. Where the fenestration area exceeds the maximum allowed by Section 5.5.4.2, the area shall be reduced proportionally along each exposure until the limit set in Section 5.5.4.2 is met.
  2. Where the fenestration area facing west or east of the proposed design exceeds the area limit set in Section 5.5.4.5, the baseline building performance shall be generated by simulating the building with its actual orientation and again after rotating the entire building 90, 180, and 270 degrees and averaging the results of the four simulations.
  3. Where the Normative Appendix C calculation is being used to determine energy credits in accordance with Section 11.5.2.1, for building use types included in Table G3.1.1-1 where the proposed fenestration area is less than the value in Table G3.1.1-1, vertical fenestration areas shall equal that in Table G3.1.1-1 based on the area of gross above-grade walls that separate conditioned spaces and semiheated spaces from the exterior. Follow additional fenestration modeling requirements for base- line building performance in Table G3.1. e. Manually operated interior shades shall be modeled on all vertical fenestration as described in Section

C3.5.5.1. Permanent shading devices, such as fins and overhangs, shall not be modeled. f. Daylight areas and photosensor locations shall be modeled as described in Section C3.5.3 after reducing the fenestration area as described in Section C3.6(d). g. The air leakage rate of the building envelope ( I75Pa ) at a fixed building pressure differential of 75 Pa

(0.30 in. of water) shall be 0.35 cfm/ft [2] and shall be converted to units for the energy model using the same method as the proposed envelope performance factor .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 289

PDF Page 292

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI require- ments for a standard and may contain material that has not been subject to public review or a consen- sus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX D (RETAINED FOR FUTURE USE)

Climatic data are no longer contained in this appendix. See Section 5.1.4 for requirements. Annex 1 of this standard contains extracts of material from ASHRAE Standard 169.

290 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 293

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements neces- sary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unre- solved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX E INFORMATIVE REFERENCES

This appendix contains informative references for the convenience of users of Standard 90.1 and to acknowledge source documents when appropriate. Some documents are also included in Section 13, “Normative References,” because there are other citations of those documents within the standard that are normative.

Address/Contact Information

Air Movement and Control Association(AMCA International, Inc.) 30 West University Drive Arlington Heights, IL 60004

American Society of Agricultural and Biological Engineers (ASABE) 2950 Niles Road St. Joseph, MI 49085

ASHRAE 180 Technology Parkway Peachtree Corners, GA 30092)

Associated Air Balance Council (AABC) 1015 18th St. NW Suite 603 Washington, DC 20036

ASTM International 100 Barr Harbor Drive P.O. Box C700 West Conshohocken, PA 19428-2959

BC Hydro Corporate Head Office 333 Dunsmuir Street Vancouver, B. C. V6B 5R3

Cooling Technology Institute (C TI) 3845 Cypress Creek Parkway, Suite 420 Houston, TX 77068 P.O. Box 681807, Houston, TX 77268

CWEC Climate Data Environment Canada Engineering Climate Datasets climate.weather.gc.ca/prods_servs/engineering_e.html

Hydraulic Institute (HI) 6 Campus Drive, First Floor North, Parsippany, NJ 07054-4405 pumps.org

Illuminating Engineering Society (IES) 120 Wall St. Fl 17 New York, NY 10005-4001 (212) 248-5000 www.ies.org

International Electechnical Commission (IEC) 3 rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland

International Standards Organization (ISO) Chemin de Blandonnet 8 CP 401-1214 Vernier, Geneva, Switzerland

Midwest Insulation Contractors Association (MICA) 16712 Elm Circle Omaha, NE 68130 www.micainsulation.org

National Environmental Balancing Bureau (NEBB) 8575 Grovemont Circle Gaithersburg, MD 20877 www.nebb.org

National Institute of Building Sciences (NIBS) 1090 Vermont Avenue NW, Suite 700 Washington, DC 20005-4950

National Renewable Energy Laboratory NREL/RReDC Attn: Pamela Gray-Hann 1617 Cole Blvd., MS-1612 Golden, Colorado, USA 80401

Sheet Metal and Air Conditioning Contractors SMACNA National Association 4201 Lafayette Center Drive Chantilly, VA 20151 www.smacna.org

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 291

PDF Page 294

Open page note

Reference Section

IES RP-8-18 Recommended Practice for Design and Maintenance of Roadway and Parking Facility Lighting

3.2

2021 ASHRAE Handbook—Fundamentals Appendix A, Chapter 26, or Chapter 33 5.5.5.5

NIBS Guideline 3-2012 Building Enclosure Commissioning Process BECx, Annex O 5.7.3.2, H1

ASTM E2947-21a Standard Guide for Building Enclosure Commissioning, Section 9.4

5.7.3.2, H1

ASTM E2947-21a Standard Guide for Building Enclosure Commissioning 5.9.1, H1

ASTM E2813-18 Standard Practice for Building Enclosure Commissioning 5.9.1, H1

CTI STD-201 OM (19) Operations Manual for Thermal Performance Certification of Evaporative Heat Rejection Equipment Cooling Technology Institute

6.4.1

MICA Insulation Standards, 9th Edition National Commercial and Industrial Insulation Standards 6.4.4.1.1

SMACNA Duct Construction Standards, 4th Ed. (2021) HVAC Duct Construction Standards, Metal and Flexible 6.4.4.2.1

SMACNA 016-2012 HVAC Air Duct Leakage Test Manual (Sections 3, 5, and 6) 6.4.4.2.2

ASHRAE Guideline 36-2021 High-Performance Sequences of Operation for HVAC Systems 6.5.3.8

ASHRAE Guideline 4-2019 Preparation of Operations and Maintenance Documentation for HVAC&R Systems

AABC, 7th Ed (2018) Associated Air Balance Council, National Standards for Total System Balance

ANSI/ASHRAE Standard 111-2008 (RA 2017) Measurement, Testing, Adjusting and Balancing of  Building HVAC Systems

6.7.3.2

6.7.3.3.1

6.7.3.3.1

ANSI/ASHRAE Standard 202-2018 Commissioning Process for Buildings and Systems 6.9.2, H1

ASHRAE Guideline 0-2019 The Commissioning Process 6.9.2, H1

ASHRAE Guideline 1.1-2007 HVAC&R Technical Requirements for the Commissioning Process

6.9.2, H1

NEBB Procedural Standards, 9th Ed. (2019) Procedural Standards for Building Systems Commissioning 6.9.2

2019 ASHRAE Handbook—HVAC Applications Chapter 51, Service Water Heating/ASHRAE 7.4.1, 7.5

ANSI/ASHRAE Standard 188-2021 Legionellosis: Risk Management for Building water Systems 7.4.4

ASHRAE Guideline 12-2020 Managing the Risk of Legionellosis Associated with Building Water Systems

ANSI/ASABE S640-2017 Quantities and Units of Electromagnetic Radiation for Plants (Photosynthetic Organisms)

IES RP-6-20 Recommended Practice for Sports and Recreational Area Lighting

7.4.4

9.4.4

9.5.2

ANSI/IES RP-28-20 Lighting and the Visual Environment for Senior Living 9.5.2

ANSI/IES/AVIXA RP-38-17 Recommended Practice: Lighting Performance for Small to Medium Sized Videoconferencing Rooms

ISO 25745-2:2015 Energy performance of lifts, escalators and moving walks— Part 2: Energy calculation and classification for lifts (elevators)

ISO 27327-1:2012 Air Curtain Units—Part 1: Laboratory Methods of Testing for Aerodynamic Performance Rating

9.5.2, 9.5.2.2

10.4.3.4

10.4.5

292 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 295

Open page note

Reference Section

ANSI/AMCA Standard 220-05 (R2012) Laboratory Methods of Testing Air Curtain Units for Aerodynamic Performance Rating

ANSI/HI 1.1-1.2-2014 Rotodynamic Centrifugal Pumps for Nomenclature and Definitions

ANSI/HI 2.1-2.2-2014 Rotodynamic Vertical Pumps or Radial, Mixed, and Axial Flow Types for Nomenclature and Definitions

10.4.5

10.4.7

10.4.7

www.ies.org/standards/lighting-library/the-interactiveilluminance-selector (includes recommended illuminance levels from the following standards):

The Interactive Illuminance Selector 11.5.2.5

ANSI/IES RP-1-2020 Recommended Practice: Lighting Offices Spaces

ANSI/IES RP-2-2020 Recommended Practice: Lighting Retail Spaces

ANSI/IES RP-3-2020 Recommended Practice: Lighting Educational Facilities

ANSI/IES RP-4-2020 Recommended Practice: Lighting Library Spaces

ANSI/IES RP-6-2020 Recommended Practice: Lighting Sports and Recreational Areas

ANSI/IES RP-7-2020 Recommended Practice: Lighting Industrial Facilities

ANSI/IES RP-8-2021 Recommended Practice: Lighting Roadway and Parking Facilities

ANSI/IES RP-9-2020 Recommended Practice: Lighting Hospitality Spaces

ANSI/IES RP-10-2020 Recommended Practice: Lighting Common Applications

ANSI/IES RP-11-2020 Recommended Practice: Lighting for Interior and Exterior Residential Environments

ANSI/IES RP-28-2020 Recommended Practice: Lighting and the Visual Environment for Older Adults and the Visually Impaired

ANSI/IES RP-29-2020 Recommended Practice: Lighting Hospital and Healthcare Facilities

ANSI/IES RP-30-2020 Recommended Practice: Lighting Museums

ANSI/IES RP-38-2017 Recommended Practice: Lighting Performance for Small to Medium Sized Videoconferencing Rooms

ANSI/IES RP-41-2020 Recommended Practice: Lighting Theaters and Worship Spaces

IES Lighting Measurements (LM) 83-12 Approved Method: IES Spatial Daylight Autonomy (sDA) and Annual Sunlight Exposure (ASE)

ANSI/ASHRAE Standard 209-2018 Energy Simulation Aided Design for Buildings Except LowRise Residential Buildings

11.5.2.5.3

12.1.1, G1.2.2

CWEC Canadian Weather for Energy Calculations 12.4.2

IWEC2 (ASHRAE) International Weather for Energy Calculations, Generation 2 12.4.2

TMY3 Typical Meteorological Year, Generation 3 12.4.2

ASHRAE Transactions 101(2). Hogan, J.F. 1995. Approach for opaque envelope U-factors for ASHRAE/IESNA 90.1-1989R

A1.1

ASHRAE Handbook—Fundamentals (2021) A9.4

ASHRAE Transactions 116(1):10–017 Choudhary, M.K., C. Kasprzak, R.H. Larson, and R. Venuturumilli. 2010. ASHRAE Standard 90.1 metal building U-factors—Part 1: Mathematical modeling and validation by calibrated hot box measurements

A9.4.6

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 293

PDF Page 296

Open page note

Reference Section

ASHRAE Transactions 116(1):10–018 Choudhary, M.K., and C.P. Kasprzak. 2010. ASHRAE Standard 90.1 Metal building U-factors—Part 2: A system based approach for predicting the thermal performance of single layer fiberglass batt insulation assemblies

ASHRAE Transactions 116(1):10–019 McBride, M.F., and P.M. Gavin. 2010. ASHRAE Standard 90.1 metal building U-factors—Part 3: Equations for double layers of fiberglass batt insulation in roof and wall assemblies

ASHRAE Transactions 116(1):10–020 Christianson, L. 2010. ASHRAE Standard 90.1 metal building U-factors—Part 4: Metal building U-factors for walls and roof based on experimental measurements.

ASHRAE Transactions 118(1):12–006 Choudhary, M.K., C.P. Kasprzak, D.E. Musick, M.J. Henry, and N.D. Fast. 2012. ASHRAE Standard 90.1 metal building U-factors—Part 5: Mathematical modeling of wall assemblies and validation by calibrated hot box measurements

ASHRAE Transactions 122(1):16–014 Choudhary, M.K 2016. A general approach for predicting the thermal performance of metal building fiberglass insulation assemblies

A9.4.6

A9.4.6

A9.4.6

A9.4.6

A9.4.6

A10.1

Table A10.1

BC Hydro New Construction Program Orientation Manual (June 2016)

https://www.bchydro.com/powersmart/business/programs/ new-construction.html#thermal

ASHRAE Research Project 1365 The Impact of Thermal Bridges on Effective Thermal Resistance and Energy Use in Mid and High Rise Buildings

2021 ASHRAE Handbook—Fundamentals Chapter 19 G2.2.3

ISO/IEC 17024:2012 Community Assessment—General Requirements for Bodies Operating Certification of Persons

294 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

H1

PDF Page 297

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI require- ments for a standard and may contain material that has not been subject to public review or a consen- sus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX F U.S. DEPARTMENT OF ENERGY MINIMUM ENERGY EFFICIENCY REQUIREMENTS,TEST PROCEDURES, AND DEFINITIONS

In the United States, the U.S. Department of Energy (U.S. DOE) establishes efficiency standards for products that it defines as “residential covered products.” Since these products are used in buildings covered by this standard, U.S. DOE efficiency requirements are shown here for convenience. All U.S. DOE efficiency requirements for residential products are found in the U.S. Code of Federal Regulations, 10 CFR 430.32.

DOE also establishes definitions and test procedures for covered products. These are found in 10 CFR 430.2 and 10 CFR 430.23, respectively.

F1. U.S. DOE MINIMUM ENERGY EFFICIENCY REQUIREMENTS FORSINGLE-PHASE AIR CONDITIONERS AND HEAT PUMPS

These standards became effective on January 1, 2015. In the United States, some of the standards are regional in nature. The U.S. has been divided into 3 regions: (a) the north, comprising states with a population weighted heating degree days (HDD) equal to or greater than 5000; (b) the southeast, comprising states with a population weighted HDD less than 5000; and (c) the southwest, comprising Arizona, California, Nevada, and New Mexico. The regions are shown in Figure F-1.

The U.S. federal minimum energy efficiency standards for single-phase air conditioners and heat pumps are shown in Table F-1. The standards apply to residential single-phase air conditioners and heat pumps that are rated at less than 65,000 Btu/h of cooling capacity.

F2. U.S. DOE MINIMUM ENERGY EFFICIENCY REQUIREMENTSFOR WATER HEATERS AND POOL HEATERS

These standards for Uniform Energy Factor became effective on December 29, 2017, and apply to products manufactured on or after that date and the thermal efficiency requirements for gas fired pool heaters manufactured on or after April 16, 2013 (Table F-2).

F3. U.S. DOE TEST PROCEDURE AND DEFINITIONS FOR CEILING FANS

U.S. DOE definitions for ceiling fans are found in 10 CFR 430.2 and 10 CFR Part 430, Subpart B, Appendix U. On or after January 23, 2017, manufacturers of ceiling fans must make any representations with respect to energy use or efficiency in accordance with the test procedure in 10 CFR Part 430, Subpart B, Appendix U. DOE also specifies, in 10 CFR 430.32, design requirements for ceiling fans, and for ceiling fans manufactured on or after January 21, 2020, minimum efficiency requirements.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 295

PDF Page 298

Open page note

Figure F-1 Map of the regions for the analysis of central air conditioners and heat pumps.  (Source: Federal Register 76 FR 37431, June 7, 2018)

Table F-1 Minimum Efficiency Requirements for Single-Phase Central Air Conditioners and Heat Pumpsfor Applications in the U.S.

Split-system
air conditioners for U.S.
applications
<45,000 Btu/h
single phase
SEER = 13.0
P  30 W
W,OFF
before 1/1/2023
SEER2 = 13.4
P  30 W
W,OFF
after 1/1/2023
SEER = 14.0
P  30 W
W,OFF
before 1/1/2023
SEER2 = 14.3
P  30 W
W,OFF
after 1/1/2023
SEER = 14.0
EER = 12.2
P  30 W
W,OFF
before 1/1/2023
SEER2 = 14.3
EER2 = 11.7/9.8 d
P  30 W
W,OFF
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Split-system
air conditioners
45,000 Btu/h and
<65,000 Btu/h
single phase
SEER = 13.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 13.4
PW,OFF  30 W
after 1/1/2023
SEER = 14.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 13.8
PW,OFF  30 W
after 1/1/2023
SEER = 14.0
EER = 11.7d
PW,OFF  30 W
before 1/1/2023
SEER2 = 13.8
EER2 = 11.2/9.8e
PW,OFF  30 W
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.

296 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 299

Open page note

Table F-1 Minimum Efficiency Requirements for Single-Phase Central Air Conditioners and Heat Pumpsfor Applications in the U.S.

Split-system
heat pumps
<65,000 Btu/h
single phase
SEER = 14.0
HSPF = 8.2
P  33 W
W,OFF
before 1/1/2023
SEER2 = 14.3
HSPF2 = 7.5
P  33 W
W,OFF
after 1/1/2023
SEER = 14.0
HSPF = 8.2
P  33 W
W,OFF
before 1/1/2023
SEER2 = 14.3
HSPF2 = 7.5
P  33 W
W,OFF
after 1/1/2023
SEER = 14.0
HSPF = 8.2
P  33 W
W,OFF
before 1/1/2023
SEER2 = 14.3
HSPF2 = 7.5
P  33 W
W,OFF
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Single-package
air conditioners
<65,000 Btu/h
single phase
SEER = 14.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 13.4
PW,OFF  30 W
after 1/1/2023
SEER = 14.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 13.4
PW,OFF  30 W
after 1/1/2023
SEER = 14.0
EER = 11.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 13.4
EER2 = 10.6
PW,OFF 30 W
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Single-package
heat pumps
<65,000 Btu/h
single phase
SEER = 14.0
HSPF = 8.0
PW,OFF  33 W
before 1/1/2023
SEER2 = 13.4
HSPF2 = 6.7
PW,OFF  33 W
after 1/1/2023
SEER = 14.0
HSPF = 8.0
PW,OFF  33 W
before 1/1/2023
SEER2 = 13.4
HSPF2 = 6.7
PW,OFF  33 W
after 1/1/2023
SEER = 14.0
HSPF = 8.0
PW,OFF  33 W
before 1/1/2023
SEER2 = 13.4
HSPF2 = 6.7
PW,OFF  33 W
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Small-duct
high-velocity_systems_
<65,000 Btu/h
single phase
SEER = 12.0
HSPF = 7.2
PW,OFF  30 W
before 1/1/2023
SEER2 = 12.0
HSPF2 = 6.1
PW,OFF  30 W
after 1/1/2023
SEER = 12.0
HSPF = 7.2
PW,OFF  30 W
before 1/1/2023
SEER2 = 12.0
HSPF2 = 6.1
PW,OFF  30 W
after 1/1/2023
SEER = 12.0
HSPF = 7.2
PW,OFF  30 W
before 1/1/2023
SEER2 = 12.0
HSPF2 = 6.1
PW,OFF  30 W
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Space-constrained
products—
air conditioners a
<65,000 Btu/h
single phase
SEER = 12.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 11.7
PW,OFF  30 W
after 1/1/2023
SEER = 12.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 11.7
PW,OFF  30 W
after 1/1/2023
SEER = 12.0
PW,OFF  30 W
before 1/1/2023
SEER2 = 11.7
PW,OFF  30 W
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
Space-constrained
products— heat pumps a
<65,000 Btu/h
single phase
SEER = 12.0
HSPF = 7.4
PW,OFF  33 W
before 1/1/2023
SEER2 = 11.9
HSPF2 = 6.3
PW,OFF  33 W
after 1/1/2023
SEER = 12.0
HSPF = 7.4
PW,OFF  33 W
before 1/1/2023
SEER2 = 11.9
HSPF2 = 6.3
PW,OFF  33 W
after 1/1/2023
SEER = 12.0
HSPF = 7.4
PW,OFF  33 W
before 1/1/2023
SEER2 = 11.9
HSPF2 = 6.3
PW,OFF  33 W
after 1/1/2023
AHRI 210/240-2017
before 1/1/2023
AHRI 210/240-2023
after 1/1/2023
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.
a. The Southeastern region for central air conditioners and heat pumps contains the following States: Alabama, Arkansas, Delaware, Florida, Georgia, Hawaii, Kentucky, Louisiana,
Maryland, Mississippi, North Carolina, Oklahoma, South Carolina, Tennessee, Texas, and Virginia, and the District of Columbia.
b. The Southwestern region for central air conditioners contains the States of Arizona, California, Nevada, and New Mexico.
c. SEER is_seasonal energy efficiency ratio_; EER is_energy efficiency ratio_; HSPF is_heating seasonal performance factor_; and Btu/h is British thermal units per hour.SEER2 is
seasonal energy efficiency ratio reflecting the new higher static that is effective 1/1/2023;EER2 is_energy efficiency ratio_ also reflecting the higher static; and_HSPF2_ is new_heating_
seasonal performance factor reflecting the new higher static and load line. Test and rating procedure defined in AHRI 210/240-2017 for_EER_, SEER, and_HSPF_ and AHRI 210/
240-2023 for_EER2_, SEER2, and_HSPF2_. The added “2” in the metric names reflects the new higher static (all metrics) and load line (HSPF2 only) for the new metrics effective
1/1/2023.
d. The 11.7_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_ EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
e. The 11.2_EER2_ standard applies to products with a certified_SEER2_ less than 15.2. The 9.8_EER2_ standard applies to products with a certified_SEER2_ greater than or equal to 15.2.
f. Section 13 contains a complete specification of the referenced test procedures, including the referenced year version of the test procedure.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 297

PDF Page 300

Open page note

Table F-2 Minimum Energy Efficiency Requirements for Water Heaters and Pool Heaters Source: 10 CFR Part 430, Energy Conservation Program: Energy Conservation Standards for Water Heaters

Product ClassRated Storage Volume and
input Rating (if applicable)
Draw PatternUniform Energy Factor (UEF) or
Thermal Efficiency (E)
t
Test Procedure
Gas-fired storage water
heater
20 gal and55 galVery smallUEF = 0.3456 – (0.0020 ×Vr)10 CFR 430
Appendix E
Gas-fired storage water
heater
20 gal and55 galLowUEF = 0.5982 – (0.0019 ×Vr)UEF = 0.5982 – (0.0019 ×Vr)
Gas-fired storage water
heater
20 gal and55 galMediumUEF = 0.6483 – (0.0017 ×Vr)UEF = 0.6483 – (0.0017 ×Vr)
Gas-fired storage water
heater
20 gal and55 galHighUEF = 0.6920 – (0.0013 ×Vr)UEF = 0.6920 – (0.0013 ×Vr)
Gas-fired storage water
heater
>55 gal and100 galVery smallUEF = 0.6470 – (0.0006 ×Vr)10 CFR 430
Appendix E
Gas-fired storage water
heater
>55 gal and100 galLowUEF = 0.7689 – (0.0005 ×Vr)UEF = 0.7689 – (0.0005 ×Vr)
Gas-fired storage water
heater
>55 gal and100 galMediumUEF = 0.7897 – (0.0004 ×Vr)UEF = 0.7897 – (0.0004 ×Vr)
Gas-fired storage water
heater
>55 gal and100 galHighUEF = 0.8072 – (0.0003 ×Vr)UEF = 0.8072 – (0.0003 ×Vr)
Oil-fired storage water
heater
50 galVery smallUEF = 0.2509 – (0.0012 ×Vr)10 CFR 430
Appendix E
Oil-fired storage water
heater
50 galLowUEF = 0.5330 – (0.0016 ×Vr)UEF = 0.5330 – (0.0016 ×Vr)
Oil-fired storage water
heater
50 galMediumUEF = 0.6078 – (0.0016 ×Vr)UEF = 0.6078 – (0.0016 ×Vr)
Oil-fired storage water
heater
50 galHighUEF = 0.6815 – (0.0014 ×Vr)UEF = 0.6815 – (0.0014 ×Vr)
Electric storage water
heaters
20 gal and55 galVery smallUEF = 0.8808 – (0.0008 ×Vr)10 CFR 430
Appendix E
Electric storage water
heaters
20 gal and55 galLowUEF = 0.9254 – (0.0003 ×Vr)UEF = 0.9254 – (0.0003 ×Vr)
Electric storage water
heaters
20 gal and55 galMediumUEF = 0.9307 – (0.0002 ×Vr)UEF = 0.9307 – (0.0002 ×Vr)
Electric storage water
heaters
20 gal and55 galHighUEF = 0.9349 – (0.0001 ×Vr)UEF = 0.9349 – (0.0001 ×Vr)
Electric storage water
heaters
>55 gal and120 galVery smallUEF = 1.9236 – (0.0011 ×Vr)10 CFR 430
Appendix E
Electric storage water
heaters
>55 gal and120 galLowUEF = 2.0440 – (0.0011 ×Vr)UEF = 2.0440 – (0.0011 ×Vr)
Electric storage water
heaters
>55 gal and120 galMediumUEF = 2.1171 – (0.0011 ×Vr)UEF = 2.1171 – (0.0011 ×Vr)
Electric storage water
heaters
>55 gal and120 galHighUEF = 2.2418 – (0.0011 ×Vr)UEF = 2.2418 – (0.0011 ×Vr)
Tabletop water heater20 gal and120 galVery smallUEF = 0.6323 – (0.0058 ×Vr)10 CFR 430
Appendix E
Tabletop water heater20 gal and120 galLowUEF = 0.9188 – (0.0031 ×Vr)UEF = 0.9188 – (0.0031 ×Vr)
Tabletop water heater20 gal and120 galMediumUEF = 0.9577 – (0.0023 ×Vr)UEF = 0.9577 – (0.0023 ×Vr)
Tabletop water heater20 gal and120 galHighUEF = 0.9884 – (0.0016 ×Vr)UEF = 0.9884 – (0.0016 ×Vr)
Instantaneous gas-fired
water heater
<2 gal and >50,000 Btu/hVery smallUEF = 0.8010 CFR 430
Appendix E
Instantaneous gas-fired
water heater
<2 gal and >50,000 Btu/hLowUEF = 0.81UEF = 0.81
Instantaneous gas-fired
water heater
<2 gal and >50,000 Btu/hMediumUEF = 0.81UEF = 0.81
Instantaneous gas-fired
water heater
<2 gal and >50,000 Btu/hHighUEF = 0.81UEF = 0.81
Instantaneous electric
water heater
<2 galVery smallUEF = 0.9110 CFR 430
Appendix E
Instantaneous electric
water heater
<2 galLowUEF = 0.91UEF = 0.91
Instantaneous electric
water heater
<2 galMediumUEF = 0.91tUEF = 0.91t
Instantaneous electric
water heater
<2 galHighUEF = 0.92UEF = 0.92
Grid-enabled water
heaters
>75 galVery smallUEF = 1.0136 – (0.0028 ×Vr)10 CFR 430
Appendix E
Grid-enabled water
heaters
>75 galLowUEF = 0.9984 – (0.0014 ×Vr)UEF = 0.9984 – (0.0014 ×Vr)
Grid-enabled water
heaters
>75 galMediumUEF = 0.9853 – (0.0010 ×Vr)UEF = 0.9853 – (0.0010 ×Vr)
Grid-enabled water
heaters
>75 galHighUEF = 0.9720 – (0.0007 ×Vr)UEF = 0.9720 – (0.0007 ×Vr)
Pool heater gas82%_ Et_10 CFR 430
Appendix P

a. Vr is the rated storage volume (in gallons), as determined pursuant to 10 CFR 429.17. b. Standards for electric storage water heaters apply to both electric resistance water heaters and heat-pump water heaters.

298 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 301

Open page note

Table F-3 Minimum Efficiency Requirements for Room Air Conditioners for U.S. Applications

Product
Class
Capacity
Range
Efficiency
Requirementsa
Test
Procedureb
Room air conditioners without reverse cycle
with louvered sides
<6,000 Btu/hCEER = 11.010 CFR 430 Appendix F
Room air conditioners without reverse cycle
with louvered sides
6,000 Btu/h and <8,000 Btu/hCEER = 11.0CEER = 11.0
Room air conditioners without reverse cycle
with louvered sides
8,000 Btu/h and <14,000 Btu/hCEER= 10.9CEER= 10.9
Room air conditioners without reverse cycle
with louvered sides
14,000 Btu/h and <20,000 Btu/hCEER = 10.7CEER = 10.7
Room air conditioners without reverse cycle
with louvered sides
20,000 Btu/h and <28,000 Btu/hCEER = 9.4CEER = 9.4
Room air conditioners without reverse cycle
with louvered sides
28,000 Btu/hCEER= 9.0CEER= 9.0
Room air conditioners without reverse cycle without
louvered sides
<6,000 Btu/hCEER = 10.010 CFR 430 Appendix F
Room air conditioners without reverse cycle without
louvered sides
6,000 Btu/h and <8,000 Btu/hCEER = 10.0CEER = 10.0
Room air conditioners without reverse cycle without
louvered sides
8,000 Btu/h and <11,000 Btu/hCEER= 9.6CEER= 9.6
Room air conditioners without reverse cycle without
louvered sides
11,000 Btu/h and <14,000 Btu/hCEER = 9.5CEER = 9.5
Room air conditioners without reverse cycle without
louvered sides
14,000 Btu/h and <20,000 Btu/hCEER = 9.3CEER = 9.3
Room air conditioners without reverse cycle without
louvered sides
20,000 Btu/hCEER= 9.4CEER= 9.4
Room air conditioners with reverse cycle
with louvered sides
<20,000 Btu/hCEER= 9.810 CFR 430 Appendix F
Room air conditioners with reverse cycle
with louvered sides
20,000 Btu/hCEER= 9.3CEER= 9.3
Room air conditioners with reverse cycle
without louvered sides
<14,000 Btu/hCEER= 9.310 CFR 430 Appendix F
Room air conditioners with reverse cycle
without louvered sides
14,000 Btu/hCEER= 8.7CEER= 8.7
Room air conditioners, casement onlyAllCEER= 9.510 CFR 430 Appendix F
Room air conditioners, casement sliderAllCEER= 10.410 CFR 430 Appendix F

a. Source: Federal Register 76 FR 37431, June 27, 2011. b. Section 13 contains a complete specification of the referenced test procedures.

Table F-4 Residential Furnaces—Minimum Efficiency Requirements for U.S. Applications (see 10 CFR 430)

Product
Class
Size Category
(input)
Subcategory or
Rating Condition
Minimum
Efficiency
Test
Procedurea
Furnace, gas fired<225,000 Btu/hNonweatherized excluding mobile home80% AFUE10 CFR 430 Appendix N
Furnace, gas fired<225,000 Btu/hNonweatherized mobile home80% AFUE80% AFUE
Furnace, gas fired<225,000 Btu/hWeatherized81% AFUE81% AFUE
Furnace oil fired<225,000 Btu/hNonweatherized excluding mobile home83% AFUE
PW,SB  11 W
PW,OFF  11 W
10 CFR 430 Appendix N
Furnace oil fired<225,000 Btu/hNonweatherized mobile home75% AFUE
PW,SB  11 W
PW,OFF  11 W
75% AFUE
PW,SB  11 W
PW,OFF  11 W
Furnace oil fired<225,000 Btu/hWeatherized78% AFUE78% AFUE
Electric furnace<225,000 Btu/hAll78% AFUE
PW,SB  10 W
PW,OFF  10 W
10 CFR 430 Appendix N

a. Section 13 contains a complete specification of the referenced test procedure.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 299

PDF Page 302

Open page note

Table F-5 Residential Boiler [ a] Minimum Efficiency Requirements for U.S. Applications (see 10 CFR 430)

Gas-fired hot-water boiler

Gas-fired steam boiler

Oil-fired hot-water boiler

Oil-fired steam boiler

Electric hot-water boiler

Electric steam boiler

Constant burning pilot not permitted. Automatic means for adjusting water temperature required (except for boilers equipped with tankless domestic water heating coils) [ d] .

Constant burning pilot not permitted.

Automatic means for adjusting temperature required (except for boilers equipped with tankless domestic water heating coils) [ d] .

None

Automatic means for adjusting temperature required (except for boilers equipped with tankless domestic water heating coils) [ d] .

None

Minimum Efficiency bStandby Mode and
Off-Mode Power Consumption
84% AFUEPW,SB  9 W
PW,OFF  9 W
82% AFUEPW,SB  8 W
PW,OFF  8 W
86% AFUEPW,SB  11 W
PW,OFF  11 W
85% AFUEPW,SB  11 W
PW,OFF  11 W
NonePW,SB  8 W
PW,OFF  8 W
NonePW,SB  8 W
PW,OFF  8 W

a. Has a heat input rate of less than 300,000 Btu per hour for electric boilers and low-pressure steam or hot-water boilers (per § 430.2). b. Annual Fuel Utilization Efficiency, as determined in § 430.23(n)(2). c. Standby mode and off-mode electric power consumption as determined in § 430.23(n)(5). d. See § 430.32(e)(2)(iv) for additional details regarding automatic means for adjusting water temperature.

Table F-6 Ceiling Fan Efficiency Requirements for U.S. Applications (see 10 CFR 430)

Equipment TypeSize CategoryMinimum EfficiencyTest Procedure
Large-diameter ceiling fanBlade span ≥ 84.5 in.CFEI ≥ 1.00 at high (maximum) speed; and
CFEI ≥ 1.31 at 40% of high speed or the nearest
speed that is not less than 40% of high speed
10 CFR 430 Appendix U

300 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 303

Open page note

(This is a normative appendix and is part of this standard.)

NORMATIVE APPENDIX G PERFORMANCE RATING METHOD

G1. GENERAL

G1.1 Performance Rating Method Scope. This appendix offers an alternative path for minimum standard compliance in accordance with Section 4.2.1.1 when administered by a building official . It is also provided for those who wish to use this appendix to quantify performance that exceeds the requirements of this standard when administered by a rating authority and not seeking minimum standard compliance in accordance with Section 4.2.1.1. It shall be used for evaluating the performance of all such proposed designs, including alterations and additions to existing buildings, except designs with no mechanical systems . In the case where this appendix is administered solely by a building official to determine compliance with this standard in accordance with Section 4.2.1.1, all references to “ rating authority ” shall be replaced with “ building official.

G1.2 Performance Rating

G1.2.1 Mandatory Provisions. The proposed building design shall comply with all of the following:

a. Sections 5.2.1, 6.2.1, 7.2.1, 8.2.1, 9.2.1, and 10.2.1. b. Interior lighting power shall not exceed the interior lighting power allowance determined using either

  1. Tables G3.7-1 and G3.7-2 and the methodology described in Section 9.5.2, or
  2. Table G3.8 and the methodology described in Section 9.5.1. c. Energy efficiency levels of installed components and systems shall meet or exceed the efficiency levels

used to calculate the proposed building performance . d. For new buildings, one of the following shall be met:

  1. The building envelope complies with Section 5.5, “Prescriptive Building Envelope Compliance Path.”
  2. Using Section 5.6, “Building Envelope Trade-Off Compliance Path,” the proposed envelope perfor- mance factor shall not exceed the base envelope performance factor by more than 15% in multifamily residential, hotel/motel, and dormitory building area types. For all other building area types, the limit shall be 7%. For buildings with both residential and nonresidential occupancies, the limit shall be based on the area-weighted average of the gross conditioned floor area . e. Verification, testing, and commissioning requirements of Section 4.2.5 shall be met. f. Proposed building systems, controls, or building envelope documented in Section G1.3(c) that do not have criteria in Sections 5 through 10 shall have verification or testing to document proper installation and operation in accordance with Section 4.2.5.

G1.2.2 Performance Rating Calculation. The performance of the proposed design is calculated in accordance with provisions of this appendix using the following formula:

Performance Cost Index = Proposed building performance / Baseline building performance Both the proposed building performance and the baseline building performance shall include all end-use load components within and associated with the property when calculating the Performance Cost Index.

Exception to G1.2.2: Energy used to recharge or refuel vehicles that are used for off- site transportation pur poses shall not be modeled in the baseline building performance or the proposed building performance .

Informative Notes:

  1. Neither the proposed building performance nor the baseline building performance are predictions of actual energy consumption or costs for the proposed design after construction . Actual experience will differ from these calculations due to variations such as occupancy, building operation and maintenance, weather, energy use not covered by this procedure, changes in energy rates between design of the building and occupancy, and the precision of the calculation tool.
  2. See Informative Appendix I for using other metrics, including site energy, source energy, and carbon emissions, in conjunction with the Normative Appendix G Performance Rating Method when approved by the rating authority .

G1.3 Submittals

G1.3.1 General. Compliance documentation and supplemental information shall be submitted in accordance with Section 4.2.2 of this standard.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 301

PDF Page 304

Open page note

G1.3.2 Application Documentation. The following documentation shall be submitted to the rating authority:

a. The simulation program used, the version of the simulation program, and the results of the energy analy sis, including the calculated values for baseline building unregulated energy cost (BBUEC), baseline building regulated energy cost (BBREC), building performance factor (BPF), baseline building perfor- mance, the proposed building performance, Performance Cost Index (PCI), and Performance Cost Index Target (PCI t ). b. An overview of the project that includes the number of stories (above and below grade ), the typical floor

size, the uses in the building (e.g., office, cafeteria, retail, parking, etc.), the gross area of each use, and whether each use is conditioned space . c. A list of the energy -related features that are included in the design and on which the performance rating

is based. This list shall document all energy features that differ between the models used in the baseline building performance and proposed building performance calculations. d. A list showing compliance for the proposed design with all the requirements of Sections 5.4, 6.4, 7.4,

8.4, 9.4, and 10.4 (mandatory provisions). e. A list identifying those aspects of the proposed design that are less stringent than the requirements of

Sections 5.5, 6.5, 7.5, and 9.5 (prescriptive provisions). f. A list identifying those aspects of the proposed design that are more stringent than the requirements of Sections 5 through 10. g. A table with a summary by end use of the proposed building performance and baseline building perfor-

mance, with each end use separated into regulated and unregulated components. h. A site plan showing all adjacent buildings and topography that may shade the proposed building (with

estimated height or number of stories ). i. Building elevations and floor plans. j. A diagram showing the thermal blocks used in the computer simulation. k. An explanation of any significant modeling assumptions. l. Backup calculations and material to support data inputs (e.g., U-factors for building envelope assemblies, NFRC ratings for fenestration, end-uses identified in Table G3.1(1)(a). m. Reports from the simulation program showing

  1. a breakdown of energy use by at least the following components: lights, internal equipment loads, service water-heating equipment, space -heating equipment, space -cooling and heat rejection equip- ment, fans, and other HVAC equipment (such as pumps );
  2. the amount of unmet load hours for both the proposed design and baseline building design ; and
  3. a description of energy -related features of the budget building design and the proposed design to support requirements of Section G1.3.2(c). n. Purchased energy rates used in the simulations. o. An explanation of any error messages noted in the simulation program output. p. For any exceptional calculation methods employed, document the predicted energy savings by energy

type, the energy cost savings, a narrative explaining the exceptional calculation method performed, and theoretical or empirical information supporting the accuracy of the method. q. The reduction in proposed building performance associated with on-site renewable energy . r. The version of the software and the link to the website that contains the ASHRAE Standard 140 results for the version used in accordance with Section G2.2.4. s. Simulation input files for the budget building design and the proposed design shall be made available if requested by the building official.

G1.3.3 Completion Requirements. Completion requirements shall be in compliance with Sections 5.7.3, 6.7.3, 7.7.3, 8.7.3, 9.7.3, and 10.7.3.

G2. SIMULATION GENERAL REQUIREMENTS

G2.1 Performance Calculations. The proposed building performance and baseline building performance shall be calculated using the following:

a. The same simulation program b. The same weather data c. The same energy rates

G2.2 Simulation Program. The simulation program shall be a computer-based program for the analysis of energy consumption in buildings (a program such as, but not limited to, DOE-2, BLAST, or EnergyPlus). The

302 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 305

Open page note

simulation program shall include calculation methodologies for the building components being modeled. For components that cannot be modeled by the simulation program, the exceptional calculation methods requirements in Section G2.5 shall be used.

Informative Note: For the ease of use and consistent application, the simulation program should automatically implement the requirements of this appendix to generate the baseline design and proposed design models based on the user model of the proposed design .

G2.2.1 The simulation program shall be approved by the rating authority and shall, at a minimum, have the ability to explicitly model all of the following:

a. 8760 hours per year b. Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat set points,

humidity set points, and HVAC system operation, defined separately for each day of the week and holidays c. Thermal mass effects d. Ten or more thermal zones e. Part-load performance curves for mechanical equipment f. Capacity and efficiency correction curves for mechanical heating and mechanical cooling equipment g. Air economizers with integrated control h. Baseline building design characteristics specified in Section G3

G2.2.2 The simulation program shall have the ability to either directly determine the proposed building performance and baseline building performance or produce hourly reports of energy use by an energy source suitable for determining the proposed building performance and baseline building performance using a separate calculation.

G2.2.3 The simulation program shall be capable of performing design load calculations to determine required HVAC equipment capacities and air and water flow rates in accordance with Section 6.4.2.1 for both the proposed design and baseline building design .

G2.2.4 Simulation Program Testing Requirements

G2.2.4.1 The simulation program shall be tested according to ASHRAE Standard 140, except for Sections 7 and 8 of Standard 140. The required tests shall include building thermal envelope and fabric load tests (Sections 5.2.1, 5.2.2, and 5.2.3), ground coupled slab-on- grade analytical verification tests (Section 5.2.4), space -cooling equipment performance tests (Section 5.3), space -heating equipment performance tests (Section 5.4), and air-side HVAC equipment analytical verification tests (Section 5.5), along with the associated reporting (Section 6).

G2.2.4.2 The test results and modeler reports shall be posted on a publicly available website and shall include the test results of the simulation program and input files used for generating the results along with the results of the other simulation programs included in ASHRAE Standard 140, Annexes B8 and B16. The modeler report in Standard 140, Annex A2, Attachment A2.7 shall be completed for results exceeding the maximum or falling below the minimum of the reference values and for omitted results.

G2.2.4.3 The testing shall be performed for the version of the simulation program used to calculate the proposed building performance and baseline building performance .

Informative Notes:

  1. There are no pass/fail criteria established by this requirement.
  2. Based on the Section 3 definition, simulation program includes the simulation engine and the corresponding user interface. The testing of a simulation program only meets the requirements of Section G2.2.4 for that simulation program and cannot be used as proxy for documenting compliance of another simulation program that uses the same simulation engine .

G2.3 Climatic Data. The simulation program shall perform the simulation using hourly values of climatic data, including temperature, humidity, solar radiation, and wind speed and direction from representative climatic data, for the site in which the proposed design is to be located. For locations for which several climatic data sources are available or weather data are not available, the designer shall select available weather data that best represent the climate at the construction site . The selected weather data shall be approved by the rating authority .

G2.4 Renewable, Recovered, and Purchased Energy

G2.4.1 On-Site Renewable Energy and Site-Recovered Energy. Site-recovered energy shall not be considered purchased energy and shall be subtracted from the proposed design energy consumption prior to calculating the proposed building performance . On-site renewable energy shall be subtracted from the proposed

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 303

PDF Page 306

Open page note

design energy consumption prior to calculating the proposed building performance, provided that the building owner

a. owns the on-site renewable energy system or b. has signed a lease agreement for the on-site renewable energy system for at least 15 years or c. has signed a contractual agreement to purchase energy generated by the on-site renewable energy system

for at least 15 years.

G2.4.2 Annual Energy Costs. The design energy cost and baseline energy cost shall be determined using either actual rates for purchased energy or state average energy prices published by U.S. DOE’s Energy Information Administration (EIA) for commercial building customers, but rates from different sources may not be mixed in the same project. Where on-site renewable energy or site-recovered energy is used, the base- line building design shall be based on the energy source used as the backup energy source, or the baseline system energy source in that category if no backup energy source has been specified, except where the baseline energy source is prescribed in Tables G3.1.1-2 and G3.1.1-3. Where the proposed design includes on- site electricity generation systems other than on-site renewable energy systems, the baseline design shall include the same generation systems excluding its site-recovered energy .

Informative Note: The above provision allows users to gain credit for features that yield load management benefits. Where such features are not present, users can simply use state average unit prices from EIA, which are updated annually and readily available on EIA’s website (www.eia.gov).

G2.5 Exceptional Calculation Methods. When the simulation program does not model a design, material, or device of the proposed design, an exceptional calculation method shall be used as approved by the rating authority . Where there are multiple designs, materials, or devices that the simulation program does not model, each shall be calculated separately and exceptional savings determined for each. At no time shall the total exceptional savings constitute more than half of the difference between the baseline building perfor- mance and the proposed building performance . All applications for approval of an exceptional method shall include the following:

a. Theoretical and empirical information verifying the method’s accuracy, and step-by-step documentation

of the exceptional calculation method performed, detailed enough to reproduce the results. b. Copies of all spreadsheets used to perform the calculations. c. A sensitivity analysis of energy consumption when each of the input parameters that are estimated is var ied from half to double the value assumed. d. The calculations shall be performed on a time-step basis consistent with the simulation program used. e. The Performance Cost Index calculated with and without the exceptional calculation method.

G3. CALCULATION OF THE PROPOSED DESIGN ANDBASELINE BUILDING PERFORMANCE

G3.1 Building Performance Calculations

G3.1.1 Scope. The simulation model for calculating the proposed building performance and baseline building performance shall be developed in accordance with Sections G3.1.2, G3.1.3, or G3.1.4 as applicable.

G3.1.2 New Buildings. The simulation model for calculating the proposed building performance and baseline building performance for new buildings shall be developed in accordance with the requirements in Section G3.2.

G3.1.3 Additions. The simulation model for calculating the proposed building performance and baseline building performance for additions shall be developed in accordance with the requirements in Section G3.2.

G3.1.4 Alterations. The simulation model for calculating the proposed building performance and base- line building performance for alterations, excluding additions, shall be developed in accordance with the applicable subparagraph (a) or (b).

a. In accordance with Section G3.2 for alterations that include replacement of two or more of the following:

  1. HVAC systems that account for more than 50% of the capacity serving either the heating or cooling loads of the alteration area. This includes HVAC unitary systems, HVAC terminal units, or components of HVAC central heating or cooling equipment . HVAC terminal units, for the purposes of this section, can include VAV boxes, fan-coil units, VRF room units, or water-loop heat pumps;
  2. 50% or more of the luminaires in the alteration area;
  3. 25% or more of the building envelope area of the alteration portion of the building, including new exterior cladding, fenestration, or insulation. b. In accordance with Section G3.3 for all other alterations.

304 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 307

Open page note

G3.2 Performance Calculations for New Buildings, Additions and Substantial Alterations

G3.2.1 Baseline HVAC System Type and Description. HVAC systems in the baseline building design shall be selected based on the building area types and criteria described in Section G3.2.1.1 and shall be adjusted, when applicable, based on the requirements in Section G3.2.1.2 and modeled in the baseline build- ing design per Section G3.2.1.3.

G3.2.1.1 Baseline HVAC System Types based on Building Area Types. HVAC system types in the baseline building design shall be determined as follows:

a. Determine the combined area of the gross conditioned floor area and semiheated floor area of each of

the following building area types in the proposed design:

  1. Residential. HVAC zones that include dwelling units, guest rooms, living quarters, private living spaces, and sleeping quarters, and residential associated HVAC zones shall be classified as residen- tial . Other space types, including patient rooms in hospitals, shall not be classified as residential.
  2. Public Assembly. Houses of worship, auditoriums, movie theaters, performance theaters, concert halls, arenas, enclosed stadiums, ice rinks, gymnasiums, convention centers, exhibition centers, and natatorium buildings shall be classified as public assembly. HVAC zones that include these area types in other buildings shall also be classified as public assembly.
  3. Heated-Only Storage. Nonrefrigerated warehouse buildings and heated parking garages that are not mechanically cooled, shall be classified as heated-only storage.
  4. Retail. Grocery stores, retail stores, and supermarket buildings with two floors or fewer shall be classified as retail.
  5. Hospitals. Hospital building area types, including patient rooms, shall be classified as hospitals.
  6. Other Nonresidential. Buildings and areas within buildings that are not classified as residential, public assembly, heated-only storage, hospital, or retail shall be classified as other nonresidential . b. Classify the nonresidential building area type with the largest combined area from Section G3.2.1.1(a) as

the predominant nonresidential building area type. Add the combined area of any remaining nonresiden- tial building area types with less than 20,000 ft [2] to the combined area of the predominant nonresidential building area type. c. Select a baseline HVAC system type from Table G3.1.1-3 for each of the following building area types

included in the proposed design :

  1. Residential based on Section G3.2.1.1(a)
  2. Predominant nonresidential based on Section G3.2.1.1(b)
  3. Each additional nonresidential building area type with more than 20,000 ft [2] of combined area based on Section G3.2.1.1(a)

G3.2.1.2 Additional and Adjusted Baseline HVAC System Types. Baseline HVAC systems shall be added or adjusted for individual HVAC zones based on the following criteria.

a. If the baseline HVAC system type is 5, 6, 7, or 8 use separate single-zone systems conforming with the

requirements of system 3 or system 4 for any HVAC zones that have occupancy, or internal gains that differ significantly from the rest of the HVAC zones served by the system . Total peak internal gains that also differ by 12 Btu/h·ft [2 ] or more from the average of other HVAC zones served by the system, or occupied hours that are more than 40 hours per week higher than the average of other HVAC zones served by the system, are considered to differ significantly. Examples where this exception may be applicable include, but are not limited to, commercial kitchens, auditoriums, natatoriums, and continually occupied security areas. This exception does not apply to computer rooms . b. In a building having a total laboratory exhaust rate greater than 15,000 cfm, use a single system of type 5

or 7 serving only those HVAC zones that include the laboratory spaces . The lab exhaust fan shall be modeled as constant horsepower reflecting constant-volume stack discharge with outdoor air bypass. c. HVAC zones designed with heating-only systems in the proposed design serving storage rooms, stairwells,

vestibules, electrical/mechanical rooms, and restrooms not exhausting or transferring air from mechanically cooled thermal zones in the proposed design shall use system type 9 or 10 in the baseline building design . d. If the baseline HVAC system type is 9 or 10, use additional system types for all HVAC zones that are

mechanically cooled in the proposed design . The baseline HVAC system types for such zones shall be determined based on the building area type determined in accordance with Section G3.2.1.1(a) and the requirements of Section G3.2.1.1(c).

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 305

PDF Page 308

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance

Proposed Building Performance Baseline Building Performance

1. Design Model

2. Additions and Alterations

3. Space Use Classification

306 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 309

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance (Continued)

Proposed Building Performance Baseline Building Performance

4. Schedule

5. Building Envelope

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 307

PDF Page 310

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance (Continued)

Proposed Building Performance Baseline Building Performance

5. Building Envelope (continued)

308 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 311

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance (Continued)

Proposed Building Performance Baseline Building Performance

6. Lighting

7. Thermal Blocks—HVAC Zones Designed

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 309

PDF Page 312

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance (Continued)

Proposed Building Performance Baseline Building Performance

8. Thermal Blocks—HVAC Zones Not Designed

9. Thermal Blocks—Multifamily Residential Buildings

10. HVAC Systems

310 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 313

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance (Continued)

Proposed Building Performance Baseline Building Performance

10. HVAC Systems (continued)

11. Service Water-Heating Systems

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 311

PDF Page 314

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance (Continued)

Proposed Building Performance Baseline Building Performance

11. Service Water-Heating Systems (continued)

12. Receptacle and Other Loads

Receptacle and process loads, such as those for office and other
equipment, shall be estimated based on the building area type or space
type category and shall be assumed to be identical in the proposed design
and baseline building design, except as specifically approved by the
rating authority only when quantifying performance that exceeds the
requirements of Standard 90.1 but not when the Performance Rating
Method is used as an alternative path for minimum standard compliance
in accordance with Section 4.2.1.1. These loads shall always be included
in simulations of the building. These loads shall be included when
calculating the proposed building performance and the baseline building
performance as required by Section G1.2.1.
Exception: When receptacle controls installed in spaces where no t
required by Section 8.4.2 are included in the proposed buildin g
design, the hourly receptacle shall be reduced as follows:
RPC = RC × 10%
where
RPC = receptacle power credit
EPS = EPS × (1 – RPC)
pro bas
RC = percentage of all controlled receptacles
EPS = baseline equipment power hourly schedule (fraction)
bas
EPS = proposed equipment power hourly schedule (fraction)
pro
a. Where power and other systems covered by Sections 8 and 10 hav e
been designed and submitted with design documents, those sys-
tems shall be determined in accordance with Sections 8 and 10.
b. Where power and other systems covered by Sections 8 and 10 hav e
not been submitted with design documents, those systems shal l
comply with but not exceed the requirements of those sections.
Motors shall be modeled as having the efficiency ratings found in Table
G3.9.1 Other systems covered by Section 10 and miscellaneous loads
shall be modeled as identical to those in the proposed design, including
schedules of operation and control of the equipment. Energy used for
cooking equipment, receptacle loads, computers, medical or laboratory
equipment, and manufacturing and industrial process equipment not
specifically identified in the standard power and energy rating or
capacity of the equipment shall be identical between the proposed
building performance and the baseline building performance.
Receptacle schedules shall be the same as the proposed design before
the receptacle power credit is applied.
Exception: When quantifying performance that exceeds the require-
ments of Standard 90.1 (but not when using the Performance Rat-
ing Method as an alternative path for minimum standar d
compliance per Section 4.2.1.1) variations of the power require-
ments, schedules, or control sequences of the equipment modeled in
the baseline building design from those in the proposed design shal l
be approved by the rating authority based on documentatio n
described in Table G3.1(1), or that the equipment installed in th e
proposed design represents a significant verifiable departure fro m
documented current conventional practice. The burden of this docu-
mentation is to demonstrate that accepted conventional practic e
would result in baseline building equipment different from that
installed in the proposed design. Occupancy and occupancy sched-
ules shall not be changed.
13. Modeling Limitations to the Simulation Program
If the_simulation program_ cannot model a component or_system_ included
in the_proposed design_ explicitly, substitute a thermodynamically similar
component model that can approximate the expected performance of the
component that cannot be modeled explicitly.
Same as_proposed design_.

14. Exterior Conditions

312 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 315

Open page note

Table G3.1 Modeling Requirements for Calculating Proposed Building Performance andBaseline Building Performance (Continued)

Proposed Building Performance Baseline Building Performance

14. Exterior Conditions (continued)

15. Distribution Transformers

16. Elevators

17. Refrigeration

18. On-Site Renewable Energy

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 313

PDF Page 316

Open page note

d. The baseline HVAC system serving HVAC zones that include computer rooms shall be modeled in accor dance with one of the following:

  1. Baseline System 11 shall be used for such HVAC zones in buildings with a total computer room peak cooling load greater than 3,000,000 Btu/h.
  2. Baseline S ystem 11 shall be used for such HVAC zones in buildings where the baseline HVAC system type is 7 or 8 and the total computer room peak cooling load is greater than 600,000 Btu/h.
  3. Baseline System 3 or 4 shall be used for all other HVAC zones that include computer rooms based on climate zone. e. Residential associated HVAC zones shall use system type 3 or 4 based on climate zone.

G3.2.1.3 For baseline HVAC systems 1, 2, 3, 4, 9, 10, 11, 12, and 13, each HVAC zone or thermal block shall be modeled with its own HVAC system . For Systems 5, 6, 7, and 8, each floor shall be modeled with a separate HVAC system . Floors with identical HVAC zones or thermal blocks can be grouped for modeling purposes.

Exception to G3.2.1.3: Baseline system 5 or 7 serving laboratory spaces in accordance with Section

G3.2.1.2(b).

G3.2.1.4 Purchased Heat. For systems using purchased hot water or steam, the heating source shall be modeled as purchased hot water or steam in both the proposed design and baseline building design . Hotwater or steam costs shall be based on actual utility rates, and on- site boilers, electric heat, and furnaces shall not be modeled in the baseline building design .

G3.2.1.5 Purchased Chilled Water. For systems using purchased chilled water, the cooling source shall be modeled as purchased chilled water in both the proposed design and baseline building design . Purchased chilled-water costs shall be based on actual utility rates, and on- site chillers and direct expansion equipment shall not be modeled in the baseline building design .

G3.2.1.6 Baseline HVAC System Requirements for Systems Utilizing Purchased Chilled Water and/or Purchased Heat. If the proposed design uses purchased chilled water and/or purchased heat, the following modifications to the baseline HVAC system types in Table G3.1.1-4 shall be used.

G3.2.1.6.1 Purchased Heat Only. If the proposed design uses purchased heat, but does not use purchased chilled water, then Tables G3.1.1-3 and G3.1.1-4 shall be used to select the baseline HVAC system type, and purchased heat shall be substituted for the heating type in Table G3.1.1-4. The same heating source shall be used in the proposed design and baseline building design .

G3.2.1.6.2 Purchased Chilled Water Only. If the proposed design uses purchased chilled water but does not use purchased heat, then Tables G3.1.1-3 and G3.1.1-4 shall be used to select the baseline HVAC system type, with the modifications listed below:

a. Purchased chilled water shall be substituted for the cooling types in Table G3.1.1-4. b. System 1 and 2 shall be constant-volume fan-coil units with fossil fuel boilers . c. System 3 and 4 shall be constant-volume single-zone air handlers with fossil fuel furnaces. d. System 7 shall be used in place of System 5. e. System 8 shall be used in place of System 6.

G3.2.1.6.3 Purchased Chilled Water and Purchased Heat. If the proposed design uses purchased chilled water and purchased heat, then Tables G3.1.1-3 and G3.1.1-4 shall be used to select the baseline HVAC system type, with the following modifications:

a. Purchased heat and purchased chilled water shall be substituted for the heating types and cooling types in

Table G3.1.1-4. b. System 1 shall be constant-volume fan-coil units. c. System 3 shall be constant-volume single-zone air handlers. d. System 7 shall be used in place of System 5.

G3.2.1.6.4 On-Site Distribution Pumps. All on- site distribution pumps shall be modeled in both the proposed design and base building design .

G3.2.1.7 Modeling Building Envelope Air Leakage. The air leakage rate of the building envelope ( I75Pa ) at a pressure differential of 75 Pa (0.30 in. of water) shall be converted to appropriate units for the simulation program using one of the following formulas:

For methods describing air leakage as a function of floor area,

IFLR = 0.112 × I75Pa × S / AFLR

314 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 317

Open page note

For methods describing air leakage as a function of the area of above-grade walls that separate condi- tioned spaces and semiheated spaces from the exterior,

IAGW = 0.112 × I75Pa × S/AAGW When using the measured air leakage rate of the building envelope at a pressure differential of 0.3 in. of water for the proposed design, the air leakage rate shall be calculated as follows:

I75Pa = Q/S

where I75Pa = air leakage rate of the building envelope (cfm/ft [2] ) at a fixed building pressure differential of 75 Pa (0.30 in. of water) Q = volume of air in cfm flowing through the building envelope when subjected to a pressure differential of 75 Pa (0.30 in. of water), in accordance with ASTM E 779, ASTM E1827, or ASTM E3158 S = total area of the building envelope (ft [2] ), including the lowest floor, any below-grade walls or above-grade walls, and roof (including vertical fenestration and skylights ) IFLR = adjusted air leakage rate of the building envelope (cfm/ft [2] ) at a reference wind speed of 10 mph and relative to the gross floor area AFLR = gross floor area, ft [2]

IAGW = adjusted air leakage rate of the building envelope (cfm/ft [2] ) at a reference wind speed of 10 mph and relative to the area of the above-grade walls of the building envelope AAGW = total area of above-grade walls of the building envelope, ft [2]

Exceptions to G3.2.1.7: A multizone airflow model alternative method to modeling building envelope

air leakage may be used, provided the following criteria are met:

  1. Where the calculations are made independently of the energy simulation program, the proposed method must comply with Section G2.5.
  2. The method for converting the air leakage rate of the building envelope at 0.3 in. of water, or 1.57 psf, to the appropriate units for the simulation program is fully documented and submitted to the rating authority for approval.

G3.2.2 General Baseline HVAC System Requirements. HVAC systems in the baseline building design shall conform with the general provisions in this section.

G3.2.2.1 Equipment Efficiencies. All HVAC equipment in the baseline building design shall be modeled at the minimum efficiency levels, both part load and full load, in accordance with Tables G3.5.1 through G3.5.6. Where multiple HVAC zones are combined into a single thermal block in accordance with Table G3.1, the efficiencies (for baseline HVAC System Types 3, 4, 9, and 10) taken from Tables G3.5.1, G3.5.2, and G3.5.5 shall be based on the equipment capacity of the thermal block divided by the number of HVAC zones . HVAC System Types 5 or 6 efficiencies taken from Table G3.5.1 shall be based on the cooling equip- ment capacity of a single story when grouping identical stories in accordance with Section G3.2.1.1(a)(4). Fan energy shall be modeled separately according to Section G3.2.1.7.

COPnfcooling and COPnfheating are the packaged HVAC equipment cooling and heating energy efficiency, respectively, to be used in the baseline building design, which excludes supply fan power.

The sets of performance curves specified in Table J-2 should be used to represent part-load performance of chillers in the baseline building design. When using performance curves from Normative Appendix J, chiller minimum part-load ratio (ratio of load to available capacity at a given simulation time step) and minimum compressor unloading ratio (part-load ratio below which the chiller capacity cannot be reduced by unloading and chiller is false loaded) shall be equal to 0.25. Simulation programs that do not use performance curves are permitted to use an alternative simulation method that results in the same performance as the curves described in Normative Appendix J.

G3.2.2.2 Equipment Capacities. System coil capacities for the baseline building design shall be based on sizing runs for each orientation in accordance with Table G3.1, No. 5[a] and Section G3.2.2.2.1, and shall be oversized by 15% for cooling and 25% for heating. The ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be 1.15 for cooling and 1.25 for heating. Plant capacities shall be based on coincident loads.

G3.2.2.2.1 Sizing Runs. Weather conditions used in sizing runs to determine baseline equipment capacities shall be based on design days developed using heating design temperatures, cooling design tem- perature, and cooling design wet-bulb temperature . For cooling sizing runs, schedules for internal loads,

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 315

PDF Page 318

Open page note

including those used for infiltration, occupants, lighting, gas and electricity using equipment, shall be equal to the highest hourly value used in the annual simulation runs and applied to the entire design day. For heating sizing runs, schedules for internal loads, including those used for occupants, lighting, gas and electricity using equipment, shall be equal to the lowest hourly value used in the annual simulation runs, and schedules for infiltration shall be equal to the highest hourly value used in the annual simulation runs and applied to the entire design day.

Exception to G3.2.2.2.1: For cooling sizing runs in residential dwelling units, the infiltration, occu pants, lighting, gas and electricity using equipment hourly schedule shall be the same as the most used hourly weekday schedule from the annual simulation.

G3.2.2.3 Unmet Loads. Unmet load hours for the proposed design or baseline building design shall not exceed 300 (of the 8760 hours simulated). Alternatively, unmet load hours exceeding these limits shall be permitted to be accepted upon approval of the rating authority, provided that sufficient justification is given indicating that the accuracy of the simulation is not significantly compromised by these unmet loads.

G3.2.2.4 Ventilation. Minimum ventilation system outdoor air intake flow shall be the same for the proposed design and baseline building design .

Exceptions to G3.2.2.4:

  1. When modeling demand control ventilation in the proposed design in systems with outdoor air capacity less than or equal to 3000 cfm serving areas with an average design capacity of 100 people per 1000 ft [2] or less.
  2. When designing systems in accordance with Standard 62.1, Section 6.2, “ Ventilation Rate Procedure,” reduced ventilation airflow rates may be calculated for each HVAC zone in the proposed design with a zone air distribution effectiveness ( Ez ) > 1.0 as defined by Standard 62.1, Table 6-2. Baseline ventilation airflow rates in those zones shall be calculated using the proposed design Ventilation Rate Procedure calculation with the following change only. Zone air distribution effectiveness shall be changed to ( Ez ) = 1.0 in each zone having a zone air distribution effectiveness ( Ez ) > 1.0. Proposed design and baseline building design Ventilation Rate Procedure calculations, as described in Standard 62.1, shall be submitted to the rating authority to claim credit for this exception.
  3. Where the minimum outdoor air intake flow in the proposed design is provided in excess of the amount required by the building code or the rating authority, the baseline building design shall be modeled to reflect the greater of that required by either the rating authority or the building code and will be less than the proposed design .
  4. For baseline systems serving only laboratory spaces that are prohibited from recirculating return air by code or accreditation standards, the baseline system shall be modeled as 100% outdoor air .

G3.2.2.5 Economizers. Air economizers shall not be included in baseline HVAC Systems 1, 2, 9, and 10. Integrated air economizer control shall be included in baseline HVAC Systems 3 through 8, and 11, 12, and 13 based on climate as specified in Table G3.2.2.5. Exceptions to G3.2.2.5: Economizers shall not be included for systems meeting one or more of the

exceptions listed below.

  1. Systems that include gas-phase air cleaning to meet the requirements of Standard 62.1, Section 6.1.2. This exception shall be used only if the system in the proposed design does not match the building design.
  2. Where the use of outdoor air for cooling will affect supermarket open refrigerated casework sys- tems . This exception shall only be used if the system in the proposed design does not use an economizer. If the exception is used, an economizer shall not be included in the baseline building design .
  3. Systems that serve computer rooms complying with Section G3.2.2.5.1.

G3.2.2.5.1 Computer Room Economizers. Systems that serve computer rooms that are HVAC System 3 or 4 shall not have an economizer. Systems that serve computer rooms that are HVAC System 11 shall include an integrated fluid economizer meeting the requirements of Section 6.5.1.2 in the baseline building design .

G3.2.2.6 Economizer High-Limit Shutoff. The high-limit shutoff shall be a dry-bulb fixed switch with set-point temperatures in accordance with the values in Table G3.2.2.6.

G3.2.2.7 Design Airflow Rates

G3.2.2.7.1 Baseline All System Types Except System Types 9 and 10. System design supply airflow rates for the baseline building design shall be based on a supply-air-to-room temperature set-point difference of 20°F or the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or

316 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 319

Open page note

accreditation standards, whichever is greater. For systems with multiple zone thermostat set points, use the design set point that will result in the lowest supply air cooling set point or highest supply air heating set point . If return or relief fans are specified in the proposed design, the baseline building design shall also be modeled with fans serving the same functions and sized for the baseline system supply fan air quantity less the minimum outdoor air, or 90% of the supply fan air quantity, whichever is larger.

Exceptions to G3.2.2.7.1:

  1. For systems serving laboratory spaces, airflow rate shall be based on a supply-air-to-room temperature set-point difference of 17°F or the required ventilation air or makeup air, whichever is greater.
  2. If the proposed design HVAC system airflow rate based on latent loads is greater than the design airflow rate based on sensible loads, then the same supply-air-to-room-air humidity ratio difference (gr/lb) used to calculate the proposed design airflow shall be used to calculate design airflow rates for the baseline building design .

G3.2.2.7.2 Baseline System Types 9 and 10. System design supply airflow rates for the baseline building design shall be based on the temperature difference between a supply air temperature set point of 105°F and the design space -heating temperature set point, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is greater. If the pro- posed design includes a fan or fans sized and controlled to provide non- mechanical cooling, the baseline building design shall include a separate fan to provide non- mechanical cooling, sized and controlled the same as the proposed design .

G3.2.2.8 System Fan Power. System fan electrical power for supply, return, exhaust, and relief (excluding power to fan-powered VAV boxes) shall be calculated using the following formulas:

For Systems 1 and 2,

Pfan = CFM s × 0.3

For Systems 3 through 8, and 11, 12, and 13,

Pfan = bhp × 746/fan motor efficiency

For Systems 9 and 10 (supply fan),

Pfan = CFM s × 0.3

For Systems 9 and 10 (non- mechanical cooling fan if required by Section G3.2.2.7.2),

Pfan = CFM nmc × 0.054

where Pfan = electric power to fan motor, W bhp = brake horsepower of baseline fan motor fromTable G3.2.2.8 fan motor efficiency = the efficiency for the next motor size greater than the bhp from Table G3.2.2.8 CFM s = the baseline system maximum design supply fan airflow rate, cfm CFM nmc = the baseline non- mechanical cooling fan airflow, cfm G3.2.2.8.1 The calculated system fan power shall be distributed to supply, return, exhaust, and relief fans in the same proportion as the proposed design .

G3.2.2.9 Exhaust Air Energy Recovery. Individual fan systems that have both a design supply air capacity of 5000 cfm or greater and have a minimum design outdoor air supply of 70% or greater shall have an energy recovery system with at least 50% enthalpy recovery ratio . Fifty percent enthalpy recovery ratio shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and return air at design conditions . Provision shall be made to bypass or control the heat recovery system to permit air economizer operation, where applicable.

Exceptions to G3.2.2.9: If any of these exceptions apply, exhaust air energy recovery shall not be

included in the baseline building design :

  1. Systems serving spaces that are not cooled and that are heated to less than 60°F.
  2. Systems exhausting toxic, flammable, or corrosive fumes or paint or dust. This exception shall only be used if exhaust air energy recovery is not used in the proposed design .
  3. Commercial kitchen hoods (grease) classified as Type 1 by NFPA 96. This exception shall only be used if exhaust air energy recovery is not used in the proposed design .
  4. Heating systems in Climate Zones 0 through 3.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 317

PDF Page 320

Open page note

  1. Cooling systems in Climate Zones 3C, 4C, 5B, 5C, 6B, 7, and 8.
  2. Where the largest exhaust source is less than 75% of the design outdoor airflow . This exception shall only be used if exhaust air energy recovery is not used in the proposed design .
  3. Systems requiring dehumidification that employ energy recovery in series with the cooling coil. This exception shall only be used if exhaust air energy recovery and series-style energy recovery coils are not used in the proposed design .
  4. Systems serving laboratory HVAC zones with a total laboratory exhaust volume greater than 15,000 cfm.

G3.2.3 System-Specific Baseline HVAC System Requirements. Baseline HVAC systems shall conform with provisions in this section, where applicable, to the specified baseline system types, as indicated in section headings.

G3.2.3.1 Heat Pumps (Systems 2 and 4). Electric air source heat pumps shall be modeled with electric auxiliary heat and an outdoor air thermostat . The systems shall be controlled to energize auxiliary heat only when the outdoor air temperature is less than 40°F. The air source heat pump shall be modeled to continue to operate while auxiliary heat is energized.

G3.2.3.2 Type and Number of Boilers (Systems 1, 5, 7, 11, and 12). The boiler plant shall be natural draft, except as noted in Section G3.2.1.4. The baseline building design boiler plant shall be modeled as having a single boiler if the baseline building design plant serves a gross conditioned floor area of 15,000 ft [2] or less, and as having two equally sized boilers for plants serving more than 15,000 ft [2] . Boilers shall be staged as required by the load.

G3.2.3.3 Hot-Water Supply Temperature (Systems 1, 5, 7, 11, and 12). Hot-water design supply temperature shall be modeled as 180°F and design return temperature as 130°F.

G3.2.3.4 Hot-Water Supply Temperature Reset (Systems 1, 5, 7, 11, and 12). Hot-water supply temperature shall be reset based on outdoor dry-bulb temperature using the following schedule: 180°F at 20°F and below, 150°F at 50°F and above, and ramped linearly between 180°F and 150°F at temperatures between 20°F and 50°F.

Exception to G3.2.3.4: Systems served by purchased heat.

G3.2.3.5 Hot-Water Pumps (Systems 1, 5, 7, 11, and 12). The baseline building design hot-water pump power shall be 19 W/gpm. The pumping system shall be modeled as primary-only with continuous variable flow and a minimum of 25% of the design flow rate. Hot-water pumps shall only be enabled when a load exists on the associated hot-water loop . Hot-water systems serving 120,000 ft [2] or more shall be modeled with variable-speed drives, and systems serving less than 120,000 ft [2] shall be modeled as riding the pump curve.

Exception to G3.2.3.5: The pump power for systems using purchased heat shall be 14 W/gpm.

G3.2.3.6 Piping Losses (Systems 1, 5, 7, 8, 11, 12, and 13). Piping losses shall not be modeled in either the proposed design or baseline building design for hot-water, chilled-water, or steam piping .

G3.2.3.7 Type and Number of Chillers (Systems 7, 8, 11, 12, and 13). Electric chillers shall be used in the baseline building design regardless of the cooling energy source, e.g. direct-fired absorption or absorption from purchased steam. The baseline building design ’s chiller plant shall be modeled with chillers having the number and type as indicated in Table G3.2.3.7 based on the peak coincident cooling load of baseline HVAC systems using chilled water.

Exception to G3.2.3.7: Systems using purchased chilled water shall be modeled in accordance with

Section G3.2.1.6.

G3.2.3.8 Chilled-Water Design Supply Temperature (Systems 7, 8, 11, 12, and 13). Chilled-water design supply temperature shall be modeled at 44°F and return water temperature at 56°F.

G3.2.3.9 Chilled-Water Supply Temperature Reset (Systems 7, 8, 11, 12, and 13). Chilled-water supply temperature shall be reset based on outdoor dry-bulb temperature using the following schedule: 44°F at 80°F and above, 54°F at 60°F and below, and ramped linearly between 44°F and 54°F at temperatures between 80°F and 60°F.

Exception to G3.2.3.9:

  1. If the baseline chilled-water system serves a computer room HVAC system, the supply chilledwater temperature shall be reset higher based on the HVAC system requiring the most cooling; i.e., the chilled-water set point is reset higher until one cooling-coil valve is nearly wide open. The maximum reset chilled-water supply temperature shall be 54°F.
  2. Systems served by purchased chilled water.

318 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 321

Open page note

G3.2.3.10 Chilled-Water Pumps (Systems 7, 8, 11, 12, and 13). Chilled-water systems shall be modeled as primary/secondary systems with constant-flow primary loop and variable-flow secondary loop. For systems with cooling capacity of 300 tons or more, the secondary pump shall be modeled with variablespeed drives and a minimum flow of 25% of the design flow rate. Chilled-water pumps shall only be enabled when a load exists on the associated chilled-water loop . For systems with less than 300 tons cooling capacity, the secondary pump shall be modeled as riding the pump curve. The baseline building constant-volume primary pump power shall be modeled as 9 W/gpm, and the variable-flow secondary pump power shall be modeled as 13 W/gpm at design conditions . For computer room systems using System 11 with an integrated fluid economizer, the baseline building design primary chilled-water pump power shall be increased by 3 W/ gpm for flow associated with the fluid economizer .

Exception to G3.2.3.10: For systems using purchased chilled water, the building distribution pump shall

be modeled with variable-speed drive, a minimum flow of 25% of the design flow rate, and a pump power of 16 W/gpm.

G3.2.3.11 Heat Rejection (Systems 7, 8, 11, 12, and 13). The heat-rejection device shall be an axialfan open-circuit cooling tower with variable-speed fan control and shall have an efficiency of 38.2 gpm/hp at the conditions specified in Table 6.8.1-7. Condenser-water design supply temperature shall be calculated using the cooling tower approach to the 0.4% evaporation design wet-bulb temperature as generated by the formula below, with a design temperature rise of 10°F:

Approach 10°F Range = 25.72 – (0.24 × WB)

where WB is the 0.4% evaporation design wet-bulb temperature (°F); valid for wet bulbs from 55°F to 90°F.

The tower shall be controlled to maintain a leaving water temperature, where weather permits, per Table G3.2.3.11, floating up to the design leaving water temperature for the cooling tower. The baseline building design condenser-water pump power shall be 19 W/gpm and modeled as constant volume. For computer room systems using System 11 with an integrated fluid economizer, the baseline building design condenserwater- pump power shall be increased by 3 W/gpm for flow associated with the fluid economizer . Each chiller shall be modeled with separate condenser-water and chilled-water pumps interlocked to operate with the associated chiller.

G3.2.3.12 Supply Air Temperature Reset (Systems 5 through 8 and 11). The air temperature for cooling shall be reset higher by 5°F under the minimum cooling load conditions.

G3.2.3.13 VAV Minimum Flow Set Points (Systems 5 and 7). Minimum volume set points for VAV reheat boxes shall be 30%of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is larger.

Exception to G3.2.3.13: Systems serving laboratory spaces shall reduce the exhaust and makeup air

volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards.

G3.2.3.14 Fan Power and Control (Systems 6 and 8). Fans in parallel VAV fan-powered boxes shall run as the first stage of heating before the reheat coil is energized. Fans in parallel VAV fan-powered boxes shall be sized for 50% of the peak design primary air (from the VAV air-handling unit) flow rate and shall be modeled with 0.35 W/cfm fan power. Minimum volume set points for fan-powered boxes shall be equal to 30% of peak design primary airflow rate or the rate required to meet the minimum outdoor air ventilation requirement, whichever is larger. The supply air temperature set point shall be constant at the design condition .

G3.2.3.15 VAV Fan Part-Load Performance (Systems 5 through 8 and 11). VAV system supply fans shall have variable-speed drives, and their part-load performance characteristics shall be modeled using either Method 1 or Method 2 specified in Table G3.2.3.15.

G3.2.3.16 Computer Room Equipment Schedules. Computer room equipment schedules shall be modeled as a constant fraction of the peak design load per the following monthly schedule:

Month 1, 5, 9—25% Month 2, 6, 10—50% Month 3, 7, 11—75% Month 4, 8, 12—100%

G3.2.3.17 System 11 Supply Air Temperature and Fan Control. Minimum volume set point shall be 50% of the maximum design airflow rate, the minimum ventilation outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is larger.

Fan volume shall be reset from 100% airflow at 100% cooling load to minimum airflow at 50% cooling load. Supply air temperature set point shall be reset from minimum supply air temperature at 50% cooling

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 319

PDF Page 322

Open page note

load and above to space temperature at 0% cooling load. In heating mode supply air temperature shall be modulated to maintain space temperature, and fan volume shall be fixed at the minimum airflow.

G3.2.3.18 Dehumidification (Systems 3 through 8 and 11, 12, and 13). If the proposed design HVAC systems have humidistatic controls, then the baseline building design shall use mechanical cooling for dehumidification and shall have reheat available to avoid overcooling. When the baseline building design HVAC system does not comply with any of the exceptions in Section 6.5.2.3, then only 25% of the system reheat energy shall be included in the baseline building performance . The reheat type shall be the same as the sys- tem heating type.

G3.2.3.19 Preheat Coils (Systems 5 through 8). The baseline system shall be modeled with a preheat coil controlled to a fixed set point 20°F less than the maximum design heating temperature set point of the HVAC zones served by the system.

G3.3 Performance Calculations for Other Alterations

G3.3.1 Proposed Building Performance. The simulation model for calculating the proposed building performance shall be developed in accordance with the requirements in Table G3.1, Proposed Building Performance column and the following additional requirements:

a. New and retrofitted systems and equipment shall be consistent with design documents. b. Systems and equipment excluded from the scope of retrofit shall reflect the existing conditions.

G3.3.2 Baseline Building Performance

G3.3.2.1 General Approach. System and equipment included in the scope of retrofit shall be modeled at efficiency levels meeting the mandatory and prescriptive requirements in Sections 5 through 10 and as described in this section. All other baseline systems and equipment shall be modeled the same as in the pro- posed design.

G3.3.2.2 Schedules. Schedules modeled in the baseline design are allowed to differ from the proposed design following Table G3.1(4), Baseline Building Performance column, Exceptions 1 through 3.

G3.3.2.3 Opaque Assemblies. Opaque assemblies shall be modeled with U-factors meeting the requirements in Section 5.1.3.

G3.3.2.4 Fenestration. Fenestration U-factor, SHGC, and VT shall be modeled as meeting the requirements in Section 5.1.3.

The fenestration area for an existing building shall equal the existing fenestration area prior to the proposed work and shall be distributed on each face of the building in the same proportions as the existing building.

G3.3.2.5 Air Leakage. When Section 5.4.3.1.3 applies, the air leakage rate of the building envelope ( I75Pa ) shall be equal to 0.35 cfm/ft [2] of building envelope area at a pressure differential of 75 Pa (0.30 in. of water). The air leakage rate shall be converted to appropriate units for the simulation software using the same method as the proposed design .

G3.3.2.6 Interior Lighting. Interior lighting power density shall be modeled as meeting Section 9.1.1.3.1 using applicable allowances in Section 9.5.2.1. Lighting controls shall be modeled as meeting Section 9.1.1.3.1.

G3.3.2.7 Exterior Lighting. Tradable exterior lighting shall be modeled as meeting Section 9.1.1.3.2.

G3.3.2.8 HVAC Systems

a. Baseline HVAC system types shall be the same as the proposed design .

Exception to G3.3.2.8(a): If the proposed design includes variable refrigerant flow heat pumps or sin-

gle-zone systems with electric resistance heat, then air source heat pumps shall be used in the base- line design . b. Baseline systems shall meet the requirements in Section 6.1.3. Chillers shall meet the efficiency require ments in Table 6.8.1-3 using Path A or Path B, the same as the proposed design . If the proposed design meets both Path A and Path B requirements, Path A shall be used. c. Where the efficiency rating includes supply fan energy, calculate the minimum COPnfcooling and COPnf-

heating [ in accordance with Section 12.5.2(c).] d. Fan system efficiency (bhp per cfm of supply air, including the effect of belt losses but excluding motor

and motor drive losses) shall be the same as the proposed design or up to the limit prescribed in Section 6.5.3.1, whichever is smaller. If this limit is reached, each fan shall be proportionally reduced in brake horsepower until the limit is met. Fan electrical power shall then be determined by adjusting the calcu

320 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 323

Open page note

lated fan hp by the minimum motor efficiency prescribed by Section 10.4.1 for the appropriate motor size for each fan. Exception to G3.3.2.8(d): When a proposed design includes energy recovery but it is not required in

the baseline building design per Section 6.5.6, the fan power of the baseline system shall be equal to either the proposed design system or the fan power limit in Section 6.5.3.1 calculated without fan power credit for energy recovery, whichever is less. e. The equipment capacities for the baseline design shall be sized proportionally to the capacities in the

proposed design based on sizing runs—i.e., the ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and budget building design .

G3.3.2.9 Service Water Heating Systems. Service water heating systems shall be modeled as meeting Section 7.1.4. Service water heating energy use can be documented to be reduced as allowed in Table G3.1(11) Baseline Building Performance column exceptions to (g).

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 321

PDF Page 324

Open page note

Table G3.1.1-1 Baseline Building Vertical Fenestration

Building Area TypesaBaseline Building Vertical Fenestration Area
as a Percentage of Gross Above-Grade-Wall Area
Grocery store7%
Healthcare (outpatient)21%
Hospital27%
Hotel/motel (≤75 rooms)24%
Hotel/motel (>75 rooms)
34%
Office (≤5000 ft2)
19%
Office (5000 to 50,000 ft2)
31%
Office (>50,000 ft2)40%
Restaurant (quick service)34%
Restaurant (full service)24%
Retail (stand alone)11%
Retail (strip mall)20%
School (primary)22%
School (secondary and university)22%
Warehouse (nonrefrigerated)6%

Table G3.1.1-2 Baseline Service Water-Heating System

Building Area TypeBaseline Heating Method
Performing arts theaterGas storage_water heater_
Police stationElectric resistance storage_water heater_
Post officeElectric resistance storage_water heater_
Religious_facility_Electric resistance storage_water heater_
RetailElectric resistance storage_water heater_
School/universityGas storage_water heater_
Sports arenaGas storage_water heater_
Town hallElectric resistance storage_water heater_
TransportationElectric resistance storage_water heater_
WarehouseElectric resistance storage_water heater_
WorkshopElectric resistance storage_water heater_
All othersGas storage_water heater_
Building Area TypeBaseline Heating Method
Automotive facilityGas storage_water heater_
Convenience storeElectric resistance water heater
Convention centerElectric resistance storage_water heater_
CourthouseElectric resistance storage_water heater_
Dining: Bar lounge/leisureGas storage_water heater_
Dining: Cafeteria/fast foodGas storage_water heater_
Dining: FamilyGas storage_water heater_
DormitoryGas storage_water heater_
Exercise centerGas storage_water heater_
Fire stationGas storage_water heater_
Grocery storeGas storage_water heater_
GymnasiumGas storage_water heater_
Health care clinicElectric resistance storage_water heater_
Hospital and outpatient
surgery center
Gas storage_water heater_
HotelGas storage_water heater_
LibraryElectric resistance storage_water heater_
Manufacturing facilityGas storage_water heater_
MotelGas storage_water heater_
Motion picture theaterElectric resistance storage_water heater_
MultifamilyGas storage_water heater_
MuseumElectric resistance storage_water heater_
OfficeElectric resistance storage_water heater_
Parking garageElectric resistance storage_water heater_
PenitentiaryGas storage_water heater_

322 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 325

Open page note

Table G3.1.1-3 Baseline HVAC System TypesCol2Col3
Building Area Types a, Number of Stories b, and
Combined Floor Area c
Climate Zones 3B, 3C, and 4 to 8Climate Zones 0 to 3A
Residential
System 1—PTACSystem 2—PTHP
Public assembly area smaller than 120,000 ft2
System 3—PSZ-ACSystem 4—PSZ-HP
Public assembly area equal to or larger than120,000 ft2System 12—SZ-CV-HWSystem 13—SZ-CV-ER
Heated-only storageSystem 9—Heating and_ventilation_System 10—Heating and_ventilation_
Retail in a_building_ that is 1 or 2_stories_System 3—PSZ-ACSystem 4—PSZ-HP
Hospital that is either
• larger than 150,000 ft2 or
• in a_building_ greater than 5_stories_.
System 7—VAV with_reheat_System 7—VAV with_reheat_
Hospital—all otherSystem 5—Packaged_VAV_ with
reheat
System 5—Packaged_VAV_ with_reheat_
Other_Nonresidential_ area that is both
• smaller than 25,000 ft2 and
• in a_building_ 3_stories_ or fewer.
System 3—PSZ-ACSystem 4—PSZ-HP
Other_Nonresidential_ area that is both
• smaller than 25,000 ft2 and
• in a_building_ with 4 or 5_stories_.
System 5—Packaged_VAV_
with_reheat_
System 6—Packaged_VAV_ with PFP
boxes
Other_nonresidential_ area that is both
• 25,000 ft2 to 150,000 ft2 and
• in a_building_ that is 5_stories_ or fewer.
System 5—Packaged_VAV_
with_reheat_
System 6—Packaged_VAV_ with PFP
boxes
Other_Nonresidential_ area that is either
• larger than 150,000 ft2 or
• in a_building_ greater than 5_stories_.
System 7—VAV with_reheat_System 8—VAV with PFP boxes

a. Building area type determined in accordance with Section G3.2.1.1. b. The total number of stories in a building, including above-grade and below-grade stories but not including stories solely devoted to parking. c. Combined gross conditioned floor area and semiheated floor area, of the building area type, based on the requirements of Section G3.2.1.1.

Table G3.1.1-4 Baseline System Descriptions

System No.System TypeFan ControlCooling Type aHeating Type a
1. PTACPackaged terminal air conditionerConstant volumeDirect expansionHot-water_fossil fuel_ boiler
2. PTHPPackaged terminal heat pumpConstant volumeDirect expansionElectric heat pump
3. PSZ-ACPackaged rooftop air conditionerConstant volumeDirect expansionFossil fuel furnace
4. PSZ-HPPackaged rooftop heat pumpConstant volumeDirect expansionElectric heat pump
5. Packaged_VAV_ with
reheat
Packaged rooftop_VAV_ with_reheat_VAVDirect expansionHot-water_fossil fuel_ boiler
6. Packaged_VAV_ with
PFP boxes
Packaged rooftop_VAV_ with parallel
fan power boxes and_reheat_
VAVDirect expansionElectric resistance
7. VAV with_reheat_VAV with_reheat_VAVChilled waterHot-water_fossil fuel_ boiler
8. VAV with PFP boxesVAV with parallel fan-powered boxes
and_reheat_
VAVChilled waterElectric resistance
9. Heating and_ventilation_Warm air furnace, gas firedConstant volumeNoneFossil fuel furnace
10.Heating and_ventilation_Warm air furnace, electricConstant volumeNoneElectric resistance
11.SZ–VAVSingle-zone_VAV_VAVChilled waterSee note (b).
12.SZ-CV-HWSingle-zone systemConstant volumeChilled waterHot-water_fossil fuel_ boiler
13.SZ-CV-ERSingle-zone systemConstant volumeChilled waterElectric resistance

a. For purchased chilled water and purchased heat, see Section G3.2.1.3. b. For Climate Zones 0 through 3A, the heating type shall be electric resistance . For all other climate zones the heating type shall be hot-water fossil- fuel boiler .

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 323

PDF Page 326

Open page note

Table G3.2.2.5 Climate Conditions under which Economizers are Included forComfort Cooling for Baseline Systems 3 through 8 and 11, 12, and 13

Note: NR means that there is no conditioned building floor area for which economizers are included for the type of zone and climate.

Table G3.2.2.6 Economizer High-Limit Shutoff Temperature

Table G3.2.2.8 Baseline Fan Brake Horsepower

Baseline Fan Motor Brake Horsepower

Notes:

  1. Where A is calculated according to Section 6.5.3.1.1 using the pressure-drop adjustment from the proposed design and the design flow rate of the baseline building system .
  2. Do not include pressure-drop adjustments for evaporative coolers or heat recovery devices that are not required in the baseline building system by Section G3.2.2.9.

Table G3.2.3.7 Type and Number of Chillers

Peak Coincident Cooling Load of
Baseline HVAC Systems Using
Chilled Water
Number and Type of Chillers
300 tons1 liquid-cooled screw chiller
>300 tons, <600 tons2 liquid-cooled screw chillers sized equally
600 tons2 liquid-cooled centrifugal chillers minimum with chillers added so that no chiller is larger than
800 tons, all sized equally

324 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 327

Open page note

Table G3.2.3.11 Heat-Rejection Leaving Water Temperature

Climate ZoneLeaving Water Temperature
5B, 5C, 6B, 865°F
0B, 1B, 2B, 3B, 3C, 4B, 4C, 5A, 6A, 770°F
3A,4A75°F
0A, 1A, 2A80°F

Table G3.2.3.15 Part-Load Performance for VAV Fan Systems

Method 1—Part-Load Fan Power Data

Fan Part-Load RatioFraction of Full-Load Power
0.000.00
0.100.03
0.200.07
0.300.13
0.400.21
0.500.30
0.600.41
0.700.54
0.800.68
0.900.83
1.001.00

Method 2—Part-Load Fan Power Equation

Pfan = 0.0013 + 0.1470  PLR fan + 0.9506  (PLR fan ) [2] - 0.0998  (PLR fan ) [3]

where Pfan = fraction of full-load fan power and PLR fan = fan part-load ratio (current cfm/design cfm)

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 325

PDF Page 328

Open page note

Opaque Elements

Performance Rating Method BuildingEnvelope Requirements for Climate Z
NonresidentialResidential
Assembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.124 U-0.124 U-0.352

Wall, Below-Grade

Floors

Steel-joist U-0.350 U-0.350 U-0.350

Slab-on-Grade Floors

Unheated F-0.730 F-0.730 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700
NonswingingU-1.450U-1.450U-1.450U-1.450U-1.450U-1.450U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_Vertical Glazing, % of_Wall_
0%
to 10.0%
U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44
10.1%
to 20.0%
U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0% to
2.0%
U -1.36
all
SHGC -0.36
all
VT -0.40
all
U -1.36
all
SHGC -0.19
all
VT -0.21
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-1.36SHGCall-0.19VTall-0.21U_all_-1.36SHGCall-0.19VTall-0.21U_all_-1.36SHGCall-0.55VTall-0.61

326 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 329

Open page note

Opaque Elements

Performance Rating Method BuildingEnvelope Requirements for Climate Z
NonresidentialResidential
Assembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.124 U-0.124 U-0.352

Wall, Below-Grade

Floors

Steel-joist U-0.052 U-0.052 U-0.350

Slab-on-Grade Floors

Unheated F-0.730 F-0.730 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700
NonswingingU-1.450U-1.450U-1.450U-1.450U-1.450U-1.450U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -1.22
all
SHGC -0.25
all
VT -0.28
all
U -1.22
all
SHGC -0.39
all
VT -0.43
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0%
to 2.0%
U -1.36
all
SHGC -0.36
all
VT -0.40
all
U -1.36
all
SHGC -0.19
all
VT -0.21
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-1.36SHGCall-0.19VTall-0.21U_all_-1.36SHGCall-0.19VTall-0.21U_all_-1.36SHGCall-0.55VTall-0.61

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 327

PDF Page 330

Open page note

Table G3.4-3 Performance Rating Method Building Envelope Requirements for Climate Zone 3 (A,B,C)*

Opaque
Elements
NonresidentialResidentialSemiheated
Opaque
Elements
Assembly MaximumAssembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.124 U-0.084 U-0.352

Wall, Below-Grade

Below-grade

wall

C-1.140 C-1.140 C-1.140

Floors

Steel-joist U-0.052 U-0.052 U-0.069

Slab-on-Grade Floors

Unheated F-0.730 F-0.730 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700
NonswingingU-1.450U-1.450U-1.450U-0.500U-0.500U-0.500U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -0.57
all
SHGC -0.39
all
VT -0.43
all
U -0.57
all
SHGC -0.39
all
VT -0.43
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-0.57SHGCall-0.25VTall-0.28U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-0.57SHGCall-0.25VTall-0.28U_all_-0.57SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-0.57SHGCall-0.25VTall-0.28U_all_-0.57SHGCall-0.25VTall-0.28U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0%
to 2.0%
U -0.69
all
SHGC -0.39
all
VT -0.43
all
U -0.69
all
SHGC -0.36
all
VT -0.40
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-0.69SHGCall-0.19VTall-0.21U_all_-0.69SHGCall-0.19VTall-0.21U_all_-1.36SHGCall-0.55VTall-0.61
Fenestration
(for Zone 3C)
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -1.22
all
SHGC -0.61
all
VT -0.67
all
U -1.22
all
SHGC -0.61
all
VT -0.67
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-1.22SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.61VTall-0.67U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-1.22SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-1.22SHGCall-0.34VTall-0.37U_all_-1.22SHGCall-0.34VTall-0.37U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0%
to 2.0%
U -1.36
all
SHGC -0.61
all
VT -0.67
all
U -1.36
all
SHGC -0.39
all
VT -0.43
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-1.36SHGCall-0.39VTall-0.43U_all_-1.36SHGCall-0.19VTall-0.21U_all_-1.36SHGCall-0.55VTall-0.61

328 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 331

Open page note

Opaque Elements

Performance Rating Method BuildingEnvelope Requirements for Climate Z
NonresidentialResidential
Assembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.124 U-0.064 U-0.124

Wall, Below-Grade

Floors

Steel-joist U-0.052 U-0.038 U-0.069

Slab-on-Grade Floors

Unheated F-0.730 F-0.730 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700
NonswingingU-1.450U-1.450U-1.450U-0.500U-0.500U-0.500U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -0.57
all
SHGC -0.39
all
VT -0.43
all
U -0.57
all
SHGC -0.39
all
VT -0.43
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0%
to 2.0%
U -0.69
all
SHGC -0.49
all
VT -0.54
all
U -0.58
all
SHGC -0.36
all
VT -0.40
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-0.69SHGCall-0.39VTall-0.43U_all_-0.58SHGCall-0.19VTall-0.21U_all_-1.36SHGCall-0.55VTall-0.61

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 329

PDF Page 332

Open page note

Table G3.4-5 Performance Rating Method Building Envelope Requirements for Climate Zone 5 (A,B,C)*

Opaque Elements

NonresidentialResidential
Assembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.084 U-0.064 U-0.124

Wall, Below-Grade

Floors

Steel-joist U-0.052 U-0.038 U-0.069

Slab-on-Grade Floors

Unheated F-0.730 F-0.730 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700U-0.700
NonswingingU-1.450U-1.450U-1.450U-0.500U-0.500U-0.500U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -0.57
all
SHGC -0.49
all
VT -0.54
all
U -0.57
all
SHGC -0.49
all
VT -0.54
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0%
to 2.0%
U -0.69
all
SHGC -0.49
all
VT -0.54
all
U -0.69
all
SHGC -0.49
all
VT -0.54
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-0.69SHGCall-0.39VTall-0.43U_all_-0.69SHGCall-0.39VTall-0.43U_all_-1.36SHGCall-0.55VTall-0.61

330 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 333

Open page note

Table G3.4-6 Performance Rating Method Building Envelope Requirements for Climate Zone 6 (A,B)*

Opaque Elements

NonresidentialResidential
Assembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.084 U-0.064 U-0.124

Wall, Below-Grade

Floors

Steel-joist U-0.038 U-0.038 U-0.069

Slab-on-Grade Floors

Unheated F-0.730 F-0.730 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.700U-0.700U-0.700U-0.500U-0.500U-0.500U-0.700U-0.700U-0.700
NonswingingU-0.500U-0.500U-0.500U-0.500U-0.500U-0.500U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -0.57
all
SHGC -0.49
all
VT -0.54
all
U -0.57
all
SHGC -0.49
all
VT -0.54
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-0.57SHGCall-0.39VTall-0.43U_all_-0.57SHGCall-0.39VTall-0.43U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0%
to 2.0%
U -0.69
all
SHGC -0.49
all
VT -0.54
all
U -0.58
all
SHGC -0.49
all
VT -0.54
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-0.69SHGCall-0.49VTall-0.54U_all_-0.58SHGCall-0.39VTall-0.43U_all_-1.36SHGCall-0.55VTall-0.61

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 331

PDF Page 334

Open page note

Opaque Elements

Performance Rating Method BuildingEnvelope Requirements for Climate Z
NonresidentialResidential
Assembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.064 U-0.064 U-0.124

Wall, Below-Grade

Floors

Steel-joist U-0.038 U-0.038 U-0.052

Slab-on-Grade Floors

Unheated F-0.730 F-0.540 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.700U-0.700U-0.700U-0.500U-0.500U-0.500U-0.700U-0.700U-0.700
NonswingingU-0.500U-0.500U-0.500U-0.500U-0.500U-0.500U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -0.57
all
SHGC -0.49
all
VT -0.54
all
U -0.57
all
SHGC -0.49
all
VT -0.54
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-0.57SHGCall-0.49VTall-0.54U_all_-0.57SHGCall-0.49VTall-0.54U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-0.57SHGCall-0.49VTall-0.54U_all_-0.57SHGCall-0.49VTall-0.54U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-0.57SHGCall-0.49VTall-0.54U_all_-0.57SHGCall-0.49VTall-0.54U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0%
to 2.0%
U -0.69
all
SHGC -0.68
all
VT -0.75
all
U -0.69
all
SHGC -0.64
all
VT -0.70
all
U -1.36
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-0.69SHGCall-0.64VTall-0.70U_all_-0.69SHGCall-0.64VTall-0.70U_all_-1.36SHGCall-0.55VTall-0.61

332 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 335

Open page note

Table G3.4-8 Performance Rating Method Building Envelope Requirements for Climate Zone 8*

Opaque Elements

NonresidentialResidential
Assembly MaximumAssembly Maximum

Roofs

Walls, Above-Grade

Steel-framed U-0.064 U-0.055 U-0.124

Wall, Below-Grade

Floors

Steel-joist U-0.038 U-0.032 U-0.052

Slab-on-Grade Floors

Unheated F-0.540 F-0.520 F-0.730

Col1Col2Col3Col4Opaque DoorsCol6Col7Col8Col9Col10
SwingingU-0.500U-0.500U-0.500U-0.500U-0.500U-0.500U-0.700U-0.700U-0.700
NonswingingU-0.500U-0.500U-0.500U-0.500U-0.500U-0.500U-1.450U-1.450U-1.450
FenestrationAssembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance
Assembly
Max. U
Assembly
Max. SHGC
Visible
Transmittance

Vertical Glazing, % of Wall

0%
to 10.0%
U -0.46
all
SHGC -0.40
all
VT -0.44
all
U -0.46
all
SHGC -0.40
all
VT -0.44
all
U -1.22
all
SHGC -0.40
all
VT -0.44
all
10.1%
to 20.0%
U_all_-0.46SHGCall-0.40VTall-0.44U_all_-0.46SHGCall-0.40VTall-0.44U_all_-1.22SHGCall-0.40VTall-0.44
20.1%
to 30.0%
U_all_-0.46SHGCall-0.40VTall-0.44U_all_-0.46SHGCall-0.40VTall-0.44U_all_-1.22SHGCall-0.40VTall-0.44
30.1%
to 40.0%
U_all_-0.46SHGCall-0.40VTall-0.44U_all_-0.46SHGCall-0.40VTall-0.44U_all_-1.22SHGCall-0.40VTall-0.44

Skylight All, % of Roof

0% to
2.0%
U -0.58
all
SHGC -0.55
all
VT -0.61
all
U -0.58
all
SHGC -0.55
all
VT -0.61
all
U -0.81
all
SHGC -0.55
all
VT -0.61
all
2.1%+U_all_-0.58SHGCall-0.55VTall-0.61U_all_-0.58SHGCall-0.55VTall-0.61U_all_-0.81SHGCall-0.55VTall-0.61

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 333

PDF Page 336

Open page note

Table G3.4-9 Heated Space CriteriaCol2
Climate ZoneHeating Output, Btu/h·ft2
0, 1, 2>5
3>10
4, 5>15
6,7>20
8>25

Table G3.5.1 Performance Rating Method Air Conditioners (efficiency ratings excluding supply fan power)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
EfficiencyTest Procedure
Air conditioners,
air-cooled
<65,000 Btu/hAllSingle-package3.0_COPnfcooling_AHRI 210/240
Air conditioners,
air-cooled
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
Split-system and
single-package
3.5_COPnfcooling_AHRI 340/360
Air conditioners,
air-cooled
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
3.4_COPnfcooling_3.4_COPnfcooling_
Air conditioners,
air-cooled
240,000 Btu/h and
<760,000 Btu/h
240,000 Btu/h and
<760,000 Btu/h
240,000 Btu/h and
<760,000 Btu/h
3.5_COPnfcooling_3.5_COPnfcooling_
Air conditioners,
air-cooled
760,000 Btu/h760,000 Btu/h760,000 Btu/h3.6_COPnfcooling_3.6_COPnfcooling_

Table G3.5.2 Performance Rating Method Electrically Operated Unitary and Applied Heat Pumps—Minimum Efficiency Requirements (efficiency ratings excluding supply fan power)

Equipment TypeSize CategoryHeating
Section Type
Subcategory or
Rating Condition
Minimum
Efficiency
Test Procedure
Air-cooled
(cooling mode)
<65,000 Btu/hAllSingle package3.0_COPnfcooling_AHRI 210/240
Air-cooled
(cooling mode)
65,000 Btu/h and
<135,000 Btu/h
65,000 Btu/h and
<135,000 Btu/h
Split-system and
single-package
3.4_COPnfcooling_AHRI 340/360
Air-cooled
(cooling mode)
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
135,000 Btu/h and
<240,000 Btu/h
3.2_COPnfcooling_3.2_COPnfcooling_
Air-cooled
(cooling mode)
240,000 Btu/h240,000 Btu/h240,000 Btu/h3.1_COPnfcooling_3.1_COPnfcooling_
Air-cooled
(heating mode)
<65,000 Btu/h
(cooling capacity)
Single-package3.4_COPnfheating_AHRI 210/240
Air-cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.4_COPnfheating_AHRI 340/360
Air-cooled
(heating mode)
65,000 Btu/h and
<135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.3_COPnfheating_2.3_COPnfheating_
Air-cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
outdoor air
3.4_COPnfheating_3.4_COPnfheating_
Air-cooled
(heating mode)
135,000 Btu/h
(cooling capacity)
17°F db/15°F wb
outdoor air
2.1_COPnfheating_2.1_COPnfheating_

334 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 337

Open page note

Table G3.5.3 Performance Rating Method Water Chilling Packages—Minimum Efficiency Requirements

Liquid-cooled, electrically operated, positive displacement

(rotary screw and scroll)

Liquid-cooled, electrically

operated, centrifugal

Size CategorySubcategory or
Rating Condition
Minimum Efficiency
<150 tonskW/ton0.7903 FL
0.6763_IPLV_.IP
150 tons and
<300 tons
150 tons and
<300 tons
0.7178 FL
0.6280_IPLV_.IP
300 tons300 tons0.6395 FL
0.5719_IPLV_.IP
<150 tonskW/ton0.7034 FL
0.6699_IPLV_.IP
150 tons and
<300 tons
150 tons and
<300 tons
0.6337 FL
0.5961_IPLV_.IP
300 tons300 tons0.5766 FL
0.5495_IPLV_.IP

Table G3.5.4 Performance Rating Method Electrically Operated Packaged Terminal Air Conditioners,Packaged Terminal Heat Pumps (efficiency ratings excluding supply fan power)

Equipment TypeSize CategorySubcategory or
Rating Condition
Minimum EfficiencyTest Procedure
PTAC (cooling mode)All capacities95°F db_outdoor air_3.2_COPnfcooling_AHRI 310/380
PTHP (cooling mode)All capacities95°F db_outdoor air_3.1_COPnfcooling_AHRI 310/380
PTHP (heating mode)All capacities3.1_COPnfheating_AHRI 310/380

Table G3.5.5 Performance Rating Method Warm-Air Furnaces and Unit Heaters

Equipment TypeSize CategorySubcategory or Rating
Condition
Minimum EfficiencyTest Procedure
Warm-air furnace, gas-fired<225,000 Btu/h78%AFUE or 80%EtDOE 10 CFR Part 430
or ANSI Z21.47
Warm-air furnace, gas-fired225,000 Btu/hMaximum capacity80%EcANSI Z21.47
Warm-air unit heaters, gas-
fired
All capacitiesMaximum capacity80%EcANSI Z83.8

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 335

PDF Page 338

Open page note

Table G3.5.6 Performance Rating Method Gas-Fired Boilers—Minimum Efficiency Requirements

Size CategorySubcategory or
Rating Condition
Minimum Efficiency
<300,000 Btu/hHot water80%AFUE
300,000 Btu/h and
2,500,000 Btu/h
Maximum capacity75%Et
>2,500,000 Btu/hHot water80%Ec

Table G3.6 Performance Rating Method Lighting Power Densities for Building Exteriors

Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds, building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Uncovered Parking AreasCol3
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Parking lots and drives0.15 W/ft2
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Building GroundsBuilding Grounds
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Walkways less than 10 ft wide1.0 W/linear foot
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Walkways 10 ft wide or greater0.2 W/ft2
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Plaza areasPlaza areas
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Special feature areasSpecial feature areas
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Stairways1.0 W/ft2
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Building Entrances and ExitsBuilding Entrances and Exits
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Main entries30 W/linear foot of_door_ width
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Other_doors_20 W/linear foot of_door_ width
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Canopies and OverhangsCanopies and Overhangs
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Canopies (free standing and attached and overhangs)1.25 W/ft2
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Outdoor SalesOutdoor Sales
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Open areas (including vehicle sales lots)0.5 W/ft2
Tradable Surfaces
(Lighting power densities for
uncovered parking areas,
building grounds,building
entrances and exits, canopies
and overhangs and outdoor sales
areas may be traded.)
Street frontage for vehicle sales lots in addition to open-area
allowance
20 W/linear foot

336 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 339

Open page note

Table G3.7-1 Performance Rating Method Lighting Power Density Allowances andOccupancy Sensor Reductions Using the Space-by-Space Method

Lighting Power

Common Space Types [a]

Atrium

Density,

W/ft [2]

<20 ft in height 0.0375 per foot in total height

 20 ft and  40 ft in height

Occupancy Sensor

Reduction [b]

10%

10%

40 ft in height 0.50 + 0.025 per foot in total height

Audience Seating Area

Auditorium 0.90 10%

Convention center 0.70 10%

Gymnasium 0.40 10%

Motion picture theater 1.20 10%

Performing arts theater 2.60 10%

In a sports arena 0.40 10%

All other audience seating area 0.90 10%

Banking Activity Area 1.50 10%

Classroom/Lecture Hall/Training Room

Preschool through 12th grade, laboratory, and shop classrooms 1.40 30%

All other classroom/lecture hall/training room 1.40 None

Computer Room 2.14 35%

Conference/Meeting/Multipurpose Room 1.30 None

Copy/Print Room 0.90 10%

Corridor 0.50 25%

Courtroom 1.90 10%

Dining Area

Bar/lounge or leisure dining 1.40 35%

Cafeteria or fast food dining 0.90 35%

Family dining 2.10 35%

All other dining area 0.90 35%

Electrical/Mechanical Room 1.50 30%

Emergency Vehicle Garage 0.80 10%

Equipment Room 1.20 10%

Food Preparation Area 1.20 30%

Guest Room 1.14 45%

Laboratory

Preschool through 12th grade, laboratory, and shop classrooms 1.40 30%

All other laboratory except in or as a classroom 1.40 10%

a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 337

PDF Page 340

Open page note

Table G3.7-1 Performance Rating Method Lighting Power Density Allowances andOccupancy Sensor Reductions Using the Space-by-Space Method (Continued)

Lighting Power

Occupancy Sensor

Reduction [b]

Common Space Types [a]

Density,

W/ft [2]

Laundry/Washing Area 0.60 10%

Loading Dock, Interior 0.59 10%

Lobby

Elevator 0.80 25%

Hotel 1.10 25%

Motion picture theater 1.10 25%

Performing arts theater 3.30 25%

All other lobbies 1.30 25%

Locker Room 0.60 25%

Lounge/Breakroom

Mother’s/wellness room 1.13 24%

All other lounge/breakroom 1.20 None

Office

Enclosed and  250 ft [2] 1.10 30%

Enclosed and >250 ft [2] 1.10 30%

Open plan 1.10 15% [c]

Parking Area, Interior

Daylight transition zone 1.75 30%

All other parking areas and drive areas 0.18 30%

Pharmacy Area 1.20 10%

Restroom 0.90 45%

Sales Area 1.70 15%

Seating Area, General 0.68 10%

Security Screening

Airport/bus/ship/train/transportation screening 1.53 0%

Airport/bus/ship/train/transportation screening queue 0.92 0%

General security screening 1.06 0%

Stairwell 0.60 75%

Storage Room

 50 ft [2] 0.80 45%

<50 ft [2] 0.80 45%

Vehicular Maintenance Area 0.70 10%

Workshop

Preschool through 12th grade, laboratory, and shop classrooms 1.40 30%

All other workshops 1.90 10%

a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.

338 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 341

Open page note

Table G3.7-2 Performance Rating Method Lighting Power Density Allowances andOccupancy Sensor Reductions Using the Space-by-Space Method

Lighting Power

Occupancy Sensor

Reduction [b]

Building-Specific Space Types [a]

Casino—Gaming Area

Density,

W/ft [2]

Betting/sportsbook/keno/bingo area 1.34 0%

High-limit game area 2.78 0%

Slot machine/digital gaming area 0.90 0%

Table games area 1.80 0%

Convention Center—Exhibit Space 1.30 35%

Correctional Facilities

Audience seating area 0.70 10%

Classroom 1.30 None

Confinement cells 0.90 10%

Dining area 1.30 35%

Dormitory—Living Quarters 1.11 10%

Facility for the Visually Impaired

Chapel (used primarily by residents) 2.77 10%

Corridor (used primarily by residents) 1.15 25%

Dining (used primarily by residents) 3.32 35%

Lobby (used primarily by residents) 2.26 25%

Recreation room (used primarily by residents) 3.02 10%

Restroom (used primarily by residents) 1.52 45%

Fire Station—Sleeping Quarters 0.30 10%

Gymnasium/Fitness Center

Exercise area 0.90 35%

Playing area 1.40 35%

Health Care Facility

Control room (MRI/CT/Radiology/PET) 2.14 10%

Exam/treatment room 1.50 10%

Hospital corridor 1.00 25%

Lounge 0.80 None

Medical supply room 1.40 45%

Nursery 0.60 10%

Nurse’s station 1.00 10%

Operating room 2.20 10%

Patient room 0.70 10%

a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 339

PDF Page 342

Open page note

Table G3.7-2 Performance Rating Method Lighting Power Density Allowances andOccupancy Sensor Reductions Using the Space-by-Space Method (Continued)

Lighting Power

Occupancy Sensor

Reduction [b]

Building-Specific Space Types [a]

Density,

W/ft [2]

Physical therapy room 0.90 10%

Recovery room 0.80 10%

Telemedicine 2.21 10%

Library

Reading area 1.20 15%

Stacks 1.70 15%

Manufacturing Facility

Detailed manufacturing area 2.10 10%

Low bay area (<25 ft floor-to-ceiling height) 1.20 10%

High bay area (25 to 50 ft floor-to-ceiling height) 1.70 10%

Extra-high bay area (>50 ft floor-to-ceiling height) 1.32 10%

Museum

General exhibition area 1.00 10%

Restoration room 1.70 10%

Performing Arts Theater—Dressing Room 0.64 0%

Post Office—Sorting Area 1.20 10%

Religious Facility

Audience seating area 1.70 10%

Fellowship hall 0.90 10%

Worship/pulpit/choir area 2.40 10%

Retail Facilities

Dressing/fitting room 0.89 10%

Hair care 1.04 10%

Manicure/pedicure 0.70 10%

Mall concourse 1.70 10%

Massage 0.81 10%

Sports Arena—Playing Area

Class I facility 4.61 10%

Class II facility 3.01 10%

Class III facility 2.26 10%

Class IV facility 1.50 10%

Natatorium

Class I facility 3.57 0%

a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.

340 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 343

Open page note

Table G3.7-2 Performance Rating Method Lighting Power Density Allowances andOccupancy Sensor Reductions Using the Space-by-Space Method (Continued)

Lighting Power

Occupancy Sensor

Reduction [b]

Building-Specific Space Types [a]

Density,

W/ft [2]

Class II facility 2.38 0%

Class III facility 1.42 0%

Class IV facility 0.48 0%

Transportation Facility

Airport hanger 2.25 0%

Baggage/carousel area 1.00 10%

Airport concourse 0.60 10%

Passenger loading area 1.11 10%

Ticket counter 1.50 10%

Warehouse—Storage Area

Medium-to-bulky, palletized items 0.90 45%

Smaller, hand-carried items 1.40 45%

a. In cases where both a common space type and a building -specific space type are listed, the building -specific space type shall apply. b. For manual -ON or partial-auto-ON occupancy sensors, the occupancy sensor reduction factor shall be multiplied by 1.25. c. For occupancy sensors controlling individual workstation lighting, occupancy sensor reduction factor shall be 30%.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 341

PDF Page 344

Open page note

Table G3.8 Performance Rating Method Lighting Power Densities Using the Building Area Method

Building Area TypeLighting Power Density, W/ft2
Automotive facility0.90
Convention center1.20
Courthouse1.20
Dining: Bar lounge/leisure1.30
Dining: Cafeteria/fast food1.40
Dining: Family1.60
Dormitory1.00
Exercise center1.00
Fire station1.00
Gymnasium1.10
Health care clinic1.00
Hospital1.20
Hotel/motel1.09
Library1.30
Manufacturing facility1.17
Motion picture theater1.20
Multifamily0.70
Museum1.10
Office1.00
Parking garage0.30
Penitentiary1.00
Performing arts theater1.60
Police station1.00
Post office1.10
Religious facility1.30
Retail1.50
School/university1.20
Sports arena1.10
Town hall1.10
Transportation1.00
Warehouse0.80
Workshop1.40

342 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 345

Open page note

Table G3.9.1 Performance Rating Method Motor Efficiency Requirements

Shaft Input PowerFull-Load Motor Efficiency for Modeling, %
1.082.5
1.584.0
2.084.0
3.087.5
5.087.5
7.589.5
10.089.5
15.091.0
20.091.0
25.092.4
30.092.4
40.093.0
50.093.0
60.093.6
75.094.1
100.094.5
125.094.5
150.095.0
200.095.0

Table G3.9.2 Performance Rating Method Baseline Elevator Motor

Number of Stories
(Including Basement)
Motor
Type
CounterweightMechanical
Efficiency
Motor
Efficiencya
4HydraulicNone58%Table G3.9.3
>4TractionProposed design counterweight, if not specified use weight
of the car plus 40% of the rated load
64%Table G3.9.3

a. Use the efficiency for the next motor size greater than the calculated bhp.

Table G3.9.3 Performance Rating Method Hydraulic Elevator Motor Efficiency

Shaft Input PowerFull-Load Motor Efficiency for Modeling, %
1072%
2075%
3078%
4078%
10080%

Table G3.10.1 Performance Rating Method Commercial Refrigerators and Freezers

Equipment TypeApplicationEnergy Use Limits,
kWh/day
Test Procedure
Refrigerator with solid_doors_Holding temperature0.125 ×_V _+ 2.76AHRI 1200
Refrigerator with transparent_doors_Refrigerator with transparent_doors_0.172 ×_V _+ 4.770.172 ×_V _+ 4.77
Freezers with solid_doors_Freezers with solid_doors_0.398 ×_V _+ 2.280.398 ×_V _+ 2.28
Freezers with transparent_doors_Freezers with transparent_doors_0.94 ×_V _+ 5.100.94 ×_V _+ 5.10
Refrigerators/freezers with solid_doors_Refrigerators/freezers with solid_doors_0.12 ×_V _+ 4.770.12 ×_V _+ 4.77
Commercial refrigerators
Pulldown
0.181 ×_V _+ 5.01
0.181 ×_V _+ 5.01
Note:V is the chiller or frozen compartment volume (ft3) as defined in Association of Home Appliance Manufacturers Standard HRF-1.Note:V is the chiller or frozen compartment volume (ft3) as defined in Association of Home Appliance Manufacturers Standard HRF-1.Note:V is the chiller or frozen compartment volume (ft3) as defined in Association of Home Appliance Manufacturers Standard HRF-1.Note:V is the chiller or frozen compartment volume (ft3) as defined in Association of Home Appliance Manufacturers Standard HRF-1.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 343

PDF Page 346

Open page note

Table G3.10.2 Performance Rating Method Commercial Refrigeration

Equipment Type

Equipment
Classa
Family CodeOperating ModeRating TemperatureEnergy Use Limits,b,c
kWh/day
Test
Procedure
VOP.RC.MVertical openRemote condensingMedium temperature1.01 × TDA + 4.07AHRI 1200
SVO.RC.MSemivertical openRemote condensingMedium temperature1.01 × TDA + 3.181.01 × TDA + 3.18
HZO.RC.MHorizontal openRemote condensingMedium temperature0.51 × TDA + 2.880.51 × TDA + 2.88
VOP.RC.LVertical openRemote condensingLow temperature2.84 × TDA + 6.852.84 × TDA + 6.85
HZO.RC.LHorizontal openRemote condensingLow temperature0.68 × TDA + 6.880.68 × TDA + 6.88
VCT.RC.MVertical transparent_door_Remote condensingMedium temperature0.48 × TDA + 1.950.48 × TDA + 1.95
VCT.RC.LVertical transparent_door_Remote condensingLow temperature1.03 × TDA + 2.611.03 × TDA + 2.61
SOC.RC.MService over counterRemote condensingMedium temperature0.62 × TDA + 0.110.62 × TDA + 0.11
VOP.SC.MVertical openSelf-containedMedium temperature2.34 × TDA + 4.712.34 × TDA + 4.71
SVO.SC.MSemivertical openSelf-containedMedium temperature2.23 × TDA + 4.592.23 × TDA + 4.59
HZO.SC.MHorizontal openSelf-containedMedium temperature1.14 × TDA + 5.551.14 × TDA + 5.55
HZO.SC.LHorizontal openSelf-containedLow temperature2.63 × TDA + 7.082.63 × TDA + 7.08
VCT.SC.IVertical transparent_door_Self-containedIce cream1.63 × TDA + 3.291.63 × TDA + 3.29
VCS.SC.IVertical solid_door_Self-containedIce cream0.55 ×_V _+ 0.880.55 ×_V _+ 0.88
HCT.SC.IHorizontal transparent_door_Self-containedIce cream1.33 × TDA + 0.431.33 × TDA + 0.43
SVO.RC.LSemivertical openRemote condensingLow temperature2.84 × TDA + 6.852.84 × TDA + 6.85
VOP.RC.IVertical openRemote condensingIce cream3.6 × TDA + 8.73.6 × TDA + 8.7
SVO.RC.ISemivertical openRemote condensingIce cream3.6 × TDA + 8.73.6 × TDA + 8.7
HZO.RC.IHorizontal openRemote condensingIce cream0.87 × TDA + 8.740.87 × TDA + 8.74
VCT.RC.IVertical transparent_door_Remote condensingIce cream1.2 × TDA + 3.051.2 × TDA + 3.05
HCT.RC.MHorizontal transparent_door_Remote condensingMedium temperature0.39 × TDA + 0.13AHRI 1200
HCT.RC.LHorizontal transparent_door_Remote condensingLow temperature0.81 × TDA + 0.260.81 × TDA + 0.26
HCT.RC.IHorizontal transparent_door_Remote condensingIce cream0.95 × TDA + 0.310.95 × TDA + 0.31
VCS.RC.MVertical solid_door_Remote condensingMedium temperature0.16 ×_V _+ 0.260.16 ×_V _+ 0.26
VCS.RC.LVertical solid_door_Remote condensingLow temperature0.33 ×_V _+ 0.540.33 ×_V _+ 0.54
VCS.RC.IVertical solid_door_Remote condensingIce cream0.39 ×_V _+ 0.630.39 ×_V _+ 0.63
HCS.RC.MHorizontal solid_door_Remote condensingMedium temperature0.16 ×_V _+ 0.260.16 ×_V _+ 0.26
HCS.RC.LHorizontal solid_door_Remote condensingLow temperature0.33 ×_V _+ 0.540.33 ×_V _+ 0.54
HCS.RC.IHorizontal solid_door_Remote condensingIce cream0.39 ×_V _+ 0.630.39 ×_V _+ 0.63
SOC.RC.LService over counterRemote condensingLow temperature1.3 × TDA + 0.221.3 × TDA + 0.22
SOC.RC.IService over counterRemote condensingIce cream1.52 × TDA + 0.261.52 × TDA + 0.26
VOP.SC.LVertical openSelf containedLow temperature5.87 × TDA + 11.825.87 × TDA + 11.82
VOP.SC.IVertical openSelf-containedIce cream7.45 × TDA + 15.027.45 × TDA + 15.02
SVO.SC.LSemivertical openSelf-containedLow temperature5.59 × TDA + 11.515.59 × TDA + 11.51
SVO.SC.ISemivertical openSelf-containedIce cream7.11 × TDA + 14.637.11 × TDA + 14.63
HZO.SC.IHorizontal openSelf-containedIce cream3.35 × TDA + 9.03.35 × TDA + 9.0
SOC.SC.IService over counterSelf-containedIce cream2.13 × TDA + 0.362.13 × TDA + 0.36
HCS.SC.IHorizontal solid_door_Self-containedIce cream0.55 ×_V _+ 0.880.55 ×_V _+ 0.88
a. Equipment class designations consist of a combination (in sequential order separated by periods [AAA].[BB].[C]) of the following:
(AAA) An_equipment_ family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent_doors_, VCS = vertical solid_doors_, HCT
= horizontal transparent_doors_, HCS = horizontal solid_doors_, and SOC = service over counter); (BB) An operating mode code (RC = remote condensing and SC = self-contained);
and (C) A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example, “VOP.RC.M” refers to the
“vertical open, remote condensing, medium temperature”equipment class.
b. V is the volume of the case (ft3) as measured in AHRI Standard 1200, Appendix C.
c. TDA is the total display area of the case (ft2) as measured in AHRI Standard 1200, Appendix D.
a. Equipment class designations consist of a combination (in sequential order separated by periods [AAA].[BB].[C]) of the following:
(AAA) An_equipment_ family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent_doors_, VCS = vertical solid_doors_, HCT
= horizontal transparent_doors_, HCS = horizontal solid_doors_, and SOC = service over counter); (BB) An operating mode code (RC = remote condensing and SC = self-contained);
and (C) A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example, “VOP.RC.M” refers to the
“vertical open, remote condensing, medium temperature”equipment class.
b. V is the volume of the case (ft3) as measured in AHRI Standard 1200, Appendix C.
c. TDA is the total display area of the case (ft2) as measured in AHRI Standard 1200, Appendix D.
a. Equipment class designations consist of a combination (in sequential order separated by periods [AAA].[BB].[C]) of the following:
(AAA) An_equipment_ family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent_doors_, VCS = vertical solid_doors_, HCT
= horizontal transparent_doors_, HCS = horizontal solid_doors_, and SOC = service over counter); (BB) An operating mode code (RC = remote condensing and SC = self-contained);
and (C) A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example, “VOP.RC.M” refers to the
“vertical open, remote condensing, medium temperature”equipment class.
b. V is the volume of the case (ft3) as measured in AHRI Standard 1200, Appendix C.
c. TDA is the total display area of the case (ft2) as measured in AHRI Standard 1200, Appendix D.
a. Equipment class designations consist of a combination (in sequential order separated by periods [AAA].[BB].[C]) of the following:
(AAA) An_equipment_ family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent_doors_, VCS = vertical solid_doors_, HCT
= horizontal transparent_doors_, HCS = horizontal solid_doors_, and SOC = service over counter); (BB) An operating mode code (RC = remote condensing and SC = self-contained);
and (C) A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example, “VOP.RC.M” refers to the
“vertical open, remote condensing, medium temperature”equipment class.
b. V is the volume of the case (ft3) as measured in AHRI Standard 1200, Appendix C.
c. TDA is the total display area of the case (ft2) as measured in AHRI Standard 1200, Appendix D.
a. Equipment class designations consist of a combination (in sequential order separated by periods [AAA].[BB].[C]) of the following:
(AAA) An_equipment_ family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent_doors_, VCS = vertical solid_doors_, HCT
= horizontal transparent_doors_, HCS = horizontal solid_doors_, and SOC = service over counter); (BB) An operating mode code (RC = remote condensing and SC = self-contained);
and (C) A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example, “VOP.RC.M” refers to the
“vertical open, remote condensing, medium temperature”equipment class.
b. V is the volume of the case (ft3) as measured in AHRI Standard 1200, Appendix C.
c. TDA is the total display area of the case (ft2) as measured in AHRI Standard 1200, Appendix D.
a. Equipment class designations consist of a combination (in sequential order separated by periods [AAA].[BB].[C]) of the following:
(AAA) An_equipment_ family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent_doors_, VCS = vertical solid_doors_, HCT
= horizontal transparent_doors_, HCS = horizontal solid_doors_, and SOC = service over counter); (BB) An operating mode code (RC = remote condensing and SC = self-contained);
and (C) A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example, “VOP.RC.M” refers to the
“vertical open, remote condensing, medium temperature”equipment class.
b. V is the volume of the case (ft3) as measured in AHRI Standard 1200, Appendix C.
c. TDA is the total display area of the case (ft2) as measured in AHRI Standard 1200, Appendix D.

344 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 347

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI require- ments for a standard and may contain material that has not been subject to public review or a consen- sus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX H ADDITIONAL GUIDANCE FOR VERIFICATION, TESTING, AND COMMISSIONING

This appendix provides guidance on best practices for stand-alone functional performance testing ( FPT ) and commissioning processes (including FPT ) that relate to Sections 4.2.5, 5.9, 6.9, 7.9, 8.9, 9.9, 10.9, 12.2(e), and G1.2.1(e) of Standard 90.1. This appendix also contains information on the typical overall commission- ing process that goes beyond the requirements of Standard 90.1. It also addresses how to integrate suggested commissioning and testing activities that are specific to ANSI/ASHRAE/IES Standard 90.1 required controls, systems, and assemblies into the typical commissioning process. The requirements for verification, testing, and commissioning in Standard 90.1 focus specifically on direct support of Standard 90.1 requirements; however, there are additional items often included in a more comprehensive commissioning process that support Standard 90.1 requirements, with these examples:

a. Commissioning building envelope moisture integrity is not required by Standard 90.1; however, prevent ing moisture damage to the envelope assembly supports the goals of Standard 90.1. b. Commissioning HVAC controls to ensure comfort are not required by Standard 90.1; however, controls

that maintain comfort properly result in longer term operation of automatic energy efficiency control elements that support the goals of Standard 90.1. c. Commissioning daylight responsive controls beyond functional testing of stepped lighting reduction for

energy efficiency is not required by Standard 90.1; however, designing and commissioning a continuous dimming daylight system with nondistracting operation and proper illumination levels reduces occupant disruption or complaints and helps ensure the longevity of the savings provided by the Standard 90.1 daylight responsive control requirements.

The information in this appendix provides suggested activities that will improve the likelihood that the energy performance defined by Standard 90.1 is achieved. Commissioning for full performance of the sys- tems installed for energy efficiency avoids a significant investment being lost due to occupants disabling energy efficiency components due to disruption or not meeting non- energy criteria. The actual energy effi- ciency of a building, designed to meet or exceed the requirements of Standard 90.1, is dependent on its operational performance. Many provisions in Standard 90.1 rely on proper execution and verification in design, construction, and operation for their energy savings to occur, especially the proper operation of control sys- tems . Commissioning can have a positive impact on building performance and compliance with Standard 90.1 by providing additional oversight and guidance to the design and construction team.

H1. BENEFITS OF AND RESOURCES FOR BUILDING COMMISSIONING

Common problems in buildings include incorrect installation of building insulation, discontinuity of air and thermal barriers, and nonfunctioning or poorly functioning lighting, HVAC, and other control systems that either are not properly configured or perform outside of intended parameters. These problems adversely affect building energy efficiency and increase building operating expenses. Achieving the intent of Standard 90.1 requires the building ’s design, construction, and operation be in accordance with the standard and includes design and construction performance verification. Using the commissioning process, as defined in ASHRAE Standard 202 and Guideline 0, to verify that a new or renovated building performs in accordance with Standard 90.1 will improve the expected operational performance of the building . See Informative Appendix E for the following references to commissioning standards and guidelines:

a. ANSI/ASHRAE/IES Standard 202, Commissioning Process for Buildings and Systems, provides a stan dard overall approach for the commissioning process. b. ASHRAE Guideline 0, The Commissioning Process, provides more detailed guidelines for steps in the

commissioning process. c. ASHRAE Guideline 1.1, HVAC&R Technical Requirements for the Commissioning Process, provides

more detailed guidelines on the commissioning technical process and functional testing of HVAC systems . d. IES DG 29, The Commissioning Process Applied to Lighting and Control Systems, provides more

detailed guidelines on the commissioning technical process and functional testing of lighting systems . e. ASTM Standard E2947, Standard Guide for Building Enclosure Commissioning, provides an overall

guide for the process of testing of building enclosures.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 345

PDF Page 348

Open page note

SECTIONS DO NOT CLARIFY

NDENCE CRITERIA”

f. ASTM Standard E2813, Standard Practice for Building Enclosure Commissioning, provides more detailed guidelines on the verification and commissioning technical process and testing of building enclosure assemblies. g. NEBB Procedural Standards, Procedural Standards for Building Systems Commissioning, establishes a

uniform and systematic set of criteria for performing the technical commissioning process when applied to new building systems, such as mechanical, electrical, and building envelope systems .

Specific functional performance tests, statistical testing methods, or verification methods for selected items are not listed in this appendix, as they are covered in other commissioning industry documents and resources. They can be selected as the commissioning plan is developed by the owner and commissioning provider . Verification of many of the system controls can be streamlined by setting up trends in the building control system and observing control performance in actual operation. Building operation can also benefit from ongoing commissioning activity that is not covered here. Several commissioning organizations or government agencies make resources available to support the commissioning process:

a. ACG—Associated Air Balance Council Commissioning Group—AABC National Headquarters b. ASHRAE—A leading organization in the development of standardized commissioning standards and

guidelines c. Association of Energy Engineers (AEE) d. Building Commissioning Association (BCxA)—A leading professional association for membership and

certification of building commissioning practitioners e. Building Services Commissioning Association (Japan) f. Commissioning Specialists Association (UK) g. Hong Kong Building Commissioning Centre h. National Conference on Building Commissioning (U.S.) i. National Environmental Balancing Bureau (NEBB)—Certification program and manuals j. National Institute of Building Sciences (NIBS)—Total building commissioning k. California Commissioning Collaborative—A group of government, utility, and building -services profes sionals committed to developing and promoting commissioning practices in California l. Energy Design Resources—Sponsored by Pacific Gas and Electric Company, San Diego Gas and Electric, Southern California Edison, and Southern California Gas m. Federal Energy Management Program—Offers programs and resources for energy efficiency in operation

of federal facilities n. Oregon Department of Energy—Benefits of Commissioning, case study, tool kit of new and existing

commissioning application materials, and the full text of Commissioning for Better Buildings in Oregon o. U.S. DOE EERE commissioning

H2. RECOMMENDED MINIMUM QUALIFICATIONS AND INDEPENDENCEOF COMMISSIONING PROVIDERS AND FUNCTIONAL PERFORMANCETESTING PROVIDERS

Section 4.2.5 requires FPT providers to be qualified and commissioning providers to have the necessary training, experience, and FPT equipment . The following can ensure the needed qualifications and independence for building project testing or commissioning :

a. Equipment: The commissioning provider or FPT providers should use the equipment necessary to per form the commissioning process and FPT . The equipment should be periodically calibrated in accordance with manufacturer ’s specifications. b. Personnel experience: The commissioning provider or FPT providers provide personnel experienced in

conducting, supervising, or evaluating function and performance testing, inspections, and where applicable, performing commissioning activities prior to and subsequent to the tests. Where possible, the com-

d. Registration, licensure, or certification of commissioning provider : Where available, a commissioning

provider should be registered or licensed in a relevant discipline or certified according to the provisions of ISO/IEC 17024 (See Informative Appendix E) or an equivalent certification process. A list of com- missioning certifications available in the U.S. is maintained by NIST (www.wbdg.org).

346 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 349

Open page note

Table H-1 Verification or Commissioning Required by Building Size and Type

Level of Verification or
Commissioning Required
Buildings <10,000 ft2, Warehouse Use Buildings, or Buildings
Using the Simplified Approach Option for HVAC Systems in
Section 6.3
Other Buildings
Verification and_FPT_
Predesign phase and design phase_commissioning_
Construction phase_commissioning_

Figure H-1 Coordination of verification/FPT and commissioning requirements.

H3. OVERVIEW OF THE COMMISSIONING PROCESS

Table H-1 provides an overview of general requirements for verification or the commissioning process required by Section 4.2.5.

An overview of the relationship between the verification/ FPT and commissioning requirements is shown in Figure H-1.

a. The core verification and FPT requirements are specified by discipline in Sections 5.9.1, 6.9.1, 7.9.1,

8.9.1, 9.9.1, 10.9.1, 12.2(e), and G1.2.1(e). b. Provisions are established in the construction documents for verification and FPT, and verification and

testing (V&T) providers are identified as required by Section 4.2.5.1.1. c. The results of this verification and FPT are documented as specified in Section 4.2.5.1.2.

These core V&T requirements and documentation satisfy requirements for smaller buildings, warehouses, and buildings using the simplified approach for HVAC systems, which are exempted from commissioning .

In buildings where commissioning is required, the same verification and FPT requirements apply:

a. A commissioning plan is developed and completed according to Section 4.2.5.2.1. b. The current edition of the standard does not require any additional testing for commissioning beyond

what is required in the base Section 4.2.5.1 verification and FPT requirements. c. In addition, there is a commissioning requirement for design review of verification of compliance with

Standard 90.1 requirements. d. The verification and FPT documentation is included in the commissioning reporting required in Section

4.2.5.2.2.

Table H-2 provides an overview of activities, documentation, and responsibilities that should be included in the commissioning process as defined by Standard 202 and Guideline 0. Not all of these activities are required by Standard 90.1, and the requirement sections are referenced in the “90.1 Section” column.

H4. STANDARD 90.1 ITEMS TO INCLUDE IN VERIFICATION, TESTING, OR COMMISSIONING

Table H-3 lists systems and requirements included in Standard 90.1 that can benefit from a verification or commissioning process. The Standard 90.1 section number and title are included, along with a list of sug

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 347

PDF Page 350

Open page note

Table H-2 Typical Commissioning (Cx) Process Activities, Deliverables and Responsibilities [ a]

ItemActivityDeliverable90.1 SectionNormally Provided byPhase
1Owner’s Project Requirements
(OPR)
OPR documentNROwner with assistance from design
and_Cx_ teams
Predesign
2Basis of Design (BoD)BoD documentNRDesign teamDesign through
construction
3Cx planCx plan document4.2.5.2.2Cx provider with input from
owner, design team, and contractor
Predesign
4Contractor_Cx_ requirementsCx specifications4.2.5.1.1,
4.2.5.2.1,
6.9.2
Design team and
Cx provider
Design
5Design review, including
Standard 90.1 compliance review
Cx design review report
4.2.5.2,
4.2.5.2.2
Cx providerDesign
6Submittal reviewSubmittal review report bNRCx providerConstruction
7Commission designated systems,
inspections,FPT
Installation, inspection,
functional test reports,
performance test reports b
4.2.5.1,
4.2.5.2
Contractors,manufacturers, Cx
provider, and_Cx provider team_
Construction
8Track identified issues to
resolution
Issues and resolution log b4.2.5.1,
4.2.5.2
Cx provider and teamConstruction
9Systems manualSystems manual review
Review NRContractors with review by
Cx provider
Construction
10TrainingTraining plan and reports bNRContractors and_manufacturers_
with review by_Cx provider_
Final
11Preliminary_Cx_ reportPreliminary
Cx report
4.2.5.2.1,
4.2.5.2.2
Cx providerConstruction
12Cx activities during occupancyAdditional information
and updates to reports b
NRCx provider and_building_
operations
Final
13Final_Cx_ reportFinal_Cx_ Report4.2.5.2.2Cx providerFinal

a. NR = not required by Standard 90.1; Cx = commissioning. b. Noted interim or partial deliverables are typically included in the preliminary and final commissioning reports.

gested items to verify in that section. There are specific verification, commissioning, or testing activities required by Standard 90.1 in Sections 4.2.5, 5.9, 6.9, 7.9, 8.9, 9.9, 10.9, 12.2(e), and G1.2.1(e). Table H-3 lists only the items in Standard 90.1 that would be beneficial to include in a commissioning scope. While these requirements cover many of the building components, they are not comprehensive, and there are benefits available from additional commissioning or testing. There are other items outside the scope of Standard 90.1 that would typically be included in a commissioning scope that are not covered here but that may improve the quality and reliability of the building systems and assemblies.

The suggested commissioning activities are intended to be included in a commissioning scope based on the building owner’s perception of desired outcomes relative to the particular building program and location and based on the experience of the commissioning provider . The activities are summarized in a checklist format and are related to the requirements that are described in the noted subsections of Standard 90.1. The scope of the items to verify should include verification of compliance with Standard 90.1 requirements by documenting each item’s applicability, inclusion, or exception. Included items should be verified for installation, proper configuration, and operation. Depending on the comprehensiveness of the commissioning effort, verification for certain items may be included at the design phase, construction phase, or both. Verification that the design and construction meet the requirements of the chosen compliance path in Standard 90.1 could be completed using the verification and compliance forms from the Standard 90.1 User’s Man- ual . Table H-3 could be used as a commissioning scope development checklist, and for each item the status for the subject building could be noted as follows:

NA = not applicable (Either the item is not in the proposed building, an exception was used, or the item or prescriptive requirement was traded off in the performance path.)

Cx = commissioned, verified, or tested

348 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 351

Open page note

Table H-3 Standard 90.1 Items to Verify

SubsectionSubsection TitleStandard 90.1 Items to Verify for Proper Operation or InclusionStatus
4.2.5.2Building Commissioning
Requirements
Document in sufficient detail compliance of the_building_ and its components,
assemblies, controls, and_systems_ with required provisions of this standard.
5.4.1InsulationDesign details maintain continuity of thermal barrier.
5.4.3.2Continuous Air Barrier Design
and Installation
Air barriers meet the following:

Air barrier design and installation per Section 5.4.3.2 and either

whole-building air leakage testing per Section 5.4.3.1 or

design and installation verification program performed in accordance
with Section 5.4.3.1 and Section 5.9.1.2.
5.8.3.1Testing, Acceptable Materials,
and Assemblies
Continuous air barrier materials and assemblies comply with specific
manufacturer requirements or are tested for leakage resistance.
5.8.3.2Fenestration and DoorsFenestration and_doors_ have_manufacturer_ documentation that_air leakage_
does not exceed allowable_air leakage_ rates.
5.5.4.2Fenestration AreaFenestration to_wall_ ratio and_skylight_ to_roof_ ratio meet either the prescriptive
requirements or the_proposed design_ in the performance path, depending on the
compliance path used.
5.8.1InsulationInsulation material meets design specifications and is continuous.
5.9Verification, Testing, and
Commissioning
Envelope assemblies and_fenestration_ comply with requirements.Building
envelope performance is tested or verified.
6.3.2CriteriaHVAC_equipment_ meets_efficiency_ criteria and controls function properly.
6.4.1Equipment Efficiencies,
Verification, and Labeling
Requirements
Equipment selected meets the minimum_efficiency_ requirements and is
correctly_labeled._
6.4.2CalculationsHVAC_equipment_ matches load and_pump_ head calculations.
6.4.3.1/
6.4.3.2
Zone Thermostatic Controls/
Set-Point Overlap Restriction
Zoning pattern and_dead band_ setting configured properly, including_VAV_ zone
controls. Heating and cooling_set points_ do not overlap.
6.4.3.3Off-Hour ControlsOff-hour control,automatic shutdown,setback controls, optimum start control,
and zone isolation are properly configured where applicable.
6.4.3.4Ventilation System ControlsStair and shaft_automatic_ damper function, shutoff damper control, damper
leakage performance, ventilation fans, and enclosed parking garage control
systems operate per code.
6.4.3.5Heat-Pump Auxiliary
Heat Control
Heat-pump auxiliary heat control properly configured.
6.4.3.6Humidifier PreheatAutomatic shutoff valve with configured controls.
6.4.3.6Humidification and
Dehumidification Control
No simultaneous humidification and dehumidification operation.
6.4.3.7Freeze Protection and
Ice/Snow Melt
Automatic shutoff based on outdoor temperature or precipitation.
6.4.3.8Ventilation Controls for
High-Occupancy Areas
Demand control ventilation (DCV) system where applicable.
6.4.3.10Single-Zone VAV ControlSingle-zone systems have multispeed or_VAV_ control properly configured.
6.4.4.1HVAC System InsulationInsulation for ductwork,piping, heating panels, and radiant floor heating
systems correct and continuous.
6.4.4.2Ductwork and Plenum LeakageDuct sealing complete, and required leakage tests performed.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 349

PDF Page 352

Open page note

Table H-3 Standard 90.1 Items to Verify (Continued)

SubsectionSubsection TitleStandard 90.1 Items to Verify for Proper Operation or InclusionStatus
6.5.1.1Air EconomizersOutdoor air and return air damper control sequence properly configured. High-
limit shutoff set properly. Damper leakage and relief air appropriate. Sensor
accuracy and calibration.
6.5.1.2Fluid EconomizersMaximum pressure drop (precooling coils, water-to-water heat exchanger).
Economizer control integration sequence with heating,mechanical cooling,
and inside humidity.
6.5.2.1Zone ControlsZone box minimum position and operating sequence,deadband, and_set points_
configured properly.
6.5.2.2Hydronic System ControlsTwo-pipe changeover control_dead band_ and hydronic heat-pump_system_
controls configured properly.
6.5.2.3/
6.5.2.4
Dehumidification/
Humidification
Humidistatic controls configured properly if applicable.
6.5.2.5Preheat CoilsControl sequence configured properly.
6.5.3.1Fan System Power
and Efficiency
Fans are within power limits or meet_efficiency_ requirements.
6.5.3.2Fan ControlFans are equipped with variable-speed drives or multispeed control where
required, and control sensors and sequence are properly implemented.VAV
static pressure_set point_ is_reset._
6.5.3.3Multiple-Zone VAV System
Ventilation Optimization
Control
Proper configuration of ventilation optimization controls for_VAV systems_.
6.5.3.4Parallel-Flow Fan-Powered
VAV Air-Terminal Control
Check for proper sequence control.
6.5.3.5Supply Air Temperature
Reset Controls
Proper operation of supply air_reset_ controls for multiple zone systems.
6.5.3.6Fractional Horsepower
Fan Motors
For smaller fans, ECM or equivalent_efficiency_ motors have speed control.
6.5.4.1Boiler TurndownBoiler turndown capability and plant load controls for multiple_boilers_ or
modulating burner operation.
6.5.4.2Hydronic Variable Flow
Systems
Hydronic systems are variable flow and equipped with_pump_ speed controls
where required.
6.5.4.3Chiller and Boiler IsolationOffline chillers and_boilers_ are properly isolated and_automatic_ controls
function as required.
6.5.4.4Chilled- and Hot-Water
Temperature Reset Controls
Hydronic temperature_reset_ controls are configured properly where required.
6.5.6Energy RecoveryEnergy recovery systems implemented where required for exhaust air_energy_
recovery and service hot-water heat recovery.
6.5.7Exhaust SystemsProper operation of kitchen and laboratory exhaust air systems where required
for demand ventilation including integration of makeup-air units with
performance testing at multiple flow rates.
6.5.8Radiant Heating SystemsRadiant heating system controls operate properly and are coordinated with
other zone controls.
6.5.10Door SwitchesDoor switches provide proper control integration.
6.5.11Refrigeration SystemsRefrigeration control elements are properly configured.

350 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 353

Open page note

Table H-3 Standard 90.1 Items to Verify (Continued)

SubsectionSubsection TitleStandard 90.1 Items to Verify for Proper Operation or InclusionStatus
6.9Verification, Testing, and
Commissioning
HVAC control_systems_ receive testing for proper operation in accordance with
Sections 6.9 and 4.2.5. See specific items in Sections 6.4 and 6.5.
7.4.4Service Water Heating
System Controls
Proper configuration of temperature and circulation_pump_ controls.
7.4.5.3Time SwitchesProper configuration of_pool_ heater and_pump_ controls.
8.4.2Automatic Receptacle ControlProper control integration of required receptacle and labeling of controlled
receptacles.
8.4.3Electrical Energy MonitoringProper assignment of electrical loads for required end-use monitoring.
9.4.1.1Interior Lighting ControlProper operation of lighting controls, including local control, bilevel control.
9.4.1.2Parking Garage Lighting
Control
Proper operation of parking lot lighting controls, including_occupancy sensor_,
time switch, and daylighting control.
9.4.1.3Special ApplicationsProper operation of lighting controls, including separate control of display,
accent, display case, hotel guest room, nonvisual, and demonstration lighting.
9.4.1.4Exterior Lighting ControlProper operation of exterior lighting controls, including parking area proximity
sensors, time switch, and photocell or astronomical time control.
9.9.1Verification and TestingRequired functional testing is completed for occupant sensors,automatic time
switches, and daylight responsive control. Include control items in Sections
9.4.1.1 through 9.4.1.4.
10.4.2Service Water Pressure
Booster Systems
Required functional testing is completed for service water pressure booster
system controls.
10.4.5Air CurtainsFunctional testing and adjustment per the_manufacturer’s_ installation
requirements
11.5.1Energy Credits RequiredAdequate_energy_ credits are included in the project to meet the requirements of
the_building_ type and climate zone.
11.5.2Energy Credits AchievedIf applicable, test or commission any items in the proposed_building_ not
already covered in Sections 5 through 10 required to achieve the_energy_
efficiency to meet the_energy_ credits required for the_building_ type and climate
zone.
12.2(d), and
G1.2.1(c)
(Energy cost budget and
performance paths)
If applicable, test or commission any items in the proposed_building_ not
already covered in Sections 5 through 10 required to achieve the_energy_
efficiency to meet the chosen performance path.

Commissioning processes and the chosen items to verify can vary based on many factors. Selection of items to verify will be based on the specific project requirements, specific systems, building configuration, and climate zone. Some items may not apply at all in particular buildings . If the Energy Cost Budget Method or Performance Rating Method is used for compliance, the items to verify include any additional efficiency features of the proposed building design that are required for the building to comply using the selected performance path. The list in Table H-3 includes both mandatory items and prescriptive items. The prescriptive items may be adjusted or traded off in one of the performance paths.

H5. COMMISSIONING DOCUMENTATION

The commissioning process typically results in the deliverables included in this section. There may also be interim partial deliverables (as noted in Table H-2) or online issue tracking systems. Standard 90.1 does not require all of these documents; however, they are all part of a complete commissioning process. Where Standard 90.1 has specific requirements, references to the relevant Standard 90.1 sections are included. A document not required by Standard 90.1 is flagged “NR by 90.1.” This section provides background on the general content of these documents, with information about how they support the goals of Standard 90.1.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 351

PDF Page 354

Open page note

Detailed information about the recommended contents of each of these documents can be found in ASHRAE Guideline 0 and other commissioning resources.

H5.1 Owner’s Project Requirements (OPR) (NR by 90.1). The Owner’s Project Requirements (OPR) is a document developed by the owner with assistance from the design and commissioning teams that details the requirements of a project and the expectations for how it will be used and operated. The OPR should include project goals, measurable performance criteria, cost considerations, benchmarks, success criteria, and supporting information. The term “project intent” or “design intent” is used by some owners for their commis- sioning process OPR. The OPR supports the energy efficiency goals of Standard 90.1 by clarifying energy efficiency goals for the building from the owner’s perspective. These goals can be referenced when defending against value engineering efforts that may eliminate efficiency measures without considering long-term building life-cycle cost.

H5.2 Basis of Design (BoD) (NR by 90.1). The Basis of Design (BoD) is a document developed by the design team that records the concepts, calculations, decisions, and product selections used to meet the OPR and to satisfy applicable regulatory requirements, standards, and guidelines. The document should include both narrative descriptions and lists of individual items that support the design process. The BoD supports the energy efficiency goals of Standard 90.1 by clarifying the criteria on which the building system design is based, so that full-load and part-load energy efficiency goals are met. In cases where a BoD is not separately developed, it can be inferred from the preliminary construction documents for purposes of developing a commissioning plan.

H5.3 Commissioning Plan (See Section 4.2.5.2.2). The commissioning plan is a document developed by a commissioning provider that supports the energy efficiency goals of Standard 90.1 by clarifying the commis- sioning activities throughout the design and construction process and how they are integrated into design team and contractor activities. The commissioning plan is also useful in providing the building official with assurance that required commissioning activities will be performed.

H5.4 Contractor Commissioning Requirements (See Sections 4.2.5.1.1, 4.2.5.2.1, and 6.9.2). The com- missioning provider works with the design team to ensure that contractor requirements for involvement in the commissioning process are included in the construction documents . The contractor commissioning requirements support the energy efficiency goals of Standard 90.1 by ensuring that the contractor supports and allows for the commissioning activities within the construction process.

H5.5 Commissioning Design Review Report and Standard 90.1 Compliance Review (See Sections 4.2.5.2 and 4.2.5.2.2). The commissioning provider provides a design review ( commissioning design review report) to the owner and design teams to report compliance with the OPR and BoD. The review includes verification that the design meets the requirements of the chosen path in Standard 90.1, which could be completed using the verification forms from the Standard 90.1 User’s Manual . This commissioning design review is not intended to replace a design peer review or a code or regulatory review. The design review supports the energy efficiency goals of Standard 90.1 by verifying that the design substantially meets the requirements of Standard 90.1. If areas of the design are found to not meet the requirements, the design can be changed at a lower cost before construction begins, avoiding costly change orders during construction .

H5.6 Record Documents (See Sections 4.2.2.1, 6.7.3.1, 8.7.3.1, 9.7.3.1). Record documents are provided to the owner upon project completion. The record documents should be accessible to the building operations and maintenance personnel. The record documents should be included in or referenced by the systems manual. The record documents support the energy efficiency goals of Standard 90.1 by providing information on the design and system criteria so that the operating staff or designers for renovations or upgrades to the building in the future can maintain the specified system efficiency .

H5.7 Systems Manual (See Sections 4.2.2.3, 6.7.3.2, 8.7.3.2, 9.7.3.2). A systems manual supports the energy efficiency goals of Standard 90.1 by providing information on system maintenance and operation so that the operating staff can maintain the specified system efficiency . Including review of the systems manual in the commissioning process will improve the quality of the manuals and make sure that relevant information to the specific building systems operation is included rather than just generic product information. A systems manual should be provided before building operations training for use in the training process. The owner should make the systems manual accessible to the building operations and maintenance personnel throughout the life of the building and ensure that updates are made as the building systems change.

H5.8 Preliminary Commissioning Report (See Section 4.2.5.2.2). A preliminary commissioning report is provided by the commissioning provider and includes the results of the commissioning activities up to the time of occupancy. The results of FPT and other verification is included. The preliminary commissioning report supports the energy efficiency goals of Standard 90.1 by identifying that control sequences related to

352 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 355

Open page note

energy efficiency are working properly, the commissioning plan is useful in providing the building official with assurance that required are in place, where the building official may not have to time or expertise to investigate proper operation. Issues that are unresolved are also identified, as are items that will be tested after occupancy.

H5.9 Final Commissioning Report (See Section 4.2.5.2.2). A final commissioning report is provided by the commissioning provider once all testing is complete. While the final commissioning report is delivered after the occupancy permit, the requirement for it in the construction documents supports the energy effi- ciency goals of Standard 90.1 by providing a future report that will address issues that cannot be resolved at the time of occupancy permit issuance.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 353

PDF Page 356

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI require- ments for a standard and may contain material that has not been subject to public review or a consen- sus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX I USING OTHER METRICS IN CONJUNCTION WITHAPPENDIX G PERFORMANCE RATING METHODWHEN APPROVED BY THE RATING AUTHORITY

I1. GENERAL

This informative appendix describes changes to Section 3, Section 4, and Normative Appendix G for using metrics other than energy cost—including site energy, source energy, and carbon emissions—that may be adopted by the rating authority for the Normative Appendix G Performance Rating Method . It also provides methodology for determining building performance factors (BPFs) that should be used in conjunction with custom energy conversion factors other than the national average defaults in Table I5-1.

I2. CHANGES TO SECTION 3

Replace references to “annual energy cost” with the reference to the selected metric in the definitions of baseline building performance and proposed building performance .

I3. CHANGES TO SECTION 4

a. Replace all references to “ energy cost” in Section 4.2.1.1 with “ site energy,” “source energy,” or “carbon

emissions,” as appropriate, throughout. b. Replace all references to “Performance Cost Index” in Section 4.2.1.1 with “Performance Index (Site

Energy),” “Performance Index (Source Energy),” or “Performance Index (Carbon Emissions),” as appropriate throughout. c. For site energy, replace Table 4.2.1.1 with Table I3-1. d. For carbon emissions, replace Table 4.2.1.1 with Table I3-2. e. For source energy, replace Table 4.2.1.1 with Table I3-3.

I4. CHANGES TO NORMATIVE APPENDIX G

a. Replace references to “ energy cost” with references to “ site energy,” “source energy,” or “carbon emis sions” as appropriate in Sections G1.2.2, G1.3.2, G2.1, G2.4.2, and G2.5 section headings. b. Remove the first sentence and informative note in Section G2.4.2, and replace it with the conversion fac tors from Table I4-1 for the selected metric. c. Add an exception to Section G2.4.2 to allow using alternative conversion factors as appropriate for

building location and as approved by the adopting authority .

I5. METHODOLOGY FOR BPF ADJUSTMENTTO ACCOUNT FOR LOCALIZED CONVERSION FACTORS

The BPF values in Table 4.2.1.1, based on energy cost, and the values in Tables I3-1, I3-2, and I3-3, are based on the coefficients in Tables I5-2 through I5-4 and the electricity and fossil fuel conversion factors in Table I5-1. The values in Table I5-1 represent U.S. national average values. The U.S. national conversion factors may not be appropriate for all locations, and some jurisdictions may want to adopt custom conversion factors other than those shown in Table I5-1. When energy conversion factors other than those specified in Table I5-1 are used, the BPFs should also be updated in accordance with Equation I-1.

BPF i,j = (EC + Ai,j × GC)/( Bi,j × EC + Ci,j × GC) (I-1)

Ai,j, Bi,j, Ci,j = coefficients from Tables I5-2, I5-3, and I5-4 for building area type i and climate zone j

EC = custom electricity conversion factor expressed using the units shown in Table I5-1 for the selected metric

GC = custom natural gas conversion factor expressed using the units shown in Table I5-1 for the selected metric

354 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 357

Open page note

Table I3-1 Building Performance Factors (BPF), Site Energy

Building Area TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Area Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.720.710.750.730.760.760.770.750.700.610.710.640.560.630.630.540.570.540.56
Healthcare/hospital0.670.660.680.650.650.610.620.640.630.620.630.610.650.630.680.640.680.690.71
Hotel/motel0.690.690.720.680.690.680.690.700.710.650.690.680.630.660.670.600.640.590.58
Office0.540.540.530.520.520.520.500.540.470.470.520.480.490.520.490.480.500.430.46
Restaurant0.640.610.600.590.600.570.610.620.610.660.650.660.690.690.680.710.710.720.74
Retail0.510.490.480.480.440.430.430.440.440.470.450.500.520.470.520.520.500.480.49
School0.520.570.570.560.520.530.530.520.550.420.490.530.440.500.510.430.420.420.44
Warehouse0.260.260.220.250.210.220.250.210.180.380.270.310.460.370.310.490.420.430.47
All others0.630.620.650.610.560.530.550.550.590.550.550.580.570.570.610.570.570.560.58

Table I3-2 Building Performance Factors (BPF), Carbon Emission

Building Area TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Area Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.710.690.730.710.740.740.740.750.670.640.730.670.600.670.660.590.610.580.60
Healthcare/hospital0.680.670.690.670.660.630.640.650.630.630.650.620.660.640.670.650.670.690.70
Hotel/motel0.670.670.700.660.670.660.660.680.680.640.670.650.630.650.650.610.630.590.58
Office0.540.540.530.520.520.520.500.540.480.470.520.480.490.520.490.480.500.450.47
Restaurant0.630.600.590.580.580.550.590.580.560.610.600.600.640.630.620.660.660.680.70
Retail0.510.490.480.480.440.430.430.430.440.440.440.480.470.450.490.470.460.450.47
School0.520.570.570.560.520.530.530.510.520.440.480.500.450.480.480.450.430.430.45
Warehouse0.260.260.220.250.210.220.250.210.180.310.240.270.380.310.260.410.360.370.41
All others0.630.610.630.600.550.520.540.540.570.540.530.560.550.550.580.560.560.550.56

Table I3-3 Building Performance Factors (BPF), Source Energy

Building Area TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Area Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.700.690.720.710.730.730.730.750.650.660.740.690.630.690.680.610.630.600.63
Healthcare/hospital0.690.680.700.670.660.640.640.660.640.640.650.630.660.640.660.660.670.680.70
Hotel/motel0.660.670.700.660.660.650.650.670.660.630.660.640.620.640.640.610.620.590.58
Office0.540.540.530.520.520.520.500.540.480.470.530.480.490.520.490.480.500.450.47
Restaurant0.630.590.580.570.580.540.580.560.540.590.570.570.610.600.590.640.620.650.68
Retail0.510.490.480.480.440.430.430.430.440.430.430.470.450.430.480.450.450.430.45
School0.520.570.570.560.520.530.530.500.510.440.470.490.460.470.470.450.430.440.45
Warehouse0.260.260.220.250.210.220.250.210.180.280.230.250.340.280.250.370.320.340.37
All others0.620.610.630.600.550.520.540.530.560.540.530.560.540.540.570.550.550.550.56

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 355

PDF Page 358

Open page note

Table I4-1 Energy Conversion Factors (see Note 1)

Building Project Energy
Source
UnitsCarbon Emissions CO
2e
lb/unit
Site Energy,
Btu/unit
(see Note 2)
Source Energy,
Btu/unit
ElectricitykWh1.2034129008
Natural gasTherm (GJ)19.96100,000109,000
PropaneTherm (GJ)19.080100,000115,000
Distillate fuel oilGallon (L)28.330137,600163,744

Notes:

  1. These conversions are based on national averages for the United States and may not be representative for other locations. Jurisdictions that choose to use localized conversion factors for source energy or carbon emissions should update the corresponding BPF table for consistency using methodology in Section I5. Jurisdictions may add conversion factors for other energy sources.
  2. Site energy only accounts for energy as measured at the building site. It does not account for the energy consumed in the extraction, processing, and transport of primary energy, nor energy consumed in conversion to electricity in power-generation plants.

Table I5-1 National Average Energy Conversion Factors Used to Calculate BPF

MetricSite EnergyCarbon Emissions CO
2e
Source EnergyEnergy Cost
Unitssite kBtu/site kBtulb/site kBtusource kBtu/site kBtu$/site kBtu
Electric conversion factors1.00.3532.640.03221
Natural gas conversion factors1.00.2001.0900.00802
Table I5-2Coefficient A ValuesCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building
Area Type
Climate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate Zone
Building
Area Type
0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.30060.32610.43210.40640.51580.54450.71280.69521.17091.13020.86441.26851.51381.12881.30671.72281.53981.85432.1737
Health care/
hospital
0.12500.14120.15070.15440.19790.16020.23190.20980.26880.32620.25960.38650.49260.36240.59720.61430.61940.84381.0747
Hotel/motel0.27110.28330.32670.33730.39220.45440.51430.60420.69220.84200.76680.97231.06390.93531.08881.24541.19951.47831.9709
Office0.00000.00000.00000.00000.00000.00000.00000.04250.01050.24790.08680.21550.44090.24960.26340.68740.50180.64050.9613
Restaurant0.22100.24180.33660.31200.39840.48130.54160.87521.07941.89871.38552.09562.95522.17912.62203.74193.13534.87437.2168
Retail0.00000.00000.00000.00000.00000.00000.00000.05090.00560.48740.11410.30740.85260.37480.37781.12460.68861.18021.5119
School0.03460.03680.04470.04610.05810.07030.07910.20520.25860.38060.32200.70760.66640.65270.79280.95290.78421.18572.0419
Warehouse0.00000.00000.00000.00000.00000.00000.00000.13230.01582.60580.83931.29164.65832.26571.23026.22183.80345.92786.3860
All others0.15520.16680.22570.20500.17840.15680.20150.31110.41070.72230.38800.73721.05940.71050.71001.26400.97931.29471.8802

Table I5-3 Coefficient B Values

Building Area TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Area Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily1.4721.5041.4401.4721.4341.4331.4551.3181.7011.3141.2631.3051.2831.2591.2881.2481.2781.2511.153
Health care/hospital1.4231.4371.4001.4491.4751.5061.5101.4921.5461.5201.5051.5481.4831.5191.5721.4831.5131.4881.447
Hotel/motel1.5471.5451.4801.5801.5741.6231.6261.5821.6271.6371.6101.6651.6271.6281.6771.6401.6601.6881.719
Office1.8551.8691.9001.9151.9131.9231.9821.8452.0582.0711.8832.0802.0401.9362.0892.1002.0332.0982.031
Restaurant1.6221.7241.7881.8071.8131.9781.8372.0362.1722.0862.1182.2192.1222.1642.2322.1132.1602.1562.192
Retail1.9612.0572.0782.0902.2862.3532.3452.3722.2962.5112.3602.2332.5732.4862.1872.6492.5162.7152.525
School1.9211.7481.7471.7781.9411.9011.9142.0742.0932.1022.1922.2752.0892.2562.3282.0732.2412.1022.146
Warehouse3.8853.8044.4543.9944.6924.5913.9674.8845.2965.7245.2415.4726.0455.5725.4195.9625.5585.9355.477
All others1.6211.6671.6321.7121.8521.9731.9021.9501.8631.8991.9851.8701.9701.9661.8661.9061.9021.8811.933

356 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 359

Open page note

Table I5-4Coefficient C ValuesCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building
Area Type
Climate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate ZoneClimate Zone
Building
Area Type
0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.32680.35470.46980.44190.56080.59210.77510.94611.38022.19381.37252.21503.16732.11092.35143.76133.20734.07654.5499
Health care/
hospital
0.25380.29520.29240.31860.37280.39660.47050.39790.48000.63180.48300.72390.81890.64070.76231.02450.87591.18021.4851
Hotel/motel0.30540.31920.36740.37940.44010.51040.57580.70700.75781.19500.94961.24311.65021.28611.43192.08061.79102.49163.3918
Office0.00000.00000.00000.00000.00000.00000.00000.07760.08900.60780.20770.45250.92240.48280.46561.42630.98181.68922.2766
Restaurant0.28760.31470.43090.40010.50430.60850.67310.98001.24002.32081.52982.49183.61172.41663.11894.58163.66415.95878.8807
Retail0.00000.00000.00000.00000.00000.00000.00000.02680.00310.65020.12920.40501.02390.41910.48731.41960.84691.80382.5674
School0.05740.06050.07160.07340.09060.10910.11850.23320.21241.20810.50760.93541.66981.07081.18242.43361.99583.15874.7541
Warehouse0.00000.00000.00000.00000.00000.00000.00000.42890.37313.79231.52641.83996.16743.29861.73948.72275.855410.16410.401
All others0.20290.21980.26400.26590.23540.22390.26970.41520.52881.25460.54211.14041.66411.04980.94352.06211.56692.24403.0603

I6. SITE ENERGY USE LANGUAGE EXAMPLE

The following example shows the recommended changes to Section 3, Section 4.2.1.1, and Table 4.2.1.1, and Sections G1.2.2, G1.3.2, G2.4.2, and G2.5, if the site energy alternative compliance metric is adopted. Example text is highlighted in gray. Example changes are illustrated with strikethrough and underline.

Modify Section 3 as follows:

proposed building performance: the annual site energy cost calculated for a proposed design .

Modify Section 4.2.1.1 as follows:

[ … ]

where

BBP = baseline building performance.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 357

PDF Page 360

Open page note

PRE = PBP nre - PBP pre

Replace values in Table 4.2.1.1 with the values from Table I3-1 (deleted values not shown):

Table 4.2.1.1 Building Performance Factors (BPF), Site Energy

Building Area TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Area Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Multifamily0.720.710.750.730.760.760.770.750.700.610.710.640.560.630.630.540.570.540.56
Healthcare/hospital0.670.660.680.650.650.610.620.640.630.620.630.610.650.630.680.640.680.690.71
Hotel/motel0.690.690.720.680.690.680.690.700.710.650.690.680.630.660.670.600.640.590.58
Office0.540.540.530.520.520.520.500.540.470.470.520.480.490.520.490.480.500.430.46
Restaurant0.640.610.600.590.600.570.610.620.610.660.650.660.690.690.680.710.710.720.74
Retail0.510.490.480.480.440.430.430.440.440.470.450.500.520.470.520.520.500.480.49
School0.520.570.570.560.520.530.530.520.550.420.490.530.440.500.510.430.420.420.44
Warehouse0.260.260.220.250.210.220.250.210.180.380.270.310.460.370.310.490.420.430.47
All others0.630.620.650.610.560.530.550.550.590.550.550.580.570.570.610.570.570.560.58

Modify Section G1.2.2 as follows:

Modify Section G1.3.2(a) and G1.3.2(p) as follows:

[ … ]

The following documentation shall be submitted to the rating authority :

358 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 361

Open page note

[ … ]

Modify Section G2.4.2 as follows:

Table G2.1 Units of Fuel to Site Energy Conversion Factors

Building Project Energy SourceUnitsSite Energy,
Btu/unit
ElectricitykWh3412
Natural gastherm100,000
Propanetherm100,000
Distillate fuel oilgal137,600

Modify Section G2.5(e) as follows:

[ … ]

e. The Performance Cost Index calculated with and without the exceptional calculation method.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 359

PDF Page 362

Open page note

(This is a normative appendix and is part of this standard.)

NORMATIVE APPENDIX J SETS OF PERFORMANCE CURVES

J1. GENERAL

J1.1 Description. This appendix provides sets of performance curves that shall be used to represent the part-load performance of chillers in the budget building design when using Section 12 and in the baseline building design when using Normative Appendix G. They are also permitted to be used for the proposed building design when specific chiller performance is not known.

Each set includes three curves: an energy-input-ratio modifier as a function of temperatures (EIR-f-T) and as a function of a chiller’s part-load ratio (EIR-f-PLR), and a capacity modifier as a function of temperatures (CAP-f-T). These curves are intended to describe the part-load performance of a chiller when its operating capacity and power (not including cycling degradation) are calculated by the simulation program as follows:

Operating Capacity = Rated Capacity × CAP-f-T Operating Power = Operating Capacity × EIR-f-T × EIR-f-PLR × Chiller Input Power at Rated Conditions/Chiller Capacity at Rated Conditions Table J-3 provides the reference values for the curves. Tables J-4 and J-6 are to be used when the simu- lation program uses I-P units to evaluate the performance curves, and Tables J-5 and J-7 are to be used when the simulation program uses SI units to evaluate the performance curves.

Table J-1 Sets of Chiller Performance Curves for Section 12

Equipment TypeSize CategorySet
Path A
Set
Path B
Air-cooled chillers<150 tonsAK
Air-cooled chillers≥150 tonsBL
Liquid-cooled, electrically operated positive displacement<75 tonsCM
Liquid-cooled, electrically operated positive displacement≥75 tons and <150 tonsDN
Liquid-cooled, electrically operated positive displacement≥150 tons and <300 tonsEO
Liquid-cooled, electrically operated positive displacement≥300 tons and <600 tonsFP
Liquid-cooled, electrically operated positive displacement≥600 tonsGQ
Liquid-cooled, electrically operated centrifugal<150 tonsHR
Liquid-cooled, electrically operated centrifugal≥150 tons and <300 tonsHS
Liquid-cooled, electrically operated centrifugal≥300 tons and <400 tonsIT
Liquid-cooled, electrically operated centrifugal≥400 tons and <600 tonsJU
Liquid-cooled, electrically operated centrifugal≥600 tonsJU

Table J-2 Sets of Chiller Performance Curves for Normative Appendix G

Equipment TypeSize CategorySet
Water-cooled, electrically operated, positive
displacement (rotary screw and scroll)
<150 tonsV
Water-cooled, electrically operated, positive
displacement (rotary screw and scroll)
≥150 tons and <300 tonsX
Water-cooled, electrically operated, positive
displacement (rotary screw and scroll)
≥300 tonsY
Water-cooled, electrically operated, centrifugal<150 tons
≥150 tons and <300 tons
Z
AA
Water-cooled, electrically operated, centrifugal≥300 tonsAB

360 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 363

Open page note

Table J-3 Chiller Performance Curves References

Chiller
Condenser
Type
Output
Variable a
Curve
Type b
X cY cMinimum/
Maximum
Value for
X (I-P °F)
Minimum/
Maximum
Value for
Y (I-P °F)
Rated Values
for X/Y
(I-P °F)
AirEIR-f-TT1CHWTOAT39/6055/12644/95
AirCAP-f-TT1CHWTOAT39/6055/12644/95
AirEIR-f-PLRT3PLR0/11
Water
Water
EIR-f-T
CAP-f-T
T1
T1
CHWT
CHWT
ECT
ECT
39/60
39/60
55/104
55/104
44/85
44/85
WaterEIR-f-PLRT2PLR0/11

a. EIR-f-T is the energy input ratio modifier as a function of temperatures; CAP-f-T is the capacity modifier as a function of temperatures; and EIR-f-PLR

is the energy input ratio modifier as a function of the chiller’s part load ratio. b. T1: Output = Coeff1 + Coeff2 × X + Coeff3 × X [2] + Coeff4 × Y + Coeff5 × Y [2] + Coeff6 × X × Y

T2 : Output = Coeff1 + Coeff2 × X + Coeff3 × X [2]

T3: Output = Coeff1 + Coeff2 × X + Coeff3 × X [2] + Coeff4 × X [3]

c. CHWT : chilled-water temperature

OAT: outdoor-air dry-bulb temperature ECT: entering condenser temperature PLR: part-load ratio = load at a given simulation time step/available capacity at given simulation time step

Table J-4 Chiller Performance Curves for Section 12 (Simulation Input Required in I-P units)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
EIR-f-T1.777758–0.0382580.000431–0.0053680.000118–0.000115
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
CAP-f-T–1.3476970.070674–0.0005660.016793–0.000104–0.000076
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
EIR-f-PLR0.0877890.1856961.561411–0.832304
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
EIR-f-T1.872341–0.0418860.000442–0.0067100.000123–0.000086
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
CAP-f-T–1.1535350.075066–0.0006220.009777–0.000071–0.000057
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
EIR-f-PLR0.1180810.1074771.570838–0.794051
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
EIR-f-T2.001725–0.0449570.000484–0.0082960.000168–0.000125
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
CAP-f-T–0.9075980.073300–0.0006530.003700–0.0000540.000006
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
EIR-f-PLR0.2437300.1659720.586099
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
EIR-f-T1.679306–0.0419600.000456–0.0020810.000128–0.000125
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
CAP-f-T–0.8577910.074596–0.0006700.001523–0.0000420.000012
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
EIR-f-PLR0.2089820.2240010.561479
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
EIR-f-T1.136125–0.0346080.0004010.0080060.000058–0.000131
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
CAP-f-T–0.4249420.047087–0.0004580.006232–0.0000700.000058
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
EIR-f-PLR0.2466440.1845760.566463
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
EIR-f-T1.161349–0.0405570.0004310.0135670.000003–0.000103
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
CAP-f-T0.0127660.033086–0.0003500.004004–0.0000610.000083
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
EIR-f-PLR0.2449260.2188900.532972
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-T0.874461–0.0413900.0004300.022262–0.000058–0.000097
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T0.1223040.024081–0.0002930.006302–0.0000810.000116
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2643710.2633020.471690

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 361

PDF Page 364

Open page note

Table J-4 Chiller Performance Curves for Section 12 (Simulation Input Required in I-P units) (Continued)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
HLiquid-cooled
centrifugal <150 tons
0.610 FL, 0.550
IPLV.IP Path A
EIR-f-T0.474969–0.0360870.0002230.030749–0.0001780.000094
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
CAP-f-T–0.4540520.056252–0.0006690.000736–0.0000990.000249
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
EIR-f-PLR0.3042060.0738660.621457
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-T0.596868–0.0227680.0001310.023536–0.0001300.000024
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
CAP-f-T0.9470090.032913–0.000354–0.0201510.0000620.000148
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-PLR0.2769610.1017490.621383
JLiquid-cooled
centrifugal ≥400 tons
<600 tons 0.560 FL,
0.500_IPLV_.IP Path A
EIR-f-T0.551957–0.0361960.0003000.028396–0.0001470.000029
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T–0.7022420.077132–0.000785–0.005637–0.0000330.000145
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2908910.0593660.649421
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-T2.054048–0.0424060.000450–0.0098130.000140–0.000093
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
CAP-f-T–1.3256520.074160–0.0006070.013871–0.000088–0.000069
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-PLR0.0368490.1007921.614142–0.748013
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-T1.673814–0.0411780.000429–0.0034240.000109–0.000084
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
CAP-f-T–0.9393450.074488–0.0006150.005127–0.000048–0.000048
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-PLR0.0957110.0099031.543396–0.646737
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-T2.018167–0.0451110.000485–0.0085030.000168–0.000124
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
CAP-f-T–0.9137520.073361–0.0006540.003787–0.0000540.000006
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-PLR0.1072000.1826110.705182
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-T1.849951–0.0434090.000467–0.0051870.000146–0.000123
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
CAP-f-T–0.8403420.071938–0.0006410.002703–0.0000470.000007
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-PLR0.183811–0.0444170.855660
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-T1.020192–0.0300460.0003630.0085040.000053–0.000135
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
CAP-f-T–0.4517490.051393–0.0004900.004351–0.0000580.000050
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-PLR0.0909360.2078120.696735
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-T1.189071–0.0385850.0004150.0115740.000017–0.000108
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
CAP-f-T–0.0638520.038321–0.0003880.002935–0.0000540.000072
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-PLR0.1036650.1480240.744887
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
EIR-f-T0.916144–0.0415410.0004360.020987–0.000047–0.000100
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
CAP-f-T0.1318800.023312–0.0002860.006699–0.0000840.000116
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
EIR-f-PLR0.0617060.2617110.677017

362 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 365

Open page note

Table J-4 Chiller Performance Curves for Section 12 (Simulation Input Required in I-P units) (Continued)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
RLiquid-cooled
centrifugal <150 tons
0.695 FL, 0.440
IPLV.IP Path B
EIR-f-T0.860442–0.0364140.0003170.022419–0.0001080.000001
RLiquid-cooled
centrifugal <150 tons
0.695 FL, 0.440
IPLV.IP Path B
CAP-f-T–0.0627720.054642–0.000550–0.0080720.0000040.000101
RLiquid-cooled
centrifugal <150 tons
0.695 FL, 0.440
IPLV.IP Path B
EIR-f-PLR0.0721830.1086500.818174
SLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.635 FL,
0.400_IPLV_.IP Path B
EIR-f-T0.582513–0.0337860.0002270.027678–0.0001570.000067
SLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.635 FL,
0.400_IPLV_.IP Path B
CAP-f-T0.0159410.049796–0.000573–0.007266–0.0000410.000219
SLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.635 FL,
0.400_IPLV_.IP Path B
EIR-f-PLR0.0649790.1518290.779131
TLiquid-cooled
centrifugal ≥300 tons
<400 tons 0.595 FL,
0.390_IPLV_.IP Path B
EIR-f-T0.634610–0.0334720.0002600.026148–0.0001300.000015
TLiquid-cooled
centrifugal ≥300 tons
<400 tons 0.595 FL,
0.390_IPLV_.IP Path B
CAP-f-T0.1275960.046709–0.000538–0.006247–0.0000470.000195
TLiquid-cooled
centrifugal ≥300 tons
<400 tons 0.595 FL,
0.390_IPLV_.IP Path B
EIR-f-PLR0.0828120.1528160.764822
ULiquid-cooled
centrifugal ≥400 tons
<600 tons 0.585 FL,
0.380_IPLV_.IP Path B
EIR-f-T0.593414–0.0289480.0002240.024197–0.0001260.000027
ULiquid-cooled
centrifugal ≥600 tons
0.585 FL, 0.380
IPLV.IP Path B
CAP-f-T–0.4874220.071558–0.000737–0.006964–0.0000320.000158
ULiquid-cooled
centrifugal ≥600 tons
0.585 FL, 0.380
IPLV.IP Path B
EIR-f-PLR0.0585830.2054860.736345

Table J-5 Chiller Performance Curves for Section 12 (Simulation Input Required in SI Units)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
EIR-f-T0.825618–0.0258610.001396–0.0027280.000381–0.000373
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
CAP-f-T0.6862060.057562–0.0018350.013810–0.000338–0.000247
AAir-cooled <150 tons,
10.100 FL, 13.700
IPLV.IP Path A
EIR-f-PLR0.0877890.1856961.561411–0.832304
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
EIR-f-T0.807832–0.0294520.001431–0.0028320.000399–0.000278
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
CAP-f-T0.7941850.060199–0.0020160.006203–0.000229–0.000183
BAir-cooled ≥150 tons,
10.100 FL, 14.00
IPLV.IP Path A
EIR-f-PLR0.1180810.1074771.570838–0.794051
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
EIR-f-T0.836880–0.0323830.001568–0.0028060.000544–0.000407
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
CAP-f-T0.8383370.057024–0.0021170.000793–0.0001750.000020
CLiquid-cooled positive
displacement <75 tons
0.750 FL, 0.600
IPLV.IP Path A
EIR-f-PLR0.2437300.1659720.586099
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
EIR-f-T0.740920–0.0301440.0014790.0038500.000416–0.000404
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
CAP-f-T0.8618400.057837–0.002170–0.001391–0.0001360.000040
DLiquid-cooled positive
displacement ≥75 and
<150 tons 0.720 FL,
0.560_IPLV_.IP Path A
EIR-f-PLR0.2089820.2240010.561479
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
EIR-f-T0.620834–0.0236420.0013000.0135550.000189–0.000425
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
CAP-f-T0.8000660.035377–0.0014820.006462–0.0002270.000187
ELiquid-cooled positive
displacement ≥150 and
<300 tons 0.660 FL,
0.540_IPLV_.IP Path A
EIR-f-PLR0.2466440.1845760.566463
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
EIR-f-T0.636828–0.0292450.0013970.0188170.000008–0.000332
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
CAP-f-T0.8631750.023955–0.0011350.004955–0.0001970.000268
FLiquid-cooled positive
displacement ≥300 and
<600 tons 0.610 FL,
0.520_IPLV_.IP Path A
EIR-f-PLR0.2449260.2188900.532972

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 363

PDF Page 366

Open page note

Table J-5 Chiller Performance Curves for Section 12 (Simulation Input Required in SI Units) (Continued)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-T0.544967–0.0304910.0013950.027852–0.000187–0.000314
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T0.8308040.016310–0.0009490.008707–0.0002630.000377
GLiquid-cooled positive
displacement ≥600
tons 0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2643710.2633020.471690
HLiquid-cooled
centrifugal <150 tons
0.610 FL, 0.550
IPLV.IP Path A
EIR-f-T0.447243–0.0337850.0007240.040274–0.0005770.000305
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
CAP-f-T0.8374200.038528–0.0021670.004185–0.0003220.000806
HLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.610 FL,
0.550_IPLV_.IP Path A
EIR-f-PLR0.3042060.0738660.621457
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-T0.647193–0.0244840.0004260.028764–0.0004210.000077
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
CAP-f-T1.2078780.026951–0.001148–0.0205760.0002020.000479
ILiquid-cooled
centrifugal ≥300 tons
<400 tons 0.560 FL,
0.520_IPLV_.IP Path A
EIR-f-PLR0.2769610.1017490.621383
JLiquid-cooled
centrifugal ≥400 tons
<600 tons 0.560 FL,
0.500_IPLV_.IP Path A
EIR-f-T0.489242–0.0288510.0009730.035835–0.0004770.000096
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
CAP-f-T0.8968060.056739–0.002544–0.005536–0.0001050.000470
JLiquid-cooled
centrifugal ≥600 tons
0.560 FL, 0.500
IPLV.IP Path A
EIR-f-PLR0.2908910.0593660.649421
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-T0.891872–0.0298210.001459–0.0069290.000453–0.000303
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
CAP-f-T0.7091950.059566–0.0019680.010899–0.000284–0.000222
KAir-cooled <150 tons,
9.700 FL, 15.800
IPLV.IP Path B
EIR-f-PLR0.0368490.1007921.614142–0.748013
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-T0.711589–0.0295200.0013900.0015540.000353–0.000272
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
CAP-f-T0.8798440.060415–0.0019940.000937–0.000156–0.000155
LAir-cooled ≥150 tons,
9.700 FL, 16.100
IPLV.IP Path B
EIR-f-PLR0.0957110.0099031.543396–0.646737
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-T0.844064–0.0325040.001571–0.0030760.000545–0.000402
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
CAP-f-T0.8358030.057057–0.0021190.000903–0.0001760.000019
MLiquid-cooled positive
displacement <75 tons
0.780 FL, 0.500
IPLV.IP Path B
EIR-f-PLR0.1072000.1826110.705182
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-T0.797371–0.0313610.0015140.0004190.000473–0.000398
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
CAP-f-T0.8507100.056037–0.002077–0.000147–0.0001530.000023
NLiquid-cooled positive
displacement ≥75 and
<150 tons 0.750 FL,
0.490_IPLV_.IP Path B
EIR-f-PLR0.183811–0.0444170.855660
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-T0.617871–0.0201100.0011750.0136230.000172–0.000439
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
CAP-f-T0.8225190.038968–0.0015880.004048–0.0001880.000164
OLiquid-cooled positive
displacement ≥150 and
<300 tons 0.680 FL,
0.440_IPLV_.IP Path B
EIR-f-PLR0.0909360.2078120.696735
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-T0.656763–0.0278910.0013430.0166270.000056–0.000348
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
CAP-f-T0.8772180.028393–0.0012570.003217–0.0001740.000232
PLiquid-cooled positive
displacement ≥300 and
<600 tons 0.625 FL,
0.410_IPLV_.IP Path B
EIR-f-PLR0.1036650.1480240.744887

364 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 367

Open page note

Table J-5 Chiller Performance Curves for Section 12 (Simulation Input Required in SI Units) (Continued)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
EIR-f-T0.553694–0.0303470.0014120.026568–0.000153–0.000325
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
CAP-f-T0.8318280.015657–0.0009280.009067–0.0002720.000376
QLiquid-cooled positive
displacement ≥600
tons 0.585 FL, 0.380
IPLV.IP Path B
EIR-f-PLR0.0617060.2617110.677017
RLiquid-cooled
centrifugal <150 tons
0.695 FL, 0.440
IPLV.IP Path B
EIR-f-T0.627360–0.0289890.0010270.027958–0.0003500.000002
RLiquid-cooled
centrifugal <150 tons
0.695 FL, 0.440
IPLV.IP Path B
CAP-f-T0.9725170.040861–0.001781–0.0082170.0000130.000328
RLiquid-cooled
centrifugal <150 tons
0.695 FL, 0.440
IPLV.IP Path B
EIR-f-PLR0.0721830.1086500.818174
SLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.635 FL,
0.400_IPLV_.IP Path B
EIR-f-T0.526475–0.0308430.0007350.035532–0.0005100.000216
SLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.635 FL,
0.400_IPLV_.IP Path B
CAP-f-T0.9716990.036192–0.001858–0.005224–0.0001340.000709
SLiquid-cooled
centrifugal ≥150 tons
<300 tons 0.635 FL,
0.400_IPLV_.IP Path B
EIR-f-PLR0.0649790.1518290.779131
TLiquid-cooled
centrifugal ≥300 tons
<400 tons 0.595 FL,
0.390_IPLV_.IP Path B
EIR-f-T0.547810–0.0294700.0008420.032888–0.0004230.000048
TLiquid-cooled
centrifugal ≥300 tons
<400 tons 0.595 FL,
0.390_IPLV_.IP Path B
CAP-f-T1.0233370.033378–0.001742–0.005438–0.0001530.000633
TLiquid-cooled
centrifugal ≥300 tons
<400 tons 0.595 FL,
0.390_IPLV_.IP Path B
EIR-f-PLR0.0828120.1528160.764822
ULiquid-cooled
centrifugal ≥400 tons
<600 tons 0.585 FL,
0.380_IPLV_.IP Path B
EIR-f-T0.569569–0.0247000.0007270.030569–0.0004090.000087
ULiquid-cooled
centrifugal ≥600 tons
0.585 FL, 0.380
IPLV.IP Path B
CAP-f-T0.9535800.053010–0.002387–0.007165–0.0001040.000510
ULiquid-cooled
centrifugal ≥600 tons
0.585 FL, 0.380
IPLV.IP Path B
EIR-f-PLR0.0585830.2054860.736345

Table J-6 Chiller Performance Curves for Normative Appendix G (Simulation Input Required in I-P Units)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
VLiquid-cooled positive
displacement <150
tons 0.7903 FL,
0.6763_IPLV_.IP
EIR–f–T2.044998–0.0475150.000505–0.0087870.000175–0.000120
VLiquid-cooled positive
displacement <150
tons 0.7903 FL,
0.6763_IPLV_.IP
CAP–f–T–0.9819090.076674–0.0006870.003920–0.0000580.000006
VLiquid-cooled positive
displacement <150
tons 0.7903 FL,
0.6763_IPLV_.IP
EIR–f–PLR0.2760370.2535770.466353
XLiquid-cooled positive
displacement ≥150
and <300 tons 0.7178
FL, 0.6280_IPLV_.IP
EIR–f–T1.037805–0.0246950.0003290.0031300.000102–0.000159
XLiquid-cooled positive
displacement ≥150
and <300 tons 0.7178
FL, 0.6280_IPLV_.IP
CAP–f–T–0.6838580.065283–0.0006020.002347–0.0000500.000036
XLiquid-cooled positive
displacement ≥150
and <300 tons 0.7178
FL, 0.6280_IPLV_.IP
EIR–f–PLR0.2508010.3459150.399138
YLiquid-cooled positive
displacement ≥300
tons 0.6395 FL,
0.5719_IPLV_.IP
EIR–f–T1.188945–0.0394260.0004130.0128880.000002–0.000098
YLiquid-cooled positive
displacement ≥300
tons 0.6395 FL,
0.5719_IPLV_.IP
CAP–f–T–0.1606810.044390–0.0004290.001024–0.0000350.000055
YLiquid-cooled positive
displacement ≥300
tons 0.6395 FL,
0.5719_IPLV_.IP
EIR–f–PLR0.3200970.0743560.602938
ZLiquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
EIR–f–T0.857485–0.0361480.0003140.022356–0.0001080.000001
ZLiquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
CAP–f–T–0.0619580.054739–0.000550–0.0081770.0000050.000101
ZLiquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
EIR–f–PLR0.2816690.2027620.515409
AALiquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
EIR–f–T0.479847–0.0359640.0002250.031377–0.0001830.000085
AALiquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
CAP–f–T–0.1280810.050459–0.000581–0.004297–0.0000490.000200
AALiquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
EIR–f–PLR0.3394940.0490900.611582

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 365

PDF Page 368

Open page note

Table J-6 Chiller Performance Curves for Normative Appendix G (Simulation Input Required in I-P Units) (Continued)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
ABLiquid-cooled
centrifugal ≥300 tons
0.5766 FL, 0.5495
IPLV.IP
EIR–f–T0.747210–0.0388740.0003130.027638–0.000133–0.000008
ABLiquid-cooled
centrifugal ≥300 tons
0.5766 FL, 0.5495
IPLV.IP
CAP–f–T0.1172080.042940–0.000478–0.003930–0.0000450.000155
ABLiquid-cooled
centrifugal ≥300 tons
0.5766 FL, 0.5495
IPLV.IP
EIR–f–PLR0.3097520.1536490.536462

Table J-7 Chiller Performance Curves for Normative Appendix G (Simulation Input Required in SI Units)

SetDescriptionOutput
Variable
Coeff 1Coeff 2Coeff 3Coeff 4Coeff 5Coeff 6
VLiquid-cooled positive
displacement <150
tons 0.7903 FL,
0.6763_IPLV_.IP
EIR-f-T0.817024–0.0342130.001638–0.0025900.000566–0.000389
VLiquid-cooled positive
displacement <150
tons 0.7903 FL,
0.6763_IPLV_.IP
CAP-f-T0.8408980.059263–0.0022250.000735–0.0001880.000020
VLiquid-cooled positive
displacement <150
tons 0.7903 FL,
0.6763_IPLV_.IP
EIR-f-PLR0.2760370.2535770.466353
XLiquid-cooled positive
displacement ≥150
and <300 tons 0.7178
FL, 0.6280_IPLV_.IP
EIR-f-T0.627193–0.0156460.0010670.0082700.000331–0.000515
XLiquid-cooled positive
displacement ≥150
and <300 tons 0.7178
FL, 0.6280_IPLV_.IP
CAP-f-T0.8501330.050234–0.0019510.000606–0.0001610.000118
XLiquid-cooled positive
displacement ≥150
and <300 tons 0.7178
FL, 0.6280_IPLV_.IP
EIR-f-PLR0.2508010.3459150.399138
YLiquid-cooled positive
displacement ≥300
tons 0.6395 FL,
0.5719_IPLV_.IP
EIR-f-T0.664854–0.0290160.0013390.0178230.000008–0.000318
YLiquid-cooled positive
displacement ≥300
tons 0.6395 FL,
0.5719_IPLV_.IP
CAP-f-T0.8731300.033599–0.0013910.000961–0.0001140.000178
YLiquid-cooled positive
displacement ≥300
tons 0.6395 FL,
0.5719_IPLV_.IP
EIR-f-PLR0.3200970.0743560.602938
Z
AA
Liquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
Liquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
EIR-f-T0.628525–0.0287980.0010190.027867–0.0003490.000002
Z
AA
Liquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
Liquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
CAP-f-T0.9733100.040996–0.001782–0.0083400.0000160.000327
Z
AA
Liquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
Liquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
EIR-f-PLR0.2816690.2027620.515409
Z
AA
Liquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
Liquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
EIR-f-T0.464330–0.0338340.0007310.040345–0.0005920.000277
Z
AA
Liquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
Liquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
CAP-f-T0.9096330.035460–0.001881–0.001808–0.0001580.000648
Z
AA
Liquid-cooled
centrifugal <150 tons
0.7034 FL, 0.6699
IPLV.IP
Liquid-cooled
centrifugal ≥150 and
<300 tons 0.6337 FL,
0.5961_IPLV_.IP
EIR-f-PLR0.3394940.0490900.611582
ABLiquid-cooled
centrifugal ≥300 tons
0.5766 FL, 0.5495
IPLV.IP
EIR-f-T0.563967–0.0343310.0010150.033941–0.000432–0.000025
ABLiquid-cooled
centrifugal ≥300 tons
0.5766 FL, 0.5495
IPLV.IP
CAP-f-T0.9882890.031128–0.001550–0.003349–0.0001470.000503
ABLiquid-cooled
centrifugal ≥300 tons
0.5766 FL, 0.5495
IPLV.IP
EIR-f-PLR0.3097520.1536490.536462

366 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 369

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI require- ments for a standard and may contain material that has not been subject to public review or a consen- sus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX K INFORMATIVE FIGURES—THERMAL BRIDGES

This appendix contains informative reference figures for Sections 5.5.5.1 through 5.5.5.4 for the convenience of users of Standard 90.1 and not for use as specific details required for compliance. These figures are not intended to include all detailed variations that may meet the requirements. It is not intended that the figures represent all possible compliant configurations. The figures do not show roof membrane or wall cladding.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 367

PDF Page 370

Open page note

SYMBOLS

(e)

(d)

Figure K-1

a. Wall with exterior continuous insulation (Section 5.5.5.1.1[a]) b. Wall with cavity insulation (Section 5.5.5.1.1[b]) c. Wall with interior or cavity insulation (Sections 5.5.5.1.1[b] and [c]) d. Mass wall with interior insulation (Section 5.5.5.1.1[c][1]) e. Mass wall with interior insulation (Section 5.5.5.1.1[c][2])

368 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 371

Open page note

(d)

(c)

Figure K-2

a. Wall with exterior continuous insulation (Section 5.5.5.1.2[a]) b. Wall with cavity insulation (Section 5.5.5.1.2[b][1]) c. Mass wall with interior insulation (Section 5.5.5.1.2[c][1]) d. Mass wall with interior insulation (Section 5.5.5.1.2[c][2])

Figure K-3 Parapet within field of roof (Section 5.5.5.1.3).

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 369

PDF Page 372

Open page note

(d) (e) (f)

(g)

Figure K-4

a. Wall with cavity insulation (Section 5.5.5.2.1[b]) b. Wall with cavity insulation (Section 5.5.5.2.1[b]) c. Wall with integral insulation (Section 5.5.5.2.1[c]) d. Mass wall with integral insulation (Section 5.5.5.2.1[c]) e. Mass wall with interior insulation (Section 5.5.5.2.1[d][1]) f. Mass wall with interior insulation (Section 5.5.5.2.1[d][2]) g. Mass wall with exterior continuous insulation plus interior insulation (Section 5.5.5.2.1[e])

370 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 373

Open page note

Figure K-5 Shelf angles supporting exterior cladding (Section 5.5.5.3).

(a) (b) (c)

(d)

(e)

Figure K-6

a. Fenestration and continuous insulation (Section 5.5.5.4[a]) b. Fenestration and continuous insulation (Section 5.5.5.4[a]) c. Fenestration and no continuous insulation (Section 5.5.5.4[b]) d. Insulation between fenestration and wall (Section 5.5.5.4[c], Items [1], [2], or [3]) e. Insulation between fenestration and wall (Section 5.5.5.4[c], Items [1], [2], or [3])

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 371

PDF Page 374

Open page note

(This is a normative appendix and is part of this standard.)

NORMATIVE APPENDIX L MECHANICAL SYSTEM PERFORMANCE RATING METHOD

L1. GENERAL

L1.1 Scope. This appendix offers an alternative path of compliance for HVAC systems in accordance with Section 6.6.2. This appendix establishes the requirements for HVAC systems that use the Mechanical System Performance Rating Method and requirements for calculating TSPRp and TSPRr to demonstrate compliance in accordance with Section 6.6.2.2. Not all HVAC systems are allowed to use the Mechanical System Performance Rating Method as described in Section L1.1.1.

L1.1.1 Allowable HVAC Systems. HVAC systems are allowed to use the Mechanical System Performance Rating Method if they comply with all the following criteria:

a. The HVAC system type is included in Table L.1.1.1. b. The HVAC system serves a building use type included in Section L1.1.1.1. c. The HVAC system is not excluded by Section L1.1.1.2. d. The HVAC system is powered by grid-delivered electricity, renewable electricity, natural gas, propane,

renewable thermal energy, or distillate fuel oil.

Informative Notes:

  1. The intention of the scope is to allow most of the building to use the TSPR path and have portions of the buildings that cannot use the TSPR path use either the prescriptive path or the Computer Room System Path.
  2. The allowed system types may not be supported by all simulation program versions. The simula- tion program is required to support the reference systems for the building types modeled, and the proposed system type(s) must be supported by the simulation program .

L1.1.1.1 Allowable Building Use Types. HVAC systems that serve the following building use types are allowed to use the Mechanical System Performance Rating Method:

a. Large office ( gross conditioned floor area >150,000 ft [2] or >5 stories ) b. Medium office ( gross conditioned floor area 5000 to 150,000 ft [2] and ≤5 stories ) c. Small office ( gross conditioned floor area ≤5000 ft [2] and ≤5 stories ) d. Retail e. Multifamily (including dormitory) f. Hotel (including motel) g. School (including education and university) h. Other building use types that are <1000 ft [2] and <10% of the building conditioned floor area unless spe cifically excluded by Section L1.1.1.2(a)

Informative Note: Item (h) allows for a small sandwich or coffee counter service area but not a restaurant in an office building lobby or bookstore, for example.

L1.1.1.2 Excluded HVAC Systems. The following HVAC systems are excluded from using the Mechanical System Performance Rating Method:

a. HVAC systems serving one of the following excluded building areas:

  1. Data centers and computer rooms with equipment power density exceeding 20 W/ft [2] of conditioned floor area and exceeding 10 kW of equipment load
  2. Laboratories with fume hoods
  3. Locker rooms with more than four showers
  4. Cafeterias and dining rooms
  5. Restaurants and commercial kitchens with total cooking capacity greater than 100,000 Btu/h (does not include break rooms)
  6. Natatoriums or rooms with saunas
  7. Areas of buildings with commercial refrigeration equipment exceeding 100 kW of power input b. HVAC systems that are not replaced in their entirety as part of an alteration and are not serving initial

build-out construction

372 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 375

Open page note

Table L.1.1.1 MethodProposed Building HVAC Systems Allowed to Use the Mechanical System Performance Rating
System No.System Name
1Packaged terminal air conditioner(with electric or hydronic heat)
2Packaged terminal heat pump
3Packaged single-zone furnacea and/or air-cooled air conditioner (includes split systems b)
4Packaged single-zone heat pump (air-to-air only) (includes split systems b and electric or gas
supplemental heat)
5VRF system (air source)
6Four-pipe fan coil
7Water-source heat pump (water loop), water-source_VRF system_, or water-source air conditioner
8Ground-source heat pump
9Packaged_VAV system_ (DX cooling) a
10VAV system (hydronic cooling) a
11VAV system with fan-powered_terminal_ units
12DOAS (in conjunction with_systems_ 1 through 8)

a. Reheat or primary heat may be electric, hydronic, or gas furnace. b. Condensing units with DX air handlers are modeled as package furnace with air conditioners or heat pumps. Informative Note: See Section 3.3 for a full list of terms used in this table.

c. HVAC systems serving portions of the building that are also served in parallel by other HVAC systems not

allowed to use the Mechanical System Performance Rating Method d. HVAC systems using any of the following:

  1. District heating or cooling
  2. Small-duct high-velocity air-cooled, space -constrained air-cooled, single-package vertical air condi- tioner, single-package vertical heat pump
  3. Double-duct air conditioner or double-duct heat pump as defined in 10CFR part 431, Subpart F
  4. Packaged terminal air conditioners and packaged terminal heat pumps that have cooling capacity greater than 12,000 Btu/h
  5. Systems with a common heating source serving both HVAC and service water heating equipment
  6. HVAC systems that provide recovered heat for service water heating

Exceptions to L1.1.1.2(a) and (c):

  1. Multiple-zone HVAC systems in Table L.1.1.1, including dedicated outdoor air systems (DOAS), where 80% or more of system supply air serves allowed building use types in accordance with Section L1.1.1.1 and 20% or less of system supply air serves excluded areas in Items (a) or (c).
  2. Central chiller or boiler plants where 80% or more of capacity serves allowed building use types in accordance with Section L1.1.1.1 and 20% or less of capacity serves excluded areas in items (a) or (c).

L2. MECHANICAL SYSTEM PERFORMANCE RATING METHOD

L2.1 Compliance

L2.1.1 Mandatory Requirements. All HVAC systems in the proposed building design shall comply with the requirements in Section 6.2.1.

Informative Note: Buildings using the Mechanical System Performance Rating Method are required to meet all mandatory provisions in Section 6.4 in accordance with Section 6.2.1. For example, while demand control ventilation ( DCV ) controlled area in the proposed building is one of the user entries in the simulation program, the minimum entry needs to meet the floor area where DCV is required in accordance with Section 6.4.3.8. The intent of this entry is to give credit for DCV control in more area than required, but not to allow DCV that is a mandatory requirement to be traded off with other efficiency improvements.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 373

PDF Page 376

Open page note

L2.1.2 Mechanical System Performance Rating Method Requirements. All HVAC systems using the Mechanical System Performance Rating Method shall demonstrate compliance using TSPRp and TSPRr in accordance with Section 6.6.2 and the following requirements:

a. TSPRp and TSPRr shall be calculated in accordance with Section L2.1.5, “Calculating TSPR, ” and the

requirements of Sections L1, L3, L4, and L5. b. Alterations that include replacement of the entire HVAC system shall be modeled as a new building . c. HVAC systems shall comply with Section L2.1.4 “Partial Prescriptive Requirements.” d. Initial build-out construction shall be modeled in accordance with Section L2.1.3, “Core and Shell/Initial

Build-Out Construction Analysis.” e. Compliance documentation and supplemental information shall be submitted in accordance with Sec tions 4.2.2 and L2.1.6 “ TSPR Submittals.”

L2.1.3 Core and Shell/Initial Build-Out Construction Analysis. Where the building permit applies to only a portion of the HVAC system in a building, and the remaining components will be designed under a future building permit or were previously installed, the future or previously installed components shall be modeled as follows:

a. Where the HVAC zones that do not include HVAC systems in the current permit will be or are served by

independent systems, the block (see Section L2.2.1) including those zones shall not be included in the model. b. Where the HVAC zones that do not include complete HVAC systems in the permit are intended to receive

HVAC services from systems in the permit, their proposed zonal systems shall be modeled with equip- ment that meets but does not exceed the requirements of Sections 6.4 and 6.5. c. Where the zone equipment in the permit receives HVAC services from previously installed systems that

are not in the permit, the previously installed systems shall be modeled with equipment matching the certified value of what is installed or equipment that meets the requirements of Sections 6.4 and 6.5, whichever has the more efficient energy use. d. Where the central plant heating and cooling equipment is completely replaced and HVAC zones with

existing systems receive HVAC services from systems in the permit, their proposed zonal systems shall be modeled with equipment that meets but does not exceed the requirements of Sections 6.4 and 6.5. Informative Notes:

  1. Examples of HVAC systems that are intended to receive HVAC services from systems in the permit include future zonal water source heat pumps that will receive loop water that is heated by a boiler or is cooled by a cooling tower included in the permit, any system that will receive outdoor ventilation air from a DOAS included in the permit, and future zone terminal units that will be connected to a central VAV system included in the permit.
  2. An initial build-out with heating coils served from a previously installed system with a high_efficiency_ condensing boiler would use the installed efficiency if it exceeded the current requirements. If the installed boiler had a lower efficiency than the current requirements, the current requirement would be used.
  3. A partial central plant upgrade (e.g., chiller but not boiler replacement) cannot use this method.

L2.1.4 Partial Prescriptive Requirements. HVAC systems using the HVAC Performance Rating Method shall meet relevant prescriptive requirements in Section 6.5 as follows:

a. Air economizers shall meet the requirements of Sections 6.5.1.1.5 and 6.5.1.1.6. b. Steam humidifiers shall meet requirements of Section 6.5.2.4. c. Variable-air-volume systems shall meet requirements of Sections 6.5.3.2.2, 6.5.3.2.3, and 6.5.3.3. d. Hydronic systems shall meet the requirements of Section 6.5.4.2. e. Plants with multiple chillers or boiler s shall meet the requirements of Section 6.5.4.3. f. Chilled-water and heating-water supply temperature reset shall meet the requirements of Section 6.5.4.4 without exception. g. Hydronic (water loop) heat pumps and water-cooled unitary air conditioners shall meet the requirements

of Section 6.5.4.5. h. Cooling-tower turndown shall meet the requirements of Section 6.5.5.4. i. Heating of unenclosed spaces shall meet the requirements of Section 6.5.8.1. j. Hot-gas bypass shall meet the requirements of Section 6.5.9. k. Systems shall meet the door switch control requirements of Section 6.5.10. l. Refrigeration systems shall meet the requirements of Section 6.5.11.

374 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 377

Open page note

L2.1.5 Calculating TSPR. TSPRp shall be calculated according to Equation L-1:

TSPRr

= -------------------------------Loads r HVACinput p

(L-1)

where

Loads r = sum of the annual heating and cooling loads for the TSPR reference building design met by the building HVAC system, thousand Btu.

HVACinput p = sum of the annual HVAC energy input for heating, cooling, fans, energy recovery, pumps, and heat rejection for the proposed design . The HVAC energy input units shall be in accordance with Section L5.

TSPRr shall be calculated according to Equation L-2:

TSPRr

= -----------------------------Loads r - HVACinput r

(L-2)

where

Loads r = sum of the annual heating and cooling loads for the TSPR reference building design met by the building HVAC system, thousand Btu.

HVACinput r = sum of the annual HVAC energy input for heating, cooling, fans, energy recovery, pumps, and heat rejection for the TSPR reference building design. The HVAC energy input units shall be in accordance with Section L5.

Informative Note: The annual HVAC energy uses calculated using the Mechanical System Performance Rating Method are not predictions of whole- building energy consumption for an actual proposed building after construction . Actual experience will differ from these calculations due to variations such as occupancy, building operation and maintenance, weather, energy use of systems and building areas not covered by this procedure, changes in energy prices between design of the building and occupancy, and the precision of the calculation tool.

L2.1.6 TSPR Submittals. Where TSPRp and TSPRr are used to demonstrate compliance in accordance with Section 6.6.2, documentation shall be provided to the building official including the following:

a. A compliance report, as outlined in Section L3.4, generated by the simulation program. b. A mapping of the actual building HVAC component characteristics and those simulated in the proposed

design showing how individual pieces of HVAC equipment identified above have been combined into average inputs as required by the simulation program, including (but not limited to) the following:

  1. Fans
  2. Hydronic pumps
  3. Air handlers
  4. Packaged cooling equipment
  5. Furnaces
  6. Heat pumps
  7. Boiler s
  8. Chillers
  9. Heat-rejection equipment (open- and closed-circuit cooling towers; dry coolers)
  10. Electric resistance coils
  11. Condensing units
  12. Motors for fans and pumps
  13. Energy recovery devices c. For each piece of equipment identified in item (b), include the following along with the units specified in

Table L2.2.3 as applicable:

  1. Equipment name or tag consistent with that found on the design documents
  2. Rated Efficiency level, full-load efficiency as rated in Section 6.8
  3. Rated capacity
  4. Where not provided by the simulation program report in item (a), documentation of the calculation of any weighted equipment efficiencies input into the program.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 375

PDF Page 378

Open page note

  1. Electrical input power for fans and pumps (before any speed or frequency control device ) at design condition and calculation of input value (W/cfm or W/gpm) d. A floor plan of the building identifying how portions of the building are assigned to the simulated blocks

(See Section L2.2.1) and which areas of the building are served by HVAC systems required to meet the requirements of Section 6.5 or Section 6.6.1.

Informative Note: The items listed under items (b) and (c) may either be included in the report generated by the simulation program or submitted separately. The compliance report required by Section L3.4 includes the composite systems entered into the program for the blocks. These may differ from actual sys- tems and may be based on capacity efficiency weighting per Section L2.2.3.1. The simulation program may allow input of individual actual systems and perform the weighting, or it may require the user to perform that weighting separately and input the weighted efficiencies . In the second case, the weighted efficiency calculation would be included under item (c) here.

L2.2 Proposed Building Information Required. The simulation of HVAC systems and the HVAC zones they serve shall be modeled based on building information required by this section.

L2.2.1 Simplified Block Approach. The geometry of buildings shall be configured using one or more simplified geometric simulation building blocks, referred to as “blocks” in this appendix. Each block contains one or multiple thermal blocks . A more complex zoning of the building shall be allowed where all thermal zones in the reference and proposed model are the same and rules related to block geometry and HVAC system assignment to blocks are met with appropriate assignment to thermal zones .

L2.2.1.1 Block Geometry. Each block shall define attributes including block dimensions, number of stories, floor-to-floor height, and floor-to-ceiling height. The simulation program is permitted to allow the use of simplified shapes (such as rectangle, L-shape, H-shape, U-shape, or T-shape) to represent blocks. Where actual building shape does not match these predefined shapes, simplifications are permitted providing the following requirements are met:

a. The gross conditioned floor area and volume of each block shall match the actual proposed design within

10%. b. The area of each exterior building envelope component from Tables 5.5-0 through 5.5-8 is accounted for

within 10% of the actual proposed design . c. The area of vertical fenestration and skylights is accounted for within 10% of the actual proposed design . d. The orientation of each component in items (b) and (c) is accounted for within 45 degrees of the actual

proposed design .

The user shall create multiple blocks , if necessary, to meet these requirements.

L2.2.1.2 Number of Blocks. One or more blocks shall be created per building based on the following restrictions:

a. Each block shall have only one building use type. At least one single block shall be created for each

unique use type, including where one HVAC system serves two different use types. b. Each block shall be served by only one type of primary or zonal HVAC system . A DOAS system shall be

permitted to serve blocks served by other systems . A single block shall be created for each unique primary or zonal HVAC system type and building use type combination. Multiple HVAC units of the same type are permitted to be represented in one block in accordance with Section L2.2.3.1. c. Each block shall have a single definition of floor-to-floor or floor-to-ceiling heights. Where story heights

differ by more than 2 ft, unique blocks shall be created for the stories with varying heights. d. Each block can include either above- grade or below- grade exterior stories . For buildings with both

above- grade and below- grade stories, separate blocks shall be created for each. For buildings with sto- ries partially above grade and partially below grade, if the total wall area of the story in consideration is greater than or equal to 50% above grade, it shall be simulated as a completely above- grade block; otherwise, it shall be simulated as a below- grade block. e. In order to combine multiple stories into a single block, each wall on a facade of a block shall have sim ilar vertical fenestration area . The product of the proposed design U-factor times the area of vertical fen- estration (UA VerFen ) on each facade of a given story cannot differ by more than 15% of the average UA VerFen for that facade in each block. The product of the proposed design solar heat gain coefficient ( SHGC ) times the area of vertical fenestration ( SHGCAVerFen ) on each facade of a given story cannot differ by more than 15% of the average SHGCAVerFen for that facade in each block. If these conditions are not met, additional blocks shall be created consisting of stories with similar fenestration .

376 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 379

Open page note

f. For a building model with multiple blocks, each block facade input shall provide adequate information to identify the outside boundary condition (outside, inside to adjacent block, ground contact, or adiabatic) of each facade or portion of each facade that match the actual proposed design .

Informative Note: The simulation program may automatically identify the adjacent block facade outside boundary conditions through a graphic input process.

L2.2.2 Building Envelope Components. Building envelope thermal properties used in the proposed design shall be based on the actual proposed design using documented user-defined values and shall comply with all of the following:

a. Where different roof thermal properties are present in a single block, an area-weighted U-factor shall be

used. b. Where different wall constructions exist on the facade of a block, an area-weighted U-factor shall be used. c. Where different below-grade wall constructions exist in a block, an area-weighted C- factor shall be used. d. Where different floor constructions exist in the block , an area-weighted U-factor shall be used. e. Where different slab-on-grade floor constructions exist in a block, an area-weighted F-factor shall be used. f. Where different vertical fenestration types or sill heights exist, area-weighted sill heights, U-factor, and SHGC values shall be used. g. Where different skylight types exist, area-weighted U-factor and SHGC values shall be used. h. Permanent shading devices such as overhangs shall be modeled only if >50% of the area of vertical fen-

estration on a facade is shaded by the same.

L2.2.3 HVAC System Components. The HVAC system parameters shall be provided for the proposed design at design conditions unless otherwise stated with clarifications and simplifications as described in Table L2.2.3 and as follows:

a. All HVAC zones within a block shall be served by the same HVAC system type as listed in Table L.1.1.1. b. Where multiple system components serve a block, average values weighted by the appropriate metric as

described in Section L2.2.3.1 shall be used. c. The Table L2.2.3 parameter requirements are based on input of full-load. equipment efficiencies with

adjustment using part-load curves integrated in the simulation program . Where other approaches to partload adjustment are used, it is permitted for specific input parameters to vary.

Informative Note: Table L2.2.3 includes both user-defined parameters and parameters that are fixed in the simulation program and may not be changed by the user. They are maintained in one table here so related items can be viewed together in context.

L2.2.3.1 Proposed Building HVAC System Aggregation. Projects using the Mechanical System Performance Rating Method shall comply with all the following requirements.

a. Where multiple fan systems serve a single block, fan power shall be based on weighted average using the

design supply air (cfm). b. Where multiple cooling systems serve a single block, COP shall be based on a weighted average using

cooling capacity. DX coils shall be entered as multistage if more than 50% of coil capacity serving the block is multistage with staged controls. c. Where multiple heating systems serve a single block, thermal efficiency or heating COP shall be based

on a weighted average using heating capacity. d. Where multiple boiler s or chillers serve a heating-water or chilled-water loop, efficiency shall be based

on a weighted average for using heating or cooling capacity. e. When multiple cooling towers serving a condenser water loop are combined, the cooling tower effi-

ciency, cooling tower design approach, and design range are based on a weighted average of the design water flow rate through each cooling tower. f. Where multiple pumps serve a heating-water, chilled-water, or condenser water loop, pump power shall be based on a weighted average for using design water flow rate. g. When multiple system types with and without economizers are combined, the economizer maximum out-

door air fraction of the combined system shall be based on weighted average of 100% supply air for sys- tems with economizers and design outdoor air for systems without economizers. h. Multiple systems with and without ERVs cannot be combined. i. Systems with and without supply air temperature reset cannot be combined. j. Systems with different fan control (constant volume, multispeed, or VAV ) for supply fans cannot be combined.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 377

PDF Page 380

Open page note

L3. SIMULATION PROGRAM

The simulation program shall have the following capabilities:

Table L2.2.3 Proposed Building HVAC System Parameters

CategoryParameterFixed or User
Defined
RequiredApplicable
Systems a
HVAC System
Type
System typeUser definedSelected from Table L.1.1.1All
System SizingDesign-day informationFixed99.6% heating design and 1% dry-bulb and 1% wet-bulb cooling designAll
System SizingZone coil capacityFixedSizing factors used are 1.25 for heating_equipment_ and 1.15 for cooling_equipment._All
System SizingSupply airflowFixedBased on the greater of a supply-air-to-room-air temperature_set point_difference of
20°F or required_OA_ ventilation
Outdoor
Ventilation Air
and Filtration
Portion of supply air with proposed filter ≥MERV 13User definedPercentage of supply airflow subject to higher filtration (adjusts reference fan power
higher; prorated)
All
Outdoor
Ventilation Air
and Filtration
Outdoor_ventilation_ supply airflow rate adjustmentsFixedBasis is 1.0 zone air distribution effectivenessAll
Outdoor
Ventilation Air
and Filtration
Outdoor_ventilation_ supply airflow rateFixedAs specified in ASHRAE/IES Standard 90.1 Normative Appendix C, adjusted for
proposed_DCV_ control (See “Demand Control Ventilation” category below.)
All
System
Operation
Space temperature_set points_FixedAs specified in ASHRAE/IES Standard 90.1 Normative Appendix C, except for
hotel/motel, which shall be 70°F heating 72°F cooling
All
System
Operation
Fan operation—occupied (where DOAS meets
ventilation requirements)
User definedFan either runs continuously during occupied hours or is cycled to meet thermal
load.
All (continuous)
1–11 (cycles)
System
Operation
Fan operation—occupied (where heating and cooling
units provide_ventilation_—no DOAS)
FixedFan runs continuously during occupied hours;VAV or multispeed fans reduce airflow
related to thermal load.
1–11
System
Operation
Fan operation—night cycleFixedFan cyclesON to meet_setback_ temperatures.1–11
Packaged
Equipment
Efficiency
DX cooling_efficiency_User definedCooling_COP_ without fan_energy_ calculated in accordance with Section L4.2.3(d)1, 2, 3, 4, 5, 7, 8,
9, 11, 12
Packaged
Equipment
Efficiency
DX coil number of stagesUser definedSingle stage or multistage3, 4, 9, 10, 11, 12
Packaged
Equipment
Efficiency
Heat-pump_efficiency_User definedHeating_COP_ without fan_energy_ calculated in accordance with Section L4.2.3(d)2, 4, 5, 7, 8, 12
Packaged
Equipment
Efficiency
Furnace_efficiency_User definedFurnace thermal_efficiency_1, 3, 9, 12
Heat-Pump
Supplemental
Heat
Heat sourceUser definedElectric resistance or gas furnace2, 4, 7, 8, 12
Heat-Pump
Supplemental
Heat
ControlFixedElectric heat locked out above 40°F OAT. Runs as needed in conjunction with
compressor between 40°F and 0°F. Gas heat operates in place of the heat pump when
the heat pump cannot meet load.
2, 4, 7, 8, 12

a. Applicable systems from Table L.1.1.1 Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 381

Open page note

Table L2.2.3 Proposed Building HVAC System Parameters (Continued)

CategoryParameterFixed or User
Defined
RequiredApplicable
Systems a
System Fan
Power
and Controls
Design fan power, W/cfmUser definedInput electric power for all fans required to operate at_fan system design conditions_
divided by the supply airflow rate. Include any VSD losses at design condition. This
is a wire-to-air value, including all drive, motor_efficiency_, and other losses.
All
System Fan
Power
and Controls
Part-load fan controls:
• Constant volume
• Two-speed or three-speed, then input:
• W/cfm at each speed
• % cfm at leach speed
• VAV
User definedStatic pressure_reset_ included for_VAV_All (constant
volume, two speed)
9, 10, 11 (VAV)
Variable-Air-
Volume Systems
SAT controls (select):
• None
• OAT SAT_reset_
• Warmest zone SAT_reset_
User definedIf not SAT_reset_, then constant at 55°F. Options for_reset_ based on OAT or warmest
zone. If OAT_reset_, SAT is_reset_ higher to 60°F at outdoor low of 50°F. SAT is 55°F
at outdoor high of 70°F. If warmest zone, then the user can specify the minimum and
maximum temperatures.
9, 10, 11
Variable-Air-
Volume Systems
• Zone minimum damper and_Evs_
• Standard 62.1 simple method except for schools
Fixed• Schools: 1.2 ×Voz zone minimum design_ventilation_ rate, cfm;Evs = 0.65
• Other_buildings_: Simple Standard 62.1 method is 1.5 ×Voz zone minimum design
ventilation rate, cfm;Evs = 0.75.
9, 10, 11
Variable-Air-
Volume Systems
Dual_set point_ minimum_VAV_ damper positionUser definedHeating minimum and maximum airflow fraction9, 10, 11
Variable-Air-
Volume Systems
Terminal-unit heating sourceUser definedElectric or hydronic
Variable-Air-
Volume Systems
FPTU typeUser definedSeries or parallel FPTU11
Variable-Air-
Volume Systems
Parallel FPTU fanSized for 50% peak primary air at 0.35 W/cfm11
Variable-Air-
Volume Systems
Series FPTU fanFixedSized for 50% peak primary air at 0.35 W/cfm11
EconomizerOSA economizer presenceUser definedYes or no3, 4, 5, 6, 9, 10, 11
EconomizerEconomizer high limitFixed• Lockout on differential dry-bulb temperature (OAT > RAT) in Climate Zones 6A,
5A, All B, and C
• Fixed enthalpy > 28 Btu/lb or fixed dry-bulb OAT > 75°F in Climate Zones 0A to
4A
Energy
Recovery
Sensible effectivenessUser definedHeat exchanger sensible effectiveness at design heating and cooling conditions3, 4, 9, 10, 11, 12
Energy
Recovery
Latent effectivenessUser definedHeat exchanger latent effectiveness at design heating and cooling conditions3, 4, 9, 10, 11, 12
Energy
Recovery
Bypass SAT_set point_User definedIf bypass, target supply air temperature3, 4, 9, 10, 11, 12
Energy
Recovery
Fan power reduction when in bypassUser definedIf bypass, specify fan power reduction, W/cfm.3, 4, 9, 10, 11, 12

a. Applicable systems from Table L.1.1.1 Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 382

Open page note

Table L2.2.3 Proposed Building HVAC System Parameters (Continued)

CategoryParameterFixed or User
Defined
RequiredApplicable
Systems a
Demand
Control
Ventilation
DCV applicationON/OFFUser definedPercentage of block floor area under occupied standby controls,ON/OFF only (see
Section 6.5.3.8) with no variable control
3, 4, 9, 10, 11, 12
Demand
Control
Ventilation
DCV application CO2User definedPercentage of block_floor_ area under variable_DCV_ control (CO2); may include both
variable andON/OFF control
3, 4, 9, 10, 11, 12
Dedicated
Outdoor Air
System
DOAS fan power, W/cfmUser definedFan electrical input power in W/cfm of supply airflow12
Dedicated
Outdoor Air
System
DOAS supplemental heating and coolingUser definedHeating source, cooling source,energy recovery, and respective_efficiencies_12
Dedicated
Outdoor Air
System
Maximum SAT_set point_ (cooling)User definedSAT_set point_ if DOAS includes supplemental cooling12
Dedicated
Outdoor Air
System
Minimum SAT_set point_ (heating)User definedSAT_set point_ if DOAS includes supplemental heating12
Heating PlantBoiler efficiencyUser definedBoiler thermal_efficiency_1, 6, 7, 9, 10, 11, 12
Heating PlantHW loop configurationUser definedVariable-flow primary only; variable-flow primary and secondary; constant-flow
primary and variable-flow secondary
1, 6, 7, 9, 10, 11, 12
Heating PlantHW primary_pump_ power, W/gpmUser definedHW constant primary_pump_ input W/gpm HW flow1, 6, 7, 9, 10, 11, 12
Heating PlantHW secondary_pump_ power, W/gpmUser definedHW variable secondary_pump_ input W/gpm HW flow (if primary/secondary)1, 6, 7, 9, 10, 11, 12
Heating PlantHW loop temperatureUser definedHW supply and return temperatures, °F1, 6, 7, 9, 10, 11, 12
Heating PlantHW temperature_reset_ includedUser definedYes/no1, 6, 7, 9, 10, 11, 12
Heating PlantHWST_reset_FixedReset HWST by 27.3% of design temperature difference (HWST – 70°F_space_
heating temperature_set point_) between 20°F and 50°F OAT
1, 6, 7, 9, 10, 11, 12
Heating PlantBoiler typeFixedRegular where input thermal_efficiency_ is less than 86%; condensing_boiler_
otherwise
1, 6, 7, 9, 10, 11, 12
Chilled-Water
Plant
Chiller condenser typeUser definedAir-cooled or water-cooled; for water-cooled, positive displacement or centrifugal6, 10, 11, 12
Chilled-Water
Plant
Chiller full-load_efficiency_User definedChiller_COP_6, 10, 11, 12
Chilled-Water
Plant
Number of chillersUser definedIn simulation, chillers will be sized equally with 1–3 chillers.6, 10, 11, 12
Chilled-Water
Plant
CHW coil design temperature difference, °FUser definedCHWST and CHW return temperature at_design conditions_6, 10, 11, 12
Chilled-Water
Plant
CHW loop configurationUser definedVariable-flow primary only; variable-flow primary and secondary; constant-flow
primary and variable-flow secondary
6, 10, 11, 12
Chilled-Water
Plant
CHW primary_pump_ power, W/gpmUser definedPrimary_pump_ input, W/gpm; CHW flow6, 10, 11, 12
Chilled-Water
Plant
CHW secondary_pump_ power, W/gpmUser definedSecondary_pump_ input, W/gpm; CHW flow (if primary/secondary)6, 10, 11, 12
Chilled-Water
Plant
CHW temperature_reset_ includedUser definedYes/no6, 10, 11, 12
Chilled-Water
Plant
CHW temperature_reset_ scheduleFixedOA reset: Use input CHWST at 80°F_outdoor air_ dry-bulb and above and CHWST
10°F at 60°F_OA_ dry-bulb and below, ramped linearly between
6, 10, 11, 12

a. Applicable systems from Table L.1.1.1 Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 383

Open page note

Table L2.2.3 Proposed Building HVAC System Parameters (Continued)

CategoryParameterFixed or User
Defined
RequiredApplicable
Systems a
Condenser
Loop
Condenser water-pump power, W/gpmUser definedPump input, W/gpm; condenser water flow6, 7, 8, 10, 11, 12
Condenser
Loop
Condenser water-pump controlFixedConstant-speed, one_pump_ per chiller6, 7, 8, 10, 11, 12
Heat RejectionHeat-rejection_equipment efficiency_User definedgpm/hp at_design conditions_, where hp is the sum of nameplate fan and integral
spray_pump_ motor hp, if applicable
6, 7, 8, 10, 11, 12
Heat RejectionOpen-circuit cooling tower flow turndownFixedFlow turndown per Section 6.5.5.46, 7, 8, 10, 11, 12
Heat RejectionHeat-rejection fan controlUser definedConstant or variable speed6, 7, 8, 10, 11, 12
Heat RejectionHeat-rejection approach and rangeUser definedDesign heat-rejection approach and range temperature6, 7, 8, 10, 11, 12
Heat-Pump
Loop
Loop flow and heat-pump control valveFixedTwo-position valve with VSD on_pump_7, 8
Heat-Pump
Loop
Heat-pump loop flow controlFixedLoop flow at 3 gpm/ton7, 8
Heat-Pump
Loop
Heat-pump loop minimum and maximum
temperature control
User definedUser input; restrict to minimum 20°F and maximum 40°F temperature difference.7, 8
Ground-Loop
Heat-Pump
Bore Field
FixedBore depth = 250 ft; bore length 200 ft/ton for greater of cooling or heating load8
Ground-Loop
Heat-Pump
Bore Field
FixedBore spacing = 15 ftBore spacing = 15 ft
Ground-Loop
Heat-Pump
Bore Field
FixedBore diameter = 5 in. with 3/4 in. nominal diameter polyethylene pipeBore diameter = 5 in. with 3/4 in. nominal diameter polyethylene pipe
Ground-Loop
Heat-Pump
Bore Field
FixedGround and grout conductivity = 4.8 Btu·in./h·ft2·°FGround and grout conductivity = 4.8 Btu·in./h·ft2·°F

a. Applicable systems from Table L.1.1.1 Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 384

Open page note

L3.1 Calculation of the TSPR. The simulation program shall calculate both the TSPRp and TSPRr based only on the input for the proposed design and the requirements of this appendix. The calculation procedure shall not allow the user to directly modify either the building component characteristics of the TSPR refer- ence building design or the HVAC parameters identified as fixed input in Table L2.2.3.

L3.2 TSPR Simulation Program. All components of the proposed design for blocks served by HVAC sys- tems using this method shall be explicitly modeled by the simulation program . The code official shall be permitted to approve a simulation program for a specified application or limited scope.

L3.2.1 Minimum Capability. The simulation program shall be approved by the code official and shall, at a minimum, have the ability to explicitly model all of the following:

a. 8760 hours per year b. Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat set points,

and HVAC system operation, defined separately for each day of the week and holidays c. Thermal mass effects d. Ten or more thermal blocks e. Part-load performance curves or other part-load adjustment methods for mechanical equipment f. Capacity and efficiency correction curves or other part-load adjustment methods for mechanical heating and mechanical cooling equipment g. Air economizers with integrated controls h. The energy use of all HVAC system types included in the analysis and energy impact from all related

fixed and user inputs in Table L2.2.3 i. Ability to automatically generate the TSPR reference building design as specified in Section L4.3

Informative Note: The simulation program shall include clear prompts or accessible help-topic references defining specific parameters and units for all required building and system characteristic inputs.

L3.2.2 TSPR Determination. The simulation program shall have the ability to either directly determine the TSPRp and TSPRr or produce hourly and annual reports of energy use by each energy source suitable for determining the TSPRp and TSPRr using a separate calculation.

L3.2.3 Load Calculations. The simulation program shall be capable of performing design load calculations to determine required HVAC equipment capacities and air and water flow rates in accordance with Section 6.4.2.1 for both the proposed design and TSPR reference building design .

L3.2.4 Testing

L3.2.4.1 The simulation program shall be tested according to ASHRAE Standard 140, except for Sections 7 and 8 of Standard 140. The required tests shall include building thermal envelope and fabric load tests (Sections 5.2.1, 5.2.2, and 5.2.3), ground coupled slab-on- grade analytical verification tests (Section 5.2.4), space -cooling equipment performance tests (Section 5.3), space -heating equipment performance tests (Section 5.4), and air-side HVAC equipment analytical verification tests (Section 5.5) along with the associated reporting (Section 6).

L3.2.4.2 The test results and modeler reports shall be posted on a publicly available website and shall include the test results of the simulation program and input files used for generating the results along with the results of the other simulation programs included in ASHRAE Standard 140, Annexes B8 and B16. The modeler report in Standard 140, Annex A2, Attachment A2.7 shall be completed for results exceeding the maximum or falling below the minimum of the reference values and for omitted results.

Informative Notes:

  1. There are no pass/fail criteria established by this testing requirement.
  2. Based on the Section 3.2 definition, simulation program includes the simulation engine and the corresponding user interface. The testing of a simulation program only meets the requirements of Section L1 for that simulation program and cannot be used as proxy for documenting compliance of another simulation program that uses the same simulation engine.

L3.3 Climatic Data. Climatic data shall meet the requirements of Section G2.3.

L3.4 Compliance Report. The simulation program shall generate a report that includes the following:

a. Address of the building b. Name of individual completing the compliance report c. Name and version of the compliance simulation program, the edition of Standard 90.1 the simulation

program method complies with, and the link to the website that contains the ASHRAE Standard 140 testing results for the version used in accordance with Section L3.2.4 d. The dimensions, story heights, and number of stories for each block

382 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 385

Open page note

e. By block, the U-factor, C-factor, or F-factor for each simulated opaque building envelope component

and the U-factor and SHGC for each fenestration component f. By block or by surface for each block, the fenestration area and total area of each opaque building enve- lope component g. By block, a list of the HVAC equipment simulated in the proposed design, including the equipment type,

fuel type, rated equipment efficiencies, rated capacities, and system control parameters h. Annual site HVAC energy use by end use and energy type for the proposed design and TSPR reference

building design i. Annual sum of hourly heating and cooling loads for the TSPR reference building design j. The HVAC total system performance ratio for both the TSPR reference building design and the proposed design and compliance result in accordance with Section 6.6.2.2

Informative Note: The simulation program, at a minimum, will report compliance with the TSPR based on the compliance criteria in Section 6.6.2.2. Should a jurisdiction adopt other compliance criteria, then a separate calculation of TSPR using the reference building design and proposed design HVAC energy type input may be necessary.

L4. CALCULATION PROCEDURE

Except as specified by this appendix, the TSPR reference building design and proposed design shall be configured and analyzed using identical methods and techniques.

L4.1 Simulation of the Proposed Design (Non-HVAC). The proposed design non- HVAC systems shall be configured and analyzed as specified in this section. At a minimum, the simulation program shall support the building use types included in the analysis. The allowed building use types are listed in Section L1.1.1.1.

L4.1.1 Simplified Block Approach. The simulation program shall model the building using one or more simplified geometric simulation building blocks, described in Section L2.1. Each block contains one or multiple thermal blocks . The simulation program shall provide for simplified input described in Section L2.2 and allow for multiple block simulation.

L4.1.2 Thermal Zoning. Each story in a block shall be modeled as a single thermal block or as five ther- mal blocks consisting of four perimeter zones and a core zone. Below- grade stories shall always be modeled as a single block. If any facade in the block is less than 45 ft in length, there shall only be a single thermal block per story . Otherwise, each story shall be modeled with five thermal blocks . A perimeter zone shall be created extending from each facade to a default depth of 15 ft with a user input range of 8 to 20 ft. Where facades intersect, the zone boundary shall be formed by a 45 degree angle with the two facades. The remaining area or each story shall be modeled as a core zone with no exterior walls .

L4.1.3 Building Use Type. The building use type for each block shall be consistent with the proposed design and allowed building use types in Section L1.1.1.1. The occupant density, heat gain, and schedule shall be as specified by Normative Appendix C.

L4.1.4 Building Envelope Components. Building envelope thermal properties used in the proposed design shall be modeled based on the actual proposed design using inputs described in Section L2.2.2 and shall comply with all of the following:

a. Roofs shall be modeled with insulation above a steel roof deck. Roof solar absorptance shall be modeled

at 0.70 and thermal emittance at 0.90. b. Above-grade walls shall be modeled as steel-frame construction. c. Above- grade exterior floors shall be modeled as steel-frame construction. d. The area, U-factor, and SHGC of vertical fenestration shall be modeled for each facade based on the

actual proposed design . The simulation program shall model a combined single window centered on each facade based on the area and sill height input by the user. e. The skylight area shall be modeled for each roof based on the actual proposed design . Skylights shall be

combined into a single skylight centered on the roof of each zone based on the area input by the user.

L4.1.5 Lighting. For each block, the interior lighting power density shall be equal to the applicable allowance in Table 9.5.1 based on the assigned building use type. The lighting profile schedule shall be for the applicable building use type as specified by Normative Appendix C. The impact of lighting controls is assumed to be captured by the lighting schedule, and no explicit controls (including daylight responsive controls) shall be modeled. Exterior lighting shall not be modeled.

L4.1.6 Miscellaneous Equipment. The miscellaneous equipment schedule and power shall be based on the assigned building use type as specified by Normative Appendix C. The impact of miscellaneous equip- ment controls is assumed to be captured by the equipment schedule, and no explicit controls shall be modeled.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 383

PDF Page 386

Open page note

Table L4.2.3-1 Fan and Pump Power Curve Coefficients

Equation TermFan Power CoefficientsCol3Pump Power CoefficientsCol5
Equation TermVSD (no Static
Pressure Reset)
VSD + Static
Pressure Reset
Ride Pump CurveVSD + Differential
Pressure/Valve Reset
b0.00130.040800
x0.1470.0883.24850.0205
_x_20.9506–0.0729–4.74430.4101
_x_3–0.09980.94372.52950.5753

Figure L4.2.3-1 Fan and pump power performance as a function of design water flow or airflow.

L4.1.7 Elevators. Elevators shall not be modeled. L4.1.8 Service Water-Heating Equipment. Service water heating shall not be modeled. L4.1.9 On-site Renewable Energy Systems. On-site renewable energy systems shall not be modeled.

L4.2 Simulation of the Proposed Design (HVAC). The proposed design HVAC systems shall be configured and analyzed as specified in this section.

L4.2.1 HVAC Equipment. The simulation program shall analyze the control parameters that meet the mandatory requirements of Section 6.4 and the parameters provided by the user or specified as fixed in Section L2.2.3 as applicable for each HVAC system included in the proposed design .

L4.2.2 Supported HVAC Systems. The HVAC systems included in the proposed design and the TSPR reference building design shall be supported by the simulation program . HVAC systems permitted are limited to those shown in Table L.1.1.1. The simulation program shall support multiple blocks being served by one central system .

L4.2.3 Proposed Building HVAC System Simulation. The HVAC systems shall be modeled as in the proposed design with clarifications and simplifications as described in Table L2.2.3 and the following rules:

a. System parameters not described in Table L2.2.3 and the following sections shall be simulated to meet

the minimum requirements of Section 6.4. b. Where multiple system components serve a block, average values weighed by the appropriate metric as

described in Section L2.2.3.1 shall be used. c. Heat loss from ducts and pipes shall not be modeled. d. The simulation program shall model part-load HVAC equipment performance using either

  1. full-load efficiency (adjusted for fan power input that is modeled separately) and typical part-load performance adjustments for the proposed equipment ;
  2. part-load adjustments based on input of both full-load and part-load metrics, or
  3. equipment -specific adjustments based on performance data provided by the equipment manufacturer for the proposed equipment .

384 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 387

Open page note

Table L4.2.3-2 DCV Outdoor Air Reduction Curve Coefficients

Equation TermDCV OA Reduction (y) as a Function of DCV Effective Controlled Floor Area (x)Col3Col4Col5
Equation TermOfficeSchoolHotel, Motel, Multifamily, DormitoryRetail
b0000
x0.40530.26760.58820.4623
_x_2–0.84890.7753–1.0712–0.848
_x_31.0092–1.51651.35651.1925
_x_4–0.41680.7136–0.6379–0.5895

Figure L4.2.3-2 DCV OA reduction as a function of controlled floor area.

e. Part-load variable-speed fan and pump power shall be calculated using a cubic function with coefficients

as shown in Table L4.2.3-1. The independent variable shall be the fraction of design water flow rate for pumps and the fraction of design airflow rate for fans as shown in Figure L4.2.3-1. f. Demand control ventilation shall be modeled using a simplified approach that adjusts the design outdoor supply airflow rate based on the area of the building that is covered by DCV with coefficients as shown in Table L4.2.3-2. The input shall accommodate two types of DCV :

  1. Variable control based on people sensor response (CO2 sensor or other)
  2. ON/OFF occupied standby control that closes the VAV box primary air damper or shuts off outdoor air when the zone is completely unoccupied based on an occupancy sensor (See Section 6.5.3.8.) (Informative Note: Due to lower probability occurrence, the ON/OFF controls are given 1/3 the reduction of the CO2 sensor DCV . The outdoor air reduction factor shall be based on a smaller area of control being applied to higher density spaces first, adjusted for building type, with outdoor air reduction factors and an application formula as shown.)

For office, school, and retail:

DCV Effective Controlled Floor Area = Area VarDCV + 1/3 × Area ON-OFF AND Area ON-OFF < 1 – Area VarDCV For hotel, motel, dormitory, and multifamily:

DCV Effective Controlled Floor Area = Area VarDCV + Area ON-OFF where

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 385

PDF Page 388

Open page note

Area VarDCV = fraction of block floor area with variable sensor-based DCV control Area ON-OFF = fraction of block floor area with only occupied standby control as defined in Section 6.5.3.8 that does not also have variable sensor-based demand control ventilation .

L4.3 Simulation of the TSPR Reference Building Design. The TSPR reference building design shall be configured and analyzed as specified in this section.

L4.3.1 Non-HVAC Inputs. Utility rates, blocks, HVAC zones, building use types, schedules, occupant density, heat gains, building envelope components, lighting power, and miscellaneous equipment loads shall be modeled the same as in the proposed design.

Elevators, service water-heating equipment, and on-site renewable energy systems shall not be modeled; same as in the proposed design .

L4.3.2 HVAC Equipment. The TSPR reference building design HVAC equipment consists of separate space conditioning systems and DOASs as described in Tables L4.3.2-1 through L4.3.2-3 for the appropriate building use types. Variable-speed drive fan and pump power shall be modeled using parameters in Tables L4.3.2-1. HVAC equipment shall be modeled at minimum efficiency based on specified efficiency metrics in Tables L4.3.2-1 through L4.3.2-3. Where available in Normative Appendix G, equipment -type-specific partload performance adjustments shall be used; otherwise, typical part-load performance adjustments shall be used.

L5. TSPR METRIC FOR SITE HVAC ENERGY INPUT

For purposes of calculating TSPR for the proposed design and the TSPR reference building design, the calculated HVAC energy input of each building project energy source shall be converted to cost using the energy cost prices from Table L5-1.

Informative Notes:

  1. The blended heating prices in Table L5-1 that are used for fossil fuels are not intended to represent actual average prices, but to represent a consistent blended price per 1000 Btu used. This will avoid requiring the simulation program to run the reference systems with a fossil fuels type that matches the proposed building . The common price per site fuel Btu allows proposed system effi- ciency to be properly compared with the reference system .

  2. Informative Tables L5-2 through L5-5 include values for alternate energy input metrics that may be adopted by a jurisdiction. If so, the jurisdiction should replace the TSPR energy input of energy cost in Section L5 with the alternate metric and should include appropriate metric values from Informative Table L5-2 into Table L5-1. The jurisdiction should replace the MPF values in Table 6.6.2.2 with one of the following:

         - For carbon emissions, replace Table 6.6.2.2 MPF values with those in Informative Table L5-3.
    

This table allows users to compare the quantity of carbon dioxide emissions generated by the proposed design building to the target building . For compliance purposes, it is intended for use in voluntary standards and in jurisdictions where the use of a carbon emissions metric is not preempted by U.S. federal law.

        - For source _energy_, replace Table 6.6.2.2 MPF values with those in Informative Table L5-4.

        - For _site_ _energy_, replace Table 6.6.2.2 MPF values with those in Informative Table L5-5.

386 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 389

Open page note

Table L4.3.2-1 TSPR Reference Building Design HVAC Complex Systems

Building Type ParameterLarge Office (warm) aLarge Office (cold) bSchool (warm) aSchool (cold) b
System typeVAV/reheat
water-cooled chiller/
electric_reheat_ with parallel fan
powered boxes
VAV/reheat
water-cooled chiller/
gas_boiler_
VAV/reheat
water-cooled chiller/
electric_reheat_ with parallel fan
powered boxes
VAV/reheat
water-cooled chiller/
gas_boiler_
Fan controlVSD, no static pressure_reset_VSD, no static pressure_reset_VSD, no static pressure_reset_VSD, no static pressure_reset_
Main fan power (W/cfm) proposed ≥MERV131.1651.1651.1651.165
Main fan power (W/cfm) proposed <MERV131.0661.0661.0661.066
Zonal fan power, W/cfm0.35NA0.35NA
Minimum zone airflow fraction1.5 ×Voz1.5 ×Voz1.2 ×Voz1.2 ×Voz
Heat/cool sizing factor1.25/1.151.25/1.151.25/1.151.25/1.15
Outdoor air economizerNoYes except 4ANoYes except 4A
Occupied_outdoor air_ (= proposed)Sum(Voz)/0.75Sum(Voz)/0.75Sum(Voz)/0.65Sum(Voz)/0.65
Energy recovery ventilator_enthalpy recovery_
ratio bypass; SAT set point
NANA50%; no bypass50%; 60°F except no bypass
required in Climate Zone 4A
Demand control ventilationNoNoNoNo
Cooling source2 water-cooled centrif. chillers2 water-cooled centrif. chillers2 water-cooled screw chillers2 water-cooled screw chillers
Cooling_efficiency_Table G3.5.3Table G3.5.3Table G3.5.3Table G3.5.3
Heating source (reheat)Electric resistanceGas_boiler_Electric resistanceGas_boiler_
Furnace or_boiler_ efficiency1.075%Et1.080%Et
Condenser heat rejectionAxial-fan open-circuit cooling towerAxial-fan open-circuit cooling towerAxial-fan open-circuit cooling towerAxial-fan open-circuit cooling tower
Cooling-tower_efficiency_, gpm/hp
(See Section G3.2.3.11)
38.238.238.238.2
Open-circuit cooling-tower turndown (>300 ton)50%50%50%50%
Pump (constant flow/variable flow)Constant flow; 10°F rangeConstant flow; 10°F rangeConstant flow; 10°F rangeConstant flow; 10°F range
Open-circuit cooling-tower approachG3.1.3.11G3.1.3.11G3.1.3.11G3.1.3.11
Cooling condenser_pump_ power, W/gpm19191919

a. “Warm” refers to Climate Zones 0 through 2 and 3A. b. “Cold” refers to Climate Zones 3B, 3C, and 4 through 8. Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 390

Open page note

Table L4.3.2-1 TSPR Reference Building Design HVAC Complex Systems (Continued)

CHWST/OAT: 44–54/80–60 (See Normative Appendix G.)

a. “Warm” refers to Climate Zones 0 through 2 and 3A. b. “Cold” refers to Climate Zones 3B, 3C, and 4 through 8.

Large Office (warm) aLarge Office (cold) bSchool (warm) a
999
131313
121212
444444
CHWST/OAT: 44–54/80–60
(See Normative Appendix G.)
CHWST/OAT: 44–54/80–60
(See Normative Appendix G.)
CHWST/OAT: 44–54/80–60
(See Normative Appendix G.)
Two-way valves and_pump_ VSDTwo-way valves and_pump_ VSDTwo-way valves and_pump_ VSD
16.116.116.1
505050
180180180
HWST/OAT: 180–150/20–50HWST/OAT: 180–150/20–50HWST/OAT: 180–150/20–50
Two-way valves and_pump_ VSDTwo-way valves and_pump_ VSDTwo-way valves and_pump_ VSD

Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 391

Open page note

Table L4.3.2-2 TSPR Reference Building Design HVAC Simple Systems 1

Building Type
Parameter
Medium Office
(warm)a
Medium Office
(cold) b
Small Office
(warm) a
Small Office
(cold) b
Retail
(warm) a
Retail
(cold) b
System typePackage_VAV_—
electric_reheat_
Package_VAV_—
hydronic_reheat_
PSZ-HPPSZ-ACPSZ-HPPSZ-AC
Fan controlVSD, no static
pressure reset
VSD, no static
pressure reset
Constant volumeConstant volumeConstant volumeConstant volume
Main fan power (W/cfm) proposed
≥MERV13
1.2851.2850.9160.9160.8990.899
Main fan power (W/cfm) proposed
<MERV13
1.1761.1760.8500.8500.8350.835
Zonal fan power (W/cfm)0.35NANANANANA
Minimum zone airflow fraction30%30%NANANANA
Heat/cool sizing factor1.25/1.151.25/1.151.25/1.151.25/1.151.25/1.151.25/1.15
Supplemental heating availabilityNANA<40°F OATNA<40°F OATNA
Outdoor air economizerNoYes except 4ANoYes except 4ANoYes except 4A
Occupied_outdoor air_sourcePackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use typesPackaged unit, occupied damper, all_building_ use types
Energy recovery ventilatorNoNoNoNoNoNo
Demand control ventilationNoNoNoNoNoNo
Cooling sourceDX, multistageDX, multistageDX, single stage
(heat pump)
DX, single stageDX, single stage
(heat pump)
DX, single stage
Cooling_COP_ (net of fan)3.403.403.003.003.403.50
Heating sourceElectric resistanceGas_boiler_Heat pumpFurnaceHeat pumpFurnace
Heating_COP_ (net of fan)/furnace
or_boiler_ efficiency
1.075%Et3.4080%Et3.4080%Et

a. “Warm” refers to Climate Zones 0 through 2 and 3A. b. “Cold” refers to Climate Zones 3B, 3C, and 4 through 8. Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 392

Open page note

Table L4.3.2-3 TSPR Reference Building Design HVAC Simple Systems 2

Building Type
Parameter
Hotel
(warm) a
Hotel
(cold) b
Multifamily
(warm) a
Multifamily
(cold) b
System typePTHPPTACPTHPPTAC
Fan controlConstant volumeConstant volumeConstant volumeConstant volume
Main fan power, W/cfm0.3000.3000.3000.300
Heat/cool sizing factor1.25/1.151.25/1.151.25/1.151.25/1.15
Supplemental heating availability<40°FNA<40°FNA
Outdoor air economizerNoNoNoNo
Occupied_outdoor air_ sourcePackaged unit, occupied damperPackaged unit, occupied damperPackaged unit, occupied damperPackaged unit, occupied damper
Energy recovery ventilatorNoNoNoNo
Demand control ventilationNoNoNoNo
Cooling sourceDX, single stage (heat pump)DX, single stageDX, single stage (heat pump)DX, single stage
Cooling_COP_ (net of fan)3.103.203.103.20
Heating sourcePTHP2 hydronic_boilers_PTHP2 hydronic_boilers_
Heating_COP_ (net of fan)/furnace
or_boiler_ efficiency
3.1075%Et3.1075%Et
Heating_pump_ power, W/gpmNA19NA19
Heating-coil HW temperature difference,FNA50NA50
Design HWST,FNA180NA180
HWST reset_set point_ vs. OAT,FNAHWST/OAT: 180–150/20–50NAHWST/OAT: 180–150/20–50
HW-loop pumping controlNATwo-way valves and ride_pump_
curve
NATwo-way valves and ride_pump_
curve

a. “Warm” refers to Climate Zones 0 through 2 and 3A. b. “Cold” refers to Climate Zones 3B, 3C, and 4 through 8. Informative Note: See Section 3.3 for a full list of terms used in this table.

PDF Page 393

Open page note

Table L5-1 Energy Conversion Factors for HVAC Energy Input [ a]

Building Project
Energy Source
UnitsEnergy Cost,
$/unit
Energy Cost,
$/1000 site Btu
ElectricitykWh$0.1099$32.21
Natural gastherm$0.983$9.83
Propanetherm$0.983$9.83
Distillate fuel oilgal$1.353$9.83

a. Energy input conversion factors are based on U.S. averages. Nonelectric heating prices are based on blended heating prices adjusted for the U.S. average mix of heating fuels.

These prices are applied to fuel output per unit.

Informative Table L5-2 Energy Conversion Factors for HVAC Energy Input [ a]

Building Project
Energy Source
UnitsCarbon Emissions (CO e), lb/
2
unit
Site Energy,
Btu/unit
Source Energy,
Btu/unit
ElectricitykWh1.41834129008
Natural gastherm19.960100,000109,000
Propanetherm19.080100,000115,000
Distillate fuel oilgal28.830137,600163,744

a. Energy input conversion factors are based on ASHRAE Standard 189.1-2020. They represent average U.S. values and may be replaced with local values.

Informative Table L5-3 Mechanical Performance Factors (MPF), Carbon Emission Basis

Building TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Office
(small and medium) a
0.720.720.700.710.690.650.710.670.630.730.660.690.760.700.710.790.750.800.82
Office (large) a0.830.830.840.840.790.820.720.830.780.680.790.660.720.740.660.730.720.710.70
Retail0.600.570.500.550.460.460.430.470.380.420.480.540.420.550.540.460.410.420.37
Hotel/motel0.620.620.630.630.620.680.610.710.730.550.640.610.490.550.630.450.480.410.34
Apartment/dormitory0.640.630.670.630.650.640.590.690.550.570.550.490.570.510.440.560.520.530.50
School/education0.820.810.800.790.750.720.710.720.680.680.710.650.750.700.610.790.730.750.71

a. Office sizes defined in Section L1.1.1.1.

Informative Table L5-4 Mechanical Performance Factors (MPF), Site Energy Basis

Building TypeClimate ZoneCol3Col4Col5Col6Col7Col8Col9Col10Col11Col12Col13Col14Col15Col16Col17Col18Col19Col20
Building Type0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B78
Office
(small and medium a
0.720.720.700.710.690.650.710.680.650.810.700.780.850.770.810.870.840.880.90
Office (large)a0.830.830.840.840.790.820.720.810.770.670.760.630.710.720.630.730.710.710.71
Retail0.600.570.500.550.460.460.430.510.400.450.570.680.460.680.670.500.450.440.38
Hotel/motel0.620.620.630.630.620.680.610.710.730.450.590.520.380.470.510.350.380.310.26
Apartment/dormitory0.640.630.670.630.650.640.590.720.550.530.500.440.540.470.380.550.500.510.47
School/education0.820.810.800.790.750.720.710.720.670.730.720.680.820.730.610.890.800.830.77

a. Office sizes defined in Section L1.1.1.1.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 391

PDF Page 394

Open page note

Informative Table L5-5 Mechanical Performance Factors (MPF), Source Energy Basis

Climate Zone

Building Type

Office (small and medium) [ a]

0A0B1A1B2A2B3A3B3C4A4B4C5A5B5C6A6B7
0.720.720.700.710.690.650.710.670.630.710.660.680.750.690.690.770.730.78
0.830.830.840.840.790.820.720.830.780.680.790.670.720.750.660.730.720.71
0.600.570.500.550.460.460.430.470.380.410.470.520.420.530.520.450.400.41
0.620.620.630.630.620.680.610.710.730.560.650.630.510.570.650.470.500.43
0.640.630.670.630.650.640.590.680.540.580.560.500.570.510.460.560.520.54
0.820.810.800.790.750.720.710.720.680.680.710.650.740.690.610.780.710.74

a. Office sizes defined in Section L1.1.1.1.

392 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 395

Open page note

(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been sub- ject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX M ADDENDA DESCRIPTION

ANSI/ASHRAE/IES Standard 90.1-2022 incorporates all addenda to ANSI/ASHRAE/IES Standard 90.1-2019. Table M-1 lists each addendum and describes the way in which the standard is affected by the change. It also lists the ASHRAE, IES, and ANSI approval dates for each addendum.

Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
afG3.1, G3.6Modifies lighting modeling requirements in Appendix G with more specific guidance on determining lighting power in
the baseline vs. proposed building.
6/30/20205/29/2020N/A6/30/2020
bc6.5.4.8Requires condensing boilers for new construction to achieve condensing-level efficiency (i.e., 90%Et) for large boiler
systems (i.e., between 1 and 10 million Btuh) and, to ensure condensing occurs, requires boiler entering water to be in
the prescribed limits for temperature or flow rate.
6/30/20205/29/2020N/A6/30/2020
cd6.5.6.1.2Establishes a minimum enthalpy recovery ratio for energy recovery systems and specifies how bypass or control of the
energy recovery system must operate to ensure proper economizer performance.
6/30/20205/29/2020N/A6/30/2020
dbG3.1, G3.4-9Clarifies how to establish the Normative Appendix G baseline space conditioning categories that must be used in
conjunction with Tables G3.4-1 through G3.4-8 so that the baseline envelope will remain consistent should Section 3
undergo changes.
6/30/20205/29/2020N/A6/30/2020
by3.2, 10.2.1, 10.5.1Adds a minimum prescriptive requirement for on-site renewable energy.6/26/20205/19/20207/1/20207/31/2020
ck12.4.1, 12.4.3,
Table 12.5.1
Explains Section 12 modeling requirements for proposed designs that utilize a trade-off for the renewable energy
requirements in Section 10.5.1.
6/26/20205/19/20207/1/20207/31/2020
cp4.2.1.1, G2.2, Table G3.1Explains Appendix G modeling requirements for proposed designs that utilize a trade-off for the renewable energy
requirements in Section 10.5.1.
6/26/20205/19/20207/1/20207/31/2020
a6.5.3.7, 6.5.3.8, 13Establishes minimum fan efficacy requirements for low-power ventilation fans and references Standard 62.2 for
determining the minimum ventilation rates for nontransient dwelling units.
10/30/202010/7/2020N/A10/30/2020
b6.4.3.8Revises demand control ventilation parameters to be based on climate zone and Standard 62.1 airflow requirements.10/30/202010/7/2020N/A10/30/2020
c6.3.2, 6.4.3.3Requires residential HVAC systems greater than 2.1 kW to be equipped with start/stop and setback controls.10/30/202010/6/2020N/A10/30/2020
d3.2, 6.4.3.4.5Adds new term to define parking garage section so that fan requirements can be refined for different configurations.
Requires fans with the ability to modulate airflow and power as specified.
12/30/202012/16/2020N/A12/30/2020
fTable 6.5.1-2Clarifies the efficiency improvement required in order to eliminate an economizer.2/26/20212/18/2021N/A2/26/2021
g6.5.1.1.5Adds more specific language about relieving excess outdoor air during air economizer operation through the use of fans
or dampers.
12/30/202012/16/2020N/A12/30/2020
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.

PDF Page 396

Open page note

Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019 (Continued)

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
h4.2.1.1Clarifies that the gross floor area should be used when calculating the area-weighted building performance factor (BPF.)10/30/202010/6/2020N/A10/30/2020
iG3.1.2.10Reinstates exception to Appendix G exhaust air energy recovery requirements for laboratory HVAC systems.10/30/202010/6/2020N/A10/30/2020
k12.5.2Adjusts Section 12 budget building fan requirements to avoid creating a fan power credit for energy recovery.10/30/202010/6/2020N/A10/30/2020
lG3.1Revises Appendix G language describing how to calculate and assign vertical fenestration in the baseline design.10/30/202010/6/2020N/A10/30/2020
m6.4.3.4.1Clarifies requirements for motorized dampers on vents for elevator shafts and stairwells; adds exception to allow
nonmotorized dampers in mild climates and low-rise buildings.
10/30/202010/6/2020N/A10/30/2020
n6.5.2.6Adds an exception to Section 6.5.2.6 allowing units to heat the ventilation airstream above 60°Fif exclusively using
series energy recovery.
10/30/202010/6/2020N/A10/30/2020
o9.4.1.1Reduces the minimum connected load that triggers daylighting responsive control requirements for sidelighting and
toplighting.
7/30/20216/9/2021N/A7/30/2021
p9.1.2, 9.1.4Modifies portions of Section 9 pertaining to alterations to ensure that such projects meet all applicable lighting
requirements.
2/26/20212/18/2021N/A2/26/2021
qTable G3.7Corrects Table G3.7 to maintain equivalent space type requirements per the established 2004 baseline.2/26/20212/18/2021N/A2/26/2021
r6.4.3.3.3Clarifies that residential spaces are not required to have optimal start controls.2/26/20212/18/2021N/A2/26/2021
s3.2, 5.5.3.1.1, 5.5.3.2,
5.5.4.5, Table 12.5.1, C3.6,
Table G3.1
Replaces the term_solar reflectance index (SRI)_ with_solar reflectance_ (for walls only) and establishes a minimum solar
reflectance requirement for east-, south-, and west-oriented walls in Climate Zone 0.
2/26/20212/18/2021N/A2/26/2021
t3.2, 4.2.5, 5.1.3, 5.4.3,
5.7.2, 5.7.3.1, 5.8, 5.9.1.2,
6.4.4.2.1, 6.4.5, 6.5.1,
Table 12.5.1 (5), 12.5.3,
13, C1.5, C3.5.5.3, C3.6,
C3.1.1.4, Table G3.1 (5),
Table H-3
Adds requirement to perform whole-building air leakage testing and measurement on buildings less than 25,000 ft2,
specifies performance requirements for compliance, references the applicable ASTM standard, and modifies relevant
Section 3 terminology.
6/25/20226/17/20226/29/20227/29/2022
u12.5.2Specifies the use of air economizers for budget building systems and clarifies method for determining prescriptive
HVAC requirements based on the budget system type and capacity.
7/30/20216/9/2021N/A7/30/2021
v12.7.2, G1.3.2Clarifies the documentation that must be submitted to the rating authority or jurisdiction by projects following Section
12 and Appendix G, including simulation files upon request.
7/30/20216/9/2021N/A7/30/2021
wG3.1.3.7Indicates that chillers (type and number) shall be modeled in the baseline building design based on the total peak
coincident cooling load of the baseline HVAC system using chilled water.
2/26/20212/18/2021N/A2/26/2021
x6.4.1.2, Table 6.8.1-3Updates the cooling efficiency adjustment for centrifugal chillers and the requirements for chillers utilizing freeze-
protection. Replaces “fluid” and “water” with “liquid” throughout.
12/9/202112/8/2021N/A12/9/2021
yTable 6.8.1-16Modifies the minimum efficiency requirements for air-source heat pumps, updates the related AHRI rating standards,
introduces a new metric (COPHR) for units that perform heat recovery during chiller operation.
12/9/202112/8/2021N/A12/9/2021
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.

PDF Page 397

Open page note

Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019 (Continued)

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
z9.1.4Lowers the wattage assigned for track lighting to reflect the predominate use of higher-efficiency LED technology.2/28/20222/25/2022N/A2/28/2022
aaG3.1.2.9, Table G3.1Corrects the SI fan power values in Appendix G to make them consistent with the rest of the standard.5/28/20215/4/2021N/A5/28/2021
ab3.2, 3.3, G3Clarifies the process for selecting baseline HVAC systems when using the Appendix G Performance Rating Method
(PRM); includes new acronyms to describe HVAC systems and a new definition for “residential associated HVAC zone.”
6/30/20216/9/2021N/A6/30/2021
ac3.2, 9.4.1.2, Table 9.2.3.1,
Table 9.6.1, Appendix E
Updates interior lighting power and minimum control requirements: adds a power exception for the germicidal function
in luminaires and sources, removes exceptions for casinos and parking garage daylight transition zone lighting, and
provides a definition for the latter item.
6/25/20226/17/20226/29/20227/29/2022
ad9Reorganizes Section 9, “Lighting,” to better parallel the structure of the other main sections.8/31/20218/26/2021N/A8/31/2021
ae8.4.4Updates exceptions and footnotes associated with Section 8.4.4 requirements for the minimum efficiency of low-voltage
dry-type transformers in commercial buildings.
8/31/20218/26/2021N/A8/31/2021
ag3.2, 3.3, 6.2.26.6,
Appendix K
Introduces an optional Mechanical System Performance Path that allows HVAC system efficiency trade-offs based on a
new metric—total system performance ratio (TSPR)—to ensure that equivalent energy savings are maintained
compared to the prescriptive approach.
7/20/20229/8/20228/15/20229/9/2022
ah7.5.3Increases the thermal efficiency required for high-capacity gas-fired service water-heating equipment and provides the
U.S. DOE criteria for defining high-capacity water heaters.
8/31/20218/26/2021N/A8/31/2021
ajTable G-1Updates Appendix G to align with Addendum ae clarifications related to baseline transformer performance.9/30/20219/27/2021N/A9/30/2021
akG3.1.1Provides criteria for determining when an HVAC zone should be isolated from a multizone system in the baseline
building model.
9/30/20219/27/2021N/A9/30/2021
am9.2.3.2, Table 9.2.3.2,
9.4.1.4, 9.4.2, Table 9.4.2-1,
Table 9.4.2-2
Modifies exterior lighting power and control requirements based on improvements in technology and revised lighting
practices; restructures portions of Section 9 to better communicate exceptions to those requirements.
incorrect reference to cavity spaces vs subject of narrative to right regarding lighting?
6/25/20226/17/20226/29/20227/29/2022
anTable G3.1Clarifies baseline HVAC fan schedule requirements for projects that rely on ventilation via operable windows that are
manually opened by the occupants.
9/30/20219/27/2021N/A9/30/2021
ao5.4.3.3.3, 6.4.3.9, 10.4.5,
Table H-3
Revises the requirements for air curtain units and controls and indicates that installation is to be performed in
accordance with the manufacturer’s instructions.
9/30/20219/27/2021N/A9/30/2021
ap3.2, 3.3, 4.2.1, 4.2.2, 9.9.1,
12.2, 13, Section 11
Introduces a new section to Standard 90.1 for the use of energy credits to enable an approximately 4% to 5% energy cost
savings. There are a total of 33 individual measures from which users can earn the required number of credits for their
building type and climate zone.
7/20/20229/8/20228/15/20229/9/2022
aq6.8.3, Table 6.8.3-1, Table
6.8.3-2, 7.4.3, Table 7-4
Introduces requirements for service water heating pipe insulation based on typical operating conditions.7/29/20227/26/2022N/A7/29/2022
ar3.2, Table 9.2.3.1, 9.4.4,
Appendix E
Adds requirements for indoor horticultural lighting based on a new metric, photosynthetic photon efficacy (PPE),
developed in ANSI/ASABE S640.
7/20/20229/8/20228/15/20229/9/2022
as4.2.4, 5.9, 6.9, 7.9, 8.9,
9.9, 10.9
Rearranges envelope inspection requirements and improves commissioning language throughout.1/27/20221/18/2022N/A1/27/2022
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.

PDF Page 398

Open page note

Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019 (Continued)

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
at3.2, 4, 5, 6, 7, 8, 10Establishes a consistent numbering system for each section of the standard and revises the definition for alteration.1/27/20221/18/2022N/A1/27/2022
au6.2, 6.3.2Requires that heating and cooling equipment under the simplified compliance approach meet the requirements of
Section 6.4.1.5.
1/21/20221/18/2022N/A1/21/2022
av3.2, 3.3, 5.5.3.2, 5.5.5,
5.6.1.1, 5.7.2, 5.8.2.3,
Table 12.5.1 (5), 13, A1,
A10, C1.2.7, C2.9,
C3.5.5.4, C3.6, Appendix
E, Table G3.1 (5),
Appendix J
Adds requirements to address the impacts of thermal bridges in the building envelope.6/25/20226/17/20226/29/20227/29/2022
aw3.2, 3.3, 6.4.1.1, Table
6.8.1-21, Table F-6, 13
Adds the minimum energy efficiency requirements (and new CFEI metric) for large-diameter ceiling fans from
10 CFR 430.
1/21/20221/18/2022N/A1/21/2022
ayModifies Tables 6.8.1-8 and 6.8.1-9 for variable refrigerant flow (VRF) equipment based on the new AHRI 1230-2021
test procedure which required an adjustment to EER and IEER values.
7/20/20229/8/20228/15/20229/9/2022
az3.2, 10.4.6Introduces compressed air system requirements with measures for reducing common sources of energy waste.1/21/20221/18/2022N/A1/21/2022
bb9.5.1Updates the lighting power density values for the Building Area Method compliance path based on manufacturer-
reported improvements in lighting performance.
7/29/20227/26/2022N/A7/29/2022
bd12.5.2, Table 12.5.1,
G3.1.2, Table G3.1, Table
G3.5.3, Appendix L
Provides performance curves for modeling chillers in budget (Section 12) and baseline designs (Appendix G) as well as
default performance curves that can be used for chillers in proposed designs.
5/31/20225/19/2022N/A5/31/2022
be12.4.1.4, 12, C3.1.4,
G2.2.4
Updates references to the latest ANSI/ASHRAE Standard 140-2020 and specifies which simulation program tests are
required for compliance with Appendix C and G of Standard 90.1.
1/21/20221/18/2022N/A1/21/2022
bf9.5.2.2Updates the decorative and retail lighting power allowances, adds an additional allowance for videoconferencing, and
moves the additional power allowances and required controls to a table for easy reference.
5/31/20225/19/2022N/A5/31/2022
bg3.2, 8.1, 8.7.3.2, 9.1.1,
9.4.1, 9.6.3, 10.1.1, Table
12.5.1 (12), G1.2.2,
Table G3.1
Updates Sections 8, 9, 10, 12 and Appendix G to reflect the new purpose and scope (Addendum cb), utilizing the new
definition of site.
6/25/20226/17/20226/29/20227/29/2022
bhTable 12.5.1Revises the default PV system in the budget building design so that the temperature coefficient of power is aligned with
the PV Watts input for a 19% panel efficiency as required by Addendum ck.
1/21/20221/18/2022N/A1/21/2022
bi3.2, 5.1.3, 5.5.3.1Creates specific provisions to distinguish roof replacements from other types of alterations.7/29/20227/26/2022N/A7/29/2022
bj5.5.3, A1, A9, Appendix EReformats and clarifies Normative Appendix A requirements for thermal performance calculations to demonstrate
compliance with Section 5.5
6/25/20226/17/20226/29/20227/29/2022
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.

PDF Page 399

Open page note

Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019 (Continued)

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
bk6.3.2, 6.4.3.3.2, 6.4.3.3.5,
6.4.5, 6.4.6, 12.4.1.1,
12.5.2, G2.2.1
Updates humidity control requirements in accordance with the latest Standard 62.1-2019.1/21/20221/18/2022N/A1/21/2022
bm6.5.3.8Modifies occupied-standby controls from multiple-zone systems to explicitly require an outdoor air reset when
ventilation is reduced to zero.
1/21/20221/18/2022N/A1/21/2022
bp9.4.1.3Removes the exception for captive card key controls in hotel guestrooms9/30/20229/8/2022N/A9/30/2022
bq8.4.3Adds a requirement to perform electrical energy monitoring with separate metering for refrigeration systems where
refrigeration accounts for 10% or more of the building load.
6/25/20226/17/20226/29/20227/29/2022
br9.4.3Increases the efficacy threshold for lamps and luminaires in dwelling units and specifies requirements for interior and
exterior lighting controls.
6/25/20226/17/20226/29/20227/29/2022
bs9.3.1, 9.3.2Updates the lighting power allowances (LPA) in the Simplified Building Method Compliance Path to maintain
alignment with the established method (0.9x the Building Area Method LPA values.). Removes an exception for
alterations that had incentivized the use of LEDs before they became commonplace.
7/29/20227/26/2022N/A7/29/2022
btG3.1.3.5, G3.1.3.10,
G3.1.3.19
Indicates that baseline system pumps are to be modeled based on the presence of a load and preheat coil temperature is
to be modeled compared to the zone with the highest set point.
6/30/20226/10/2022N/A6/30/2022
bvTable 4.2.1.1Updates the building performance factors (BPFs) used to determine compliance with Normative Appendix G based on
energy-efficiency improvements in the 2022 standard.
6/30/20226/10/2022N/A6/30/2022
bw6.5.3.1.3Clarifies that the fan efficiency metric is to be applied at the highest design airflow rate.4/29/20224/27/2022N/A4/29/2022
bxTable 6.8.1-5Modifies Table 6.8.1-5 for warm air furnace efficiency requirements to more accurately distinguish between different
products and test procedures based on locations in which they are used and their status as DOE or non-DOE covered
products.
7/29/20227/26/2022N/A7/29/2022
bz6.5.6Adds language to specify the sensible energy recovery ratio requirement for systems that require only sensible heating
energy recovery.
4/29/20224/27/2022N/A4/29/2022
cb1.1, 2.1, 2.2, 2.3, 3.2,
4.1.1.6, 4.2.1.4, 4.1.2.5,
10.4.6, Table G3.1
Revises the 90.1 Purpose and Scope to apply to areas outside of the physical building that qualify under the new
definition for “site.”
2/2/20221/28/20222/2/20223/1/2022
ceA2.5, A3.3, A9.2, 13Adds new reference and requirements for steel-framed walls aligned with ANSI/AISI S250, which provides additional
options for wall framing and insulation placement.
4/29/20224/27/2022N/A4/29/2022
cf10.4.3, 10.9.3Introduces provisions that improve elevator fan, lighting, and movement efficiency.4/29/20224/27/2022N/A4/29/2022
cg5.5.3, A9.4.7Adds a definition for insulated metal panels (IMPs) and a new section to explain how the U-factor of a given IMP is
determined.
4/29/20224/27/2022N/A4/29/2022
ciTable 6.5.1-1Requires fan cooling-units outside of the building to have an economizer at the indicated capacity range.4/29/20224/27/2022N/A4/29/2022
cjTable 6.8.1-16Corrects numerical errors that were present in the centrifugal chiller category when it was updated in Addendum y.4/29/20224/27/2022N/A4/29/2022
cm13Updates the normative references used in the standard to the latest applicable versions.7/29/20227/26/2022N/A7/29/2022
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.

PDF Page 400

Open page note

Table M-1 Addenda to ANSI/ASHRAE/IES Standard 90.1-2019 (Continued)

AddendumSectionsDescription of ChangesaASHRAE
Standard
Committee
Approval
Cosponsor
Approval
(IES)
ASHRAE
BOD/Tech
Council
Approval
ANSI
Approval
co4.2.1.1, 4.2.1.3, G3.1,
G3.2, G3.3
Adds new performance requirements for alterations, allowing larger retrofit projects a 5% increase in Building
Performance Factor (BPF) relative to new construction vs. smaller retrofit projects which are subject to a new Section G3.3.
6/25/20226/17/20226/29/20227/29/2022
cqG3.1.2.1, Table G3.1 (10),
Table G3.1.3.7, Table
G3.5.3
Modifies Appendix G to align with Section 6 updates (e.g., removes outdated references, corrects instructions for
determining equipment efficiency, converts “water” to “liquid” in the descriptions for chiller equipment.)
6/25/20226/27/20226/29/20227/29/2022
cr12.2, G1.2.1Adds language to limit the extent that envelope trade-offs can be used for compliance with Section 12 and Appendix G
based on the amount that a proposed envelope performance factor is permitted to exceed the base value (i.e., envelope
“backstop”).
11/4/202010/7/202011/18/202012/16/2020
cs12.5.2Clarifies efficiency requirements for HVAC and service water-heating equipment in the Section 12 budget building
design.
6/30/20226/10/2022N/A6/30/2022
ctTable G3.1 (5)Provides additional details about the envelope modeling requirements for Appendix G baseline buildings.6/30/20226/10/2022N/A6/30/2022
cu6.5.6.3Specifies that the heat source for performing heat recovery, as required for most acute inpatient hospitals, is the return
water from a heat-pump chiller.
6/30/20226/10/2022N/A6/30/2022
cySection 12Updates the normative references to include the latest published addenda to 90.4-20199/30/20229/8/2022N/A9/30/2022
daG1.3.2, G2.2, G2.3,
G2.4.2, G2.5, Table G3.1
Aligns Appendix G requirements for documentation, simulation programs, climactic data, and exceptions with the
corresponding portions of Section 12.
12/30/202012/16/2020N/A12/30/2020
a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.a. These descriptions may not be complete and are provided for information only.

NOTE

Approved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAE website at www.ashrae.org/technology.

PDF Page 401

Open page note

(This annex contains normative material from an existing ASHRAE standard that is cited in this stan- dard. This annex is not part of this standard; its inclusion is merely informative. It is included here to facilitate use of this standard.)

ANNEX 1 REFERENCE STANDARD REPRODUCTION—ASHRAE STANDARD 169

Annex 1 contains extractions of the following material from ASHRAE Standard 169 in the following order:

ASHRAE Standard 169 Material

Table Annex1-1: Table B-1, U.S. Climate Zones by State and County

Figure Annex1-1: Figure B-1, Climate zones for United States counties.

Table Annex1-2: Table A-5, Canada Stations and Climate Zones

Figure Annex1-3: Table A-6, International Stations and Climate Zones

Section Annex1-1: Section A3, Climate Zone Definitions

Table Annex1-4: Table A-3, Thermal Climate Zone Definitions

Figure Annex1-2: Figure A-1, Thermal climate zones as a function of heating and cooling degree-days.

Figure Annex1-3: Figure C-2, World climate zones map.

Section Annex1-2: Section 4, Climatic Design Data and Climate Zones

Informative Note: Section references that appear in this annex are references to sections or appendices in ANSI/ASHRAE Standard 169.

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 399

PDF Page 402

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County

State/County Zone State/County Zone

Alabama (AL) Arkansas (AR)

Zone 3A except… Zone 3A except…

Baldwin 2A Baxter 4A

Coffee 2A Benton 4A

Covington 2A Boone 4A

Dale 2A Carroll 4A

Escambia 2A Fulton 4A

Geneva 2A Izard 4A

Henry 2A Madison 4A

Houston 2A Marion 4A

Mobile 2A Newton 4A

Alaska (AK) Searcy 4A

Zone 7 except… Stone 4A

Ketchikan Gateway 5C Washington 4A

Prince of Wales-Outer Ketchikan 5C California (CA)

Sitka 5C Zone 3B except…

Haines 6A Imperial 2B

Juneau 6A Alameda 3C

Kodiak Island 6A Marin 3C

Skagway-Hoonah-Angoon 6A Mendocino 3C

Wrangell-Petersburg 6A Monterey 3C

Denali 8 Napa 3C

Fairbanks North Star 8 San Benito 3C

Nome 8 San Francisco 3C

North Slope 8 San Luis Obispo 3C

Northwest Arctic 8 San Mateo 3C

Southeast Fairbanks 8 Santa Barbara 3C

Wade Hampton 8 Santa Clara 3C

Yukon-Koyukuk 8 Santa Cruz 3C

Arizona (AZ) Sonoma 3C

Zone 3B except… Ventura 3C

La Paz 2B Amador 4B

Maricopa 2B Calaveras 4B

Pima 2B El Dorado 4B

Pinal 2B Inyo 4B

Yuma 2B Lake 4B

Gila 4B Mariposa 4B

Yavapai 4B Trinity 4B

400 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 403

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Apache 5B Tuolumne 4B

Coconino 5B Del Norte 4C

Navajo 5B Humboldt 4C

Lassen 5B Connecticut (CT)

Modoc 5B Zone 5A

Nevada 5B Delaware (DE)

Plumas 5B Zone 4A

Sierra 5B District of Columbia (DC)

Siskiyou 5B Zone 4A

Alpine 6B Florida (FL)

Mono 6B Zone 2A except…

Colorado (CO) Broward 1A

Zone 5B except… Miami-Dade 1A

Baca 4B Monroe 1A

Bent 4B Palm Beach 1A

Las Animas 4B Georgia (GA)

Otero 4B Zone 3A except…

Prowers 4B Appling 2A

Alamosa 6B Atkinson 2A

Archuleta 6B Bacon 2A

Chaffee 6B Baker 2A

Conejos 6B Berrien 2A

Costilla 6B Brantley 2A

Dolores 6B Brooks 2A

Eagle 6B Bryan 2A

Moffat 6B Calhoun 2A

Ouray 6B Camden 2A

Rio Blanco 6B Charlton 2A

Saguache 6B Chatham 2A

San Miguel 6B Clinch 2A

Clear Creek 7 Coffee 2A

Grand 7 Colquitt 2A

Gunnison 7 Cook 2A

Hinsdale 7 Decatur 2A

Jackson 7 Dougherty 2A

Lake 7 Early 2A

Mineral 7 Echols 2A

Park 7 Effingham 2A

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 401

PDF Page 404

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Pitkin 7 Evans 2A

Rio Grande 7 Glynn 2A

Routt 7 Grady 2A

San Juan 7 Irwin 2A

Summit 7 Jeff Davis 2A

Lanier 2A Illinois (IL)

Liberty 2A Zone 5A except…

Long 2A Alexander 4A

Lowndes 2A Bond 4A

McIntosh 2A Calhoun 4A

Miller 2A Christian 4A

Mitchell 2A Clark 4A

Pierce 2A Clay 4A

Seminole 2A Clinton 4A

Tattnall 2A Coles 4A

Thomas 2A Crawford 4A

Tift 2A Cumberland 4A

Toombs 2A Edwards 4A

Ware 2A Effingham 4A

Wayne 2A Fayette 4A

Worth 2A Franklin 4A

Hawaii (HI) Gallatin 4A

Zone 1A Greene 4A

Idaho (ID) Hamilton 4A

Zone 6B except… Hardin 4A

Ada 5B Jackson 4A

Benewah 5B Jasper 4A

Canyon 5B Jefferson 4A

Cassia 5B Jersey 4A

Clearwater 5B Johnson 4A

Elmore 5B Lawrence 4A

Gem 5B Macoupin 4A

Gooding 5B Madison 4A

Idaho 5B Marion 4A

Jerome 5B Massac 4A

Kootenai 5B Monroe 4A

Latah 5B Montgomery 4A

Lewis 5B Perry 4A

402 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 405

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Lincoln 5B Pope 4A

Minidoka 5B Pulaski 4A

Nez Perce 5B Randolph 4A

Owyhee 5B Richland 4A

Payette 5B Saline 4A

Power 5B Shelby 4A

Shoshone 5B St. Clair 4A

Twin Falls 5B Union 4A

Washington 5B Wabash 4A

Washington 4A Scott 4A

Wayne 4A Shelby 4A

White 4A Spencer 4A

Williamson 4A Sullivan 4A

Indiana (IN) Switzerland 4A

Zone 5A except… Union 4A

Bartholomew 4A Vanderburgh 4A

Brown 4A Vigo 4A

Clark 4A Warrick 4A

Clay 4A Washington 4A

Crawford 4A Iowa (IA)

Daviess 4A Zone 5A except…

Dearborn 4A Cerro Gordo 6A

Decatur 4A Clay 6A

Dubois 4A Dickinson 6A

Fayette 4A Emmet 6A

Floyd 4A Hancock 6A

Franklin 4A Kossuth 6A

Gibson 4A Lyon 6A

Greene 4A Mitchell 6A

Harrison 4A O’Brien 6A

Hendricks 4A Osceola 6A

Jackson 4A Palo Alto 6A

Jefferson 4A Sioux 6A

Jennings 4A Winnebago 6A

Johnson 4A Worth 6A

Knox 4A Kansas (KS)

Lawrence 4A Zone 4A except…

Marion 4A Cheyenne 5A

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 403

PDF Page 406

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Martin 4A Decatur 5A

Monroe 4A Gove 5A

Morgan 4A Greeley 5A

Ohio 4A Jewell 5A

Orange 4A Logan 5A

Owen 4A Norton 5A

Perry 4A Phillips 5A

Pike 4A Rawlins 5A

Posey 4A Republic 5A

Putnam 4A Scott 5A

Ripley 4A Sheridan 5A

Rush 4A Sherman 5A

Smith 5A Massachusetts (MA)

Thomas 5A Zone 5A

Wallace 5A Michigan (MI)

Wichita 5A Zone 5A except…

Kentucky (KY) Alcona 6A

Zone 4A Alger 6A

Louisiana (LA) Alpena 6A

Zone 2A except… Antrim 6A

Bienville Parish 3A Arenac 6A

Bossier Parish 3A Baraga 6A

Caddo Parish 3A Benzie 6A

Caldwell Parish 3A Charlevoix 6A

Catahoula Parish 3A Cheboygan 6A

Claiborne Parish 3A Chippewa 6A

Concordia Parish 3A Clare 6A

De Soto Parish 3A Crawford 6A

East Carroll Parish 3A Delta 6A

Franklin Parish 3A Dickinson 6A

Grant Parish 3A Emmet 6A

Jackson Parish 3A Gladwin 6A

La Salle Parish 3A Gogebic 6A

Lincoln Parish 3A Grand Traverse 6A

Madison Parish 3A Houghton 6A

Morehouse Parish 3A Iosco 6A

Natchitoches Parish 3A Iron 6A

Ouachita Parish 3A Isabella 6A

404 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 407

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Red River Parish 3A Kalkaska 6A

Richland Parish 3A Lake 6A

Sabine Parish 3A Leelanau 6A

Tensas Parish 3A Luce 6A

Union Parish 3A Mackinac 6A

Vernon Parish 3A Manistee 6A

Webster Parish 3A Mason 6A

West Carroll Parish 3A Mecosta 6A

Winn Parish 3A Menominee 6A

Maine (ME) Missaukee 6A

Zone 6A except… Montmorency 6A

Aroostook 7 Newaygo 6A

Maryland (MD) Oceana 6A

Zone 4A except… Ogemaw 6A

Allegany 5A Ontonagon 6A

Garrett 5A Osceola 6A

Oscoda 6A Jackson 2A

Otsego 6A Pearl River 2A

Presque Isle 6A Stone 2A

Roscommon 6A Missouri (MO)

Schoolcraft 6A Zone 4A except…

Wexford 6A Dunklin 3A

Keweenaw 7 Pemiscot 3A

Marquette 7 Adair 5A

Minnesota (MN) Andrew 5A

Zone 6A except… Atchison 5A

Fillmore 5A Clark 5A

Houston 5A Daviess 5A

Winona 5A DeKalb 5A

Aitkin 7 Gentry 5A

Beltrami 7 Grundy 5A

Carlton 7 Harrison 5A

Cass 7 Holt 5A

Clearwater 7 Knox 5A

Cook 7 Lewis 5A

Crow Wing 7 Linn 5A

Hubbard 7 Livingston 5A

Itasca 7 Macon 5A

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 405

PDF Page 408

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Kittson 7 Marion 5A

Koochiching 7 Mercer 5A

Lake 7 Nodaway 5A

Lake of the Woods 7 Pike 5A

Mahnomen 7 Putnam 5A

Marshall 7 Ralls 5A

Norman 7 Schuyler 5A

Pennington 7 Scotland 5A

Pine 7 Shelby 5A

Polk 7 Sullivan 5A

Red Lake 7 Worth 5A

Roseau 7 Montana (MT)

St. Louis 7 Zone 6B

Wadena 7 Nebraska (NE)

Mississippi (MS) Zone 5A

Zone 3A except… Nevada (NV)

George 2A Zone 5B except…

Hancock 2A Clark 3B

Harrison 2A Carson City 4B

Douglas 4B Union 4B

Esmeralda 4B Valencia 4B

Lincoln 4B New York (NY)

Lyon 4B Zone 5A except…

Mineral 4B Bronx 4A

Nye 4B Kings 4A

New Hampshire (NH) Nassau 4A

Zone 6A except… New York 4A

Hillsborough 5A Queens 4A

Merrimack 5A Richmond 4A

Rockingham 5A Suffolk 4A

Strafford 5A Chenango 6A

New Jersey (NJ) Clinton 6A

Zone 4A except… Delaware 6A

Bergen 5A Essex 6A

Hunterdon 5A Franklin 6A

Morris 5A Fulton 6A

Passaic 5A Hamilton 6A

Somerset 5A Herkimer 6A

406 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 409

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Sussex 5A Jefferson 6A

Warren 5A Lewis 6A

New Mexico (NM) Madison 6A

Zone 5B except… Montgomery 6A

Chaves 3B Oneida 6A

Dona Ana 3B Otsego 6A

Eddy 3B St. Lawrence 6A

Hidalgo 3B Sullivan 6A

Lea 3B Ulster 6A

Luna 3B Warren 6A

Otero 3B North Carolina (NC)

Sierra 3B Zone 3A except…

Bernalillo 4B Alleghany 5A

Catron 4B Ashe 5A

Curry 4B Avery 5A

DeBaca 4B Buncombe 4A

Grant 4B Burke 4A

Guadalupe 4B Caldwell 4A

Lincoln 4B Graham 4A

Quay 4B Haywood 4A

Roosevelt 4B Henderson 4A

Socorro 4B Jackson 4A

Macon 4A Greene 4A

Madison 4A Hamilton 4A

McDowell 4A Highland 4A

Mitchell 4A Hocking 4A

Stokes 4A Jackson 4A

Surry 4A Lawrence 4A

Swain 4A Madison 4A

Transylvania 4A Meigs 4A

Watauga 5A Pickaway 4A

Wilkes 5A Pike 4A

Yadkin 4A Ross 4A

Yancy 5A Scioto 4A

North Dakota (ND) Vinton 4A

Zone 6A except… Warren 4A

Benson 7 Washington 4A

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 407

PDF Page 410

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Bottineau 7 Oklahoma (OK)

Burke 7 Zone 3A except…

Cavalier 7 Alfalfa 4A

Divide 7 Craig 4A

Grand Forks 7 Delaware 4A

McHenry 7 Ellis 4A

Nelson 7 Garfield 4A

Pembina 7 Grant 4A

Pierce 7 Harper 4A

Ramsey 7 Kay 4A

Renville 7 Major 4A

Rolette 7 Nowata 4A

Towner 7 Osage 4A

Walsh 7 Ottawa 4A

Ward 7 Washington 4A

Ohio (OH) Woods 4A

Zone 5A except… Woodward 4A

Adams 4A Beaver 4B

Athens 4A Cimarron 4B

Brown 4A Texas 4B

Butler 4A Oregon (OR)

Clermont 4A Zone 4C except…

Clinton 4A Baker 5B

Fayette 4A Crook 5B

Franklin 4A Deschutes 5B

Gallia 4A Gilliam 5B

Grant 5B Charles Mix 5A

Harney 5B Clay 5A

Hood River 5B Douglas 5A

Jefferson 5B Gregory 5A

Klamath 5B Haakon 5A

Lake 5B Hutchinson 5A

Malheur 5B Jackson 5A

Morrow 5B Jones 5A

Sherman 5B Lyman 5A

Umatilla 5B Mellette 5A

Union 5B Stanley 5A

Wallowa 5B Todd 5A

408 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 411

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Wasco 5B Tripp 5A

Wheeler 5B Union 5A

Pennsylvania (PA) Yankton 5A

Zone 5A except… Tennessee (TN)

Adams 4A Zone 4A except…

Berks 4A Bedford 3A

Bucks 4A Chester 3A

Chester 4A Coffee 3A

Cumberland 4A Crockett 3A

Dauphin 4A Davidson 3A

Delaware 4A Decatur 3A

Franklin 4A Dyer 3A

Lancaster 4A Fayette 3A

Lebanon 4A Franklin 3A

Montgomery 4A Gibson 3A

Perry 4A Giles 3A

Philadelphia 4A Grundy 3A

York 4A Hamilton 3A

Rhode Island (RH) Hardeman 3A

Zone 5A Hardin 3A

South Carolina (SC) Haywood 3A

Zone 3A except… Henderson 3A

Beaufort 2A Hickman 3A

Jasper 2A Lauderdale 3A

South Dakota (SD) Lawrence 3A

Zone 6A except… Lewis 3A

Bennett 5A Lincoln 3A

Bon Homme 5A Madison 3A

Brule 5A Marion 3A

Marshall 3A Fayette 2A

Maury 3A Fort Bend 2A

McNairy 3A Freestone 2A

Moore 3A Galveston 2A

Perry 3A Goliad 2A

Rutherford 3A Gonzales 2A

Shelby 3A Grimes 2A

Tipton 3A Guadalupe 2A

Wayne 3A Hardin 2A

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 409

PDF Page 412

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Williamson 3A Harris 2A

Texas (TX) Hays 2A

Zone 3A except… Hill 2A

Cameron 1A Houston 2A

Hidalgo 1A Jackson 2A

Willacy 1A Jasper 2A

Anderson 2A Jefferson 2A

Angelina 2A Jim Hogg 2A

Aransas 2A Jim Wells 2A

Atascosa 2A Johnson 2A

Austin 2A Karnes 2A

Bastrop 2A Kenedy 2A

Bee 2A Kleberg 2A

Bell 2A Lavaca 2A

Bexar 2A Lee 2A

Bosque 2A Leon 2A

Brazoria 2A Liberty 2A

Brazos 2A Limestone 2A

Brooks 2A Live Oak 2A

Burleson 2A Madison 2A

Caldwell 2A Matagorda 2A

Calhoun 2A McLennan 2A

Chambers 2A McMullen 2A

Cherokee 2A Milam 2A

Colorado 2A Montgomery 2A

Comal 2A Navarro 2A

Coryell 2A Newton 2A

Dallas 2A Nueces 2A

DeWitt 2A Orange 2A

Duval 2A Polk 2A

Ellis 2A Refugio 2A

Falls 2A Robertson 2A

San Jacinto 2A Crosby 3B

San Patricio 2A Culberson 3B

Starr 2A Dawson 3B

Tarrant 2A Dickens 3B

Travis 2A Ector 3B

Trinity 2A El Paso 3B

410 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 413

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Tyler 2A Fisher 3B

Victoria 2A Foard 3B

Walker 2A Gaines 3B

Waller 2A Garza 3B

Washington 2A Glasscock 3B

Wharton 2A Hall 3B

Williamson 2A Hardeman 3B

Wilson 2A Haskell 3B

Bandera 2B Hemphill 3B

Dimmit 2B Howard 3B

Edwards 2B Hudspeth 3B

Frio 2B Irion 3B

Kinney 2B Jeff Davis 3B

La Salle 2B Jones 3B

Maverick 2B Kent 3B

Medina 2B Kerr 3B

Real 2B Kimble 3B

Uvalde 2B King 3B

Val Verde 2B Knox 3B

Webb 2B Loving 3B

Zapata 2B Lubbock 3B

Zavala 2B Lynn 3B

Andrews 3B Martin 3B

Baylor 3B Mason 3B

Borden 3B McCulloch 3B

Brewster 3B Menard 3B

Callahan 3B Midland 3B

Childress 3B Mitchell 3B

Coke 3B Motley 3B

Coleman 3B Nolan 3B

Collingsworth 3B Pecos 3B

Concho 3B Presidio 3B

Cottle 3B Reagan 3B

Crane 3B Reeves 3B

Crockett 3B Runnels 3B

Schleicher 3B Sherman 4B

Scurry 3B Swisher 4B

Shackelford 3B Yoakum 4B

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 411

PDF Page 414

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Sterling 3B Utah (UT)

Stonewall 3B Zone 5B except…

Sutton 3B Washington 3B

Taylor 3B Daggett 6B

Terrell 3B Duchesne 6B

Terry 3B Morgan 6B

Throckmorton 3B Rich 6B

Tom Green 3B Summit 6B

Upton 3B Uintah 6B

Ward 3B Wasatch 6B

Wheeler 3B Vermont (VT)

Wilbarger 3B Zone 6A

Winkler 3B Virginia (VA)

Armstrong 4B Zone 4A except…

Bailey 4B Alleghany 5A

Briscoe 4B Bath 5A

Carson 4B Brunswick 3A

Castro 4B Chesapeake city 3A

Cochran 4B Clifton Forge city 5A

Dallam 4B Covington city 5A

Deaf Smith 4B Emporia city 3A

Donley 4B Franklin city 3A

Floyd 4B Greensville 3A

Gray 4B Halifax 3A

Hale 4B Hampton city 3A

Hansford 4B Highland 5A

Hartley 4B Isle of Wight 3A

Hockley 4B Mecklenburg 3A

Hutchinson 4B Newport News city 3A

Lamb 4B Norfolk city 3A

Lipscomb 4B Pittsylvania 3A

Moore 4B Portsmouth city 3A

Ochiltree 4B South Boston 3A

Oldham 4B Southampton 3A

Parmer 4B Suffolk city 3A

Potter 4B Surry 3A

Randall 4B Sussex 3A

Roberts 4B Virginia Beach city 3A

412 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 415

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Washington (WA) Mason 4A

Zone 5B except… McDowell 4A

Clark 4C Mercer 4A

Cowlitz 4C Mingo 4A

Grays Harbor 4C Monroe 4A

Jefferson 4C Morgan 4A

King 4C Nicholas 4A

Lewis 4C Pleasants 4A

Mason 4C Putnam 4A

Pacific 4C Raleigh 4A

Pierce 4C Ritchie 4A

Skagit 4C Roane 4A

Snohomish 4C Summers 4A

Thurston 4C Tyler 4A

Wahkiakum 4C Upshur 4A

Whatcom 4C Wayne 4A

Clallam 5C Webster 4A

Island 5C Wirt 4A

Kitsap 5C Wood 4A

San Juan 5C Wyoming 4A

Ferry 6B Wisconsin (WI)

Pend Oreille 6B Zone 6A except…

Stevens 6B Adams 5A

West Virginia (WV) Calumet 5A

Zone 5A except… Columbia 5A

Berkeley 4A Crawford 5A

Boone 4A Dane 5A

Braxton 4A Dodge 5A

Cabell 4A Fond du Lac 5A

Calhoun 4A Grant 5A

Clay 4A Green 5A

Doddridge 4A Green Lake 5A

Fayette 4A Iowa 5A

Gilmer 4A Jefferson 5A

Greenbrier 4A Juneau 5A

Jackson 4A Kenosha 5A

Jefferson 4A La Crosse 5A

Kanawha 4A Lafayette 5A

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 413

PDF Page 416

Open page note

Table Annex1-1 ASHRAE Standard 169-2013, Table B-1: U.S. Climate Zones by State and County (Continued)

State/County Zone State/County Zone

Lewis 4A Milwaukee 5A

Lincoln 4A Monroe 5A

Logan 4A Outagamie 5A

Ozaukee 5A Platte 5B

Racine 5A Lincoln 7

Richland 5A Sublette 7

Rock 5A Teton 7

Sauk 5A Commonwealth/Municipality Zone

Vernon 5A Puerto Rico (PR)

Walworth 5A Zone 1A except…

Washington 5A Barraquitas 2B

Waukesha 5A Cayey 2B

Waushara 5A Other Zone

Winnebago 5A Pacific Islands (PI)

Wyoming (WY) Zone 1A except…

Zone 6B except… Midway Sand Island 2A

Goshen 5B Virgin Islands (VI)

Laramie 5B Zone 1A

414 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 417

Open page note

PDF Page 418

Open page note

Table Annex1-2 ASHRAE Standard 169-2013, Table A-5: Canada Stations and Climate Zones

Precipitation

Precipitation

Province/LOCATION WMO# Lat Long CZ

mm in. Province/LOCATION WMO# Lat Long CZ mm in.

Alberta (AB) British Columbia (BC)

BANFF CS 711220 51.19 –115.55 7 487 19 ABBOTSFORD A 711080 49.03 –122.36 4C 1168 46

BOW ISLAND 712310 49.73 –111.45 6A 374 15 AGASSIZ CS 711130 49.25 –121.77 4C 1769 70

BOW VALLEY 712320 51.08 –115.07 7 584 23 ALERT BAY 711100 50.58 –126.93 5C 1668 66

BRETON PLOTS 712330 53.09 –114.44 7 460 18 AMPHITRITE POINT 711120 48.92 –125.54 5C 3212 126

BROOKS 714570 50.55 –111.85 6B 318 13 BALLENAS ISLAND 717690 49.35 –124.16 4C 981 39

CALGARY INT’L A 718770 51.11 –114.02 7 425 17 BLUE RIVER CS 718830 52.13 –119.29 6A 1032 41

CAMROSE 712540 53.03 –112.81 7 499 20 BONILLA ISLAND (AUT) 714840 53.50 –130.63 5C 2169 85

CARDSTON 711530 49.20 –113.29 6A 505 20 BURNS LAKE DECKER LAKE 719520 54.38 –125.96 7 503 20

CLARESHOLM 712340 50.00 –113.64 6A 433 17 CAPE SCOTT 711110 50.78 –128.43 5C 2296 90

COLD LAKE A 711200 54.42 –110.28 7 464 18 CAPE ST JAMES CS 711070 51.94 –131.02 5C 1599 63

COP UPPER 712350 51.08 –114.22 7 451 18 CATHEDRAL POINT (AUT) 714820 52.19 –127.47 5C 3439 135

CORONATION (AUT) 718730 52.08 –111.45 7 405 16 CLINTON (AUT) 714740 51.14 –121.50 7 392 15

CROWSNEST 712360 49.63 –114.48 7 664 26 COMOX A 718930 49.72 –124.90 5C 1340 53

DRUMHELLER EAST 712370 51.43 –112.67 7 390 15 CRANBROOK A 718800 49.61 –115.78 6A 408 16

EDMONTON CITY CENTRE A 718790 53.57 –113.52 7 481 19 CRESTON CAMPBELL SCIENTIFIC 717700 49.08 –116.50 5A 511 20

EDMONTON INT’L A 711230 53.32 –113.58 7 493 19 CUMSHEWA ISLAND 717710 53.03 –131.60 5C 2374 93

EDMONTON NAMAO A 711210 53.67 –113.47 7 457 18 DEASE LAKE 719580 58.43 –130.01 7 452 18

EDSON A 718810 53.60 –116.48 7 597 24 DISCOVERY ISLAND 710310 48.42 –123.23 4C 646 25

ELK ISLAND NAT PARK 712380 53.68 –112.87 7 442 17 ENTRANCE ISLAND CS 717720 49.22 –123.80 4C 1135 45

ESTHER 1 712400 51.67 –110.21 7 323 13 ESQUIMALT HARBOUR 717980 48.43 –123.44 4C 646 25

FORT CHIPEWYAN A 719330 58.77 –111.12 8 417 16 ESTEVAN POINT CS 718940 49.38 –126.54 5C 3276 129

FORT MCMURRAY A 719320 56.65 –111.22 7 476 19 FORT NELSON A 719450 58.84 –122.60 7 469 18

GARDEN RIVER 712530 58.71 –113.87 7 385 15 FORT ST JOHN A 719430 56.24 –120.74 7 477 19

GRANDE PRAIRIE A 719400 55.18 –118.88 7 477 19 GREY ISLET (AUT) 714760 54.58 –130.70 5A 2302 91

HIGH LEVEL A 710660 58.62 –117.16 8 441 17 HERBERT ISLAND (AUT) 714850 50.94 –127.64 5C 2155 85

HIGHVALE 712410 53.45 –114.47 7 458 18 HOLLAND ROCK 712190 54.17 –130.36 5C 2353 93

JASPER 718880 52.88 –118.07 7 415 16 HOPE 711140 49.37 –121.48 5C 1760 69

JASPER WARDEN 714860 52.93 –118.03 7 415 16 HOWE SOUND - PAM ROCKS 712110 49.49 –123.30 4C 1535 60

LAC LA BICHE (AUT) 729310 54.77 –112.02 7 457 18 KAMLOOPS A 718870 50.70 –120.44 5B 286 11

LACOMBE CDA 2 712420 52.45 –113.76 7 454 18 KELOWNA A 712030 49.96 –119.38 5A 471 19

LETHBRIDGE A 718740 49.63 –112.80 6A 425 17 KINDAKUN ROCKS (AUT) 714720 53.32 –132.77 5C 1981 78

LETHBRIDGE CDA 712430 49.70 –112.78 6A 425 17 LANGARA 718990 54.26 –133.06 5C 1952 77

LLOYDMINSTER A 718710 53.31 –110.07 7 426 17 LILLOOET 719990 50.68 –121.93 5A 392 15

MEDICINE HAT A 718720 50.02 –110.72 6B 347 14 LUCY ISLAND LIGHTSTATION 712200 54.30 –130.61 5C 2317 91

MILDRED LAKE 712550 57.04 –111.56 7 345 14 LYTTON 718910 50.22 –121.58 5C 455 18

MILK RIVER 712440 49.13 –112.05 6B 364 14 MACKENZIE A 719440 55.31 –123.14 7 687 27

NAKISKA RIDGETOP 712450 50.94 –115.19 8 605 24 MALAHAT 717740 48.57 –123.53 5C 1095 43

ONEFOUR CDA 711160 49.12 –110.47 6A 347 14 NAKUSP CS 712160 50.27 –117.81 5A 832 33

PEACE RIVER A 710680 56.23 –117.45 7 412 16 NELSON CS 717760 49.49 –117.31 5A 741 29

PINCHER CREEK (AUT) 718750 49.52 –113.98 6A 484 19 OSOYOOS CS 712150 49.03 –119.44 5B 319 13

RED DEER A 718780 52.18 –113.89 7 473 19 PEMBERTON AIRPORT CS 717770 50.30 –122.74 5C 850 33

RED EARTH 712460 56.55 –115.28 7 430 17 PENTICTON A 718890 49.46 –119.60 5B 303 12

ROCKY MTN HOUSE (AUT) 719280 52.42 –114.91 7 522 21 PITT MEADOWS CS 717750 49.21 –122.69 4C 1483 58

SLAVE LAKE A 710690 55.28 –114.78 7 525 21 POINT ATKINSON 710370 49.33 –123.26 4C 1535 60

SPRINGBANK A 718600 51.10 –114.37 7 491 19 PORT ALBERNI (AUT) 714750 49.32 –124.93 5C 1636 64

STAVELY AAFC 715550 50.18 –113.88 6A 472 19 PORT HARDY A 711090 50.68 –127.37 5C 1917 75

SUNDRE A 712480 51.78 –114.68 7 464 18 PRINCE GEORGE A 718960 53.89 –122.68 7 658 26

THREE HILLS 712490 51.83 –113.21 7 407 16 PRINCE RUPERT A 718980 54.29 –130.44 5C 2690 106

VAUXHALL CDA CS 712510 50.05 –112.13 6B 351 14 PRINCETON CS 710320 49.47 –120.51 6A 369 15

VEGREVILLE 714580 53.51 –112.10 7 375 15 PUNTZI MOUNTAIN (AUT) 710500 52.11 –124.14 7 394 16

WAINWRIGHT CFB AIRFIELD 21 711180 52.83 –111.10 7 431 17 QUESNEL A 711030 53.03 –122.51 6A 554 22

WATERTON PARK GATE 711540 49.13 –113.81 6A 551 22 REVELSTOKE A 718820 50.96 –118.18 6A 1018 40

WHITECOURT A 719300 54.14 –115.79 7 594 23 ROSE SPIT (AUT) 714770 54.16 –131.66 5A 1434 56

416 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 419

Open page note

Table Annex1-2 ASHRAE Standard 169-2013, Table A-5: Canada Stations and Climate Zones (Continued)

Precipitation

Precipitation

Province/LOCATION WMO# Lat Long CZ

mm in. Province/LOCATION WMO# Lat Long CZ mm in.

SALMON ARM CS 712180 50.70 –119.29 5A 458 18 VICTORIA BEACH (AUT) 715520 50.70 –96.57 7 489 19

SANDHEADS CS 712090 49.11 –123.30 4C 1082 43 WASAGAMING 714440 50.66 –99.94 7 528 21

SANDSPIT A 711010 53.25 –131.81 5C 1323 52 WILSON CREEK WEIR CS 711490 50.71 –99.53 7 536 21

SARTINE ISLAND (AUT) 714780 50.82 –128.91 5C 1920 76 WINNIPEG RICHARDSON INT’L A 718520 49.92 –97.23 7 523 21

SHERINGHAM POINT 717800 48.38 –123.92 5C 1497 59 New Brunswick (NB)

SISTERS ISLAND 717810 49.49 –124.43 4C 1103 43 BAS CARAQUET 715980 47.80 –64.83 6A 1049 41

SMITHERS A 719500 54.82 –127.18 7 539 21 CHARLO A 717110 47.98 –66.33 7 1112 44

SOLANDER ISLAND (AUT) 714790 50.11 –127.94 5C 2375 94 FREDERICTON A 717000 45.87 –66.53 6A 1151 45

SPARWOOD CS 717820 49.75 –114.89 7 1021 40 MIRAMICHI A 717170 47.01 –65.47 7 1090 43

SQUAMISH 712070 49.78 –123.16 5C 2294 90 MIRAMICHI RCS 717440 47.01 –65.46 6A 1090 43

SUMMERLAND CS 717680 49.56 –119.64 5B 321 13 MISCOU ISLAND (AUT) 717190 48.01 –64.49 7 1037 41

TERRACE A 719510 54.47 –128.58 6A 1378 54 MONCTON A 717050 46.10 –64.69 6A 1290 51

VANCOUVER HARBOUR CS 712010 49.30 –123.12 4C 1517 60 POINT ESCUMINAC (AUT) 714140 47.07 –64.80 6A 1133 45

VANCOUVER INT’L A 718920 49.20 –123.18 4C 1209 48 POINT LEPREAU CS 716990 45.07 –66.45 6A 1253 49

VERNON CS 711150 50.22 –119.19 5A 453 18 SAINT JOHN A 716090 45.32 –65.89 6A 1317 52

VICTORIA GONZALES CS 712000 48.41 –123.33 4C 646 25 ST LEONARD CS 710190 47.16 –67.83 7 997 39

VICTORIA HARTLAND CS 710380 48.53 –123.46 4C 948 37 ST STEPHEN (AUT) 716070 45.22 –67.25 6A 1149 45

VICTORIA INT’L A 717990 48.65 –123.43 5C 948 37 Newfoundland And Labrador (NL)

VICTORIA MARINE 712020 48.37 –123.75 5C 1265 50 ARGENTIA (AUT) 718070 47.29 –53.99 6A 1304 51

VICTORIA UNIVERSITY CS 717830 48.46 –123.30 4C 646 25 BADGER (AUT) 714000 48.97 –56.07 7 1072 42

WEST VANCOUVER AUT 717840 49.35 –123.19 4C 1517 60 BONAVISTA 711960 48.67 –53.11 6A 1068 42

WHITE ROCK CAMPBELL SCIENTIFI

717850 49.02 –122.78 4C 1049 41 BURGEO 2 711940 47.62 –57.62 6A 1818 72

WILLIAMS LAKE A 711040 52.18 –122.05 7 451 18 CAPE KAKKIVIAK 711760 59.98 –64.16 8 376 15

YOHO PARK 717860 51.44 –116.34 7 541 21 CAPE RACE (AUT) 718000 46.66 –53.08 6A 1378 54

Manitoba (MB) CARTWRIGHT 718180 53.71 –57.04 7 1060 42

BERENS RIVER CS 711580 52.36 –97.02 7 475 19 CHURCHILL FALLS 711820 53.56 –64.09 8 999 39

BRANDON A 711400 49.91 –99.95 7 471 19 COMFORT COVE 711930 49.27 –54.88 7 1213 48

CARBERRY CS 711700 49.91 –99.36 7 523 21 CORNER BROOK 719730 48.93 –57.92 6A 1222 48

CARMAN U OF M CS 711470 49.50 –98.03 7 527 21 DANIELS HARBOUR 711850 50.24 –57.58 7 1164 46

CHURCHILL A 719130 58.74 –94.06 8 449 18 DEER LAKE A 718090 49.22 –57.40 7 1105 44

DAUPHIN A 718550 51.10 –100.05 7 513 20 ENGLEE (AUT) 714170 50.72 –56.11 7 1022 40

DELTA MARSH CS 715630 50.18 –98.38 7 530 21 FEROLLE POINT (AUT) 714060 51.02 –57.10 7 1185 47

EMERSON AUT 715600 49.00 –97.24 7 488 19 GANDER INT’L A 718030 48.95 –54.58 7 1255 49

FISHER BRANCH (AUT) 714420 51.08 –97.55 7 562 22 GOOSE A 718160 53.32 –60.42 7 996 39

GEORGE ISLAND (AUT) 714450 52.82 –97.62 7 449 18 GRATES COVE 713360 48.17 –52.94 6A 1408 55

GILLAM A 719120 56.36 –94.71 8 518 20 HOPEDALE (AUT) 719000 55.45 –60.22 8 884 35

GIMLI INDUSTRIAL PARK 718560 50.63 –97.05 7 500 20 LA SCIE 713370 49.92 –55.67 7 1293 51

GRAND RAPIDS (AUT) 718580 53.19 –99.27 7 485 19 MARTICOT ISLAND 716920 47.33 –54.59 6A 1395 55

GRETNA (AUT) 714410 49.03 –97.56 7 512 20 POOLS ISLAND 719310 49.11 –53.58 6A 1015 40

HUNTERS POINT MARINE 711420 53.03 –100.93 7 462 18 PORT AUX BASQUES 711970 47.57 –59.15 7 1563 62

ISLAND LAKE A 711450 53.85 –94.65 7 581 23 SAGLEK 713350 58.33 –62.59 8 836 33

LYNN LAKE A 710780 56.86 –101.08 8 535 21 SAGONA ISLAND 714080 47.37 –55.79 6A 1574 62

MELITA 714470 49.28 –100.99 7 446 18 ST ANTHONY 715580 51.38 –56.10 7 1183 47

NORWAY HOUSE A 711410 53.95 –97.85 7 530 21 ST JOHN’S A 718010 47.62 –52.74 6A 1547 61

OAKPOINT MARINE 711440 50.50 –98.04 7 532 21 ST LAWRENCE 718020 46.92 –55.38 6A 1603 63

PILOT MOUND (AUT) 711480 49.19 –98.90 7 487 19 STEPHENVILLE A 718150 48.53 –58.55 6A 1364 54

PINAWA 714480 50.18 –96.06 7 435 17 TWILLINGATE (AUT) 714020 49.68 –54.80 7 1015 40

PORTAGE SOUTHPORT A 718510 49.90 –98.27 7 515 20 WABUSH LAKE A 718250 52.93 –66.87 8 936 37

ROBLIN 715530 51.18 –101.36 7 466 18 Nova Scotia (NS)

SHOAL LAKE CS 711500 50.45 –100.60 7 504 20 AMHERST (AUT) 714100 45.85 –64.27 6A 1212 48

SPRAGUE 714490 49.02 –95.60 7 622 24 BACCARO POINT 716910 43.45 –65.47 6A 1258 50

SWAN RIVER RCS 714430 52.12 –101.23 7 468 18 BEAVER ISLAND (AUT) 714030 44.82 –62.33 6A 1472 58

THE PAS A 718670 53.97 –101.10 7 470 18 BRIER ISLAND 719880 44.29 –66.35 6A 1202 47

THOMPSON A 710790 55.80 –97.86 8 520 20 CARIBOU POINT (AUT) 714150 45.77 –62.68 6A 1063 42

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 417

PDF Page 420

Open page note

Table Annex1-2 ASHRAE Standard 169-2013, Table A-5: Canada Stations and Climate Zones (Continued)

Precipitation

Precipitation

Province/LOCATION WMO# Lat Long CZ

mm in. Province/LOCATION WMO# Lat Long CZ mm in.

GRAND ETANG 715970 46.55 –61.05 6A 1202 47 CROKER RIVER 710590 69.28 –119.22 8 183 7

GREENWOOD A 713970 44.98 –64.92 6A 1253 49 DEWAR LAKES 710920 68.65 –71.17 8 248 10

HALIFAX STANFIELD INT’L A 713950 44.88 –63.52 6A 1532 60 ENNADAI LAKE (AUT) 719230 61.13 –100.88 8 326 13

HART ISLAND (AUT) 714190 45.35 –60.98 6A 1464 58 EUREKA 719170 79.98 –85.93 8 76 3

KEJIMKUJIK 1 715990 44.43 –65.20 6A 1438 57 FOX FIVE 710960 67.54 –63.79 8 289 11

SABLE ISLAND 716000 43.93 –60.01 5A 1392 55 GLADMAN POINT A 719270 68.67 –97.80 8 125 5

SHEARWATER A 716010 44.63 –63.50 6A 1414 56 HALL BEACH A 710810 68.78 –81.24 8 235 9

SHEARWATER JETTY CAN35X 44.63 –63.52 5A 1414 56 HAT ISLAND 710840 68.32 –100.09 8 204 8

ST PAUL ISLAND (AUT) 714180 47.23 –60.14 6A 1391 55 IQALUIT A 719090 63.75 –68.55 8 422 17

SYDNEY A 717070 46.17 –60.05 6A 1523 60 JENNY LIND ISLAND A 710710 68.65 –101.73 8 116 5

WESTERN HEAD 714110 43.99 –64.66 6A 1405 55 KUGLUKTUK A 719380 67.82 –115.14 8 263 10

YARMOUTH A 716030 43.83 –66.09 6A 1305 51 LADY FRANKLIN POINT A 719370 68.50 –113.22 8 121 5

Northwest Territories (NT) LONGSTAFF BLUFF 710910 68.90 –75.14 8 212 8

AULAVIK NATIONAL PARK 719740 74.14 –119.99 8 116 5 MACKAR INLET 710800 68.30 –85.67 8 187 7

CAPE PARRY A 719480 70.17 –124.72 8 154 6 PANGNIRTUNG 718260 66.15 –65.72 8 427 17

COLVILLE LAKE 710550 67.04 –126.08 8 317 12 PELLY BAY 719190 68.43 –89.72 8 240 9

FORT GOOD HOPE CS 714910 66.24 –128.64 8 317 12 POND INLET A 710950 72.68 –77.98 8 196 8

FORT LIARD 714970 60.23 –123.47 8 435 17 RANKIN INLET A 710830 62.82 –92.12 8 324 13

FORT PROVIDENCE 710870 61.32 –117.60 8 266 10 RESOLUTE CARS 719240 74.72 –94.99 8 152 6

FORT RELIANCE 710730 62.72 –109.17 8 283 11 RESOLUTION ISLAND 719720 61.60 –64.63 8 364 14

FORT SIMPSON A 719460 61.76 –121.24 8 376 15 ROBERTSON LAKE (AUT) 714900 65.10 –102.43 8 256 10

FORT SMITH A 719340 60.02 –111.96 8 373 15 SHEPHERD BAY A 719110 68.82 –93.43 8 155 6

HANBURY RIVER 719630 63.60 –105.13 8 275 11 Ontario (ON)

HAY RIVER A 719350 60.84 –115.78 8 373 15 ARMSTRONG (AUT) 718410 50.29 –88.91 7 737 29

INNER WHALEBACKS 711620 61.92 –113.73 8 283 11 ATIKOKAN (AUT) 717470 48.76 –91.63 7 798 31

INUVIK A 719570 68.30 –133.48 8 267 11 BANCROFT AUTO 712940 45.07 –77.88 7 873 34

LAC LA MARTRE 711630 63.13 –117.25 8 265 10 BEAUSOLEIL 712720 44.85 –79.87 6A 934 37

LINDBURG LANDING 716820 61.12 –122.85 8 399 16 BELLE RIVER 712730 42.30 –82.70 5A 804 32

LITTLE CHICAGO 711640 67.18 –130.23 8 310 12 BIG TROUT LAKE 718480 53.83 –89.87 8 582 23

LIVERPOOL BAY 719600 69.60 –130.91 8 130 5 BIG TROUT LAKE READAC 718440 53.82 –89.90 8 582 23

MOULD BAY A 710720 76.23 –119.33 8 114 4 BURLINGTON PIERS (AUT) 714370 43.30 –79.80 5A 827 33

NICHOLSON PENINSULA 719560 69.93 –128.97 8 107 4 COBOURG (AUT) 714310 43.95 –78.17 6A 808 32

NORMAN WELLS A 710430 65.28 –126.80 8 336 13 COLLINGWOOD 712700 44.50 –80.22 6A 766 30

PELLY ISLAND 715020 69.63 –135.44 8 194 8 COVE ISLAND (AUT) 714390 45.33 –81.73 6A 869 34

RAE LAKES 711650 64.11 –117.33 8 260 10 EARLTON A 717350 47.70 –79.85 7 801 32

SACHS HARBOUR CLIMATE 714670 71.99 –125.25 8 134 5 ERIEAU (AUT) 714650 42.25 –81.90 5A 797 31

TROUT LAKE 711660 60.44 –121.24 8 405 16 GERALDTON A 718340 49.78 –86.93 7 774 30

TUKTOYAKTUK 719850 69.43 –133.02 8 136 5 GODERICH 712610 43.77 –81.72 5A 981 39

YELLOWKNIFE A 719360 62.46 –114.44 8 287 11 GORE BAY A 717330 45.88 –82.57 6A 834 33

YOHIN 710200 61.24 –123.74 8 413 16 GREAT DUCK ISLAND (AUT) 714620 45.63 –82.95 6A 809 32

Nunavut (NU) GRENADIER ISLAND 712810 44.42 –75.85 6A 947 37

ALERT 710820 82.52 –62.28 8 172 7 KAPUSKASING A 718310 49.41 –82.47 7 891 35

BAKER LAKE A 719260 64.30 –96.08 8 272 11 KENORA A 718500 49.79 –94.37 7 674 27

BREVOORT ISLAND 710970 63.34 –64.15 8 624 25 KILLARNEY (AUT) 714600 45.97 –81.48 6A 839 33

BYRON BAY A 719290 68.75 –109.07 8 121 5 LAGOON CITY 712820 44.55 –79.22 6A 929 37

CAMBRIDGE BAY A 719250 69.11 –105.14 8 149 6 LANSDOWNE HOUSE (AUT) 718460 52.20 –87.94 7 719 28

CAPE DORSET A 719100 64.23 –76.53 8 402 16 LONDON INT’L AIRPORT 716230 43.03 –81.15 5A 981 39

CAPE DYER 710940 66.65 –61.38 8 627 25 LONG POINT (AUT) 714640 42.57 –80.05 5A 948 37

CAPE HOOPER 710930 68.47 –66.82 8 265 10 MOOSONEE A 718360 51.29 –80.61 7 722 28

CAPE MERCY 719750 64.96 –63.58 8 467 18 MOUNT FOREST (AUT) 716310 43.98 –80.75 6A 969 38

CAPE PEEL WEST 710640 69.04 –107.82 8 133 5 NAGAGAMI (AUT) 718320 49.75 –84.16 7 793 31

CLINTON POINT 710530 69.58 –120.80 8 161 6 NORTH BAY A 717310 46.36 –79.42 7 1012 40

CLYDE A 710900 70.49 –68.52 8 239 9 OTTAWA MACDONALD-CARTIER INT’

716280 45.32 –75.67 6A 922 36

CORAL HARBOUR A 719150 64.19 –83.36 8 299 12 PEAWANUCK (AUT) 714340 54.98 –85.43 8 602 24

418 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 421

Open page note

Table Annex1-2 ASHRAE Standard 169-2013, Table A-5: Canada Stations and Climate Zones (Continued)

Precipitation

Precipitation

Province/LOCATION WMO# Lat Long CZ

mm in. Province/LOCATION WMO# Lat Long CZ mm in.

PETAWAWA A 716250 45.95 –77.32 7 851 34 INUKJUAK A 719070 58.47 –78.08 8 457 18

PETERBOROUGH A 716290 44.23 –78.37 6A 843 33 JONQUIERE 716170 48.42 –71.15 7 948 37

PICKLE LAKE (AUT) 718350 51.45 –90.22 7 726 29 KUUJJUAQ A 719060 58.10 –68.42 8 520 20

POINT PETRE (AUT) 714300 43.83 –77.15 6A 965 38 KUUJJUARAPIK A 719050 55.28 –77.75 8 667 26

PORT COLBORNE (AUT) 714630 42.87 –79.25 5A 986 39 LA BAIE 713880 48.30 –70.92 7 966 38

PORT WELLER (AUT) 714320 43.25 –79.22 5A 890 35 LA GRANDE IV A 718230 53.76 –73.68 8 773 30

PUKASKWA (AUT) 717500 48.59 –86.29 7 865 34 LA GRANDE RIVIERE A 718270 53.63 –77.70 8 683 27

RED LAKE A 718540 51.07 –93.79 7 668 26 LA POCATIERE 717130 47.36 –70.03 6A 963 38

ROYAL ISLAND (AUT) CAN21X 49.47 –94.76 7 613 24 LA TUQUE 713780 47.41 –72.79 7 959 38

SAULT STE MARIE A 712600 46.48 –84.51 6A 932 37 LAC BENOIT 715200 51.53 –71.11 8 925 36

SIOUX LOOKOUT A 718420 50.12 –91.90 7 739 29 LAC EON 714210 51.87 –63.28 8 1058 42

SUDBURY A 717300 46.62 –80.80 7 917 36 LAC SAINT-PIERRE 711980 46.18 –72.92 6A 993 39

THUNDER BAY A 717490 48.37 –89.33 7 731 29 L’ACADIE 713720 45.29 –73.35 6A 1021 40

TIMMINS VICTOR POWER A 717390 48.57 –81.38 7 921 36 L’ASSOMPTION 715240 45.81 –73.43 6A 999 39

TORONTO BUTTONVILLE A 716390 43.86 –79.37 6A 781 31 LENNOXVILLE 716110 45.37 –71.82 6A 1095 43

TORONTO ISLAND A 712650 43.63 –79.40 5A 848 33 L’ETAPE 713820 47.56 –71.23 7 1261 50

TORONTO LESTER B. PEARSON INT

716240 43.68 –79.63 5A 785 31 LONGUE-POINTE-DE-MINGAN 715120 50.27 –64.23 7 1108 44

TRENTON A 716210 44.12 –77.53 6A 858 34 MANIWAKI AIRPORT 717210 46.27 –75.99 7 966 38

UPSALA (AUT) 714350 49.03 –90.47 7 715 28 MANIWAKI UA 717220 46.30 –76.01 7 928 37

WAWA (AUT) 717380 47.97 –84.78 7 906 36 MANOUANE EST 715210 50.66 –70.53 8 908 36

WELCOME ISLAND (AUT) 717510 48.37 –89.12 7 659 26 MATAGAMI A 718210 49.77 –77.80 7 838 33

WIARTON A 716330 44.75 –81.11 6A 1049 41 MCTAVISH 716120 45.50 –73.58 6A 1096 43

WINDSOR A 715380 42.28 –82.96 5A 920 36 MISTOOK 713810 48.60 –71.72 7 942 37

Prince Edward Island (PE) MONT-JOLI A 717180 48.60 –68.22 7 969 38

CHARLOTTETOWN A 717060 46.29 –63.13 6A 1217 48 MONT-ORFORD 716180 45.31 –72.24 7 1082 43

EAST POINT (AUT) 714120 46.46 –61.99 6A 1285 51 MONTREAL/MIRABEL INT’L A 716260 45.67 –74.03 6A 1024 40

NORTH CAPE 719870 47.06 –64.00 6A 1103 43 MONTREAL/PIERRE ELLIOTT TRUDE

716270 45.47 –73.75 6A 988 39

SUMMERSIDE 717020 46.44 –63.84 6A 1077 42 MONTREAL/ST-HUBERT A 713710 45.52 –73.42 6A 1027 40

Quebec (QC) MONTREAL-EST 716750 45.63 –73.55 6A 1013 40

AMQUI 713860 48.47 –67.43 7 1028 40 NATASHQUAN A 718130 50.18 –61.82 7 1182 47

BAGOTVILLE A 717270 48.33 –71.00 7 966 38 NEW CARLISLE 1 716190 48.01 –65.33 7 1015 40

BAIE-COMEAU 718290 49.26 –68.15 7 981 39 NICOLET 717230 46.23 –72.66 6A 1026 40

BAIE-COMEAU A 711870 49.13 –68.20 7 1045 41 NORMANDIN 713790 48.84 –72.55 7 913 36

BARRAGE TEMISCAMINGUE 717320 46.71 –79.10 6A 956 38 ONATCHIWAY 713870 48.89 –71.03 7 937 37

BEAUCEVILLE 713230 46.20 –70.78 7 1127 44 PARENT 717260 47.92 –74.62 7 1015 40

BLANC-SABLON A 718080 51.45 –57.18 7 1091 43 POINTE CLAVEAU 711890 48.26 –70.11 7 995 39

BONNARD 1 713830 50.73 –71.01 7 1006 40 POINTE NOIRE CS 713900 50.16 –66.43 7 1119 44

CAP-CHAT 714280 49.11 –66.65 7 928 37 POINTE-AU-PERE (INRS) 715540 48.51 –68.47 7 888 35

CAP-D’ESPOIR 714290 48.42 –64.32 7 1089 43 POINTE-DES-MONTS 714270 49.32 –67.38 7 982 39

CAP-MADELEINE 714250 49.25 –65.32 7 897 35 PORT-MENIER 718100 49.84 –64.29 7 1047 41

CAP-ROUGE 711860 48.37 –70.54 7 944 37 QUEBEC/JEAN LESAGE INTL A 717080 46.80 –71.38 7 1266 50

CAP-TOURMENTE 713840 47.08 –70.78 6A 1104 43 RIVIERE-DU-LOUP 717150 47.81 –69.55 7 981 39

CHARLEVOIX (MRC) 713190 47.28 –70.64 7 1103 43 ROBERVAL A 717280 48.52 –72.27 7 872 34

CHEVERY 718140 50.46 –59.64 7 1161 46 ROUYN 717340 48.25 –79.03 7 865 34

CHIBOUGAMAU CHAPAIS A 718220 49.77 –74.53 7 969 38 ROUYN A 717400 48.22 –78.83 7 882 35

CHUTE-DES-PASSES 715220 49.84 –71.17 7 1091 43 SCHEFFERVILLE A 718280 54.80 –66.82 8 784 31

DESCHAMBAULT 713890 46.69 –71.97 7 1134 45 SEPT-ILES A 718110 50.22 –66.27 7 1173 46

FRELIGHSBURG 713730 45.05 –72.86 6A 1180 46 SHERBROOKE A 716100 45.43 –71.68 7 1162 46

GASPE A 711880 48.78 –64.48 7 1048 41 ST-ANICET 1 717120 45.12 –74.29 6A 968 38

HAVRE-SAINT-PIERRE A 713130 50.28 –63.60 7 1094 43 STE AGATHE DES MONTS 717200 46.05 –74.28 7 1236 49

HEATH POINT 714230 49.09 –61.70 7 1030 41 STE-ANNE-DE-BELLEVUE 1 713770 45.43 –73.93 6A 958 38

ILE AUX PERROQUETS 713750 50.22 –64.21 7 1099 43 STE-CLOTHILDE 716140 45.17 –73.68 6A 925 36

ILE ROUGE 714260 48.07 –69.56 7 998 39 STE-FOY (U. LAVAL) 713920 46.78 –71.29 6A 1266 50

ILES DE LA MADELEINE 717100 47.43 –61.77 6A 1049 41 ST-JOVITE 713760 46.08 –74.56 7 1130 44

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 419

PDF Page 422

Open page note

Table Annex1-2 ASHRAE Standard 169-2013, Table A-5: Canada Stations and Climate Zones (Continued)

Precipitation

Precipitation

Province/LOCATION WMO# Lat Long CZ

mm in. Province/LOCATION WMO# Lat Long CZ mm in.

TROIS-RIVIERES 717240 46.35 –72.52 6A 1024 40 ROCKGLEN (AUT) 711350 49.17 –105.98 7 335 13

VAL-D’OR A 717250 48.06 –77.79 7 981 39 ROSETOWN EAST 715100 51.57 –107.92 7 347 14

VARENNES 711840 45.72 –73.38 6A 1027 40 SASKATOON DIEFENBAKER  INT’L A

718660 52.17 –106.72 7 364 14

Saskatchewan (SK) SASKATOON KERNEN FARM 715130 52.15 –106.55 7 364 14

ASSINIBOIA AIRPORT 714870 49.73 –105.93 7 400 16 SCOTT CDA 714890 52.36 –108.83 7 388 15

BROADVIEW 718610 50.37 –102.57 7 416 16 SOUTHEND 714510 56.33 –103.28 8 535 21

COLLINS BAY 710750 58.18 –103.70 8 546 21 SPIRITWOOD WEST 711330 53.37 –107.55 7 417 16

CORONACH SPC 715160 49.05 –105.48 7 338 13 STONY RAPIDS A 711320 59.25 –105.83 8 429 17

CREE LAKE 719200 57.35 –107.13 8 476 19 SWIFT CURRENT A 718700 50.30 –107.68 7 389 15

CYPRESS HILLS PARK 711390 49.65 –109.52 7 346 14 SWIFT CURRENT CDA 714460 50.27 –107.73 7 389 15

EASTEND CYPRESS (AUT) 711310 49.43 –108.98 7 386 15 URANIUM CITY (AUT) 710760 59.57 –108.48 8 379 15

ELBOW CS 714500 51.13 –106.58 7 325 13 VAL MARIE SOUTHEAST 711370 49.07 –107.58 7 295 12

ESTEVAN A 718620 49.22 –102.97 7 434 17 WASKESIU LAKE 714540 53.92 –106.07 7 414 16

HUDSON BAY 718680 52.82 –102.32 7 479 19 WATROUS EAST 715110 51.67 –105.40 7 379 15

INDIAN HEAD CDA 715150 50.55 –103.65 7 444 17 WEYBURN 714520 49.70 –103.80 7 391 15

KEY LAKE A 714880 57.25 –105.60 8 493 19 WYNYARD (AUT) 718650 51.77 –104.20 7 429 17

KINDERSLEY A 711290 51.52 –109.18 7 324 13 YORKTON A 711380 51.27 –102.47 7 457 18

LA RONGE A 719220 55.15 –105.27 7 501 20 Yukon (YT)

LAST MOUNTAIN CS 715560 51.42 –105.25 7 384 15 BURWASH A 719670 61.37 –139.05 8 302 12

LEADER AIRPORT 714590 50.90 –109.50 7 365 14 FARO (AUT) 719490 62.23 –133.35 8 275 11

LUCKY LAKE 714550 50.95 –107.15 7 342 13 HAINES JUNCTION 715050 60.77 –137.58 8 334 13

MAPLE CREEK 714530 49.90 –109.47 6A 371 15 HERSCHEL ISLAND 715010 69.57 –138.91 8 188 7

MEADOW LAKE A 711250 54.13 –108.52 7 431 17 IVVAVIK NAT. PARK 719780 69.16 –140.15 8 176 7

MELFORT 714560 52.82 –104.60 7 416 16 KOMAKUK BEACH 710460 69.61 –140.20 8 168 7

MOOSE JAW A 718640 50.33 –105.55 7 375 15 MAYO A 719650 63.62 –135.87 8 329 13

MOOSE JAW CS 715390 50.33 –105.56 7 375 15 ROCK RIVER 715060 66.98 –136.22 8 337 13

NIPAWIN A 711300 53.33 –104.00 7 453 18 SHINGLE POINT A 719680 68.95 –137.22 8 260 10

NORTH BATTLEFORD A 718760 52.77 –108.26 7 391 15 TESLIN (AUT) 710450 60.17 –132.73 8 340 13

OUTLOOK PFRA 715510 51.48 –107.05 7 350 14 WATSON LAKE A 719530 60.12 –128.82 8 436 17

PRINCE ALBERT A 718690 53.22 –105.67 7 426 17 WHITEHORSE A 719640 60.71 –135.07 7 281 11

REGINA A 718630 50.43 –104.67 7 395 16

420 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 423

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Albania (ALB)
TIRANA
136150
41.33
19.78
3A
1234
49
HALLEY
890220
–75.50
–26.65
8
307
12
MANUELA
898640
–74.95
163.69
8
350
14
MARBLE POINT
898660
–77.43
163.75
8
190
7
MAWSON
895640
–67.60
62.87
8
307
12
MIRNYJ
895920
–66.55
93.02
8
745
29
MOLODEZNAJA
895420
–67.67
45.85
8
529
21
MOUNT SIPLE
893270
–73.20
–127.05
8
504
20
NEUMAYER
890020
–70.67
–8.25
8
394
16
NOVOLAZAREVSKAJA
895120
–70.77
11.83
8
354
14
POSSESSION ISLAND
898790
–71.89
171.21
8
453
18
SIPLE DOME
893450
–81.65
–148.77
8
285
11
SYOWA
895320
–69.00
39.58
8
449
18
Algeria (DZA)
ADRAR
606200
27.88
–0.18
1B
14
1
ANNABA
603600
36.83
7.82
3A
630
25
BATNA
604680
35.75
6.32
3B
362
14
BECHAR
605710
31.50
–2.25
2B
87
3
BEJAIA-AEROPORT
604020
36.72
5.07
3A
776
31
BISKRA
605250
34.80
5.73
2B
110
4
BORDJ-BOU-ARRERIDJ
604440
36.07
4.77
3B
420
17
CONSTANTINE
604190
36.28
6.62
3A
516
20
DAR-EL-BEIDA
603900
36.68
3.22
3A
701
28
DJANET
606700
24.27
9.47
2B
21
1
EL-BAYADH
605500
33.67
1.00
4B
269
11
EL-GOLEA
605900
30.57
2.87
2B
37
1
EL-OUED
605590
33.50
6.78
2B
71
3
GHARDAIA
605660
32.40
3.80
2B
65
3
HASSI-MESSAOUD
605810
31.67
6.15
2B
40
2
ILLIZI
606400
26.50
8.42
1B
18
1
IN-AMENAS
606110
28.05
9.63
2B
25
1
IN-SALAH
606300
27.23
2.50
0B
12
0
JIJEL-ACHOUAT
603510
36.80
5.88
3A
943
37
MASCARA-MATEMORE
605060
35.60
0.30
3A
443
17
MECHERIA
605490
33.58
–0.28
3B
231
9
ORAN-SENIA
604900
35.63
–0.60
3A
368
15
OUARGLA
605800
31.93
5.40
2B
50
2
SETIF
604450
36.18
5.25
4A
492
19
SKIKDA
603550
36.88
6.90
3A
734
29
TAMANRASSET
606800
22.80
5.43
2B
40
2
TAMANRASSET
606805
22.80
5.45
2B
40
2
TEBESSA
604750
35.42
8.12
3B
369
15
TIARET
605110
35.35
1.47
3B
355
14
TINDOUF
606560
27.70
–8.17
1B
51
2
TLEMCEN-ZENATA
605310
35.02
–1.47
3A
468
18
TOUGGOURT
605550
33.12
6.13
2B
58
2
Algeria (DZA)
ADRAR
606200
27.88
–0.18
1B
14
1
ANNABA
603600
36.83
7.82
3A
630
25
BATNA
604680
35.75
6.32
3B
362
14
BECHAR
605710
31.50
–2.25
2B
87
3
BEJAIA-AEROPORT
604020
36.72
5.07
3A
776
31
BISKRA
605250
34.80
5.73
2B
110
4
BORDJ-BOU-ARRERIDJ
604440
36.07
4.77
3B
420
17
CONSTANTINE
604190
36.28
6.62
3A
516
20
DAR-EL-BEIDA
603900
36.68
3.22
3A
701
28
DJANET
606700
24.27
9.47
2B
21
1
EL-BAYADH
605500
33.67
1.00
4B
269
11
EL-GOLEA
605900
30.57
2.87
2B
37
1
EL-OUED
605590
33.50
6.78
2B
71
3
GHARDAIA
605660
32.40
3.80
2B
65
3
HASSI-MESSAOUD
605810
31.67
6.15
2B
40
2
ILLIZI
606400
26.50
8.42
1B
18
1
IN-AMENAS
606110
28.05
9.63
2B
25
1
IN-SALAH
606300
27.23
2.50
0B
12
0
JIJEL-ACHOUAT
603510
36.80
5.88
3A
943
37
MASCARA-MATEMORE
605060
35.60
0.30
3A
443
17
MECHERIA
605490
33.58
–0.28
3B
231
9
ORAN-SENIA
604900
35.63
–0.60
3A
368
15
OUARGLA
605800
31.93
5.40
2B
50
2
SETIF
604450
36.18
5.25
4A
492
19
SKIKDA
603550
36.88
6.90
3A
734
29
TAMANRASSET
606800
22.80
5.43
2B
40
2
TAMANRASSET
606805
22.80
5.45
2B
40
2
TEBESSA
604750
35.42
8.12
3B
369
15
TIARET
605110
35.35
1.47
3B
355
14
TINDOUF
606560
27.70
–8.17
1B
51
2
TLEMCEN-ZENATA
605310
35.02
–1.47
3A
468
18
TOUGGOURT
605550
33.12
6.13
2B
58
2
Algeria (DZA)
ADRAR
606200
27.88
–0.18
1B
14
1
ANNABA
603600
36.83
7.82
3A
630
25
BATNA
604680
35.75
6.32
3B
362
14
BECHAR
605710
31.50
–2.25
2B
87
3
BEJAIA-AEROPORT
604020
36.72
5.07
3A
776
31
BISKRA
605250
34.80
5.73
2B
110
4
BORDJ-BOU-ARRERIDJ
604440
36.07
4.77
3B
420
17
CONSTANTINE
604190
36.28
6.62
3A
516
20
DAR-EL-BEIDA
603900
36.68
3.22
3A
701
28
DJANET
606700
24.27
9.47
2B
21
1
EL-BAYADH
605500
33.67
1.00
4B
269
11
EL-GOLEA
605900
30.57
2.87
2B
37
1
EL-OUED
605590
33.50
6.78
2B
71
3
GHARDAIA
605660
32.40
3.80
2B
65
3
HASSI-MESSAOUD
605810
31.67
6.15
2B
40
2
ILLIZI
606400
26.50
8.42
1B
18
1
IN-AMENAS
606110
28.05
9.63
2B
25
1
IN-SALAH
606300
27.23
2.50
0B
12
0
JIJEL-ACHOUAT
603510
36.80
5.88
3A
943
37
MASCARA-MATEMORE
605060
35.60
0.30
3A
443
17
MECHERIA
605490
33.58
–0.28
3B
231
9
ORAN-SENIA
604900
35.63
–0.60
3A
368
15
OUARGLA
605800
31.93
5.40
2B
50
2
SETIF
604450
36.18
5.25
4A
492
19
SKIKDA
603550
36.88
6.90
3A
734
29
TAMANRASSET
606800
22.80
5.43
2B
40
2
TAMANRASSET
606805
22.80
5.45
2B
40
2
TEBESSA
604750
35.42
8.12
3B
369
15
TIARET
605110
35.35
1.47
3B
355
14
TINDOUF
606560
27.70
–8.17
1B
51
2
TLEMCEN-ZENATA
605310
35.02
–1.47
3A
468
18
TOUGGOURT
605550
33.12
6.13
2B
58
2
Antigua and Barbuda (ATG)
VC BIRD INTL AIRPOR
788620
17.12
–61.78
0A
883
35
Algeria (DZA)
ADRAR
606200
27.88
–0.18
1B
14
1
ANNABA
603600
36.83
7.82
3A
630
25
BATNA
604680
35.75
6.32
3B
362
14
BECHAR
605710
31.50
–2.25
2B
87
3
BEJAIA-AEROPORT
604020
36.72
5.07
3A
776
31
BISKRA
605250
34.80
5.73
2B
110
4
BORDJ-BOU-ARRERIDJ
604440
36.07
4.77
3B
420
17
CONSTANTINE
604190
36.28
6.62
3A
516
20
DAR-EL-BEIDA
603900
36.68
3.22
3A
701
28
DJANET
606700
24.27
9.47
2B
21
1
EL-BAYADH
605500
33.67
1.00
4B
269
11
EL-GOLEA
605900
30.57
2.87
2B
37
1
EL-OUED
605590
33.50
6.78
2B
71
3
GHARDAIA
605660
32.40
3.80
2B
65
3
HASSI-MESSAOUD
605810
31.67
6.15
2B
40
2
ILLIZI
606400
26.50
8.42
1B
18
1
IN-AMENAS
606110
28.05
9.63
2B
25
1
IN-SALAH
606300
27.23
2.50
0B
12
0
JIJEL-ACHOUAT
603510
36.80
5.88
3A
943
37
MASCARA-MATEMORE
605060
35.60
0.30
3A
443
17
MECHERIA
605490
33.58
–0.28
3B
231
9
ORAN-SENIA
604900
35.63
–0.60
3A
368
15
OUARGLA
605800
31.93
5.40
2B
50
2
SETIF
604450
36.18
5.25
4A
492
19
SKIKDA
603550
36.88
6.90
3A
734
29
TAMANRASSET
606800
22.80
5.43
2B
40
2
TAMANRASSET
606805
22.80
5.45
2B
40
2
TEBESSA
604750
35.42
8.12
3B
369
15
TIARET
605110
35.35
1.47
3B
355
14
TINDOUF
606560
27.70
–8.17
1B
51
2
TLEMCEN-ZENATA
605310
35.02
–1.47
3A
468
18
TOUGGOURT
605550
33.12
6.13
2B
58
2
Argentina (ARG)
AEROPARQUE BS. AS.
875820
–34.57
–58.42
3A
1049
41
BAHIA BLANCA AERO
877500
–38.73
–62.17
3A
632
25
BARILOCHE AERO
877650
–41.15
–71.17
5C
801
32
CATAMARCA AERO.
872220
–28.60
–65.77
2B
383
15
CERES AERO
872570
–29.88
–61.95
3A
936
37
COMODORO RIVADAVIA
878600
–45.78
–67.50
4C
238
9
CONCORDIA AERO
873950
–31.30
–58.02
3A
1298
51
CORDOBA AERO
873440
–31.32
–64.22
3A
827
33
CORRIENTES AERO.
871660
–27.45
–58.77
2A
1460
57
ESQUEL AERO
878030
–42.93
–71.15
5C
488
19
EZEIZA AERO
875760
–34.82
–58.53
3A
967
38
FORMOSA AERO
871620
–26.20
–58.23
2A
1411
56
GUALEGUAYCHU AERO
874970
–33.00
–58.62
3A
1038
41
IGUAZU AERO
870970
–25.73
–54.47
2A
1826
72
JUJUY AERO
870460
–24.38
–65.08
3A
818
32
JUNIN AERO
875480
–34.55
–60.92
3A
983
39
LA RIOJA AERO.
872170
–29.38
–66.82
2B
361
14
LAGO ARGENTINO ARPT
879030
–50.33
–72.30
5C
200
8
MALARGUE AERO
875060
–35.50
–69.58
4B
285
11
MAR DEL PLATA AERO
876920
–37.93
–57.58
3A
879
35
MARCOS JUAREZ AERO
874670
–32.70
–62.15
3A
884
35
MENDOZA AERO
874180
–32.83
–68.78
3B
196
8
MONTE CASEROS AERO
873930
–30.27
–57.65
2A
1466
58
NEUQUEN AERO
877150
–38.95
–68.13
3B
194
8
PARANA AERO
873740
–31.78
–60.48
3A
1025
40
PASO DE LOS LIBRES
872890
–29.68
–57.15
2A
1492
59
POSADAS AERO.
871780
–27.37
–55.97
2A
1686
66
PRESIDENCIA ROQUE S
871490
–26.82
–60.45
2A
1054
41
RECONQUISTA AERO
872700
–29.18
–59.70
2A
1206
47
RESISTENCIA AERO
871550
–27.45
–59.05
2A
1335
53
RIO CUARTO AERO
874530
–33.12
–64.23
3A
827
33
RIO GALLEGOS AERO
879250
–51.62
–69.28
5B
253
10
RIO GRANDE B.A.
879340
–53.80
–67.75
6A
325
13
ROSARIO AERO
874800
–32.92
–60.78
3A
977
38
SALTA AERO
870470
–24.85
–65.48
3A
740
29
SAN ANTONIO OESTE A
877840
–40.78
–65.10
3B
242
10
SAN JUAN AERO
873110
–31.40
–68.42
3B
92
4
SAN JULIAN AERO
879090
–49.32
–67.75
5B
243
10
American Samoa (ASM)
PAGO PAGO WSO AP
917650
–14.33
–170.71
0A
2990
118
American Samoa (ASM)
PAGO PAGO WSO AP
917650
–14.33
–170.71
0A
2990
118
Antarctica (ATA)
BASE ARTURO PRAT
890570
–62.50
–59.68
8
902
35
BASE ESPERANZA
889630
–63.40
–56.98
8
840
33
BASE JUBANY
890530
–62.23
–58.63
8
905
36
BASE MARAMBIO
890550
–64.23
–56.72
8
792
31
BASE ORCADAS
889680
–60.73
–44.73
8
902
35
BASE SAN MARTIN
890660
–68.12
–67.13
8
624
25
BELLINGSHAUSEN AWS
890500
–62.20
–58.93
8
905
36
BERNARDO O`HIGGINS
890590
–63.32
–57.90
8
858
34
BUTLER ISLAND
892660
–72.21
–60.17
8
610
24
CASEY
896110
–66.28
110.52
8
398
16
DAVIS
895710
–68.58
77.95
8
281
11
DINAMET-URUGUAY
890540
–62.18
–58.83
8
905
36
DUMONT DURVILLE
896420
–66.67
140.02
8
431
17
FREI CHI-BASE
890560
–62.18
–58.98
8
905
36
GREAT_WALL_
890580
–62.22
–58.97
8
905
36
Antarctica (ATA)
BASE ARTURO PRAT
890570
–62.50
–59.68
8
902
35
BASE ESPERANZA
889630
–63.40
–56.98
8
840
33
BASE JUBANY
890530
–62.23
–58.63
8
905
36
BASE MARAMBIO
890550
–64.23
–56.72
8
792
31
BASE ORCADAS
889680
–60.73
–44.73
8
902
35
BASE SAN MARTIN
890660
–68.12
–67.13
8
624
25
BELLINGSHAUSEN AWS
890500
–62.20
–58.93
8
905
36
BERNARDO O`HIGGINS
890590
–63.32
–57.90
8
858
34
BUTLER ISLAND
892660
–72.21
–60.17
8
610
24
CASEY
896110
–66.28
110.52
8
398
16
DAVIS
895710
–68.58
77.95
8
281
11
DINAMET-URUGUAY
890540
–62.18
–58.83
8
905
36
DUMONT DURVILLE
896420
–66.67
140.02
8
431
17
FREI CHI-BASE
890560
–62.18
–58.98
8
905
36
GREAT_WALL_
890580
–62.22
–58.97
8
905
36

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 421

PDF Page 424

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
SAN LUIS AERO
874360
–33.27
–66.35
3B
617
24
SAN MARTIN
874160
–33.08
–68.42
3B
169
7
SAN RAFAEL AERO
875090
–34.58
–68.40
3B
336
13
SANTA ROSA AERO
876230
–36.57
–64.27
3A
695
27
SANTIAGO DEL ESTERO
871290
–27.77
–64.30
2B
577
23
SAUCE VIEJO AERO
873710
–31.70
–60.82
3A
991
39
TANDIL AERO
876450
–37.23
–59.25
3A
969
38
TARTAGAL AERO
870220
–22.65
–63.82
2A
1008
40
TRELEW AERO
878280
–43.20
–65.27
3B
183
7
TUCUMAN AERO
871210
–26.85
–65.10
2A
1078
42
USHUAIA AERO
879380
–54.80
–68.32
6A
525
21
VIEDMA AERO
877910
–40.85
–63.02
3B
353
14
VILLA REYNOLDS AERO
874480
–33.73
–65.38
3A
700
28
CAIRNS AERO
942870
–16.88
145.75
1A
2013
79
CAMDEN AIRPORT
947550
–34.03
150.68
3A
857
34
CANBERRA AIRPORT
949260
–35.30
149.20
4A
614
24
CANTERBURY RACECOUR
947660
–33.90
151.12
3A
1104
43
CAPE BORDA
948050
–35.75
136.58
3C
604
24
CAPE BRUNY LIGHTHOU
949670
–43.50
147.15
4A
1006
40
CAPE DON AWS
941290
–11.32
131.77
0A
1310
52
CAPE FOURCROY
941220
–11.78
130.02
0A
1845
73
CAPE GRIM B.A.P.S.
949540
–40.67
144.68
4A
946
37
CAPE JAFFA AWS
948130
–36.97
139.72
3C
569
22
CAPE LEEUWIN
946010
–34.37
115.13
3C
1017
40
CAPE MORETON LIGHTH
945940
–27.03
153.47
2A
1532
60
CAPE NATURALISTE
946000
–33.53
115.02
3C
834
33
CAPE NELSON LIGHTHO
948260
–38.43
141.55
3C
774
30
CAPE OTWAY LIGHTHOU
948420
–38.85
143.52
3A
954
38
CAPE SORELL
949740
–42.20
145.17
4A
1603
63
CAPE WESSEL AWS
941470
–11.02
136.75
0A
1365
54
CARNARVON AIRPORT
943000
–24.88
113.67
2B
211
8
CATO ISLAND
943940
–23.25
155.53
1A
814
32
CEDUNA AMO
946530
–32.13
133.70
3C
287
11
CENTRE ISLAND
942480
–15.75
136.80
0A
981
39
CERBERUS AWS
948980
–38.35
145.17
3A
807
32
CESSNOCK AIRPORT
957710
–32.78
151.33
3A
746
29
CHARLEVILLE AERO
945100
–26.42
146.27
2B
476
19
COBAR AIRPORT AWS
947100
–31.53
145.80
3B
405
16
COBAR MO
947110
–31.48
145.83
3B
405
16
COCONUT ISLAND
941820
–10.05
143.07
0A
1522
60
COFFS HARBOUR MO
947910
–30.32
153.12
3A
1649
65
COMBIENBAR
949140
–37.33
149.02
4A
971
38
CONDOBOLIN AIRPORT
957080
–33.07
147.22
3B
468
18
COOBER PEDY AIRPORT
954580
–29.03
134.72
2B
173
7
COOKTOWN MISSION
942830
–15.43
145.18
1A
1732
68
COOLANGATTA AIRPORT
945920
–28.17
153.50
2A
1710
67
COOMA AIRPORT AWS
949210
–36.30
148.97
4A
541
21
COONABARABRAN NAMOI
947280
–31.27
149.27
3A
826
33
CREAL REEF
943710
–20.53
150.38
1A
858
34
CUNDERDIN AIRFIELD
956250
–31.62
117.22
3A
371
15
CUNNAMULLA POST OFF
945000
–28.07
145.68
2B
384
15
CURTIN AERO
942040
–17.58
123.82
0B
752
30
DARWIN AIRPORT
941200
–12.42
130.88
0A
1730
68
DERBY AERO
952050
–17.37
123.67
0B
632
25
DEVONPORT AIRPORT
959600
–41.17
146.42
4A
792
31
DOUBLE ISLAND POINT
945840
–25.93
153.18
2A
1569
62
DUBBO AIRPORT AWS
957190
–32.22
148.57
3A
617
24
DUNNS HILL
948720
–37.88
145.33
4A
936
37
EAST SALE AIRPORT
949070
–38.10
147.13
3A
586
23
EDDYSTONE POINT
949830
–41.00
148.35
3A
804
32
EDITHBURGH AWS
948090
–35.12
137.73
3C
392
15
EILDON FIRE TOWER
948810
–37.22
145.83
4A
827
33
EMERALD AIRPORT
943630
–23.57
148.18
2B
646
25
ESPERANCE
946380
–33.83
121.88
3C
611
24
ESPERANCE AERO
956380
–33.68
121.83
3C
549
22
FALLS CREEK AWS
949030
–36.87
147.27
6A
1197
47
Armenia (ARM)
AMASIA
376820
40.78
43.83
6A
599
24
SEVAN
377090
40.55
44.93
6A
498
20
YEREVAN/YEREVAN-ARA
377890
40.13
44.47
4B
342
13
Armenia (ARM)
AMASIA
376820
40.78
43.83
6A
599
24
SEVAN
377090
40.55
44.93
6A
498
20
YEREVAN/YEREVAN-ARA
377890
40.13
44.47
4B
342
13
Aruba (ABW)
QUEEN BEATRIX AIRPO
789820
12.50
–70.02
0B
417
16
Aruba (ABW)
QUEEN BEATRIX AIRPO
789820
12.50
–70.02
0B
417
16
Australia (AUS)
ADELAIDE AIRPORT
946720
–34.95
138.53
3B
446
18
ADELAIDE REGIONAL O
946750
–34.92
138.62
3A
552
22
ADELE ISLAND
942100
–15.52
123.15
0A
847
33
AIREYS INLET
948460
–38.45
144.10
3A
679
27
ALBANY AIRPORT
948020
–34.93
117.80
3C
806
32
ALBURY AEROPORT
958960
–36.07
146.95
3A
722
28
ALICE SPRINGS AIRPO
943260
–23.80
133.88
2B
296
12
AMBERLEY AMO
945680
–27.63
152.72
2A
859
34
APPLETHORPE GBHRS A
945530
–28.62
151.95
3A
784
31
ARARAT PRISON
948340
–37.28
142.98
4A
594
23
ARCHERFIELD AIRPORT
945750
–27.57
153.00
2A
1178
46
ARGYLE AERODROME
942170
–16.63
128.45
0B
725
29
AVALON AIRPORT
948540
–38.03
144.47
3A
564
22
BALLARAT AERODROME
948520
–37.52
143.78
4A
681
27
BANKSTOWN AIRPORT A
947650
–33.92
150.98
3A
911
36
BATCHELOR AERO
941250
–13.05
131.02
0A
1389
55
BATHURST AIRPORT AW
947290
–33.42
149.65
4A
654
26
BEGA AWS
959310
–36.67
149.82
3A
839
33
BENDIGO AIRPORT AWS
948550
–36.73
144.32
3A
582
23
BILOELA THANGOOL AI
943760
–24.48
150.57
2B
661
26
BIRDSVILLE POLICE S
944820
–25.90
139.35
2B
172
7
BOMBALA AWS
949290
–37.00
149.23
4A
660
26
BORROLOOLA
941520
–16.08
136.30
1A
935
37
BOULIA AIRPORT
943330
–22.92
139.90
1B
259
10
BOURKE AIRPORT AWS
947030
–30.03
145.95
2B
366
14
BOWEN AIRPORT
943660
–20.02
148.20
1A
974
38
BRAIDWOOD RACECOURS
949270
–35.43
149.78
4A
773
30
BRISBANE AERO
945780
–27.38
153.13
2A
1130
44
BROKEN HILL AIRPORT
946910
–32.00
141.47
3B
266
10
BROOME AIRPORT
942030
–17.95
122.23
0B
660
26
BUNDABERG AERO
943870
–24.90
152.32
2A
1015
40
BURKETOWN POST OFFI
942590
–17.75
139.55
1B
753
30
BUSSELTON AERO
956110
–33.68
115.40
3C
791
31
Australia (AUS)
ADELAIDE AIRPORT
946720
–34.95
138.53
3B
446
18
ADELAIDE REGIONAL O
946750
–34.92
138.62
3A
552
22
ADELE ISLAND
942100
–15.52
123.15
0A
847
33
AIREYS INLET
948460
–38.45
144.10
3A
679
27
ALBANY AIRPORT
948020
–34.93
117.80
3C
806
32
ALBURY AEROPORT
958960
–36.07
146.95
3A
722
28
ALICE SPRINGS AIRPO
943260
–23.80
133.88
2B
296
12
AMBERLEY AMO
945680
–27.63
152.72
2A
859
34
APPLETHORPE GBHRS A
945530
–28.62
151.95
3A
784
31
ARARAT PRISON
948340
–37.28
142.98
4A
594
23
ARCHERFIELD AIRPORT
945750
–27.57
153.00
2A
1178
46
ARGYLE AERODROME
942170
–16.63
128.45
0B
725
29
AVALON AIRPORT
948540
–38.03
144.47
3A
564
22
BALLARAT AERODROME
948520
–37.52
143.78
4A
681
27
BANKSTOWN AIRPORT A
947650
–33.92
150.98
3A
911
36
BATCHELOR AERO
941250
–13.05
131.02
0A
1389
55
BATHURST AIRPORT AW
947290
–33.42
149.65
4A
654
26
BEGA AWS
959310
–36.67
149.82
3A
839
33
BENDIGO AIRPORT AWS
948550
–36.73
144.32
3A
582
23
BILOELA THANGOOL AI
943760
–24.48
150.57
2B
661
26
BIRDSVILLE POLICE S
944820
–25.90
139.35
2B
172
7
BOMBALA AWS
949290
–37.00
149.23
4A
660
26
BORROLOOLA
941520
–16.08
136.30
1A
935
37
BOULIA AIRPORT
943330
–22.92
139.90
1B
259
10
BOURKE AIRPORT AWS
947030
–30.03
145.95
2B
366
14
BOWEN AIRPORT
943660
–20.02
148.20
1A
974
38
BRAIDWOOD RACECOURS
949270
–35.43
149.78
4A
773
30
BRISBANE AERO
945780
–27.38
153.13
2A
1130
44
BROKEN HILL AIRPORT
946910
–32.00
141.47
3B
266
10
BROOME AIRPORT
942030
–17.95
122.23
0B
660
26
BUNDABERG AERO
943870
–24.90
152.32
2A
1015
40
BURKETOWN POST OFFI
942590
–17.75
139.55
1B
753
30
BUSSELTON AERO
956110
–33.68
115.40
3C
791
31

422 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 425

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
FLINDERS ISLAND AIR
949800
–40.10
148.00
3A
745
29
FLINDERS REEF
942900
–17.72
148.45
1A
945
37
FORBES AIRPORT
947150
–33.37
147.92
3A
558
22
FORREST
956460
–30.83
128.12
3B
199
8
FRANKSTON AWS
948710
–38.15
145.12
3A
773
30
GABO ISLAND
949330
–37.57
149.90
3A
958
38
GANNET CAY
943790
–21.97
152.47
1A
821
32
GAYNDAH POST OFFICE
945430
–25.63
151.62
2A
723
28
GEELONG AIRPORT
948570
–38.23
144.33
3A
564
22
GELANTIPY
949130
–37.22
148.27
4A
794
31
GEORGETOWN POST OFF
942750
–18.30
143.55
1A
812
32
GERALDTON AIRPORT
944030
–28.80
114.70
3A
443
17
GILES METEOROLOGICA
944610
–25.03
128.30
2B
271
11
GLADSTONE AIRPORT
943810
–23.87
151.22
2A
919
36
GLADSTONE RADAR
943800
–23.85
151.27
2A
919
36
GLEN INNES AIRPORT
945880
–29.68
151.70
4A
911
36
GOLD COAST SEAWAY
945800
–27.93
153.43
2A
1522
60
GOLDSTREAM
948640
–37.73
145.40
4A
889
35
GOONDIWINDI AIRPORT
945300
–28.52
150.32
2A
584
23
GOULBURN AIRPORT AW
957160
–34.82
149.73
4A
680
27
GOVE AIRPORT
941500
–12.28
136.82
1A
1437
57
GREEN ISLAND
952890
–16.77
145.97
1A
2315
91
GRIFFITH AWS
947050
–34.32
146.07
3B
407
16
HALLS CREEK AIRPORT
942120
–18.23
127.67
0B
586
23
HAMILTON AIRPORT
948290
–37.65
142.07
4A
667
26
HAY AWS
947010
–34.53
144.87
3B
398
16
HERON ISLAND RES ST
943860
–23.45
151.92
1A
876
34
HOBART AIRPORT
949750
–42.83
147.50
4A
495
19
HOBART ELLERSLIE RO
949700
–42.88
147.33
4A
589
23
HOLMES REEF
942890
–16.47
147.87
1A
1263
50
HOMEBUSH (OLYMPIC SITE)
957650
–33.85
151.07
3A
928
37
HUNTERS HILL
948780
–36.22
147.53
4A
934
37
JABIRU AIRPORT
941370
–12.67
132.90
0A
1450
57
JACUP
956360
–33.88
119.10
3B
429
17
JANDAKOT AERO
946090
–32.10
115.88
3A
838
33
KALGOORLIE-BOULDER
946370
–30.78
121.45
3B
275
11
KARRATHA AERO
953070
–20.72
116.77
1B
252
10
KARRATHA LEGENDRE I
943070
–20.37
116.85
1B
405
16
KATANNING
946290
–33.68
117.55
3A
480
19
KATOOMBA
947440
–33.72
150.28
4A
1390
55
KHANCOBAN
949190
–36.23
148.13
3A
961
38
KILMORE GAP
948600
–37.38
144.97
4A
699
28
KING ISLAND AIRPORT
948500
–39.88
143.88
4C
888
35
KING ISLAND CURRIE
948510
–39.93
143.85
3C
888
35
KUNUNURRA AERO
942160
–15.78
128.72
0B
779
31
KYANCUTTA
946570
–33.13
135.55
3B
300
12
LADY ELLIOT ISLAND
943880
–24.12
152.72
2A
1166
46
LAKE GRACE
946350
–33.12
118.47
3B
345
14
LANCELIN
956060
–31.02
115.32
3A
600
24
LATROBE VALLEY AIRP
948910
–38.22
146.47
3A
760
30
LAUNCESTON AIRPORT
949680
–41.53
147.20
4A
652
26
LAVERTON AERO
944490
–28.62
122.42
2B
246
10
LAVERTON AERODROME
948650
–37.87
144.75
3A
547
22
LEARMONTH AIRPORT
943020
–22.23
114.08
1B
235
9
LEINSTER AERO
954480
–27.85
120.70
2B
238
9
LEONORA POST OFFICE
944480
–28.88
121.33
2B
249
10
LIHOU REEF
942960
–17.12
152.00
1A
1026
40
LONGERENONG
958350
–36.67
142.30
3B
422
17
LONGREACH AERO
943460
–23.43
144.28
1B
418
16
LOOKOUT HILL
948350
–37.28
143.25
5A
675
27
LORD HOWE ISLAND AE
949950
–31.53
159.07
3A
1456
57
LOW ROCKY POINT (AWS)
959610
–42.98
145.50
4A
1922
76
LUCINDA POINT AWS
942950
–18.52
146.40
1A
2183
86
MAATSUYKER ISLAND L
949620
–43.65
146.27
4A
1377
54
MACKAY MO
943670
–21.12
149.22
2A
1563
62
MACQUARIE ISLAND
949980
–54.50
158.95
6A
947
37
MALLACOOTA
949350
–37.60
149.73
3A
1020
40
MANDURAH
946050
–32.52
115.72
3A
842
33
MANGALORE AWS COMPO
948740
–36.88
145.18
3A
574
23
MANGROVE MOUNTAIN A
957740
–33.28
151.22
3A
1059
42
MARION REEF
942980
–19.08
152.38
1A
858
34
MARLA POLICE STATIO
944770
–27.30
133.62
2B
229
9
MAROOCHYDORE AERO
945690
–26.60
153.10
2A
1687
66
MARYBOROUGH COMPOSI
945670
–25.52
152.72
2A
1070
42
MEEKATHARRA AIRPORT
944300
–26.62
118.55
2B
246
10
MELBOURNE
948680
–37.82
144.97
3A
635
25
MELBOURNE AIRPORT
948660
–37.67
144.85
3A
537
21
MILDURA AIRPORT
946930
–34.23
142.08
3B
280
11
MILINGIMBI
941400
–12.12
134.90
0A
1199
47
MOOMBA AIRPORT
954810
–28.10
140.20
2B
175
7
MOORABBIN AIRPORT
948700
–37.98
145.10
3A
724
29
MOREE
945270
–29.47
149.85
3A
588
23
MOREE AERO
955270
–29.48
149.83
3A
588
23
MORTLAKE AWS
948400
–38.07
142.77
4A
685
27
MORUYA HEADS PILOT
949370
–35.92
150.15
3A
1014
40
MOUNT BOYCE
947430
–33.62
150.27
4A
1184
47
MOUNT BULLER AWS
948940
–37.15
146.43
6A
1243
49
MOUNT GAMBIER AERO
948210
–37.73
140.78
3C
696
27
MOUNT ISA AERO
943320
–20.68
139.48
1B
446
18
MOUNT LAWLEY PERTH
946080
–31.92
115.87
3A
820
32
MT HOTHAM AWS
949060
–36.97
147.12
7
1336
53
MT LOFTY AWS
956780
–34.97
138.70
4C
651
26
MT MOORNAPA
959130
–37.75
147.13
4A
685
27
MT WELLINGTON
959790
–42.88
147.23
7
662
26
MUDGEE AIRPORT AWS
947270
–32.57
149.62
3A
709
28
NAMBOUR DPI
955720
–26.65
152.93
2A
1680
66
NEPTUNE ISLAND
948040
–35.33
136.12
3C
467
18
NEWCASTLE NOBBYS SI
947740
–32.92
151.78
3A
1130
44
NORAH HEAD LIGHTHOU
957700
–33.27
151.57
3A
1206
47
NORMANTON
942670
–17.67
141.08
0A
853
34
NORSEMAN
946390
–32.20
121.78
3B
305
12
NORTH EAST ISLAND
941510
–13.65
136.93
0A
963
38
NOWRA RAN AIR STATI
947500
–34.95
150.53
3A
1075
42
NULLARBOR ROADHOUSE
946510
–31.45
130.90
3B
265
10
NULLO MOUNTAIN AWS
947540
–32.73
150.23
4A
731
29
OAKEY AERO
945520
–27.42
151.73
3A
638
25

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 423

PDF Page 426

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
ONSLOW
943050
–21.63
115.12
1B
287
11
OUSE FIRE STATION
949570
–42.48
146.72
4A
544
21
PARABURDOO AERO
943160
–23.17
117.75
1B
267
10
PARKES (MACARTHUR ST)
947170
–33.13
148.17
3A
634
25
PAYNES FIND
944040
–29.27
117.68
2B
279
11
PEARCE RAAF
946120
–31.67
116.02
3A
660
26
PENRITH
947630
–33.72
150.68
3A
883
35
PERTH AIRPORT
946100
–31.93
115.97
3A
763
30
POINT WILSON
948470
–38.10
144.53
3A
561
22
PORT ARTHUR (PALM.)
949780
–43.17
147.83
4A
1165
46
PORT FAIRY AWS
948300
–38.40
142.23
3A
801
32
PORT HEDLAND AIRPOR
943120
–20.37
118.63
1B
277
11
PORT KEATS AWS AUT
941110
–14.23
129.45
0A
1491
59
PORT MACQUARIE AIRP
947860
–31.43
152.85
3A
1522
60
PORTLAND CASHMORE A
948280
–38.32
141.47
4C
812
32
PROSERPINE AIRPORT
943650
–20.50
148.53
2A
1455
57
QUILPIE AIRPORT
944940
–26.62
144.25
2B
365
14
RAVENSTHORPE HOPETO
956350
–33.93
120.13
3C
519
20
REDESDALE
948590
–37.02
144.53
4A
697
27
RENMARK
946870
–34.17
140.75
3B
259
10
RHYLL (AWS)
948920
–38.45
145.30
3A
829
33
RICHMOND POST OFFIC
943400
–20.73
143.13
1B
489
19
RICHMOND RAAF
957530
–33.60
150.78
3A
842
33
ROCKHAMPTON AERO
943740
–23.38
150.48
2A
791
31
ROEBOURNE POST OFFI
943090
–20.78
117.15
0B
296
12
ROMA AIRPORT
945150
–26.55
148.78
2A
616
24
ROTTNEST ISLAND
946020
–32.02
115.50
3A
629
25
RUNDLE ISLAND
943780
–23.53
151.28
2A
863
34
SCONE AIRPORT
957580
–32.03
150.83
3A
708
28
SCORESBY RESEARCH
958670
–37.87
145.25
3A
936
37
SHARK BAY (DENHAM)
944020
–25.92
113.52
2B
221
9
SHEOAKS AWS
948630
–37.90
144.12
4A
613
24
SHEPPARTON AIRPORT
948750
–36.43
145.40
3A
504
20
SMITHTON AERODROME
949530
–40.83
145.08
4C
1105
44
SOUTHERN CROSS
946340
–31.23
119.33
3B
323
13
SOUTHERN CROSS AIRF
956340
–31.23
119.35
3B
323
13
ST LAWRENCE POST OF
943690
–22.35
149.53
2A
990
39
STRAHAN AERODROME
949560
–42.15
145.28
4A
2101
83
SWAN HILL AERODROME
948430
–35.38
143.53
3B
337
13
SWANBOURNE
946140
–31.95
115.77
3A
820
32
SYDNEY AIRPORT AMO
947670
–33.93
151.18
3A
1104
43
SYDNEY REGIONAL OFF
947680
–33.85
151.20
3A
1253
49
TAMWORTH AIRPORT AW
957620
–31.07
150.83
3A
676
27
TELFER AERO
943190
–21.72
122.22
1B
302
12
TENNANT CREEK MET O
942380
–19.63
134.18
1B
446
18
TEWANTIN RSL PARK
945700
–26.38
153.03
2A
1678
66
THREDBO (CRACKENBACK)
959090
–36.50
148.28
7
975
38
TINDAL RAAF
941310
–14.52
132.37
0A
1013
40
TOOWOOMBA AIRPORT
955510
–27.55
151.92
3A
937
37
TOWN OF 1770
943840
–24.15
151.88
2A
1104
43
TOWNSVILLE AERO
942940
–19.25
146.77
1A
1042
41
TROUGHTON ISLAND
941020
–13.75
126.15
0A
955
38
TUGGERANONG ISABELL
949250
–35.42
149.10
4A
733
29
TUNNAK FIRE STATION
949600
–42.45
147.47
5A
611
24
ULLADULLA AWS
949380
–35.35
150.48
3A
1254
49
URANDANGIE
943290
–21.60
138.30
1B
314
12
VICTORIA RIVER DOWN
942320
–16.40
131.02
0B
743
29
WAGGA WAGGA AMO
949100
–35.17
147.45
3A
574
23
WALGETT AIRPORT
957150
–30.03
148.12
2B
507
20
WANGARATTA AERO
948890
–36.42
146.30
3A
679
27
WARBURTO POINT
946660
–34.00
137.53
3B
351
14
WARRNAMBOOL AIRPORT
948320
–38.28
142.43
4C
775
30
WARWICK
945550
–28.20
152.10
3A
728
29
WEIPA AERO
941700
–12.68
141.92
0A
1883
74
WILLIAMTOWN RAAF
947760
–32.80
151.83
3A
1144
45
WILLIS ISLAND
942990
–16.30
149.97
1A
1029
41
WILSONS PROMONTORY
948930
–39.12
146.42
3C
1088
43
WINDORAH
944880
–25.42
142.65
2B
269
11
WINTON (POST OFFICE)
943390
–22.38
143.03
1B
397
16
WONTHAGGI COMPOSITE
958810
–38.60
145.58
3A
954
38
WOOMERA AERODROME
946590
–31.15
136.82
3B
184
7
WYNDHAM
942140
–15.48
128.12
0B
759
30
WYNYARD AIRPORT
959570
–41.00
145.73
4C
960
38
YEPPOON AWS
943730
–23.13
150.75
2A
1220
48
YOUNG AIRPORT
947120
–34.25
148.25
3A
668
26
YULARA AERO
944620
–25.20
130.98
2B
333
13
ONSLOW
943050
–21.63
115.12
1B
287
11
OUSE FIRE STATION
949570
–42.48
146.72
4A
544
21
PARABURDOO AERO
943160
–23.17
117.75
1B
267
10
PARKES (MACARTHUR ST)
947170
–33.13
148.17
3A
634
25
PAYNES FIND
944040
–29.27
117.68
2B
279
11
PEARCE RAAF
946120
–31.67
116.02
3A
660
26
PENRITH
947630
–33.72
150.68
3A
883
35
PERTH AIRPORT
946100
–31.93
115.97
3A
763
30
POINT WILSON
948470
–38.10
144.53
3A
561
22
PORT ARTHUR (PALM.)
949780
–43.17
147.83
4A
1165
46
PORT FAIRY AWS
948300
–38.40
142.23
3A
801
32
PORT HEDLAND AIRPOR
943120
–20.37
118.63
1B
277
11
PORT KEATS AWS AUT
941110
–14.23
129.45
0A
1491
59
PORT MACQUARIE AIRP
947860
–31.43
152.85
3A
1522
60
PORTLAND CASHMORE A
948280
–38.32
141.47
4C
812
32
PROSERPINE AIRPORT
943650
–20.50
148.53
2A
1455
57
QUILPIE AIRPORT
944940
–26.62
144.25
2B
365
14
RAVENSTHORPE HOPETO
956350
–33.93
120.13
3C
519
20
REDESDALE
948590
–37.02
144.53
4A
697
27
RENMARK
946870
–34.17
140.75
3B
259
10
RHYLL (AWS)
948920
–38.45
145.30
3A
829
33
RICHMOND POST OFFIC
943400
–20.73
143.13
1B
489
19
RICHMOND RAAF
957530
–33.60
150.78
3A
842
33
ROCKHAMPTON AERO
943740
–23.38
150.48
2A
791
31
ROEBOURNE POST OFFI
943090
–20.78
117.15
0B
296
12
ROMA AIRPORT
945150
–26.55
148.78
2A
616
24
ROTTNEST ISLAND
946020
–32.02
115.50
3A
629
25
RUNDLE ISLAND
943780
–23.53
151.28
2A
863
34
SCONE AIRPORT
957580
–32.03
150.83
3A
708
28
SCORESBY RESEARCH
958670
–37.87
145.25
3A
936
37
SHARK BAY (DENHAM)
944020
–25.92
113.52
2B
221
9
SHEOAKS AWS
948630
–37.90
144.12
4A
613
24
SHEPPARTON AIRPORT
948750
–36.43
145.40
3A
504
20
SMITHTON AERODROME
949530
–40.83
145.08
4C
1105
44
SOUTHERN CROSS
946340
–31.23
119.33
3B
323
13
SOUTHERN CROSS AIRF
956340
–31.23
119.35
3B
323
13
ST LAWRENCE POST OF
943690
–22.35
149.53
2A
990
39
STRAHAN AERODROME
949560
–42.15
145.28
4A
2101
83
SWAN HILL AERODROME
948430
–35.38
143.53
3B
337
13
SWANBOURNE
946140
–31.95
115.77
3A
820
32
SYDNEY AIRPORT AMO
947670
–33.93
151.18
3A
1104
43
SYDNEY REGIONAL OFF
947680
–33.85
151.20
3A
1253
49
TAMWORTH AIRPORT AW
957620
–31.07
150.83
3A
676
27
TELFER AERO
943190
–21.72
122.22
1B
302
12
TENNANT CREEK MET O
942380
–19.63
134.18
1B
446
18
TEWANTIN RSL PARK
945700
–26.38
153.03
2A
1678
66
THREDBO (CRACKENBACK)
959090
–36.50
148.28
7
975
38
TINDAL RAAF
941310
–14.52
132.37
0A
1013
40
TOOWOOMBA AIRPORT
955510
–27.55
151.92
3A
937
37
TOWN OF 1770
943840
–24.15
151.88
2A
1104
43
TOWNSVILLE AERO
942940
–19.25
146.77
1A
1042
41
TROUGHTON ISLAND
941020
–13.75
126.15
0A
955
38
TUGGERANONG ISABELL
949250
–35.42
149.10
4A
733
29
Austria (AUT)
AIGEN IM ENNSTAL
111570
47.53
14.13
6A
1300
51
ALLENTSTEIG
110190
48.68
15.37
5A
629
25
ALPINZENTRUM RUDOLF
111380
47.13
12.63
7
1130
44
AMSTETTEN
110180
48.10
14.90
5A
989
39
ARRIACH
112750
46.73
13.85
6A
1322
52
BAD RADKERSBURG
112480
46.68
15.98
5A
943
37
BISCHOFSHOFEN
111410
47.40
13.22
5A
1314
52
BREGENZ
111010
47.50
9.75
5A
1784
70
BRENNER
111280
47.00
11.52
6A
933
37
DELLACH IM DRAUTAL
112700
46.73
13.08
5A
1073
42
DORNBIRN
113020
47.43
9.73
5A
1393
55
EISENSTADT
111900
47.85
16.53
5A
610
24
FELDKIRCH
111050
47.27
9.62
5A
1393
55
FEUERKOGEL
111550
47.82
13.72
7
1361
54
FREISTADT
110150
48.50
14.50
5A
779
31
GMUNDEN
111540
47.90
13.80
5A
1416
56
GRAZ-THALERHOF-FLUG
112400
47.00
15.43
5A
847
33
GUMPOLDSKIRCHEN
110820
48.03
16.28
5A
604
24
HAHNENKAMM/EHRENBAC
111350
47.42
12.37
7
1242
49
HOHE WAND/HOCHKOGEL
113850
47.82
16.03
6A
745
29
INNSBRUCK-FLUGHAFEN
111200
47.27
11.35
5A
914
36
ISCHGL/IDALPE
113100
46.98
10.32
7
789
31
JAUERLING
110240
48.33
15.33
6A
646
25
KLAGENFURT-FLUGHAFE
112310
46.65
14.33
5A
905
36
KLEINZICKEN
111920
47.20
16.33
5A
741
29
KOETSCHACH-MAUTHEN
112550
46.68
13.00
5A
1427
56
KREMSMUENSTER
110120
48.05
14.13
5A
955
38
KUFSTEIN
111300
47.58
12.17
5A
1440
57
LANDECK
111120
47.13
10.57
5A
913
36

424 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 427

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
LANGENLOIS
110750
48.47
15.70
5A
574
23
LASSNITZHOEHE
112920
47.07
15.58
5A
869
34
LIENZ
112040
46.83
12.82
5A
1207
48
LILIENFELD/TARSCHBE
110780
48.03
15.58
5A
838
33
LINZ/HOERSCHING-FLU
110100
48.23
14.18
5A
955
38
LINZ/STADT
110600
48.30
14.28
5A
840
33
LITSCHAU
110210
48.95
15.03
6A
691
27
LUNZ
111700
47.85
15.07
6A
1229
48
MARIAPFARR
113480
47.15
13.75
6A
980
39
MARIAZELL
111720
47.77
15.32
6A
1066
42
MATTSEE
111520
47.98
13.10
5A
1400
55
MOENICHKIRCHEN
111850
47.52
16.03
6A
855
34
MURAU
112800
47.12
14.18
6A
962
38
NEUSIEDL
111940
47.95
16.85
5A
605
24
OBERTAUERN
111490
47.25
13.57
7
976
38
POYSDORF
110320
48.67
16.63
5A
527
21
PUCHBERG
113820
47.78
15.90
5A
991
39
RAMSAU/DACHSTEIN
113510
47.43
13.63
6A
1349
53
RAX/SEILBAHN-BERGST
111800
47.72
15.78
7
1039
41
REICHENAU/RAX
113800
47.70
15.83
5A
1039
41
RETZ
110220
48.77
15.95
5A
512
20
SALZBURG-FLUGHAFEN
111500
47.80
13.00
5A
1174
46
SCHMITTENHOEHE
113400
47.33
12.73
7
1364
54
SCHOECKL
112410
47.20
15.47
7
917
36
ST. MICHAEL/LEOBEN
111740
47.33
15.00
5A
1027
40
ST. POELTEN
110280
48.18
15.62
5A
690
27
ST. WOLFGANG
113570
47.73
13.45
5A
1465
58
STIFT ZWETTL
110200
48.62
15.20
6A
744
29
TULLN
110300
48.32
16.12
5A
606
24
VILLACH
112130
46.62
13.88
5A
1322
52
VIRGEN
112520
47.00
12.45
6A
921
36
WARTH
113080
47.25
10.18
6A
1500
59
WIEN/CITY
110340
48.20
16.37
4A
604
24
WIEN/HOHE WARTE
110350
48.25
16.37
5A
628
25
WIEN/SCHWECHAT-FLUG
110360
48.12
16.57
5A
558
22
WIENER NEUSTADT
111820
47.83
16.22
5A
745
29
WINDISCHGARSTEN
113550
47.73
14.33
5A
1190
47
ZELL AM SEE
111440
47.33
12.80
5A
1409
55
ZELTWEG
111650
47.20
14.75
6A
847
33
GOMEL
330410
52.40
30.95
6A
591
23
GRODNO
268250
53.60
24.05
6A
608
24
KOSTUCKOVICHI
268870
53.35
32.07
6A
585
23
LEPEL
266590
54.88
28.70
6A
672
26
LIDA
268320
53.85
25.32
6A
655
26
LYNTUPY
266450
55.05
26.32
6A
678
27
MINSK
268500
53.93
27.63
6A
673
27
MOGILEV
268630
53.95
30.07
6A
623
25
MOZYR
330360
51.95
29.17
6A
615
24
ORSHA
267630
54.50
30.42
6A
617
24
PINSK
330190
52.12
26.12
6A
575
23
SLUTSK
269510
53.03
27.55
6A
599
24
VERHNEDVINSK
265540
55.82
27.95
6A
614
24
VITEBSK
266660
55.17
30.22
6A
662
26
ZHITCKOVICHI
330270
52.22
27.87
6A
663
26
LANGENLOIS
110750
48.47
15.70
5A
574
23
LASSNITZHOEHE
112920
47.07
15.58
5A
869
34
LIENZ
112040
46.83
12.82
5A
1207
48
LILIENFELD/TARSCHBE
110780
48.03
15.58
5A
838
33
LINZ/HOERSCHING-FLU
110100
48.23
14.18
5A
955
38
LINZ/STADT
110600
48.30
14.28
5A
840
33
LITSCHAU
110210
48.95
15.03
6A
691
27
LUNZ
111700
47.85
15.07
6A
1229
48
MARIAPFARR
113480
47.15
13.75
6A
980
39
MARIAZELL
111720
47.77
15.32
6A
1066
42
MATTSEE
111520
47.98
13.10
5A
1400
55
MOENICHKIRCHEN
111850
47.52
16.03
6A
855
34
MURAU
112800
47.12
14.18
6A
962
38
NEUSIEDL
111940
47.95
16.85
5A
605
24
OBERTAUERN
111490
47.25
13.57
7
976
38
POYSDORF
110320
48.67
16.63
5A
527
21
PUCHBERG
113820
47.78
15.90
5A
991
39
RAMSAU/DACHSTEIN
113510
47.43
13.63
6A
1349
53
RAX/SEILBAHN-BERGST
111800
47.72
15.78
7
1039
41
REICHENAU/RAX
113800
47.70
15.83
5A
1039
41
RETZ
110220
48.77
15.95
5A
512
20
SALZBURG-FLUGHAFEN
111500
47.80
13.00
5A
1174
46
SCHMITTENHOEHE
113400
47.33
12.73
7
1364
54
SCHOECKL
112410
47.20
15.47
7
917
36
ST. MICHAEL/LEOBEN
111740
47.33
15.00
5A
1027
40
ST. POELTEN
110280
48.18
15.62
5A
690
27
ST. WOLFGANG
113570
47.73
13.45
5A
1465
58
STIFT ZWETTL
110200
48.62
15.20
6A
744
29
TULLN
110300
48.32
16.12
5A
606
24
VILLACH
112130
46.62
13.88
5A
1322
52
VIRGEN
112520
47.00
12.45
6A
921
36
WARTH
113080
47.25
10.18
6A
1500
59
WIEN/CITY
110340
48.20
16.37
4A
604
24
WIEN/HOHE WARTE
110350
48.25
16.37
5A
628
25
WIEN/SCHWECHAT-FLUG
110360
48.12
16.57
5A
558
22
WIENER NEUSTADT
111820
47.83
16.22
5A
745
29
WINDISCHGARSTEN
113550
47.73
14.33
5A
1190
47
ZELL AM SEE
111440
47.33
12.80
5A
1409
55
ZELTWEG
111650
47.20
14.75
6A
847
33
Belgium (BEL)
ANTWERPEN/DEURNE
064500
51.20
4.47
4A
792
31
BEAUVECHAIN
064580
50.75
4.77
5A
807
32
BIERSET
064780
50.65
5.45
5A
899
35
BRUXELLES NATIONAL
064510
50.90
4.53
4A
784
31
CHARLEROI/GOSSELIES
064490
50.47
4.45
5A
883
35
CHIEVRES
064320
50.57
3.83
5A
767
30
ELSENBORN
064960
50.47
6.18
6A
1092
43
FLORENNES
064560
50.23
4.65
5A
984
39
GENT/INDUSTRIE-ZONE
064310
51.18
3.82
4A
772
30
KLEINE BROGEL
064790
51.17
5.47
5A
829
33
KOKSIJDE
064000
51.08
2.65
4A
697
27
LIEGE
064324
50.63
5.45
5A
899
35
OOSTENDE (AIRPORT)
064070
51.20
2.87
5A
755
30
OOSTENDE (PIER)
064080
51.23
2.92
4A
755
30
SEMMERZAKE
064280
50.93
3.67
4A
810
32
ST. TRUIDEN (BAFB)
064700
50.80
5.20
5A
823
32
ST-HUBERT
064760
50.03
5.40
5A
998
39
UCCLE
064470
50.80
4.35
4A
829
33
LANGENLOIS
110750
48.47
15.70
5A
574
23
LASSNITZHOEHE
112920
47.07
15.58
5A
869
34
LIENZ
112040
46.83
12.82
5A
1207
48
LILIENFELD/TARSCHBE
110780
48.03
15.58
5A
838
33
LINZ/HOERSCHING-FLU
110100
48.23
14.18
5A
955
38
LINZ/STADT
110600
48.30
14.28
5A
840
33
LITSCHAU
110210
48.95
15.03
6A
691
27
LUNZ
111700
47.85
15.07
6A
1229
48
MARIAPFARR
113480
47.15
13.75
6A
980
39
MARIAZELL
111720
47.77
15.32
6A
1066
42
MATTSEE
111520
47.98
13.10
5A
1400
55
MOENICHKIRCHEN
111850
47.52
16.03
6A
855
34
MURAU
112800
47.12
14.18
6A
962
38
NEUSIEDL
111940
47.95
16.85
5A
605
24
OBERTAUERN
111490
47.25
13.57
7
976
38
POYSDORF
110320
48.67
16.63
5A
527
21
PUCHBERG
113820
47.78
15.90
5A
991
39
RAMSAU/DACHSTEIN
113510
47.43
13.63
6A
1349
53
RAX/SEILBAHN-BERGST
111800
47.72
15.78
7
1039
41
REICHENAU/RAX
113800
47.70
15.83
5A
1039
41
RETZ
110220
48.77
15.95
5A
512
20
SALZBURG-FLUGHAFEN
111500
47.80
13.00
5A
1174
46
SCHMITTENHOEHE
113400
47.33
12.73
7
1364
54
SCHOECKL
112410
47.20
15.47
7
917
36
ST. MICHAEL/LEOBEN
111740
47.33
15.00
5A
1027
40
ST. POELTEN
110280
48.18
15.62
5A
690
27
ST. WOLFGANG
113570
47.73
13.45
5A
1465
58
STIFT ZWETTL
110200
48.62
15.20
6A
744
29
TULLN
110300
48.32
16.12
5A
606
24
VILLACH
112130
46.62
13.88
5A
1322
52
VIRGEN
112520
47.00
12.45
6A
921
36
WARTH
113080
47.25
10.18
6A
1500
59
WIEN/CITY
110340
48.20
16.37
4A
604
24
WIEN/HOHE WARTE
110350
48.25
16.37
5A
628
25
WIEN/SCHWECHAT-FLUG
110360
48.12
16.57
5A
558
22
WIENER NEUSTADT
111820
47.83
16.22
5A
745
29
WINDISCHGARSTEN
113550
47.73
14.33
5A
1190
47
ZELL AM SEE
111440
47.33
12.80
5A
1409
55
ZELTWEG
111650
47.20
14.75
6A
847
33
Belize (BLZ)
BELIZE/PHILLIP GOLD
785830
17.53
–88.30
0A
1944
77
LANGENLOIS
110750
48.47
15.70
5A
574
23
LASSNITZHOEHE
112920
47.07
15.58
5A
869
34
LIENZ
112040
46.83
12.82
5A
1207
48
LILIENFELD/TARSCHBE
110780
48.03
15.58
5A
838
33
LINZ/HOERSCHING-FLU
110100
48.23
14.18
5A
955
38
LINZ/STADT
110600
48.30
14.28
5A
840
33
LITSCHAU
110210
48.95
15.03
6A
691
27
LUNZ
111700
47.85
15.07
6A
1229
48
MARIAPFARR
113480
47.15
13.75
6A
980
39
MARIAZELL
111720
47.77
15.32
6A
1066
42
MATTSEE
111520
47.98
13.10
5A
1400
55
MOENICHKIRCHEN
111850
47.52
16.03
6A
855
34
MURAU
112800
47.12
14.18
6A
962
38
NEUSIEDL
111940
47.95
16.85
5A
605
24
OBERTAUERN
111490
47.25
13.57
7
976
38
POYSDORF
110320
48.67
16.63
5A
527
21
PUCHBERG
113820
47.78
15.90
5A
991
39
RAMSAU/DACHSTEIN
113510
47.43
13.63
6A
1349
53
RAX/SEILBAHN-BERGST
111800
47.72
15.78
7
1039
41
REICHENAU/RAX
113800
47.70
15.83
5A
1039
41
RETZ
110220
48.77
15.95
5A
512
20
SALZBURG-FLUGHAFEN
111500
47.80
13.00
5A
1174
46
SCHMITTENHOEHE
113400
47.33
12.73
7
1364
54
SCHOECKL
112410
47.20
15.47
7
917
36
ST. MICHAEL/LEOBEN
111740
47.33
15.00
5A
1027
40
ST. POELTEN
110280
48.18
15.62
5A
690
27
ST. WOLFGANG
113570
47.73
13.45
5A
1465
58
STIFT ZWETTL
110200
48.62
15.20
6A
744
29
TULLN
110300
48.32
16.12
5A
606
24
VILLACH
112130
46.62
13.88
5A
1322
52
VIRGEN
112520
47.00
12.45
6A
921
36
WARTH
113080
47.25
10.18
6A
1500
59
WIEN/CITY
110340
48.20
16.37
4A
604
24
WIEN/HOHE WARTE
110350
48.25
16.37
5A
628
25
WIEN/SCHWECHAT-FLUG
110360
48.12
16.57
5A
558
22
WIENER NEUSTADT
111820
47.83
16.22
5A
745
29
WINDISCHGARSTEN
113550
47.73
14.33
5A
1190
47
ZELL AM SEE
111440
47.33
12.80
5A
1409
55
ZELTWEG
111650
47.20
14.75
6A
847
33
Benin (BEN)
BOHICON
653380
7.17
2.07
0A
1145
45
COTONOU
653440
6.35
2.38
0A
1297
51
KANDI
653060
11.13
2.93
0A
1011
40
NATITINGOU
653190
10.32
1.38
0A
1242
49
PARAKOU
653300
9.35
2.62
0A
1177
46
SAVE
653350
8.03
2.47
0A
1116
44
Azerbaijan (AZE)
LANKARAN
379850
38.73
48.83
4A
1167
46
ZAKATALA
375750
41.67
46.65
4A
975
38
Azerbaijan (AZE)
LANKARAN
379850
38.73
48.83
4A
1167
46
ZAKATALA
375750
41.67
46.65
4A
975
38
Bahamas (BHS)
NASSAU AIRPORT NEW
780730
25.05
–77.47
1A
1334
53
SETTLEMENT POINT
994390
26.68
–79.00
1A
1281
50
Bahamas (BHS)
NASSAU AIRPORT NEW
780730
25.05
–77.47
1A
1334
53
SETTLEMENT POINT
994390
26.68
–79.00
1A
1281
50
Bahamas (BHS)
NASSAU AIRPORT NEW
780730
25.05
–77.47
1A
1334
53
SETTLEMENT POINT
994390
26.68
–79.00
1A
1281
50
Bermuda (BMU)
BERMUDA INTL
780160
32.37
–64.68
2A
1456
57
Bahrain (BHR)
BAHRAIN (INT. AIRPORT)
411500
26.27
50.65
0B
57
2
Bolivia (BOL)
COCHABAMBA
852230
–17.42
–66.18
3B
472
19
LA PAZ/ALTO
852010
–16.52
–68.18
5A
535
21
VIRU-VIRU
852440
–17.63
–63.13
1A
1365
54
Barbados (BRB)
GRANTLEY ADAMS
789540
13.07
–59.48
0A
1155
45
Barbados (BRB)
GRANTLEY ADAMS
789540
13.07
–59.48
0A
1155
45
Belarus (BLR)
BARANOVICHI
269410
53.12
26.00
6A
610
24
BOBRUISK
269610
53.22
29.18
6A
622
24
BREST
330080
52.12
23.68
5A
601
24
Bosnia and Herzegovina (BIH)
BANJA LUKA
132420
44.78
17.22
4A
1056
42
BIHAC
132280
44.82
15.88
4A
1252
49
BJELASNICA
146520
43.72
18.27
7
1155
45

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 425

PDF Page 428

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
MOSTAR
133480
43.33
17.78
3A
1632
64
SARAJEVO/BUTMIR
133530
43.82
18.33
5A
993
39
SARAJEVO-BJELAVE
146540
43.87
18.43
5A
921
36
IVAILO
156280
42.22
24.33
4A
515
20
KALIAKPA
155620
43.37
28.47
4A
422
17
KURDJALI
157300
41.65
25.37
4A
633
25
KUSTENDIL
156010
42.27
22.77
4A
668
26
LOM
155110
43.82
23.25
4A
553
22
LOVETCH
155250
43.13
24.72
4A
663
26
MOURGASH
156000
42.83
23.67
7
714
28
MUSSALA (TOP/SOMMET)
156150
42.18
23.58
8
971
38
PLEVEN
155260
43.42
24.60
4A
584
23
PLOVDIV
156250
42.13
24.75
4A
518
20
RAZGRAD
155490
43.52
26.53
4A
582
23
ROUSSE
155350
43.85
25.95
4A
583
23
SANDANSKI
157120
41.52
23.27
4A
539
21
SHABLA
155610
43.53
28.53
4A
408
16
SHUMEN
155440
43.27
26.93
4A
559
22
SLIVEN
156400
42.67
26.32
4A
559
22
SOFIA (OBSERV.)
156140
42.65
23.38
5A
612
24
SVICHTOV
155330
43.62
25.35
4A
534
21
SVILENGRAD
157410
41.77
26.20
4A
577
23
VARNA
155520
43.20
27.92
4A
490
19
VELIKO TARNOVO
155300
43.08
25.65
4A
655
26
VIDIN
155020
43.82
22.88
4A
544
21
VRATZA
155050
43.20
23.53
4A
754
30
Botswana (BWA)
SERETSE KHAMA INTER
682400
–24.55
25.92
2B
449
18
Botswana (BWA)
SERETSE KHAMA INTER
682400
–24.55
25.92
2B
449
18
Brazil (BRA)
ANAPOLIS (BRAZ-AFB)
834190
–16.23
–48.97
2A
1584
62
ARACAJU (AEROPORTO)
830950
–10.98
–37.07
0A
1489
59
BELEM (AEROPORTO)
821930
–1.38
–48.48
0A
2958
116
BELO HORIZONTE
835870
–19.93
–43.93
2A
1477
58
BELO HORIZONTE (AERO)
835830
–19.85
–43.95
2A
1477
58
BOA VISTA (AEROPORTO)
820220
2.83
–60.70
0A
1547
61
BRASILIA (AEROPORTO)
833780
–15.87
–47.93
2A
1515
60
CAMPINAS (AEROPORTO)
837210
–23.00
–47.13
2A
1354
53
CAMPO GRANDE (AERO)
836120
–20.47
–54.67
1A
1498
59
CARAVELAS (AEROPORTO)
834970
–17.63
–39.25
1A
1472
58
CUIABA (AEROPORTO)
833620
–15.65
–56.10
0A
1346
53
CURITIBA (AEROPORTO)
838400
–25.52
–49.17
3A
1604
63
EDUARDO GOMES INTL
821110
–3.03
–60.05
0A
2282
90
FERNANDO DE NORONHA
824000
–3.85
–32.42
0A
1029
41
FLORIANOPOLIS (AERO)
838990
–27.67
–48.55
2A
1578
62
FORTALEZA (AEROPORTO)
823980
–3.78
–38.53
0A
1628
64
FOZ DO IGUACU (AERO)
838270
–25.52
–54.58
2A
1788
70
GALEAO
837460
–22.82
–43.25
1A
1397
55
GOIANIA (AEROPORTO)
834240
–16.63
–49.22
1A
1628
64
GUARULHOS
837753
–23.43
–46.47
2A
1472
58
LONDRINA (AEROPORTO)
837680
–23.33
–51.13
2A
1551
61
MACAPA
820980
0.03
–51.05
0A
2733
108
MACEIO (AEROPORTO)
829930
–9.52
–35.78
1A
1627
64
MANAUS (AEROPORTO)
823320
–3.15
–59.98
0A
2282
90
NATAL AEROPORTO
825990
–5.92
–35.25
0A
1306
51
PORTO ALEGRE (AERO)
839710
–30.00
–51.18
2A
1353
53
PORTO VELHO (AERO)
828240
–8.77
–63.92
0A
2230
88
RECIFE (AEROPORTO)
828990
–8.07
–34.85
0A
2353
93
RIO BRANCO
829170
–10.00
–67.80
1A
1451
57
RIO DE JANEIRO (AERO)
837550
–22.90
–43.17
1A
1154
45
SALVADOR (AEROPORTO)
832480
–12.90
–38.33
0A
1804
71
SANTAREM-AEROPORTO
822440
–2.43
–54.72
0A
2312
91
SAO LUIZ (AEROPORTO)
822810
–2.60
–44.23
0A
1982
78
SAO PAULO (AEROPORTO)
837800
–23.62
–46.65
2A
1511
59
TERESINA (AEROPORTO)
825790
–5.05
–42.82
0A
1392
55
UBERABA
835760
–19.78
–47.97
2A
1631
64
VITORIA (AEROPORTO)
836490
–20.27
–40.28
1A
1289
51
Brazil (BRA)
ANAPOLIS (BRAZ-AFB)
834190
–16.23
–48.97
2A
1584
62
ARACAJU (AEROPORTO)
830950
–10.98
–37.07
0A
1489
59
BELEM (AEROPORTO)
821930
–1.38
–48.48
0A
2958
116
BELO HORIZONTE
835870
–19.93
–43.93
2A
1477
58
BELO HORIZONTE (AERO)
835830
–19.85
–43.95
2A
1477
58
BOA VISTA (AEROPORTO)
820220
2.83
–60.70
0A
1547
61
BRASILIA (AEROPORTO)
833780
–15.87
–47.93
2A
1515
60
CAMPINAS (AEROPORTO)
837210
–23.00
–47.13
2A
1354
53
CAMPO GRANDE (AERO)
836120
–20.47
–54.67
1A
1498
59
CARAVELAS (AEROPORTO)
834970
–17.63
–39.25
1A
1472
58
CUIABA (AEROPORTO)
833620
–15.65
–56.10
0A
1346
53
CURITIBA (AEROPORTO)
838400
–25.52
–49.17
3A
1604
63
EDUARDO GOMES INTL
821110
–3.03
–60.05
0A
2282
90
FERNANDO DE NORONHA
824000
–3.85
–32.42
0A
1029
41
FLORIANOPOLIS (AERO)
838990
–27.67
–48.55
2A
1578
62
FORTALEZA (AEROPORTO)
823980
–3.78
–38.53
0A
1628
64
FOZ DO IGUACU (AERO)
838270
–25.52
–54.58
2A
1788
70
GALEAO
837460
–22.82
–43.25
1A
1397
55
GOIANIA (AEROPORTO)
834240
–16.63
–49.22
1A
1628
64
GUARULHOS
837753
–23.43
–46.47
2A
1472
58
LONDRINA (AEROPORTO)
837680
–23.33
–51.13
2A
1551
61
MACAPA
820980
0.03
–51.05
0A
2733
108
MACEIO (AEROPORTO)
829930
–9.52
–35.78
1A
1627
64
MANAUS (AEROPORTO)
823320
–3.15
–59.98
0A
2282
90
NATAL AEROPORTO
825990
–5.92
–35.25
0A
1306
51
PORTO ALEGRE (AERO)
839710
–30.00
–51.18
2A
1353
53
PORTO VELHO (AERO)
828240
–8.77
–63.92
0A
2230
88
RECIFE (AEROPORTO)
828990
–8.07
–34.85
0A
2353
93
RIO BRANCO
829170
–10.00
–67.80
1A
1451
57
RIO DE JANEIRO (AERO)
837550
–22.90
–43.17
1A
1154
45
SALVADOR (AEROPORTO)
832480
–12.90
–38.33
0A
1804
71
SANTAREM-AEROPORTO
822440
–2.43
–54.72
0A
2312
91
SAO LUIZ (AEROPORTO)
822810
–2.60
–44.23
0A
1982
78
SAO PAULO (AEROPORTO)
837800
–23.62
–46.65
2A
1511
59
TERESINA (AEROPORTO)
825790
–5.05
–42.82
0A
1392
55
UBERABA
835760
–19.78
–47.97
2A
1631
64
VITORIA (AEROPORTO)
836490
–20.27
–40.28
1A
1289
51
Brazil (BRA)
ANAPOLIS (BRAZ-AFB)
834190
–16.23
–48.97
2A
1584
62
ARACAJU (AEROPORTO)
830950
–10.98
–37.07
0A
1489
59
BELEM (AEROPORTO)
821930
–1.38
–48.48
0A
2958
116
BELO HORIZONTE
835870
–19.93
–43.93
2A
1477
58
BELO HORIZONTE (AERO)
835830
–19.85
–43.95
2A
1477
58
BOA VISTA (AEROPORTO)
820220
2.83
–60.70
0A
1547
61
BRASILIA (AEROPORTO)
833780
–15.87
–47.93
2A
1515
60
CAMPINAS (AEROPORTO)
837210
–23.00
–47.13
2A
1354
53
CAMPO GRANDE (AERO)
836120
–20.47
–54.67
1A
1498
59
CARAVELAS (AEROPORTO)
834970
–17.63
–39.25
1A
1472
58
CUIABA (AEROPORTO)
833620
–15.65
–56.10
0A
1346
53
CURITIBA (AEROPORTO)
838400
–25.52
–49.17
3A
1604
63
EDUARDO GOMES INTL
821110
–3.03
–60.05
0A
2282
90
FERNANDO DE NORONHA
824000
–3.85
–32.42
0A
1029
41
FLORIANOPOLIS (AERO)
838990
–27.67
–48.55
2A
1578
62
FORTALEZA (AEROPORTO)
823980
–3.78
–38.53
0A
1628
64
FOZ DO IGUACU (AERO)
838270
–25.52
–54.58
2A
1788
70
GALEAO
837460
–22.82
–43.25
1A
1397
55
GOIANIA (AEROPORTO)
834240
–16.63
–49.22
1A
1628
64
GUARULHOS
837753
–23.43
–46.47
2A
1472
58
LONDRINA (AEROPORTO)
837680
–23.33
–51.13
2A
1551
61
MACAPA
820980
0.03
–51.05
0A
2733
108
MACEIO (AEROPORTO)
829930
–9.52
–35.78
1A
1627
64
MANAUS (AEROPORTO)
823320
–3.15
–59.98
0A
2282
90
NATAL AEROPORTO
825990
–5.92
–35.25
0A
1306
51
PORTO ALEGRE (AERO)
839710
–30.00
–51.18
2A
1353
53
PORTO VELHO (AERO)
828240
–8.77
–63.92
0A
2230
88
RECIFE (AEROPORTO)
828990
–8.07
–34.85
0A
2353
93
RIO BRANCO
829170
–10.00
–67.80
1A
1451
57
RIO DE JANEIRO (AERO)
837550
–22.90
–43.17
1A
1154
45
SALVADOR (AEROPORTO)
832480
–12.90
–38.33
0A
1804
71
SANTAREM-AEROPORTO
822440
–2.43
–54.72
0A
2312
91
SAO LUIZ (AEROPORTO)
822810
–2.60
–44.23
0A
1982
78
SAO PAULO (AEROPORTO)
837800
–23.62
–46.65
2A
1511
59
TERESINA (AEROPORTO)
825790
–5.05
–42.82
0A
1392
55
UBERABA
835760
–19.78
–47.97
2A
1631
64
VITORIA (AEROPORTO)
836490
–20.27
–40.28
1A
1289
51
Burkina Faso (BFA)
BOBO-DIOULASSO
655100
11.17
–4.32
0A
1033
41
BOROMO
655160
11.75
–2.93
0A
883
35
DORI
655010
14.03
–0.03
0B
451
18
OUAGADOUGOU
655030
12.35
–1.52
0B
768
30
OUAHIGOUYA
655020
13.57
–2.42
0B
618
24
Brazil (BRA)
ANAPOLIS (BRAZ-AFB)
834190
–16.23
–48.97
2A
1584
62
ARACAJU (AEROPORTO)
830950
–10.98
–37.07
0A
1489
59
BELEM (AEROPORTO)
821930
–1.38
–48.48
0A
2958
116
BELO HORIZONTE
835870
–19.93
–43.93
2A
1477
58
BELO HORIZONTE (AERO)
835830
–19.85
–43.95
2A
1477
58
BOA VISTA (AEROPORTO)
820220
2.83
–60.70
0A
1547
61
BRASILIA (AEROPORTO)
833780
–15.87
–47.93
2A
1515
60
CAMPINAS (AEROPORTO)
837210
–23.00
–47.13
2A
1354
53
CAMPO GRANDE (AERO)
836120
–20.47
–54.67
1A
1498
59
CARAVELAS (AEROPORTO)
834970
–17.63
–39.25
1A
1472
58
CUIABA (AEROPORTO)
833620
–15.65
–56.10
0A
1346
53
CURITIBA (AEROPORTO)
838400
–25.52
–49.17
3A
1604
63
EDUARDO GOMES INTL
821110
–3.03
–60.05
0A
2282
90
FERNANDO DE NORONHA
824000
–3.85
–32.42
0A
1029
41
FLORIANOPOLIS (AERO)
838990
–27.67
–48.55
2A
1578
62
FORTALEZA (AEROPORTO)
823980
–3.78
–38.53
0A
1628
64
FOZ DO IGUACU (AERO)
838270
–25.52
–54.58
2A
1788
70
GALEAO
837460
–22.82
–43.25
1A
1397
55
GOIANIA (AEROPORTO)
834240
–16.63
–49.22
1A
1628
64
GUARULHOS
837753
–23.43
–46.47
2A
1472
58
LONDRINA (AEROPORTO)
837680
–23.33
–51.13
2A
1551
61
MACAPA
820980
0.03
–51.05
0A
2733
108
MACEIO (AEROPORTO)
829930
–9.52
–35.78
1A
1627
64
MANAUS (AEROPORTO)
823320
–3.15
–59.98
0A
2282
90
NATAL AEROPORTO
825990
–5.92
–35.25
0A
1306
51
PORTO ALEGRE (AERO)
839710
–30.00
–51.18
2A
1353
53
PORTO VELHO (AERO)
828240
–8.77
–63.92
0A
2230
88
RECIFE (AEROPORTO)
828990
–8.07
–34.85
0A
2353
93
RIO BRANCO
829170
–10.00
–67.80
1A
1451
57
RIO DE JANEIRO (AERO)
837550
–22.90
–43.17
1A
1154
45
SALVADOR (AEROPORTO)
832480
–12.90
–38.33
0A
1804
71
SANTAREM-AEROPORTO
822440
–2.43
–54.72
0A
2312
91
SAO LUIZ (AEROPORTO)
822810
–2.60
–44.23
0A
1982
78
SAO PAULO (AEROPORTO)
837800
–23.62
–46.65
2A
1511
59
TERESINA (AEROPORTO)
825790
–5.05
–42.82
0A
1392
55
UBERABA
835760
–19.78
–47.97
2A
1631
64
VITORIA (AEROPORTO)
836490
–20.27
–40.28
1A
1289
51
Cape Verde (CPV)
SAL
085940
16.73
–22.95
1B
219
9
Brazil (BRA)
ANAPOLIS (BRAZ-AFB)
834190
–16.23
–48.97
2A
1584
62
ARACAJU (AEROPORTO)
830950
–10.98
–37.07
0A
1489
59
BELEM (AEROPORTO)
821930
–1.38
–48.48
0A
2958
116
BELO HORIZONTE
835870
–19.93
–43.93
2A
1477
58
BELO HORIZONTE (AERO)
835830
–19.85
–43.95
2A
1477
58
BOA VISTA (AEROPORTO)
820220
2.83
–60.70
0A
1547
61
BRASILIA (AEROPORTO)
833780
–15.87
–47.93
2A
1515
60
CAMPINAS (AEROPORTO)
837210
–23.00
–47.13
2A
1354
53
CAMPO GRANDE (AERO)
836120
–20.47
–54.67
1A
1498
59
CARAVELAS (AEROPORTO)
834970
–17.63
–39.25
1A
1472
58
CUIABA (AEROPORTO)
833620
–15.65
–56.10
0A
1346
53
CURITIBA (AEROPORTO)
838400
–25.52
–49.17
3A
1604
63
EDUARDO GOMES INTL
821110
–3.03
–60.05
0A
2282
90
FERNANDO DE NORONHA
824000
–3.85
–32.42
0A
1029
41
FLORIANOPOLIS (AERO)
838990
–27.67
–48.55
2A
1578
62
FORTALEZA (AEROPORTO)
823980
–3.78
–38.53
0A
1628
64
FOZ DO IGUACU (AERO)
838270
–25.52
–54.58
2A
1788
70
GALEAO
837460
–22.82
–43.25
1A
1397
55
GOIANIA (AEROPORTO)
834240
–16.63
–49.22
1A
1628
64
GUARULHOS
837753
–23.43
–46.47
2A
1472
58
LONDRINA (AEROPORTO)
837680
–23.33
–51.13
2A
1551
61
MACAPA
820980
0.03
–51.05
0A
2733
108
MACEIO (AEROPORTO)
829930
–9.52
–35.78
1A
1627
64
MANAUS (AEROPORTO)
823320
–3.15
–59.98
0A
2282
90
NATAL AEROPORTO
825990
–5.92
–35.25
0A
1306
51
PORTO ALEGRE (AERO)
839710
–30.00
–51.18
2A
1353
53
PORTO VELHO (AERO)
828240
–8.77
–63.92
0A
2230
88
RECIFE (AEROPORTO)
828990
–8.07
–34.85
0A
2353
93
RIO BRANCO
829170
–10.00
–67.80
1A
1451
57
RIO DE JANEIRO (AERO)
837550
–22.90
–43.17
1A
1154
45
SALVADOR (AEROPORTO)
832480
–12.90
–38.33
0A
1804
71
SANTAREM-AEROPORTO
822440
–2.43
–54.72
0A
2312
91
SAO LUIZ (AEROPORTO)
822810
–2.60
–44.23
0A
1982
78
SAO PAULO (AEROPORTO)
837800
–23.62
–46.65
2A
1511
59
TERESINA (AEROPORTO)
825790
–5.05
–42.82
0A
1392
55
UBERABA
835760
–19.78
–47.97
2A
1631
64
VITORIA (AEROPORTO)
836490
–20.27
–40.28
1A
1289
51
Chad (TCD)
NDJAMENA
647000
12.13
15.03
0B
507
20
Brazil (BRA)
ANAPOLIS (BRAZ-AFB)
834190
–16.23
–48.97
2A
1584
62
ARACAJU (AEROPORTO)
830950
–10.98
–37.07
0A
1489
59
BELEM (AEROPORTO)
821930
–1.38
–48.48
0A
2958
116
BELO HORIZONTE
835870
–19.93
–43.93
2A
1477
58
BELO HORIZONTE (AERO)
835830
–19.85
–43.95
2A
1477
58
BOA VISTA (AEROPORTO)
820220
2.83
–60.70
0A
1547
61
BRASILIA (AEROPORTO)
833780
–15.87
–47.93
2A
1515
60
CAMPINAS (AEROPORTO)
837210
–23.00
–47.13
2A
1354
53
CAMPO GRANDE (AERO)
836120
–20.47
–54.67
1A
1498
59
CARAVELAS (AEROPORTO)
834970
–17.63
–39.25
1A
1472
58
CUIABA (AEROPORTO)
833620
–15.65
–56.10
0A
1346
53
CURITIBA (AEROPORTO)
838400
–25.52
–49.17
3A
1604
63
EDUARDO GOMES INTL
821110
–3.03
–60.05
0A
2282
90
FERNANDO DE NORONHA
824000
–3.85
–32.42
0A
1029
41
FLORIANOPOLIS (AERO)
838990
–27.67
–48.55
2A
1578
62
FORTALEZA (AEROPORTO)
823980
–3.78
–38.53
0A
1628
64
FOZ DO IGUACU (AERO)
838270
–25.52
–54.58
2A
1788
70
GALEAO
837460
–22.82
–43.25
1A
1397
55
GOIANIA (AEROPORTO)
834240
–16.63
–49.22
1A
1628
64
GUARULHOS
837753
–23.43
–46.47
2A
1472
58
LONDRINA (AEROPORTO)
837680
–23.33
–51.13
2A
1551
61
MACAPA
820980
0.03
–51.05
0A
2733
108
MACEIO (AEROPORTO)
829930
–9.52
–35.78
1A
1627
64
MANAUS (AEROPORTO)
823320
–3.15
–59.98
0A
2282
90
NATAL AEROPORTO
825990
–5.92
–35.25
0A
1306
51
PORTO ALEGRE (AERO)
839710
–30.00
–51.18
2A
1353
53
PORTO VELHO (AERO)
828240
–8.77
–63.92
0A
2230
88
RECIFE (AEROPORTO)
828990
–8.07
–34.85
0A
2353
93
RIO BRANCO
829170
–10.00
–67.80
1A
1451
57
RIO DE JANEIRO (AERO)
837550
–22.90
–43.17
1A
1154
45
SALVADOR (AEROPORTO)
832480
–12.90
–38.33
0A
1804
71
SANTAREM-AEROPORTO
822440
–2.43
–54.72
0A
2312
91
SAO LUIZ (AEROPORTO)
822810
–2.60
–44.23
0A
1982
78
SAO PAULO (AEROPORTO)
837800
–23.62
–46.65
2A
1511
59
TERESINA (AEROPORTO)
825790
–5.05
–42.82
0A
1392
55
UBERABA
835760
–19.78
–47.97
2A
1631
64
VITORIA (AEROPORTO)
836490
–20.27
–40.28
1A
1289
51
Chile (CHL)
ANTOFAGASTA
854420
–23.43
–70.45
3C
23
1
ARICA
854060
–18.47
–70.17
3B
24
1
BALMACEDA
858740
–45.92
–71.70
6A
600
24
CONCEPCION
856820
–36.77
–73.07
3C
1286
51
FARO EVANGELISTAS
859300
–52.40
–75.10
6A
1267
50
IQUIQUE
854180
–20.53
–70.18
3B
6
0
ISLA DIEGO RAMIREZ
859720
–56.50
–68.67
6A
1088
43
LA SERENA
854880
–29.92
–71.20
3C
80
3
PUDAHUEL
855740
–33.38
–70.78
3C
324
13
PUERTO MONTT
857990
–41.43
–73.10
4A
1742
69
PUNTA ARENAS
859340
–53.00
–70.97
6A
386
15
TEMUCO
857430
–38.75
–72.63
4C
1475
58
British Indian Ocean Territory (IOT)
DIEGO GARCIA NAF
619670
–7.30
72.40
0A
2026
80
British Indian Ocean Territory (IOT)
DIEGO GARCIA NAF
619670
–7.30
72.40
0A
2026
80
Brunei (BRN)
BRUNEI AIRPORT
963150
4.93
114.93
0A
2922
115
Brunei (BRN)
BRUNEI AIRPORT
963150
4.93
114.93
0A
2922
115
Brunei (BRN)
BRUNEI AIRPORT
963150
4.93
114.93
0A
2922
115
China (CHN)
ABAG QI
531920
44.02
114.95
7
242
10
AIHUI
504680
50.25
127.45
7
559
22
AKQI
517110
40.93
78.45
6B
187
7
ALAR
517300
40.50
81.05
5B
44
2
ALTAY
510760
47.73
88.08
7
188
7
ANDA
508540
46.38
125.32
7
429
17
Bulgaria (BGR)
BOTEV VRAH (TOP/SOMMET)
156270
42.67
24.83
7
884
35
BURGAS
156550
42.48
27.48
4A
588
23
CHERNI VRAH (TOP/SOMMET)
156130
42.58
23.27
7
775
30
CHIRPAN
156350
42.20
25.33
4A
589
23
ELHOVO
156420
42.18
26.57
4A
541
21
Bulgaria (BGR)
BOTEV VRAH (TOP/SOMMET)
156270
42.67
24.83
7
884
35
BURGAS
156550
42.48
27.48
4A
588
23
CHERNI VRAH (TOP/SOMMET)
156130
42.58
23.27
7
775
30
CHIRPAN
156350
42.20
25.33
4A
589
23
ELHOVO
156420
42.18
26.57
4A
541
21

426 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 429

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
ANDIR
518480
37.93
83.65
5B
21
1
ANKANG
572450
32.72
109.03
3A
834
33
ANQING
584240
30.53
117.05
3A
1370
54
ANYANG
538980
36.05
114.40
4B
569
22
ARXAN
507270
47.17
119.93
8
451
18
BACHU
517160
39.80
78.57
4B
52
2
BAILING-MIAO
533520
41.70
110.43
7
249
10
BAINGOIN
552790
31.37
90.02
7
304
12
BAISE
592110
23.90
106.60
2A
1090
43
BALGUNTAY
514670
42.67
86.33
6B
193
8
BAODING
546020
38.85
115.57
4B
536
21
BAOJI
570160
34.35
107.13
4A
690
27
BAOQING
508880
46.32
132.18
7
521
21
BAOSHAN
567480
25.12
99.18
3A
961
38
BARKAM
561720
31.90
102.23
5A
770
30
BATANG
562470
30.00
99.10
4B
473
19
BAYAN MOD
524950
40.75
104.50
6B
89
3
BAYANBULAK
515420
43.03
84.15
8
265
10
BAYTIK SHAN
512880
45.37
90.53
7
165
6
BEIHAI
596440
21.48
109.10
2A
1717
68
BEIJING
545110
39.93
116.28
4A
553
22
BENGBU
582210
32.95
117.37
3A
904
36
BENXI
543460
41.32
123.78
6A
812
32
BIJIE
577070
27.30
105.23
4A
882
35
BINHAI
545273
39.12
117.33
4A
556
22
BOXIAN
581020
33.88
115.77
4A
802
32
BUGT
506320
48.77
121.92
7
479
19
BUGT
542260
42.33
120.70
6B
420
17
CANGZHOU
546160
38.33
116.83
4A
613
24
CHANG DAO
547510
37.93
120.72
4A
586
23
CHANGBAI
543860
41.35
128.17
7
692
27
CHANGCHUN
541610
43.90
125.22
6A
580
23
CHANGDE
576620
29.05
111.68
3A
1303
51
CHANGLING
540490
44.25
123.97
6A
457
18
CHANGSHA
576870
28.23
112.87
3A
1426
56
CHANGTING
589110
25.85
116.37
3A
1734
68
CHAOYANG
543240
41.55
120.45
5A
478
19
CHENGDE
544230
40.98
117.95
5A
521
21
CHENGDU
562940
30.67
104.02
3A
921
36
CHENGSHANTOU
547760
37.40
122.68
4A
751
30
CHENZHOU
579720
25.80
113.03
2A
1487
59
CHIFENG
542180
42.27
118.97
6B
354
14
CHONGQING
575160
29.58
106.47
3A
1101
43
CHUXIONG
567680
25.02
101.52
3A
788
31
DA XIAN
573280
31.20
107.50
3A
1208
48
DACHEN DAO
586660
28.45
121.88
3A
1325
52
DALI
567510
25.70
100.18
3C
1055
42
DALIAN
546620
38.90
121.63
5A
633
25
DANDONG
544970
40.05
124.33
5A
969
38
DANXIAN
598450
19.52
109.58
1A
1803
71
DAOCHENG
563570
29.05
100.30
6A
623
25
DA-QAIDAM
527130
37.85
95.37
7
86
3
DARLAG
560460
33.75
99.65
7
546
22
DATONG
534870
40.10
113.33
6B
376
15
DAWU
561670
30.98
101.12
5A
596
23
DEGE
561440
31.80
98.57
5A
613
24
DELINGHA
527370
37.37
97.37
6B
159
6
DENGQEN
561160
31.42
95.60
7
636
25
DEQEN
564440
28.45
98.88
6A
655
26
DEZHOU
547140
37.43
116.32
4A
571
22
DINGHAI
584770
30.03
122.12
3A
1321
52
DINGTAO
549090
35.07
115.57
4A
687
27
DIWOPU
514635
43.90
87.47
6B
258
10
DONGFANG
598380
19.10
108.62
1A
935
37
DONGSHENG
535430
39.83
109.98
6B
393
15
DONGTAI
582510
32.85
120.28
4A
1036
41
DULAN
528360
36.30
98.10
7
201
8
DUNHUA
541860
43.37
128.20
7
634
25
DUNHUANG
524180
40.15
94.68
5B
38
1
DUOLUN
542080
42.18
116.47
7
366
14
DUSHAN
579220
25.83
107.55
3A
1329
52
EJIN QI
522670
41.95
101.07
5B
31
1
EMEI SHAN
563850
29.52
103.33
7
1863
73
ENSHI
574470
30.28
109.47
3A
1470
58
ERENHOT
530680
43.65
112.00
7
136
5
FANGXIAN
572590
32.03
110.77
4A
854
34
FENGJIE
573480
31.02
109.53
3A
1142
45
FENGNING
543080
41.22
116.63
6A
463
18
FEZXZAN
549290
35.25
117.95
4A
863
34
FOGANG
590870
23.87
113.53
2A
2198
87
FUDING
587540
27.33
120.20
3A
1677
66
FUJIN
507880
47.23
131.98
7
513
20
FUYANG
582030
32.87
115.73
3A
876
34
FUYUN
510870
46.98
89.52
7
167
7
FUZHOU
588470
26.08
119.28
2A
1352
53
GANGCA
527540
37.33
100.13
7
380
15
GANYU
580400
34.83
119.13
4A
941
37
GANZHOU
579930
25.87
115.00
2A
1426
56
GAOYAO
592780
23.05
112.47
2A
1645
65
GARZE
561460
31.62
100.00
6A
635
25
GENGMA
569460
23.55
99.40
2A
1362
54
GOLMUD
528180
36.42
94.90
6B
41
2
GUAIZIHU
523780
41.37
102.37
5B
34
1
GUANGCHANG
588130
26.85
116.33
2A
1719
68
GUANGHUA
572650
32.38
111.67
3A
846
33
GUANGNAN
590070
24.07
105.07
3A
1037
41
GUANGZHOU
592870
23.17
113.33
2A
1726
68
GUILIN
579570
25.33
110.30
2A
1830
72
GUIPING
592540
23.40
110.08
2A
1670
66
GUIYANG
578160
26.58
106.73
3A
1166
46
GUSHI
582080
32.17
115.67
3A
1081
43
HAIKOU
597580
20.03
110.35
1A
1662
65
HAILAR
505270
49.22
119.75
7
346
14
HAILS
532310
41.45
106.38
6B
110
4
HAILUN
507560
47.43
126.97
7
551
22
HAIYANG
548630
36.77
121.17
4A
778
31

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 427

PDF Page 430

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
HAIYANG DAO
545870
39.05
123.22
4A
788
31
HALIUT
533360
41.57
108.52
6B
200
8
HAMI
522030
42.82
93.52
5B
36
1
HANGZHOU
584570
30.23
120.17
3A
1380
54
HANZHONG
571270
33.07
107.03
4A
900
35
HARBIN
509530
45.75
126.77
7
527
21
HECHI
590230
24.70
108.05
2A
1471
58
HEFEI
583210
31.87
117.23
3A
984
39
HENAN
560650
34.73
101.60
7
597
24
HEQU
535640
39.38
111.15
5B
418
16
HEYUAN
592930
23.80
114.73
2A
1922
76
HEZE/CAOZHOU
549060
35.25
115.43
4A
646
25
HEZUO
560800
35.00
102.90
7
549
22
HOBOKSAR
511560
46.78
85.72
7
136
5
HOHHOT
534630
40.82
111.68
6B
400
16
HONG KONG INTERNATI
450070
22.32
113.92
1A
1894
75
HONG KONG OBSERVATO
450050
22.30
114.17
2A
2225
88
HOTAN
518280
37.13
79.93
4B
35
1
HUA SHAN
570460
34.48
110.08
6A
875
34
HUADE
533910
41.90
114.00
7
319
13
HUADIAN
542730
42.98
126.75
7
743
29
HUAILAI
544050
40.40
115.50
5B
387
15
HUAJIALING
529960
35.38
105.00
7
513
20
HUANG SHAN
584370
30.13
118.15
5A
2317
91
HUILI
566710
26.65
102.25
3C
1134
45
HUIMIN
547250
37.50
117.53
4A
585
23
HUIZE
566840
26.42
103.28
3A
776
31
HULIN
509830
45.77
132.97
7
556
22
HUMA
503530
51.72
126.65
7
467
18
HUOSHAN
583140
31.40
116.33
3A
1339
53
JARTAI
535020
39.78
105.75
5B
103
4
JARUD QI
540260
44.57
120.90
6B
386
15
JIAN
543770
41.10
126.15
2A
942
37
JIAN
577990
27.12
114.97
6A
1477
58
JIANGCHENG
569770
22.62
101.82
2A
2229
88
JIANGLING
574760
30.33
112.18
3A
1083
43
JIEXIU
538630
37.03
111.92
5B
498
20
JINAN
548230
36.60
117.05
4A
733
29
JINGDEZHEN
585270
29.30
117.20
3A
1694
67
JINGHE
513340
44.62
82.90
6B
96
4
JINGHONG
569590
22.00
100.78
1A
1173
46
JINING
534800
41.03
113.07
7
361
14
JINZHOU
543370
41.13
121.12
5A
581
23
JIULONG
564620
29.00
101.50
5A
907
36
JIUQUAN
525330
39.77
98.48
5B
85
3
JIUXIAN SHAN
589310
25.72
118.10
4A
1720
68
JIXI
509780
45.28
130.95
7
546
21
JURH
532760
42.40
112.90
6B
213
8
KABA HE
510530
48.05
86.35
6B
176
7
KANGDING
563740
30.05
101.97
5A
801
32
KARAMAY
512430
45.60
84.85
6B
104
4
KASHI
517090
39.47
75.98
4B
62
2
KESHAN
506580
48.05
125.88
7
486
19
KORLA
516560
41.75
86.13
5B
53
2
KUANDIAN
544930
40.72
124.78
6A
1100
43
KUNMING
567780
25.02
102.68
3C
1004
40
KUOCANG SHAN
586530
28.82
120.92
5A
2097
83
KUQA
516440
41.72
82.95
5B
62
2
LANCANG
569540
22.57
99.93
2A
1639
65
LANGZHONG
573060
31.58
105.97
3A
1039
41
LANZHOU
528890
36.05
103.88
5B
317
12
LENGHU
526020
38.83
93.38
7
17
1
LETING
545390
39.43
118.90
5A
638
25
LHASA
555910
29.67
91.13
5B
440
17
LHUNZE
556960
28.42
92.47
6B
269
11
LIAN XIAN
590720
24.78
112.38
2A
1578
62
LIANGPING
574260
30.68
107.80
3A
1301
51
LIANPING
590960
24.37
114.48
2A
1781
70
LIJING
566510
26.83
100.47
3C
954
38
LINCANG
569510
23.95
100.22
3A
1187
47
LINDONG
540270
43.98
119.40
6B
370
15
LINGLING
578660
26.23
111.62
3A
1352
53
LINGXIAN
547150
37.33
116.57
4B
522
21
LINHAI
586600
28.85
121.13
3A
1778
70
LINHE
535130
40.77
107.40
5B
135
5
LINJIANG
543740
41.72
126.92
6A
837
33
LINXI
541150
43.60
118.07
6B
368
14
LINYI
549380
35.05
118.35
4A
870
34
LISHI
537640
37.50
111.10
5A
500
20
LISHUI
586460
28.45
119.92
3A
1371
54
LITANG
562570
30.00
100.27
7
712
28
LIUZHOU
590460
24.35
109.40
2A
1388
55
LIYANG
583450
31.43
119.48
3A
1144
45
LONGKOU
547530
37.62
120.32
4A
618
24
LONGYAN
589270
25.10
117.02
2A
1713
67
LONGZHOU
594170
22.37
106.75
2A
1380
54
LU SHAN
585060
29.58
115.98
4A
1965
77
LUODIAN
579160
25.43
106.77
2A
1150
45
LUSHI
570670
34.05
111.03
4A
636
25
LUSI
582650
32.07
121.60
3A
1037
41
LUXI
568860
24.53
103.77
3A
957
38
LUZHOU
576020
28.88
105.43
3A
1152
45
MACHENG
573990
31.18
114.97
3A
1216
48
MADOI
560330
34.92
98.22
8
309
12
MANDAL
531490
42.53
110.13
6B
168
7
MANGNAI
518860
38.25
90.85
7
49
2
MAZONG SHAN
523230
41.80
97.03
7
76
3
MEI XIAN
591170
24.30
116.12
2A
1509
59
MENGDING
569450
23.57
99.08
2A
1519
60
MENGJIN
570710
34.82
112.43
4A
603
24
MENGLA
569690
21.50
101.58
2A
1522
60
MENGSHAN
590580
24.20
110.52
2A
1691
67
MENGZI
569850
23.38
103.38
2A
855
34
MIANYANG
561960
31.45
104.73
3A
925
36
MINFENG
518390
37.07
82.72
5B
41
2
MINQIN
526810
38.63
103.08
5B
111
4

428 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 431

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
MOHE
501360
52.13
122.52
8
414
16
MUDANJIANG
540940
44.57
129.60
7
535
21
NAGQU
552990
31.48
92.07
7
424
17
NANCHANG
586060
28.60
115.92
3A
1523
60
NANCHENG
587150
27.58
116.65
3A
1649
65
NANCHONG
574110
30.80
106.08
3A
1026
40
NANJING
582380
32.00
118.80
3A
1031
41
NANNING
594310
22.82
108.35
2A
1294
51
NANPING
588340
26.63
118.00
2A
1655
65
NANYANG
571780
33.03
112.58
4A
788
31
NANYUE
577760
27.30
112.70
4A
2004
79
NAPO
592090
23.30
105.95
2A
1407
55
NARAN BULAG
530830
44.62
114.15
7
222
9
NEIJIANG
575040
29.58
105.05
3A
1058
42
NENJIANG
505570
49.17
125.23
7
481
19
NYINGCHI
563120
29.57
94.47
5A
660
26
OTOG QI
535290
39.10
107.98
6B
262
10
PAGRI
557730
27.73
89.08
7
415
16
PINGLIANG
539150
35.55
106.67
5A
518
20
PINGTAN
589440
25.52
119.78
2A
1192
47
PINGWU
561930
32.42
104.52
3A
837
33
PISHAN
518180
37.62
78.28
4B
50
2
POTOU
546180
38.08
116.55
4B
554
22
PUCHENG
587310
27.92
118.53
3A
1687
66
QAMDO
561370
31.15
97.17
5A
473
19
QIAN GORLOS
509490
45.08
124.87
6A
438
17
QIEMO/QARQAN
518550
38.15
85.55
5B
23
1
QINGDAO
548570
36.07
120.33
4A
730
29
QINGJIANG
581440
33.60
119.03
4A
919
36
QINGLONG
544360
40.40
118.95
5A
715
28
QINGYUAN
542590
42.10
124.95
6A
811
32
QINZHOU
596320
21.95
108.62
2A
2136
84
QIONGHAI
598550
19.23
110.47
1A
1999
79
QIQIHAR
507450
47.38
123.92
7
430
17
QITAI
513790
44.02
89.57
6B
175
7
QIXIAN SHAN
587260
27.95
117.83
4A
2021
80
QU XIAN
586330
28.97
118.87
3A
1630
64
QUMARLEB
560210
34.13
95.78
8
407
16
RIZHAO
549450
35.43
119.53
4A
891
35
RONGJIANG
579320
25.97
108.53
3A
1177
46
RUILI
568380
24.02
97.83
2A
1400
55
RUOERGAI
560790
33.58
102.97
7
661
26
RUOQIANG
517770
39.03
88.17
5B
25
1
SANGZHI
575540
29.40
110.17
3A
1392
55
SANHU DAO
599850
16.53
111.62
0A
1321
52
SANSUI
578320
26.97
108.67
3A
1112
44
SERTAR
561520
32.28
100.33
7
649
26
SHACHE
518110
38.43
77.27
4B
47
2
SHANGCHUAN DAO
596730
21.73
112.77
2A
2159
85
SHANGHAI
583620
31.40
121.47
3A
1130
45
SHANGHAI/HONGQIAO
583670
31.17
121.43
3A
1125
44
SHANGZHI
509680
45.22
127.97
7
666
26
SHANTOU
593160
23.40
116.68
2A
1579
62
SHANWEI
595010
22.78
115.37
2A
1806
71
SHAOGUAN
590820
24.80
113.58
2A
1493
59
SHAOWU
587250
27.33
117.47
3A
1793
71
SHAOYANG
577660
27.23
111.47
3A
1303
51
SHENG SHANG
584730
30.72
122.82
3A
1431
56
SHENGSI
584720
30.73
122.45
3A
987
39
SHENGXIAN
585560
29.60
120.82
3A
1282
50
SHENYANG
543420
41.73
123.52
6A
683
27
SHENZHEN
594930
22.55
114.10
2A
1837
72
SHEYANG
581500
33.77
120.25
4A
1030
41
SHIJIAZHUANG
536980
38.03
114.42
4B
528
21
SHIPU
585690
29.20
121.95
3A
1423
56
SHIQUANHE
552280
32.50
80.08
7
67
3
SHISANJIANFANG
514950
43.22
91.73
5B
27
1
SIMAO
569640
22.77
100.98
2A
1513
60
SINAN
577310
27.95
108.25
3A
1123
44
SIPING
541570
43.18
124.33
6A
638
25
SOG XIAN
561060
31.88
93.78
7
569
22
SONGPAN
561820
32.65
103.57
5A
718
28
SUIFENHE
540960
44.38
131.15
7
564
22
SUNWU
505640
49.43
127.35
7
547
22
TACHENG
511330
46.73
83.00
6B
281
11
TAI SHAN
548260
36.25
117.10
6A
1086
43
TAILAI
508440
46.40
123.42
7
391
15
TAISHAN
588530
27.00
120.70
3A
1099
43
TAIYUAN
537720
37.78
112.55
5B
448
18
TANGSHAN
545340
39.67
118.15
4A
635
25
TAOXIAN
543424
41.63
123.48
6A
729
29
TENGCHONG
567390
25.12
98.48
3A
1494
59
TIANJIN
545270
39.10
117.17
4A
559
22
TIANMU SHAN (MTNS)
584450
30.35
119.42
5A
1690
67
TIANSHUI
570060
34.58
105.75
4A
539
21
TIKANLIK
517650
40.63
87.70
5B
37
1
TINGRI
556640
28.63
87.08
7
355
14
TONGCHUAN
539470
35.17
109.05
5A
578
23
TONGDAO
578450
26.17
109.78
3A
1418
56
TONGDE
529570
35.27
100.65
7
427
17
TONGHE
509630
45.97
128.73
7
596
23
TONGLIAO
541350
43.60
122.27
6B
373
15
TRUONG SA
489200
8.65
111.92
0A
1942
76
TULIHE
504340
50.45
121.70
8
457
18
TUOTUOHE
560040
34.22
92.43
8
266
10
TURPAN
515730
42.93
89.20
4B
16
1
ULIASTAI
509150
45.52
116.97
7
249
10
WANYUAN
572370
32.07
108.03
3A
1236
49
WEICHANG
543110
41.93
117.75
6A
422
17
WEIFANG
548430
36.77
119.18
4A
621
24
WEINING
566910
26.87
104.28
4A
928
37
WENZHOU
586590
28.02
120.67
3A
1698
67
WU LU MU QI
514630
43.80
87.65
6B
257
10
WUDAOLIANG
529080
35.22
93.08
8
264
10
WUDU
560960
33.40
104.92
3B
485
19
WUGANG
578530
26.73
110.63
3A
1381
54

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 429

PDF Page 432

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
WUHAN
574940
30.62
114.13
3A
1218
48
WUHU
583380
31.33
118.35
3A
1161
46
WUSHAOLING
527870
37.20
102.87
7
390
15
WUTAI SHAN
535880
38.95
113.52
8
815
32
WUYISHAN
587300
27.77
118.03
3A
1905
75
WUZHOU
592650
23.48
111.30
2A
1487
59
XAINZA
554720
30.95
88.63
7
285
11
XI UJIMQIN QI
540120
44.58
117.60
7
333
13
XIAMEN
591340
24.48
118.08
2A
1185
47
XIAN
570360
34.30
108.93
4B
562
22
XIAOERGOU
505480
49.20
123.72
7
490
19
XICHANG
565710
27.90
102.27
3A
968
38
XIFENGZHEN
539230
35.73
107.63
5A
569
22
XIGAZE
555780
29.25
88.88
6C
432
17
XIHUA
571930
33.78
114.52
4A
745
29
XILIN HOT
541020
43.95
116.12
7
277
11
XIN BARAG YOUQI
506030
48.67
116.82
7
250
10
XINGREN
579020
25.43
105.18
3A
1332
52
XINGTAI
537980
37.07
114.50
4B
527
21
XINING
528660
36.62
101.77
6B
371
15
XINXIAN
548080
36.23
115.67
4A
579
23
XINYANG
572970
32.13
114.05
3A
1115
44
XINYI
594560
22.35
110.93
2A
1781
70
XISHA DAO
599810
16.83
112.33
0A
1496
59
XIUSHUI
575980
29.03
114.58
3A
1538
61
XUNWU
591020
24.95
115.65
2A
1651
65
XUZHOU
580270
34.28
117.15
4A
828
33
YAAN
562870
29.98
103.00
3A
1724
68
YAN AN
538450
36.60
109.50
5A
561
22
YANCHI
537230
37.80
107.38
5B
278
11
YANGCHENG
539750
35.48
112.40
4A
616
24
YANGJIANG
596630
21.87
111.97
2A
2276
90
YANJI
542920
42.87
129.50
6A
514
20
YANZHOU
549160
35.57
116.85
4A
689
27
YAXIAN
599480
18.23
109.52
0A
1248
49
YIBIN
564920
28.80
104.60
3A
1147
45
YICHANG
574610
30.70
111.30
3A
1178
46
YICHUN
507740
47.72
128.90
7
643
25
YICHUN
577930
27.80
114.38
3A
1602
63
YINCHUAN
536140
38.47
106.20
5B
196
8
YINGKOU
544710
40.67
122.20
5A
675
27
YINING
514310
43.95
81.33
5B
262
10
YIWU
521180
43.27
94.70
7
90
4
YIYUAN
548360
36.18
118.15
4A
701
28
YONGAN
589210
25.97
117.35
2A
1566
62
YOUYANG
576330
28.83
108.77
3A
1360
54
YU XIAN
535930
39.83
114.57
6B
408
16
YUANJIANG
569660
23.60
101.98
1A
782
31
YUANLING
576550
28.47
110.40
3A
1422
56
YUANMOU
567630
25.73
101.87
2B
619
24
YUANPING
536730
38.75
112.70
5B
424
17
YUEYANG
575840
29.38
113.08
3A
1264
50
YULIN
536460
38.23
109.70
5B
402
16
YUMENZHEN
524360
40.27
97.03
6B
59
2
YUNCHENG
539590
35.05
111.05
4B
545
21
YUSHE
537870
37.07
112.98
5A
587
23
YUSHU
560290
33.02
97.02
7
487
19
YUTIAN/KERIYA
519310
36.87
81.70
5B
50
2
ZADOI
560180
32.90
95.30
7
531
21
ZAOYANG
572790
32.15
112.67
3A
862
34
ZHANG PING
589260
25.30
117.40
2A
1537
61
ZHANGJIAKOU
544010
40.78
114.88
5B
399
16
ZHANGWU
542360
42.42
122.53
6A
512
20
ZHANGYE
526520
38.93
100.43
5B
128
5
ZHANJIANG
596580
21.22
110.40
1A
1634
64
ZHANYI
567860
25.58
103.83
3C
830
33
ZHAOTONG
565860
27.33
103.75
4A
725
29
ZHENGZHOU
570830
34.72
113.65
4A
641
25
ZHIJIANG
577450
27.45
109.68
3A
1239
49
ZHONGNING
537050
37.48
105.68
5B
216
9
ZHONGXIANG
573780
31.17
112.57
3A
962
38
ZHUMADIAN
572900
33.00
114.02
4A
978
38
ZUNYI
577130
27.70
106.88
3A
1067
42
WUHAN
574940
30.62
114.13
3A
1218
48
WUHU
583380
31.33
118.35
3A
1161
46
WUSHAOLING
527870
37.20
102.87
7
390
15
WUTAI SHAN
535880
38.95
113.52
8
815
32
WUYISHAN
587300
27.77
118.03
3A
1905
75
WUZHOU
592650
23.48
111.30
2A
1487
59
XAINZA
554720
30.95
88.63
7
285
11
XI UJIMQIN QI
540120
44.58
117.60
7
333
13
XIAMEN
591340
24.48
118.08
2A
1185
47
XIAN
570360
34.30
108.93
4B
562
22
XIAOERGOU
505480
49.20
123.72
7
490
19
XICHANG
565710
27.90
102.27
3A
968
38
XIFENGZHEN
539230
35.73
107.63
5A
569
22
XIGAZE
555780
29.25
88.88
6C
432
17
XIHUA
571930
33.78
114.52
4A
745
29
XILIN HOT
541020
43.95
116.12
7
277
11
XIN BARAG YOUQI
506030
48.67
116.82
7
250
10
XINGREN
579020
25.43
105.18
3A
1332
52
XINGTAI
537980
37.07
114.50
4B
527
21
XINING
528660
36.62
101.77
6B
371
15
XINXIAN
548080
36.23
115.67
4A
579
23
XINYANG
572970
32.13
114.05
3A
1115
44
XINYI
594560
22.35
110.93
2A
1781
70
XISHA DAO
599810
16.83
112.33
0A
1496
59
XIUSHUI
575980
29.03
114.58
3A
1538
61
XUNWU
591020
24.95
115.65
2A
1651
65
XUZHOU
580270
34.28
117.15
4A
828
33
YAAN
562870
29.98
103.00
3A
1724
68
YAN AN
538450
36.60
109.50
5A
561
22
YANCHI
537230
37.80
107.38
5B
278
11
YANGCHENG
539750
35.48
112.40
4A
616
24
YANGJIANG
596630
21.87
111.97
2A
2276
90
YANJI
542920
42.87
129.50
6A
514
20
YANZHOU
549160
35.57
116.85
4A
689
27
YAXIAN
599480
18.23
109.52
0A
1248
49
YIBIN
564920
28.80
104.60
3A
1147
45
YICHANG
574610
30.70
111.30
3A
1178
46
YICHUN
507740
47.72
128.90
7
643
25
YICHUN
577930
27.80
114.38
3A
1602
63
YINCHUAN
536140
38.47
106.20
5B
196
8
YINGKOU
544710
40.67
122.20
5A
675
27
YINING
514310
43.95
81.33
5B
262
10
YIWU
521180
43.27
94.70
7
90
4
YIYUAN
548360
36.18
118.15
4A
701
28
YONGAN
589210
25.97
117.35
2A
1566
62
YOUYANG
576330
28.83
108.77
3A
1360
54
YU XIAN
535930
39.83
114.57
6B
408
16
YUANJIANG
569660
23.60
101.98
1A
782
31
YUANLING
576550
28.47
110.40
3A
1422
56
YUANMOU
567630
25.73
101.87
2B
619
24
YUANPING
536730
38.75
112.70
5B
424
17
YUEYANG
575840
29.38
113.08
3A
1264
50
YULIN
536460
38.23
109.70
5B
402
16
Christmas Island (CRX)
CHRISTMAS ISLAND AE
969950
–10.45
105.68
1A
1848
73
Cocos (Keeling) Islands (CCK)
COCOS ISLAND AERO
969960
–12.18
96.83
0A
1865
73
WUHAN
574940
30.62
114.13
3A
1218
48
WUHU
583380
31.33
118.35
3A
1161
46
WUSHAOLING
527870
37.20
102.87
7
390
15
WUTAI SHAN
535880
38.95
113.52
8
815
32
WUYISHAN
587300
27.77
118.03
3A
1905
75
WUZHOU
592650
23.48
111.30
2A
1487
59
XAINZA
554720
30.95
88.63
7
285
11
XI UJIMQIN QI
540120
44.58
117.60
7
333
13
XIAMEN
591340
24.48
118.08
2A
1185
47
XIAN
570360
34.30
108.93
4B
562
22
XIAOERGOU
505480
49.20
123.72
7
490
19
XICHANG
565710
27.90
102.27
3A
968
38
XIFENGZHEN
539230
35.73
107.63
5A
569
22
XIGAZE
555780
29.25
88.88
6C
432
17
XIHUA
571930
33.78
114.52
4A
745
29
XILIN HOT
541020
43.95
116.12
7
277
11
XIN BARAG YOUQI
506030
48.67
116.82
7
250
10
XINGREN
579020
25.43
105.18
3A
1332
52
XINGTAI
537980
37.07
114.50
4B
527
21
XINING
528660
36.62
101.77
6B
371
15
XINXIAN
548080
36.23
115.67
4A
579
23
XINYANG
572970
32.13
114.05
3A
1115
44
XINYI
594560
22.35
110.93
2A
1781
70
XISHA DAO
599810
16.83
112.33
0A
1496
59
XIUSHUI
575980
29.03
114.58
3A
1538
61
XUNWU
591020
24.95
115.65
2A
1651
65
XUZHOU
580270
34.28
117.15
4A
828
33
YAAN
562870
29.98
103.00
3A
1724
68
YAN AN
538450
36.60
109.50
5A
561
22
YANCHI
537230
37.80
107.38
5B
278
11
YANGCHENG
539750
35.48
112.40
4A
616
24
YANGJIANG
596630
21.87
111.97
2A
2276
90
YANJI
542920
42.87
129.50
6A
514
20
YANZHOU
549160
35.57
116.85
4A
689
27
YAXIAN
599480
18.23
109.52
0A
1248
49
YIBIN
564920
28.80
104.60
3A
1147
45
YICHANG
574610
30.70
111.30
3A
1178
46
YICHUN
507740
47.72
128.90
7
643
25
YICHUN
577930
27.80
114.38
3A
1602
63
YINCHUAN
536140
38.47
106.20
5B
196
8
YINGKOU
544710
40.67
122.20
5A
675
27
YINING
514310
43.95
81.33
5B
262
10
YIWU
521180
43.27
94.70
7
90
4
YIYUAN
548360
36.18
118.15
4A
701
28
YONGAN
589210
25.97
117.35
2A
1566
62
YOUYANG
576330
28.83
108.77
3A
1360
54
YU XIAN
535930
39.83
114.57
6B
408
16
YUANJIANG
569660
23.60
101.98
1A
782
31
YUANLING
576550
28.47
110.40
3A
1422
56
YUANMOU
567630
25.73
101.87
2B
619
24
YUANPING
536730
38.75
112.70
5B
424
17
YUEYANG
575840
29.38
113.08
3A
1264
50
YULIN
536460
38.23
109.70
5B
402
16
Colombia (COL)
BARRANQUILLA/ERNEST
800280
10.88
–74.78
0A
824
32
BOGOTA/ELDORADO
802220
4.70
–74.13
3A
900
35
CALI/ALFONSO BONILL
802590
3.55
–76.38
1A
967
38
CARTAGENA/RAFAEL NU
800220
10.45
–75.52
0A
1055
42
RIONEGRO/J.M.CORDOV
801120
6.13
–75.43
3A
1934
76
WUHAN
574940
30.62
114.13
3A
1218
48
WUHU
583380
31.33
118.35
3A
1161
46
WUSHAOLING
527870
37.20
102.87
7
390
15
WUTAI SHAN
535880
38.95
113.52
8
815
32
WUYISHAN
587300
27.77
118.03
3A
1905
75
WUZHOU
592650
23.48
111.30
2A
1487
59
XAINZA
554720
30.95
88.63
7
285
11
XI UJIMQIN QI
540120
44.58
117.60
7
333
13
XIAMEN
591340
24.48
118.08
2A
1185
47
XIAN
570360
34.30
108.93
4B
562
22
XIAOERGOU
505480
49.20
123.72
7
490
19
XICHANG
565710
27.90
102.27
3A
968
38
XIFENGZHEN
539230
35.73
107.63
5A
569
22
XIGAZE
555780
29.25
88.88
6C
432
17
XIHUA
571930
33.78
114.52
4A
745
29
XILIN HOT
541020
43.95
116.12
7
277
11
XIN BARAG YOUQI
506030
48.67
116.82
7
250
10
XINGREN
579020
25.43
105.18
3A
1332
52
XINGTAI
537980
37.07
114.50
4B
527
21
XINING
528660
36.62
101.77
6B
371
15
XINXIAN
548080
36.23
115.67
4A
579
23
XINYANG
572970
32.13
114.05
3A
1115
44
XINYI
594560
22.35
110.93
2A
1781
70
XISHA DAO
599810
16.83
112.33
0A
1496
59
XIUSHUI
575980
29.03
114.58
3A
1538
61
XUNWU
591020
24.95
115.65
2A
1651
65
XUZHOU
580270
34.28
117.15
4A
828
33
YAAN
562870
29.98
103.00
3A
1724
68
YAN AN
538450
36.60
109.50
5A
561
22
YANCHI
537230
37.80
107.38
5B
278
11
YANGCHENG
539750
35.48
112.40
4A
616
24
YANGJIANG
596630
21.87
111.97
2A
2276
90
YANJI
542920
42.87
129.50
6A
514
20
YANZHOU
549160
35.57
116.85
4A
689
27
YAXIAN
599480
18.23
109.52
0A
1248
49
YIBIN
564920
28.80
104.60
3A
1147
45
YICHANG
574610
30.70
111.30
3A
1178
46
YICHUN
507740
47.72
128.90
7
643
25
YICHUN
577930
27.80
114.38
3A
1602
63
YINCHUAN
536140
38.47
106.20
5B
196
8
YINGKOU
544710
40.67
122.20
5A
675
27
YINING
514310
43.95
81.33
5B
262
10
YIWU
521180
43.27
94.70
7
90
4
YIYUAN
548360
36.18
118.15
4A
701
28
YONGAN
589210
25.97
117.35
2A
1566
62
YOUYANG
576330
28.83
108.77
3A
1360
54
YU XIAN
535930
39.83
114.57
6B
408
16
YUANJIANG
569660
23.60
101.98
1A
782
31
YUANLING
576550
28.47
110.40
3A
1422
56
YUANMOU
567630
25.73
101.87
2B
619
24
YUANPING
536730
38.75
112.70
5B
424
17
YUEYANG
575840
29.38
113.08
3A
1264
50
YULIN
536460
38.23
109.70
5B
402
16
Congo (COG)
BRAZZAVILLE/MAYA-M
644500
–4.25
15.25
1A
1375
54
Cook Islands (COK)
AMURI/AITUTAKI ISL
918300
–18.83
–159.77
1A
1964
77
MANGAIA ISLAND
918470
–21.92
–157.95
1A
1969
78
MAUKE ISLAND
918400
–20.13
–157.35
1A
1653
65
PENRHYN ISLAND
918000
–9.02
–158.07
0A
1573
62
PUKAPUKA
918110
–10.88
–165.82
0A
2788
110
RAROTONGA
918430
–21.20
–159.82
1A
2176
86
WUHAN
574940
30.62
114.13
3A
1218
48
WUHU
583380
31.33
118.35
3A
1161
46
WUSHAOLING
527870
37.20
102.87
7
390
15
WUTAI SHAN
535880
38.95
113.52
8
815
32
WUYISHAN
587300
27.77
118.03
3A
1905
75
WUZHOU
592650
23.48
111.30
2A
1487
59
XAINZA
554720
30.95
88.63
7
285
11
XI UJIMQIN QI
540120
44.58
117.60
7
333
13
XIAMEN
591340
24.48
118.08
2A
1185
47
XIAN
570360
34.30
108.93
4B
562
22
XIAOERGOU
505480
49.20
123.72
7
490
19
XICHANG
565710
27.90
102.27
3A
968
38
XIFENGZHEN
539230
35.73
107.63
5A
569
22
XIGAZE
555780
29.25
88.88
6C
432
17
XIHUA
571930
33.78
114.52
4A
745
29
XILIN HOT
541020
43.95
116.12
7
277
11
XIN BARAG YOUQI
506030
48.67
116.82
7
250
10
XINGREN
579020
25.43
105.18
3A
1332
52
XINGTAI
537980
37.07
114.50
4B
527
21
XINING
528660
36.62
101.77
6B
371
15
XINXIAN
548080
36.23
115.67
4A
579
23
XINYANG
572970
32.13
114.05
3A
1115
44
XINYI
594560
22.35
110.93
2A
1781
70
XISHA DAO
599810
16.83
112.33
0A
1496
59
XIUSHUI
575980
29.03
114.58
3A
1538
61
XUNWU
591020
24.95
115.65
2A
1651
65
XUZHOU
580270
34.28
117.15
4A
828
33
YAAN
562870
29.98
103.00
3A
1724
68
YAN AN
538450
36.60
109.50
5A
561
22
YANCHI
537230
37.80
107.38
5B
278
11
YANGCHENG
539750
35.48
112.40
4A
616
24
YANGJIANG
596630
21.87
111.97
2A
2276
90
YANJI
542920
42.87
129.50
6A
514
20
YANZHOU
549160
35.57
116.85
4A
689
27
YAXIAN
599480
18.23
109.52
0A
1248
49
YIBIN
564920
28.80
104.60
3A
1147
45
YICHANG
574610
30.70
111.30
3A
1178
46
YICHUN
507740
47.72
128.90
7
643
25
YICHUN
577930
27.80
114.38
3A
1602
63
YINCHUAN
536140
38.47
106.20
5B
196
8
YINGKOU
544710
40.67
122.20
5A
675
27
YINING
514310
43.95
81.33
5B
262
10
YIWU
521180
43.27
94.70
7
90
4
YIYUAN
548360
36.18
118.15
4A
701
28
YONGAN
589210
25.97
117.35
2A
1566
62
YOUYANG
576330
28.83
108.77
3A
1360
54
YU XIAN
535930
39.83
114.57
6B
408
16
YUANJIANG
569660
23.60
101.98
1A
782
31
YUANLING
576550
28.47
110.40
3A
1422
56
YUANMOU
567630
25.73
101.87
2B
619
24
YUANPING
536730
38.75
112.70
5B
424
17
YUEYANG
575840
29.38
113.08
3A
1264
50
YULIN
536460
38.23
109.70
5B
402
16
Costa Rica (CRI)
JUAN SANTAMARIA INT
787620
9.98
–84.22
2A
1946
77
WUHAN
574940
30.62
114.13
3A
1218
48
WUHU
583380
31.33
118.35
3A
1161
46
WUSHAOLING
527870
37.20
102.87
7
390
15
WUTAI SHAN
535880
38.95
113.52
8
815
32
WUYISHAN
587300
27.77
118.03
3A
1905
75
WUZHOU
592650
23.48
111.30
2A
1487
59
XAINZA
554720
30.95
88.63
7
285
11
XI UJIMQIN QI
540120
44.58
117.60
7
333
13
XIAMEN
591340
24.48
118.08
2A
1185
47
XIAN
570360
34.30
108.93
4B
562
22
XIAOERGOU
505480
49.20
123.72
7
490
19
XICHANG
565710
27.90
102.27
3A
968
38
XIFENGZHEN
539230
35.73
107.63
5A
569
22
XIGAZE
555780
29.25
88.88
6C
432
17
XIHUA
571930
33.78
114.52
4A
745
29
XILIN HOT
541020
43.95
116.12
7
277
11
XIN BARAG YOUQI
506030
48.67
116.82
7
250
10
XINGREN
579020
25.43
105.18
3A
1332
52
XINGTAI
537980
37.07
114.50
4B
527
21
XINING
528660
36.62
101.77
6B
371
15
XINXIAN
548080
36.23
115.67
4A
579
23
XINYANG
572970
32.13
114.05
3A
1115
44
XINYI
594560
22.35
110.93
2A
1781
70
XISHA DAO
599810
16.83
112.33
0A
1496
59
XIUSHUI
575980
29.03
114.58
3A
1538
61
XUNWU
591020
24.95
115.65
2A
1651
65
XUZHOU
580270
34.28
117.15
4A
828
33
YAAN
562870
29.98
103.00
3A
1724
68
YAN AN
538450
36.60
109.50
5A
561
22
YANCHI
537230
37.80
107.38
5B
278
11
YANGCHENG
539750
35.48
112.40
4A
616
24
YANGJIANG
596630
21.87
111.97
2A
2276
90
YANJI
542920
42.87
129.50
6A
514
20
YANZHOU
549160
35.57
116.85
4A
689
27
YAXIAN
599480
18.23
109.52
0A
1248
49
YIBIN
564920
28.80
104.60
3A
1147
45
YICHANG
574610
30.70
111.30
3A
1178
46
YICHUN
507740
47.72
128.90
7
643
25
YICHUN
577930
27.80
114.38
3A
1602
63
YINCHUAN
536140
38.47
106.20
5B
196
8
YINGKOU
544710
40.67
122.20
5A
675
27
YINING
514310
43.95
81.33
5B
262
10
YIWU
521180
43.27
94.70
7
90
4
YIYUAN
548360
36.18
118.15
4A
701
28
YONGAN
589210
25.97
117.35
2A
1566
62
YOUYANG
576330
28.83
108.77
3A
1360
54
YU XIAN
535930
39.83
114.57
6B
408
16
YUANJIANG
569660
23.60
101.98
1A
782
31
YUANLING
576550
28.47
110.40
3A
1422
56
YUANMOU
567630
25.73
101.87
2B
619
24
YUANPING
536730
38.75
112.70
5B
424
17
YUEYANG
575840
29.38
113.08
3A
1264
50
YULIN
536460
38.23
109.70
5B
402
16
Côte D’Ivoire (CIV)
ABIDJAN
655780
5.25
–3.93
0A
1886
74
WUHAN
574940
30.62
114.13
3A
1218
48
WUHU
583380
31.33
118.35
3A
1161
46
WUSHAOLING
527870
37.20
102.87
7
390
15
WUTAI SHAN
535880
38.95
113.52
8
815
32
WUYISHAN
587300
27.77
118.03
3A
1905
75
WUZHOU
592650
23.48
111.30
2A
1487
59
XAINZA
554720
30.95
88.63
7
285
11
XI UJIMQIN QI
540120
44.58
117.60
7
333
13
XIAMEN
591340
24.48
118.08
2A
1185
47
XIAN
570360
34.30
108.93
4B
562
22
XIAOERGOU
505480
49.20
123.72
7
490
19
XICHANG
565710
27.90
102.27
3A
968
38
XIFENGZHEN
539230
35.73
107.63
5A
569
22
XIGAZE
555780
29.25
88.88
6C
432
17
XIHUA
571930
33.78
114.52
4A
745
29
XILIN HOT
541020
43.95
116.12
7
277
11
XIN BARAG YOUQI
506030
48.67
116.82
7
250
10
XINGREN
579020
25.43
105.18
3A
1332
52
XINGTAI
537980
37.07
114.50
4B
527
21
XINING
528660
36.62
101.77
6B
371
15
XINXIAN
548080
36.23
115.67
4A
579
23
XINYANG
572970
32.13
114.05
3A
1115
44
XINYI
594560
22.35
110.93
2A
1781
70
XISHA DAO
599810
16.83
112.33
0A
1496
59
XIUSHUI
575980
29.03
114.58
3A
1538
61
XUNWU
591020
24.95
115.65
2A
1651
65
XUZHOU
580270
34.28
117.15
4A
828
33
YAAN
562870
29.98
103.00
3A
1724
68
YAN AN
538450
36.60
109.50
5A
561
22
YANCHI
537230
37.80
107.38
5B
278
11
YANGCHENG
539750
35.48
112.40
4A
616
24
YANGJIANG
596630
21.87
111.97
2A
2276
90
YANJI
542920
42.87
129.50
6A
514
20
YANZHOU
549160
35.57
116.85
4A
689
27
YAXIAN
599480
18.23
109.52
0A
1248
49
YIBIN
564920
28.80
104.60
3A
1147
45
YICHANG
574610
30.70
111.30
3A
1178
46
YICHUN
507740
47.72
128.90
7
643
25
YICHUN
577930
27.80
114.38
3A
1602
63
YINCHUAN
536140
38.47
106.20
5B
196
8
YINGKOU
544710
40.67
122.20
5A
675
27
YINING
514310
43.95
81.33
5B
262
10
YIWU
521180
43.27
94.70
7
90
4
YIYUAN
548360
36.18
118.15
4A
701
28
YONGAN
589210
25.97
117.35
2A
1566
62
YOUYANG
576330
28.83
108.77
3A
1360
54
YU XIAN
535930
39.83
114.57
6B
408
16
YUANJIANG
569660
23.60
101.98
1A
782
31
YUANLING
576550
28.47
110.40
3A
1422
56
YUANMOU
567630
25.73
101.87
2B
619
24
YUANPING
536730
38.75
112.70
5B
424
17
YUEYANG
575840
29.38
113.08
3A
1264
50
YULIN
536460
38.23
109.70
5B
402
16
Croatia (HRV)
DARUVAR
142580
45.60
17.23
4A
890
35
DUBROVNIK-CILIPI
134520
42.57
18.27
3A
1857
73
GOSPIC
143300
44.55
15.37
5A
1400
55
PULA AERODROME
143070
44.90
13.92
4A
907
36
SPLIT/MARJAN
144450
43.52
16.43
3A
829
33
SPLIT/RESNIK
144440
43.53
16.30
3A
970
38
ZADAR/ZEMUNIK
144310
44.10
15.35
3A
928
37
ZAGREB/MAKSIMIR
142400
45.82
16.03
4A
1001
39
ZAGREB/PLESO
142410
45.73
16.07
4A
873
34

430 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 433

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Cuba (CUB)
AEROPUERTO JOSE MAR
782240
22.98
–82.40
1A
1536
60
CAMAGUEY AEROPUERTO
782550
21.42
–77.85
1A
1386
55
GUANTANAMO BAY NAS
783670
19.90
–75.22
0B
567
22
SANTIAGO DE CUBA
782640
19.97
–75.85
1A
1124
44
VARADERO/MT
782290
23.02
–81.43
1A
1428
56
BLAAVANDSHUK
060810
55.55
8.08
5A
792
31
CHRISTIANSO (LGT-H)
061910
55.32
15.18
5A
608
24
DROGDEN
061830
55.53
12.72
5A
602
24
ESBJERG
060800
55.53
8.57
5A
843
33
FORNAES (CAPE)
060710
56.45
10.97
5A
585
23
FREDERIKSHAVN
060430
57.40
10.52
5A
674
27
GNIBEN
061690
56.02
11.28
5A
550
22
HAMMER ODDE
061930
55.30
14.78
5A
538
21
HOLBAEK
061560
55.73
11.60
5A
601
24
HVIDE SANDE
060580
56.00
8.13
5A
788
31
KARUP
060600
56.30
9.12
5A
767
30
KEGNAES
061190
54.85
9.98
5A
706
28
KOEBENHAVN/KASTRUP
061800
55.62
12.65
5A
602
24
LANGOE
061380
54.82
11.00
5A
585
23
MARIBO
061430
54.70
11.45
5A
615
24
MOEN
061790
54.95
12.53
5A
763
30
NAKKEHOVED
061680
56.12
12.35
5A
626
25
ODENSE/BELDRINGE
061200
55.48
10.33
5A
632
25
OMOE
061510
55.17
11.13
5A
574
23
ROEMOE/JUVRE
060960
55.18
8.57
5A
801
32
ROENNE
061900
55.07
14.75
5A
577
23
ROESNAES
061590
55.75
10.87
5A
552
22
ROSKILDE/TUNE
061700
55.58
12.13
5A
606
24
SAEDENSTRAND
060890
55.50
8.40
5A
782
31
SKAGEN
060410
57.73
10.63
5A
640
25
SKRYDSTRUP
061100
55.23
9.27
5A
828
33
THYBOROEN
060520
56.70
8.22
5A
811
32
TIRSTRUP
060700
56.32
10.63
5A
627
25
VAERLOESE
061600
55.77
12.33
5A
642
25
Curaçao (CUW)
HATO ARPT (CIV/MIL)
789880
12.20
–68.97
0B
551
22
Curaçao (CUW)
HATO ARPT (CIV/MIL)
789880
12.20
–68.97
0B
551
22
Cyprus (CYP)
AKROTIRI
176010
34.58
32.98
3A
591
23
LARNACA AIRPORT
176090
34.88
33.63
3B
330
13
PAPHOS AIRPORT
176000
34.72
32.48
3A
480
19
Cyprus (CYP)
AKROTIRI
176010
34.58
32.98
3A
591
23
LARNACA AIRPORT
176090
34.88
33.63
3B
330
13
PAPHOS AIRPORT
176000
34.72
32.48
3A
480
19
Czech Republic (CZE)
BRNO/TURANY
117230
49.15
16.70
5A
497
20
CASLAV
116240
49.93
15.38
5A
578
23
CERVENA
117660
49.77
17.55
6A
685
27
CESKE BUDEJOVICE
115410
48.95
14.43
5A
648
26
CHEB
114060
50.08
12.40
5A
564
22
CHURANOV
114570
49.07
13.62
6A
983
39
DOKSANY
115090
50.47
14.17
5A
496
20
DUKOVANY
116930
49.10
16.13
5A
505
20
HOLESOV
117740
49.32
17.57
5A
649
26
HRADEC KRALOVE
116480
50.25
15.85
5A
609
24
KARLOVY VARY
114140
50.20
12.92
6A
641
25
KOCELOVICE
114870
49.47
13.83
5A
611
24
KOSTELNI MYSLOVA
116360
49.18
15.47
6A
639
25
KRESIN-KRAMOLIN
116280
49.58
15.08
5A
650
26
KUCHAROVICE
116980
48.88
16.08
5A
492
19
LIBEREC
116030
50.77
15.02
5A
917
36
LUKA
117100
49.65
16.95
5A
617
24
LYSA HORA
117870
49.55
18.45
7
1004
40
MARIANSKE LAZNE
114180
49.92
12.72
6A
706
28
MILESOVKA
114640
50.55
13.93
6A
686
27
NAMEST NAD OSLAV
116920
49.17
16.12
5A
505
20
OSTRAVA/MOSNOV
117820
49.68
18.12
5A
864
34
PARDUBICE
116520
50.02
15.73
5A
584
23
PEC POD SNEZKOU
116430
50.67
15.75
6A
897
35
PLZEN LINE
114480
49.68
13.27
5A
565
22
PRADED MOUNTAIN
117350
50.07
17.23
7
946
37
PRAHA/RUZYNE
115180
50.10
14.25
5A
482
19
PRAHA-KBELY
115670
50.12
14.53
5A
548
22
PRAHA-LIBUS
115200
50.02
14.45
5A
497
20
PREROV
117480
49.42
17.40
5A
605
24
PRIBYSLAV
116590
49.58
15.77
6A
701
28
PRIMDA
114230
49.67
12.67
6A
814
32
SVRATOUCH
116830
49.73
16.03
6A
722
28
TEMELIN
115380
49.20
14.33
5A
600
24
TUSIMICE
114380
50.38
13.33
5A
650
26
USTI NAD LABEM
115020
50.68
14.03
5A
603
24
USTI NAD ORLICI
116790
49.98
16.43
5A
734
29
Czech Republic (CZE)
BRNO/TURANY
117230
49.15
16.70
5A
497
20
CASLAV
116240
49.93
15.38
5A
578
23
CERVENA
117660
49.77
17.55
6A
685
27
CESKE BUDEJOVICE
115410
48.95
14.43
5A
648
26
CHEB
114060
50.08
12.40
5A
564
22
CHURANOV
114570
49.07
13.62
6A
983
39
DOKSANY
115090
50.47
14.17
5A
496
20
DUKOVANY
116930
49.10
16.13
5A
505
20
HOLESOV
117740
49.32
17.57
5A
649
26
HRADEC KRALOVE
116480
50.25
15.85
5A
609
24
KARLOVY VARY
114140
50.20
12.92
6A
641
25
KOCELOVICE
114870
49.47
13.83
5A
611
24
KOSTELNI MYSLOVA
116360
49.18
15.47
6A
639
25
KRESIN-KRAMOLIN
116280
49.58
15.08
5A
650
26
KUCHAROVICE
116980
48.88
16.08
5A
492
19
LIBEREC
116030
50.77
15.02
5A
917
36
LUKA
117100
49.65
16.95
5A
617
24
LYSA HORA
117870
49.55
18.45
7
1004
40
MARIANSKE LAZNE
114180
49.92
12.72
6A
706
28
MILESOVKA
114640
50.55
13.93
6A
686
27
NAMEST NAD OSLAV
116920
49.17
16.12
5A
505
20
OSTRAVA/MOSNOV
117820
49.68
18.12
5A
864
34
PARDUBICE
116520
50.02
15.73
5A
584
23
PEC POD SNEZKOU
116430
50.67
15.75
6A
897
35
PLZEN LINE
114480
49.68
13.27
5A
565
22
PRADED MOUNTAIN
117350
50.07
17.23
7
946
37
PRAHA/RUZYNE
115180
50.10
14.25
5A
482
19
PRAHA-KBELY
115670
50.12
14.53
5A
548
22
PRAHA-LIBUS
115200
50.02
14.45
5A
497
20
PREROV
117480
49.42
17.40
5A
605
24
PRIBYSLAV
116590
49.58
15.77
6A
701
28
PRIMDA
114230
49.67
12.67
6A
814
32
SVRATOUCH
116830
49.73
16.03
6A
722
28
TEMELIN
115380
49.20
14.33
5A
600
24
TUSIMICE
114380
50.38
13.33
5A
650
26
USTI NAD LABEM
115020
50.68
14.03
5A
603
24
USTI NAD ORLICI
116790
49.98
16.43
5A
734
29
Czech Republic (CZE)
BRNO/TURANY
117230
49.15
16.70
5A
497
20
CASLAV
116240
49.93
15.38
5A
578
23
CERVENA
117660
49.77
17.55
6A
685
27
CESKE BUDEJOVICE
115410
48.95
14.43
5A
648
26
CHEB
114060
50.08
12.40
5A
564
22
CHURANOV
114570
49.07
13.62
6A
983
39
DOKSANY
115090
50.47
14.17
5A
496
20
DUKOVANY
116930
49.10
16.13
5A
505
20
HOLESOV
117740
49.32
17.57
5A
649
26
HRADEC KRALOVE
116480
50.25
15.85
5A
609
24
KARLOVY VARY
114140
50.20
12.92
6A
641
25
KOCELOVICE
114870
49.47
13.83
5A
611
24
KOSTELNI MYSLOVA
116360
49.18
15.47
6A
639
25
KRESIN-KRAMOLIN
116280
49.58
15.08
5A
650
26
KUCHAROVICE
116980
48.88
16.08
5A
492
19
LIBEREC
116030
50.77
15.02
5A
917
36
LUKA
117100
49.65
16.95
5A
617
24
LYSA HORA
117870
49.55
18.45
7
1004
40
MARIANSKE LAZNE
114180
49.92
12.72
6A
706
28
MILESOVKA
114640
50.55
13.93
6A
686
27
NAMEST NAD OSLAV
116920
49.17
16.12
5A
505
20
OSTRAVA/MOSNOV
117820
49.68
18.12
5A
864
34
PARDUBICE
116520
50.02
15.73
5A
584
23
PEC POD SNEZKOU
116430
50.67
15.75
6A
897
35
PLZEN LINE
114480
49.68
13.27
5A
565
22
PRADED MOUNTAIN
117350
50.07
17.23
7
946
37
PRAHA/RUZYNE
115180
50.10
14.25
5A
482
19
PRAHA-KBELY
115670
50.12
14.53
5A
548
22
PRAHA-LIBUS
115200
50.02
14.45
5A
497
20
PREROV
117480
49.42
17.40
5A
605
24
PRIBYSLAV
116590
49.58
15.77
6A
701
28
PRIMDA
114230
49.67
12.67
6A
814
32
SVRATOUCH
116830
49.73
16.03
6A
722
28
TEMELIN
115380
49.20
14.33
5A
600
24
TUSIMICE
114380
50.38
13.33
5A
650
26
USTI NAD LABEM
115020
50.68
14.03
5A
603
24
USTI NAD ORLICI
116790
49.98
16.43
5A
734
29
Dominican Republic (DOM)
LAS AMERICAS
784850
18.43
–69.67
1A
1198
47
SANTO DOMINGO
784860
18.43
–69.88
0A
1338
53
Czech Republic (CZE)
BRNO/TURANY
117230
49.15
16.70
5A
497
20
CASLAV
116240
49.93
15.38
5A
578
23
CERVENA
117660
49.77
17.55
6A
685
27
CESKE BUDEJOVICE
115410
48.95
14.43
5A
648
26
CHEB
114060
50.08
12.40
5A
564
22
CHURANOV
114570
49.07
13.62
6A
983
39
DOKSANY
115090
50.47
14.17
5A
496
20
DUKOVANY
116930
49.10
16.13
5A
505
20
HOLESOV
117740
49.32
17.57
5A
649
26
HRADEC KRALOVE
116480
50.25
15.85
5A
609
24
KARLOVY VARY
114140
50.20
12.92
6A
641
25
KOCELOVICE
114870
49.47
13.83
5A
611
24
KOSTELNI MYSLOVA
116360
49.18
15.47
6A
639
25
KRESIN-KRAMOLIN
116280
49.58
15.08
5A
650
26
KUCHAROVICE
116980
48.88
16.08
5A
492
19
LIBEREC
116030
50.77
15.02
5A
917
36
LUKA
117100
49.65
16.95
5A
617
24
LYSA HORA
117870
49.55
18.45
7
1004
40
MARIANSKE LAZNE
114180
49.92
12.72
6A
706
28
MILESOVKA
114640
50.55
13.93
6A
686
27
NAMEST NAD OSLAV
116920
49.17
16.12
5A
505
20
OSTRAVA/MOSNOV
117820
49.68
18.12
5A
864
34
PARDUBICE
116520
50.02
15.73
5A
584
23
PEC POD SNEZKOU
116430
50.67
15.75
6A
897
35
PLZEN LINE
114480
49.68
13.27
5A
565
22
PRADED MOUNTAIN
117350
50.07
17.23
7
946
37
PRAHA/RUZYNE
115180
50.10
14.25
5A
482
19
PRAHA-KBELY
115670
50.12
14.53
5A
548
22
PRAHA-LIBUS
115200
50.02
14.45
5A
497
20
PREROV
117480
49.42
17.40
5A
605
24
PRIBYSLAV
116590
49.58
15.77
6A
701
28
PRIMDA
114230
49.67
12.67
6A
814
32
SVRATOUCH
116830
49.73
16.03
6A
722
28
TEMELIN
115380
49.20
14.33
5A
600
24
TUSIMICE
114380
50.38
13.33
5A
650
26
USTI NAD LABEM
115020
50.68
14.03
5A
603
24
USTI NAD ORLICI
116790
49.98
16.43
5A
734
29
Ecuador (ECU)
GUAYAQUIL AEROPUERT
842030
–2.15
–79.88
1A
866
34
MANTA
841170
–0.95
–80.68
1B
404
16
QUITO AEROPUERTO
840710
–0.13
–78.48
3A
1083
43
Czech Republic (CZE)
BRNO/TURANY
117230
49.15
16.70
5A
497
20
CASLAV
116240
49.93
15.38
5A
578
23
CERVENA
117660
49.77
17.55
6A
685
27
CESKE BUDEJOVICE
115410
48.95
14.43
5A
648
26
CHEB
114060
50.08
12.40
5A
564
22
CHURANOV
114570
49.07
13.62
6A
983
39
DOKSANY
115090
50.47
14.17
5A
496
20
DUKOVANY
116930
49.10
16.13
5A
505
20
HOLESOV
117740
49.32
17.57
5A
649
26
HRADEC KRALOVE
116480
50.25
15.85
5A
609
24
KARLOVY VARY
114140
50.20
12.92
6A
641
25
KOCELOVICE
114870
49.47
13.83
5A
611
24
KOSTELNI MYSLOVA
116360
49.18
15.47
6A
639
25
KRESIN-KRAMOLIN
116280
49.58
15.08
5A
650
26
KUCHAROVICE
116980
48.88
16.08
5A
492
19
LIBEREC
116030
50.77
15.02
5A
917
36
LUKA
117100
49.65
16.95
5A
617
24
LYSA HORA
117870
49.55
18.45
7
1004
40
MARIANSKE LAZNE
114180
49.92
12.72
6A
706
28
MILESOVKA
114640
50.55
13.93
6A
686
27
NAMEST NAD OSLAV
116920
49.17
16.12
5A
505
20
OSTRAVA/MOSNOV
117820
49.68
18.12
5A
864
34
PARDUBICE
116520
50.02
15.73
5A
584
23
PEC POD SNEZKOU
116430
50.67
15.75
6A
897
35
PLZEN LINE
114480
49.68
13.27
5A
565
22
PRADED MOUNTAIN
117350
50.07
17.23
7
946
37
PRAHA/RUZYNE
115180
50.10
14.25
5A
482
19
PRAHA-KBELY
115670
50.12
14.53
5A
548
22
PRAHA-LIBUS
115200
50.02
14.45
5A
497
20
PREROV
117480
49.42
17.40
5A
605
24
PRIBYSLAV
116590
49.58
15.77
6A
701
28
PRIMDA
114230
49.67
12.67
6A
814
32
SVRATOUCH
116830
49.73
16.03
6A
722
28
TEMELIN
115380
49.20
14.33
5A
600
24
TUSIMICE
114380
50.38
13.33
5A
650
26
USTI NAD LABEM
115020
50.68
14.03
5A
603
24
USTI NAD ORLICI
116790
49.98
16.43
5A
734
29
Egypt (EGY)
ALEXANDRIA/NOUZHA
623180
31.20
29.95
2B
182
7
ASSWAN
624140
23.97
32.78
0B
1
0
ASYUT
623930
27.05
31.02
2B
6
0
BALTIM
623250
31.55
31.10
2B
180
7
CAIRO AIRPORT
623660
30.13
31.40
2B
23
1
DAKHLA
624320
25.48
29.00
1B
1
0
EL ARISH
623370
31.08
33.82
2B
135
5
EL TOR
624590
28.23
33.62
2B
7
0
HURGUADA
624630
27.15
33.72
1B
6
0
ISMAILIA
624400
30.60
32.25
2B
30
1
KHARGA
624350
25.45
30.53
1B
1
0
KOSSEIR
624650
26.13
34.15
1B
4
0
LUXOR
624050
25.67
32.70
1B
2
0
MERSA MATRUH
623060
31.33
27.22
2B
123
5
MINYA
623870
28.08
30.73
2B
3
0
PORT SAID
623330
31.27
32.30
2B
67
3
Denmark (DNK)
AALBORG
060300
57.10
9.85
5A
607
24
BILLUND
061040
55.73
9.17
5A
888
35
Denmark (DNK)
AALBORG
060300
57.10
9.85
5A
607
24
BILLUND
061040
55.73
9.17
5A
888
35

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 431

PDF Page 434

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
PORT SAID/EL GAMIL
623320
31.28
32.23
2B
67
3
SIWA
624170
29.20
25.32
2B
12
0
MIKKELI
029470
61.73
27.30
7
625
25
MOIKIPAA
029210
62.88
21.10
7
542
21
MUONIO
028230
67.97
23.68
8
531
21
NIINISALO
029420
61.85
22.47
7
628
25
NIVALA
029050
63.92
24.97
7
567
22
NYHAMN
029800
59.97
19.97
6A
715
28
OULU
028750
64.93
25.37
7
442
17
PELLO
028440
66.80
24.00
7
523
21
PORI
029520
61.47
21.80
6A
604
24
PUDASJARVI
028670
65.37
27.02
7
601
24
RANKKI
029760
60.37
26.97
6A
634
25
ROVANIEMI
028450
66.57
25.83
7
535
21
RUSSARO
029820
59.77
22.95
6A
695
27
SALLA KK
028490
66.83
28.68
7
561
22
SAVONLINNA
029480
61.95
28.95
7
611
24
SODANKYLA
028360
67.37
26.65
7
530
21
SUOMUSSALMI
028790
64.90
29.02
7
664
26
TAMPERE/PIRKKALA
029440
61.42
23.58
7
566
22
TURKU
029720
60.52
22.27
6A
723
28
UTO
029810
59.78
21.38
6A
847
33
UTTI
029660
60.90
26.93
7
641
25
VAASA AIRPORT
029110
63.05
21.77
7
506
20
VALASSAARET
029100
63.43
21.07
7
719
28
VIITASAARI
029150
63.08
25.87
7
616
24
Estonia (EST)
KUNDA
260450
59.52
26.53
6A
564
22
KURESSAARE
262150
58.23
22.50
6A
621
24
NARVA
260580
59.37
28.12
6A
640
25
PJARNU
262310
58.37
24.50
6A
657
26
RISTNA
261150
58.92
22.07
6A
880
35
TALLINN
260380
59.47
24.82
6A
654
26
TARTU
262420
58.30
26.73
6A
586
23
TURI
261350
58.82
25.42
6A
717
28
VALKE-MAARJA
261410
59.13
26.23
6A
658
26
Estonia (EST)
KUNDA
260450
59.52
26.53
6A
564
22
KURESSAARE
262150
58.23
22.50
6A
621
24
NARVA
260580
59.37
28.12
6A
640
25
PJARNU
262310
58.37
24.50
6A
657
26
RISTNA
261150
58.92
22.07
6A
880
35
TALLINN
260380
59.47
24.82
6A
654
26
TARTU
262420
58.30
26.73
6A
586
23
TURI
261350
58.82
25.42
6A
717
28
VALKE-MAARJA
261410
59.13
26.23
6A
658
26
Falkland Islands (Malvinas) (FLK)
MOUNT PLEASANT AIRP
888890
–51.82
–58.45
6A
601
24
Falkland Islands (Malvinas) (FLK)
MOUNT PLEASANT AIRP
888890
–51.82
–58.45
6A
601
24
Faroe Islands (FRO)
AKRABERG
060090
61.40
–6.67
6A
1606
63
TORSHAVN
060110
62.02
–6.77
6A
1411
56
Faroe Islands (FRO)
AKRABERG
060090
61.40
–6.67
6A
1606
63
TORSHAVN
060110
62.02
–6.77
6A
1411
56
Fiji (FJI)
LAKEBA AWS
916910
–18.23
–178.80
1A
1482
58
MATUKU AWS
916970
–19.13
179.75
1A
1639
65
NADI AIRPORT
916800
–17.75
177.45
1A
1850
73
NAUSORI
916830
–18.05
178.57
1A
2866
113
ONO-I-LAU AWS
916990
–20.67
–178.72
1A
1740
69
ROTUMA
916500
–12.50
177.05
0A
3504
138
UDU POINT AWS
916520
–16.13
–179.98
0A
2433
96
VIWA AWS
916700
–17.15
176.90
0A
1763
69
VUNISEA
916930
–19.05
178.17
1A
1712
67
YASAWA-I-RARA AWS
916600
–16.70
177.58
0A
1854
73
Fiji (FJI)
LAKEBA AWS
916910
–18.23
–178.80
1A
1482
58
MATUKU AWS
916970
–19.13
179.75
1A
1639
65
NADI AIRPORT
916800
–17.75
177.45
1A
1850
73
NAUSORI
916830
–18.05
178.57
1A
2866
113
ONO-I-LAU AWS
916990
–20.67
–178.72
1A
1740
69
ROTUMA
916500
–12.50
177.05
0A
3504
138
UDU POINT AWS
916520
–16.13
–179.98
0A
2433
96
VIWA AWS
916700
–17.15
176.90
0A
1763
69
VUNISEA
916930
–19.05
178.17
1A
1712
67
YASAWA-I-RARA AWS
916600
–16.70
177.58
0A
1854
73
Fiji (FJI)
LAKEBA AWS
916910
–18.23
–178.80
1A
1482
58
MATUKU AWS
916970
–19.13
179.75
1A
1639
65
NADI AIRPORT
916800
–17.75
177.45
1A
1850
73
NAUSORI
916830
–18.05
178.57
1A
2866
113
ONO-I-LAU AWS
916990
–20.67
–178.72
1A
1740
69
ROTUMA
916500
–12.50
177.05
0A
3504
138
UDU POINT AWS
916520
–16.13
–179.98
0A
2433
96
VIWA AWS
916700
–17.15
176.90
0A
1763
69
VUNISEA
916930
–19.05
178.17
1A
1712
67
YASAWA-I-RARA AWS
916600
–16.70
177.58
0A
1854
73
France (FRA)
ABBEVILLE
070050
50.13
1.83
4A
771
30
AGEN
075240
44.18
0.60
4A
755
30
AJACCIO
077610
41.92
8.80
3A
626
25
ALBI
076320
43.92
2.12
4A
882
35
ALENCON
071390
48.43
0.10
4A
736
29
AMBERIEU
074820
45.98
5.33
4A
1181
46
AUCH
076220
43.68
0.60
4A
756
30
AURILLAC
075490
44.88
2.42
5A
1322
52
AUXERRE
072650
47.80
3.55
4A
654
26
BALE-MULHOUSE
072990
47.60
7.52
4A
775
30
BASTIA
077900
42.55
9.48
3A
756
30
BEAUCOUZE
072300
47.48
–0.60
4A
620
24
BEAUVAIS
070550
49.47
2.12
4A
730
29
BELFORT
072950
47.63
6.88
5A
1316
52
BELLE IIE LE TALUT
072070
47.30
–3.17
4A
705
28
BERGERAC
075300
44.82
0.52
4A
812
32
BESANCON
072880
47.25
5.98
4A
1170
46
BIARRITZ
076020
43.47
–1.53
3A
1824
72
BISCAROSSE
075030
44.43
–1.25
3A
937
37
BORDEAUX MERIGNAC
075100
44.83
–0.68
4A
940
37
BOULOGNE
070020
50.73
1.60
4A
760
30
BOURG ST-MAURICE
074970
45.62
6.77
5A
1258
50
BOURGES
072550
47.07
2.37
4A
734
29
BREHAT ISLAND
071210
48.85
–3.00
4A
752
30
BREST
071100
48.45
–4.42
4A
1152
45
BRIGNOGAN
071070
48.68
–4.33
4A
965
38
BRIVE
074380
45.15
1.47
4A
931
37
CAEN CARPIQUET
070270
49.18
–0.45
4A
776
31
Finland (FIN)
AHTARI
029240
62.53
24.02
7
627
25
BAGASKAR
029840
59.93
24.02
6A
547
22
HALLI
029450
61.85
24.80
7
657
26
HELSINKI-VANTAA
029740
60.32
24.97
6A
658
26
ILOMANTSI
029190
62.68
30.95
7
685
27
ISOSAARI
029880
60.10
25.07
6A
654
26
IVALO
028070
68.62
27.42
7
393
15
JOENSUU
029290
62.67
29.63
7
627
25
JOKIOINEN
029630
60.82
23.50
7
597
23
JOMALA
029710
60.15
19.87
6A
530
21
JYVASKYLA
029350
62.40
25.68
7
636
25
KAJAANI
028970
64.28
27.68
7
559
22
KAUHAVA
029130
63.10
23.03
7
540
21
KEMI
028640
65.78
24.58
7
563
22
KEVO
028050
69.75
27.03
8
416
16
KRUUNUPYY
029030
63.72
23.15
7
553
22
KUMLINGE ISLAND
029900
60.30
20.75
6A
792
31
KUOPIO
029170
63.02
27.80
7
677
27
KUUSAMO
028690
65.97
29.18
7
598
24
KUUSKAJASKARI
029610
61.13
21.37
6A
607
24
LAHTI
029650
60.97
25.63
7
636
25
LAPPEENRANTA
029580
61.05
28.20
7
645
25
MARIEHAMN/ALAND ISL
029700
60.12
19.90
6A
530
21
MASSKAR
029010
63.73
22.58
7
531
21
Finland (FIN)
AHTARI
029240
62.53
24.02
7
627
25
BAGASKAR
029840
59.93
24.02
6A
547
22
HALLI
029450
61.85
24.80
7
657
26
HELSINKI-VANTAA
029740
60.32
24.97
6A
658
26
ILOMANTSI
029190
62.68
30.95
7
685
27
ISOSAARI
029880
60.10
25.07
6A
654
26
IVALO
028070
68.62
27.42
7
393
15
JOENSUU
029290
62.67
29.63
7
627
25
JOKIOINEN
029630
60.82
23.50
7
597
23
JOMALA
029710
60.15
19.87
6A
530
21
JYVASKYLA
029350
62.40
25.68
7
636
25
KAJAANI
028970
64.28
27.68
7
559
22
KAUHAVA
029130
63.10
23.03
7
540
21
KEMI
028640
65.78
24.58
7
563
22
KEVO
028050
69.75
27.03
8
416
16
KRUUNUPYY
029030
63.72
23.15
7
553
22
KUMLINGE ISLAND
029900
60.30
20.75
6A
792
31
KUOPIO
029170
63.02
27.80
7
677
27
KUUSAMO
028690
65.97
29.18
7
598
24
KUUSKAJASKARI
029610
61.13
21.37
6A
607
24
LAHTI
029650
60.97
25.63
7
636
25
LAPPEENRANTA
029580
61.05
28.20
7
645
25
MARIEHAMN/ALAND ISL
029700
60.12
19.90
6A
530
21
MASSKAR
029010
63.73
22.58
7
531
21

432 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 435

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
CALVI
077540
42.53
8.80
3A
672
26
CAP BEAR
077490
42.52
3.13
3A
595
23
CAP CEPET
076610
43.08
5.93
3A
727
29
CAP CORSE
077850
43.00
9.35
3A
705
28
CAP COURONNE
076530
43.33
5.05
3A
514
20
CAP DE LA HEVE
070280
49.50
0.07
4A
796
31
CAP FERRET
075000
44.63
–1.25
3A
904
36
CAP PERTUSATO
077700
41.37
9.17
3A
616
24
CAP POMEGUES
076520
43.27
5.30
3A
566
22
CAPE FERRAT
076950
43.68
7.33
3A
904
36
CAPE SAGRO
077910
42.80
9.48
3A
705
28
CARCASSONNE
076350
43.22
2.32
3A
728
29
CARPENTRAS
075860
44.08
5.05
3A
749
30
CAZAUX
075020
44.53
–1.13
4A
904
36
CHAMBERY/AIX-LES-BA
074910
45.63
5.87
4A
1218
48
CHARLEVILLE
070750
49.78
4.63
5A
1013
40
CHARTRES
071430
48.47
1.50
4A
611
24
CHASSIRON
073140
46.05
–1.42
3A
730
29
CHATEAUROUX/DEOLS
073540
46.85
1.72
4A
774
30
CLERMONT-FERRAND
074600
45.78
3.17
4A
595
23
COGNAC
074120
45.67
–0.32
4A
852
34
DIEPPE
070400
49.93
1.10
4A
854
34
DIJON
072800
47.27
5.08
4A
747
29
DINARD
071250
48.58
–2.07
4A
685
27
DUNKERQUE
070100
51.05
2.33
4A
685
27
EMBRUN
075910
44.57
6.50
5A
844
33
EVREUX/FAUVILLE FAF
070380
49.02
1.22
4A
685
27
FIGARI
077800
41.50
9.10
3A
616
24
GOURDON
075350
44.75
1.40
4A
871
34
GRENOBLE-ST-GEOIRS
074860
45.37
5.33
4A
991
39
GROUIN DE CANCALE
071270
48.72
–1.85
4A
688
27
HYERES
076670
43.10
6.15
3A
745
29
ILE ROUSSE
077530
42.63
8.92
3A
672
26
ISTRES
076470
43.52
4.92
3A
623
25
L IIE D YEU
073000
46.70
–2.33
4A
796
31
LA CHIAPPA
077680
41.60
9.37
3A
746
29
LA ROCHELLE
073150
46.15
–1.15
4A
758
30
LA ROCHE-SUR-YON
073060
46.70
–1.38
4A
856
34
LANGRES
072830
47.85
5.33
5A
849
33
LE BOURGET
071500
48.97
2.43
4A
647
25
LE LUC
076750
43.38
6.38
3A
907
36
LE MANS
072350
47.93
0.20
4A
682
27
LE PUY
074710
45.08
3.77
5A
769
30
LE RAIZET/GUADELOUP
788970
16.27
–61.60
0A
1475
58
LILLE LESQUI
070150
50.57
3.10
4A
698
27
LIMOGES
074340
45.87
1.18
4A
1013
40
LONS-LE-SAUNIER
073900
46.68
5.52
4A
1368
54
LORIENT LAN BIHOUE
072050
47.77
–3.45
4A
867
34
LUXEUIL
072920
47.80
6.38
5A
1155
45
LYON-BRON
074800
45.72
4.93
4A
808
32
LYON-SATOLAS
074810
45.73
5.08
4A
927
37
MACON
073850
46.30
4.80
4A
847
33
MARIGNANE
076500
43.45
5.23
3A
514
20
MARTIN DE VIVIES (ILE AMST.)
619960
–37.80
77.50
3A
1101
43
MAUPERTUS
070240
49.65
–1.48
4A
845
33
MELUN
071530
48.62
2.68
4A
651
26
METZ/FRESCATY
070900
49.08
6.13
4A
768
30
MEYENHEIM-COLMAR
071970
47.92
7.40
4A
746
29
MILLAU
075580
44.12
3.02
4A
921
36
MONT AIGOUAL
075600
44.12
3.58
6A
1444
57
MONT-DE-MARSAN
076070
43.92
–0.50
4A
945
37
MONTELIMAR
075770
44.58
4.73
4A
930
37
MONTPELLIER
076430
43.58
3.97
3A
869
34
NANCY-ESSEY
071800
48.68
6.22
5A
768
30
NANCY-OCHEY
071810
48.58
5.97
5A
837
33
NANTES
072220
47.15
–1.60
4A
778
31
NEVERS
072600
47.00
3.10
4A
786
31
NICE
076900
43.65
7.20
3A
790
31
NIMES/GARONS (NAVY)
076460
43.75
4.42
3A
714
28
NIMES-COURBESSAC
076450
43.87
4.40
3A
775
31
NIORT
073300
46.32
–0.40
4A
903
36
ORANGE
075790
44.13
4.83
3A
719
28
ORLEANS
072490
47.98
1.78
4A
641
25
OUESSANT
071000
48.48
–5.05
4A
869
34
PARIS-AEROPORT CHAR
071570
49.02
2.53
4A
701
28
PARIS-MONTSOURIS
071560
48.82
2.33
4A
647
25
PARIS-ORLY
071490
48.72
2.38
4A
634
25
PAU
076100
43.38
–0.42
4A
1173
46
PERPIGNAN
077470
42.73
2.87
3A
572
23
POINTE DU RAZ
071030
48.03
–4.73
4A
797
31
POITIERS
073350
46.58
0.30
4A
712
28
PORQUEROLLES
076700
43.00
6.23
3A
681
27
PORT EN BESSIN
070290
49.35
–0.77
4A
796
31
PTE DE LA HAGUE
070200
49.72
–1.93
4A
809
32
PTE DE PENMARCH
072000
47.80
–4.37
4A
875
34
QUIMPER
072010
47.97
–4.17
4A
919
36
REIMS
070700
49.30
4.03
4A
656
26
RENNES
071300
48.07
–1.73
4A
710
28
ROUEN
070370
49.38
1.18
4A
790
31
SAINT GIRONS
076270
43.00
1.10
4A
1163
46
SAINT-DIZIER
071690
48.63
4.90
4A
891
35
SAINT-NAZAIRE-MONTO
072170
47.32
–2.17
4A
735
29
SAINT-QUENTIN
070610
49.82
3.20
5A
696
27
SAINT-YAN
073790
46.42
4.02
4A
884
35
SERGE-FROLOW (ILE TROMELIN)
619760
–15.80
54.50
1A
850
33
SETE
076410
43.40
3.68
3A
650
26
SOCOA
076000
43.40
–1.68
3A
1824
72
SOLENZARA
077650
41.92
9.40
3A
843
33
ST-AUBAN-SUR-DURANC
075880
44.07
6.00
4A
746
29
ST-ETIENNE BOUTHEON
074750
45.53
4.30
4A
765
30
STRASBOURG-ENTZHEIM
071900
48.55
7.63
4A
623
25
TARBES-OSSUN
076210
43.18
0.00
4A
1140
45
TOULON
076600
43.10
5.93
3A
674
27
TOULOUSE BLAGNAC
076300
43.63
1.37
4A
669
26
TOURS
072400
47.45
0.73
4A
674
27
TRAPPES
071450
48.77
2.00
4A
672
26

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 433

PDF Page 436

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
TREMUSON-ST-BRIEUC
071200
48.53
–2.85
4A
764
30
TROYES BARBEREY
071680
48.33
4.02
4A
695
27
VANNES/SENE
072100
47.60
–2.72
4A
840
33
VICHY
073740
46.17
3.40
4A
763
30
VILLACOUBLAY
071470
48.77
2.20
4A
644
25
CHEMNITZ
105770
50.80
12.87
5A
781
31
COTTBUS (FLUGPLATZ)
104920
51.77
14.30
5A
567
22
CUXHAVEN
101310
53.87
8.70
5A
835
33
DIEPHOLZ
103210
52.58
8.35
5A
729
29
DOBERLUG/KIRCHHAIN
094900
51.65
13.58
5A
587
23
DRESDEN/KLOTZSCHE
094880
51.13
13.77
5A
648
26
DUSSELDORF
104000
51.28
6.78
4A
844
33
EGGEBEK
100340
54.63
9.35
5A
842
33
EMDEN-FLUGPLATZ
102000
53.38
7.23
5A
785
31
ERFURT/BINDERSLEBN
095540
50.98
10.97
5A
514
20
ESSEN/MULHEIM
104100
51.40
6.97
5A
933
37
FASSBERG
102460
52.92
10.18
5A
753
30
FICHTELBERG MTN
095780
50.43
12.95
7
1136
45
FRANKFURT MAIN ARPT
106370
50.05
8.60
5A
651
26
FREIBURG (CIV/FAFB)
108030
48.00
7.85
4A
962
38
FRITZLAR
104390
51.12
9.28
5A
668
26
FUERSTENFELDBRUCK
108580
48.20
11.27
5A
968
38
FUERSTENZELL
108950
48.55
13.35
5A
955
38
GARDELEGEN (AUT)
103590
52.52
11.40
5A
550
22
GEILENKIRCHEN
105000
50.97
6.05
4A
789
31
GERA/LEUMNITZ
105670
50.88
12.13
5A
620
24
GIESSEN
105320
50.58
8.70
5A
739
29
GLUECKSBURG/MEIERWI
100330
54.83
9.50
5A
763
30
GOERLITZ
104990
51.17
14.95
5A
660
26
GRAFENWOEHR
106870
49.70
11.95
5A
767
30
GREIFSWALD
091840
54.10
13.38
5A
574
23
GUETERSLOH
103200
51.93
8.32
5A
767
30
HAHN
106160
49.95
7.27
5A
727
29
HAMBURG/FUHLSBUTTEL
101470
53.63
10.00
5A
782
31
HANNOVER
103380
52.47
9.70
5A
647
25
HEIDELBERG (USA-AF)
107340
49.40
8.65
4A
796
31
HOF
106850
50.32
11.88
6A
765
30
HOHENPEISSENBERG
109620
47.80
11.02
6A
1190
47
HOHN
100380
54.32
9.53
5A
836
33
HOLZDORF
104760
51.77
13.17
5A
548
22
HOPSTEN
103140
52.33
7.53
5A
758
30
IDAR-OBERSTEIN
106180
49.70
7.33
5A
781
31
ITZEHOE
101420
53.98
9.57
5A
824
32
JEVER
101220
53.53
7.90
5A
810
32
KAHLER ASTEN(MOUNT)
104270
51.18
8.48
6A
1104
43
KALKAR
104040
51.73
6.27
4A
759
30
KARLSRUHE BADEN BAD
107275
48.77
8.07
5A
916
36
KASSEL
104380
51.30
9.45
5A
706
28
KIEL HOLTENAU
100465
54.37
10.13
5A
779
31
KOLN/BONN (CIV/MIL)
105130
50.87
7.17
5A
833
33
KONSTANZ
109290
47.68
9.18
5A
831
33
KUEMMERSBRUCK
107710
49.43
11.90
5A
737
29
LAAGE
101720
53.92
12.28
5A
598
24
LAHR
108050
48.37
7.83
4A
897
35
LANDSBERG
108570
48.07
10.90
5A
942
37
LAUPHEIM
108370
48.22
9.92
5A
849
33
LECHFELD
108560
48.18
10.85
5A
942
37
LECK
100220
54.80
8.95
5A
822
32
French Guiana (GUF)
ROCHAMBEAU
814050
4.83
–52.37
0A
3614
142
French Guiana (GUF)
ROCHAMBEAU
814050
4.83
–52.37
0A
3614
142
French Polynesia (PYF)
ATUONA
919250
–9.80
–139.03
0A
1311
52
BORA-BORA
919290
–16.43
–151.75
0A
2036
80
HAO
919440
–18.07
–140.95
0A
1428
56
MURUROA
919520
–21.82
–138.80
1A
1610
63
RAPA
919580
–27.62
–144.33
2A
2672
105
RIKITEA
919480
–23.13
–134.97
2A
1783
70
TAHITI-FAAA
919380
–17.55
–149.62
0A
1685
66
TAKAROA
919430
–14.48
–145.03
0A
1529
60
TUBUAI
919540
–23.35
–149.48
2A
1880
74
French Polynesia (PYF)
ATUONA
919250
–9.80
–139.03
0A
1311
52
BORA-BORA
919290
–16.43
–151.75
0A
2036
80
HAO
919440
–18.07
–140.95
0A
1428
56
MURUROA
919520
–21.82
–138.80
1A
1610
63
RAPA
919580
–27.62
–144.33
2A
2672
105
RIKITEA
919480
–23.13
–134.97
2A
1783
70
TAHITI-FAAA
919380
–17.55
–149.62
0A
1685
66
TAKAROA
919430
–14.48
–145.03
0A
1529
60
TUBUAI
919540
–23.35
–149.48
2A
1880
74
French Southern Territories (ATF)
PORT-AUX-FRANCAIS
619980
–49.30
70.20
6A
1132
45
French Southern Territories (ATF)
PORT-AUX-FRANCAIS
619980
–49.30
70.20
6A
1132
45
Gabon (GAB)
LIBREVILLE
645000
0.45
9.42
0A
2769
109
Gabon (GAB)
LIBREVILLE
645000
0.45
9.42
0A
2769
109
Gambia (GMB)
BANJUL/YUNDUM
617010
13.20
–16.63
0A
1162
46
Georgia (GEO)
BATUMI
374840
41.62
41.60
3A
2575
101
KUTAISI
373950
42.27
42.63
3A
1599
63
PASANAURI
374320
42.35
44.70
5A
1507
59
SUHUMI
372600
42.87
41.13
4A
1532
60
TBILISI
375490
41.68
44.95
4A
480
19
Gambia (GMB)
BANJUL/YUNDUM
617010
13.20
–16.63
0A
1162
46
Georgia (GEO)
BATUMI
374840
41.62
41.60
3A
2575
101
KUTAISI
373950
42.27
42.63
3A
1599
63
PASANAURI
374320
42.35
44.70
5A
1507
59
SUHUMI
372600
42.87
41.13
4A
1532
60
TBILISI
375490
41.68
44.95
4A
480
19
Germany (DEU)
AACHEN
105010
50.78
6.10
5A
789
31
AHLHORN(GAFB)
102180
52.88
8.23
5A
744
29
ANGERMUENDE
102910
53.03
14.00
5A
522
21
ARKONA (CAPE)
090910
54.68
13.43
5A
529
21
ARTERN
104600
51.38
11.30
5A
546
21
AUGSBERG/MULHAUSEN
108520
48.43
10.93
5A
810
32
BERGEN
102380
52.82
9.93
5A
766
30
BERLIN/DAHLEM
103810
52.47
13.30
5A
581
23
BERLIN/SCHONEFELD
093850
52.38
13.52
5A
563
22
BERLIN/TEGEL (FAFB)
103820
52.57
13.32
5A
605
24
BERLIN/TEMPELHOF
103840
52.47
13.40
5A
581
23
BITBURG(US ARMY)
106100
49.95
6.57
5A
774
30
BOIZENBURG (AUT)
102490
53.40
10.68
5A
675
27
BOLTENHAGEN
101610
54.00
11.20
5A
607
24
BRAUNSCHWEIG
103480
52.30
10.45
5A
652
26
BREMEN
102240
53.05
8.80
5A
712
28
BREMERHAVEN
101290
53.53
8.58
5A
796
31
BREMGARTEN(GAFB)
109000
47.90
7.62
4A
941
37
BROCKEN (PEAK)
104530
51.80
10.62
7
1753
69
BRUGGEN (RAF)
104010
51.20
6.13
5A
747
29
BUECHEL
106130
50.17
7.07
5A
749
29
BUECKEBURG
103350
52.28
9.08
5A
732
29
CELLE
103430
52.60
10.02
5A
708
28
Germany (DEU)
AACHEN
105010
50.78
6.10
5A
789
31
AHLHORN(GAFB)
102180
52.88
8.23
5A
744
29
ANGERMUENDE
102910
53.03
14.00
5A
522
21
ARKONA (CAPE)
090910
54.68
13.43
5A
529
21
ARTERN
104600
51.38
11.30
5A
546
21
AUGSBERG/MULHAUSEN
108520
48.43
10.93
5A
810
32
BERGEN
102380
52.82
9.93
5A
766
30
BERLIN/DAHLEM
103810
52.47
13.30
5A
581
23
BERLIN/SCHONEFELD
093850
52.38
13.52
5A
563
22
BERLIN/TEGEL (FAFB)
103820
52.57
13.32
5A
605
24
BERLIN/TEMPELHOF
103840
52.47
13.40
5A
581
23
BITBURG(US ARMY)
106100
49.95
6.57
5A
774
30
BOIZENBURG (AUT)
102490
53.40
10.68
5A
675
27
BOLTENHAGEN
101610
54.00
11.20
5A
607
24
BRAUNSCHWEIG
103480
52.30
10.45
5A
652
26
BREMEN
102240
53.05
8.80
5A
712
28
BREMERHAVEN
101290
53.53
8.58
5A
796
31
BREMGARTEN(GAFB)
109000
47.90
7.62
4A
941
37
BROCKEN (PEAK)
104530
51.80
10.62
7
1753
69
BRUGGEN (RAF)
104010
51.20
6.13
5A
747
29
BUECHEL
106130
50.17
7.07
5A
749
29
BUECKEBURG
103350
52.28
9.08
5A
732
29
CELLE
103430
52.60
10.02
5A
708
28

434 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 437

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
LEINEFELDE (AUT)
104490
51.40
10.32
5A
689
27
LEIPZIG
104710
51.32
12.42
5A
513
20
LEIPZIG/SCHKEUDITZ
104690
51.42
12.23
5A
527
21
LINDENBERG
093930
52.22
14.12
5A
548
22
LUEDENSCHEID
104180
51.25
7.65
5A
1219
48
MAGDEBURG
093610
52.10
11.58
5A
508
20
MARNITZ (AUT)
102640
53.32
11.93
5A
608
24
MEININGEN
105480
50.57
10.38
6A
662
26
MEMMINGEN (GER-AFB)
109470
47.98
10.23
5A
1179
46
MENDIG
105140
50.37
7.32
5A
719
28
MESSSTETTEN
108270
48.18
9.00
6A
869
34
MUNICH
108650
48.13
11.55
5A
991
39
MUNICH/RIEM
108660
48.13
11.70
5A
928
37
NEUBURG/DONAU
108530
48.72
11.22
5A
766
30
NEUHAUSEN OB ECK
109210
47.98
8.90
6A
850
33
NEURUPPIN
102700
52.90
12.82
5A
566
22
NIEDERSTETTEN
107430
49.38
9.97
5A
781
31
NOERVENICH
105020
50.83
6.67
5A
701
28
NORDHOLZ
101360
53.77
8.67
5A
835
33
NUERBURG-BARWEILER
105060
50.37
6.87
5A
744
29
NURNBERG
107630
49.50
11.08
5A
627
25
OLDENBURG
102150
53.18
8.17
5A
765
30
OSCHATZ
104800
51.30
13.10
5A
571
22
PASSAU
108930
48.58
13.47
5A
955
38
PFERDSFELD (GER-AF)
106260
49.85
7.60
5A
628
25
PLAUEN (AUT)
105690
50.48
12.13
5A
727
29
POTSDAM
093790
52.38
13.07
5A
580
23
QUICKBORN
101460
53.73
9.88
5A
750
30
RAMSTEIN
106140
49.43
7.60
5A
864
34
REGENSBURG/OBERHUB
107760
49.05
12.10
5A
636
25
RHEINE-BENTLAGE
103060
52.30
7.38
5A
761
30
ROTH
107650
49.22
11.10
5A
725
29
SAARBRUCKEN/ENSHEIM
107080
49.22
7.12
5A
852
34
SCHLESWIG-JAGEL
100370
54.47
9.52
5A
898
35
SCHMUECKE (RIDGE)
105520
50.65
10.77
6A
893
35
SCHWERIN
091620
53.63
11.42
5A
629
25
SEEHAUSEN/ALTMARK
092610
52.90
11.73
5A
557
22
SONNEBERG/NEUFANG
105580
50.38
11.18
6A
896
35
SPANGDAHLEM
106070
49.98
6.70
5A
774
30
STRAUBING
107880
48.83
12.57
5A
835
33
STUTTGART/ECHTERDI
107380
48.68
9.22
5A
718
28
STUTTGART/SCHNARREN
107390
48.83
9.20
5A
672
26
TETEROW
101770
53.77
12.62
5A
592
23
TRIER/PETRISBERG
106090
49.75
6.67
5A
764
30
TROLLENHAGEN
102810
53.60
13.32
5A
548
22
UECKERMUENDE (AUT)
091930
53.75
14.07
5A
546
21
WAREN
102680
53.52
12.67
5A
567
22
WARNEMUENDE
091700
54.18
12.08
5A
597
23
WASSERKUPPE (MOUNT)
105440
50.50
9.95
6A
883
35
WEIMAR
105550
50.98
11.32
5A
572
23
WERNIGERODE (AUT)
104540
51.85
10.77
5A
587
23
WESTERMARKELSDORF
100550
54.53
11.07
5A
585
23
WIESENBURG
103680
52.12
12.47
5A
578
23
WILDENRATH(GAFB)
104020
51.12
6.22
5A
747
29
WITTENBERG
104740
51.88
12.65
5A
576
23
WITTMUNDHAVEN
101260
53.55
7.67
5A
793
31
WUNSTORF
103340
52.47
9.43
5A
773
30
ZINNWALD/GEORGENFE
105820
50.73
13.75
6A
686
27
ZUGSPITZE MOUNTAIN
109610
47.42
10.98
8
2020
80
LEINEFELDE (AUT)
104490
51.40
10.32
5A
689
27
LEIPZIG
104710
51.32
12.42
5A
513
20
LEIPZIG/SCHKEUDITZ
104690
51.42
12.23
5A
527
21
LINDENBERG
093930
52.22
14.12
5A
548
22
LUEDENSCHEID
104180
51.25
7.65
5A
1219
48
MAGDEBURG
093610
52.10
11.58
5A
508
20
MARNITZ (AUT)
102640
53.32
11.93
5A
608
24
MEININGEN
105480
50.57
10.38
6A
662
26
MEMMINGEN (GER-AFB)
109470
47.98
10.23
5A
1179
46
MENDIG
105140
50.37
7.32
5A
719
28
MESSSTETTEN
108270
48.18
9.00
6A
869
34
MUNICH
108650
48.13
11.55
5A
991
39
MUNICH/RIEM
108660
48.13
11.70
5A
928
37
NEUBURG/DONAU
108530
48.72
11.22
5A
766
30
NEUHAUSEN OB ECK
109210
47.98
8.90
6A
850
33
NEURUPPIN
102700
52.90
12.82
5A
566
22
NIEDERSTETTEN
107430
49.38
9.97
5A
781
31
NOERVENICH
105020
50.83
6.67
5A
701
28
NORDHOLZ
101360
53.77
8.67
5A
835
33
NUERBURG-BARWEILER
105060
50.37
6.87
5A
744
29
NURNBERG
107630
49.50
11.08
5A
627
25
OLDENBURG
102150
53.18
8.17
5A
765
30
OSCHATZ
104800
51.30
13.10
5A
571
22
PASSAU
108930
48.58
13.47
5A
955
38
PFERDSFELD (GER-AF)
106260
49.85
7.60
5A
628
25
PLAUEN (AUT)
105690
50.48
12.13
5A
727
29
POTSDAM
093790
52.38
13.07
5A
580
23
QUICKBORN
101460
53.73
9.88
5A
750
30
RAMSTEIN
106140
49.43
7.60
5A
864
34
REGENSBURG/OBERHUB
107760
49.05
12.10
5A
636
25
RHEINE-BENTLAGE
103060
52.30
7.38
5A
761
30
ROTH
107650
49.22
11.10
5A
725
29
SAARBRUCKEN/ENSHEIM
107080
49.22
7.12
5A
852
34
SCHLESWIG-JAGEL
100370
54.47
9.52
5A
898
35
SCHMUECKE (RIDGE)
105520
50.65
10.77
6A
893
35
SCHWERIN
091620
53.63
11.42
5A
629
25
SEEHAUSEN/ALTMARK
092610
52.90
11.73
5A
557
22
SONNEBERG/NEUFANG
105580
50.38
11.18
6A
896
35
SPANGDAHLEM
106070
49.98
6.70
5A
774
30
STRAUBING
107880
48.83
12.57
5A
835
33
STUTTGART/ECHTERDI
107380
48.68
9.22
5A
718
28
STUTTGART/SCHNARREN
107390
48.83
9.20
5A
672
26
TETEROW
101770
53.77
12.62
5A
592
23
TRIER/PETRISBERG
106090
49.75
6.67
5A
764
30
TROLLENHAGEN
102810
53.60
13.32
5A
548
22
UECKERMUENDE (AUT)
091930
53.75
14.07
5A
546
21
WAREN
102680
53.52
12.67
5A
567
22
WARNEMUENDE
091700
54.18
12.08
5A
597
23
WASSERKUPPE (MOUNT)
105440
50.50
9.95
6A
883
35
WEIMAR
105550
50.98
11.32
5A
572
23
WERNIGERODE (AUT)
104540
51.85
10.77
5A
587
23
WESTERMARKELSDORF
100550
54.53
11.07
5A
585
23
WIESENBURG
103680
52.12
12.47
5A
578
23
Gibraltar (GIB)
GIBRALTAR
084950
36.15
–5.35
3A
750
30
LEINEFELDE (AUT)
104490
51.40
10.32
5A
689
27
LEIPZIG
104710
51.32
12.42
5A
513
20
LEIPZIG/SCHKEUDITZ
104690
51.42
12.23
5A
527
21
LINDENBERG
093930
52.22
14.12
5A
548
22
LUEDENSCHEID
104180
51.25
7.65
5A
1219
48
MAGDEBURG
093610
52.10
11.58
5A
508
20
MARNITZ (AUT)
102640
53.32
11.93
5A
608
24
MEININGEN
105480
50.57
10.38
6A
662
26
MEMMINGEN (GER-AFB)
109470
47.98
10.23
5A
1179
46
MENDIG
105140
50.37
7.32
5A
719
28
MESSSTETTEN
108270
48.18
9.00
6A
869
34
MUNICH
108650
48.13
11.55
5A
991
39
MUNICH/RIEM
108660
48.13
11.70
5A
928
37
NEUBURG/DONAU
108530
48.72
11.22
5A
766
30
NEUHAUSEN OB ECK
109210
47.98
8.90
6A
850
33
NEURUPPIN
102700
52.90
12.82
5A
566
22
NIEDERSTETTEN
107430
49.38
9.97
5A
781
31
NOERVENICH
105020
50.83
6.67
5A
701
28
NORDHOLZ
101360
53.77
8.67
5A
835
33
NUERBURG-BARWEILER
105060
50.37
6.87
5A
744
29
NURNBERG
107630
49.50
11.08
5A
627
25
OLDENBURG
102150
53.18
8.17
5A
765
30
OSCHATZ
104800
51.30
13.10
5A
571
22
PASSAU
108930
48.58
13.47
5A
955
38
PFERDSFELD (GER-AF)
106260
49.85
7.60
5A
628
25
PLAUEN (AUT)
105690
50.48
12.13
5A
727
29
POTSDAM
093790
52.38
13.07
5A
580
23
QUICKBORN
101460
53.73
9.88
5A
750
30
RAMSTEIN
106140
49.43
7.60
5A
864
34
REGENSBURG/OBERHUB
107760
49.05
12.10
5A
636
25
RHEINE-BENTLAGE
103060
52.30
7.38
5A
761
30
ROTH
107650
49.22
11.10
5A
725
29
SAARBRUCKEN/ENSHEIM
107080
49.22
7.12
5A
852
34
SCHLESWIG-JAGEL
100370
54.47
9.52
5A
898
35
SCHMUECKE (RIDGE)
105520
50.65
10.77
6A
893
35
SCHWERIN
091620
53.63
11.42
5A
629
25
SEEHAUSEN/ALTMARK
092610
52.90
11.73
5A
557
22
SONNEBERG/NEUFANG
105580
50.38
11.18
6A
896
35
SPANGDAHLEM
106070
49.98
6.70
5A
774
30
STRAUBING
107880
48.83
12.57
5A
835
33
STUTTGART/ECHTERDI
107380
48.68
9.22
5A
718
28
STUTTGART/SCHNARREN
107390
48.83
9.20
5A
672
26
TETEROW
101770
53.77
12.62
5A
592
23
TRIER/PETRISBERG
106090
49.75
6.67
5A
764
30
TROLLENHAGEN
102810
53.60
13.32
5A
548
22
UECKERMUENDE (AUT)
091930
53.75
14.07
5A
546
21
WAREN
102680
53.52
12.67
5A
567
22
WARNEMUENDE
091700
54.18
12.08
5A
597
23
WASSERKUPPE (MOUNT)
105440
50.50
9.95
6A
883
35
WEIMAR
105550
50.98
11.32
5A
572
23
WERNIGERODE (AUT)
104540
51.85
10.77
5A
587
23
WESTERMARKELSDORF
100550
54.53
11.07
5A
585
23
WIESENBURG
103680
52.12
12.47
5A
578
23
Greece (GRC)
AKTION (AIRPORT)
166430
38.95
20.77
3A
917
36
ALEXANDROUPOLI (AIR)
166270
40.85
25.92
4A
554
22
ANDRAVIDA (AIRPORT)
166820
37.92
21.28
3A
820
32
ARAXOS (AIRPORT)
166870
38.15
21.42
3A
659
26
ATHINAI (AIRPORT)
167160
37.90
23.73
3B
353
14
CHRYSOPOULI (AIRPORT)
166240
40.98
24.60
3A
456
18
ELEFSIS (AIRPORT)
167180
38.07
23.55
3A
438
17
HERAKLION (AIRPORT)
167540
35.33
25.18
3A
485
19
KALAMATA (AIRPORT)
167260
37.07
22.02
3A
783
31
KERKYRA (AIRPORT)
166410
39.62
19.92
3A
1057
42
KOS (AIRPORT)
167420
36.78
27.07
3A
687
27
LARISSA (AIRPORT)
166480
39.63
22.42
3B
420
17
LIMNOS (AIRPORT)
166500
39.92
25.23
3A
480
19
METHONI
167340
36.83
21.70
3A
688
27
MILOS
167380
36.72
24.45
3A
409
16
MYTILINI (AIRPORT)
166670
39.07
26.60
3A
662
26
NAXOS
167320
37.10
25.38
3A
602
24
RHODES (AIRPORT)
167490
36.40
28.08
3A
743
29
SAMOS (AIRPORT)
167230
37.70
26.92
3A
606
24
SKYROS (AIRPORT)
166840
38.97
24.48
3A
661
26
SOUDA (AIRPORT)
167460
35.48
24.12
3A
792
31
SOUDA BAY CRETE
167464
35.53
24.15
3A
555
22
THESSALONIKI (AIRPORT)
166220
40.52
22.97
3B
444
17
TRIPOLIS (AIRPORT)
167100
37.53
22.40
4A
802
32
LEINEFELDE (AUT)
104490
51.40
10.32
5A
689
27
LEIPZIG
104710
51.32
12.42
5A
513
20
LEIPZIG/SCHKEUDITZ
104690
51.42
12.23
5A
527
21
LINDENBERG
093930
52.22
14.12
5A
548
22
LUEDENSCHEID
104180
51.25
7.65
5A
1219
48
MAGDEBURG
093610
52.10
11.58
5A
508
20
MARNITZ (AUT)
102640
53.32
11.93
5A
608
24
MEININGEN
105480
50.57
10.38
6A
662
26
MEMMINGEN (GER-AFB)
109470
47.98
10.23
5A
1179
46
MENDIG
105140
50.37
7.32
5A
719
28
MESSSTETTEN
108270
48.18
9.00
6A
869
34
MUNICH
108650
48.13
11.55
5A
991
39
MUNICH/RIEM
108660
48.13
11.70
5A
928
37
NEUBURG/DONAU
108530
48.72
11.22
5A
766
30
NEUHAUSEN OB ECK
109210
47.98
8.90
6A
850
33
NEURUPPIN
102700
52.90
12.82
5A
566
22
NIEDERSTETTEN
107430
49.38
9.97
5A
781
31
NOERVENICH
105020
50.83
6.67
5A
701
28
NORDHOLZ
101360
53.77
8.67
5A
835
33
NUERBURG-BARWEILER
105060
50.37
6.87
5A
744
29
NURNBERG
107630
49.50
11.08
5A
627
25
OLDENBURG
102150
53.18
8.17
5A
765
30
OSCHATZ
104800
51.30
13.10
5A
571
22
PASSAU
108930
48.58
13.47
5A
955
38
PFERDSFELD (GER-AF)
106260
49.85
7.60
5A
628
25
PLAUEN (AUT)
105690
50.48
12.13
5A
727
29
POTSDAM
093790
52.38
13.07
5A
580
23
QUICKBORN
101460
53.73
9.88
5A
750
30
RAMSTEIN
106140
49.43
7.60
5A
864
34
REGENSBURG/OBERHUB
107760
49.05
12.10
5A
636
25
RHEINE-BENTLAGE
103060
52.30
7.38
5A
761
30
ROTH
107650
49.22
11.10
5A
725
29
SAARBRUCKEN/ENSHEIM
107080
49.22
7.12
5A
852
34
SCHLESWIG-JAGEL
100370
54.47
9.52
5A
898
35
SCHMUECKE (RIDGE)
105520
50.65
10.77
6A
893
35
SCHWERIN
091620
53.63
11.42
5A
629
25
SEEHAUSEN/ALTMARK
092610
52.90
11.73
5A
557
22
SONNEBERG/NEUFANG
105580
50.38
11.18
6A
896
35
SPANGDAHLEM
106070
49.98
6.70
5A
774
30
STRAUBING
107880
48.83
12.57
5A
835
33
STUTTGART/ECHTERDI
107380
48.68
9.22
5A
718
28
STUTTGART/SCHNARREN
107390
48.83
9.20
5A
672
26
TETEROW
101770
53.77
12.62
5A
592
23
TRIER/PETRISBERG
106090
49.75
6.67
5A
764
30
TROLLENHAGEN
102810
53.60
13.32
5A
548
22
UECKERMUENDE (AUT)
091930
53.75
14.07
5A
546
21
WAREN
102680
53.52
12.67
5A
567
22
WARNEMUENDE
091700
54.18
12.08
5A
597
23
WASSERKUPPE (MOUNT)
105440
50.50
9.95
6A
883
35
WEIMAR
105550
50.98
11.32
5A
572
23
WERNIGERODE (AUT)
104540
51.85
10.77
5A
587
23
WESTERMARKELSDORF
100550
54.53
11.07
5A
585
23
WIESENBURG
103680
52.12
12.47
5A
578
23
Greenland (GRL)
AASIAAT (EGEDESMINDE)
042200
68.70
–52.85
8
287
11
ANGISOQ
042850
59.98
–45.20
7
1524
60
APUTITEEQ
043510
67.78
–32.30
8
949
37
DANEBORG
043300
74.30
–20.22
8
236
9
DANMARKSHAVN
043200
76.77
–18.67
8
156
6
HALL LAND
042070
81.68
–59.93
8
153
6
HENRIK KROEYER HOLM
043130
80.65
–13.72
8
226
9
IKERMIIT
043730
64.78
–40.30
8
918
36
IKERMIUARSUK
043820
61.93
–42.07
7
1333
52
ILULISSAT (JAKOBSHAVN)
042210
69.23
–51.07
8
258
10
ITTOQQORTOORMIIT
043390
70.48
–21.95
8
411
16
KANGERLUSSUAQ (SDR.)
042310
67.02
–50.70
8
181
7
KAP MORRIS JESUP
043010
83.65
–33.37
8
202
8
KITSISSORSUIT
042080
74.03
–57.82
8
230
9
KITSISSUT (ATTU)
042280
67.78
–53.97
8
325
13
KITSISSUT (CAREY OEER)
042030
76.63
–73.00
8
212
8
NARSARSUAQ
042700
61.13
–45.43
7
615
24
NUNARSUIT
042660
60.77
–48.42
7
1008
40
NUUK (GODTHAAB)
042500
64.17
–51.75
8
735
29

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 435

PDF Page 438

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
NUUSSUAATAA
042140
70.68
–54.62
8
273
11
PAAMIUT (FREDERIKSHAAB)
042600
62.00
–49.67
8
885
35
PITUFFIK (THULE A.B.)
042020
76.53
–68.75
8
113
4
PRINS CHRISTIAN SUN
043900
60.05
–43.17
7
2102
83
QAQORTOQ (JULIANEHAAB)
042720
60.72
–46.05
7
851
33
SIORALIK
042420
65.02
–52.55
8
588
23
SISIMIUT (HOLSTEINS)
042300
66.92
–53.67
8
379
15
STATION NORD AWS
043120
81.60
–16.68
8
233
9
TASIILAQ (AMMASSALIK)
043600
65.60
–37.63
8
910
36
UKIIVIK (FREDERIKSHAAB)
042530
62.57
–50.42
7
858
34
AKURNES
040820
64.30
–15.22
7
1370
54
BERGSTADIR
040530
65.70
–19.62
7
504
20
BOLUNGAVIK
040050
66.15
–23.25
7
969
38
DALATANGI
040970
65.27
–13.58
7
1301
51
EGILSSTADIR
040890
65.28
–14.40
7
760
30
GUFUSKALAR
040040
64.90
–23.93
7
1067
42
HORNBJARGSVITI (LH)
040230
66.42
–22.38
7
1018
40
HVERAVELLIR
040560
64.87
–19.57
7
701
28
KEFLAVIK
040180
63.97
–22.60
6A
1109
44
KIRKJUBAEJARKLAUSTU
040640
63.78
–18.07
6A
1857
73
RAUFARHOFN
040770
66.45
–15.95
7
686
27
REYKJAVIK
040300
64.13
–21.90
6A
818
32
VESTMANNAEYJAR
040480
63.40
–20.28
6A
1572
62
Grenada (GRD)
POINT SALINES AIRPO
789580
12.00
–61.78
0A
1197
47
Grenada (GRD)
POINT SALINES AIRPO
789580
12.00
–61.78
0A
1197
47
Guam (GUM)
ANDERSEN AFB
912180
13.57
144.92
0A
2354
93
GUAM WFO
912120
13.48
144.80
0A
2288
90
Guam (GUM)
ANDERSEN AFB
912180
13.57
144.92
0A
2354
93
GUAM WFO
912120
13.48
144.80
0A
2288
90
Guam (GUM)
ANDERSEN AFB
912180
13.57
144.92
0A
2354
93
GUAM WFO
912120
13.48
144.80
0A
2288
90
India (IND)
AGARTALA
427240
23.88
91.25
1A
2260
89
AHMADABAD
426470
23.07
72.63
0B
773
30
AKOLA
429340
20.70
77.07
0B
772
30
AURANGABAD CHIKALTH
430140
19.85
75.40
1A
799
31
BALASORE
428950
21.52
86.93
0A
1635
64
BANGALORE
432950
12.97
77.58
1A
997
39
BELGAUM/SAMBRA
431980
15.85
74.62
1A
1063
42
BHOPAL/BAIRAGARH
426670
23.28
77.35
1A
1207
48
BHUBANESWAR
429710
20.25
85.83
0A
1514
60
BHUJ-RUDRAMATA
426340
23.25
69.67
0B
362
14
BIKANER
421650
28.00
73.30
0B
285
11
BOMBAY/SANTACRUZ
430030
19.12
72.85
0A
2448
96
CALCUTTA/DUM DUM
428090
22.65
88.45
0A
1675
66
CHITRADURGA
432330
14.23
76.43
1B
608
24
COIMBATORE/PEELAMED
433210
11.03
77.05
0B
648
26
CUDDALORE
433290
11.77
79.77
0A
1384
54
CWC VISHAKHAPATNAM
431500
17.70
83.30
0A
996
39
GADAG
432010
15.42
75.63
1B
669
26
GAUHATI
424100
26.10
91.58
1A
1690
67
GOA/PANJIM
431920
15.48
73.82
0A
2840
112
GWALIOR
423610
26.23
78.25
1A
817
32
HISSAR
421310
29.17
75.73
1B
401
16
HYDERABAD AIRPORT
431280
17.45
78.47
0A
822
32
INDORE
427540
22.72
75.80
1A
956
38
JABALPUR
426750
23.20
79.95
1A
1336
53
JAGDALPUR
430410
19.08
82.03
1A
1435
56
JAIPUR/SANGANER
423480
26.82
75.80
1B
562
22
JAMSHEDPUR
427980
22.82
86.18
0A
1434
56
JODHPUR
423390
26.30
73.02
0B
342
13
KAKINADA
431890
16.95
82.23
0A
1048
41
KOZHIKODE
433140
11.25
75.78
0A
3163
125
KURNOOL
432130
15.80
78.07
0B
695
27
LUCKNOW/AMAUSI
423690
26.75
80.88
1A
1038
41
MACHILIPATNAM
431850
16.20
81.15
0A
1090
43
MADRAS/MINAMBAKKAM
432790
13.00
80.18
0A
1401
55
MANGALORE/BAJPE
432840
12.92
74.88
0A
3730
147
NAGPUR SONEGAON
428670
21.10
79.05
0A
1110
44
NELLORE
432450
14.45
79.98
0A
1046
41
NEW DELHI/PALAM
421810
28.57
77.12
1B
783
31
Guatemala (GTM)
GUATEMALA (AEROPUERTO)
786410
14.58
–90.52
2A
1141
45
Guatemala (GTM)
GUATEMALA (AEROPUERTO)
786410
14.58
–90.52
2A
1141
45
Guernsey (GGY)
GUERNSEY AIRPORT
038940
49.43
–2.60
4A
872
34
Guernsey (GGY)
GUERNSEY AIRPORT
038940
49.43
–2.60
4A
872
34
Guyana (GUY)
TIMEHRI\CHEDDI JAG
810020
6.50
–58.25
0A
2234
88
Guyana (GUY)
TIMEHRI\CHEDDI JAG
810020
6.50
–58.25
0A
2234
88
Honduras (HND)
LA MESA (SAN PEDRO SULA)
787080
15.45
–87.93
0A
1192
47
TEGUCIGALPA
787200
14.05
–87.22
2A
1085
43
Honduras (HND)
LA MESA (SAN PEDRO SULA)
787080
15.45
–87.93
0A
1192
47
TEGUCIGALPA
787200
14.05
–87.22
2A
1085
43
Hungary (HUN)
BAJA
129600
46.18
19.02
5A
592
23
BEKESCSABA
129920
46.68
21.17
5A
551
22
BUDAORS
128380
47.45
18.97
5A
560
22
BUDAPEST/FERIHEGY I
128390
47.43
19.27
5A
533
21
BUDAPEST/PESTSZENTL
128430
47.43
19.18
5A
533
21
DEBRECEN
128820
47.48
21.60
5A
559
22
GYOR
128220
47.72
17.68
5A
573
23
KECSKEMET
129700
46.92
19.75
5A
521
20
KEKESTETO
128510
47.87
20.02
6A
614
24
KESZTHELY
129200
46.73
17.23
5A
667
26
MISKOLC
127720
48.10
20.77
5A
557
22
MOSONMAGYAROVAR
128150
47.88
17.28
5A
570
22
NAGYKANIZSA
129250
46.45
16.97
5A
767
30
NYIREGYHAZA/NAPKOR
128920
47.97
21.88
5A
541
21
PAKS
129500
46.58
18.85
5A
564
22
PAPA
128250
47.20
17.50
5A
646
25
PECS/POGANY
129420
46.00
18.23
4A
648
25
SIOFOK
129350
46.92
18.05
4A
612
24
SOPRON
128050
47.68
16.60
5A
663
26
SZEGED
129820
46.25
20.10
5A
507
20
SZENTGOTTHARD/FARKA
129100
46.92
16.32
5A
788
31
SZOLNOK
128600
47.12
20.23
5A
509
20
SZOMBATHELY
128120
47.27
16.63
5A
662
26
TASZAR
129320
46.40
17.92
4A
662
26
VESZPREM/SZENTKIRAL
128300
47.07
17.83
5A
617
24
ZALAEGERSZEG/ANDRAS
129150
46.87
16.80
5A
693
27
Hungary (HUN)
BAJA
129600
46.18
19.02
5A
592
23
BEKESCSABA
129920
46.68
21.17
5A
551
22
BUDAORS
128380
47.45
18.97
5A
560
22
BUDAPEST/FERIHEGY I
128390
47.43
19.27
5A
533
21
BUDAPEST/PESTSZENTL
128430
47.43
19.18
5A
533
21
DEBRECEN
128820
47.48
21.60
5A
559
22
GYOR
128220
47.72
17.68
5A
573
23
KECSKEMET
129700
46.92
19.75
5A
521
20
KEKESTETO
128510
47.87
20.02
6A
614
24
KESZTHELY
129200
46.73
17.23
5A
667
26
MISKOLC
127720
48.10
20.77
5A
557
22
MOSONMAGYAROVAR
128150
47.88
17.28
5A
570
22
NAGYKANIZSA
129250
46.45
16.97
5A
767
30
NYIREGYHAZA/NAPKOR
128920
47.97
21.88
5A
541
21
PAKS
129500
46.58
18.85
5A
564
22
PAPA
128250
47.20
17.50
5A
646
25
PECS/POGANY
129420
46.00
18.23
4A
648
25
SIOFOK
129350
46.92
18.05
4A
612
24
SOPRON
128050
47.68
16.60
5A
663
26
SZEGED
129820
46.25
20.10
5A
507
20
SZENTGOTTHARD/FARKA
129100
46.92
16.32
5A
788
31
SZOLNOK
128600
47.12
20.23
5A
509
20
SZOMBATHELY
128120
47.27
16.63
5A
662
26
TASZAR
129320
46.40
17.92
4A
662
26
VESZPREM/SZENTKIRAL
128300
47.07
17.83
5A
617
24
ZALAEGERSZEG/ANDRAS
129150
46.87
16.80
5A
693
27
Iceland (ISL)
AKUREYRI
040630
65.68
–18.08
7
500
20
Iceland (ISL)
AKUREYRI
040630
65.68
–18.08
7
500
20

436 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 439

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
NEW DELHI/SAFDARJUN
421820
28.58
77.20
1B
783
31
PATIALA
421010
30.33
76.47
2B
728
29
PATNA
424920
25.60
85.10
1A
1169
46
PBO ANANTAPUR
432370
14.58
77.63
0B
533
21
POONA
430630
18.53
73.85
1B
733
29
RAJKOT
427370
22.30
70.78
0B
659
26
RATNAGIRI
431100
16.98
73.33
0A
2851
112
SHOLAPUR
431170
17.67
75.90
0B
716
28
SURAT
428400
21.20
72.83
0A
1252
49
THIRUVANANTHAPURAM
433710
8.48
76.95
0A
1795
71
TIRUCHCHIRAPALLI
433440
10.77
78.72
0A
915
36
VERAVAL
429090
20.90
70.37
0B
802
32
CLONES
039740
54.18
–7.23
5A
942
37
CONNAUGHT AIRPORT
039730
53.90
–8.82
5A
1264
50
CORK AIRPORT
039550
51.85
–8.48
5A
1221
48
DUBLIN AIRPORT
039690
53.43
–6.25
5A
743
29
KILKENNY
039600
52.67
–7.27
5A
842
33
MALIN HEAD
039800
55.37
–7.33
5A
1084
43
MULLINGAR
039710
53.53
–7.37
5A
945
37
ROCHES POINT
039520
51.80
–8.25
4A
945
37
ROSSLARE
039570
52.25
–6.33
4A
877
35
SHANNON AIRPORT
039620
52.70
–8.92
4A
960
38
VALENTIA OBSERVATOR
039530
51.93
–10.25
4A
1488
59
NEW DELHI/SAFDARJUN
421820
28.58
77.20
1B
783
31
PATIALA
421010
30.33
76.47
2B
728
29
PATNA
424920
25.60
85.10
1A
1169
46
PBO ANANTAPUR
432370
14.58
77.63
0B
533
21
POONA
430630
18.53
73.85
1B
733
29
RAJKOT
427370
22.30
70.78
0B
659
26
RATNAGIRI
431100
16.98
73.33
0A
2851
112
SHOLAPUR
431170
17.67
75.90
0B
716
28
SURAT
428400
21.20
72.83
0A
1252
49
THIRUVANANTHAPURAM
433710
8.48
76.95
0A
1795
71
TIRUCHCHIRAPALLI
433440
10.77
78.72
0A
915
36
VERAVAL
429090
20.90
70.37
0B
802
32
Isle of Man (IMN)
ISLE OF MAN/RONALDS
032040
54.08
–4.63
5A
947
37
POINT OF AYRE (LH)
032080
54.42
–4.37
4A
838
33
Indonesia (IDN)
DENPASAR/NGURAH RAI
972300
–8.75
115.17
0A
1558
61
JAKARTA/SOEKARNO-HA
967490
–6.12
106.65
0A
1979
78
MEDAN/POLONIA
960350
3.57
98.68
0A
2465
97
MENADO/ SAM RATULAN
970140
1.53
124.92
0A
3143
124
PADANG/TABING
961630
–0.88
100.35
0A
3801
150
PEKAN BARU/SIMPANGT
961090
0.47
101.45
0A
2603
102
RENGAT/JAPURA
961710
–0.33
102.32
0A
2230
88
SIBOLGA/PINANGSORI
960730
1.55
98.88
0A
4076
160
SURABAYA/JUANDA
969350
–7.37
112.77
0A
1650
65
UJUNG PANDANG/HASAN
971800
–5.07
119.55
0A
3307
130
Indonesia (IDN)
DENPASAR/NGURAH RAI
972300
–8.75
115.17
0A
1558
61
JAKARTA/SOEKARNO-HA
967490
–6.12
106.65
0A
1979
78
MEDAN/POLONIA
960350
3.57
98.68
0A
2465
97
MENADO/ SAM RATULAN
970140
1.53
124.92
0A
3143
124
PADANG/TABING
961630
–0.88
100.35
0A
3801
150
PEKAN BARU/SIMPANGT
961090
0.47
101.45
0A
2603
102
RENGAT/JAPURA
961710
–0.33
102.32
0A
2230
88
SIBOLGA/PINANGSORI
960730
1.55
98.88
0A
4076
160
SURABAYA/JUANDA
969350
–7.37
112.77
0A
1650
65
UJUNG PANDANG/HASAN
971800
–5.07
119.55
0A
3307
130
Indonesia (IDN)
DENPASAR/NGURAH RAI
972300
–8.75
115.17
0A
1558
61
JAKARTA/SOEKARNO-HA
967490
–6.12
106.65
0A
1979
78
MEDAN/POLONIA
960350
3.57
98.68
0A
2465
97
MENADO/ SAM RATULAN
970140
1.53
124.92
0A
3143
124
PADANG/TABING
961630
–0.88
100.35
0A
3801
150
PEKAN BARU/SIMPANGT
961090
0.47
101.45
0A
2603
102
RENGAT/JAPURA
961710
–0.33
102.32
0A
2230
88
SIBOLGA/PINANGSORI
960730
1.55
98.88
0A
4076
160
SURABAYA/JUANDA
969350
–7.37
112.77
0A
1650
65
UJUNG PANDANG/HASAN
971800
–5.07
119.55
0A
3307
130
Israel (ISR)
BEER-SHEVA
401910
31.23
34.78
2B
193
8
BEN-GURION INT. AIR
401800
32.00
34.90
2A
563
22
EILAT
401990
29.55
34.95
1B
23
1
HAIFA
401550
32.80
35.03
2A
613
24
OVDA
401980
30.00
34.83
2B
25
1
SDE-DOV (TEL-AVIV)
401760
32.10
34.78
2A
564
22
Indonesia (IDN)
DENPASAR/NGURAH RAI
972300
–8.75
115.17
0A
1558
61
JAKARTA/SOEKARNO-HA
967490
–6.12
106.65
0A
1979
78
MEDAN/POLONIA
960350
3.57
98.68
0A
2465
97
MENADO/ SAM RATULAN
970140
1.53
124.92
0A
3143
124
PADANG/TABING
961630
–0.88
100.35
0A
3801
150
PEKAN BARU/SIMPANGT
961090
0.47
101.45
0A
2603
102
RENGAT/JAPURA
961710
–0.33
102.32
0A
2230
88
SIBOLGA/PINANGSORI
960730
1.55
98.88
0A
4076
160
SURABAYA/JUANDA
969350
–7.37
112.77
0A
1650
65
UJUNG PANDANG/HASAN
971800
–5.07
119.55
0A
3307
130
Italy (ITA)
ALGHERO
165200
40.63
8.28
3A
583
23
AMENDOLA
162610
41.53
15.72
3A
508
20
AVIANO (USAF)
160365
46.02
12.62
4A
1404
55
BARI/PALESE MACCHIE
162700
41.13
16.78
3A
549
22
BERGAMO/ORIO AL SER
160760
45.67
9.70
4A
1085
43
BOLOGNA/BORGO PANIG
161400
44.53
11.30
4A
725
29
BOLZANO
160200
46.47
11.33
4A
725
29
BRESCIA/GHEDI
160880
45.42
10.28
4A
896
35
BRINDISI
163200
40.65
17.95
3A
601
24
CAGLIARI/ELMAS
165600
39.25
9.07
3A
422
17
CAMPOBASSO
162520
41.57
14.65
4A
634
25
CAPO BELLAVISTA
165500
39.93
9.72
3A
604
24
CAPO CACCIA
165220
40.57
8.17
3A
521
21
CAPO FRASCA
165390
39.75
8.47
3A
541
21
CAPO MELE
161530
43.95
8.17
3A
786
31
CAPO PALINURO
163100
40.02
15.28
3A
766
30
CATANIA/FONTANAROSS
164600
37.47
15.05
3A
564
22
CATANIA/SIGONELLA
164590
37.40
14.92
3A
518
20
CERVIA
161480
44.22
12.30
4A
722
28
COZZO SPADARO
164800
36.68
15.13
3B
364
14
CROTONE
163500
39.00
17.07
3A
707
28
DOBBIACO
160330
46.73
12.22
6A
876
34
FALCONARA
161910
43.62
13.37
3A
809
32
FIRENZE/PERETOLA
161700
43.80
11.20
3A
847
33
FORLI
161470
44.20
12.07
4A
747
29
FUCINO
162270
41.88
13.58
4C
923
36
GELA
164530
37.08
14.22
3A
384
15
GENOVA/SESTRI
161200
44.42
8.85
3A
1110
44
GIOIA DEL COLLE
163120
40.77
16.93
3A
672
26
GRAZZANISE
162530
41.05
14.07
3A
930
37
GROSSETO
162060
42.75
11.07
3A
653
26
Iran, Islamic Republic of (IRN)
ABADAN
408310
30.37
48.25
1B
160
6
AHWAZ
408110
31.33
48.67
1B
222
9
ANZALI
407180
37.47
49.47
3A
1427
56
ARAK
407690
34.10
49.77
4A
351
14
BABULSAR
407360
36.72
52.65
3A
799
31
BANDARABBASS
408750
27.22
56.37
0B
181
7
BIRJAND
408090
32.87
59.20
3B
190
7
ESFAHAN
408000
32.47
51.67
3B
143
6
HAMEDAN
407680
34.85
48.53
4A
351
14
KASHAN
407850
33.98
51.45
2B
141
6
KERMAN
408410
30.25
56.97
3B
157
6
KERMANSHAH
407660
34.27
47.12
4A
450
18
KHOY
407030
38.55
44.97
4B
359
14
MASHHAD
407450
36.27
59.63
4B
268
11
ORUMIEH
407120
37.53
45.08
4B
274
11
RAMSAR
407320
36.90
50.67
3A
1144
45
SABZEVAR
407430
36.22
57.67
3B
193
8
SHAHRUD
407390
36.42
54.95
4B
175
7
SHIRAZ
408480
29.53
52.53
3A
381
15
TABRIZ
407060
38.08
46.28
4B
270
11
TEHRAN-MEHRABAD
407540
35.68
51.32
3B
217
9
TORBAT-HEYDARIEH
407620
35.27
59.22
4B
282
11
ZAHEDAN
408560
29.47
60.88
2B
87
3
ZANJAN
407290
36.68
48.48
4B
314
12
Iran, Islamic Republic of (IRN)
ABADAN
408310
30.37
48.25
1B
160
6
AHWAZ
408110
31.33
48.67
1B
222
9
ANZALI
407180
37.47
49.47
3A
1427
56
ARAK
407690
34.10
49.77
4A
351
14
BABULSAR
407360
36.72
52.65
3A
799
31
BANDARABBASS
408750
27.22
56.37
0B
181
7
BIRJAND
408090
32.87
59.20
3B
190
7
ESFAHAN
408000
32.47
51.67
3B
143
6
HAMEDAN
407680
34.85
48.53
4A
351
14
KASHAN
407850
33.98
51.45
2B
141
6
KERMAN
408410
30.25
56.97
3B
157
6
KERMANSHAH
407660
34.27
47.12
4A
450
18
KHOY
407030
38.55
44.97
4B
359
14
MASHHAD
407450
36.27
59.63
4B
268
11
ORUMIEH
407120
37.53
45.08
4B
274
11
RAMSAR
407320
36.90
50.67
3A
1144
45
SABZEVAR
407430
36.22
57.67
3B
193
8
SHAHRUD
407390
36.42
54.95
4B
175
7
SHIRAZ
408480
29.53
52.53
3A
381
15
TABRIZ
407060
38.08
46.28
4B
270
11
TEHRAN-MEHRABAD
407540
35.68
51.32
3B
217
9
TORBAT-HEYDARIEH
407620
35.27
59.22
4B
282
11
ZAHEDAN
408560
29.47
60.88
2B
87
3
ZANJAN
407290
36.68
48.48
4B
314
12
Ireland (IRL)
BELMULLET
039760
54.23
–10.00
4A
1185
47
BIRR
039650
53.08
–7.88
5A
825
32
CASEMENT AERODROME
039670
53.30
–6.43
5A
735
29
CLAREMORRIS
039700
53.72
–8.98
5A
1146
45
Ireland (IRL)
BELMULLET
039760
54.23
–10.00
4A
1185
47
BIRR
039650
53.08
–7.88
5A
825
32
CASEMENT AERODROME
039670
53.30
–6.43
5A
735
29
CLAREMORRIS
039700
53.72
–8.98
5A
1146
45

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 437

PDF Page 440

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
ISOLA DI CARLOFORTE
165490
39.13
8.32
3A
571
22
LAMEZIA TERME
163620
38.90
16.25
3A
927
36
LAMPEDUSA
164900
35.50
12.60
2B
270
11
LATINA
162430
41.55
12.90
3A
969
38
LECCE
163320
40.23
18.15
3A
662
26
MARINA DI GINOSA
163250
40.43
16.88
3B
449
18
MESSINA
164200
38.20
15.55
3A
852
34
MILANO/LINATE
160800
45.43
9.28
4A
971
38
MILANO/MALPENSA
160660
45.62
8.73
4A
1087
43
MONTE ARGENTARIO
161680
42.38
11.17
4A
525
21
MONTE CIMONE
161340
44.20
10.70
7
778
31
MONTE SCURO
163440
39.33
16.40
5C
822
32
MONTE TERMINILLO
162190
42.47
12.98
6A
787
31
NAPLES
162894
40.90
14.30
3A
1019
40
NAPOLI/CAPODICHINO
162890
40.85
14.30
3A
1019
40
NOVARA/CAMERI
160640
45.52
8.67
4A
1087
43
NOVI LIGURE
161180
44.77
8.78
4A
812
32
OLBIA/COSTA SMERALD
165310
40.90
9.52
3A
535
21
PAGANELLA
160220
46.15
11.03
7
917
36
PALERMO/PUNTA RAISI
164050
38.18
13.10
3A
620
24
PANTELLERIA
164700
36.82
11.97
3B
442
17
PASSO ROLLE
160210
46.30
11.78
7
1044
41
PERUGIA
161810
43.08
12.50
4A
850
33
PESCARA
162300
42.43
14.20
3A
696
27
PIACENZA
160840
44.92
9.73
4A
911
36
PIAN ROSA
160520
45.93
7.70
8
513
20
PISA/S. GIUSTO
161580
43.68
10.38
3A
890
35
PONZA
162800
40.92
12.95
3A
631
25
PRATICA DI MARE
162450
41.65
12.45
3A
812
32
REGGIO CALABRIA
164220
38.07
15.65
3A
680
27
RESIA PASS
160083
46.83
10.50
6A
747
29
RIMINI
161490
44.03
12.62
4A
716
28
ROMA FIUMICINO
162420
41.80
12.23
3A
708
28
ROMA/CIAMPINO
162390
41.78
12.58
3A
800
32
RONCHI DEI LEGIONAR
161080
45.82
13.48
4A
1331
52
S. MARIA DI LEUCA
163600
39.82
18.35
3A
662
26
S. VALENTINO ALLA M
160080
46.75
10.53
6A
694
27
TORINO/BRIC DELLA C
160610
45.03
7.73
4A
816
32
TORINO/CASELLE
160590
45.22
7.65
4A
929
37
TRAPANI/BIRGI
164290
37.92
12.50
3A
470
18
TREVISO/ISTRANA
160980
45.68
12.10
4A
966
38
TREVISO/S. ANGELO
160990
45.65
12.18
4A
966
38
TRIESTE
161100
45.65
13.75
3A
1036
41
UDINE/RIVOLTO
160450
45.98
13.03
4A
1240
49
USTICA
164000
38.70
13.18
3A
400
16
VENEZIA/TESSERA
161050
45.50
12.33
4A
859
34
VERONA/VILLAFRANCA
160900
45.38
10.87
4A
769
30
Jamaica (JAM)
KINGSTON/NORMAN MAN
783970
17.93
–76.78
0A
730
29
MONTEGO BAY/SANGSTE
783880
18.50
–77.92
0A
1184
47
AIKAWA
476020
38.03
138.23
4A
1595
63
AJIRO
476680
35.05
139.10
3A
1832
72
AKITA
475820
39.72
140.10
4A
1727
68
AKUNE
478230
32.03
130.20
3A
2151
85
AOMORI
475750
40.82
140.77
5A
1325
52
ASAHIKAWA
474070
43.77
142.37
6A
1066
42
ASHIYA AB
478030
33.88
130.65
3A
1798
71
ASOSAN
478210
32.88
131.07
5A
2852
112
ATSUGI NAS
476790
35.45
139.45
3A
1556
61
CHIBA
476820
35.60
140.10
3A
1371
54
CHICHIBU
476410
35.98
139.07
4A
1382
54
CHICHIJIMA ISLAND
479710
27.08
142.18
2A
1321
52
CHITOSE (JASDF)
474340
42.82
141.68
6A
1212
48
CHITOSE AB
474250
42.80
141.67
6A
1212
48
CHOSHI
476480
35.73
140.85
3A
1641
65
ESASHI
474280
41.87
140.12
5A
1222
48
FUJISAN
476390
35.37
138.73
8
1624
64
FUKAURA
475740
40.65
139.93
5A
1508
59
FUKUE
478430
32.70
128.83
3A
1862
73
FUKUI
476160
36.05
136.22
4A
2381
94
FUKUOKA
478070
33.58
130.38
3A
1620
64
FUKUOKA AIRPORT
478080
33.58
130.45
3A
1620
64
FUKUSHIMA
475950
37.77
140.47
4A
1148
45
FUKUYAMA
477670
34.45
133.25
3A
1186
47
FUSHIKI
476060
36.80
137.05
4A
2302
91
FUTENMA
479330
26.27
127.75
2A
2078
82
GIFU
476320
35.40
136.77
3A
1820
72
GIFU AB
476340
35.38
136.87
3A
1820
72
HABORO
474040
44.37
141.70
6A
1322
52
HACHIJOJIMA
476780
33.12
139.78
3A
3153
124
HACHINOHE
475810
40.53
141.52
5A
1074
42
HACHINOHE AB
475150
40.55
141.47
5A
1114
44
HAGI
477540
34.42
131.40
3A
1773
70
HAKODATE
474300
41.82
140.75
5A
1172
46
HAMADA
477550
34.90
132.07
3A
1649
65
HAMAMATSU
476540
34.72
137.72
3A
1859
73
HAMAMATSU AB
476810
34.75
137.70
3A
1859
73
HIKONE
477610
35.28
136.25
4A
2007
79
HIMEJI
477690
34.83
134.67
3A
1352
53
HIRADO
478050
33.37
129.55
3A
2036
80
HIROO
474400
42.30
143.32
6A
1511
59
HIROSHIMA
477650
34.40
132.47
3A
1565
62
HITA
478140
33.32
130.93
3A
1883
74
HITOYOSHI
478240
32.22
130.75
3A
2414
95
HOFU AB
477880
34.03
131.55
3A
1829
72
HYAKURI AB
477150
36.18
140.42
4A
1308
52
IIDA
476370
35.52
137.82
4A
1537
61
IIZUKA
478090
33.65
130.70
3A
1780
70
IRAKO
476530
34.63
137.10
3A
1664
66
IROZAKI
476660
34.60
138.85
3A
2022
80
IRUMA AB
476430
35.83
139.42
4A
1432
56
ISHIGAKIJIMA
479180
24.33
124.17
1A
2064
81
ISHINOMAKI
475920
38.43
141.30
4A
1115
44
Japan (JPN)
ABASHIRI
474090
44.02
144.28
6A
819
32
ABURATSU
478350
31.58
131.40
3A
2593
102
Japan (JPN)
ABASHIRI
474090
44.02
144.28
6A
819
32
ABURATSU
478350
31.58
131.40
3A
2593
102

438 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 441

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
IWAKUNI
477640
34.15
132.23
3A
1693
67
IWAMIZAWA
474130
43.22
141.78
6A
1211
48
IWOJIMA
479810
24.78
141.32
1A
1205
47
IZUHARA
478000
34.20
129.30
3A
2207
87
KADENA (USAF\NAVY)
479310
26.35
127.77
2A
2078
82
KAGOSHIMA
478270
31.55
130.55
3A
2245
88
KANAZAWA
476050
36.58
136.63
4A
2465
97
KANOYA AB
478500
31.37
130.83
3A
2421
95
KANSAI INTERNATIONA
477740
34.43
135.25
3A
1412
56
KARUIZAWA
476220
36.35
138.55
5A
1275
50
KATSUURA
476740
35.15
140.32
3A
1873
74
KAWAGUCHIKO
476400
35.50
138.77
4A
1671
66
KITAMIESASHI
474020
44.93
142.58
6A
1170
46
KOBE
477700
34.70
135.22
3A
1376
54
KOCHI
478930
33.57
133.55
3A
2601
102
KOFU
476380
35.67
138.55
4A
1304
51
KOMATSU AB
477040
36.40
136.40
4A
2453
97
KOMATSUSHIMA AB
478840
34.00
134.63
3A
1870
74
KUMAGAYA
476260
36.15
139.38
3A
1311
52
KUMAMOTO
478190
32.82
130.70
3A
2280
90
KUMEJIMA
479290
26.33
126.80
2A
1851
73
KURE
477660
34.23
132.55
3A
1442
57
KUSHIRO
474180
42.98
144.38
6A
1074
42
KUTCHAN
474330
42.90
140.75
6A
1405
55
KYOTO
477590
35.02
135.73
3A
1662
65
MAEBASHI
476240
36.40
139.07
4A
1173
46
MAIZURU
477500
35.45
135.32
4A
1886
74
MAKURAZAKI
478310
31.27
130.30
3A
2254
89
MATSUE
477410
35.45
133.07
3A
1737
68
MATSUMOTO
476180
36.25
137.97
4A
1024
40
MATSUSHIMA AB
475910
38.40
141.22
4A
1157
46
MATSUYAMA
478870
33.85
132.78
3A
1443
57
MIHO AB
477430
35.48
133.23
3A
1894
75
MINAMIDAITOJIMA
479450
25.83
131.23
2A
1596
63
MINAMITORISHIMA
479910
24.28
153.98
1A
1014
40
MISAWA AB
475800
40.70
141.37
5A
1114
44
MISHIMA
476570
35.12
138.93
3A
1888
74
MITO
476290
36.38
140.47
4A
1324
52
MIYAKEJIMA
476770
34.12
139.52
3A
1880
74
MIYAKO
475850
39.65
141.97
5A
1306
51
MIYAKOJIMA
479270
24.80
125.28
1A
2012
79
MIYAKONOJO
478290
31.73
131.08
3A
2527
99
MIYAZAKI
478300
31.93
131.42
3A
2480
98
MOMBETSU
474350
44.35
143.35
6A
851
33
MORIOKA
475840
39.70
141.17
5A
1302
51
MURORAN
474230
42.32
140.98
5A
1263
50
MUROTOMISAKI
478990
33.25
134.18
3A
2455
97
MUTSU
475760
41.28
141.22
5A
1288
51
NAGANO
476100
36.67
138.20
4A
1176
46
NAGASAKI
478170
32.73
129.87
3A
1898
75
NAGOYA
476360
35.17
136.97
3A
1541
61
NAGOYA AIRPORT
476350
35.25
136.92
3A
1541
61
NAHA
479360
26.20
127.68
2A
2026
80
NAHA AIRPORT
479300
26.20
127.65
2A
2026
80
NARA
477800
34.70
135.83
3A
1504
59
NAZE
479090
28.38
129.50
2A
2856
112
NEMURO
474200
43.33
145.58
6A
1040
41
NEW TOKYO INTERNATI
476860
35.77
140.38
4A
1353
53
NIIGATA
476040
37.92
139.05
4A
1802
71
NIKKO
476900
36.73
139.50
6A
1763
69
NOBEOKA
478220
32.58
131.65
3A
2359
93
NYUTABARU AB
478540
32.08
131.45
3A
2472
97
OBIHIRO
474170
42.92
143.22
6A
1007
40
OFUNATO
475120
39.07
141.72
4A
1464
58
OITA
478150
33.23
131.62
3A
1670
66
OKAYAMA
477680
34.67
133.92
3A
1208
48
OKINOERABU
479420
27.43
128.70
2A
2084
82
OMAEZAKI
476550
34.60
138.22
3A
2069
81
OMINATO AB
475160
41.23
141.13
5A
1288
51
OMU
474050
44.58
142.97
6A
988
39
ONAHAMA
475980
36.95
140.90
4A
1380
54
OSAKA
477720
34.68
135.52
3A
1303
51
OSAKA INTERNATIONAL
477710
34.78
135.43
3A
1431
56
OSHIMA
476750
34.75
139.38
3A
1880
74
OTARU
474110
43.18
141.02
5A
1245
49
OWASE
476630
34.07
136.20
3A
3605
142
OZUKI AB
477870
34.05
131.05
3A
1776
70
RUMOI
474060
43.95
141.63
6A
1248
49
SAGA
478130
33.27
130.30
3A
1806
71
SAIGO
477400
36.20
133.33
4A
1599
63
SAKAI
477420
35.55
133.23
3A
1921
76
SAKATA
475870
38.92
139.85
4A
1883
74
SAPPORO
474120
43.07
141.33
5A
1120
44
SASEBO
478120
33.15
129.73
3A
2024
80
SENDAI
475900
38.27
140.90
4A
1242
49
SHIMIZU
478980
32.72
133.02
3A
2465
97
SHIMOFUSA AB
477270
35.80
140.02
3A
1296
51
SHIMONOSEKI
477620
33.95
130.93
3A
1772
70
SHINJO
475200
38.75
140.32
5A
1669
66
SHIONOMISAKI
477780
33.45
135.77
3A
2605
103
SHIRAKAWA
475970
37.13
140.22
4A
1367
54
SHIZUHAMA AB
476580
34.82
138.30
3A
2215
87
SHIZUOKA
476560
34.98
138.40
3A
2215
87
SUKUMO
478970
32.92
132.70
3A
2007
79
SUMOTO
477760
34.33
134.90
3A
1482
58
SUTTSU
474210
42.80
140.22
5A
1212
48
SUWA
476200
36.05
138.12
4A
1205
47
TADOTSU
478900
34.28
133.75
3A
1191
47
TAKADA
476120
37.10
138.25
4A
2619
103
TAKAMATSU
478910
34.32
134.05
3A
1087
43
TAKAYAMA
476170
36.15
137.25
4A
1653
65
TANEGASHIMA
478370
30.73
130.98
2A
2157
85
TATEYAMA
476720
34.98
139.87
3A
1797
71
TATEYAMA AB
476880
34.98
139.83
3A
1797
71
TOKUSHIMA
478950
34.07
134.57
3A
1622
64
TOKUSHIMA AB
478810
34.13
134.62
3A
1622
64

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 439

PDF Page 442

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
TOKYO
476620
35.68
139.77
3A
1441
57
TOKYO INTERNATIONAL
476710
35.55
139.78
3A
1441
57
TOMAKOMAI
474240
42.62
141.55
6A
1229
48
TOTTORI
477460
35.48
134.20
3A
1814
71
TOYAMA
476070
36.72
137.20
4A
2252
89
TOYOOKA
477470
35.53
134.82
4A
2019
80
TSU
476510
34.73
136.52
3A
1768
70
TSUIKI AB
478400
33.68
131.05
3A
1795
71
TSURUGA
476310
35.65
136.07
3A
2264
89
TSUYAMA
477560
35.07
134.02
4A
1578
62
UENO
476490
34.77
136.15
4A
1531
60
UNZENDAKE
478180
32.73
130.27
4A
2576
101
URAKAWA
474260
42.17
142.78
5A
1123
44
USHIBUKA
478380
31.72
130.03
3A
2244
88
UTSUNOMIYA
476150
36.55
139.87
4A
1543
61
UWAJIMA
478920
33.23
132.55
3A
1825
72
WAJIMA
476000
37.40
136.90
4A
2200
87
WAKAMATSU
475700
37.48
139.92
4A
1258
50
WAKAYAMA
477770
34.23
135.17
3A
1458
57
WAKKANAI
474010
45.42
141.68
6A
1116
44
YAKUSHIMA
478360
30.38
130.67
2A
2157
85
YAMAGATA
475880
38.25
140.35
4A
1172
46
YAMAGUCHI
477840
34.17
131.45
3A
1827
72
YOKKAICHI
476840
34.93
136.58
3A
1714
67
YOKOHAMA
476700
35.43
139.65
3A
1561
61
YOKOSUKA
476960
35.28
139.67
3A
1577
62
YOKOTA (JASDF/USAF)
476420
35.75
139.35
4A
1474
58
YONAGO
477440
35.43
133.33
3A
1860
73
YONAGUNIJIMA
479120
24.47
123.02
1A
1708
67
BLACOVESCHENKA
287660
54.37
66.97
7
349
14
BOLSHE NARYMSKOE
364280
49.20
84.52
7
382
15
CARDARA
384390
41.37
68.00
4B
250
10
CELKAR
356330
47.85
59.62
7
185
7
CIRIK-RABAT
380490
44.07
62.90
5B
105
4
DZHAMBEJTY
352170
50.25
52.57
6B
265
10
DZHUSALY
359530
45.50
64.08
5B
140
6
ESIL
350670
51.88
66.33
7
281
11
FORT SHEVCHENKO
380010
44.55
50.25
4B
143
6
IRGIZ
355420
48.62
61.27
7
174
7
IRTYSHSK
298070
53.35
75.45
7
293
12
ISILKUL
286880
54.90
71.25
7
343
14
KARAGANDA
353940
49.80
73.15
7
331
13
KARSAKPAJ
356630
47.83
66.75
7
190
7
KAZALINSK
358490
45.77
62.12
6B
129
5
KOKPEKTY
365350
48.75
82.37
7
315
12
KOKSHETAY
288790
53.28
69.38
7
310
12
KOZASAJ
355290
48.22
57.12
6B
201
8
KULSARY
357150
46.80
53.92
6B
179
7
KUSTANAI
289520
53.22
63.62
7
328
13
KYZYLORDA
380620
44.85
65.50
5B
147
6
KZYLZAR
355760
48.30
69.65
7
193
8
LENINOGORSK
362080
50.33
83.55
7
656
26
MOINTY
357910
47.20
73.35
7
186
7
MUGODZARSKAJA
355320
48.63
58.50
6A
306
12
NOVYJ USHTOGAN
346910
47.90
48.80
5B
181
7
PAVLODAR
360030
52.30
76.93
7
256
10
PETROPAVLOVSK
286790
54.83
69.15
7
368
15
POLTAVKA
287860
54.37
71.75
7
333
13
RUZAEVKA
289660
52.82
66.97
7
332
13
SAM
359250
45.40
56.12
5B
152
6
SEMIJARKA
361520
50.87
78.35
7
227
9
SEMIPALATINSK
361770
50.42
80.30
7
286
11
SHYMKENT
383280
42.32
69.70
4A
554
22
SUCINSK
289840
52.95
70.22
7
328
13
TAIPAK
354060
49.05
51.87
6B
200
8
TASTY
380810
44.80
69.12
5B
166
7
TEMIR
354260
49.15
57.12
6A
273
11
TORGAI
353580
49.63
63.50
7
209
8
TURKESTAN
381980
43.27
68.22
4B
203
8
UC-ARAL
367290
46.17
80.93
6B
285
11
UIL
354160
49.07
54.68
6B
238
9
UJUK
382030
43.78
70.93
5B
213
8
ULANBEL`
380910
44.80
71.07
5B
158
6
URALSK
351080
51.25
51.28
6A
324
13
URDZHAR
366390
47.12
81.62
6A
443
17
URICKY
288670
53.32
65.55
7
343
14
VOLODARSKOE
288770
53.32
68.10
7
392
15
ZAJSAN
366650
47.47
84.92
7
301
12
ZHALTYR
351730
51.62
69.80
7
326
13
ZHAMBYL
383410
42.85
71.38
5B
334
13
ZHARKENT
368590
44.17
80.07
5B
180
7
ZHARYK
354970
48.85
72.87
7
330
13
Jersey (JEY)
JERSEY AIRPORT
038950
49.22
–2.20
4A
850
33
Jersey (JEY)
JERSEY AIRPORT
038950
49.22
–2.20
4A
850
33
Jordan (JOR)
AMMAN AIRPORT
402700
31.98
35.98
3B
271
11
AQABA AIRPORT
403400
29.55
35.00
1B
23
1
H-4 IRWAISHED
402500
32.50
38.20
2B
82
3
IRBED
402550
32.55
35.85
3A
483
19
MAAN
403100
30.17
35.78
3B
39
2
MAFRAQ
402650
32.37
36.25
3B
155
6
QUEEN ALIA AIRPORT
402720
31.72
35.98
3B
237
9
Jordan (JOR)
AMMAN AIRPORT
402700
31.98
35.98
3B
271
11
AQABA AIRPORT
403400
29.55
35.00
1B
23
1
H-4 IRWAISHED
402500
32.50
38.20
2B
82
3
IRBED
402550
32.55
35.85
3A
483
19
MAAN
403100
30.17
35.78
3B
39
2
MAFRAQ
402650
32.37
36.25
3B
155
6
QUEEN ALIA AIRPORT
402720
31.72
35.98
3B
237
9
Kazakhstan (KAZ)
AKKOL
350850
52.00
70.95
7
351
14
AKKUDUK
382320
42.97
54.12
5B
131
5
AKTOBE
352290
50.28
57.15
7
305
12
ALMATY
368700
43.23
76.93
5A
635
25
AMANGELDY
353610
50.13
65.23
7
229
9
ARALSKOE MORE
357460
46.78
61.65
6B
144
6
ASTANA
351880
51.13
71.37
7
315
12
ATBASAR
350780
51.82
68.37
7
305
12
ATYRAU
357000
47.12
51.92
5B
156
6
BALHASH
357960
46.80
75.08
6B
144
6
BALKASINO
289780
52.53
68.75
7
359
14
BARSHATAS
364980
48.17
78.67
7
215
8
BERLIK
353760
49.88
69.52
7
240
9
Kazakhstan (KAZ)
AKKOL
350850
52.00
70.95
7
351
14
AKKUDUK
382320
42.97
54.12
5B
131
5
AKTOBE
352290
50.28
57.15
7
305
12
ALMATY
368700
43.23
76.93
5A
635
25
AMANGELDY
353610
50.13
65.23
7
229
9
ARALSKOE MORE
357460
46.78
61.65
6B
144
6
ASTANA
351880
51.13
71.37
7
315
12
ATBASAR
350780
51.82
68.37
7
305
12
ATYRAU
357000
47.12
51.92
5B
156
6
BALHASH
357960
46.80
75.08
6B
144
6
BALKASINO
289780
52.53
68.75
7
359
14
BARSHATAS
364980
48.17
78.67
7
215
8
BERLIK
353760
49.88
69.52
7
240
9

440 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 443

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
ZHEZKAZGAN
356710
47.80
67.72
7
190
7
ZLIKHA
359690
45.25
67.07
5B
141
6
ZMEINOGORSK
360380
51.15
82.20
7
664
26
ZVERINOGOLOVSKAJA
287560
54.47
64.87
7
343
14
CHEJU
471850
33.28
126.17
3A
1326
52
CHEONGJU
471310
36.63
127.45
4A
1208
48
CHEONGJU INTL AIRPO
471280
36.72
127.50
4A
1215
48
CHEORWON
470950
38.15
127.30
5A
1376
54
CHUNCHEON
471010
37.90
127.73
5A
1320
52
CHUPUNGNYEONG
471350
36.22
128.00
4A
1146
45
DAEGU
471430
35.88
128.62
4A
1028
40
DAEGU INTL AIRPORT
471420
35.90
128.67
4A
1028
40
DAEGWALLYEONG
471000
37.68
128.77
6A
1684
66
DAEJEON
471330
36.37
127.37
4A
1368
54
DONGHAE RADAR
471060
37.50
129.13
4A
1299
51
GANGNEUNG
471050
37.75
128.90
4A
1426
56
GANGNEUNG AB
471070
37.75
128.95
4A
1426
56
GIMHAE INTL AIRPORT
471530
35.18
128.93
4A
1498
59
GIMPO INTL AIRPORT
471100
37.57
126.78
5A
1386
55
GUNSAN
471400
36.00
126.77
4A
1188
47
GWANGJU
471560
35.17
126.90
4A
1337
53
GWANGJU AB
471580
35.12
126.82
4A
1337
53
INCHEON
471120
37.47
126.63
4A
1174
46
JEJU
471840
33.52
126.53
3A
1467
58
JEJU INTL AIRPORT
471820
33.52
126.50
3A
1467
58
JEONJU
471460
35.82
127.15
4A
1286
51
JINJU
471920
35.20
128.12
4A
1526
60
KUNSAN (US/KOR-AFB)
471410
35.90
126.62
4A
1205
47
MASAN
471550
35.18
128.57
3A
1532
60
MOESULPO AB
471870
33.20
126.27
3A
1486
59
MOKPO
471650
34.82
126.38
4A
1125
44
OSAN AB
471220
37.10
127.03
4A
1302
51
POHANG
471380
36.03
129.38
4A
1135
45
POHANG AB
471390
35.98
129.42
4A
1135
45
PYONGTAEK (A-511)
471270
36.97
127.03
4A
1250
49
SACHON (KOR-AFB)
471610
35.08
128.08
4A
1525
60
SEOGWIPO
471890
33.25
126.57
3A
1789
70
SEOSAN
471290
36.77
126.50
4A
1199
47
SEOUL
471080
37.57
126.97
4A
1400
55
SEOUL (KOR-AF HQ)
471170
37.50
126.93
4A
1400
55
SEOUL AB
471110
37.43
127.12
4A
1333
52
SOKCHO
470900
38.25
128.57
4A
1327
52
SUWON
471190
37.27
126.98
4A
1296
51
TONGYEONG
471620
34.85
128.43
3A
1423
56
ULJIN
471300
36.98
129.42
4A
1111
44
ULLEUNGDO
471150
37.48
130.90
4A
1334
53
ULSAN
471520
35.55
129.32
4A
1287
51
WANDO
471700
34.40
126.70
4A
1390
55
WONJU
471140
37.33
127.95
4A
1281
50
YECHEON AB
471340
36.63
128.35
4A
1141
45
YEONGWOL
471210
37.18
128.47
5A
1245
49
YEOSU
471680
34.73
127.75
4A
1415
56
Kenya (KEN)
EMBU
637200
–0.50
37.45
3C
1173
46
GARISSA
637230
–0.47
39.63
0B
366
14
KISUMU
637080
–0.10
34.75
2A
1345
53
KITALE
636610
1.02
35.00
3A
1237
49
LODWAR
636120
3.12
35.62
0B
167
7
MAKINDU
637660
–2.28
37.83
2B
581
23
MARSABIT
636410
2.30
37.90
2A
821
32
MERU
636950
0.08
37.65
3C
1371
54
MOMBASA
638200
–4.03
39.62
1A
1095
43
MOYALE
636190
3.53
39.03
2A
701
28
NAIROBI/KENYATTA AI
637400
–1.32
36.92
3C
733
29
NAKURU
637140
–0.27
36.10
3C
907
36
NYERI
637170
–0.50
36.97
3C
1696
67
VOI
637930
–3.40
38.57
1B
577
23
Kenya (KEN)
EMBU
637200
–0.50
37.45
3C
1173
46
GARISSA
637230
–0.47
39.63
0B
366
14
KISUMU
637080
–0.10
34.75
2A
1345
53
KITALE
636610
1.02
35.00
3A
1237
49
LODWAR
636120
3.12
35.62
0B
167
7
MAKINDU
637660
–2.28
37.83
2B
581
23
MARSABIT
636410
2.30
37.90
2A
821
32
MERU
636950
0.08
37.65
3C
1371
54
MOMBASA
638200
–4.03
39.62
1A
1095
43
MOYALE
636190
3.53
39.03
2A
701
28
NAIROBI/KENYATTA AI
637400
–1.32
36.92
3C
733
29
NAKURU
637140
–0.27
36.10
3C
907
36
NYERI
637170
–0.50
36.97
3C
1696
67
VOI
637930
–3.40
38.57
1B
577
23
Kiribati (KIR)
TARAWA
916100
1.35
172.92
0A
2092
82
Kiribati (KIR)
TARAWA
916100
1.35
172.92
0A
2092
82
Korea, Democratic People’s Republic of (PRK)
ANJU
470500
39.62
125.65
5A
1162
46
CHANGJIN
470310
40.37
127.25
7
857
34
CHANGJON
470610
38.73
128.18
4A
1607
63
CHONGJIN
470080
41.78
129.82
5A
642
25
CHUNGGANG
470140
41.78
126.88
6A
837
33
HAEJU
470690
38.03
125.70
4A
1153
45
HAMHEUNG
470410
39.93
127.55
5A
966
38
HUICHON
470390
40.17
126.25
5A
1287
51
HYESAN
470160
41.40
128.17
7
675
27
KAESONG
470700
37.97
126.57
5A
1393
55
KANGGYE
470200
40.97
126.60
6A
953
38
KIMCHAEK
470250
40.67
129.20
5A
735
29
KUSONG
470370
39.98
125.25
5A
1308
52
NAMPO
470600
38.72
125.38
5A
976
38
PUNGSAN
470220
40.82
128.15
7
697
27
PYONGGANG
470750
38.42
127.28
5A
1388
55
PYONGYANG
470580
39.03
125.78
5A
1039
41
RYONGYON
470680
38.15
124.88
5A
981
39
SAMJIYON
470050
41.82
128.30
7
908
36
SARIWON
470650
38.52
125.77
5A
1043
41
SENBONG
470030
42.32
130.40
6A
788
31
SINGYE
470670
38.50
126.53
5A
1358
53
SINPO
470460
40.03
128.18
5A
826
33
SINUIJU
470350
40.10
124.38
5A
969
38
SUPUNG
470280
40.45
124.93
5A
1101
43
WONSAN
470550
39.18
127.43
4A
1452
57
YANGDOK
470520
39.22
126.65
5A
1220
48
Korea, Democratic People’s Republic of (PRK)
ANJU
470500
39.62
125.65
5A
1162
46
CHANGJIN
470310
40.37
127.25
7
857
34
CHANGJON
470610
38.73
128.18
4A
1607
63
CHONGJIN
470080
41.78
129.82
5A
642
25
CHUNGGANG
470140
41.78
126.88
6A
837
33
HAEJU
470690
38.03
125.70
4A
1153
45
HAMHEUNG
470410
39.93
127.55
5A
966
38
HUICHON
470390
40.17
126.25
5A
1287
51
HYESAN
470160
41.40
128.17
7
675
27
KAESONG
470700
37.97
126.57
5A
1393
55
KANGGYE
470200
40.97
126.60
6A
953
38
KIMCHAEK
470250
40.67
129.20
5A
735
29
KUSONG
470370
39.98
125.25
5A
1308
52
NAMPO
470600
38.72
125.38
5A
976
38
PUNGSAN
470220
40.82
128.15
7
697
27
PYONGGANG
470750
38.42
127.28
5A
1388
55
PYONGYANG
470580
39.03
125.78
5A
1039
41
RYONGYON
470680
38.15
124.88
5A
981
39
SAMJIYON
470050
41.82
128.30
7
908
36
SARIWON
470650
38.52
125.77
5A
1043
41
SENBONG
470030
42.32
130.40
6A
788
31
SINGYE
470670
38.50
126.53
5A
1358
53
SINPO
470460
40.03
128.18
5A
826
33
SINUIJU
470350
40.10
124.38
5A
969
38
SUPUNG
470280
40.45
124.93
5A
1101
43
WONSAN
470550
39.18
127.43
4A
1452
57
YANGDOK
470520
39.22
126.65
5A
1220
48
Korea, Democratic People’s Republic of (PRK)
ANJU
470500
39.62
125.65
5A
1162
46
CHANGJIN
470310
40.37
127.25
7
857
34
CHANGJON
470610
38.73
128.18
4A
1607
63
CHONGJIN
470080
41.78
129.82
5A
642
25
CHUNGGANG
470140
41.78
126.88
6A
837
33
HAEJU
470690
38.03
125.70
4A
1153
45
HAMHEUNG
470410
39.93
127.55
5A
966
38
HUICHON
470390
40.17
126.25
5A
1287
51
HYESAN
470160
41.40
128.17
7
675
27
KAESONG
470700
37.97
126.57
5A
1393
55
KANGGYE
470200
40.97
126.60
6A
953
38
KIMCHAEK
470250
40.67
129.20
5A
735
29
KUSONG
470370
39.98
125.25
5A
1308
52
NAMPO
470600
38.72
125.38
5A
976
38
PUNGSAN
470220
40.82
128.15
7
697
27
PYONGGANG
470750
38.42
127.28
5A
1388
55
PYONGYANG
470580
39.03
125.78
5A
1039
41
RYONGYON
470680
38.15
124.88
5A
981
39
SAMJIYON
470050
41.82
128.30
7
908
36
SARIWON
470650
38.52
125.77
5A
1043
41
SENBONG
470030
42.32
130.40
6A
788
31
SINGYE
470670
38.50
126.53
5A
1358
53
SINPO
470460
40.03
128.18
5A
826
33
SINUIJU
470350
40.10
124.38
5A
969
38
SUPUNG
470280
40.45
124.93
5A
1101
43
WONSAN
470550
39.18
127.43
4A
1452
57
YANGDOK
470520
39.22
126.65
5A
1220
48
Kuwait (KWT)
KUWAIT INTERNATIONA
405820
29.22
47.97
1B
112
4
Korea, Republic of (KOR)
ANDONG
471360
36.57
128.72
4A
1024
40
BAENGNYEONGDO AB
471030
37.93
124.67
4A
934
37
BUSAN
471590
35.10
129.03
3A
1502
59
Korea, Republic of (KOR)
ANDONG
471360
36.57
128.72
4A
1024
40
BAENGNYEONGDO AB
471030
37.93
124.67
4A
934
37
BUSAN
471590
35.10
129.03
3A
1502
59
Korea, Republic of (KOR)
ANDONG
471360
36.57
128.72
4A
1024
40
BAENGNYEONGDO AB
471030
37.93
124.67
4A
934
37
BUSAN
471590
35.10
129.03
3A
1502
59
Kyrgyzstan (KGZ)
BISHKEK
383530
42.85
74.53
5A
439
17
DZHALAL-ABAD
386130
40.92
72.95
4A
472
19

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 441

PDF Page 444

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
NARYN
369740
41.43
76.00
7
297
12
OSH
386150
40.53
72.80
4B
333
13
TALAS
383450
42.52
72.22
5A
327
13
TIAN-SHAN
369820
41.88
78.23
8
291
11
TOKMAK
369110
42.83
75.28
4A
452
18
KUANTAN
486570
3.78
103.22
0A
2981
117
KUCHING
964130
1.48
110.33
0A
4215
166
LABUAN
964650
5.30
115.25
0A
3388
133
MALACCA
486650
2.27
102.25
0A
1940
76
MIRI
964490
4.33
113.98
0A
2847
112
PENANG/BAYAN LEPAS
486010
5.30
100.27
0A
2387
94
SANDAKAN
964910
5.90
118.07
0A
3224
127
SIBU
964210
2.33
111.83
0A
3389
133
SITIAWAN
486200
4.22
100.70
0A
1726
68
TAWAU
964810
4.27
117.88
0A
2218
87
Latvia (LTV)
AINAZI
262290
57.87
24.37
6A
633
25
DAUGAVPILS
265440
55.87
26.62
6A
631
25
GULBENE
263480
57.13
26.72
6A
665
26
KOLKA
263130
57.75
22.60
6A
613
24
LIEPAJA
264060
56.48
21.02
6A
673
26
MERSRAGS
263240
57.35
23.12
6A
641
25
REZEKNE
264460
56.53
27.27
6A
614
24
RIGA
264220
56.97
24.05
6A
654
26
RIGA
264225
56.92
23.97
6A
654
26
VALGA
262470
57.78
26.03
6A
680
27
Latvia (LTV)
AINAZI
262290
57.87
24.37
6A
633
25
DAUGAVPILS
265440
55.87
26.62
6A
631
25
GULBENE
263480
57.13
26.72
6A
665
26
KOLKA
263130
57.75
22.60
6A
613
24
LIEPAJA
264060
56.48
21.02
6A
673
26
MERSRAGS
263240
57.35
23.12
6A
641
25
REZEKNE
264460
56.53
27.27
6A
614
24
RIGA
264220
56.97
24.05
6A
654
26
RIGA
264225
56.92
23.97
6A
654
26
VALGA
262470
57.78
26.03
6A
680
27
Latvia (LTV)
AINAZI
262290
57.87
24.37
6A
633
25
DAUGAVPILS
265440
55.87
26.62
6A
631
25
GULBENE
263480
57.13
26.72
6A
665
26
KOLKA
263130
57.75
22.60
6A
613
24
LIEPAJA
264060
56.48
21.02
6A
673
26
MERSRAGS
263240
57.35
23.12
6A
641
25
REZEKNE
264460
56.53
27.27
6A
614
24
RIGA
264220
56.97
24.05
6A
654
26
RIGA
264225
56.92
23.97
6A
654
26
VALGA
262470
57.78
26.03
6A
680
27
Maldives (MDV)
MALE
435550
4.20
73.53
0A
1493
59
Latvia (LTV)
AINAZI
262290
57.87
24.37
6A
633
25
DAUGAVPILS
265440
55.87
26.62
6A
631
25
GULBENE
263480
57.13
26.72
6A
665
26
KOLKA
263130
57.75
22.60
6A
613
24
LIEPAJA
264060
56.48
21.02
6A
673
26
MERSRAGS
263240
57.35
23.12
6A
641
25
REZEKNE
264460
56.53
27.27
6A
614
24
RIGA
264220
56.97
24.05
6A
654
26
RIGA
264225
56.92
23.97
6A
654
26
VALGA
262470
57.78
26.03
6A
680
27
Mali (MLI)
BAMAKO/SENOU
612910
12.53
–7.95
0A
944
37
Latvia (LTV)
AINAZI
262290
57.87
24.37
6A
633
25
DAUGAVPILS
265440
55.87
26.62
6A
631
25
GULBENE
263480
57.13
26.72
6A
665
26
KOLKA
263130
57.75
22.60
6A
613
24
LIEPAJA
264060
56.48
21.02
6A
673
26
MERSRAGS
263240
57.35
23.12
6A
641
25
REZEKNE
264460
56.53
27.27
6A
614
24
RIGA
264220
56.97
24.05
6A
654
26
RIGA
264225
56.92
23.97
6A
654
26
VALGA
262470
57.78
26.03
6A
680
27
Malta (MLT)
LUQA
165970
35.85
14.48
3A
517
20
Lebanon (LBN)
BEYROUTH (AEROPORT)
401000
33.82
35.48
2A
784
31
Marshall Islands (MHL)
KWAJALEIN MISSLE RAN
913660
8.72
167.73
0A
2533
100
MAJURO WSO AP
913760
7.08
171.38
0A
3321
131
Libya (LBY)
AGEDABIA
620550
30.72
20.17
2B
152
6
BENINA
620530
32.10
20.27
2B
258
10
MISURATA
620160
32.42
15.05
2B
277
11
SIRTE
620190
31.20
16.58
2B
180
7
TRIPOLI INTERNATION
620100
32.70
13.08
2B
301
12
ZUARA
620070
32.88
12.08
2B
243
10
Libya (LBY)
AGEDABIA
620550
30.72
20.17
2B
152
6
BENINA
620530
32.10
20.27
2B
258
10
MISURATA
620160
32.42
15.05
2B
277
11
SIRTE
620190
31.20
16.58
2B
180
7
TRIPOLI INTERNATION
620100
32.70
13.08
2B
301
12
ZUARA
620070
32.88
12.08
2B
243
10
Libya (LBY)
AGEDABIA
620550
30.72
20.17
2B
152
6
BENINA
620530
32.10
20.27
2B
258
10
MISURATA
620160
32.42
15.05
2B
277
11
SIRTE
620190
31.20
16.58
2B
180
7
TRIPOLI INTERNATION
620100
32.70
13.08
2B
301
12
ZUARA
620070
32.88
12.08
2B
243
10
Martinique (MTQ)
LE LAMENTIN
789250
14.60
–61.00
0A
1110
44
Libya (LBY)
AGEDABIA
620550
30.72
20.17
2B
152
6
BENINA
620530
32.10
20.27
2B
258
10
MISURATA
620160
32.42
15.05
2B
277
11
SIRTE
620190
31.20
16.58
2B
180
7
TRIPOLI INTERNATION
620100
32.70
13.08
2B
301
12
ZUARA
620070
32.88
12.08
2B
243
10
Mauritania (MRT)
NOUADHIBOU
614150
20.93
–17.03
2B
17
1
NOUAKCHOTT
614420
18.10
–15.95
1B
87
3
Libya (LBY)
AGEDABIA
620550
30.72
20.17
2B
152
6
BENINA
620530
32.10
20.27
2B
258
10
MISURATA
620160
32.42
15.05
2B
277
11
SIRTE
620190
31.20
16.58
2B
180
7
TRIPOLI INTERNATION
620100
32.70
13.08
2B
301
12
ZUARA
620070
32.88
12.08
2B
243
10
Mauritius (MUS)
AGALEGA
619740
–10.43
56.75
0A
1153
45
PLAISANCE (MAURITIUS)
619900
–20.43
57.68
1A
1069
42
RODRIGUES
619880
–19.68
63.42
1A
1027
40
VACOAS (MAURITIUS)
619950
–20.30
57.50
2A
1069
42
Liechtenstein (LIE)
VADUZ (LIECHTENSTEIN)
069900
47.13
9.52
5A
1300
51
Liechtenstein (LIE)
VADUZ (LIECHTENSTEIN)
069900
47.13
9.52
5A
1300
51
Lithuania (LTU)
BIRZAI
265310
56.20
24.77
6A
608
24
KAUNAS
266290
54.88
23.83
6A
632
25
KLAIPEDA
265090
55.73
21.07
5A
720
28
LAUKUVA
265180
55.62
22.23
6A
801
32
SIAULIAI
265240
55.93
23.32
6A
595
23
UTENA
266330
55.53
25.60
6A
664
26
VILNIUS
267300
54.63
25.28
6A
672
26
Lithuania (LTU)
BIRZAI
265310
56.20
24.77
6A
608
24
KAUNAS
266290
54.88
23.83
6A
632
25
KLAIPEDA
265090
55.73
21.07
5A
720
28
LAUKUVA
265180
55.62
22.23
6A
801
32
SIAULIAI
265240
55.93
23.32
6A
595
23
UTENA
266330
55.53
25.60
6A
664
26
VILNIUS
267300
54.63
25.28
6A
672
26
Lithuania (LTU)
BIRZAI
265310
56.20
24.77
6A
608
24
KAUNAS
266290
54.88
23.83
6A
632
25
KLAIPEDA
265090
55.73
21.07
5A
720
28
LAUKUVA
265180
55.62
22.23
6A
801
32
SIAULIAI
265240
55.93
23.32
6A
595
23
UTENA
266330
55.53
25.60
6A
664
26
VILNIUS
267300
54.63
25.28
6A
672
26
Mayotte (MYT)
DZAOUDZI/PAMANZI
670050
–12.80
45.28
0A
971
38
Lithuania (LTU)
BIRZAI
265310
56.20
24.77
6A
608
24
KAUNAS
266290
54.88
23.83
6A
632
25
KLAIPEDA
265090
55.73
21.07
5A
720
28
LAUKUVA
265180
55.62
22.23
6A
801
32
SIAULIAI
265240
55.93
23.32
6A
595
23
UTENA
266330
55.53
25.60
6A
664
26
VILNIUS
267300
54.63
25.28
6A
672
26
Mexico (MEX)
AEROP. INTERNACIONA
766790
19.43
–99.13
3A
764
30
AEROP.INTERNACIONAL
766440
20.98
–89.65
0A
935
37
CANCUN INTL
765906
21.03
–86.87
0A
1283
51
DE GUANAJUATO INTL
765773
20.98
–101.48
2A
698
27
DON MIGUEL Y HIDALG
766133
20.52
–103.30
3A
944
37
GENERAL ABELARDO L
760013
32.53
–116.97
3B
338
13
GENERAL FRANCISCO J
765493
22.28
–97.87
1A
969
38
GENERAL HERIBERTO J
766913
19.13
–96.18
1A
1755
69
GENERAL JUAN N ALVA
768056
16.75
–99.75
0A
1428
56
GENERAL LEOBARDO C
765255
22.88
–102.68
3C
391
15
GENERAL MARIANO ESC
763943
25.77
–100.10
2B
637
25
GENERAL RAFAEL BUEL
764593
23.15
–106.27
1A
943
37
GUANAJUATO
765770
21.00
–101.28
3A
698
27
LICENCIADO ADOLFO L
766753
19.33
–99.57
3A
845
33
LICENCIADO BENITO J
766793
19.43
–99.07
3A
848
33
LICENCIADO GUSTAVO
766013
20.67
–105.25
1A
1092
43
MAZATLAN/G.BUELNA I
764594
23.15
–106.25
1A
968
38
MONTERREY (CITY)
763930
25.73
–100.30
2B
637
25
PUERTO VALLARTA
766014
20.68
–105.25
1A
1092
43
SAN LUIS POTOSI
765390
22.18
–100.98
3B
401
16
TAMPICO/GEN FJ MINA
765494
22.28
–97.85
1A
969
38
Luxembourg (LUX)
LUXEMBOURG/LUXEMBOU
065900
49.62
6.22
5A
835
33
Luxembourg (LUX)
LUXEMBOURG/LUXEMBOU
065900
49.62
6.22
5A
835
33
Macedonia (MKD)
BITOLA
135830
41.05
21.37
4A
623
25
KRIVA PALANKA
134930
42.20
22.33
5A
586
23
OHRID
135780
41.12
20.80
4A
749
29
SKOPJE- AIRPORT
135860
41.97
21.65
4A
513
20
Macedonia (MKD)
BITOLA
135830
41.05
21.37
4A
623
25
KRIVA PALANKA
134930
42.20
22.33
5A
586
23
OHRID
135780
41.12
20.80
4A
749
29
SKOPJE- AIRPORT
135860
41.97
21.65
4A
513
20
Macao (MAC)
TAIPA GRANDE
450110
22.15
113.60
2A
1958
77
Macao (MAC)
TAIPA GRANDE
450110
22.15
113.60
2A
1958
77
Madagascar (MDG)
ANTANANARIVO/IVATO
670830
–18.80
47.48
3A
1438
57
MAHAJANGA
670270
–15.67
46.35
0A
1429
56
TOAMASINA
670950
–18.12
49.40
1A
3287
129
Madagascar (MDG)
ANTANANARIVO/IVATO
670830
–18.80
47.48
3A
1438
57
MAHAJANGA
670270
–15.67
46.35
0A
1429
56
TOAMASINA
670950
–18.12
49.40
1A
3287
129
Malaysia (MYS)
BINTULU
964410
3.20
113.03
0A
3811
150
KOTA BHARU
486150
6.17
102.28
0A
2627
103
KOTA KINABALU
964710
5.93
116.05
0A
2603
102
KUALA LUMPUR SUBANG
486470
3.12
101.55
0A
2473
97
Malaysia (MYS)
BINTULU
964410
3.20
113.03
0A
3811
150
KOTA BHARU
486150
6.17
102.28
0A
2627
103
KOTA KINABALU
964710
5.93
116.05
0A
2603
102
KUALA LUMPUR SUBANG
486470
3.12
101.55
0A
2473
97

442 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 445

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
VERACRUZ/GEN JARA
766910
19.15
–96.18
1A
1755
69
ERRACHIDIA
602100
31.93
–4.40
2B
141
6
ESSAOUIRA
602200
31.52
–9.78
3C
303
12
FES-SAIS
601410
33.93
–4.98
3A
532
21
MARRAKECH
602300
31.62
–8.03
2B
245
10
MEKNES
601500
33.88
–5.53
3A
581
23
MIDELT
601950
32.68
–4.73
3B
212
8
NADOR-AROUI
603400
34.98
–3.02
3B
358
14
NOUASSEUR
601560
33.37
–7.58
3A
381
15
OUARZAZATE
602650
30.93
–6.90
2B
88
3
OUJDA
601150
34.78
–1.93
3B
335
13
RABAT-SALE
601350
34.05
–6.77
3A
563
22
SAFI
601850
32.28
–9.23
3A
388
15
TANGER (AERODROME)
601010
35.73
–5.90
3A
750
30
TAZA
601270
34.22
–4.00
3A
681
27
TETUAN/SANIA RAMEL
603180
35.58
–5.33
3A
684
27
Micronesia, Federated States of (FSM)
CHUUK WSO AP
913340
7.45
151.83
0A
3523
139
POHNPEI WSO
913480
6.97
158.22
0A
4670
184
YAP ISLAND WSO AP
914130
9.48
138.08
0A
3089
122
Micronesia, Federated States of (FSM)
CHUUK WSO AP
913340
7.45
151.83
0A
3523
139
POHNPEI WSO
913480
6.97
158.22
0A
4670
184
YAP ISLAND WSO AP
914130
9.48
138.08
0A
3089
122
Moldova (MDA)
KISINEV
338150
47.02
28.98
5A
543
21
Moldova (MDA)
KISINEV
338150
47.02
28.98
5A
543
21
Mongolia (MNG)
ALTAI
442770
46.40
96.25
8
170
7
ARVAIHEER
442880
46.27
102.78
7
231
9
BAITAG
442650
46.12
91.47
7
87
3
BARUUNHARAA
442410
48.92
106.07
7
290
11
BARUUNTURUUN
442130
49.65
94.40
8
215
8
BARUUN-URT
443050
46.68
113.28
7
183
7
BAYANBULAG
442750
46.83
98.08
8
134
5
BAYANDELGER
443520
45.73
112.37
7
195
8
BAYANHONGOR
442870
46.13
100.68
7
209
8
BAYAN-OVOO
443020
47.78
112.12
7
283
11
BULGAN
442390
48.80
103.55
7
313
12
CHOIBALSAN
442590
48.08
114.55
7
100
4
CHOIR
442980
46.45
108.22
7
170
7
DALANZADGAD
443730
43.58
104.42
7
121
5
DASHBALBAR
442560
49.55
114.40
7
318
13
ERDENEMANDAL
442370
48.53
101.38
7
281
11
GALUUT
442840
46.70
100.13
8
210
8
HATGAL
442070
50.43
100.15
8
277
11
HOVD
442180
48.02
91.57
7
114
4
HUJIRT
442850
46.90
102.77
7
295
12
HUTAG
442320
49.38
102.70
7
141
6
KHALKH-GOL
443130
47.62
118.62
7
299
12
MAANTI
442940
47.30
107.48
8
224
9
MANDALGOBI
443410
45.77
106.28
7
141
6
MATAD
443140
47.17
115.63
7
233
9
MUREN
442310
49.63
100.17
7
235
9
OMNO-GOBI
442150
49.02
91.72
7
125
5
RINCHINLHUMBE
442030
51.12
99.67
8
269
11
SAIKHAN-OVOO
443360
45.45
103.90
7
123
5
SAINSHAND
443540
44.90
110.12
7
111
4
TARIALAN
442300
49.57
102.00
7
297
12
TOSONTSENGEL
442250
48.73
98.20
8
206
8
TSETSERLEG
442820
47.45
101.47
7
330
13
TSOGT-OVOO
443470
44.42
105.32
7
95
4
ULAANBAATAR
442920
47.92
106.87
7
298
12
ULAANGOM
442120
49.80
92.08
8
132
5
ULGI
442140
48.93
89.93
7
107
4
ULIASTAI
442720
47.75
96.85
8
203
8
UNDERKHAAN
443040
47.32
110.63
7
249
10
ZAMYN-UUD
443580
43.73
111.90
7
119
5
Mongolia (MNG)
ALTAI
442770
46.40
96.25
8
170
7
ARVAIHEER
442880
46.27
102.78
7
231
9
BAITAG
442650
46.12
91.47
7
87
3
BARUUNHARAA
442410
48.92
106.07
7
290
11
BARUUNTURUUN
442130
49.65
94.40
8
215
8
BARUUN-URT
443050
46.68
113.28
7
183
7
BAYANBULAG
442750
46.83
98.08
8
134
5
BAYANDELGER
443520
45.73
112.37
7
195
8
BAYANHONGOR
442870
46.13
100.68
7
209
8
BAYAN-OVOO
443020
47.78
112.12
7
283
11
BULGAN
442390
48.80
103.55
7
313
12
CHOIBALSAN
442590
48.08
114.55
7
100
4
CHOIR
442980
46.45
108.22
7
170
7
DALANZADGAD
443730
43.58
104.42
7
121
5
DASHBALBAR
442560
49.55
114.40
7
318
13
ERDENEMANDAL
442370
48.53
101.38
7
281
11
GALUUT
442840
46.70
100.13
8
210
8
HATGAL
442070
50.43
100.15
8
277
11
HOVD
442180
48.02
91.57
7
114
4
HUJIRT
442850
46.90
102.77
7
295
12
HUTAG
442320
49.38
102.70
7
141
6
KHALKH-GOL
443130
47.62
118.62
7
299
12
MAANTI
442940
47.30
107.48
8
224
9
MANDALGOBI
443410
45.77
106.28
7
141
6
MATAD
443140
47.17
115.63
7
233
9
MUREN
442310
49.63
100.17
7
235
9
OMNO-GOBI
442150
49.02
91.72
7
125
5
RINCHINLHUMBE
442030
51.12
99.67
8
269
11
SAIKHAN-OVOO
443360
45.45
103.90
7
123
5
SAINSHAND
443540
44.90
110.12
7
111
4
TARIALAN
442300
49.57
102.00
7
297
12
TOSONTSENGEL
442250
48.73
98.20
8
206
8
TSETSERLEG
442820
47.45
101.47
7
330
13
TSOGT-OVOO
443470
44.42
105.32
7
95
4
ULAANBAATAR
442920
47.92
106.87
7
298
12
ULAANGOM
442120
49.80
92.08
8
132
5
ULGI
442140
48.93
89.93
7
107
4
ULIASTAI
442720
47.75
96.85
8
203
8
UNDERKHAAN
443040
47.32
110.63
7
249
10
ZAMYN-UUD
443580
43.73
111.90
7
119
5
Mongolia (MNG)
ALTAI
442770
46.40
96.25
8
170
7
ARVAIHEER
442880
46.27
102.78
7
231
9
BAITAG
442650
46.12
91.47
7
87
3
BARUUNHARAA
442410
48.92
106.07
7
290
11
BARUUNTURUUN
442130
49.65
94.40
8
215
8
BARUUN-URT
443050
46.68
113.28
7
183
7
BAYANBULAG
442750
46.83
98.08
8
134
5
BAYANDELGER
443520
45.73
112.37
7
195
8
BAYANHONGOR
442870
46.13
100.68
7
209
8
BAYAN-OVOO
443020
47.78
112.12
7
283
11
BULGAN
442390
48.80
103.55
7
313
12
CHOIBALSAN
442590
48.08
114.55
7
100
4
CHOIR
442980
46.45
108.22
7
170
7
DALANZADGAD
443730
43.58
104.42
7
121
5
DASHBALBAR
442560
49.55
114.40
7
318
13
ERDENEMANDAL
442370
48.53
101.38
7
281
11
GALUUT
442840
46.70
100.13
8
210
8
HATGAL
442070
50.43
100.15
8
277
11
HOVD
442180
48.02
91.57
7
114
4
HUJIRT
442850
46.90
102.77
7
295
12
HUTAG
442320
49.38
102.70
7
141
6
KHALKH-GOL
443130
47.62
118.62
7
299
12
MAANTI
442940
47.30
107.48
8
224
9
MANDALGOBI
443410
45.77
106.28
7
141
6
MATAD
443140
47.17
115.63
7
233
9
MUREN
442310
49.63
100.17
7
235
9
OMNO-GOBI
442150
49.02
91.72
7
125
5
RINCHINLHUMBE
442030
51.12
99.67
8
269
11
SAIKHAN-OVOO
443360
45.45
103.90
7
123
5
SAINSHAND
443540
44.90
110.12
7
111
4
TARIALAN
442300
49.57
102.00
7
297
12
TOSONTSENGEL
442250
48.73
98.20
8
206
8
TSETSERLEG
442820
47.45
101.47
7
330
13
TSOGT-OVOO
443470
44.42
105.32
7
95
4
ULAANBAATAR
442920
47.92
106.87
7
298
12
ULAANGOM
442120
49.80
92.08
8
132
5
ULGI
442140
48.93
89.93
7
107
4
ULIASTAI
442720
47.75
96.85
8
203
8
UNDERKHAAN
443040
47.32
110.63
7
249
10
ZAMYN-UUD
443580
43.73
111.90
7
119
5
Mozambique (MOZ)
MAPUTO/MAVALANE
673410
–25.92
32.57
2A
791
31
Mongolia (MNG)
ALTAI
442770
46.40
96.25
8
170
7
ARVAIHEER
442880
46.27
102.78
7
231
9
BAITAG
442650
46.12
91.47
7
87
3
BARUUNHARAA
442410
48.92
106.07
7
290
11
BARUUNTURUUN
442130
49.65
94.40
8
215
8
BARUUN-URT
443050
46.68
113.28
7
183
7
BAYANBULAG
442750
46.83
98.08
8
134
5
BAYANDELGER
443520
45.73
112.37
7
195
8
BAYANHONGOR
442870
46.13
100.68
7
209
8
BAYAN-OVOO
443020
47.78
112.12
7
283
11
BULGAN
442390
48.80
103.55
7
313
12
CHOIBALSAN
442590
48.08
114.55
7
100
4
CHOIR
442980
46.45
108.22
7
170
7
DALANZADGAD
443730
43.58
104.42
7
121
5
DASHBALBAR
442560
49.55
114.40
7
318
13
ERDENEMANDAL
442370
48.53
101.38
7
281
11
GALUUT
442840
46.70
100.13
8
210
8
HATGAL
442070
50.43
100.15
8
277
11
HOVD
442180
48.02
91.57
7
114
4
HUJIRT
442850
46.90
102.77
7
295
12
HUTAG
442320
49.38
102.70
7
141
6
KHALKH-GOL
443130
47.62
118.62
7
299
12
MAANTI
442940
47.30
107.48
8
224
9
MANDALGOBI
443410
45.77
106.28
7
141
6
MATAD
443140
47.17
115.63
7
233
9
MUREN
442310
49.63
100.17
7
235
9
OMNO-GOBI
442150
49.02
91.72
7
125
5
RINCHINLHUMBE
442030
51.12
99.67
8
269
11
SAIKHAN-OVOO
443360
45.45
103.90
7
123
5
SAINSHAND
443540
44.90
110.12
7
111
4
TARIALAN
442300
49.57
102.00
7
297
12
TOSONTSENGEL
442250
48.73
98.20
8
206
8
TSETSERLEG
442820
47.45
101.47
7
330
13
TSOGT-OVOO
443470
44.42
105.32
7
95
4
ULAANBAATAR
442920
47.92
106.87
7
298
12
ULAANGOM
442120
49.80
92.08
8
132
5
ULGI
442140
48.93
89.93
7
107
4
ULIASTAI
442720
47.75
96.85
8
203
8
UNDERKHAAN
443040
47.32
110.63
7
249
10
ZAMYN-UUD
443580
43.73
111.90
7
119
5
Namibia (NAM)
WALVIS BAY (PELICAN BAY)
681040
–22.88
14.43
3C
12
0
WINDHOEK
681100
–22.57
17.10
2B
354
14
Mongolia (MNG)
ALTAI
442770
46.40
96.25
8
170
7
ARVAIHEER
442880
46.27
102.78
7
231
9
BAITAG
442650
46.12
91.47
7
87
3
BARUUNHARAA
442410
48.92
106.07
7
290
11
BARUUNTURUUN
442130
49.65
94.40
8
215
8
BARUUN-URT
443050
46.68
113.28
7
183
7
BAYANBULAG
442750
46.83
98.08
8
134
5
BAYANDELGER
443520
45.73
112.37
7
195
8
BAYANHONGOR
442870
46.13
100.68
7
209
8
BAYAN-OVOO
443020
47.78
112.12
7
283
11
BULGAN
442390
48.80
103.55
7
313
12
CHOIBALSAN
442590
48.08
114.55
7
100
4
CHOIR
442980
46.45
108.22
7
170
7
DALANZADGAD
443730
43.58
104.42
7
121
5
DASHBALBAR
442560
49.55
114.40
7
318
13
ERDENEMANDAL
442370
48.53
101.38
7
281
11
GALUUT
442840
46.70
100.13
8
210
8
HATGAL
442070
50.43
100.15
8
277
11
HOVD
442180
48.02
91.57
7
114
4
HUJIRT
442850
46.90
102.77
7
295
12
HUTAG
442320
49.38
102.70
7
141
6
KHALKH-GOL
443130
47.62
118.62
7
299
12
MAANTI
442940
47.30
107.48
8
224
9
MANDALGOBI
443410
45.77
106.28
7
141
6
MATAD
443140
47.17
115.63
7
233
9
MUREN
442310
49.63
100.17
7
235
9
OMNO-GOBI
442150
49.02
91.72
7
125
5
RINCHINLHUMBE
442030
51.12
99.67
8
269
11
SAIKHAN-OVOO
443360
45.45
103.90
7
123
5
SAINSHAND
443540
44.90
110.12
7
111
4
TARIALAN
442300
49.57
102.00
7
297
12
TOSONTSENGEL
442250
48.73
98.20
8
206
8
TSETSERLEG
442820
47.45
101.47
7
330
13
TSOGT-OVOO
443470
44.42
105.32
7
95
4
ULAANBAATAR
442920
47.92
106.87
7
298
12
ULAANGOM
442120
49.80
92.08
8
132
5
ULGI
442140
48.93
89.93
7
107
4
ULIASTAI
442720
47.75
96.85
8
203
8
UNDERKHAAN
443040
47.32
110.63
7
249
10
ZAMYN-UUD
443580
43.73
111.90
7
119
5
Netherlands (NLD)
AMSTERDAM AP SCHIPH
062400
52.30
4.77
5A
829
33
DE BILT
062600
52.10
5.18
5A
818
32
DE KOOY
062350
52.92
4.78
5A
768
30
DEELEN
062750
52.07
5.88
5A
858
34
EINDHOVEN
063700
51.45
5.42
5A
796
31
F3-FB-1
062390
54.85
4.70
5A
956
38
GILZE RIJEN
063500
51.57
4.93
5A
806
32
GRONINGEN AP EELDE
062800
53.13
6.58
5A
791
31
HERWIJNEN AWS
063560
51.87
5.15
4A
801
32
HOEK VAN HOLLAND
063300
51.98
4.10
4A
818
32
HOOGEVEEN
062790
52.75
6.52
5A
807
32
HOUTRIB
062680
52.53
5.43
5A
810
32
HUPSEL AWS
062830
52.07
6.65
5A
795
31
IJMUIDEN
062250
52.47
4.57
4A
816
32
K13-A
062520
53.22
3.22
4A
865
34
LEEUWARDEN
062700
53.22
5.77
5A
808
32
LELYSTAD AWS
062690
52.45
5.53
5A
832
33
MAASTRICHT AP ZUID
063800
50.92
5.78
5A
773
30
MARKNESSE AWS
062730
52.70
5.88
5A
796
31
NIEUW BEERTA AWS
062860
53.20
7.15
5A
747
29
ROTTERDAM AP ZESTIE
063440
51.95
4.45
5A
829
33
SOESTERBERG
062650
52.13
5.28
5A
818
32
TERSCHELLING(LGT-H)
062500
53.37
5.22
5A
956
38
TWENTHE
062900
52.27
6.90
5A
786
31
VALKENBURG
062100
52.18
4.42
5A
838
33
VLIELAND
062420
53.25
4.92
4A
783
31
VLISSINGEN
063100
51.45
3.60
4A
743
29
VOLKEL
063750
51.65
5.70
5A
758
30
WILHELMINADORP AWS
063230
51.53
3.90
4A
778
31
WOENSDRECHT
063400
51.45
4.33
4A
796
31
Morocco (MAR)
AGADIR
602500
30.38
–9.57
3B
255
10
AGADIR AL MASSIRA
602520
30.32
–9.40
2B
234
9
AL HOCEIMA
601070
35.18
–3.85
3B
328
13
BENI-MELLAL
601910
32.37
–6.40
3A
419
16
CASABLANCA
601550
33.57
–7.67
3A
428
17
Morocco (MAR)
AGADIR
602500
30.38
–9.57
3B
255
10
AGADIR AL MASSIRA
602520
30.32
–9.40
2B
234
9
AL HOCEIMA
601070
35.18
–3.85
3B
328
13
BENI-MELLAL
601910
32.37
–6.40
3A
419
16
CASABLANCA
601550
33.57
–7.67
3A
428
17
Morocco (MAR)
AGADIR
602500
30.38
–9.57
3B
255
10
AGADIR AL MASSIRA
602520
30.32
–9.40
2B
234
9
AL HOCEIMA
601070
35.18
–3.85
3B
328
13
BENI-MELLAL
601910
32.37
–6.40
3A
419
16
CASABLANCA
601550
33.57
–7.67
3A
428
17
New Caledonia (NCL)
ILE SURPRISE
915700
–18.48
163.08
1A
1088
43
KOUMAC (NLLE-CALEDONIE)
915770
–20.57
164.28
2A
1036
41

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 443

PDF Page 446

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
LA ROCHE (ILE MARE)
915870
–21.48
168.03
2A
1332
52
LA TONTOUTA (NLLE-CALEDONIE)
915900
–22.02
166.22
2A
951
37
MATTHEW (ILOT)
915980
–22.33
171.33
2A
1245
49
MOUE (ILE DES PINS)
915960
–22.60
167.45
2A
1168
46
NOUMEA (NLLE-CALEDONIE)
915920
–22.27
166.45
2A
1047
41
OUANAHAM (ILE LIFOU)
915820
–20.77
167.23
2A
1694
67
OULOUP (ILE OUVEA)
915790
–20.65
166.58
1A
1321
52
POINDIMIE (NLLE-CAL)
915830
–20.93
165.32
1A
2565
101
GOURE
610450
13.98
10.30
0B
282
11
MAGARIA
610910
12.98
8.93
0B
545
21
MAINE-SOROA
610960
13.23
11.98
0B
350
14
MARADI
610800
13.47
7.08
0B
490
19
NGUIGMI
610490
14.25
13.12
0B
191
8
NIAMEY-AERO
610520
13.48
2.17
0B
539
21
TAHOUA
610430
14.90
5.25
0B
369
15
TILLABERY
610360
14.20
1.45
0B
399
16
ZINDER
610900
13.78
8.98
0B
411
16
New Zealand (NZL)
AUCKLAND AERO AWS
931100
–37.00
174.80
3A
1140
45
AUCKLAND AIRPORT
931190
–37.02
174.80
3A
1140
45
CAMPBELL ISLAND AWS
939470
–52.55
169.15
6A
1342
53
CAPE CAMPBELL AWS
935970
–41.73
174.20
4A
690
27
CAPE REINGA AWS
930040
–34.43
172.68
3A
975
38
CASTLEPOINT
934980
–40.90
176.23
3A
881
35
CHATHAM ISLANDS AWS
939870
–43.95
–176.57
4A
870
34
CHRISTCHURCH
937800
–43.48
172.55
4A
584
23
CHRISTCHURCH AERO A
937810
–43.48
172.52
4A
614
24
ENDERBY ISLAND AWS
939290
–50.48
166.30
5A
1029
41
FAREWELL SPIT AWS
935270
–40.55
173.00
3A
1665
66
GISBORNE AERODROME
932920
–38.65
177.98
3A
1032
41
HAAST AWS
937090
–43.87
169.00
4A
3012
119
HICKS BAY AWS
931960
–37.55
178.30
3A
1460
57
HOKITIKA AERODROME
936150
–42.72
170.98
4A
2795
110
INVERCARGILL AERODR
938440
–46.42
168.32
5A
1088
43
INVERCARGILL AIRPOR
938450
–46.42
168.33
5A
1088
43
KAIKOURA
936780
–42.42
173.70
4A
729
29
KAITAIA
930120
–35.10
173.27
3A
1338
53
MOKOHINAU AWS
930690
–35.90
175.10
3A
956
38
NAPIER AERODROME AW
933730
–39.45
176.85
3A
800
31
NELSON AERODROME AW
935460
–41.28
173.23
4A
1092
43
NEW PLYMOUTH AWS
933090
–39.02
174.18
3A
1439
57
PALMERSTON NORTH AW
934040
–40.32
175.60
4A
934
37
PARAPARAUMU AWS
934200
–40.90
174.98
3A
979
39
PURERUA
930230
–35.12
174.02
3A
1175
46
PUYSEGUR POINT AWS
938050
–46.17
166.63
4A
2428
96
QUEENSTOWN AERODROM
938310
–45.02
168.73
5A
988
39
RAOUL ISLAND (AUT)
939940
–29.25
–177.92
3A
1468
58
SECRETARY ISLAND AW
938000
–45.22
166.88
4A
3712
146
SOUTH WEST CAPE AWS
939090
–47.27
167.45
4A
1200
47
TAIAROA HEAD
938960
–45.77
170.73
4A
707
28
TAUPO AWS
932450
–38.73
176.07
4A
1009
40
TAURANGA AERO AWS
931860
–37.67
176.20
3A
1238
49
TIMARU AERODROME AW
937730
–44.30
171.23
4A
587
23
WAIOURU AWS
933340
–39.47
175.68
5A
1782
70
WELLINGTON AIRPORT
934360
–41.33
174.80
3A
1056
42
WESTPORT AERODROME
935150
–41.73
171.57
4A
1843
73
New Zealand (NZL)
AUCKLAND AERO AWS
931100
–37.00
174.80
3A
1140
45
AUCKLAND AIRPORT
931190
–37.02
174.80
3A
1140
45
CAMPBELL ISLAND AWS
939470
–52.55
169.15
6A
1342
53
CAPE CAMPBELL AWS
935970
–41.73
174.20
4A
690
27
CAPE REINGA AWS
930040
–34.43
172.68
3A
975
38
CASTLEPOINT
934980
–40.90
176.23
3A
881
35
CHATHAM ISLANDS AWS
939870
–43.95
–176.57
4A
870
34
CHRISTCHURCH
937800
–43.48
172.55
4A
584
23
CHRISTCHURCH AERO A
937810
–43.48
172.52
4A
614
24
ENDERBY ISLAND AWS
939290
–50.48
166.30
5A
1029
41
FAREWELL SPIT AWS
935270
–40.55
173.00
3A
1665
66
GISBORNE AERODROME
932920
–38.65
177.98
3A
1032
41
HAAST AWS
937090
–43.87
169.00
4A
3012
119
HICKS BAY AWS
931960
–37.55
178.30
3A
1460
57
HOKITIKA AERODROME
936150
–42.72
170.98
4A
2795
110
INVERCARGILL AERODR
938440
–46.42
168.32
5A
1088
43
INVERCARGILL AIRPOR
938450
–46.42
168.33
5A
1088
43
KAIKOURA
936780
–42.42
173.70
4A
729
29
KAITAIA
930120
–35.10
173.27
3A
1338
53
MOKOHINAU AWS
930690
–35.90
175.10
3A
956
38
NAPIER AERODROME AW
933730
–39.45
176.85
3A
800
31
NELSON AERODROME AW
935460
–41.28
173.23
4A
1092
43
NEW PLYMOUTH AWS
933090
–39.02
174.18
3A
1439
57
PALMERSTON NORTH AW
934040
–40.32
175.60
4A
934
37
PARAPARAUMU AWS
934200
–40.90
174.98
3A
979
39
PURERUA
930230
–35.12
174.02
3A
1175
46
PUYSEGUR POINT AWS
938050
–46.17
166.63
4A
2428
96
QUEENSTOWN AERODROM
938310
–45.02
168.73
5A
988
39
RAOUL ISLAND (AUT)
939940
–29.25
–177.92
3A
1468
58
SECRETARY ISLAND AW
938000
–45.22
166.88
4A
3712
146
SOUTH WEST CAPE AWS
939090
–47.27
167.45
4A
1200
47
TAIAROA HEAD
938960
–45.77
170.73
4A
707
28
TAUPO AWS
932450
–38.73
176.07
4A
1009
40
TAURANGA AERO AWS
931860
–37.67
176.20
3A
1238
49
TIMARU AERODROME AW
937730
–44.30
171.23
4A
587
23
WAIOURU AWS
933340
–39.47
175.68
5A
1782
70
WELLINGTON AIRPORT
934360
–41.33
174.80
3A
1056
42
WESTPORT AERODROME
935150
–41.73
171.57
4A
1843
73
New Zealand (NZL)
AUCKLAND AERO AWS
931100
–37.00
174.80
3A
1140
45
AUCKLAND AIRPORT
931190
–37.02
174.80
3A
1140
45
CAMPBELL ISLAND AWS
939470
–52.55
169.15
6A
1342
53
CAPE CAMPBELL AWS
935970
–41.73
174.20
4A
690
27
CAPE REINGA AWS
930040
–34.43
172.68
3A
975
38
CASTLEPOINT
934980
–40.90
176.23
3A
881
35
CHATHAM ISLANDS AWS
939870
–43.95
–176.57
4A
870
34
CHRISTCHURCH
937800
–43.48
172.55
4A
584
23
CHRISTCHURCH AERO A
937810
–43.48
172.52
4A
614
24
ENDERBY ISLAND AWS
939290
–50.48
166.30
5A
1029
41
FAREWELL SPIT AWS
935270
–40.55
173.00
3A
1665
66
GISBORNE AERODROME
932920
–38.65
177.98
3A
1032
41
HAAST AWS
937090
–43.87
169.00
4A
3012
119
HICKS BAY AWS
931960
–37.55
178.30
3A
1460
57
HOKITIKA AERODROME
936150
–42.72
170.98
4A
2795
110
INVERCARGILL AERODR
938440
–46.42
168.32
5A
1088
43
INVERCARGILL AIRPOR
938450
–46.42
168.33
5A
1088
43
KAIKOURA
936780
–42.42
173.70
4A
729
29
KAITAIA
930120
–35.10
173.27
3A
1338
53
MOKOHINAU AWS
930690
–35.90
175.10
3A
956
38
NAPIER AERODROME AW
933730
–39.45
176.85
3A
800
31
NELSON AERODROME AW
935460
–41.28
173.23
4A
1092
43
NEW PLYMOUTH AWS
933090
–39.02
174.18
3A
1439
57
PALMERSTON NORTH AW
934040
–40.32
175.60
4A
934
37
PARAPARAUMU AWS
934200
–40.90
174.98
3A
979
39
PURERUA
930230
–35.12
174.02
3A
1175
46
PUYSEGUR POINT AWS
938050
–46.17
166.63
4A
2428
96
QUEENSTOWN AERODROM
938310
–45.02
168.73
5A
988
39
RAOUL ISLAND (AUT)
939940
–29.25
–177.92
3A
1468
58
SECRETARY ISLAND AW
938000
–45.22
166.88
4A
3712
146
SOUTH WEST CAPE AWS
939090
–47.27
167.45
4A
1200
47
TAIAROA HEAD
938960
–45.77
170.73
4A
707
28
TAUPO AWS
932450
–38.73
176.07
4A
1009
40
TAURANGA AERO AWS
931860
–37.67
176.20
3A
1238
49
TIMARU AERODROME AW
937730
–44.30
171.23
4A
587
23
WAIOURU AWS
933340
–39.47
175.68
5A
1782
70
WELLINGTON AIRPORT
934360
–41.33
174.80
3A
1056
42
WESTPORT AERODROME
935150
–41.73
171.57
4A
1843
73
Niue (NIU)
ALOFI
918220
–19.07
–169.92
1A
2083
82
New Zealand (NZL)
AUCKLAND AERO AWS
931100
–37.00
174.80
3A
1140
45
AUCKLAND AIRPORT
931190
–37.02
174.80
3A
1140
45
CAMPBELL ISLAND AWS
939470
–52.55
169.15
6A
1342
53
CAPE CAMPBELL AWS
935970
–41.73
174.20
4A
690
27
CAPE REINGA AWS
930040
–34.43
172.68
3A
975
38
CASTLEPOINT
934980
–40.90
176.23
3A
881
35
CHATHAM ISLANDS AWS
939870
–43.95
–176.57
4A
870
34
CHRISTCHURCH
937800
–43.48
172.55
4A
584
23
CHRISTCHURCH AERO A
937810
–43.48
172.52
4A
614
24
ENDERBY ISLAND AWS
939290
–50.48
166.30
5A
1029
41
FAREWELL SPIT AWS
935270
–40.55
173.00
3A
1665
66
GISBORNE AERODROME
932920
–38.65
177.98
3A
1032
41
HAAST AWS
937090
–43.87
169.00
4A
3012
119
HICKS BAY AWS
931960
–37.55
178.30
3A
1460
57
HOKITIKA AERODROME
936150
–42.72
170.98
4A
2795
110
INVERCARGILL AERODR
938440
–46.42
168.32
5A
1088
43
INVERCARGILL AIRPOR
938450
–46.42
168.33
5A
1088
43
KAIKOURA
936780
–42.42
173.70
4A
729
29
KAITAIA
930120
–35.10
173.27
3A
1338
53
MOKOHINAU AWS
930690
–35.90
175.10
3A
956
38
NAPIER AERODROME AW
933730
–39.45
176.85
3A
800
31
NELSON AERODROME AW
935460
–41.28
173.23
4A
1092
43
NEW PLYMOUTH AWS
933090
–39.02
174.18
3A
1439
57
PALMERSTON NORTH AW
934040
–40.32
175.60
4A
934
37
PARAPARAUMU AWS
934200
–40.90
174.98
3A
979
39
PURERUA
930230
–35.12
174.02
3A
1175
46
PUYSEGUR POINT AWS
938050
–46.17
166.63
4A
2428
96
QUEENSTOWN AERODROM
938310
–45.02
168.73
5A
988
39
RAOUL ISLAND (AUT)
939940
–29.25
–177.92
3A
1468
58
SECRETARY ISLAND AW
938000
–45.22
166.88
4A
3712
146
SOUTH WEST CAPE AWS
939090
–47.27
167.45
4A
1200
47
TAIAROA HEAD
938960
–45.77
170.73
4A
707
28
TAUPO AWS
932450
–38.73
176.07
4A
1009
40
TAURANGA AERO AWS
931860
–37.67
176.20
3A
1238
49
TIMARU AERODROME AW
937730
–44.30
171.23
4A
587
23
WAIOURU AWS
933340
–39.47
175.68
5A
1782
70
WELLINGTON AIRPORT
934360
–41.33
174.80
3A
1056
42
WESTPORT AERODROME
935150
–41.73
171.57
4A
1843
73
Norfolk Island (NFK)
NORFOLK ISLAND AERO
949960
–29.03
167.93
3A
1267
50
New Zealand (NZL)
AUCKLAND AERO AWS
931100
–37.00
174.80
3A
1140
45
AUCKLAND AIRPORT
931190
–37.02
174.80
3A
1140
45
CAMPBELL ISLAND AWS
939470
–52.55
169.15
6A
1342
53
CAPE CAMPBELL AWS
935970
–41.73
174.20
4A
690
27
CAPE REINGA AWS
930040
–34.43
172.68
3A
975
38
CASTLEPOINT
934980
–40.90
176.23
3A
881
35
CHATHAM ISLANDS AWS
939870
–43.95
–176.57
4A
870
34
CHRISTCHURCH
937800
–43.48
172.55
4A
584
23
CHRISTCHURCH AERO A
937810
–43.48
172.52
4A
614
24
ENDERBY ISLAND AWS
939290
–50.48
166.30
5A
1029
41
FAREWELL SPIT AWS
935270
–40.55
173.00
3A
1665
66
GISBORNE AERODROME
932920
–38.65
177.98
3A
1032
41
HAAST AWS
937090
–43.87
169.00
4A
3012
119
HICKS BAY AWS
931960
–37.55
178.30
3A
1460
57
HOKITIKA AERODROME
936150
–42.72
170.98
4A
2795
110
INVERCARGILL AERODR
938440
–46.42
168.32
5A
1088
43
INVERCARGILL AIRPOR
938450
–46.42
168.33
5A
1088
43
KAIKOURA
936780
–42.42
173.70
4A
729
29
KAITAIA
930120
–35.10
173.27
3A
1338
53
MOKOHINAU AWS
930690
–35.90
175.10
3A
956
38
NAPIER AERODROME AW
933730
–39.45
176.85
3A
800
31
NELSON AERODROME AW
935460
–41.28
173.23
4A
1092
43
NEW PLYMOUTH AWS
933090
–39.02
174.18
3A
1439
57
PALMERSTON NORTH AW
934040
–40.32
175.60
4A
934
37
PARAPARAUMU AWS
934200
–40.90
174.98
3A
979
39
PURERUA
930230
–35.12
174.02
3A
1175
46
PUYSEGUR POINT AWS
938050
–46.17
166.63
4A
2428
96
QUEENSTOWN AERODROM
938310
–45.02
168.73
5A
988
39
RAOUL ISLAND (AUT)
939940
–29.25
–177.92
3A
1468
58
SECRETARY ISLAND AW
938000
–45.22
166.88
4A
3712
146
SOUTH WEST CAPE AWS
939090
–47.27
167.45
4A
1200
47
TAIAROA HEAD
938960
–45.77
170.73
4A
707
28
TAUPO AWS
932450
–38.73
176.07
4A
1009
40
TAURANGA AERO AWS
931860
–37.67
176.20
3A
1238
49
TIMARU AERODROME AW
937730
–44.30
171.23
4A
587
23
WAIOURU AWS
933340
–39.47
175.68
5A
1782
70
WELLINGTON AIRPORT
934360
–41.33
174.80
3A
1056
42
WESTPORT AERODROME
935150
–41.73
171.57
4A
1843
73
North Mariana Islands (MNP)
SAIPAN
912320
15.12
145.70
0A
1310
52
New Zealand (NZL)
AUCKLAND AERO AWS
931100
–37.00
174.80
3A
1140
45
AUCKLAND AIRPORT
931190
–37.02
174.80
3A
1140
45
CAMPBELL ISLAND AWS
939470
–52.55
169.15
6A
1342
53
CAPE CAMPBELL AWS
935970
–41.73
174.20
4A
690
27
CAPE REINGA AWS
930040
–34.43
172.68
3A
975
38
CASTLEPOINT
934980
–40.90
176.23
3A
881
35
CHATHAM ISLANDS AWS
939870
–43.95
–176.57
4A
870
34
CHRISTCHURCH
937800
–43.48
172.55
4A
584
23
CHRISTCHURCH AERO A
937810
–43.48
172.52
4A
614
24
ENDERBY ISLAND AWS
939290
–50.48
166.30
5A
1029
41
FAREWELL SPIT AWS
935270
–40.55
173.00
3A
1665
66
GISBORNE AERODROME
932920
–38.65
177.98
3A
1032
41
HAAST AWS
937090
–43.87
169.00
4A
3012
119
HICKS BAY AWS
931960
–37.55
178.30
3A
1460
57
HOKITIKA AERODROME
936150
–42.72
170.98
4A
2795
110
INVERCARGILL AERODR
938440
–46.42
168.32
5A
1088
43
INVERCARGILL AIRPOR
938450
–46.42
168.33
5A
1088
43
KAIKOURA
936780
–42.42
173.70
4A
729
29
KAITAIA
930120
–35.10
173.27
3A
1338
53
MOKOHINAU AWS
930690
–35.90
175.10
3A
956
38
NAPIER AERODROME AW
933730
–39.45
176.85
3A
800
31
NELSON AERODROME AW
935460
–41.28
173.23
4A
1092
43
NEW PLYMOUTH AWS
933090
–39.02
174.18
3A
1439
57
PALMERSTON NORTH AW
934040
–40.32
175.60
4A
934
37
PARAPARAUMU AWS
934200
–40.90
174.98
3A
979
39
PURERUA
930230
–35.12
174.02
3A
1175
46
PUYSEGUR POINT AWS
938050
–46.17
166.63
4A
2428
96
QUEENSTOWN AERODROM
938310
–45.02
168.73
5A
988
39
RAOUL ISLAND (AUT)
939940
–29.25
–177.92
3A
1468
58
SECRETARY ISLAND AW
938000
–45.22
166.88
4A
3712
146
SOUTH WEST CAPE AWS
939090
–47.27
167.45
4A
1200
47
TAIAROA HEAD
938960
–45.77
170.73
4A
707
28
TAUPO AWS
932450
–38.73
176.07
4A
1009
40
TAURANGA AERO AWS
931860
–37.67
176.20
3A
1238
49
TIMARU AERODROME AW
937730
–44.30
171.23
4A
587
23
WAIOURU AWS
933340
–39.47
175.68
5A
1782
70
WELLINGTON AIRPORT
934360
–41.33
174.80
3A
1056
42
WESTPORT AERODROME
935150
–41.73
171.57
4A
1843
73
Norway (NOR)
ALTA LUFTHAVN
010490
69.98
23.37
7
419
16
ANDOYA
010100
69.30
16.13
7
1117
44
BANAK
010590
70.07
24.98
7
431
17
BARDUFOSS
010230
69.07
18.53
7
848
33
BERGEN/FLESLAND
013110
60.28
5.23
6A
2026
80
BERGEN/FLORIDA
013170
60.38
5.33
5A
2199
87
BODO VI
011520
67.27
14.37
6A
1050
41
EKOFISK OIL PLTFRM
014033
56.55
3.25
5C
1102
43
FAGERNES
013670
60.98
9.23
7
586
23
FERDER FYR
014820
59.03
10.53
5A
897
35
FOKSTUA II
012380
62.12
9.28
7
457
18
FRUHOLMEN FYR
010550
71.10
24.00
7
613
24
GEILO-GEILOSTOLEN
013640
60.52
8.22
7
754
30
GULLFAX (PLATFORM)
013755
61.03
2.03
5A
1595
63
HAMMERFEST
010520
70.67
23.67
7
772
30
JAN MAYEN
010010
70.93
–8.67
7
677
27
KAUTOKEINO
010470
69.00
23.03
8
409
16
KIRKENES
010890
69.73
29.90
7
458
18
KONGSBERG IV
014770
59.67
9.65
6A
973
38
KRISTIANSAND/KJEVIK
014520
58.20
8.08
6A
1312
52
LISTA FYR
014270
58.12
6.57
5A
1834
72
LYNGOR FYR
014670
58.63
9.15
5A
1140
45
MYKEN
011150
66.77
12.48
6A
1310
52
OKSOY FYR
014480
58.07
8.05
5A
1312
52
ORLAND III
012410
63.70
9.60
6A
1021
40
OSLO/FORNEBU
014880
59.90
10.62
6A
772
30
OSLO/GARDERMOEN
013840
60.20
11.08
6A
865
34
OSLO-BLINDERN
014920
59.95
10.72
6A
772
30
RENA-HAUGEDALEN
013890
61.17
11.45
7
740
29
RYGGE
014940
59.38
10.78
6A
866
34
SKLINNA FYR
011020
65.20
11.00
6A
1307
51
SKROVA FYR
011600
68.15
14.65
6A
2304
91
SLATTEROY FYR
014060
59.92
5.07
5A
1750
69
SLETTNES FYR
010780
71.10
28.22
7
605
24
SORTLAND
011670
68.70
15.42
7
1471
58
STAVANGER/SOLA
014150
58.88
5.63
5A
1187
47
SULA
012280
63.85
8.47
6A
1138
45
Nicaragua (NIC)
MANAGUA A.C.SANDINO
787410
12.15
–86.17
0A
1107
44
Nicaragua (NIC)
MANAGUA A.C.SANDINO
787410
12.15
–86.17
0A
1107
44
Niger (NER)
AGADEZ
610240
16.97
7.97
0B
117
5
BIRNI-NKONNI
610750
13.80
5.25
0B
482
19
GAYA
610990
11.88
3.45
0B
791
31
Niger (NER)
AGADEZ
610240
16.97
7.97
0B
117
5
BIRNI-NKONNI
610750
13.80
5.25
0B
482
19
GAYA
610990
11.88
3.45
0B
791
31

444 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 447

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
SVINOY FYR
012050
62.33
5.27
5A
1557
61
TAFJORD
012180
62.23
7.42
5A
1143
45
TORSVAG FYR
010330
70.25
19.50
6A
968
38
TROMSO/LANGNES
010250
69.68
18.92
7
973
38
TRONDHEIM/VERNES
012710
63.47
10.93
6A
971
38
TVEITSUND
014550
59.03
8.52
6A
1036
41
UTSIRA FYR
014030
59.30
4.88
5A
1584
62
VARDO
010980
70.37
31.10
7
571
22
DAET
984400
14.13
122.98
0A
3563
140
DAGUPAN
983250
16.05
120.33
0A
2429
96
DAVAO AIRPORT
987530
7.12
125.65
0A
1805
71
DUMAGUETE
986420
9.30
123.30
0A
1215
48
GEN. SANTOS
988510
6.12
125.18
0A
1044
41
IBA
983240
15.33
119.97
0A
3802
150
ILOILO
986370
10.70
122.57
0A
2024
80
INFANTA
984340
14.75
121.65
0A
3937
155
LAOAG
982230
18.18
120.53
0A
2226
88
LEGASPI
984440
13.13
123.73
0A
2618
103
LUMBIA AIRPORT
987470
8.43
124.28
0A
1888
74
MACTAN
986460
10.30
123.97
0A
1607
63
MALAYBALAY
987510
8.15
125.08
1A
2580
102
MANILA
984250
14.58
120.98
0A
2134
84
MASBATE
985430
12.37
123.62
0A
1793
71
MUNOZ
983290
15.72
120.90
0A
1942
76
NINOY AQUINO INTERN
984290
14.52
121.00
0A
2134
84
PUERTO PRINCESA
986180
9.75
118.73
0A
1541
61
ROXAS
985380
11.58
122.75
0A
1990
78
SAN JOSE
985310
12.35
121.03
0A
2352
93
SANGLEY POINT
984280
14.50
120.92
0A
1907
75
SCIENCE GARDEN
984300
14.63
121.02
0A
2134
84
SINAIT
982220
17.88
120.45
0A
2478
98
TACLOBAN
985500
11.25
125.00
0A
2241
88
TAGBILARAN
986440
9.60
123.85
0A
1411
56
TAYABAS
984270
14.03
121.58
1A
2439
96
ZAMBOANGA
988360
6.90
122.07
0A
1221
48
Oman (OMN)
BURAIMI
412440
24.23
55.78
0B
89
3
FAHUD
412620
22.33
56.48
0B
52
2
MASIRAH
412880
20.67
58.90
0B
33
1
SALALAH
413160
17.03
54.08
1B
74
3
SEEB INTL AIRPORT
412560
23.58
58.28
0B
87
3
SOHAR MAJIS
412460
24.47
56.63
0B
108
4
SUR
412680
22.53
59.47
0B
95
4
THUMRAIT
413140
17.67
54.02
0B
67
3
Oman (OMN)
BURAIMI
412440
24.23
55.78
0B
89
3
FAHUD
412620
22.33
56.48
0B
52
2
MASIRAH
412880
20.67
58.90
0B
33
1
SALALAH
413160
17.03
54.08
1B
74
3
SEEB INTL AIRPORT
412560
23.58
58.28
0B
87
3
SOHAR MAJIS
412460
24.47
56.63
0B
108
4
SUR
412680
22.53
59.47
0B
95
4
THUMRAIT
413140
17.67
54.02
0B
67
3
Pakistan (PAK)
ISLAMABAD AIRPORT
415710
33.62
73.10
2A
1054
41
KARACHI AIRPORT
417800
24.90
67.13
0B
213
8
LAHORE AIRPORT
416410
31.52
74.40
1B
550
22
Pakistan (PAK)
ISLAMABAD AIRPORT
415710
33.62
73.10
2A
1054
41
KARACHI AIRPORT
417800
24.90
67.13
0B
213
8
LAHORE AIRPORT
416410
31.52
74.40
1B
550
22
Palau (PLW)
KOROR WSO
914080
7.33
134.48
0A
3753
148
Palau (PLW)
KOROR WSO
914080
7.33
134.48
0A
3753
148
Palestinian Territory, Occupied (PSE)
JERUSALEM AIRPORT
402900
31.87
35.22
3A
590
23
Palestinian Territory, Occupied (PSE)
JERUSALEM AIRPORT
402900
31.87
35.22
3A
590
23
Panama (PAN)
MARCOS A GELABERT I
783842
8.97
–79.55
0A
1799
71
TOCUMEN
787920
9.05
–79.37
0A
2154
85
Panama (PAN)
MARCOS A GELABERT I
783842
8.97
–79.55
0A
1799
71
TOCUMEN
787920
9.05
–79.37
0A
2154
85
Panama (PAN)
MARCOS A GELABERT I
783842
8.97
–79.55
0A
1799
71
TOCUMEN
787920
9.05
–79.37
0A
2154
85
Poland (POL)
BIALYSTOK
122950
53.10
23.17
6A
594
23
BIELSKO-BIALA
126000
49.80
19.00
5A
892
35
CHOJNICE
122350
53.72
17.55
5A
563
22
CZESTOCHOWA
125500
50.82
19.10
5A
620
24
ELBLAG
121600
54.17
19.43
5A
681
27
GDANSK-REBIECHOWO
121500
54.38
18.47
6A
551
22
GDANSK-SWIBNO
121550
54.33
18.93
5A
562
22
GORZOW WLKP
123000
52.75
15.28
5A
547
22
HEL
121350
54.60
18.82
5A
556
22
JELENIA GORA
125000
50.90
15.80
5A
861
34
KALISZ
124350
51.78
18.08
5A
517
20
KASPROWY WIERCH
126500
49.23
19.98
7
1151
45
KATOWICE
125600
50.23
19.03
5A
750
30
KETRZYN
121850
54.07
21.37
6A
598
24
KIELCE
125700
50.82
20.70
6A
620
24
KLODZKO
125200
50.43
16.62
5A
775
31
KOLO
123450
52.20
18.67
5A
525
21
KOLOBRZEG
121000
54.18
15.58
5A
668
26
KOSZALIN
121050
54.20
16.15
5A
708
28
KOZIENICE
124880
51.57
21.55
5A
567
22
KRAKOW
125660
50.08
19.80
5A
696
27
LEBA
121200
54.75
17.53
5A
654
26
LEBORK
121250
54.55
17.75
5A
655
26
LEGNICA
124150
51.20
16.20
5A
629
25
LESKO
126900
49.47
22.35
5A
960
38
Paraguay (PRY)
ASUNCION/AEROPUERTO
862180
–25.25
–57.52
2A
1401
55
VILLARRICA
862330
–25.75
–56.43
2A
1598
63
Paraguay (PRY)
ASUNCION/AEROPUERTO
862180
–25.25
–57.52
2A
1401
55
VILLARRICA
862330
–25.75
–56.43
2A
1598
63
Peru (PER)
AREQUIPA
847520
–16.33
–71.57
3C
87
3
CHICLAYO
844520
–6.78
–79.82
2B
19
1
CUZCO
846860
–13.53
–71.93
4A
664
26
IQUITOS
843770
–3.78
–73.30
0A
2858
113
LIMA-CALLAO/AEROP.
846280
–12.00
–77.12
2B
17
1
PISCO
846910
–13.73
–76.22
2B
10
0
PIURA
844010
–5.20
–80.60
1B
43
2
PUCALLPA
845150
–8.37
–74.57
0A
1603
63
SAN JUAN
847210
–15.38
–75.17
2B
4
0
TACNA
847820
–18.05
–70.27
3B
18
1
TALARA
843900
–4.57
–81.23
2B
10
0
TRUJILLO
845010
–8.08
–79.10
2B
29
1
TUMBES
843700
–3.55
–80.40
1B
438
17
Peru (PER)
AREQUIPA
847520
–16.33
–71.57
3C
87
3
CHICLAYO
844520
–6.78
–79.82
2B
19
1
CUZCO
846860
–13.53
–71.93
4A
664
26
IQUITOS
843770
–3.78
–73.30
0A
2858
113
LIMA-CALLAO/AEROP.
846280
–12.00
–77.12
2B
17
1
PISCO
846910
–13.73
–76.22
2B
10
0
PIURA
844010
–5.20
–80.60
1B
43
2
PUCALLPA
845150
–8.37
–74.57
0A
1603
63
SAN JUAN
847210
–15.38
–75.17
2B
4
0
TACNA
847820
–18.05
–70.27
3B
18
1
TALARA
843900
–4.57
–81.23
2B
10
0
TRUJILLO
845010
–8.08
–79.10
2B
29
1
TUMBES
843700
–3.55
–80.40
1B
438
17
Philippines (PHL)
BAGUIO
983280
16.42
120.60
2A
3686
145
CAGAYAN DE ORO
987480
8.48
124.63
0A
1667
66
CALAPAN
984310
13.42
121.18
0A
1885
74
CATANDUANES RADAR
984470
13.98
124.32
1A
3343
132
CATBALOGAN
985480
11.78
124.88
0A
2555
101
CLARK AB
983270
15.17
120.57
0A
2059
81
CUBI POINT NF
984260
14.80
120.27
0A
3685
145
Philippines (PHL)
BAGUIO
983280
16.42
120.60
2A
3686
145
CAGAYAN DE ORO
987480
8.48
124.63
0A
1667
66
CALAPAN
984310
13.42
121.18
0A
1885
74
CATANDUANES RADAR
984470
13.98
124.32
1A
3343
132
CATBALOGAN
985480
11.78
124.88
0A
2555
101
CLARK AB
983270
15.17
120.57
0A
2059
81
CUBI POINT NF
984260
14.80
120.27
0A
3685
145

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 445

PDF Page 448

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
LESZNO
124180
51.83
16.53
5A
544
21
LODZ
124650
51.73
19.40
5A
565
22
LUBLIN RADAWIEC
124950
51.22
22.40
5A
580
23
MIKOLAJKI
122800
53.78
21.58
5A
596
23
MLAWA
122700
53.10
20.35
5A
567
22
NOWY SACZ
126600
49.62
20.70
5A
775
31
OLSZTYN
122720
53.77
20.42
6A
642
25
OPOLE
125300
50.80
17.97
5A
580
23
OSTROLEKA
122850
53.08
21.57
5A
569
22
PILA
122300
53.13
16.75
5A
564
22
PLOCK
123600
52.58
19.73
5A
534
21
POZNAN
123300
52.42
16.85
5A
521
21
PRZEMYSL
126950
49.80
22.77
5A
676
27
RACIBORZ
125400
50.05
18.20
5A
635
25
RESKO
122100
53.77
15.42
5A
666
26
RZESZOW-JASIONKA
125800
50.10
22.05
5A
655
26
SANDOMIERZ
125850
50.70
21.72
5A
581
23
SIEDLCE
123850
52.25
22.25
5A
541
21
SNIEZKA
125100
50.73
15.73
7
996
39
SULEJOW
124690
51.35
19.87
5A
564
22
SUWALKI
121950
54.13
22.95
6A
594
23
SWINOUJSCIE
122000
53.92
14.23
5A
567
22
SZCZECIN
122050
53.40
14.62
5A
535
21
SZCZECINEK
122150
53.72
16.68
5A
613
24
TARNOW
125750
50.03
20.98
5A
719
28
TERESPOL
123990
52.07
23.62
5A
601
24
TORUN
122500
53.05
18.58
5A
538
21
USTKA
121150
54.58
16.87
5A
698
27
WARSZAWA-OKECIE
123750
52.17
20.97
5A
523
21
WIELUN
124550
51.22
18.57
5A
606
24
WLODAWA
124970
51.55
23.53
5A
552
22
WROCLAW II
124240
51.10
16.88
5A
577
23
ZAKOPANE
126250
49.30
19.97
6A
1120
44
ZAMOSC
125950
50.70
23.25
5A
603
24
ZIELONA GORA
124000
51.93
15.53
5A
594
23
SAGRES
085380
37.00
–8.95
3C
461
18
SANTA MARIA (ACORES)
085150
36.97
–25.17
3A
742
29
SINES/MONTES CHAOS
085410
37.95
–8.87
3C
551
22
VIANA DO CASTELO
085430
41.70
–8.80
3C
1422
56
VILA REAL
085660
41.32
–7.73
4C
1112
44
VILA REAL
085670
41.27
–7.72
4C
1112
44
VISEU
085600
40.72
–7.88
4C
1255
49
LESZNO
124180
51.83
16.53
5A
544
21
LODZ
124650
51.73
19.40
5A
565
22
LUBLIN RADAWIEC
124950
51.22
22.40
5A
580
23
MIKOLAJKI
122800
53.78
21.58
5A
596
23
MLAWA
122700
53.10
20.35
5A
567
22
NOWY SACZ
126600
49.62
20.70
5A
775
31
OLSZTYN
122720
53.77
20.42
6A
642
25
OPOLE
125300
50.80
17.97
5A
580
23
OSTROLEKA
122850
53.08
21.57
5A
569
22
PILA
122300
53.13
16.75
5A
564
22
PLOCK
123600
52.58
19.73
5A
534
21
POZNAN
123300
52.42
16.85
5A
521
21
PRZEMYSL
126950
49.80
22.77
5A
676
27
RACIBORZ
125400
50.05
18.20
5A
635
25
RESKO
122100
53.77
15.42
5A
666
26
RZESZOW-JASIONKA
125800
50.10
22.05
5A
655
26
SANDOMIERZ
125850
50.70
21.72
5A
581
23
SIEDLCE
123850
52.25
22.25
5A
541
21
SNIEZKA
125100
50.73
15.73
7
996
39
SULEJOW
124690
51.35
19.87
5A
564
22
SUWALKI
121950
54.13
22.95
6A
594
23
SWINOUJSCIE
122000
53.92
14.23
5A
567
22
SZCZECIN
122050
53.40
14.62
5A
535
21
SZCZECINEK
122150
53.72
16.68
5A
613
24
TARNOW
125750
50.03
20.98
5A
719
28
TERESPOL
123990
52.07
23.62
5A
601
24
TORUN
122500
53.05
18.58
5A
538
21
USTKA
121150
54.58
16.87
5A
698
27
WARSZAWA-OKECIE
123750
52.17
20.97
5A
523
21
WIELUN
124550
51.22
18.57
5A
606
24
WLODAWA
124970
51.55
23.53
5A
552
22
WROCLAW II
124240
51.10
16.88
5A
577
23
ZAKOPANE
126250
49.30
19.97
6A
1120
44
ZAMOSC
125950
50.70
23.25
5A
603
24
ZIELONA GORA
124000
51.93
15.53
5A
594
23
Qatar (QAT)
DOHA INTERNATIONAL
411700
25.25
51.57
0B
72
3
LESZNO
124180
51.83
16.53
5A
544
21
LODZ
124650
51.73
19.40
5A
565
22
LUBLIN RADAWIEC
124950
51.22
22.40
5A
580
23
MIKOLAJKI
122800
53.78
21.58
5A
596
23
MLAWA
122700
53.10
20.35
5A
567
22
NOWY SACZ
126600
49.62
20.70
5A
775
31
OLSZTYN
122720
53.77
20.42
6A
642
25
OPOLE
125300
50.80
17.97
5A
580
23
OSTROLEKA
122850
53.08
21.57
5A
569
22
PILA
122300
53.13
16.75
5A
564
22
PLOCK
123600
52.58
19.73
5A
534
21
POZNAN
123300
52.42
16.85
5A
521
21
PRZEMYSL
126950
49.80
22.77
5A
676
27
RACIBORZ
125400
50.05
18.20
5A
635
25
RESKO
122100
53.77
15.42
5A
666
26
RZESZOW-JASIONKA
125800
50.10
22.05
5A
655
26
SANDOMIERZ
125850
50.70
21.72
5A
581
23
SIEDLCE
123850
52.25
22.25
5A
541
21
SNIEZKA
125100
50.73
15.73
7
996
39
SULEJOW
124690
51.35
19.87
5A
564
22
SUWALKI
121950
54.13
22.95
6A
594
23
SWINOUJSCIE
122000
53.92
14.23
5A
567
22
SZCZECIN
122050
53.40
14.62
5A
535
21
SZCZECINEK
122150
53.72
16.68
5A
613
24
TARNOW
125750
50.03
20.98
5A
719
28
TERESPOL
123990
52.07
23.62
5A
601
24
TORUN
122500
53.05
18.58
5A
538
21
USTKA
121150
54.58
16.87
5A
698
27
WARSZAWA-OKECIE
123750
52.17
20.97
5A
523
21
WIELUN
124550
51.22
18.57
5A
606
24
WLODAWA
124970
51.55
23.53
5A
552
22
WROCLAW II
124240
51.10
16.88
5A
577
23
ZAKOPANE
126250
49.30
19.97
6A
1120
44
ZAMOSC
125950
50.70
23.25
5A
603
24
ZIELONA GORA
124000
51.93
15.53
5A
594
23
Reunion (REU)
SAINT-DENIS/GILLOT
619800
–20.88
55.52
1A
1523
60
LESZNO
124180
51.83
16.53
5A
544
21
LODZ
124650
51.73
19.40
5A
565
22
LUBLIN RADAWIEC
124950
51.22
22.40
5A
580
23
MIKOLAJKI
122800
53.78
21.58
5A
596
23
MLAWA
122700
53.10
20.35
5A
567
22
NOWY SACZ
126600
49.62
20.70
5A
775
31
OLSZTYN
122720
53.77
20.42
6A
642
25
OPOLE
125300
50.80
17.97
5A
580
23
OSTROLEKA
122850
53.08
21.57
5A
569
22
PILA
122300
53.13
16.75
5A
564
22
PLOCK
123600
52.58
19.73
5A
534
21
POZNAN
123300
52.42
16.85
5A
521
21
PRZEMYSL
126950
49.80
22.77
5A
676
27
RACIBORZ
125400
50.05
18.20
5A
635
25
RESKO
122100
53.77
15.42
5A
666
26
RZESZOW-JASIONKA
125800
50.10
22.05
5A
655
26
SANDOMIERZ
125850
50.70
21.72
5A
581
23
SIEDLCE
123850
52.25
22.25
5A
541
21
SNIEZKA
125100
50.73
15.73
7
996
39
SULEJOW
124690
51.35
19.87
5A
564
22
SUWALKI
121950
54.13
22.95
6A
594
23
SWINOUJSCIE
122000
53.92
14.23
5A
567
22
SZCZECIN
122050
53.40
14.62
5A
535
21
SZCZECINEK
122150
53.72
16.68
5A
613
24
TARNOW
125750
50.03
20.98
5A
719
28
TERESPOL
123990
52.07
23.62
5A
601
24
TORUN
122500
53.05
18.58
5A
538
21
USTKA
121150
54.58
16.87
5A
698
27
WARSZAWA-OKECIE
123750
52.17
20.97
5A
523
21
WIELUN
124550
51.22
18.57
5A
606
24
WLODAWA
124970
51.55
23.53
5A
552
22
WROCLAW II
124240
51.10
16.88
5A
577
23
ZAKOPANE
126250
49.30
19.97
6A
1120
44
ZAMOSC
125950
50.70
23.25
5A
603
24
ZIELONA GORA
124000
51.93
15.53
5A
594
23
Romania (ROU)
ARAD
152000
46.13
21.35
5A
592
23
BACAU
151500
46.53
26.92
5A
546
22
BAIA MARE
150140
47.67
23.50
5A
854
34
BARLAD
151970
46.23
27.65
5A
514
20
BISTRITA
150850
47.15
24.50
5A
706
28
BLAJ
152090
46.18
23.93
5A
552
22
BOTOSANI
150200
47.73
26.65
5A
571
22
BUCURESTI AFUMATI
154210
44.48
26.18
5A
612
24
BUCURESTI INMH-BANE
154200
44.48
26.12
5A
612
24
BUZAU
153500
45.13
26.85
4A
521
20
CALAFAT
154820
43.98
22.95
4A
544
21
CALARASI
154600
44.20
27.33
4A
492
19
CARANSEBES
152920
45.42
22.25
5A
906
36
CEAHLAU TOACA
151080
46.98
25.95
7
627
25
CLUJ-NAPOCA
151200
46.78
23.57
5A
584
23
CONSTANTA
154800
44.22
28.65
4A
422
17
CRAIOVA
154500
44.32
23.87
4A
584
23
DEVA
152300
45.87
22.90
5A
596
23
DROBETA TURNU SEVER
154100
44.63
22.63
4A
668
26
FAGARAS
152350
45.83
24.93
5A
713
28
FETESTI
154440
44.37
27.85
4A
454
18
GALATI
153100
45.48
28.03
5A
485
19
GIURGIU
154910
43.88
25.95
4A
583
23
GRIVITA
154050
44.75
27.30
5A
475
19
IASI
150900
47.17
27.63
5A
587
23
INTORSURA BUZAULUI
152610
45.68
26.02
6A
659
26
JURILOVCA
154090
44.77
28.88
4A
398
16
KOGALNICEANU
154810
44.33
28.43
4A
420
17
MANGALIA
154990
43.82
28.58
4A
405
16
MIERCUREA CIUC
151700
46.37
25.73
6A
566
22
ORADEA
150800
47.03
21.90
5A
596
23
ORAVITA
153380
45.03
21.68
4A
759
30
PETROSANI
152960
45.42
23.38
5A
812
32
PLOIESTI
153770
44.95
26.00
5A
620
24
PREDEAL
153020
45.50
25.58
6A
950
37
RARAU (MONASTERY)
150520
47.45
25.57
7
789
31
RIMNICU VALCEA
153460
45.10
24.37
4A
722
28
ROMAN
151110
46.97
26.92
5A
505
20
ROSIORI DE VEDE
154700
44.10
24.98
4A
534
21
SATU MARE
150100
47.72
22.88
5A
594
23
SIBIU
152600
45.80
24.15
5A
651
26
Portugal (PRT)
BEJA
085620
38.02
–7.87
3A
583
23
BRAGANCA
085750
41.80
–6.73
4C
735
29
CASTELO BRANCO
085700
39.83
–7.48
3A
779
31
COIMBRA
085490
40.20
–8.42
3A
998
39
EVORA
085570
38.57
–7.90
3A
638
25
EVORA/C. COORD
085580
38.53
–7.90
3A
638
25
FARO/AEROPORTO
085540
37.02
–7.97
3A
502
20
FLORES (ACORES)
085010
39.45
–31.13
3A
986
39
FUNCHAL
085220
32.63
–16.90
2A
607
24
FUNCHAL/S.CATARINA
085210
32.68
–16.77
3A
398
16
HORTA/CASTELO BRANC
085050
38.52
–28.72
3A
799
31
LAJES (ACORES)
085090
38.77
–27.10
3A
1154
45
LISBOA/PORTELA
085360
38.77
–9.13
3A
713
28
PONTA DELGADA/NORDE
085120
37.73
–25.70
3C
1025
40
PORTALEGRE
085710
39.28
–7.42
3A
881
35
PORTO SANTO
085240
33.07
–16.35
3B
376
15
PORTO/PEDRAS RUBRAS
085450
41.23
–8.68
3C
1252
49
Portugal (PRT)
BEJA
085620
38.02
–7.87
3A
583
23
BRAGANCA
085750
41.80
–6.73
4C
735
29
CASTELO BRANCO
085700
39.83
–7.48
3A
779
31
COIMBRA
085490
40.20
–8.42
3A
998
39
EVORA
085570
38.57
–7.90
3A
638
25
EVORA/C. COORD
085580
38.53
–7.90
3A
638
25
FARO/AEROPORTO
085540
37.02
–7.97
3A
502
20
FLORES (ACORES)
085010
39.45
–31.13
3A
986
39
FUNCHAL
085220
32.63
–16.90
2A
607
24
FUNCHAL/S.CATARINA
085210
32.68
–16.77
3A
398
16
HORTA/CASTELO BRANC
085050
38.52
–28.72
3A
799
31
LAJES (ACORES)
085090
38.77
–27.10
3A
1154
45
LISBOA/PORTELA
085360
38.77
–9.13
3A
713
28
PONTA DELGADA/NORDE
085120
37.73
–25.70
3C
1025
40
PORTALEGRE
085710
39.28
–7.42
3A
881
35
PORTO SANTO
085240
33.07
–16.35
3B
376
15
PORTO/PEDRAS RUBRAS
085450
41.23
–8.68
3C
1252
49

446 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 449

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
SIGHETUL MARMATIEI
150040
47.93
23.92
5A
820
32
SUCEAVA
150230
47.63
26.25
5A
595
23
SULINA
153600
45.17
29.73
4B
270
11
TARGOVISTE
153750
44.93
25.43
5A
663
26
TG. JIU
153400
45.03
23.27
5A
806
32
TG. MURES
151450
46.53
24.53
5A
601
24
TIMISOARA
152470
45.77
21.25
4A
611
24
TR. MAGURELE
154900
43.75
24.88
4A
547
22
TULCEA
153350
45.18
28.82
4A
434
17
VARFU OMU
152800
45.45
25.45
8
935
37
ZALAU
150630
47.18
23.08
5A
643
25
BALASOV
341520
51.55
43.15
6A
500
20
BARABINSK
296120
55.33
78.37
7
377
15
BARENCBURG
201070
78.07
14.25
8
468
18
BARNAUL
298380
53.43
83.52
7
441
17
BATAMAJ
246560
63.52
129.48
8
293
12
BEJA
299620
53.05
90.92
7
399
16
BELOGORSK
315130
50.92
128.47
7
554
22
BELYJ
265850
55.85
32.95
6A
709
28
BEREZOVO
236310
63.93
65.05
8
526
21
BERINGOVSKAJA
256770
63.05
179.32
8
574
23
BEZECK
272170
57.80
36.70
7
541
21
BIJSK ZONALNAJA
299390
52.68
84.95
7
534
21
BIKIN
318320
46.80
134.27
7
645
25
BIRILIUSSY
293670
57.13
90.70
7
501
20
BIROBIDZHAN
317130
48.73
132.95
7
666
26
BIRSK
286210
55.42
55.53
7
580
23
BLAGOVESCENSK
315100
50.25
127.57
7
559
22
BODAJBO
302530
57.85
114.23
8
447
18
BOGORODSKOE
314390
52.38
140.47
8
504
20
BOGOTOL
295530
56.23
89.58
7
499
20
BOGUCANY
292820
58.38
97.45
8
339
13
BOGUCAR
343360
49.93
40.57
6A
514
20
BOL`SIE-UKI
284910
56.93
72.67
7
447
18
BOLOGOE
262980
57.90
34.05
7
629
25
BOLSHAJA MURTA
294710
56.90
93.13
7
413
16
BOLSHERECHE
285930
56.10
74.63
7
364
14
BOLSOJ SANTAR
311740
54.83
137.53
8
524
21
BOMNAK
312530
54.72
128.93
8
574
23
BOR
238840
61.60
90.02
8
588
23
BORZJA
309650
50.40
116.52
8
296
12
BRATOLJUBOVKA
315210
50.78
129.33
8
564
22
BRATSK
303090
56.28
101.75
8
374
15
BRJANSK
268980
53.25
34.32
6A
649
26
BUDENNOVSK
370610
44.78
44.13
5A
406
16
BUGULMA
287110
54.58
52.80
7
523
21
BUHTA PROVIDENJA
255940
64.42
–173.23
8
666
26
BUJ
272420
58.48
41.53
7
633
25
BURUKAN
313480
53.05
136.03
8
642
25
BUZULUK
289090
52.82
52.22
7
470
19
CAJVO
320360
52.37
143.18
8
683
27
CAPE BOLVANSKIJ
209460
70.45
59.07
8
256
10
CAPE KAMENNYJ
231460
68.47
73.60
8
389
15
CAPE MENSHIKOVA
209430
70.72
57.62
8
588
23
CAPE STERLEGOVA
204760
75.42
88.90
8
296
12
CAPE VASILEVA
322170
50.02
155.40
7
1240
49
CEKUNDA
315320
50.87
132.25
8
672
26
CELINA
347470
46.55
41.05
5A
546
21
CEMAL
360580
51.43
86.00
7
513
20
CENTRALNYJ RUDNIK
296540
55.22
87.65
7
951
37
CEREPOVEC
271130
59.25
37.97
7
667
26
CERLAK
287990
54.17
74.80
7
348
14
CERNUSKA
284280
56.50
56.13
7
559
22
CHANY
296020
55.28
76.60
7
338
13
Russian Federation (RUS)
ABAKAN
298650
53.75
91.40
7
324
13
ACINSK
294670
56.28
90.50
7
422
17
ADLER
371710
43.43
39.90
4A
1559
61
AGATA
233830
66.88
93.47
8
464
18
AGINSKOE
296760
55.25
94.88
7
461
18
AGINSKOE
308590
51.10
114.52
8
371
15
AGZU
318250
47.60
138.40
7
663
26
AJAN
311680
56.45
138.15
8
887
35
AKJAR
350370
51.87
58.18
7
361
14
AKSA
309570
50.27
113.27
7
386
15
ALATYR`
276790
54.82
46.58
7
518
20
ALDAN
310040
58.62
125.37
8
676
27
ALEJSKAJA
299370
52.52
82.77
7
431
17
ALEKSANDROV-GAJ
343910
50.15
48.55
6A
316
12
ALEKSANDROVSKIJ ZAV
309710
50.92
117.93
8
399
16
ALEKSANDROVSKOE
239550
60.43
77.87
8
501
20
ALEKSANDROVSK-SAHAL
320610
50.90
142.17
7
622
24
AMDERMA
230220
69.75
61.70
8
380
15
AMGA
249620
60.90
131.98
8
256
10
ANADYR
255630
64.78
177.57
8
333
13
ANAPA
370010
44.88
37.28
4A
520
20
ANDREYA ISLAND
213010
76.80
110.83
8
210
8
ANTIPAJETA
230580
69.08
76.85
8
268
11
ANUCINO
319810
43.97
133.07
7
719
28
APUKA
259560
60.43
169.67
8
515
20
ARHANGELSK
225500
64.55
40.58
7
579
23
ARHARA
315940
49.42
130.08
7
640
25
ARKA
249880
60.08
142.33
8
446
18
ARMAVIR
370310
44.98
41.12
5A
572
23
ASTRAHAN
348800
46.28
48.05
5B
214
8
ASTRAHANKA
319210
44.72
132.07
7
582
23
ATKA
259020
60.85
151.77
8
328
13
B. PRONCHISHCHEVOY
214050
75.53
113.52
8
212
8
BABAEVO
270080
59.40
35.93
7
621
24
BABUSKIN
308220
51.72
105.85
7
523
21
BAEVO
298270
53.27
80.77
7
328
13
BAGDARIN
305540
54.47
113.58
8
378
15
BAJANDAJ
306270
53.10
105.53
8
375
15
BAKALY
286150
55.18
53.80
7
462
18
BAKCHAR
293280
57.08
81.92
7
464
18
BALAGANSK
306120
54.00
103.07
8
326
13
Russian Federation (RUS)
ABAKAN
298650
53.75
91.40
7
324
13
ACINSK
294670
56.28
90.50
7
422
17
ADLER
371710
43.43
39.90
4A
1559
61
AGATA
233830
66.88
93.47
8
464
18
AGINSKOE
296760
55.25
94.88
7
461
18
AGINSKOE
308590
51.10
114.52
8
371
15
AGZU
318250
47.60
138.40
7
663
26
AJAN
311680
56.45
138.15
8
887
35
AKJAR
350370
51.87
58.18
7
361
14
AKSA
309570
50.27
113.27
7
386
15
ALATYR`
276790
54.82
46.58
7
518
20
ALDAN
310040
58.62
125.37
8
676
27
ALEJSKAJA
299370
52.52
82.77
7
431
17
ALEKSANDROV-GAJ
343910
50.15
48.55
6A
316
12
ALEKSANDROVSKIJ ZAV
309710
50.92
117.93
8
399
16
ALEKSANDROVSKOE
239550
60.43
77.87
8
501
20
ALEKSANDROVSK-SAHAL
320610
50.90
142.17
7
622
24
AMDERMA
230220
69.75
61.70
8
380
15
AMGA
249620
60.90
131.98
8
256
10
ANADYR
255630
64.78
177.57
8
333
13
ANAPA
370010
44.88
37.28
4A
520
20
ANDREYA ISLAND
213010
76.80
110.83
8
210
8
ANTIPAJETA
230580
69.08
76.85
8
268
11
ANUCINO
319810
43.97
133.07
7
719
28
APUKA
259560
60.43
169.67
8
515
20
ARHANGELSK
225500
64.55
40.58
7
579
23
ARHARA
315940
49.42
130.08
7
640
25
ARKA
249880
60.08
142.33
8
446
18
ARMAVIR
370310
44.98
41.12
5A
572
23
ASTRAHAN
348800
46.28
48.05
5B
214
8
ASTRAHANKA
319210
44.72
132.07
7
582
23
ATKA
259020
60.85
151.77
8
328
13
B. PRONCHISHCHEVOY
214050
75.53
113.52
8
212
8
BABAEVO
270080
59.40
35.93
7
621
24
BABUSKIN
308220
51.72
105.85
7
523
21
BAEVO
298270
53.27
80.77
7
328
13
BAGDARIN
305540
54.47
113.58
8
378
15
BAJANDAJ
306270
53.10
105.53
8
375
15
BAKALY
286150
55.18
53.80
7
462
18
BAKCHAR
293280
57.08
81.92
7
464
18
BALAGANSK
306120
54.00
103.07
8
326
13

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 447

PDF Page 450

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
CHARA
303720
56.90
118.27
8
346
14
CHELJABINSK-BALANDI
286420
55.30
61.53
7
441
17
CHERDYN
239140
60.40
56.52
7
712
28
CHERNISHEVSKIJ
247240
63.03
112.50
8
337
13
CHERNJAEVO
313710
52.78
126.00
8
485
19
CHERSKIJ
251230
68.75
161.28
8
210
8
CHITA
307580
52.08
113.48
8
346
14
CHOKURDAH
219460
70.62
147.88
8
217
9
CJULBJU
311230
57.77
130.90
8
384
15
CUGUEVKA
319390
44.15
133.87
7
719
28
CULMAN
303930
56.83
124.87
8
530
21
CULYM
296250
55.10
80.97
7
379
15
CURAPCA
247680
62.03
132.60
8
245
10
DALNERECHENSK
318730
45.87
133.73
7
637
25
DEMJANSKOE
280760
59.60
69.28
7
534
21
DIVNOE
348580
45.92
43.35
5A
434
17
DUDINKA
230740
69.40
86.17
8
456
18
DUKI
314820
51.72
135.93
8
646
25
DUVAN
285370
55.70
57.90
7
515
20
DZALINDA
306950
53.47
123.90
8
471
19
DZARDZAN
241430
68.73
124.00
8
304
12
DZERZHINSKOE
294810
56.85
95.22
7
350
14
EGVEKINOT
253780
66.35
–179.12
8
389
15
EKATERINBURG
284400
56.83
60.63
7
511
20
EKATERINO-NIKOLSKOE
317070
47.73
130.97
7
625
25
EKIMCHAN
313290
53.07
132.98
8
693
27
ELABUGA
285060
55.77
52.07
7
544
21
ELAT`MA
276480
54.95
41.77
7
605
24
ELEC
279280
52.63
38.52
6A
579
23
ENISEJSK
292630
58.45
92.15
8
470
19
ERBOGACEN
248170
61.27
108.02
8
340
13
ERMAKOVSKOE
298690
53.30
92.42
7
528
21
EROFEJ PAVLOVIC
306830
53.97
121.93
8
419
16
ERSOV
341860
51.37
48.30
6A
393
15
GAJNY
239090
60.28
54.35
7
626
25
GAR
313840
52.57
129.07
8
574
23
GARI
280490
59.43
62.33
7
468
18
GLAZOV
282140
58.13
52.58
7
587
23
GMO IM.E.K. FEDOROV
202920
77.72
104.30
8
213
8
GORIN
314890
51.20
136.80
8
606
24
GORJACINSK
307310
52.98
108.28
7
400
16
GOR’KIJ
275530
56.22
43.82
7
606
24
GRIDINO
224220
65.90
34.77
7
429
17
GROSSEVICHI
318230
47.97
139.53
7
694
27
GROZNYJ
372350
43.35
45.68
5A
462
18
GUGA
314210
52.70
137.53
8
474
19
GVASJUGI
318010
47.67
136.18
7
915
36
HABAROVSK
317350
48.52
135.17
7
673
27
HADAMA
298920
53.95
98.82
8
529
21
HAKASSKAJA
298620
53.77
91.32
7
310
12
HANTY-MANSIJSK
239330
61.02
69.03
8
535
21
HATANGA
208910
71.98
102.47
8
283
11
HILOK
308440
51.35
110.47
8
380
15
HOLM
263780
57.15
31.18
6A
645
25
HOLMSK
321280
47.05
142.05
6A
795
31
HORINSK
307390
52.17
109.78
8
283
11
HOSEDA-HARD
232190
67.08
59.38
8
455
18
HULARIN
314840
51.42
135.08
7
605
24
ICA
324110
55.58
155.58
7
741
29
IDRINSKOE
297660
54.37
92.13
7
382
15
IGARKA
232740
67.47
86.57
8
494
19
IGNASINO
306860
53.47
122.40
8
421
17
IKEJ
305070
54.18
100.08
8
470
18
ILYINSKIY
321210
47.98
142.20
7
856
34
IM POLINY OSIPENKO
314160
52.42
136.50
8
471
19
IM. M.V. POPOVA
206670
73.33
70.05
8
206
8
IRBEJSKOE
295870
55.63
95.47
7
434
17
IRKUTSK
307100
52.27
104.32
7
475
19
ISIM
285730
56.10
69.43
7
377
15
ISIT
249510
60.82
125.32
8
290
11
IVDEL
239210
60.68
60.45
7
510
20
IZHEVSK
284110
56.83
53.45
7
527
21
JAKUTSK
249590
62.02
129.72
8
234
9
JALTUROVOSK
284650
56.68
66.35
7
423
17
JANAUL
284190
56.27
54.90
7
479
19
JARCEVO
239870
60.25
90.23
8
590
23
JARENSK
227980
62.17
49.12
7
599
24
JASKUL
348660
46.18
45.35
5B
249
10
JUBILEJNAJA
219310
70.77
136.22
8
245
10
JUR`EVEC
273550
57.33
43.12
7
600
24
JUZHNO-KURILSK
321650
44.02
145.87
6A
1238
49
JUZHNO-SAHALINSK
321500
46.95
142.72
7
863
34
KACUG
306220
53.97
105.90
8
310
12
KAJLASTUJ
309780
49.83
118.38
7
341
13
KALAC
342470
50.42
41.05
6A
486
19
KALACINSK
286960
55.03
74.58
7
340
13
KALAKAN
304690
55.12
116.77
8
395
16
KALEVALA
224080
65.22
31.17
7
533
21
KALININGRAD
267020
54.72
20.55
5A
796
31
KALUGA
277030
54.57
36.40
6A
642
25
KAMEN-NA-OBI
298220
53.82
81.27
7
330
13
KAMENSKOE
257440
62.43
166.08
8
413
16
KAMYSIN
343630
50.07
45.37
6A
378
15
KAMYSLOV
284510
56.85
62.72
7
459
18
KANDALAKSA
222170
67.15
32.35
7
509
20
KANIN NOS
221650
68.65
43.30
7
431
17
KANSK
295810
56.20
95.63
7
312
12
KARASUK
298140
53.70
78.07
7
299
12
KARGASOK
291220
59.05
80.95
8
449
18
KARGOPOL
228450
61.50
38.93
7
617
24
KAZACHINSK
303370
56.32
107.62
8
400
16
KAZAN
275950
55.60
49.28
7
532
21
KEDON
256210
64.00
158.92
8
274
11
KEM
225220
64.95
34.65
7
434
17
KEMCHUG
295620
56.10
91.67
7
507
20
KEMEROVO
296420
55.23
86.12
7
465
18

448 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 451

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
KESTENGA
224030
65.88
31.83
7
540
21
KINGISEPP
260590
59.37
28.60
6A
686
27
KIRENSK
302300
57.77
108.07
8
383
15
KIROV
271960
58.65
49.62
7
613
24
KIROV
271990
58.60
49.63
7
613
24
KIROVSKIJ
318780
45.08
133.53
7
670
26
KIRS
280090
59.37
52.22
7
607
24
KJAHTA
309250
50.37
106.45
7
350
14
KJUSJUR
219210
70.68
127.40
8
343
14
KLJUCHI
323890
56.32
160.83
7
618
24
KLJUCI
360210
52.25
79.13
7
318
13
KOCHKI
297240
54.30
80.50
7
358
14
KOCUBEJ
370850
44.40
46.55
4B
243
10
KOJNAS
225830
64.75
47.65
7
609
24
KOLBA
296750
55.08
93.37
7
591
23
KOLPASEVO
292310
58.32
82.95
7
504
20
KOLYVAN
296310
55.30
82.75
7
411
16
KOMMUNAR
297590
54.33
89.28
7
860
34
KORF
259540
60.35
166.00
8
423
17
KOTELNIKOVO<br>346550<br>47.63<br>43.15<br>5A<br>402<br>16<br>KOTLAS<br>228870<br>61.23<br>46.72<br>7<br>538<br>21<br>KOZMODEM`JANSK
274790
56.33
46.58
7
586
23
KRASNODAR
349290
45.03
39.15
4A
702
28
KRASNOJARSK
295740
56.00
92.88
7
495
19
KRASNOJARSK OPYTNOE
295700
56.03
92.75
7
495
19
KRASNOOZERSK
298130
53.97
79.23
7
355
14
KRASNOSCELE
222350
67.35
37.05
8
519
20
KRASNOUFIMSK
284340
56.65
57.78
7
531
21
KRASNYE BAKI
273690
57.13
45.17
7
631
25
KRASNYJ CHIKOJ
309350
50.37
108.75
8
347
14
KRASNYJ JAR
318450
46.53
135.32
7
872
34
KRESCHENKA
295240
55.85
80.03
7
422
17
KUDYMKAR
281160
58.98
54.65
7
548
22
KUPINO
297060
54.37
77.28
7
308
12
KUR
316320
49.93
134.63
7
752
30
KURGAN
286610
55.47
65.40
7
380
15
KURSK
340090
51.77
36.17
6A
627
25
KYRA
309490
49.57
111.97
7
377
15
KYSTOVKA
294050
56.60
76.57
7
416
16
KYZYL
360960
51.72
94.50
8
233
9
LAKE TAJMYR
205940
74.50
102.50
8
227
9
LENSK
249230
60.72
114.88
8
375
15
LEUSI
280640
59.62
65.72
7
488
19
LJUBAN
260780
59.35
31.23
7
635
25
LOKSAK
312630
54.73
130.45
8
577
23
LOSINOBORSKOE
292530
58.43
89.37
8
553
22
LOVOZERO
221270
68.00
35.03
8
486
19
LUKOJANOV
276650
55.03
44.50
7
572
23
MAGADAN
259130
59.55
150.78
8
528
21
MAGDAGACI
312950
53.47
125.82
8
470
18
MAGNITOGORSK
288380
53.35
59.08
7
365
14
MAHACKALA
374720
43.02
47.48
4B
336
13
MAJSK
292090
57.78
77.28
7
494
19
MAKUSINO
286660
55.25
67.30
7
366
14
MALYE KARMAKULY
207440
72.37
52.70
8
343
13
MAMA
301570
58.32
112.87
8
554
22
MARESALE
230320
69.72
66.80
8
258
10
MARIINSK
295510
56.22
87.75
7
441
17
MARKOVO
255510
64.68
170.42
8
397
16
MASLJANINO
297360
54.33
84.22
7
454
18
MATUA
322070
48.07
153.22
7
1321
52
MEDVEZEGORSK
227210
62.92
34.43
7
672
26
MELEUZ
289250
52.95
55.97
7
443
17
MEZEN
224710
65.87
44.22
7
509
20
MINERALNYE VODY
370540
44.23
43.07
5A
524
21
MOGOCA
306730
53.75
119.73
8
426
17
MONDY
308020
51.68
100.98
8
332
13
MOROZOVSK
345450
48.35
41.87
5A
414
16
MOSKVA
276120
55.83
37.62
6A
684
27
MOZDOK
371450
43.73
44.67
5A
531
21
MURMANSK
221130
68.97
33.05
7
473
19
MUZI
234260
65.38
64.72
8
514
20
MYS SHALAUROVA
216470
73.18
143.23
8
116
5
MYS SHMIDTA
251730
68.90
–179.37
8
248
10
MYS UELEN
253990
66.17
–169.83
8
377
15
MYS ZELANIJA
203530
76.85
68.55
8
314
12
NAGORNYJ
304930
55.97
124.88
8
568
22
NAJAHAN
258210
61.95
158.97
8
448
18
NAPAS
290230
59.85
81.95
8
569
22
NARJAN-MAR
232050
67.63
53.03
8
463
18
NAZYVOEVSK
285880
55.57
71.37
7
378
15
NELKAN
311520
57.67
136.15
8
407
16
NERCHINSKIJ ZAVOD
308790
51.32
119.62
8
438
17
NIKOL`SK
270660
59.53
45.47
7
606
24
NIKOLAEVSK-NA-AMURE
313690
53.15
140.70
8
640
25
NIKOLAEVSKOE
261670
58.57
29.80
6A
652
26
NIKOLO-POLOMA
272520
58.35
43.38
7
620
24
NIKOLSKOE
326180
55.20
165.98
7
673
26
NIZHNEANGARSK
304330
55.78
109.55
8
360
14
NIZHNEUDINSK
296980
54.88
99.03
7
404
16
NIZHNYJ TAGIL
282400
57.88
60.07
7
532
21
NIZNIJ NOVGOROD
274590
56.27
44.00
7
608
24
NJAKSIMVOL
237240
62.43
60.87
8
528
21
NJANDOMA
228540
61.67
40.18
7
729
29
NJURBA
246390
63.28
118.33
8
283
11
NOGLIKI
320530
51.92
143.13
7
693
27
NOLINSK
273930
57.55
49.95
7
641
25
NORSK
313880
52.35
129.92
8
559
22
NOVOKUZNETSK
298460
53.82
86.88
7
462
18
NOVOSELENGINSK
308290
51.10
106.65
7
268
11
NOVOSIBIRSK
296340
55.08
82.90
7
436
17
NOZOVKA
283190
57.08
54.75
7
531
21
OBJACEVO
229960
60.37
49.65
7
606
24
OBLUCE
317020
49.00
131.08
7
720
28
ODESSKOE
287970
54.20
72.97
7
330
13
OHANSK
283210
57.72
55.38
7
549
22

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 449

PDF Page 452

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
OHOTSK
310880
59.37
143.20
8
489
19
OKTJABRSKOE
237340
62.45
66.05
8
591
23
OLEKMINSK
249440
60.40
120.42
8
307
12
OLENEK
241250
68.50
112.43
8
290
11
OLOVJANNAJA
309610
50.95
115.58
7
327
13
OMSK
286980
55.02
73.38
7
381
15
ONEGA
226410
63.90
38.12
7
591
23
ONGUDAJ
362310
50.73
86.15
7
363
14
OPARINO
270830
59.85
48.28
7
658
26
ORDYNSKOE
297260
54.37
81.95
7
398
16
OREL
279060
52.93
36.00
6A
639
25
ORENBURG
351210
51.68
55.10
7
365
14
OSTASKOV
263890
57.13
33.12
7
615
24
OSTROV CHETYREHSTOL
219650
70.63
162.48
8
88
3
OSTROV DIKSON
206740
73.50
80.40
8
348
14
OSTROV GOLOMJANNYJ
200870
79.55
90.62
8
226
9
OSTROV KOTELNYJ
214320
76.00
137.87
8
135
5
OSTROV PREOBRAZENIJ
215040
74.67
112.93
8
158
6
OSTROV UEDINENIJA
202740
77.50
82.20
8
158
6
OSTROV VIZE
200690
79.50
76.98
8
209
8
OSTROV VRANGELJA
219820
70.98
–178.48
8
171
7
OZERNAJA
325940
51.48
156.48
7
809
32
PADUN
221060
68.60
31.85
7
525
21
PARTIZANSK
319870
43.15
133.02
6A
782
31
PAVELEC
278230
53.78
39.25
7
542
21
PECHORA
234180
65.12
57.10
8
569
22
PENZA
279620
53.12
45.02
7
540
21
PERM
282250
57.95
56.20
7
614
24
PERVOMAJSKOE
293480
57.07
86.22
7
439
17
PETROPAVLOVSK-KAMCH
325400
53.08
158.58
7
1127
44
PETROPAVLOVSK-KAMCH
325830
52.98
158.65
7
1152
45
PETROVSKIJ ZAVOD
308380
51.32
108.87
8
328
13
PETROZAVODSK
228200
61.82
34.27
7
574
23
PIHTOVKA
295340
55.98
82.70
7
410
16
PILVO
320690
50.05
142.17
7
639
25
PINEGA
225630
64.70
43.38
7
557
22
PIROVSKOE
293630
57.63
92.27
8
481
19
PJALICA
223490
66.18
39.53
7
447
18
POGIBI
320270
52.22
141.63
8
570
22
POGRANICHNOE
320760
50.40
143.77
8
751
30
POGRANICHNYJ
319150
44.40
131.38
7
618
24
POJARKOVO
315870
49.62
128.65
7
533
21
POKROVSKAJA
248560
61.48
129.15
8
269
11
POLARGMO IM. E.T. K
200460
80.62
58.05
8
256
10
POLTAVKA
319170
44.03
131.32
7
588
23
PORONAJSK
320980
49.22
143.10
7
750
30
POSET
319690
42.65
130.80
6A
742
29
PREOBRAZHENIE
319890
42.90
133.90
6A
784
31
PRIARGUNSK
309750
50.40
119.07
8
357
14
PRIMORSKO-AHTARSK
348240
46.03
38.15
5A
565
22
PSKOV
262580
57.82
28.42
6A
629
25
PUDINO
293130
57.53
79.37
7
452
18
PUDOZ
228310
61.80
36.52
7
690
27
RA-IZ
233310
66.90
65.67
8
774
30
REBOLY
226020
63.83
30.82
7
596
23
REBRIHA
299230
53.07
82.30
7
409
16
REMONTNOE
347590
46.57
43.67
5A
379
15
RJAZAN’
277310
54.62
39.72
6A
584
23
RJAZAN<br>277300<br>54.63<br>39.70<br>6A<br>584<br>23<br>ROMANOVKA<br>306500<br>53.20<br>112.78<br>8<br>359<br>14<br>ROSLAVL<br>268820<br>53.93<br>32.83<br>6A<br>604<br>24<br>ROSTOV<br>273290<br>57.20<br>39.42<br>7<br>590<br>23<br>ROSTOV-NA-DONU<br>347310<br>47.25<br>39.82<br>5A<br>593<br>23<br>RUBCOVSK<br>360340<br>51.50<br>81.22<br>7<br>341<br>13<br>RUDNAJA PRISTAN<br>319590<br>44.37<br>135.85<br>7<br>776<br>31<br>RUSSKAYA GAVAN
203570
76.18
62.57
8
377
15
RYBINSK
272250
58.10
38.68
7
671
26
RZEV
264980
56.27
34.32
6A
626
25
SADRINSK
285520
56.07
63.65
7
433
17
SAIM
239290
60.32
64.22
7
457
18
SAKUNJA<br>273730<br>57.67<br>46.63<br>7<br>600<br>24<br>SALEHARD<br>233300<br>66.53<br>66.67<br>8<br>442<br>17<br>SAMARA<br>289000<br>53.25<br>50.45<br>7<br>530<br>21<br>SAMARY<br>283340<br>57.35<br>58.22<br>7<br>660<br>26<br>SANGARY<br>246520<br>63.97<br>127.47<br>8<br>311<br>12<br>SARJA
272710
58.37
45.53
7
643
25
SARAN-PAUL
235270
64.28
60.88
8
499
20
SARATOV
341720
51.57
46.03
6A
431
17
SARGATSKOE
285980
55.60
73.48
7
399
16
SEGEZA
226210
63.77
34.28
7
586
23
SEJAHA
209670
70.17
72.52
8
364
14
SEJMCHAN
257030
62.92
152.42
8
311
12
SEKTAGLI
315340
50.43
131.02
8
724
29
SELAGONCY
243290
66.25
114.28
8
292
11
SELEMDZA
313380
53.13
133.97
8
666
26
SEMJACHIK
325090
54.12
159.98
7
1297
51
SENKURSK
227680
62.10
42.90
7
568
22
SERAFIMOVIC
343570
49.57
42.75
6A
435
17
SERBAKUL
287910
54.63
72.43
7
338
13
SEROV
280440
59.60
60.53
7
487
19
SEVERNOE
294180
56.35
78.35
7
443
17
SEVERO-KURILSK
322150
50.68
156.13
7
1731
68
SHEREMETYEVO
275155
55.97
37.42
7
674
27
SHILKA
308620
51.87
116.03
8
339
13
SIMANOVSK
314420
51.98
127.65
8
534
21
SIMUSIR
321950
46.85
151.87
7
1310
52
SIRA
297560
54.50
89.93
7
454
18
SKOVORODINO
306920
54.00
123.97
8
434
17
SLAVGOROD
299150
52.97
78.65
7
304
12
SMIDOVICH
317250
48.62
133.83
7
699
28
SMOLENSK
267810
54.75
32.07
6A
674
27
SOFIJSKIJ PRIISK
314780
52.27
133.98
8
739
29
SOJNA
222710
67.88
44.13
8
401
16
SOLNETHNAYA
305370
54.03
108.27
7
267
10
SOLOVEVSK
309670
49.90
115.75
7
303
12
SORTAVALA
228020
61.72
30.72
7
606
24

450 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 453

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
SOSNOVO-OZERSKOE
307450
52.53
111.55
8
345
14
SOSUNOVO
318660
46.53
138.33
7
729
29
SOSVA
236250
63.65
62.10
8
487
19
SOVETSKAYA GAVAN
317700
48.97
140.30
7
739
29
SREDNY VASJUGAN
291110
59.22
78.23
7
550
22
SRETENSK
307770
52.23
117.70
8
353
14
ST.PETERSBURG
260630
59.97
30.30
6A
625
25
STARAJA RUSSA
262750
58.02
31.32
6A
605
24
STAVROPOL
349490
45.12
42.08
5A
551
22
STERLITAMAK
288250
53.58
56.00
7
520
20
STRELKA
292740
58.08
93.00
7
480
19
SUHAJA
307260
52.57
107.13
7
304
12
SUHINICI
277070
54.10
35.58
6A
624
25
SUHOBUZIMSKOE
294770
56.50
93.28
7
378
15
SUMIHA
286550
55.23
63.32
7
409
16
SUNTAR
247380
62.15
117.65
8
280
11
SURA
226760
63.58
45.63
7
542
21
SURGUT
238490
61.25
73.50
8
549
22
SUTUR
315380
50.07
132.13
8
688
27
SVETLOGRAD
349540
45.35
42.85
5A
485
19
SVOBODNYJ
314450
51.45
128.12
8
565
22
SYKTYVKAR
238040
61.68
50.78
7
569
22
SYM
239750
60.35
88.37
8
513
20
SYZRAN<br>279830<br>53.18<br>48.40<br>6A<br>455<br>18<br>TADIBE-YAKHA<br>209640<br>70.35<br>74.13<br>8<br>349<br>14<br>TAJSHET<br>295940<br>55.95<br>98.00<br>7<br>427<br>17<br>TAMBEY<br>208640<br>71.48<br>71.82<br>8<br>320<br>13<br>TAMBOV<br>279470<br>52.80<br>41.33<br>6A<br>556<br>22<br>TANGUJ<br>304050<br>55.38<br>101.03<br>7<br>364<br>14<br>TANHOJ<br>308240<br>51.57<br>105.12<br>7<br>795<br>31<br>TARA<br>284930<br>56.90<br>74.38<br>7<br>442<br>17<br>TARKO-SALE<br>235520<br>64.92<br>77.82<br>8<br>501<br>20<br>TASTYP<br>299560<br>52.80<br>89.92<br>7<br>460<br>18<br>TATARSK<br>296050<br>55.20<br>75.97<br>7<br>376<br>15<br>TAZOVSKOE<br>232560<br>67.47<br>78.73<br>8<br>447<br>18<br>TERIBERKA<br>220280<br>69.20<br>35.12<br>7<br>491<br>19<br>TERNEJ<br>319090<br>45.00<br>136.60<br>7<br>828<br>33<br>TEVRIZ<br>283830<br>57.52<br>72.40<br>7<br>474<br>19<br>TIHORECK<br>348380<br>45.85<br>40.08<br>5A<br>622<br>25<br>TIHVIN<br>260940<br>59.65<br>33.55<br>7<br>701<br>28<br>TIKSI<br>218240<br>71.58<br>128.92<br>8<br>227<br>9<br>TISUL<br>295570<br>55.75<br>88.32<br>7<br>542<br>21<br>TIVJAKU<br>317540<br>48.60<br>137.05<br>8<br>890<br>35<br>TJUHTET<br>294560<br>56.53<br>89.32<br>7<br>508<br>20<br>TJUKALINSK<br>285860<br>55.87<br>72.20<br>7<br>391<br>15<br>TJUMEN<br>283670<br>57.12<br>65.43<br>7<br>470<br>19<br>TOBOLSK<br>282750<br>58.15<br>68.25<br>7<br>473<br>19<br>TOGUCHIN<br>296360<br>55.23<br>84.40<br>7<br>438<br>17<br>TOKO<br>311370<br>56.28<br>131.13<br>8<br>473<br>19<br>TOMPA<br>304390<br>55.12<br>109.75<br>8<br>357<br>14<br>TOMSK<br>294300<br>56.50<br>84.92<br>7<br>527<br>21<br>TOTMA
270510
59.88
42.75
7
647
25
TROICKOE
316550
49.45
136.57
7
658
26
TROICKO-PECHERSKOE
237110
62.70
56.20
8
633
25
TROIZK
287480
54.08
61.62
7
370
15
TRUBCEVSK
269970
52.58
33.77
6A
644
25
TUAPSE
370180
44.10
39.07
4A
1469
58
TULA
277190
54.23
37.62
6A
620
24
TULUN
305040
54.60
100.63
7
416
16
TUMNIN
316830
49.67
140.12
7
561
22
TUNGOKOCEN
306640
53.53
115.62
8
390
15
TUNKA
308110
51.73
102.53
8
372
15
TURA
245070
64.27
100.23
8
362
14
TURINSK
282550
58.05
63.68
7
485
19
TUROCAK
360610
52.27
87.17
7
852
34
TURUHANSK
234720
65.78
87.93
8
559
22
TVER
274020
56.90
35.88
7
645
25
TYNDA
304990
55.18
124.67
8
578
23
UAKIT
304550
55.47
113.62
8
365
14
UEGA
249820
60.72
142.78
8
439
17
UFA
287220
54.72
55.83
7
590
23
UHTA
236060
63.55
53.82
7
542
21
UJAR
295760
55.80
94.33
7
447
18
ULAN-UDE
308230
51.83
107.60
7
272
11
ULETY
308460
51.35
112.47
7
332
13
ULYANOVSK
277860
54.32
48.33
7
491
19
UMBA
223240
66.68
34.35
7
489
19
UNAHA
311990
55.03
126.80
8
585
23
URJUPINSK
342400
50.80
42.00
6A
475
19
URMI
316240
49.40
133.23
7
854
34
URUP
321860
46.20
150.50
7
1263
50
UST-BARGUZIN
306350
53.42
109.02
8
372
15
UST-CILMA
234050
65.43
52.27
8
550
22
UST-ILIMSK
301170
58.20
102.75
8
391
15
UST-ISIM
283820
57.72
–71.18
7
525
21
UST-JUDOMA
310540
59.18
135.15
8
360
14
UST-KAMCHATSK
324080
56.22
162.47
7
692
27
UST-KULOM
238030
61.68
53.68
7
625
25
UST-KUT
303200
56.87
105.70
8
525
21
UST-MAJA
249660
60.38
134.45
8
307
12
UST-NJUKZHA
303850
56.58
121.48
8
439
17
UST-OLOJ
253250
66.55
159.42
8
256
10
USTORDYNSKIJ
307130
52.82
104.77
8
314
12
UST-UDA
305140
54.17
103.02
8
302
12
UST-UMALTA
314740
51.63
133.32
8
777
31
UST-USA
234120
65.97
56.92
8
509
20
UST-VOJAMPOLKA
322520
58.50
159.17
8
477
19
USUGLI
307640
52.65
115.17
8
360
14
UYBAT
298640
53.72
90.37
7
288
11
UZUR
296530
55.30
89.82
7
414
16
VANZIL-KYNAK
239660
60.35
84.08
8
577
23
VELIKIE LUKI
264770
56.35
30.62
6A
596
23
VELSK
228670
61.08
42.07
7
594
23
VERESCAGINO
282160
58.08
54.68
7
580
23
VERHNEE PENZINO
255380
64.22
164.23
8
322
13
VERHNEIMBATSK
236780
63.15
87.95
8
561
22

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 451

PDF Page 454

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
VERHNIJ BASKUNCAK
345790
48.22
46.73
5B
269
11
VERHNIJ UFALEJ
285410
56.08
60.30
7
535
21
VERHNJAJA TOJMA
227780
62.23
45.02
7
596
23
VERHNJAJA TOM
314590
51.35
130.43
8
665
26
VERHOTUR`E
281440
58.87
60.78
7
520
20
VESELAJA GORKA
314180
52.28
135.80
7
607
24
VESLJANA
237010
62.98
50.90
7
581
23
VIKULOVO
284810
56.82
70.62
7
427
17
VILJUJSK
246410
63.77
121.62
8
264
10
VITIM
300540
59.45
112.58
8
433
17
VJAZMA
266950
55.17
34.40
7
660
26
VLADIMIR
275320
56.12
40.35
7
620
24
VLADIVOSTOK
319600
43.12
131.93
6A
795
31
VNUKOVO
275185
55.58
37.25
6A
667
26
VOLCIHA
360220
52.02
80.37
7
343
14
VOLGOGRAD
345600
48.78
44.37
6A
387
15
VOLOGDA
270370
59.32
39.92
7
561
22
VORKUTA
232260
67.48
64.02
8
574
23
VOROGOVO
239730
61.03
89.63
8
575
23
VORONEZ
341220
51.65
39.25
6A
570
22
VORONEZ
341230
51.70
39.22
6A
570
22
VOZEGA
229540
60.47
40.20
7
672
26
VYBORG
228920
60.72
28.73
7
693
27
VYTEGRA
228370
61.02
36.45
7
671
26
WLADIKAVKAZ
372280
43.05
44.65
5A
895
35
ZAMETCINO
278570
53.48
42.63
6A
496
20
ZAMOKTA
307410
52.77
109.97
8
471
19
ZAVITAJA
315270
50.12
129.47
7
595
23
ZDVINSK
297120
54.70
78.67
7
332
13
ZEJA
313000
53.70
127.30
8
527
21
ZERDEVKA
340470
51.83
41.48
6A
504
20
ZHIGALOVO
305210
54.80
105.22
8
333
13
ZHIGANSK
243430
66.77
123.40
8
274
11
ZILAIR
350260
52.22
57.40
7
569
22
ZILOVO
306690
53.07
117.48
8
401
16
ZIMA
306030
53.93
102.05
7
348
14
ZIZGIN
224380
65.20
36.82
7
371
15
ZOHOVA ISLAND
213580
76.15
152.83
8
201
8
ZOLOTOJ
318290
47.32
138.98
7
912
36
ZURAVLEVKA
319420
44.75
134.47
7
656
26
ZYRJANKA
254000
65.73
150.90
8
275
11
AL-WEJH
404000
26.20
36.48
1B
35
1
ARAR
403570
30.90
41.13
2B
59
2
BISHA
410840
19.98
42.63
1B
117
5
DHAHRAN
404160
26.27
50.17
0B
79
3
GASSIM
404050
26.30
43.77
1B
187
7
GIZAN
411400
16.88
42.58
0B
136
5
GURIAT
403600
31.40
37.28
2B
66
3
HAIL
403940
27.43
41.68
2B
125
5
JEDDAH (KING ABDUL AZIZ INTL)
410240
21.70
39.18
0B
57
2
KHAMIS MUSHAIT
411140
18.30
42.80
2B
214
8
KING KHALED INT. AI
404370
24.93
46.72
1B
127
5
MAKKAH
410300
21.43
39.77
0B
102
4
NAJRAN
411280
17.62
44.42
1B
76
3
RAFHA
403620
29.62
43.48
2B
81
3
RIYADH OBS. (O.A.P.)
404380
24.70
46.73
0B
130
5
SHARORAH
411360
17.47
47.10
0B
66
3
TABUK
403750
28.38
36.60
2B
54
2
TURAIF
403560
31.68
38.73
3B
102
4
YENBO
404390
24.13
38.07
0B
38
2
VERHNIJ BASKUNCAK
345790
48.22
46.73
5B
269
11
VERHNIJ UFALEJ
285410
56.08
60.30
7
535
21
VERHNJAJA TOJMA
227780
62.23
45.02
7
596
23
VERHNJAJA TOM
314590
51.35
130.43
8
665
26
VERHOTUR`E
281440
58.87
60.78
7
520
20
VESELAJA GORKA
314180
52.28
135.80
7
607
24
VESLJANA
237010
62.98
50.90
7
581
23
VIKULOVO
284810
56.82
70.62
7
427
17
VILJUJSK
246410
63.77
121.62
8
264
10
VITIM
300540
59.45
112.58
8
433
17
VJAZMA
266950
55.17
34.40
7
660
26
VLADIMIR
275320
56.12
40.35
7
620
24
VLADIVOSTOK
319600
43.12
131.93
6A
795
31
VNUKOVO
275185
55.58
37.25
6A
667
26
VOLCIHA
360220
52.02
80.37
7
343
14
VOLGOGRAD
345600
48.78
44.37
6A
387
15
VOLOGDA
270370
59.32
39.92
7
561
22
VORKUTA
232260
67.48
64.02
8
574
23
VOROGOVO
239730
61.03
89.63
8
575
23
VORONEZ
341220
51.65
39.25
6A
570
22
VORONEZ
341230
51.70
39.22
6A
570
22
VOZEGA
229540
60.47
40.20
7
672
26
VYBORG
228920
60.72
28.73
7
693
27
VYTEGRA
228370
61.02
36.45
7
671
26
WLADIKAVKAZ
372280
43.05
44.65
5A
895
35
ZAMETCINO
278570
53.48
42.63
6A
496
20
ZAMOKTA
307410
52.77
109.97
8
471
19
ZAVITAJA
315270
50.12
129.47
7
595
23
ZDVINSK
297120
54.70
78.67
7
332
13
ZEJA
313000
53.70
127.30
8
527
21
ZERDEVKA
340470
51.83
41.48
6A
504
20
ZHIGALOVO
305210
54.80
105.22
8
333
13
ZHIGANSK
243430
66.77
123.40
8
274
11
ZILAIR
350260
52.22
57.40
7
569
22
ZILOVO
306690
53.07
117.48
8
401
16
ZIMA
306030
53.93
102.05
7
348
14
ZIZGIN
224380
65.20
36.82
7
371
15
ZOHOVA ISLAND
213580
76.15
152.83
8
201
8
ZOLOTOJ
318290
47.32
138.98
7
912
36
ZURAVLEVKA
319420
44.75
134.47
7
656
26
ZYRJANKA
254000
65.73
150.90
8
275
11
Senegal (SEN)
DAKAR/YOFF
616410
14.73
–17.50
1B
423
17
KAOLACK
616790
14.13
–16.07
0B
597
24
LINGUERE
616270
15.38
–15.12
0B
432
17
MATAM
616300
15.65
–13.25
0B
369
15
SAINT-LOUIS
616000
16.05
–16.45
1B
255
10
TAMBACOUNDA
616870
13.77
–13.68
0B
765
30
ZIGUINCHOR
616950
12.55
–16.27
0A
1264
50
VERHNIJ BASKUNCAK
345790
48.22
46.73
5B
269
11
VERHNIJ UFALEJ
285410
56.08
60.30
7
535
21
VERHNJAJA TOJMA
227780
62.23
45.02
7
596
23
VERHNJAJA TOM
314590
51.35
130.43
8
665
26
VERHOTUR`E
281440
58.87
60.78
7
520
20
VESELAJA GORKA
314180
52.28
135.80
7
607
24
VESLJANA
237010
62.98
50.90
7
581
23
VIKULOVO
284810
56.82
70.62
7
427
17
VILJUJSK
246410
63.77
121.62
8
264
10
VITIM
300540
59.45
112.58
8
433
17
VJAZMA
266950
55.17
34.40
7
660
26
VLADIMIR
275320
56.12
40.35
7
620
24
VLADIVOSTOK
319600
43.12
131.93
6A
795
31
VNUKOVO
275185
55.58
37.25
6A
667
26
VOLCIHA
360220
52.02
80.37
7
343
14
VOLGOGRAD
345600
48.78
44.37
6A
387
15
VOLOGDA
270370
59.32
39.92
7
561
22
VORKUTA
232260
67.48
64.02
8
574
23
VOROGOVO
239730
61.03
89.63
8
575
23
VORONEZ
341220
51.65
39.25
6A
570
22
VORONEZ
341230
51.70
39.22
6A
570
22
VOZEGA
229540
60.47
40.20
7
672
26
VYBORG
228920
60.72
28.73
7
693
27
VYTEGRA
228370
61.02
36.45
7
671
26
WLADIKAVKAZ
372280
43.05
44.65
5A
895
35
ZAMETCINO
278570
53.48
42.63
6A
496
20
ZAMOKTA
307410
52.77
109.97
8
471
19
ZAVITAJA
315270
50.12
129.47
7
595
23
ZDVINSK
297120
54.70
78.67
7
332
13
ZEJA
313000
53.70
127.30
8
527
21
ZERDEVKA
340470
51.83
41.48
6A
504
20
ZHIGALOVO
305210
54.80
105.22
8
333
13
ZHIGANSK
243430
66.77
123.40
8
274
11
ZILAIR
350260
52.22
57.40
7
569
22
ZILOVO
306690
53.07
117.48
8
401
16
ZIMA
306030
53.93
102.05
7
348
14
ZIZGIN
224380
65.20
36.82
7
371
15
ZOHOVA ISLAND
213580
76.15
152.83
8
201
8
ZOLOTOJ
318290
47.32
138.98
7
912
36
ZURAVLEVKA
319420
44.75
134.47
7
656
26
ZYRJANKA
254000
65.73
150.90
8
275
11
Serbia (SRB)
BANATSKI KARLOVAC
131800
45.05
21.03
4A
627
25
BEOGRAD
132740
44.80
20.47
4A
674
27
BEOGRAD/SURCIN
132720
44.82
20.28
4A
666
26
CRNI VRH
132890
44.12
21.95
6A
684
27
CUPRIJA
133840
43.93
21.38
4A
652
26
DIMITROVGRAD
133970
43.02
22.75
5A
618
24
KIKINDA
131740
45.85
20.47
4A
544
21
KOPAONIK
133780
43.28
20.80
7
845
33
KRALJEVO
133760
43.70
20.70
4A
785
31
KRUSEVAC
133830
43.57
21.35
4A
648
26
LESKOVAC
133890
42.98
21.95
4A
610
24
LOZNICA
132620
44.55
19.23
4A
832
33
NEGOTIN
132950
44.23
22.55
4A
592
23
NIS
133880
43.33
21.90
4A
615
24
NOVI SAD RIMSKI SAN
131680
45.33
19.85
4A
581
23
PALIC
130670
46.10
19.77
4A
539
21
PEC
134730
42.67
20.30
4A
863
34
PLEVLJA
133630
43.35
19.35
5A
936
37
PODGORICA
134624
42.35
19.25
3A
1707
67
PODGORICA/GOLUBOVCI
134620
42.37
19.25
3A
1707
67
PRISTINA
134810
42.65
21.15
5A
629
25
PRIZREN
134770
42.22
20.73
4A
852
34
SJENICA
133690
43.28
20.00
6A
763
30
SMEDEREVSKA PALANKA
132790
44.37
20.95
4A
644
25
SOMBOR
131600
45.77
19.15
4A
591
23
Saint Lucia (LCA)
HEWANORRA INTL AIRP
789480
13.75
–60.95
0A
1128
44
Saint Lucia (LCA)
HEWANORRA INTL AIRP
789480
13.75
–60.95
0A
1128
44
Samoa (WSM)
APIA
917620
–13.80
–171.78
0A
2971
117
Samoa (WSM)
APIA
917620
–13.80
–171.78
0A
2971
117
Saudi Arabia (SAU)
ABHA
411120
18.23
42.65
3B
224
9
AL-AHSA
404200
25.30
49.48
0B
90
4
AL-BAHA
410550
20.30
41.65
2B
157
6
AL-JOUF
403610
29.78
40.10
2B
56
2
AL-MADINAH
404300
24.55
39.70
0B
61
2
AL-QAISUMAH
403730
28.32
46.13
1B
136
5
AL-TAIF
410360
21.48
40.55
2B
150
6
Saudi Arabia (SAU)
ABHA
411120
18.23
42.65
3B
224
9
AL-AHSA
404200
25.30
49.48
0B
90
4
AL-BAHA
410550
20.30
41.65
2B
157
6
AL-JOUF
403610
29.78
40.10
2B
56
2
AL-MADINAH
404300
24.55
39.70
0B
61
2
AL-QAISUMAH
403730
28.32
46.13
1B
136
5
AL-TAIF
410360
21.48
40.55
2B
150
6

452 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 455

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
SREMSKA MITROVICA
132660
45.10
19.55
4A
618
24
TIVAT
134570
42.40
18.73
3A
2205
87
VALJEVO
132690
44.32
19.92
4A
783
31
VELIKO GRADISTE
132850
44.75
21.52
4A
644
25
VRANJE
134890
42.55
21.92
4A
611
24
VRSAC
131830
45.15
21.32
4A
678
27
ZLATIBOR
133670
43.73
19.72
5A
951
37
ZRENJANIN
131730
45.37
20.42
4A
567
22
DE AAR
685380
–30.65
24.00
3B
331
13
DURBAN INTNL. AIRPO
685880
–29.97
30.95
2A
909
36
EAST LONDON
688580
–33.03
27.83
3A
875
34
GEORGE AIRPORT
688280
–34.02
22.38
3A
741
29
GOUGH ISLAND
689060
–40.35
–9.88
4A
3191
126
JOHANNESBURG INTNL.
683680
–26.15
28.23
3A
727
29
KIMBERLEY
684380
–28.80
24.77
3B
421
17
LANGEBAANWEG
687140
–32.97
18.17
3B
281
11
MAFIKENG WO
682420
–25.82
25.55
3B
562
22
MARION ISLAND
689940
–46.88
37.87
6A
2280
90
MOSSEL BAY (CAPE ST BLAIZE)
689280
–34.18
22.15
3B
379
15
PIETERSBURG
681740
–23.87
29.45
3B
487
19
PORT ELIZABETH
688420
–33.98
25.62
3A
608
24
PRETORIA (IRENE)
682630
–25.92
28.22
3A
714
28
PRETORIA-EENDRACHT
682620
–25.73
28.18
3A
681
27
SPRINGBOK
685120
–29.67
17.90
3B
192
8
UPINGTON
684240
–28.40
21.27
2B
195
8
Seychelles (SYC)
SEYCHELLES INTERNAT
639800
–4.67
55.52
0A
2337
92
Seychelles (SYC)
SEYCHELLES INTERNAT
639800
–4.67
55.52
0A
2337
92
Singapore (SGP)
SINGAPORE/CHANGI AI
486980
1.37
103.98
0A
2068
81
Singapore (SGP)
SINGAPORE/CHANGI AI
486980
1.37
103.98
0A
2068
81
Sint Maarten, Dutch part (SXM)
PRINSES JULIANA
788660
18.03
–63.12
0A
1056
42
Sint Maarten, Dutch part (SXM)
PRINSES JULIANA
788660
18.03
–63.12
0A
1056
42
Slovakia (SVK)
BRATISLAVA-LETISKO
118160
48.20
17.20
5A
578
23
CHOPOK
119160
48.98
19.60
7
990
39
DUDINCE
118800
48.17
18.87
5A
579
23
HURBANOVO
118580
47.87
18.20
5A
554
22
KAMENICA NAD CIROCH
119930
48.93
22.00
5A
733
29
KOSICE
119680
48.67
21.22
5A
613
24
LIESEK
119180
49.37
19.68
6A
895
35
LOMNICKY STIT
119300
49.20
20.22
8
1156
46
LUCENEC
119270
48.33
19.73
5A
664
26
MILHOSTOV
119780
48.67
21.73
5A
599
24
NITRA
118550
48.28
18.13
5A
590
23
PIESTANY
118260
48.62
17.83
5A
603
24
POPRAD/TATRY
119340
49.07
20.25
6A
590
23
PRIEVIDZA
118670
48.77
18.60
5A
739
29
SLIAC
119030
48.65
19.15
5A
690
27
STRBSKE PLESO
119330
49.12
20.08
7
1156
46
STROPKOV/TISINEC
119760
49.22
21.65
5A
698
27
TELGART
119380
48.85
20.18
6A
801
32
ZILINA/HRICOV
118410
49.23
18.62
5A
787
31
Slovakia (SVK)
BRATISLAVA-LETISKO
118160
48.20
17.20
5A
578
23
CHOPOK
119160
48.98
19.60
7
990
39
DUDINCE
118800
48.17
18.87
5A
579
23
HURBANOVO
118580
47.87
18.20
5A
554
22
KAMENICA NAD CIROCH
119930
48.93
22.00
5A
733
29
KOSICE
119680
48.67
21.22
5A
613
24
LIESEK
119180
49.37
19.68
6A
895
35
LOMNICKY STIT
119300
49.20
20.22
8
1156
46
LUCENEC
119270
48.33
19.73
5A
664
26
MILHOSTOV
119780
48.67
21.73
5A
599
24
NITRA
118550
48.28
18.13
5A
590
23
PIESTANY
118260
48.62
17.83
5A
603
24
POPRAD/TATRY
119340
49.07
20.25
6A
590
23
PRIEVIDZA
118670
48.77
18.60
5A
739
29
SLIAC
119030
48.65
19.15
5A
690
27
STRBSKE PLESO
119330
49.12
20.08
7
1156
46
STROPKOV/TISINEC
119760
49.22
21.65
5A
698
27
TELGART
119380
48.85
20.18
6A
801
32
ZILINA/HRICOV
118410
49.23
18.62
5A
787
31
Slovakia (SVK)
BRATISLAVA-LETISKO
118160
48.20
17.20
5A
578
23
CHOPOK
119160
48.98
19.60
7
990
39
DUDINCE
118800
48.17
18.87
5A
579
23
HURBANOVO
118580
47.87
18.20
5A
554
22
KAMENICA NAD CIROCH
119930
48.93
22.00
5A
733
29
KOSICE
119680
48.67
21.22
5A
613
24
LIESEK
119180
49.37
19.68
6A
895
35
LOMNICKY STIT
119300
49.20
20.22
8
1156
46
LUCENEC
119270
48.33
19.73
5A
664
26
MILHOSTOV
119780
48.67
21.73
5A
599
24
NITRA
118550
48.28
18.13
5A
590
23
PIESTANY
118260
48.62
17.83
5A
603
24
POPRAD/TATRY
119340
49.07
20.25
6A
590
23
PRIEVIDZA
118670
48.77
18.60
5A
739
29
SLIAC
119030
48.65
19.15
5A
690
27
STRBSKE PLESO
119330
49.12
20.08
7
1156
46
STROPKOV/TISINEC
119760
49.22
21.65
5A
698
27
TELGART
119380
48.85
20.18
6A
801
32
ZILINA/HRICOV
118410
49.23
18.62
5A
787
31
Spain (ESP)
ALBACETE/LOS LLANOS
082800
38.95
–1.85
4B
357
14
ALICANTE/EL ALTET
083600
38.28
–0.55
3B
319
13
ALMERIA/AEROPUERTO
084870
36.85
–2.38
3B
200
8
BARCELONA/AEROPUERT
081810
41.28
2.07
3A
623
25
BILBAO/SONDICA
080250
43.30
–2.90
3A
1231
48
CACERES
082610
39.47
–6.33
3A
569
22
CIUDAD REAL
083480
38.98
–3.92
3B
428
17
COIMBRA/CERNACHE
085480
40.15
–8.47
3C
998
39
GERONA/COSTA BRAVA
081840
41.90
2.77
3A
727
29
GRANADA/AEROPUERTO
084190
37.18
–3.78
3A
507
20
IBIZA/ES CODOLA
083730
38.88
1.38
3B
414
16
LA CORUNA
080010
43.37
–8.42
3C
1014
40
LAS PALMAS DE GRAN
600300
27.93
–15.38
2B
125
5
LOGRONO/AGONCILLO
080840
42.45
–2.33
3A
718
28
MADRID/BARAJAS RS
082210
40.45
–3.55
4A
454
18
MADRID/TORREJON
082270
40.48
–3.45
4A
461
18
MALAGA/AEROPUERTO
084820
36.67
–4.48
3A
558
22
MENORCA/MAHON
083140
39.87
4.23
3A
580
23
MORON DE LA FRONTER
083970
37.15
–5.62
3A
556
22
MURCIA
084300
38.00
–1.17
3B
283
11
OVIEDO
080150
43.35
–5.87
4A
1043
41
PALMA DE MALLORCA/S
083060
39.55
2.73
3A
620
24
ROTA NAS
084490
36.65
–6.35
3A
535
21
SALAMANCA/MATACAN
082020
40.95
–5.50
4C
459
18
SAN SEBASTIAN/IGUEL
080270
43.30
–2.03
3A
1715
68
SANTANDER
080230
43.48
–3.80
3C
1171
46
SANTIAGO/LABACOLLA
080420
42.90
–8.43
4C
1649
65
SEVILLA/SAN PABLO
083910
37.42
–5.90
3A
604
24
STA. CRUZ DE TENERI
600200
28.45
–16.25
2B
221
9
TENERIFE SUR
600250
28.05
–16.57
2B
286
11
VALENCIA/AEROPUERTO
082840
39.50
–0.47
3B
437
17
VALLADOLID
081410
41.65
–4.77
4A
454
18
VIGO/PEINADOR
080450
42.23
–8.63
3C
1587
62
VITORIA
080800
42.88
–2.72
4A
1042
41
ZARAGOZA (USAFB)
081605
41.67
–1.05
3B
311
12
Slovenia (SVN)
KREDARICA
140080
46.38
13.85
7
1998
79
LISCA
140240
46.07
15.28
5A
1132
45
LJUBLJANA/BEZIGRAD
140150
46.07
14.52
4A
1364
54
LJUBLJANA/BRNIK
130140
46.22
14.48
5A
1500
59
MARIBOR
130260
46.48
15.68
5A
1099
43
MURSKA SOBOTA
140310
46.65
16.18
5A
894
35
NOVA GORICA
141060
45.90
13.63
4A
1520
60
NOVO MESTO
141210
45.80
15.18
5A
1208
48
PORTOROZ
131050
45.52
13.57
4A
1116
44
SLAVONSKI BROD
131500
45.17
18.00
5A
822
32
Slovenia (SVN)
KREDARICA
140080
46.38
13.85
7
1998
79
LISCA
140240
46.07
15.28
5A
1132
45
LJUBLJANA/BEZIGRAD
140150
46.07
14.52
4A
1364
54
LJUBLJANA/BRNIK
130140
46.22
14.48
5A
1500
59
MARIBOR
130260
46.48
15.68
5A
1099
43
MURSKA SOBOTA
140310
46.65
16.18
5A
894
35
NOVA GORICA
141060
45.90
13.63
4A
1520
60
NOVO MESTO
141210
45.80
15.18
5A
1208
48
PORTOROZ
131050
45.52
13.57
4A
1116
44
SLAVONSKI BROD
131500
45.17
18.00
5A
822
32
Solomon Islands (SLB)
HONIARA/HENDERSON
915200
–9.42
160.05
0A
2004
79
Solomon Islands (SLB)
HONIARA/HENDERSON
915200
–9.42
160.05
0A
2004
79
South Africa (ZAF)
BETHLEHEM
684610
–28.25
28.33
3A
690
27
BLOEMFONTEIN AIRPOR
684420
–29.10
26.30
3B
568
22
CALVINIA
686180
–31.47
19.77
3B
210
8
CAPE COLUMBINE
687120
–32.83
17.85
3C
273
11
CAPE TOWN INTNL. AI
688160
–33.97
18.60
3C
521
21
South Africa (ZAF)
BETHLEHEM
684610
–28.25
28.33
3A
690
27
BLOEMFONTEIN AIRPOR
684420
–29.10
26.30
3B
568
22
CALVINIA
686180
–31.47
19.77
3B
210
8
CAPE COLUMBINE
687120
–32.83
17.85
3C
273
11
CAPE TOWN INTNL. AI
688160
–33.97
18.60
3C
521
21

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 453

PDF Page 456

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
ZARAGOZA/AEROPUERTO
081600
41.67
–1.00
3B
311
12
KIRUNA
020440
67.82
20.33
8
502
20
KLIMPFJALL
021080
65.07
14.80
7
736
29
KRANGEDE
022470
63.15
16.17
7
579
23
KUGGOREN
023550
61.70
17.53
6A
683
27
KULLEN (LGT-H)
026060
56.30
12.45
5A
573
23
KVIKKJOKK-ARRENJARK
021200
66.88
17.75
7
629
25
LAINIO
020860
67.77
22.35
8
535
21
LANDSORT
025820
58.75
17.87
6A
446
18
LINKOPING/MALMSLATT
025620
58.40
15.53
6A
552
22
LJUNGBY
026220
56.85
13.88
6A
825
32
LJUNGBYHED
020001
56.08
13.20
5A
798
31
LULEA-KALLAX
021860
65.55
22.13
7
532
21
MALILLA
025660
57.40
15.82
6A
572
23
MALMO/STURUP
026360
55.55
13.37
5A
696
27
MALUNG
024100
60.68
13.72
7
704
28
MASESKAR
025050
58.10
11.33
5A
648
25
NAIMAKKA
020600
68.68
21.53
8
462
18
NIDINGEN
025180
57.30
11.90
5A
742
29
NIKKALUOKTA
020360
67.85
19.03
8
513
20
NORRKOPING/BRAVALLA
025700
58.62
16.12
6A
549
22
NORRKOPING/KUNGSANG
025710
58.58
16.15
6A
549
22
OLANDS NORRA UDDE
025920
57.37
17.10
5A
422
17
OLANDS SODRA UDDE
026440
56.20
16.40
5A
726
29
OREBRO
024320
59.23
15.05
6A
650
26
ORSKAR
024880
60.53
18.38
6A
475
19
OSBY
026260
56.37
13.95
6A
796
31
OSTERSUND FROSON
022260
63.20
14.50
7
486
19
OSTMARK
024000
60.35
12.65
7
799
31
OVERKALIX SVARTBYN
021810
66.27
22.85
7
549
22
PAJALA
020960
67.22
23.40
7
586
23
PALKEM
021640
66.38
21.63
7
670
26
PITE-RONNSKAR
021760
65.03
21.57
7
446
18
RANGEDALA
025360
57.78
13.17
6A
933
37
RITSEM
020120
67.73
17.47
7
608
24
RONNEBY/KALLINGE
026640
56.27
15.27
6A
655
26
RORBACKSNAS
023060
61.13
12.82
7
753
30
SARNA
023160
61.70
13.18
7
686
27
SATENAS
025200
58.43
12.72
6A
689
27
SINGO ISLAND
024740
60.17
18.75
6A
640
25
SKAGSUDDE
022690
63.18
19.02
6A
532
21
SKAVSTA
024853
58.78
16.90
6A
534
21
SKILLINGE
026250
55.48
14.32
5A
557
22
SODERHAMN
022861
61.25
17.10
6A
636
25
STOCKHOLM/ARLANDA
024600
59.65
17.95
6A
556
22
STOCKHOLM/BROMMA
024640
59.37
17.90
6A
550
22
STORLIEN
022060
63.30
12.12
7
986
39
SVEG
023240
62.02
14.37
7
631
25
SVENSKA HOGARNA
024960
59.45
19.50
6A
453
18
TANNAS
023080
62.45
12.67
7
614
24
TIMRA/MIDLANDA
023660
62.52
17.45
7
597
23
UMEA
022860
63.80
20.28
7
596
23
UNGSKAR
026660
56.03
15.80
5A
537
21
Sri Lanka (LKA)
KATUNAYAKE
434500
7.17
79.88
0A
2031
80
Sri Lanka (LKA)
KATUNAYAKE
434500
7.17
79.88
0A
2031
80
St. Helena, Ascension, and Tristan de Cunha (SHN)
ST. HELENA IS.
619010
–15.93
–5.67
3C
44
2
WIDE AWAKE FIELD (ASI)
619020
–7.97
–14.40
1B
117
5
St. Helena, Ascension, and Tristan de Cunha (SHN)
ST. HELENA IS.
619010
–15.93
–5.67
3C
44
2
WIDE AWAKE FIELD (ASI)
619020
–7.97
–14.40
1B
117
5
Suriname (SUR)
ZANDERIJ
812250
5.45
–55.20
0A
2249
89
Suriname (SUR)
ZANDERIJ
812250
5.45
–55.20
0A
2249
89
Svalbard and Jan Mayen (SJM)
BJORNOYA
010280
74.52
19.02
8
391
15
HOPEN
010620
76.50
25.07
8
431
17
SVALBARD LUFTHAVN
010080
78.25
15.47
8
186
7
Svalbard and Jan Mayen (SJM)
BJORNOYA
010280
74.52
19.02
8
391
15
HOPEN
010620
76.50
25.07
8
431
17
SVALBARD LUFTHAVN
010080
78.25
15.47
8
186
7
Sweden (SWE)
ANGELHOLM
025635
56.30
12.85
5A
742
29
ARJEPLOG
021240
66.05
17.87
7
588
23
ARVIKA
024040
59.67
12.58
6A
702
28
BJUROKLUBB (LGT-H)
022960
64.48
21.58
7
588
23
BLOMSKOG
024080
59.22
12.08
6A
812
32
BORLANGE
024350
60.43
15.52
6A
638
25
EDSBYN
023380
61.37
15.72
7
589
23
FALSTERBO
026160
55.38
12.82
5A
502
20
FARO ISLAND
025880
57.90
19.17
6A
535
21
FLODA
024760
59.05
16.40
6A
575
23
FOLKARNA
024440
60.17
16.32
6A
602
24
FRANSTA
023420
62.50
16.18
7
545
21
GADDEDE
022220
64.50
14.17
7
799
31
GALLIVARE
020490
67.15
20.65
7
526
21
GAVLE
024530
60.72
17.17
6A
632
25
GLADHAMMAR
025760
57.78
16.60
6A
538
21
GOTEBORG
025130
57.72
12.00
5A
813
32
GOTEBORG/LANDVETTER
025260
57.67
12.30
6A
931
37
GOTEBORG/SAVE
025120
57.78
11.88
6A
813
32
GOTSKA SANDON
025840
58.40
19.20
6A
537
21
GUNNARN
021280
65.02
17.68
7
597
24
HAGSHULT
025560
57.30
14.13
6A
769
30
HALLANDS VADERO
026050
56.45
12.55
5A
667
26
HANO
026280
56.02
14.85
5A
577
23
HAPARANDA
021960
65.83
24.15
7
577
23
HARSTENA
025860
58.25
17.02
6A
664
26
HELSINGBORG
026110
56.03
12.77
5A
729
29
HOBURG
026800
56.92
18.15
5A
507
20
HOLMOGADD
022880
63.60
20.75
7
572
23
IDVATTNET
022520
64.45
17.08
7
605
24
JOKKMOKK (SWE-AFB)
021420
66.63
19.65
8
501
20
JONKOPING/AXAMO
025500
57.75
14.08
6A
690
27
JUNSELE
022440
63.68
16.95
7
575
23
KALMAR
026700
56.68
16.30
5A
501
20
KALMAR
026720
56.73
16.30
6A
501
20
KARESUANDO
020800
68.45
22.45
8
456
18
KARLSBORG(SAFB)
025440
58.52
14.53
6A
582
23
KARLSTAD FLYGPLATS
024180
59.45
13.47
6A
638
25
KATTERJAKK
020200
68.42
18.17
8
817
32
Sweden (SWE)
ANGELHOLM
025635
56.30
12.85
5A
742
29
ARJEPLOG
021240
66.05
17.87
7
588
23
ARVIKA
024040
59.67
12.58
6A
702
28
BJUROKLUBB (LGT-H)
022960
64.48
21.58
7
588
23
BLOMSKOG
024080
59.22
12.08
6A
812
32
BORLANGE
024350
60.43
15.52
6A
638
25
EDSBYN
023380
61.37
15.72
7
589
23
FALSTERBO
026160
55.38
12.82
5A
502
20
FARO ISLAND
025880
57.90
19.17
6A
535
21
FLODA
024760
59.05
16.40
6A
575
23
FOLKARNA
024440
60.17
16.32
6A
602
24
FRANSTA
023420
62.50
16.18
7
545
21
GADDEDE
022220
64.50
14.17
7
799
31
GALLIVARE
020490
67.15
20.65
7
526
21
GAVLE
024530
60.72
17.17
6A
632
25
GLADHAMMAR
025760
57.78
16.60
6A
538
21
GOTEBORG
025130
57.72
12.00
5A
813
32
GOTEBORG/LANDVETTER
025260
57.67
12.30
6A
931
37
GOTEBORG/SAVE
025120
57.78
11.88
6A
813
32
GOTSKA SANDON
025840
58.40
19.20
6A
537
21
GUNNARN
021280
65.02
17.68
7
597
24
HAGSHULT
025560
57.30
14.13
6A
769
30
HALLANDS VADERO
026050
56.45
12.55
5A
667
26
HANO
026280
56.02
14.85
5A
577
23
HAPARANDA
021960
65.83
24.15
7
577
23
HARSTENA
025860
58.25
17.02
6A
664
26
HELSINGBORG
026110
56.03
12.77
5A
729
29
HOBURG
026800
56.92
18.15
5A
507
20
HOLMOGADD
022880
63.60
20.75
7
572
23
IDVATTNET
022520
64.45
17.08
7
605
24
JOKKMOKK (SWE-AFB)
021420
66.63
19.65
8
501
20
JONKOPING/AXAMO
025500
57.75
14.08
6A
690
27
JUNSELE
022440
63.68
16.95
7
575
23
KALMAR
026700
56.68
16.30
5A
501
20
KALMAR
026720
56.73
16.30
6A
501
20
KARESUANDO
020800
68.45
22.45
8
456
18
KARLSBORG(SAFB)
025440
58.52
14.53
6A
582
23
KARLSTAD FLYGPLATS
024180
59.45
13.47
6A
638
25
KATTERJAKK
020200
68.42
18.17
8
817
32

454 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 457

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
UPPSALA
024580
59.90
17.60
6A
570
22
VASTERAS/HASSLO AFB
024460
59.58
16.63
6A
544
21
VIDSEL
021540
65.88
20.15
7
615
24
VILHELMINA
022450
64.58
16.85
7
594
23
VISBY
025900
57.67
18.35
6A
521
21
VUOGGATJALME
021120
66.57
16.35
8
621
24
CHIAYI
467480
23.50
120.45
2A
1793
71
CHIAYI (TW-AFB)
467460
23.47
120.38
2A
1793
71
CHIHHANG (TW-AFB)
467600
22.80
121.18
1A
1943
77
CHILUNG
466940
25.15
121.80
2A
3111
122
CHINMEM/SHATOU(AFB)
467360
24.43
118.37
2A
1110
44
DONGSHA DAO
597920
20.67
116.72
1A
1445
57
HENGCHUN
467520
21.93
120.83
1A
1982
78
HENGCHUN
595590
22.00
120.75
1A
1982
78
HSINCHU (TW-AFB)
467560
24.82
120.93
2A
1697
67
HSINCHU CITY
467570
24.83
120.93
2A
1697
67
HUA-LIEN CITY
466990
23.98
121.60
2A
2129
84
HULIEN AB (=593620)
467630
24.03
121.62
2A
2129
84
ILAN CITY
467080
24.75
121.78
2A
2621
103
KANGSHAN (TW-AFB)
467450
22.78
120.27
1A
1571
62
KAOHSIUNG
467440
22.63
120.28
1A
1619
64
KAOHSIUNG INTL ARPT
467400
22.58
120.35
1A
1619
64
LAN YU
595670
22.03
121.55
2A
1862
73
MAKUNG AB (=593450)
467340
23.58
119.62
2A
951
37
MAZU
588490
26.17
119.93
3A
1242
49
NANSHA DAO
599970
10.38
114.37
0A
1891
74
PENGHU ISLANDS
467350
23.50
119.50
2A
1606
63
PENGJIA YU
589740
25.63
122.07
2A
1657
65
PINGTUNG NORTH(AFB)
467580
22.70
120.48
1A
1619
64
PINGTUNG SOUTH(AFB)
467500
22.68
120.47
1A
1619
64
SUAO MET STATION
467060
24.60
121.85
2A
2621
103
SUNGSHAN/TAIPEI
466960
25.07
121.55
2A
2218
87
TAIBEI
589680
25.03
121.52
2A
2218
87
TAICHUNG (TW-AFB)
467510
24.18
120.65
2A
1603
63
TAIDONG
595620
22.75
121.15
1A
1878
74
TAINAN
593580
23.00
120.22
1A
1585
62
TAINAN (TW-AFB)
467430
22.95
120.20
1A
1585
62
TAIZHONG
591580
24.15
120.68
1A
1603
63
TAOYUAN AB (=589650)
466970
25.07
121.23
2A
1827
72
WU-CHI OBSERVATORY
467770
24.25
120.52
2A
1652
65
WUCHIA OBSERVATORY
467700
24.27
120.62
2A
1464
58
Switzerland (CHE)
AIGLE
067120
46.33
6.92
5A
1324
52
ALTDORF
066720
46.87
8.63
5A
1715
68
CHUR-EMS
067860
46.87
9.53
5A
1123
44
CIMETTA
067590
46.20
8.80
6A
1748
69
COMPROVASCO
067560
46.47
8.93
4A
1568
62
CORVATSCH
067910
46.42
9.82
8
1061
42
DISENTIS
067820
46.70
8.85
6A
1357
53
FAHY
066160
47.43
6.95
5A
1245
49
GENEVE-COINTRIN
067000
46.25
6.13
4A
957
38
GUETSCH
067500
46.65
8.62
7
1613
63
HOERNKI
066890
47.37
8.95
6A
1341
53
INTERLAKEN
067340
46.67
7.87
5A
1304
51
JUNGFRAUJOCH
067300
46.55
7.98
8
1304
51
LA CHAUX-DE-FONDS
066120
47.08
6.80
6A
1301
51
LA DOLE
067020
46.43
6.10
7
1268
50
LAEGERN
066690
47.48
8.40
5A
1116
44
LOCARNO-MAGADINO
067620
46.17
8.88
4A
1748
69
LOCARNO-MONTI
067600
46.17
8.78
4A
1748
69
LUGANO
067700
46.00
8.97
4A
1593
63
MONTANA
067240
46.32
7.48
6A
1097
43
NAPF
066390
47.00
7.93
6A
1332
52
NEUCHATEL
066040
47.00
6.95
5A
978
38
PAYERNE
066100
46.82
6.95
5A
897
35
PIOTTA
067530
46.52
8.68
5A
1613
63
PLAFFEIEN-OBERSCHRO
066280
46.75
7.27
6A
1350
53
ROBBIA
067940
46.35
10.07
6A
1022
40
SAENTIS
066800
47.25
9.35
7
2474
97
SAMEDAM-FLUGPLATZ
067920
46.53
9.88
7
1001
39
SAN BERNARDINO
067830
46.47
9.18
7
1543
61
SION
067200
46.22
7.33
5A
871
34
ST. GALLEN
066810
47.43
9.40
5A
1459
57
STABIO
067710
45.85
8.93
4A
1626
64
WYNAU
066430
47.25
7.78
5A
1273
50
ZUERICH METEOSCHWEI
066600
47.38
8.57
5A
1131
45
ZURICH-KLOTEN
066700
47.48
8.53
5A
1191
47
Switzerland (CHE)
AIGLE
067120
46.33
6.92
5A
1324
52
ALTDORF
066720
46.87
8.63
5A
1715
68
CHUR-EMS
067860
46.87
9.53
5A
1123
44
CIMETTA
067590
46.20
8.80
6A
1748
69
COMPROVASCO
067560
46.47
8.93
4A
1568
62
CORVATSCH
067910
46.42
9.82
8
1061
42
DISENTIS
067820
46.70
8.85
6A
1357
53
FAHY
066160
47.43
6.95
5A
1245
49
GENEVE-COINTRIN
067000
46.25
6.13
4A
957
38
GUETSCH
067500
46.65
8.62
7
1613
63
HOERNKI
066890
47.37
8.95
6A
1341
53
INTERLAKEN
067340
46.67
7.87
5A
1304
51
JUNGFRAUJOCH
067300
46.55
7.98
8
1304
51
LA CHAUX-DE-FONDS
066120
47.08
6.80
6A
1301
51
LA DOLE
067020
46.43
6.10
7
1268
50
LAEGERN
066690
47.48
8.40
5A
1116
44
LOCARNO-MAGADINO
067620
46.17
8.88
4A
1748
69
LOCARNO-MONTI
067600
46.17
8.78
4A
1748
69
LUGANO
067700
46.00
8.97
4A
1593
63
MONTANA
067240
46.32
7.48
6A
1097
43
NAPF
066390
47.00
7.93
6A
1332
52
NEUCHATEL
066040
47.00
6.95
5A
978
38
PAYERNE
066100
46.82
6.95
5A
897
35
PIOTTA
067530
46.52
8.68
5A
1613
63
PLAFFEIEN-OBERSCHRO
066280
46.75
7.27
6A
1350
53
ROBBIA
067940
46.35
10.07
6A
1022
40
SAENTIS
066800
47.25
9.35
7
2474
97
SAMEDAM-FLUGPLATZ
067920
46.53
9.88
7
1001
39
SAN BERNARDINO
067830
46.47
9.18
7
1543
61
SION
067200
46.22
7.33
5A
871
34
ST. GALLEN
066810
47.43
9.40
5A
1459
57
STABIO
067710
45.85
8.93
4A
1626
64
WYNAU
066430
47.25
7.78
5A
1273
50
ZUERICH METEOSCHWEI
066600
47.38
8.57
5A
1131
45
ZURICH-KLOTEN
066700
47.48
8.53
5A
1191
47
Switzerland (CHE)
AIGLE
067120
46.33
6.92
5A
1324
52
ALTDORF
066720
46.87
8.63
5A
1715
68
CHUR-EMS
067860
46.87
9.53
5A
1123
44
CIMETTA
067590
46.20
8.80
6A
1748
69
COMPROVASCO
067560
46.47
8.93
4A
1568
62
CORVATSCH
067910
46.42
9.82
8
1061
42
DISENTIS
067820
46.70
8.85
6A
1357
53
FAHY
066160
47.43
6.95
5A
1245
49
GENEVE-COINTRIN
067000
46.25
6.13
4A
957
38
GUETSCH
067500
46.65
8.62
7
1613
63
HOERNKI
066890
47.37
8.95
6A
1341
53
INTERLAKEN
067340
46.67
7.87
5A
1304
51
JUNGFRAUJOCH
067300
46.55
7.98
8
1304
51
LA CHAUX-DE-FONDS
066120
47.08
6.80
6A
1301
51
LA DOLE
067020
46.43
6.10
7
1268
50
LAEGERN
066690
47.48
8.40
5A
1116
44
LOCARNO-MAGADINO
067620
46.17
8.88
4A
1748
69
LOCARNO-MONTI
067600
46.17
8.78
4A
1748
69
LUGANO
067700
46.00
8.97
4A
1593
63
MONTANA
067240
46.32
7.48
6A
1097
43
NAPF
066390
47.00
7.93
6A
1332
52
NEUCHATEL
066040
47.00
6.95
5A
978
38
PAYERNE
066100
46.82
6.95
5A
897
35
PIOTTA
067530
46.52
8.68
5A
1613
63
PLAFFEIEN-OBERSCHRO
066280
46.75
7.27
6A
1350
53
ROBBIA
067940
46.35
10.07
6A
1022
40
SAENTIS
066800
47.25
9.35
7
2474
97
SAMEDAM-FLUGPLATZ
067920
46.53
9.88
7
1001
39
SAN BERNARDINO
067830
46.47
9.18
7
1543
61
SION
067200
46.22
7.33
5A
871
34
ST. GALLEN
066810
47.43
9.40
5A
1459
57
STABIO
067710
45.85
8.93
4A
1626
64
WYNAU
066430
47.25
7.78
5A
1273
50
ZUERICH METEOSCHWEI
066600
47.38
8.57
5A
1131
45
ZURICH-KLOTEN
066700
47.48
8.53
5A
1191
47
Tajikistan (TJK)
DUSHANBE
388360
38.55
68.78
3A
671
26
KHOROG
389540
37.50
71.50
5B
239
9
KHUDJAND
385990
40.22
69.73
4B
162
6
Switzerland (CHE)
AIGLE
067120
46.33
6.92
5A
1324
52
ALTDORF
066720
46.87
8.63
5A
1715
68
CHUR-EMS
067860
46.87
9.53
5A
1123
44
CIMETTA
067590
46.20
8.80
6A
1748
69
COMPROVASCO
067560
46.47
8.93
4A
1568
62
CORVATSCH
067910
46.42
9.82
8
1061
42
DISENTIS
067820
46.70
8.85
6A
1357
53
FAHY
066160
47.43
6.95
5A
1245
49
GENEVE-COINTRIN
067000
46.25
6.13
4A
957
38
GUETSCH
067500
46.65
8.62
7
1613
63
HOERNKI
066890
47.37
8.95
6A
1341
53
INTERLAKEN
067340
46.67
7.87
5A
1304
51
JUNGFRAUJOCH
067300
46.55
7.98
8
1304
51
LA CHAUX-DE-FONDS
066120
47.08
6.80
6A
1301
51
LA DOLE
067020
46.43
6.10
7
1268
50
LAEGERN
066690
47.48
8.40
5A
1116
44
LOCARNO-MAGADINO
067620
46.17
8.88
4A
1748
69
LOCARNO-MONTI
067600
46.17
8.78
4A
1748
69
LUGANO
067700
46.00
8.97
4A
1593
63
MONTANA
067240
46.32
7.48
6A
1097
43
NAPF
066390
47.00
7.93
6A
1332
52
NEUCHATEL
066040
47.00
6.95
5A
978
38
PAYERNE
066100
46.82
6.95
5A
897
35
PIOTTA
067530
46.52
8.68
5A
1613
63
PLAFFEIEN-OBERSCHRO
066280
46.75
7.27
6A
1350
53
ROBBIA
067940
46.35
10.07
6A
1022
40
SAENTIS
066800
47.25
9.35
7
2474
97
SAMEDAM-FLUGPLATZ
067920
46.53
9.88
7
1001
39
SAN BERNARDINO
067830
46.47
9.18
7
1543
61
SION
067200
46.22
7.33
5A
871
34
ST. GALLEN
066810
47.43
9.40
5A
1459
57
STABIO
067710
45.85
8.93
4A
1626
64
WYNAU
066430
47.25
7.78
5A
1273
50
ZUERICH METEOSCHWEI
066600
47.38
8.57
5A
1131
45
ZURICH-KLOTEN
066700
47.48
8.53
5A
1191
47
Tanzania, United Republic of (TZA)
DAR ES SALAAM AIRPO
638940
–6.87
39.20
1A
1125
44
Switzerland (CHE)
AIGLE
067120
46.33
6.92
5A
1324
52
ALTDORF
066720
46.87
8.63
5A
1715
68
CHUR-EMS
067860
46.87
9.53
5A
1123
44
CIMETTA
067590
46.20
8.80
6A
1748
69
COMPROVASCO
067560
46.47
8.93
4A
1568
62
CORVATSCH
067910
46.42
9.82
8
1061
42
DISENTIS
067820
46.70
8.85
6A
1357
53
FAHY
066160
47.43
6.95
5A
1245
49
GENEVE-COINTRIN
067000
46.25
6.13
4A
957
38
GUETSCH
067500
46.65
8.62
7
1613
63
HOERNKI
066890
47.37
8.95
6A
1341
53
INTERLAKEN
067340
46.67
7.87
5A
1304
51
JUNGFRAUJOCH
067300
46.55
7.98
8
1304
51
LA CHAUX-DE-FONDS
066120
47.08
6.80
6A
1301
51
LA DOLE
067020
46.43
6.10
7
1268
50
LAEGERN
066690
47.48
8.40
5A
1116
44
LOCARNO-MAGADINO
067620
46.17
8.88
4A
1748
69
LOCARNO-MONTI
067600
46.17
8.78
4A
1748
69
LUGANO
067700
46.00
8.97
4A
1593
63
MONTANA
067240
46.32
7.48
6A
1097
43
NAPF
066390
47.00
7.93
6A
1332
52
NEUCHATEL
066040
47.00
6.95
5A
978
38
PAYERNE
066100
46.82
6.95
5A
897
35
PIOTTA
067530
46.52
8.68
5A
1613
63
PLAFFEIEN-OBERSCHRO
066280
46.75
7.27
6A
1350
53
ROBBIA
067940
46.35
10.07
6A
1022
40
SAENTIS
066800
47.25
9.35
7
2474
97
SAMEDAM-FLUGPLATZ
067920
46.53
9.88
7
1001
39
SAN BERNARDINO
067830
46.47
9.18
7
1543
61
SION
067200
46.22
7.33
5A
871
34
ST. GALLEN
066810
47.43
9.40
5A
1459
57
STABIO
067710
45.85
8.93
4A
1626
64
WYNAU
066430
47.25
7.78
5A
1273
50
ZUERICH METEOSCHWEI
066600
47.38
8.57
5A
1131
45
ZURICH-KLOTEN
066700
47.48
8.53
5A
1191
47
Thailand (THA)
ARANYAPRATHET
484620
13.70
102.58
0A
1426
56
BANGKOK METROPOLIS
484550
13.73
100.57
0A
1500
59
BHUMIBOL DAM
483770
17.25
99.02
0A
1061
42
BUA CHUM
484180
15.27
101.18
0A
1131
45
CHAIYAPHUM
484030
15.80
102.03
0A
1207
48
CHANTHABURI
484800
12.60
102.12
0A
2902
114
CHIANG MAI
483270
18.78
98.98
1A
1183
47
CHIANG RAI
483030
19.97
99.88
1A
1671
66
CHON BURI
484590
13.37
100.98
0A
1323
52
CHUMPHON
485170
10.48
99.18
0A
2354
93
DON MUANG
484560
13.92
100.60
0A
1438
57
HAT YAI
485690
6.92
100.43
0A
1779
70
Syria (SYR)
ALEPPO INT. AEROPOR
400070
36.18
37.20
3B
326
13
DAMASCUS INT. AIRPO
400800
33.42
36.52
3B
172
7
DARAA
400950
32.60
36.10
3B
268
11
DEIR EZZOR
400450
35.32
40.15
2B
154
6
HAMA
400300
35.12
36.75
3A
373
15
LATTAKIA
400220
35.53
35.77
3A
769
30
NABK
400830
34.03
36.72
4A
279
11
PALMYRA
400610
34.55
38.30
2B
131
5
SAFITA
400660
34.82
36.13
3A
977
38
Syria (SYR)
ALEPPO INT. AEROPOR
400070
36.18
37.20
3B
326
13
DAMASCUS INT. AIRPO
400800
33.42
36.52
3B
172
7
DARAA
400950
32.60
36.10
3B
268
11
DEIR EZZOR
400450
35.32
40.15
2B
154
6
HAMA
400300
35.12
36.75
3A
373
15
LATTAKIA
400220
35.53
35.77
3A
769
30
NABK
400830
34.03
36.72
4A
279
11
PALMYRA
400610
34.55
38.30
2B
131
5
SAFITA
400660
34.82
36.13
3A
977
38
Taiwan, Province of China (TWN)
CHIANG KAI SHEK
466860
25.08
121.22
2A
1827
72
Taiwan, Province of China (TWN)
CHIANG KAI SHEK
466860
25.08
121.22
2A
1827
72

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 455

PDF Page 458

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
HUA HIN
484750
12.58
99.95
0A
1002
39
KAM PAENG PHET
483800
16.48
99.53
0A
1277
50
KANCHANABURI
484500
14.02
99.53
0A
1095
43
KHLONG YAI
485010
11.77
102.88
0A
4583
180
KHON KAEN
483810
16.43
102.83
0A
1167
46
KO LANTA
485660
7.53
99.05
0A
2181
86
KO SAMUI
485500
9.47
100.05
0A
1954
77
KO SICHANG
484600
13.17
100.80
0A
1218
48
LAMPANG
483280
18.28
99.52
0A
1132
45
LAMPHUN
483290
18.57
99.03
0A
1062
42
LOEI
483530
17.45
101.73
1A
1218
48
LOP BURI
484260
14.80
100.62
0A
1239
49
MAE HONG SON
483000
19.30
97.83
0A
1313
52
MAE SARIANG
483250
18.17
97.93
0A
1282
50
MAE SOT
483750
16.67
98.55
1A
1584
62
MUKDAHAN
483830
16.53
104.72
0A
1564
62
NAKHON PHANOM
483570
17.42
104.78
0A
2422
95
NAKHON RATCHASIMA
484310
14.97
102.08
0A
1055
42
NAKHON SAWAN
484000
15.80
100.17
0A
1140
45
NAKHON SI THAMMARAT
485520
8.53
99.95
0A
2520
99
NAN
483310
18.77
100.77
0A
1307
51
NARATHIWAT
485830
6.42
101.82
0A
2713
107
NONG KHAI
483520
17.87
102.72
0A
1670
66
PATTANI
485800
6.78
101.15
0A
1873
74
PHATTHAYA
484610
12.92
100.87
0A
1225
48
PHAYAO
483100
19.13
99.90
1A
1127
44
PHETCHABUN
483790
16.43
101.15
0A
1149
45
PHETCHABURI
484650
13.15
100.07
0A
1002
39
PHITSANULOK
483780
16.78
100.27
0A
1345
53
PHRAE
483300
18.17
100.17
0A
1141
45
PHUKET
485640
7.88
98.40
0A
2350
93
PHUKET AIRPORT
485650
8.13
98.32
0A
2656
105
PRACHIN BURI
484300
14.05
101.37
0A
2063
81
PRACHUAP KHIRIKHAN
485000
11.82
99.82
0A
1142
45
RANONG
485320
9.98
98.62
0A
4304
169
RAYONG
484780
12.63
101.35
0A
1433
56
ROI ET
484050
16.05
103.68
0A
1461
58
SAKON NAKHON
483560
17.15
104.13
0A
1615
64
SATTAHIP
484770
12.68
100.98
0A
1274
50
SONGKHLA
485680
7.20
100.62
0A
2116
83
SUPHAN BURI
484250
14.47
100.13
0A
1238
49
SURAT THANI
485510
9.12
99.15
0A
1801
71
SURIN
484320
14.88
103.50
0A
1289
51
TAK
483760
16.88
99.15
0A
1081
43
THA TUM
484160
15.32
103.68
0A
1382
54
THONG PHA PHUM
484210
14.75
98.63
0A
2273
89
TRANG
485670
7.52
99.62
0A
2274
90
UBON RATCHATHANI
484070
15.25
104.87
0A
1644
65
UDON THANI
483540
17.38
102.80
0A
1481
58
UTTARADIT
483510
17.62
100.10
0A
1481
58
Trinidad and Tobago (TTO)
CROWN POINT AIRPORT
789620
11.15
–60.83
0A
1452
57
PIARCO INT. AIRPORT
789700
10.62
–61.35
0A
1781
70
HUA HIN
484750
12.58
99.95
0A
1002
39
KAM PAENG PHET
483800
16.48
99.53
0A
1277
50
KANCHANABURI
484500
14.02
99.53
0A
1095
43
KHLONG YAI
485010
11.77
102.88
0A
4583
180
KHON KAEN
483810
16.43
102.83
0A
1167
46
KO LANTA
485660
7.53
99.05
0A
2181
86
KO SAMUI
485500
9.47
100.05
0A
1954
77
KO SICHANG
484600
13.17
100.80
0A
1218
48
LAMPANG
483280
18.28
99.52
0A
1132
45
LAMPHUN
483290
18.57
99.03
0A
1062
42
LOEI
483530
17.45
101.73
1A
1218
48
LOP BURI
484260
14.80
100.62
0A
1239
49
MAE HONG SON
483000
19.30
97.83
0A
1313
52
MAE SARIANG
483250
18.17
97.93
0A
1282
50
MAE SOT
483750
16.67
98.55
1A
1584
62
MUKDAHAN
483830
16.53
104.72
0A
1564
62
NAKHON PHANOM
483570
17.42
104.78
0A
2422
95
NAKHON RATCHASIMA
484310
14.97
102.08
0A
1055
42
NAKHON SAWAN
484000
15.80
100.17
0A
1140
45
NAKHON SI THAMMARAT
485520
8.53
99.95
0A
2520
99
NAN
483310
18.77
100.77
0A
1307
51
NARATHIWAT
485830
6.42
101.82
0A
2713
107
NONG KHAI
483520
17.87
102.72
0A
1670
66
PATTANI
485800
6.78
101.15
0A
1873
74
PHATTHAYA
484610
12.92
100.87
0A
1225
48
PHAYAO
483100
19.13
99.90
1A
1127
44
PHETCHABUN
483790
16.43
101.15
0A
1149
45
PHETCHABURI
484650
13.15
100.07
0A
1002
39
PHITSANULOK
483780
16.78
100.27
0A
1345
53
PHRAE
483300
18.17
100.17
0A
1141
45
PHUKET
485640
7.88
98.40
0A
2350
93
PHUKET AIRPORT
485650
8.13
98.32
0A
2656
105
PRACHIN BURI
484300
14.05
101.37
0A
2063
81
PRACHUAP KHIRIKHAN
485000
11.82
99.82
0A
1142
45
RANONG
485320
9.98
98.62
0A
4304
169
RAYONG
484780
12.63
101.35
0A
1433
56
ROI ET
484050
16.05
103.68
0A
1461
58
SAKON NAKHON
483560
17.15
104.13
0A
1615
64
SATTAHIP
484770
12.68
100.98
0A
1274
50
SONGKHLA
485680
7.20
100.62
0A
2116
83
SUPHAN BURI
484250
14.47
100.13
0A
1238
49
SURAT THANI
485510
9.12
99.15
0A
1801
71
SURIN
484320
14.88
103.50
0A
1289
51
TAK
483760
16.88
99.15
0A
1081
43
THA TUM
484160
15.32
103.68
0A
1382
54
THONG PHA PHUM
484210
14.75
98.63
0A
2273
89
TRANG
485670
7.52
99.62
0A
2274
90
UBON RATCHATHANI
484070
15.25
104.87
0A
1644
65
UDON THANI
483540
17.38
102.80
0A
1481
58
UTTARADIT
483510
17.62
100.10
0A
1481
58
Tunisia (TUN)
BIZERTE
607140
37.25
9.80
3A
612
24
DJERBA MELLITA
607690
33.87
10.77
2B
232
9
GABES
607650
33.88
10.10
2B
203
8
GAFSA
607450
34.42
8.82
2B
163
6
HABIB BOURGUIBA INT
607403
35.75
10.75
2B
375
15
JENDOUBA
607250
36.48
8.80
3B
466
18
KAIROUAN
607350
35.67
10.10
2B
289
11
KELIBIA
607200
36.85
11.08
3A
534
21
MONASTIR-SKANES
607400
35.67
10.75
2B
375
15
SFAX EL-MAOU
607500
34.72
10.68
2B
225
9
TABARKA
607100
36.95
8.75
3A
1007
40
THALA
607380
35.55
8.68
3B
420
17
TOZEUR
607600
33.92
8.17
2B
99
4
TUNIS-CARTHAGE
607150
36.83
10.23
3A
466
18
HUA HIN
484750
12.58
99.95
0A
1002
39
KAM PAENG PHET
483800
16.48
99.53
0A
1277
50
KANCHANABURI
484500
14.02
99.53
0A
1095
43
KHLONG YAI
485010
11.77
102.88
0A
4583
180
KHON KAEN
483810
16.43
102.83
0A
1167
46
KO LANTA
485660
7.53
99.05
0A
2181
86
KO SAMUI
485500
9.47
100.05
0A
1954
77
KO SICHANG
484600
13.17
100.80
0A
1218
48
LAMPANG
483280
18.28
99.52
0A
1132
45
LAMPHUN
483290
18.57
99.03
0A
1062
42
LOEI
483530
17.45
101.73
1A
1218
48
LOP BURI
484260
14.80
100.62
0A
1239
49
MAE HONG SON
483000
19.30
97.83
0A
1313
52
MAE SARIANG
483250
18.17
97.93
0A
1282
50
MAE SOT
483750
16.67
98.55
1A
1584
62
MUKDAHAN
483830
16.53
104.72
0A
1564
62
NAKHON PHANOM
483570
17.42
104.78
0A
2422
95
NAKHON RATCHASIMA
484310
14.97
102.08
0A
1055
42
NAKHON SAWAN
484000
15.80
100.17
0A
1140
45
NAKHON SI THAMMARAT
485520
8.53
99.95
0A
2520
99
NAN
483310
18.77
100.77
0A
1307
51
NARATHIWAT
485830
6.42
101.82
0A
2713
107
NONG KHAI
483520
17.87
102.72
0A
1670
66
PATTANI
485800
6.78
101.15
0A
1873
74
PHATTHAYA
484610
12.92
100.87
0A
1225
48
PHAYAO
483100
19.13
99.90
1A
1127
44
PHETCHABUN
483790
16.43
101.15
0A
1149
45
PHETCHABURI
484650
13.15
100.07
0A
1002
39
PHITSANULOK
483780
16.78
100.27
0A
1345
53
PHRAE
483300
18.17
100.17
0A
1141
45
PHUKET
485640
7.88
98.40
0A
2350
93
PHUKET AIRPORT
485650
8.13
98.32
0A
2656
105
PRACHIN BURI
484300
14.05
101.37
0A
2063
81
PRACHUAP KHIRIKHAN
485000
11.82
99.82
0A
1142
45
RANONG
485320
9.98
98.62
0A
4304
169
RAYONG
484780
12.63
101.35
0A
1433
56
ROI ET
484050
16.05
103.68
0A
1461
58
SAKON NAKHON
483560
17.15
104.13
0A
1615
64
SATTAHIP
484770
12.68
100.98
0A
1274
50
SONGKHLA
485680
7.20
100.62
0A
2116
83
SUPHAN BURI
484250
14.47
100.13
0A
1238
49
SURAT THANI
485510
9.12
99.15
0A
1801
71
SURIN
484320
14.88
103.50
0A
1289
51
TAK
483760
16.88
99.15
0A
1081
43
THA TUM
484160
15.32
103.68
0A
1382
54
THONG PHA PHUM
484210
14.75
98.63
0A
2273
89
TRANG
485670
7.52
99.62
0A
2274
90
UBON RATCHATHANI
484070
15.25
104.87
0A
1644
65
UDON THANI
483540
17.38
102.80
0A
1481
58
UTTARADIT
483510
17.62
100.10
0A
1481
58
Turkey (TUR)
ADANA
173520
36.98
35.30
2A
696
27
ADANA/INCIRLIK AB
691464
37.00
35.43
3A
696
27
ADANA/INCIRLIK AFB
173500
37.00
35.42
3A
696
27
AFYON
171900
38.75
30.53
4C
413
16
AKHISAR
171840
38.92
27.85
3A
587
23
ANTALYA
173000
36.87
30.73
3A
1091
43
AYDIN
172340
37.85
27.85
3A
585
23
BALIKESIR
171500
39.62
27.92
4A
554
22
BANDIRMA
171150
40.32
27.97
4A
725
29
BODRUM
172900
37.03
27.43
2A
698
27
BOLU
170700
40.73
31.60
4A
551
22
BURSA
171160
40.18
29.07
3A
682
27
CANAKKALE
171120
40.13
26.40
3A
619
24
CORUM
170840
40.55
34.95
5C
437
17
DALAMAN
172950
36.70
28.78
3A
868
34
DIKILI
171800
39.07
26.88
3A
645
25
DIYARBAKIR
172800
37.88
40.18
4A
480
19
EDIRNE
170500
41.67
26.57
4A
590
23
ELAZIG
172020
38.60
39.28
4A
503
20
ERZINCAN
170920
39.70
39.52
5A
386
15
ERZURUM
170960
39.95
41.17
7
407
16
ESENBOGA
171280
40.12
33.00
5C
421
17
ESKISEHIR
171240
39.78
30.57
4A
390
15
ETIMESGUT
171290
39.95
32.68
4A
375
15
GAZIANTEP
172600
37.08
37.37
3A
583
23
GOKCEADA
171100
40.18
25.90
3A
733
29
GOLCUK/DUMLUPINAR
170670
40.67
29.83
3A
738
29
INEBOLU
170240
41.98
33.78
4A
1007
40
ISKENDERUN
173700
36.58
36.17
2A
766
30
ISPARTA
172400
37.75
30.55
4A
537
21
ISTANBUL/ATATURK
170600
40.97
28.82
3A
640
25
IZMIR/A. MENDERES
172190
38.27
27.15
3A
692
27
IZMIR/CIGLI
172180
38.52
27.02
3A
672
26
KAYSERI/ERKILET
171950
38.82
35.43
5C
384
15
KONYA
172440
37.97
32.55
4B
322
13
MALATYA/ERHAC
172000
38.43
38.08
4A
407
16
Togo (TGO)
LOME
653870
6.17
1.25
0A
856
34
Togo (TGO)
LOME
653870
6.17
1.25
0A
856
34
Tonga (TON)
FUAAMOTU
917920
–21.23
–175.15
1A
1732
68
HAAPAI
917840
–19.80
–174.35
1A
1680
66
Tonga (TON)
FUAAMOTU
917920
–21.23
–175.15
1A
1732
68
HAAPAI
917840
–19.80
–174.35
1A
1680
66

456 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 459

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
MERZIFON
170820
40.85
35.58
4C
406
16
MUGLA
172920
37.22
28.37
3A
1168
46
SAMSUN
170300
41.28
36.30
3A
698
27
SILIFKE
173300
36.38
33.93
2A
564
22
SINOP
170260
42.03
35.17
3A
651
26
SIVAS
170900
39.75
37.02
5A
431
17
TEKIRDAG
170560
40.98
27.55
4A
566
22
TRABZON
170380
41.00
39.72
3A
771
30
USAK
171880
38.68
29.40
4A
515
20
VAN
171700
38.45
43.32
5C
387
15
ZONGULDAK
170220
41.45
31.80
4A
1202
47
LUHANSK
345230
48.57
39.25
5A
474
19
LVIV
333930
49.82
23.95
5A
741
29
MARIUPOL
347120
47.03
37.50
5A
527
21
MOHYLIV-PODILSKYI
336630
48.45
27.78
5A
612
24
MYRONIVKA
334660
49.67
31.00
5A
565
22
NIZHYN
332460
51.05
31.90
6A
607
24
NOVA KAKHOVKA
338690
46.78
33.37
5A
439
17
ODESA
338370
46.43
30.77
5A
446
18
POLTAVA
335060
49.60
34.55
5A
566
22
RIVNE
333010
50.58
26.13
6A
589
23
SARNY
330880
51.28
26.62
5A
633
25
SHEPETIVKA
333170
50.17
27.03
6A
712
28
SIMFEROPOL
339460
45.02
33.98
5A
498
20
SUMY
332750
50.85
34.67
6A
603
24
SVITLOVODSK
336140
49.05
33.25
5A
552
22
TERNOPIL
334150
49.53
25.67
6A
610
24
UMAN
335870
48.77
30.23
5A
630
25
UZHHOROD
336310
48.63
22.27
5A
729
29
VINNYTSIA
335620
49.23
28.60
6A
632
25
VOLODYMYR-VOLYNSKYI
331770
50.83
24.32
5A
620
24
VOZNESENSK
337770
47.57
31.33
5A
506
20
YALTA
339900
44.48
34.17
4A
603
24
ZAPORIZHZHIA
346010
47.80
35.02
5A
504
20
ZHYTOMYR
333250
50.23
28.73
6A
607
24
Turkmenistan (TKM)
ASHGABAT KESHI
388800
37.92
58.33
3B
236
9
BAJRAMALY
388950
37.60
62.18
3B
178
7
BAKHERDEN
387740
38.43
57.42
3B
238
9
BYRDALYK
388060
38.47
64.37
3B
175
7
CARSANGA
389150
37.52
66.02
2B
197
8
CHARDZHEV
386870
39.08
63.60
4B
129
5
DASHKHOVUZ
383920
41.75
59.82
4B
102
4
EKEZHE
383880
41.03
57.77
4B
128
5
ERBENT
386560
39.32
58.60
4B
106
4
ESENGYLY
387500
37.47
53.97
3B
207
8
GAZANDZHYK
386470
39.25
55.52
3B
171
7
GYSHGY
389870
35.28
62.35
3B
292
11
GYZYLARBAT
387630
38.98
56.28
4B
203
8
KERKI
389110
37.83
65.20
3B
181
7
SARAGT
389740
36.53
61.22
3B
203
8
TEDZHEN
388860
37.38
60.52
3B
169
7
TURKMENBASHI
385070
40.05
53.00
4B
137
5
UCHADZHY
387990
38.08
62.80
3B
143
6
Turkmenistan (TKM)
ASHGABAT KESHI
388800
37.92
58.33
3B
236
9
BAJRAMALY
388950
37.60
62.18
3B
178
7
BAKHERDEN
387740
38.43
57.42
3B
238
9
BYRDALYK
388060
38.47
64.37
3B
175
7
CARSANGA
389150
37.52
66.02
2B
197
8
CHARDZHEV
386870
39.08
63.60
4B
129
5
DASHKHOVUZ
383920
41.75
59.82
4B
102
4
EKEZHE
383880
41.03
57.77
4B
128
5
ERBENT
386560
39.32
58.60
4B
106
4
ESENGYLY
387500
37.47
53.97
3B
207
8
GAZANDZHYK
386470
39.25
55.52
3B
171
7
GYSHGY
389870
35.28
62.35
3B
292
11
GYZYLARBAT
387630
38.98
56.28
4B
203
8
KERKI
389110
37.83
65.20
3B
181
7
SARAGT
389740
36.53
61.22
3B
203
8
TEDZHEN
388860
37.38
60.52
3B
169
7
TURKMENBASHI
385070
40.05
53.00
4B
137
5
UCHADZHY
387990
38.08
62.80
3B
143
6
Turkmenistan (TKM)
ASHGABAT KESHI
388800
37.92
58.33
3B
236
9
BAJRAMALY
388950
37.60
62.18
3B
178
7
BAKHERDEN
387740
38.43
57.42
3B
238
9
BYRDALYK
388060
38.47
64.37
3B
175
7
CARSANGA
389150
37.52
66.02
2B
197
8
CHARDZHEV
386870
39.08
63.60
4B
129
5
DASHKHOVUZ
383920
41.75
59.82
4B
102
4
EKEZHE
383880
41.03
57.77
4B
128
5
ERBENT
386560
39.32
58.60
4B
106
4
ESENGYLY
387500
37.47
53.97
3B
207
8
GAZANDZHYK
386470
39.25
55.52
3B
171
7
GYSHGY
389870
35.28
62.35
3B
292
11
GYZYLARBAT
387630
38.98
56.28
4B
203
8
KERKI
389110
37.83
65.20
3B
181
7
SARAGT
389740
36.53
61.22
3B
203
8
TEDZHEN
388860
37.38
60.52
3B
169
7
TURKMENBASHI
385070
40.05
53.00
4B
137
5
UCHADZHY
387990
38.08
62.80
3B
143
6
United Arab Emirates (ARE)
ABU DHABI BATEEN AI
412160
24.43
54.47
0B
72
3
ABU DHABI INTER. AI
412170
24.43
54.65
0B
68
3
AL AIN INTERNATIONA
412180
24.27
55.60
0B
73
3
DUBAI INTERNATIONAL
411940
25.25
55.33
0B
117
5
FUJAIRAH
411980
25.10
56.33
0B
90
4
RAS AL KHAIMAH INTE
411840
25.62
55.93
0B
128
5
SHARJAH INTER. AIRP
411960
25.33
55.52
0B
84
3
Tuvalu (TUV)
FUNAFUTI NF
916430
–8.53
179.22
0A
3467
136
Tuvalu (TUV)
FUNAFUTI NF
916430
–8.53
179.22
0A
3467
136
Ukraine (UKR)
BORYSPIL
333470
50.33
30.97
6A
551
22
CHERNIHIV
331350
51.47
31.25
6A
596
23
CHERNIVTSI
336580
48.37
25.90
5A
641
25
CHORNOMORSKE
339240
45.52
32.70
4A
399
16
DNIPROPETROVSK
345040
48.37
35.08
5A
509
20
DONETSK
345190
48.07
37.77
5A
533
21
HENICHESK
339100
46.17
34.82
5A
391
15
IVANO-FRANKIVSK
335260
48.97
24.70
5A
716
28
IZIUM
344150
49.18
37.30
5A
553
22
IZMAIL
338890
45.37
28.85
5A
478
19
KERCH
339830
45.40
36.42
5A
440
17
KHARKIV
343000
49.97
36.13
6A
533
21
KHERSON
339020
46.63
32.57
5A
433
17
KHMELNYTSKYI
334290
49.43
26.98
6A
664
26
KIROVOHRAD
337110
48.52
32.20
5A
499
20
KONOTOP
332610
51.23
33.20
6A
609
24
KRYVYI RIH
337910
48.03
33.22
5A
484
19
KYIV
333450
50.40
30.57
5A
633
25
LIUBASHIVKA
337610
47.85
30.27
5A
548
22
LUBNY
333770
50.00
33.02
6A
625
25
United Kingdom (GBR)
ABERDARON
034050
52.78
–4.73
4A
1296
51
ABERDEEN/DYCE AIRPO
030910
57.20
–2.22
5A
813
32
ABERPORTH
035020
52.13
–4.57
5A
1224
48
ABOYNE
030800
57.08
–2.83
5A
901
35
ALCONBURY RAF
035620
52.37
–0.22
5A
537
21
ALTNAHARRA NO2
030440
58.28
–4.43
5A
1243
49
ANDREWSFIELD
036840
51.88
0.45
4A
575
23
AONACH MOR
030410
56.82
–4.97
7
1758
69
AUGHTON
033220
53.55
–2.92
5A
881
35
AULTBEA NO2
030340
57.87
–5.63
5A
1635
64
AVIEMORE
030630
57.20
–3.83
6A
1019
40
BALLYKELLY
039080
55.07
–7.02
5A
1099
43
BALLYPATRICK FOREST
039160
55.18
–6.17
5A
1269
50
BALTASOUND NO.2
030020
60.75
–0.85
5A
1210
48
BANGOR HARBOUR
039270
54.67
–5.67
4A
892
35
BARRA
030350
57.03
–7.45
5A
1358
53
BEDFORD
035600
52.22
–0.48
5A
569
22
BELFAST/ALDERGROVE
039170
54.65
–6.22
5A
851
34
BENBECULA ISLAND
030220
57.47
–7.37
5A
1358
53
BENSON
036580
51.62
–1.08
5A
655
26

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 457

PDF Page 460

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
BINGLEY NO.2
033440
53.82
–1.87
5A
992
39
BIRMINGHAM AIRPORT
035340
52.45
–1.73
5A
672
26
BLACKPOOL AIRPORT
033180
53.77
–3.03
5A
977
38
BOSCOMBE DOWN
037460
51.17
–1.75
5A
713
28
BOULMER
032400
55.42
–1.60
5A
687
27
BOURNEMOUTH/HURN
038620
50.78
–1.83
4A
808
32
BRACKNELL/BEAUFORT
037630
51.38
–0.78
4A
684
27
BRAWDY(RAF)
036030
51.88
–5.12
5A
1112
44
BRIDLINGTON MRSC
032920
54.10
–0.17
5A
754
30
BRISTOL
037243
51.38
–2.72
5A
922
36
BRISTOL WEA CENTER
037260
51.47
–2.60
4A
894
35
BRIZE NORTON
036490
51.75
–1.58
5A
737
29
BUTT OF LEWIS (LH)
030250
58.52
–6.27
5A
1203
47
CAMBORNE
038080
50.22
–5.32
4A
1116
44
CAPE WRATH (LGT-H)
030490
58.63
–5.00
5A
1434
56
CAPEL CURIG
033050
53.10
–3.93
5A
1539
61
CARDIFF WEATHER CEN
037170
51.48
–3.18
4A
1073
42
CARDIFF-WALES ARPT
037150
51.40
–3.35
4A
947
37
CARDINHAM
038230
50.50
–4.67
5A
1304
51
CARLISLE
032200
54.93
–2.97
5A
776
31
CELLARHEAD
033380
53.03
–2.08
5A
955
38
CHARTERHALL
031580
55.70
–2.38
5A
783
31
CHIVENOR
037070
51.08
–4.15
4A
989
39
CHURCH LAWFORD
035440
52.37
–1.33
5A
674
27
CILFYNYDD
036140
51.63
–3.30
5A
1329
52
COLLAFIRTH HILL
030040
60.53
–1.38
6A
1076
42
COLTISHALL
034950
52.77
1.35
5A
630
25
CONINGSBY
033910
53.08
–0.17
5A
626
25
CORSEWALL PT. (LH)
031180
55.00
–5.15
5A
1183
47
COTTESMORE
034530
52.73
–0.65
5A
607
24
CRANWELL
033790
53.03
–0.50
5A
583
23
CROSBY
033160
53.50
–3.07
4A
773
30
CULDROSE
038090
50.08
–5.25
4A
1086
43
DISFORTH AIRFIELD
032610
54.13
–1.42
5A
647
25
DONNA NOOK NO.2
033850
53.48
0.08
5A
681
27
DRUMALBIN
031550
55.62
–3.73
5A
1104
43
DUMFRIES/DRUNGANS
031540
55.05
–3.65
5A
1050
41
DUNDRENNAN
031530
54.80
–4.00
5A
1215
48
DUNKESWELL AERODROM
038400
50.87
–3.23
5A
936
37
EAST MIDLANDS
034185
52.83
–1.32
5A
622
24
EDINBURGH AIRPORT
031600
55.95
–3.35
5A
661
26
EMLEY MOOR
033450
53.62
–1.67
5A
784
31
ESKDALEMUIR
031620
55.32
–3.20
6A
1606
63
EXETER AIRPORT
038390
50.73
–3.42
4A
811
32
FAIR ISLE
030080
59.53
–1.63
5A
1124
44
FAIRFORD RAF
036440
51.68
–1.78
5A
748
29
FARNBOROUGH
037680
51.28
–0.77
4A
684
27
FIFE NESS
031740
56.30
–2.58
5A
660
26
FINNINGLEY(RAF)
033600
53.48
–1.00
5A
575
23
FOULA
030140
60.12
–2.07
5A
1226
48
FOYERS
030570
57.27
–4.48
5A
932
37
FYLINGDALES
032810
54.37
–0.67
5A
767
30
GLASGOW AIRPORT
031400
55.87
–4.43
5A
1170
46
GLEN OGLE
031480
56.42
–4.32
6A
1675
66
GLENANNE
039230
54.23
–6.50
5A
1026
40
GRAVESEND-BROADNESS
037840
51.47
0.30
4A
643
25
GREAT DUN FELL
032270
54.68
–2.45
7
1249
49
GREENOCK MRCC
031380
55.97
–4.80
5A
1659
65
GWENNAP HEAD
038060
50.03
–5.67
4A
1091
43
HAWARDEN
033210
53.17
–2.98
5A
703
28
HEMSBY
034960
52.68
1.68
5A
589
23
HERSTMONCEUX
038820
50.90
0.32
4A
802
32
HERSTMONCEUX
038840
50.87
0.33
5A
802
32
HIGH WYCOMBE HQSTC
036600
51.68
–0.80
5A
660
26
HILLSBOROUGH
039200
54.48
–6.10
5A
1021
40
HOLBEACH
034690
52.87
0.15
5A
592
23
HONINGTON
035860
52.33
0.77
5A
608
24
HYSKEIR (LGT-H)
030240
56.97
–6.68
5A
1515
60
INVERBERVIE NO.2
030880
56.85
–2.27
5A
810
32
INVERGORDON HARBOUR
030580
57.68
–4.17
5A
711
28
ISLE OF PORTLAND
038570
50.52
–2.45
4A
912
36
KENLEY AIRFIELD
037810
51.30
–0.08
4A
688
27
KESWICK
032120
54.62
–3.17
5A
1364
54
KINLOSS
030660
57.65
–3.57
5A
629
25
KIRKWALL AIRPORT
030170
58.95
–2.90
5A
1017
40
LAKENHEATH RAF
035830
52.42
0.57
4A
607
24
LAKENHEATH RAF
035833
52.40
0.57
5A
607
24
LANGDON BAY
037960
51.13
1.35
5A
696
27
LARKHILL
037430
51.20
–1.80
5A
768
30
LARNE
039280
54.85
–5.80
5A
1172
46
LECONFIELD
033820
53.87
–0.43
5A
681
27
LEEDS BRADFORD
033463
53.87
–1.65
5A
769
30
LEEDS WEATHER CTR
033470
53.80
–1.55
4A
734
29
LEEMING
032570
54.30
–1.53
5A
626
25
LERWICK
030050
60.13
–1.18
6A
1220
48
LEUCHARS
031710
56.40
–2.87
5A
666
26
LINTON-ON-OUSE
032660
54.05
–1.25
5A
658
26
LISCOMBE
037100
51.08
–3.60
5A
1457
57
LITTLE RISSINGTON
036470
51.87
–1.68
5A
714
28
LIVERPOOL
033233
53.33
–2.85
4A
774
30
LOCH GLASCARNOCH
030310
57.72
–4.88
6A
1543
61
LOFTUS SAMOS
032750
54.57
–0.87
5A
696
27
LONDON WEA CENTER
037780
51.52
–0.12
4A
586
23
LONDON WEATHER CENT
037790
51.52
–0.10
4A
586
23
LONDON/GATWICK ARPT
037760
51.15
–0.18
4A
762
30
LONDON/HEATHROW AIR
037720
51.48
–0.45
4A
602
24
LOSSIEMOUTH
030680
57.72
–3.32
5A
691
27
LOUGH FEA
039110
54.72
–6.82
5A
1137
45
LUNDY ISL (LGT-H)
037020
51.17
–4.65
4A
947
37
LUTON
036733
51.87
–0.37
5A
693
27
LYNEHAM
037400
51.50
–1.98
5A
716
28
MACHRIHANISH
031110
55.43
–5.70
5A
1343
53
MADLEY
035210
52.03
–2.85
5A
806
32
MANCHESTER AIRPORT
033340
53.35
–2.28
5A
832
33
MANSTON
037970
51.35
1.37
4A
576
23
MARHAM
034820
52.65
0.57
5A
623
25

458 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 461

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
Precipitation
Country/LOCATION WMO# Lat Long CZ mm in.
MIDDLE WALLOP
037490
51.15
–1.57
4A
749
29
MILDENHALL RAF
035773
52.37
0.48
4A
586
23
MILFORD HAVEN
036040
51.70
–5.05
4A
861
34
MUCKLE FLUGGA
030010
60.85
–0.88
5A
1210
48
MUCKLE HOLM
030070
60.58
–1.27
5A
1076
42
MUMBLES
036090
51.57
–3.98
4A
1198
47
NEWCASTLE
032433
55.03
–1.68
5A
668
26
NEWCASTLE WEATHER C
032460
54.98
–1.60
5A
666
26
NEWHAVEN (LGT-H)
038800
50.78
0.05
4A
841
33
NORTH RONA
030110
59.12
–5.82
5A
1398
55
NORTHOLT
036720
51.55
–0.42
4A
602
24
NORWICH WEA CNTRE
034920
52.63
1.32
4A
648
26
NOTTINGHAM/WATNALL
033540
53.00
–1.25
5A
715
28
OBAN
031140
56.42
–5.47
5A
2131
84
ODIHAM
037610
51.23
–0.95
4A
799
31
ORSAY (LGT-H)
031020
55.67
–6.50
5A
1266
50
PEMBREY SANDS
036050
51.72
–4.37
4A
1215
48
PENDENNIS POINT
038100
50.15
–5.07
4A
1117
44
PENDINE (AUT)
036080
51.75
–4.52
4A
1212
48
PERSHORE
035290
52.15
–2.03
5A
633
25
PETERHEAD HARBOUR
030920
57.50
–1.77
5A
724
29
PLYMOUTH MOUNT BATT
038270
50.35
–4.12
4A
1004
40
PORTGLENONE
039150
54.87
–6.45
5A
1098
43
PORTLAND HELIPORT
038580
50.57
–2.45
4A
912
36
PRESTWICK RNAS
031360
55.52
–4.58
5A
949
37
PRESTWICK(CIV/NAVY)
031350
55.50
–4.58
5A
949
37
REDESDALE CAMP
032300
55.28
–2.28
5A
957
38
RHYL
033130
53.25
–3.50
4A
1007
40
SCILLY: ST MARYS AI
038030
49.92
–6.30
4A
909
36
SELLA NESS
030060
60.45
–1.27
5A
1106
44
SENNYBRIDGE
035070
52.07
–3.62
5A
1495
59
SHAP
032250
54.50
–2.68
5A
1373
54
SHAWBURY
034140
52.80
–2.67
5A
658
26
SHEERNESS
037910
51.45
0.75
4A
599
24
SHOBDON
035200
52.25
–2.88
5A
827
33
SHOEBURYNESS
036930
51.55
0.83
4A
504
20
SHOREHAM AIRPORT
038760
50.83
–0.28
4A
715
28
SKYE/LUSA
030370
57.25
–5.80
5A
2115
83
SOLENT M.R.S.C.
038740
50.80
–1.22
4A
786
31
SOUTHAMPTON WX CNTR
038650
50.90
–1.40
4A
789
31
SOUTHEND
036913
51.57
0.68
4A
558
22
SPADEADAM
032240
55.05
–2.55
5A
1226
48
ST ANGELO
039030
54.40
–7.65
5A
1300
51
ST BEES HEAD NO.2
032100
54.52
–3.60
5A
1136
45
ST. CATHERINES POIN
038660
50.58
–1.30
4A
764
30
ST. MAWGAN
038170
50.43
–5.00
4A
1148
45
STANSTED AIRPORT
036830
51.88
0.23
5A
623
25
STORNOWAY
030260
58.22
–6.32
5A
1188
47
STRATHALLEN AIRFIEL
031440
56.32
–3.73
5A
954
38
SULE SKERRY
030100
59.08
–4.40
5A
1278
50
SUMBURGH (CAPE)
030030
59.88
–1.30
5A
1124
44
TAIN RANGE
030620
57.82
–3.97
5A
770
30
THAMES TOWER (AUT)
036950
51.67
1.10
4A
557
22
THORNEY ISLAND
038720
50.82
–0.92
4A
793
31
TIREE
031000
56.50
–6.88
5A
1182
47
TRAWSGOED
035030
52.35
–3.95
5A
1174
46
TULLOCH BRIDGE
030470
56.87
–4.70
5A
1553
61
TYNEMOUTH
032620
55.02
–1.42
5A
646
25
UPPER HEYFORD RAF
036553
51.93
–1.25
5A
645
25
VALLEY
033020
53.25
–4.53
4A
839
33
WADDINGTON
033770
53.17
–0.52
5A
603
24
WAINFLEET
033920
53.08
0.27
5A
584
23
WALNEY ISLAND
032140
54.12
–3.25
5A
1238
49
WALTON-ON-NAZE
036960
51.85
1.28
4A
546
21
WARCOP RANGE
032260
54.57
–2.42
5A
1249
49
WATTISHAM
035900
52.12
0.97
5A
582
23
WEST FREUGH
031320
54.85
–4.95
5A
977
38
WEYBOURNE
034880
52.95
1.13
4A
667
26
WICK
030750
58.45
–3.08
5A
787
31
WITTERING
034620
52.62
–0.47
5A
580
23
WYTON(RAF)
035660
52.35
–0.12
5A
537
21
YEOVILTON
038530
51.00
–2.63
4A
727
29
MIDDLE WALLOP
037490
51.15
–1.57
4A
749
29
MILDENHALL RAF
035773
52.37
0.48
4A
586
23
MILFORD HAVEN
036040
51.70
–5.05
4A
861
34
MUCKLE FLUGGA
030010
60.85
–0.88
5A
1210
48
MUCKLE HOLM
030070
60.58
–1.27
5A
1076
42
MUMBLES
036090
51.57
–3.98
4A
1198
47
NEWCASTLE
032433
55.03
–1.68
5A
668
26
NEWCASTLE WEATHER C
032460
54.98
–1.60
5A
666
26
NEWHAVEN (LGT-H)
038800
50.78
0.05
4A
841
33
NORTH RONA
030110
59.12
–5.82
5A
1398
55
NORTHOLT
036720
51.55
–0.42
4A
602
24
NORWICH WEA CNTRE
034920
52.63
1.32
4A
648
26
NOTTINGHAM/WATNALL
033540
53.00
–1.25
5A
715
28
OBAN
031140
56.42
–5.47
5A
2131
84
ODIHAM
037610
51.23
–0.95
4A
799
31
ORSAY (LGT-H)
031020
55.67
–6.50
5A
1266
50
PEMBREY SANDS
036050
51.72
–4.37
4A
1215
48
PENDENNIS POINT
038100
50.15
–5.07
4A
1117
44
PENDINE (AUT)
036080
51.75
–4.52
4A
1212
48
PERSHORE
035290
52.15
–2.03
5A
633
25
PETERHEAD HARBOUR
030920
57.50
–1.77
5A
724
29
PLYMOUTH MOUNT BATT
038270
50.35
–4.12
4A
1004
40
PORTGLENONE
039150
54.87
–6.45
5A
1098
43
PORTLAND HELIPORT
038580
50.57
–2.45
4A
912
36
PRESTWICK RNAS
031360
55.52
–4.58
5A
949
37
PRESTWICK(CIV/NAVY)
031350
55.50
–4.58
5A
949
37
REDESDALE CAMP
032300
55.28
–2.28
5A
957
38
RHYL
033130
53.25
–3.50
4A
1007
40
SCILLY: ST MARYS AI
038030
49.92
–6.30
4A
909
36
SELLA NESS
030060
60.45
–1.27
5A
1106
44
SENNYBRIDGE
035070
52.07
–3.62
5A
1495
59
SHAP
032250
54.50
–2.68
5A
1373
54
SHAWBURY
034140
52.80
–2.67
5A
658
26
SHEERNESS
037910
51.45
0.75
4A
599
24
SHOBDON
035200
52.25
–2.88
5A
827
33
SHOEBURYNESS
036930
51.55
0.83
4A
504
20
SHOREHAM AIRPORT
038760
50.83
–0.28
4A
715
28
SKYE/LUSA
030370
57.25
–5.80
5A
2115
83
SOLENT M.R.S.C.
038740
50.80
–1.22
4A
786
31
SOUTHAMPTON WX CNTR
038650
50.90
–1.40
4A
789
31
SOUTHEND
036913
51.57
0.68
4A
558
22
SPADEADAM
032240
55.05
–2.55
5A
1226
48
ST ANGELO
039030
54.40
–7.65
5A
1300
51
ST BEES HEAD NO.2
032100
54.52
–3.60
5A
1136
45
ST. CATHERINES POIN
038660
50.58
–1.30
4A
764
30
ST. MAWGAN
038170
50.43
–5.00
4A
1148
45
STANSTED AIRPORT
036830
51.88
0.23
5A
623
25
STORNOWAY
030260
58.22
–6.32
5A
1188
47
STRATHALLEN AIRFIEL
031440
56.32
–3.73
5A
954
38
SULE SKERRY
030100
59.08
–4.40
5A
1278
50
SUMBURGH (CAPE)
030030
59.88
–1.30
5A
1124
44
TAIN RANGE
030620
57.82
–3.97
5A
770
30
THAMES TOWER (AUT)
036950
51.67
1.10
4A
557
22
Uruguay (URY)
ARTIGAS
863300
–30.38
–56.50
3A
1486
59
CARRASCO
865800
–34.83
–56.00
3A
950
37
COLONIA
865600
–34.45
–57.83
3A
1108
44
PASO DE LOS TOROS
864600
–32.80
–56.52
3A
1315
52
PRADO
865850
–34.85
–56.20
3A
1069
42
RIVERA
863500
–30.88
–55.53
3A
1500
59
ROCHA
865650
–34.48
–54.30
3A
1051
41
SALTO
863600
–31.38
–57.95
3A
1264
50
TREINTA Y TRES
865000
–33.22
–54.38
3A
1335
53
MIDDLE WALLOP
037490
51.15
–1.57
4A
749
29
MILDENHALL RAF
035773
52.37
0.48
4A
586
23
MILFORD HAVEN
036040
51.70
–5.05
4A
861
34
MUCKLE FLUGGA
030010
60.85
–0.88
5A
1210
48
MUCKLE HOLM
030070
60.58
–1.27
5A
1076
42
MUMBLES
036090
51.57
–3.98
4A
1198
47
NEWCASTLE
032433
55.03
–1.68
5A
668
26
NEWCASTLE WEATHER C
032460
54.98
–1.60
5A
666
26
NEWHAVEN (LGT-H)
038800
50.78
0.05
4A
841
33
NORTH RONA
030110
59.12
–5.82
5A
1398
55
NORTHOLT
036720
51.55
–0.42
4A
602
24
NORWICH WEA CNTRE
034920
52.63
1.32
4A
648
26
NOTTINGHAM/WATNALL
033540
53.00
–1.25
5A
715
28
OBAN
031140
56.42
–5.47
5A
2131
84
ODIHAM
037610
51.23
–0.95
4A
799
31
ORSAY (LGT-H)
031020
55.67
–6.50
5A
1266
50
PEMBREY SANDS
036050
51.72
–4.37
4A
1215
48
PENDENNIS POINT
038100
50.15
–5.07
4A
1117
44
PENDINE (AUT)
036080
51.75
–4.52
4A
1212
48
PERSHORE
035290
52.15
–2.03
5A
633
25
PETERHEAD HARBOUR
030920
57.50
–1.77
5A
724
29
PLYMOUTH MOUNT BATT
038270
50.35
–4.12
4A
1004
40
PORTGLENONE
039150
54.87
–6.45
5A
1098
43
PORTLAND HELIPORT
038580
50.57
–2.45
4A
912
36
PRESTWICK RNAS
031360
55.52
–4.58
5A
949
37
PRESTWICK(CIV/NAVY)
031350
55.50
–4.58
5A
949
37
REDESDALE CAMP
032300
55.28
–2.28
5A
957
38
RHYL
033130
53.25
–3.50
4A
1007
40
SCILLY: ST MARYS AI
038030
49.92
–6.30
4A
909
36
SELLA NESS
030060
60.45
–1.27
5A
1106
44
SENNYBRIDGE
035070
52.07
–3.62
5A
1495
59
SHAP
032250
54.50
–2.68
5A
1373
54
SHAWBURY
034140
52.80
–2.67
5A
658
26
SHEERNESS
037910
51.45
0.75
4A
599
24
SHOBDON
035200
52.25
–2.88
5A
827
33
SHOEBURYNESS
036930
51.55
0.83
4A
504
20
SHOREHAM AIRPORT
038760
50.83
–0.28
4A
715
28
SKYE/LUSA
030370
57.25
–5.80
5A
2115
83
SOLENT M.R.S.C.
038740
50.80
–1.22
4A
786
31
SOUTHAMPTON WX CNTR
038650
50.90
–1.40
4A
789
31
SOUTHEND
036913
51.57
0.68
4A
558
22
SPADEADAM
032240
55.05
–2.55
5A
1226
48
ST ANGELO
039030
54.40
–7.65
5A
1300
51
ST BEES HEAD NO.2
032100
54.52
–3.60
5A
1136
45
ST. CATHERINES POIN
038660
50.58
–1.30
4A
764
30
ST. MAWGAN
038170
50.43
–5.00
4A
1148
45
STANSTED AIRPORT
036830
51.88
0.23
5A
623
25
STORNOWAY
030260
58.22
–6.32
5A
1188
47
STRATHALLEN AIRFIEL
031440
56.32
–3.73
5A
954
38
SULE SKERRY
030100
59.08
–4.40
5A
1278
50
SUMBURGH (CAPE)
030030
59.88
–1.30
5A
1124
44
TAIN RANGE
030620
57.82
–3.97
5A
770
30
THAMES TOWER (AUT)
036950
51.67
1.10
4A
557
22
Uzbekistan (UZB)
AK-BAJTAL
381780
43.15
64.33
5B
117
5
BUHARA
386830
39.72
64.62
4B
146
6
BUZAUBAJ
384030
41.75
62.47
4B
88
3
CHIMBAJ
382620
42.95
59.82
5B
120
5
DARGANATA
385450
40.47
62.28
4B
140
6
DZIZAK
385790
40.12
67.83
4B
385
15
FERGANA
386180
40.37
71.75
4B
175
7
KARSHI
388120
38.80
65.72
3B
253
10
KUNGRAD
381490
43.08
58.93
5B
118
5
NAMANGAN
386110
40.98
71.58
4B
189
7
NUKUS
382640
42.45
59.62
5B
106
4
NURATA
385650
40.55
65.68
4B
238
9
PSKEM
384620
41.90
70.37
5C
854
34
SAMARKAND
386960
39.57
66.95
4B
340
13
SYR-DARJA
385830
40.82
68.68
4A
312
12
TAMDY
384130
41.73
64.62
4B
127
5
TASHKENT
384570
41.27
69.27
4A
435
17
TERMEZ
389270
37.23
67.27
3B
148
6
URGENCH
383960
41.57
60.57
4B
92
4
MIDDLE WALLOP
037490
51.15
–1.57
4A
749
29
MILDENHALL RAF
035773
52.37
0.48
4A
586
23
MILFORD HAVEN
036040
51.70
–5.05
4A
861
34
MUCKLE FLUGGA
030010
60.85
–0.88
5A
1210
48
MUCKLE HOLM
030070
60.58
–1.27
5A
1076
42
MUMBLES
036090
51.57
–3.98
4A
1198
47
NEWCASTLE
032433
55.03
–1.68
5A
668
26
NEWCASTLE WEATHER C
032460
54.98
–1.60
5A
666
26
NEWHAVEN (LGT-H)
038800
50.78
0.05
4A
841
33
NORTH RONA
030110
59.12
–5.82
5A
1398
55
NORTHOLT
036720
51.55
–0.42
4A
602
24
NORWICH WEA CNTRE
034920
52.63
1.32
4A
648
26
NOTTINGHAM/WATNALL
033540
53.00
–1.25
5A
715
28
OBAN
031140
56.42
–5.47
5A
2131
84
ODIHAM
037610
51.23
–0.95
4A
799
31
ORSAY (LGT-H)
031020
55.67
–6.50
5A
1266
50
PEMBREY SANDS
036050
51.72
–4.37
4A
1215
48
PENDENNIS POINT
038100
50.15
–5.07
4A
1117
44
PENDINE (AUT)
036080
51.75
–4.52
4A
1212
48
PERSHORE
035290
52.15
–2.03
5A
633
25
PETERHEAD HARBOUR
030920
57.50
–1.77
5A
724
29
PLYMOUTH MOUNT BATT
038270
50.35
–4.12
4A
1004
40
PORTGLENONE
039150
54.87
–6.45
5A
1098
43
PORTLAND HELIPORT
038580
50.57
–2.45
4A
912
36
PRESTWICK RNAS
031360
55.52
–4.58
5A
949
37
PRESTWICK(CIV/NAVY)
031350
55.50
–4.58
5A
949
37
REDESDALE CAMP
032300
55.28
–2.28
5A
957
38
RHYL
033130
53.25
–3.50
4A
1007
40
SCILLY: ST MARYS AI
038030
49.92
–6.30
4A
909
36
SELLA NESS
030060
60.45
–1.27
5A
1106
44
SENNYBRIDGE
035070
52.07
–3.62
5A
1495
59
SHAP
032250
54.50
–2.68
5A
1373
54
SHAWBURY
034140
52.80
–2.67
5A
658
26
SHEERNESS
037910
51.45
0.75
4A
599
24
SHOBDON
035200
52.25
–2.88
5A
827
33
SHOEBURYNESS
036930
51.55
0.83
4A
504
20
SHOREHAM AIRPORT
038760
50.83
–0.28
4A
715
28
SKYE/LUSA
030370
57.25
–5.80
5A
2115
83
SOLENT M.R.S.C.
038740
50.80
–1.22
4A
786
31
SOUTHAMPTON WX CNTR
038650
50.90
–1.40
4A
789
31
SOUTHEND
036913
51.57
0.68
4A
558
22
SPADEADAM
032240
55.05
–2.55
5A
1226
48
ST ANGELO
039030
54.40
–7.65
5A
1300
51
ST BEES HEAD NO.2
032100
54.52
–3.60
5A
1136
45
ST. CATHERINES POIN
038660
50.58
–1.30
4A
764
30
ST. MAWGAN
038170
50.43
–5.00
4A
1148
45
STANSTED AIRPORT
036830
51.88
0.23
5A
623
25
STORNOWAY
030260
58.22
–6.32
5A
1188
47
STRATHALLEN AIRFIEL
031440
56.32
–3.73
5A
954
38
SULE SKERRY
030100
59.08
–4.40
5A
1278
50
SUMBURGH (CAPE)
030030
59.88
–1.30
5A
1124
44
TAIN RANGE
030620
57.82
–3.97
5A
770
30
THAMES TOWER (AUT)
036950
51.67
1.10
4A
557
22
Vanuatu (VUT)
ANEITYUM
915680
–20.23
169.77
1A
1416
56
BAUERFIELD (EFATE)
915570
–17.70
168.30
1A
2249
89
PEKOA AIRPORT (SANTO)
915540
–15.52
167.22
1A
2823
111

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 459

PDF Page 462

Open page note

Table Annex1-3 ASHRAE Standard 169-2013, Table A-6: International Stations and Climate Zones (Continued)

460 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 463

Open page note

SECTION ANNEX1-1 ASHRAE STANDARD 169-2013, SECTION A3: CLIMATE ZONE DEFINITIONS

A3. CLIMATE ZONE DEFINITIONS

To determine the climate zones for locations not listed in this standard, use the following information to determine climate zone numbers and letters.

Determine the thermal climate zone, 0–8, from Table A-3, using the heating and cooling degree-days for the location.

Determine the moisture zone (Marine, Dry or Humid):

a. If monthly average temperature and precipitation data are available, use the Marine, Dry, and Humid

definitions below to determine the moisture zone (C, B, or A). b. If annual average temperature information (including degree-days) and annual precipitation (i.e. annual

mean) are available, use the following to determine the moisture zone:

  1. If thermal climate zone is 3 and CDD50°F  4500 (CDD10°C  2500), climate zone is Marine (3C).
  2. If thermal climate zone is 4 and CDD50°F  2700 (CDD10°C  1500), climate zone is Marine (4C).
  3. If thermal climate zone is 5 and CDD50°F  1800 (CDD10°C  1000), climate zone is Marine (5C).

Use the the third criteria below for determining the Dry/Humid threshold if not Marine (C).

c. If only degree-day information is available, use the following to determine the moisture zone:

  1. If thermal climate zone is 3 and CDD50°F  4500 (CDD10°C  2500), climate zone is Marine (3C).
  2. If thermal climate zone is 4 and CDD50°F  2700 (CDD10°C  1500), climate zone is Marine (4C).
  3. If thermal climate zone is 5 and CDD50°F  1800 (CDD10°C  1000), climate zone is Marine (5C) .

It is not possible to assign Dry/Humid splits in this case.

Marine (C) Zone Definition —Locations meeting all four of the following criteria:

a. Mean temperature of coldest month between 27°F (–3°C) and 65°F (18°C) b. Warmest month mean < 72°F (22°C) c. At least four months with mean temperatures over 50°F (10°C) d. Dry season in summer. The month with the heaviest precipitation in the cold season has at least three

times as much precipitation as the month with the least precipitation in the rest of the year. The cold season is October through March in the Northern Hemisphere and April through September in the Southern Hemisphere.

Dry (B) Definition —Locations meeting the following criteria:

a. Not Marine (C) b. If 70% or more of the precipitation, P, occurs during the high sun period, then the dry/humid threshold is

P < 0.44 × ( T - 7) (I-P) P < 20.0 × ( T + 14) (SI) c. If between 30% and 70% of the precipitation, P, occurs during the high sun period, then the dry/humid

threshold is

P < 0.44 × ( T - 19.5) (I-P) P < 20.0 × ( T + 7) (SI) d. If 30% or less of the precipitation, P, occurs during the high sun period, then the dry/humid threshold is

P < 0.44 × ( T - 32) (I-P) P < 20 × T (SI) where

P = annual precipitation, in. (mm)

T = annual mean temperature, °F (°C)

Summer or high sun period = April through September in the Northern Hemisphere and October through March in the Southern Hemisphere

Winter or cold season = October through March in the Northern Hemisphere and April through September in the Southern Hemisphere

Humid (A) Definition —Locations that are not Marine (C) and not Dry (B)

ANSI/ASHRAE/IES Standard 90.1-2022 (I-P) 461

PDF Page 464

Open page note

Table Annex1-4 ASHRAE Standard 169-2013, Table A-3: Thermal Climate Zone Definitions

Thermal ZoneNameI-P UnitsSI Units
0Extremely hot10,800 < CDD50°F6000 < CDD10°C
1Very hot9000 < CDD50°F 10,8005000 < CDD10°C 6000
2Hot6300 < CDD50°F 90003500 < CDD10°C 5000
3WarmCDD50°F 6300 and
HDD65°F 3600
CDD10°C < 3500 and
HDD18°C 2000
4MixedCDD50°F 6300 and
3600 < HDD65°F 5400
CDD10°C < 3500 and
2000 < HDD18°C 3000
5CoolCDD50°F 6300 and
5400 < HDD65°F 7200
CDD10°C 3500 and
3000 < HDD18°C 4000
6Cold7200 < HDD65°F 90004000 < HDD18°C 5000
7Very cold9000 < HDD65°F 126005000 < HDD18°C 7000
8Subarctic/arctic12600 < HDD65°F7000 < HDD18°C

Figure Annex1-2 ASHRAE Standard 169-2013, Figure A-1: Thermal climate zones as a function of heating and cooling degree-days.

462 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 465

Open page note

Figure Annex1-3 ASHRAE Standard 169-2013, Figure C-2: World climate zones map.

PDF Page 466

Open page note

SECTION ANNEX1-2 ASHRAE STANDARD 169-2013, SECTION 4:CLIMATIC DESIGN DATA AND CLIMATE ZONES

4. CLIMATIC DESIGN DATA AND CLIMATE ZONES

Normative Appendix A comprises data for 5564 U.S., Canadian, and international locations. This information generally represents annual and monthly percentiles of occurrence of temperature, various measures of humidity, and wind speed for use in the design of building energy and ventilation systems. These data also include HDD and CDD annual average values and the number of hours between 8 a.m. and 4 p.m. when the dry-bulb temperature is between 55°F and 69°F (13°C and 21°C). A sample of this climatic data is provided in Table A-1 for Atlanta, Georgia, USA. Design conditions for all 5564 locations are located online at the following location:

www.ashrae.org/169_2013data

Table A-4 in Normative Appendix A lists climate zones and other key climatic data for U.S., Canadian, and international locations and includes links to the design conditions.

464 ANSI/ASHRAE/IES Standard 90.1-2022 (I-P)

PDF Page 467

Open page note

POLICY STATEMENT DEFINING ASHRAE’S CONCERN FOR THE ENVIRONMENTAL IMPACT OF ITS ACTIVITIES

ASHRAE is concerned with the impact of its members’ activities on both the indoor and outdoor environment. ASHRAE’s members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of the systems and components in their responsibility while maximizing the beneficial effects these systems provide, consistent with accepted Standards and the practical state of the art.

ASHRAE’s short-range goal is to ensure that the systems and components within its scope do not impact the indoor and outdoor environment to a greater extent than specified by the Standards and Guidelines as established by itself and other responsible bodies.

As an ongoing goal, ASHRAE will, through its Standards Committee and extensive Technical Committee structure, continue to generate up-to-date Standards and Guidelines where appropriate and adopt, recommend, and promote those new and revised Standards developed by other responsible organizations.

Through its Handbook, appropriate chapters will contain up-to-date Standards and design considerations as the material is systematically revised.

ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and will seek out and disseminate information from other responsible organizations that is pertinent, as guides to updating Standards and Guidelines.

The effects of the design and selection of equipment and systems will be considered within the scope of the system’s intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.

ASHRAE’s primary concern for environmental impact will be at the site where equipment within ASHRAE’s scope operates. However, energy source selection and the possible environmental impact due to the energy source and energy transportation will be considered where possible. Recommendations concerning energy source selection should be made by its members.

PDF Page 468

Open page note

ASHRAE · 180 Technology Parkway · Peachtree Corners, GA 30092 · www.ashrae.org

About ASHRAE

Founded in 1894, ASHRAE is a global professional society committed to serve humanity by advancing the arts and sciences of heating, ventilation, air conditioning, refrigeration, and their allied fields.

As an industry leader in research, standards writing, publishing, certification, and continuing education, ASHRAE and its members are dedicated to promoting a healthy and sustainable built environment for all, through strategic partnerships with organizations in the HVAC&R community and across related industries.

To stay current with this and other ASHRAE Standards and Guidelines, visit www.ashrae.org/standards, and connect on LinkedIn, Facebook, Twitter, and YouTube.

Visit the ASHRAE Bookstore

ASHRAE offers its Standards and Guidelines in print, as immediately downloadable PDFs, and via ASHRAE Digital Collections, which provides online access with automatic updates as well as historical versions of publications. Selected Standards and Guidelines are also offered in redline versions that indicate the changes made between the active Standard or Guideline and its previous edition. For more information, visit the Standards and Guidelines section of the ASHRAE Bookstore at www.ashrae.org/bookstore.

IMPORTANT NOTICES ABOUT THIS STANDARD

To ensure that you have all of the approved addenda, errata, and interpretations for this Standard, visit www.ashrae.org/standards to download them free of charge.

Addenda, errata, and interpretations for ASHRAE Standards and Guidelines are no longer distributed with copies of the Standards and Guidelines. ASHRAE provides these addenda, errata, and interpretations only in electronic form to promote more sustainable use of resources.

Product code: 86327 12/22